Re: Glassing Ridge Subdivision, Response to Comments
Ms. Wockenfuss,
Thank you for your comments on the proposed Glassing Ridge Subdivision, dated 9/8/21.
We have reviewed them and would like to offer the following responses:
Comment #1— Substantiate that there is adequate and safe potable water for each
proposed lot and neighboring lots.
Response - The proposed Lot 58B has an existing well at the top of the
embankment, near the south property line, that was drilled in 2019 to a depth of 75
ft. Well production was found to be 30 gpm, and nitrates tested at 3.96 mg/L. It is
reasonable to assume the proposed Lot 58A will be able to construct a well to pull
water from the same soil strata. The flow is adequate, and the nitrate levels are
below the EPA standard of 10 mg/L.
Other surrounding wells:
o The existing well on Mariann Lot 73A (bordering lot to the south) was
drilled in 1982 to a depth of 81 feet. Well production was found to be 30
gpm. An inspection in 1995 found the well production to be greater than
6.4 gpm and the nitrates to be 0.12 mg/L.
o The existing well on Lot 8A (across the road to the east) was drilled in 1978
to a depth of 88 feet. Well production was found to be 30 gpm. An
inspection in 1987 found the nitrates to be 0.14 mg/L.
o The existing well on Zed Lot 1 (lot to the north) was drilled in 2008 to a
depth of 61 feet. Well production was found to be 25 gpm. An inspection
in 2014 found the well production to be greater than 5.3 gpm and the
nitrates to be 1.36 mg/L.
Glassing Ridge Sub 'd — Response to Comments
September 24, 2011
Page 2 of 2
Comment #2 — Substantiate the capability of the proposed lots to adequately dispose of
wastewater, see AMC 15.65.405 for requirements.
Response - The proposed Lot 58B has an existing 3 bedroom home served by a
septic system, near the future property line, that was constructed in 2019
(OSP 191327). Three test holes were excavated to a depth ranging from 18 to 21
feet in the design of this system, with no groundwater observed and percolation
rates varying from 13 min/inch to 59 min/inch. Ultimately, a 56'L x 3'W x 9'D
deep trench was constructed with an application rate of 0.45 gpd/sf.
The attached map shows the potential location for a drainfield if a fixture home on
Lot 58A is constructed at the top of the embankment. With a well .located in the
northeast corner of the property, there would be adequate space to construct a
primary (and replacement) deep trench disposal field matching the dimensions of
the existing trench to the south. Much of the potential trench lies within the
boundary of Test Hole #2, which had the most favorable percolation rate of 13
min/inch.
If necessary, an advanced treatment system could be used to minimize the footprint
of the drainf eld. The example deep trench could be shortened to 13'L in this
scenario.
If you have any questions, please contact me at 337-3330.
Sincerely,
VEI CONSULTANTS
Scott T. Roel s,
Attaclunent : Drawing — Potential Well / Drainfield for Lot 58A
Civil Engineering and Surveying Consultants 1345 Rudakof Circle, Suite 201
Serving All of Alaska Anchorage, Alaska 99508
FAX: (907) 338-5386
Phone: (907) 337-3330
April 2, 2021
Municipality of Anchorage
Planning Department
P.O. Box 196650
Anchorage, AK 99519-6650
Re: On -Site Sewer and Soils for Lot 58, Section 5, Township 15N, Range 1 W, S.M.
(Grid NW1457)
Narrative
To whom it may concern,
VEI Consultants was contracted in 2019 to design an onsite wastewater disposal system at
the above referenced property. A new three (3) bedroom single family residence was
constructed and approved on the property in 2019. As shown on the attached site plan the
new house with well and septic system is located on proposed Lot 58B. As part of this
work a test hole was located on proposed Lot 58A for this soils investigation.
Soils
VEI conducted field investigations including surveying, digging test pits, performing
percolation tests and groundwater monitoring. The Soils Log—Percolation Test for Test
Hole #2 is attached. No groundwater has been observed in these test holes/monitoring
pipes, and soils logs from surrounding properties led us to believe that groundwater is not
an issue in this area. Still, we required the contractor to extend all three test holes (if
necessary) to verify that there is no groundwater or impermeable strata within 6 feet of the
bottom of the trench.
The percolation tests were perforned using a falling head method (never exceeding the 8"
of head outlined in code) and the percolation rate was calculated using the entire test (total
minutes / total inches). We performed the tests multiple times throughout the day and we
witnessed repeatable results. Only the last test of the day is provided on the soils log.
Therefore, we are confident that we calculated conservative percolation rates.
Surface Water & Topograpliy
There are no surface waters within 100 feet of the proposed system. Additionally, no
seasonal surface water was observed collecting anywhere on the property. The general
On -Site Seiner and Soils Jor Lot 58
April 2, 2021
Page 2 of 2
slope of the lot is from southeast to northwest at a grade ranging from 2%-10%. An
embankment, with a height of 50 feet and slopes between 40% to 70%, runs down the
center of the property from the southwest to the northeast. There is ample space for an
absorption system 50ft back from the embankment.
