GARNESS ENGINEERING GROUP, Ltd
-- v-. -.- *rw ENGINEERING,* SALES CONSULTING
January 2, 2020
Municipality of Anchorage
Development Service Department
On -Site Water & Wastewater Program
4700 Elmore Road
Anchorage, AK 99507
Ref: Soils Investigation Report and Septic Reserve Area for the Proposed Brandt
Subdivision; Lot 1 and 2 in Anchorage, Alaska (A SUBDIVISION OF T12N R3W SECTION
22 LOT 43A)
To whom it may concern:
The reference property is located off Gamache Drive in Anchorage, Alaska. Based upon the
preliminary plat drawing provided to us by Edge Survey and Design, LLC, T12N, R3W, Section
22, Lot 43A is to be subdivide into two lots, Brandt Subdivision, Lot 1 and 2. It should be noted
that access to the proposed Brandt; Lot 2 will be accessed off of Totem Road, Anchorage, AK.
The lot has an existing house located on it with a MOA approved well and septic system. We
have excavated and logged four (4) testholes on the proposed Brandt; Lot 2. The testhole data
has been used to establish a septic reserve area for the proposed subdivision. The proposed lot
will be served by a private well and septic system.
PROPOSED SEPTIC RESERVE AREAS
Per MOA wastewater ordinance AMC 15.65.405 and 15.65.410, we are required to provide a
site map showing a septic reserve area that meets the requirement set forth in Table 7 of
15.65.410 (see below):
Table 7. Reserved Area Requirements
Percolation Rate
(minutes/inch)
Reserved Area
(square feet)
'1-5
10,000
6 -12
12,000
13-24
14,000
25.60
16,000
Four (4) testhole were excated on proposed Brandt; Lot 2. As can be seen on the attached soils
logs, Testhole #1 and Testhole #2 could not be perked due to water weeping in through the
organics. However, the soils appeared visually permeable. A percolation test was performed on
3701 East Tudor Road, Suite 101 * Anchorage, Alaska 99507-1259
Phone: (907) 337-6179 * Fax: (907) 338-3246 * Website: www.garnessengineering.com
Page 2 of 2
Testholes #3 and #4 and both perked at a rate between 1-5 minutes/inch. Therefore, per table 7
(listed above) a 10,000 ft2 septic reserve area is required. Attached is a site map which shows
the septic reserve area for the proposed lot of 10,000+ ft2 (80 x 130 = 10,400 ft2). Per the
recommendation of the field tech, a 0.8 application rating should be used for the design (visual
determination). Therefore, we show a 12,000 ft2 reserve area to be conservative. There appears
to be sufficient area for a structure, driveway and onsite wastewater disposal system and private
well for the proposed lot.
TOPOGRAPHY:
As can be seen on the attached 100 scale, the topography information has been overlain. Per
the GEG site visit and the attached topography drawing, there are slopes greater than 25%
however, they are less than 46%. In short, given the fast percolation rate (5 min/inch) and low
groundwater table (testholes dry), it is reasonable to believe that the drainfield would meet the
MOA steep slopes provision. Due to his fact, a waiver will not be required, and topography
appears to meet MOA requirements.
WATER AVAILABILITY:
Well flow and nitrate information were obtained from MOA records on the adjacent lots
(attached). They are as follows:
® T1 2N RM Sections 22 Lot 43A — 18 gallons/minute with a total depth of 140 feet
® David Ring; Lot 1 — 3.2 gallons/minute with a total depth of 125 feet and nitrates of 0.141
mg/L
® David Ring; Lot 2B — 50 gallons/minute with a total depth of 137
® David Ring; Lot 2A — 30 gallons/minute with a total depth of 140
® Latta; Lot 4 — Nitrates were non-detectable 6/2/2015 — North of proposed subdivision
® Greenland; Block 3, Lot 3 — Nitrates at 1.85 mg/L — West of proposed subdivision
Although there are limited nitrate samples in the vicinity of the proposed subdivision, it appears
that elevated nitrates are not a concern. Well production will not be an issue for the proposed
lot.
If you have any questions, please contact us as at 337-6179.
S.
3701 East Tudor Road, Suite 101 * Anchorage, Alaska 99507-1259
Phone: (907) 337-6179 * Fax: (907) 338-3246 * Website: www. garnessengineering.com
. ❑ I
TOPO CONTOUR LINES TESTHOLELOCATIONAREAPPROXIMATE;THEY
WERE NOT SUREYED IN BUT ARE BASED UPON
DAVID RING; LOT 1 ARE 5' AND APPROXIMATE FLAGGING OF THE LOT LINES IN THE FIELD 1
<< R DIUS I
EPTIC
_ AREA I I\
VID RING; LOT 2B \ /
\ \ T.H. T.H.#1 I EKVALL;
$ TRACT B-1
I_1 0
I
SEPTIC
✓ 150 EET RESERVEAREA
/ I\
80 EE --I
I/
E TING LOT
LL O LO TO TH EASTD BRANCH
ECOME "LOT 1 O PROPOSE
OES OT NCRO H ON SUBDIVISION; LOT 2 /
P OP SED L T
T R3W SECTIO 2; LOT 46
WF�0-I/
I
XMALINOI/S;
1"=100'
i
• 4t••'(,
_.-------— ------ ----- —------------- j'
GARNESS ENGINEERING GROUP, Ltd �. �� 49 i•• �.
—_ --� ENGINEERING o SALES �, CONSULTING -� - -- 10 J s
3701 E. TUDOR ROAD, SUITE 101 -ANCHORAGE, AK 99507 -PHONE (907) 337-6179 -FAX (907) 338-3246-WEBSITE:w .gamessengineedng.com 0••••••• •J••.••••..•.•••...........0
PREPARED FOR: PHONE NUMBER: PAGE NUMBER: ,0 ••e A. Gamess I -Li ,
LARRY BRANDY 907-351-7957 1OF 2 �� J,'� • C - 53 :�AV
Aw
PROJECT/LEGAL DESCRIPTION: DRAWN BY: #♦�••. +� "�j•.` ���
Tl 2N R3W SECTION 22 LOT 43A D.J.G. 1�Fp••''••• .... • ry��"�, �.
TYPE OF WORK: DATE: LICENS 44FFe � OE
SEPTIC SYSTEM DESIGN UPGRADE 1/2/2019 #AECC884
GA.RNESS, ENGINEERING GROUP, Ltd
-.---- --- -
aru �. i�wrtnvHu, auiie iui--hu--fu<—f-FHuNt(uuf)33/-El/Y-FA (uu/)339-3146-VVEBSITE�gameaaen9neeNng.mm
SOIL LOG - PERCOLATION TEST
LEGAL DESCRIPTION: Tl 2N R3W SECTION 22 LOT 43A
PERFORMED FOR: LARRY BRANDT
DEPTH
(feet)
ORG
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
914
DATE: 12/13/2019
•
II�III�'I i//iI
%/% 11NN •
}1}2YY`Y`II
DEPTH TO
GROUNDWATER
DATE
DRY
12/13/2019
DRY
12/30/2019
MORA
DEPTH TO
GROUNDWATER
DATE
DRY
12/13/2019
DRY
12/30/2019
SITE PLAN
11 a11181
DATE READING CLOCK I NET TIME WATER LEVEL NET DROP
TIME (MINUTES) READING (INCHES)
A PERCOLATION TEST COULD NOT BE PERFORMED DUE TO RUNOFF AND/OR WEEPING
FROM THE ORGANIC LAYER INTO THE PERCOLATION BENCHES - SOILS APPEARED
PERMEABLE AND A PERCOLATION TEST COULD BE ATTEMPTED AT A LATER DATE
19
PERCOLATION RATE - (MIN./INCH) PERC. HOLE DIA.
TEST RUN BETWEEN - FT. AND FT.
20 A FOUR HOUR PRESOAK WAS PERFORMED: ❑ YES E NO
SOILS LOGGED BY: DAVID GARNESS PERCOLATION TEST PERFORMED BY: N/A
COMMENTS: PERCOLATION READINGS ARE WITHIN 1/16 OF INCH.
PERFORMED BY GEG, Ltd. I, JEFFREY A. GARNESS, CERTIFY THAT THIS WAS PERFOR ED IN ACCORDANCE
WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE: ?� 3/
6 (INCHES)
GARNESS ENGINEERING GROUP, Ltd
- ENGINEERING GALES > CONSULTING
3701 E. TUDOR ROAD, SUITE 101 'ANCHORAGE, AK 99507 -PHONE (907) 3376179 -FAX (907) 338-3246' WEBSITE: wvrw.gamessengineenng.com
SOIL LOG - PERCOLATION TEST
LEGAL DESCRIPTION: T12N R3W SECTION 22 LOT 43A
PERFORMED FOR:
DEPTH
(feet) flE
1 ORG
LARRY BRANDT
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
DATE: 12/13/2019
TEST HOLE #2
SOIL CLASSIFICATIONS
•-e
II�I'I�II i//iICL
GC1111N
OIL
..
•YY,7ZY �
MH
�'
SPCH
ltY!`YY1iI ��yy���
Y��
•
ML
DEPTH TO DATE
GROUNDWATER
DRY 12/13/2019
I SITE PLAN
! Q
�\ `VV
�O
G�
�P
4,�CiP QN
SCALE:
1°=100
DATE READING CLOCK NET TIME WATER LEVEL NET DROP
TIME (MINUTES) READING (INCHES)
A PERCOLATION TEST COULD NOT BE PERFORMED DUE TO RUNOFF AND/OR WEEPING
FROM THE ORGANIC LAYER INTO THE PERCOLATION BENCHES - SOILS APPEARED
PERMEABLE AND A PERCOLATION TEST COULD BE ATTEMPTED AT A LATER DATE
19. 111111111
PERCOLATION RATE (MIN./INCH) PERC. HOLE DIA. 6 (INCHES)
B.O.H. TEST RUN BETWEEN FT. AND - FT.
20 A FOUR HOUR PRESOAK WAS PERFORMED:
❑ YES NO
SOILS LOGGED BY: DAVID GARNESS PERCOLATION TEST PERFORMED BY: N/A
COMMENTS: PERCOLATION READINGS ARE WITHIN 1/16 OF INCH; TESTHOLE WAS BACKFILLED AND NO LONGER VIABLE FOR GROUNDWATER MONITORING
PERFORMED BY GEG, Ltd. I, JEFFREY A. GARNESS, CERTIFY THAT THIS WAS PERFORMED IN ACCORDANCE
WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE:
e
rAV/I AF �7i1 \fit
GARNESS ENGINEERING GROUP, Ltd
—1 t. I U-11 HVAU. DUI It lUl ' ANUHUHAUt, A 95507' PHONE (50/) 337-6779' FAX(9W) 338-3246' WEBSITE v garne enginee6ng,c m
SOIL LOG - PERCOLATION TEST
LEGAL DESCRIPTION: T12N R3W SECTION 22 LOT 43A
PERFORMED FOR:
DEPTJf(feet)��1 ORG
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
LARRY BRANDT
TEST HOLE #3
DATE: 12/20/2019
SOIL CLASSIFICATIONS
CLOCK
TIME
.•
WATER LEVEL
READING
GW
0.
GP
ML
II�II','IGM i//iICL
-
//. NNN
O
IIIIIIIIIMH
01I
�•' y�
Y``YYYII P�yyp�iCH
3
Yy�OH
-
SC
-
SM TO ML
DEPTH TO DATE
GROUNDWATER
DRY 12/20/2019
DRY 12/30/2019
SITE PLAN
'AD
Pc'
N
SCALE:
1"=100'
DATE READING
CLOCK
TIME
NET TIME
(MINUTES)
WATER LEVEL
READING
NET DROP
(INCHES)
12/20/2019 1
11:50
-
6"
-
2
12:20
30
01I
6"
3
12:20
-
6"
-
4
12:50
30
01I
6"
5
12:50
-
6"
-
6
1:20
30
01I
6"
7
1:20
-
6"
-
6
1:50
30
01I
6"
19 PERCOLATION RATE <5 (MIN./INCH) PERC. HOLE DIA. 6 (INCHES)
TEST RUN BETWEEN 4.5 FT. AND 5.5 FT.
20 A FOUR HOUR PRESOAK WAS PERFORMED:
❑ YES NO
SOILS LOGGED BY: JODY MADS PERCOLATION TEST PERFORMED BY: JODY MAUS
COMMENTS: PERCOLATION READINGS ARE WITHIN 1/16 OF INCH. RECOMMEND SOIL APPLICATION RATE OF 0.8 GPD/FT2
PERFORMED BY GEG, Ltd. I, JEFFREY A. GARNESS, CERTIFY THAT THIS WAS PE !FOR DIED IN ACCORDANCE
WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE: 2 5
vi it AF ��c
GARNES S ENGINEERING GROUP, Ltd
ENGINEERING -SA TING
„vi �. ivwrtnv iie iUI'nn—"Writ,nn99>UI"YHQNt(9U/)331{1/9-FA (9UT)33&3246'WEBSITE:—.g—neng,,eenng.com
SOIL LOG - PERCOLATION TEST
LEGAL DESCRIPTION: T12N R3W SECTION 22 LOT 43A
PERFORMED FOR: _
DEPTH
LARRY BRANDT
(feet) TEST HOLE #4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
DATE: 12/20/2019
SM TO ML
DEPTH TO DATE
GROUNDWATER
DRY 12/20/2019
DRY 12/30/2019
SITE PLAN
Pc'
P�
C6
DATE READING
SOIL
CLASSIFICATIONS
WATER LEVEL
READING
GW ORG
�� •-:,
W
ORGANICS, STUMP,
GP ML
DEBRIS - AREA DISTURBED
2
G M GL
30
0"
GC OL
3
SW MH
-
ORGANICS/LOAM
�• °�°
SP CH
12:51
30
SM ,' OH
6"
5
SC
-
SM TO ML
DEPTH TO DATE
GROUNDWATER
DRY 12/20/2019
DRY 12/30/2019
SITE PLAN
Pc'
P�
C6
DATE READING
CLOCK
TIME
NET TIME
(MINUTES)
WATER LEVEL
READING
NET DROP
(INCHES)
12/20/2019 1
11:51
-
6"
-
2
12:21
30
0"
6"
3
12:21
-
6"
-
4
12:51
30
0"
6"
5
12:51
-
6"
-
6
1:21
30
0"
6"
7
1:21
-
6"
-
6
1:51
30
0"
6"
19 B.O.H. PERCOLATION RATE <5 (MIN./INCH) PERC. HOLE DIA. 6 (INCHES)
TEST RUN BETWEEN 6.5 FT. AND 7.5 FT.
20 A FOUR HOUR PRESOAK WAS PERFORMED:
❑ YES NO
SOILS LOGGED BY: JODY MAUS PERCOLATION TEST PERFORMED BY: JODY MAUS
COMMENTS: PERCOLATION READINGS ARE WITHIN 1/16 OF INCH. RECOMMEND SOIL APPLICATION RATE OF 0.8 GPD/FT2
PERFORMED BY GEG, Ltd. I, JEFFREY A. GARNESS, CERTIFY THAT THIS WAS PE ORf�ED IN ACCORDANCE
WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE: / Z ; ///r