If you have any questions, please contact me at 337-3330.
Sincerely,
VEI CONSULTANTS
Scott T. Roelfs, P
Attachments: Overall Site Plan V=100'
Soils Log TH #2
72
58A
59
POTENTIAL DRAINFIELD LOCATION
W/ REPLACEMENT
58B /
�.., THy3
73A
0
Q
ISTING
SEPTIC
OF ��SYSTEMS /
................
AMP
Vis®
AW 2:
' 9th
®.....: ............................. . ...80
r
SCOTTT OE
CE 4 �•_AV
Air
AV
1414® 4111lk
RADIUS
s
I
/ 73B ,
yi
T
1
VEI CONSULTANTS
1345 RUDAKOF CIRCLE
POTENTIAL WELL / DRAINFIELD FOR LOT 58A VEI LOT 58A AND 58B
GLASSING RIDGE SUBDIVISION Consultants
HORZ SCALE: -100' I DATE: 12/30/22 1 GRID: NW1457 Pg 1 OF 1
EXISTING
SEPTIC
`POTENTIAL /%
SYSTEM
WELL
I LOCATION /
3
�
"q0
USABLE AREA
j
2455 SF
`
EXISTING
8A
SEPTIC
SYSTEM
\
RADIUS
s
I
/ 73B ,
yi
T
1
VEI CONSULTANTS
1345 RUDAKOF CIRCLE
POTENTIAL WELL / DRAINFIELD FOR LOT 58A VEI LOT 58A AND 58B
GLASSING RIDGE SUBDIVISION Consultants
HORZ SCALE: -100' I DATE: 12/30/22 1 GRID: NW1457 Pg 1 OF 1
-VElConsultants
Civil Engineeritrg and Surveying Consultants
Serving All of Alaska
SOILS LOG - PERCOLATION TEST
1345 Rudakof Circle, Suite 201
Anchorage, Alaska 99508
FAX: (907) 338-5386
Phone: (907) 337-3330
PERFORMED FOR: Oliver and Venita Moore DATE PERFORMED: 6/26/19, extended 9/25/19
LEGAL DESCRIPTION: Lot 58, Sec 5, T15N, R1 W, S.M. TOWNSHIP, RANGE, SECTION: T15N, R11V, Sec 5
PERFORMED BY: Scott Roelfs, P.E.
TEST HOLE No. TH #2 SLOPE SITE PLAN
0-
DEPTH
(FEET)
Net Time
(mfn.)
GROUNDWATER ENCOUNTERED:
®
--
Topsoil
■
YES
DEPTH TO GROUNDWATER:
2—""r.,e...:
14:52
SW
sand,
®
❑
some gravel
NO
YES
SP
4
:®:-':co'
fine sand,
5-
®
some gravel
5
15:14
5
6-
3/8
6
7-
9
3 7/8
8-
7
15.30
9-
4 3/8
1/2
10-
,.
SP
11-
'!
fine
sand
12-
7--
5 1/2
13 -
13-
Is -
Is-
16 -
6-17-
17 -
6/26/19
18-
1s-
20 -
•:"'
Y
9/25/19
21-
TOTAL DEPTH OF TESTHoLF_
21.0
Net Time
(mfn.)
GROUNDWATER ENCOUNTERED:
®
❑
14:38
■
YES
DEPTH TO GROUNDWATER:
2
14:52
GROUNDWATER ENCOUNTERED:
®
❑
(After Monitoring)
NO
YES
DEPTH TO GROUNDWATER:
3/4
4
MONITORING DATE 7 29 19
8
2 7/8
5/8
5
15:14
TOTAL DEPTH OF TESTHoLF_
21.0
Net Time
(mfn.)
GROUNDWATER ENCOUNTERED:
®
❑
14:38
NO
YES
DEPTH TO GROUNDWATER:
2
14:52
GROUNDWATER ENCOUNTERED:
®
❑
(After Monitoring)
NO
YES
DEPTH TO GROUNDWATER:
3/4
4
MONITORING DATE 7 29 19
b.5
4—
a-
0
a -
0
V)
Date Rearing
Gross Time
Net Time
(mfn.)
Depth to Water
(inches)
Net Drop
(rMhes)
6/26/19 1
14:38
0
2
14:52
14
1 1/2
1 1/2
3
15:01
9
2 1/4
3/4
4
15:09
8
2 7/8
5/8
5
15:14
5
3 1/4
3/8
6
15:23
9
3 7/8
5/8
7
15.30
7
4 3/8
1/2
8
15:40
10
5
5/8
9
15:50
10
5 1/2
1/2
PERCOLATION RATE 13.1 (minuteaAnch) PERC HOLE DIAMETER 6"
TEST RUN BETWEEN 6.0 FT AND 7.0 FT
COMMENTS: Pre—Soak 4hrs
Extended from 18.0 to 21.0 on 9/25/19
PERFORMED BY VEI CONSULTANTS. 1, SCOTT T. ROELFS , CERTIFY THAT THIS WAS PERFORMED IN
ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE: