MUNICIPALITY OF ANCHORAGE
On -Site Water & Wastewater Program
PO Box 196650 4700 Elmore Road 4,
Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997
http://www.muni.org/onsite I
Department
On -Site Water & Wastewater System Permit
Permit Number: OSP241054 Effective Date: 5/23/2024
Work Type: WellSeptic Initial Expiration Date: 5/23/2025
Tax Code Number: 01823104000
Site Legal Address: OLSON HEIGHTS BLK 1 LT 3 G:2936
Site Mailing Address: 4301 E 135th AVE, Anchorage
Owner: WILSON KENDALL & SAMANTHA Lot Size in Sq Ft: 49507
Design Engineer: AK BUILT CONSTRUCTION & DESIGN LLC^ Total Bedrooms: 5
This permit is for the construction of:
Q Disposal Field Q Septic Tank ❑ Holding Tank ❑ Privy Q Private Well ❑ Water Storage
All construction shall be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80)
3. The wastewater code requires inspections during the installation. The engineer shall notify the Development
Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
shall be either:
a. Opened and Closed on the same day, or
b. Covered, sealed, and heated to prevent freezing
�Y 1—.55me U fU 1 1` &u 1 I t
Issued By:
Date:
Date: _ _ 30 ,
Development Services DepartmentPhone: 907-343-7904
On -Site Water & Wastewater Section --~' Fax: 907-343-7997
ON-SITE SEPTIC/WELL PERMIT APPLICATION
Parcel I.D. 01823104000
Property owner(s) Wilson Kendall & Samantha
Mailing address 4155 Kingston Dr, Anchorage, AK 99504
Site address NHN E 135th Ave, Anchorage, AK 99516
Legal description (Sub'd., Block & Lot) Olson Heights, Blk 1 Lt 3
Day phone 907-223-9980
Legal description (Township, Range & Section) Sec. 27, T12N, R3W, SM
Lot Size 49507 Sq. Ft. Number of Bedrooms 5
APPLICATION IS FOR:
APPLICATION IS AN:
TYPE OF DWELLING:
(® all that apply)
Absorption Field
0
Initial 0
Single Family (SF) El
ADU)
Septic Tank
0
Upgrade El(w/wo
Duplex (D) ❑
Holding Tank
ElRenewal
❑
Multiple Dwellings ❑
Privy
❑
(SF and/or D)
Private Well
FXr
Water Storage
❑
THIS APPLICATION INCLUDES A WAIVER REQUEST FOR:
None
Distance: N/A
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit/Rush Fees: 3� y -9 S_ wel Fees: well f 22�;_
Date of Payment: Y/ l ��''� z `/ Date of Payment: gr3of z�(
Receipt Number: Receipt Number: 62q
Permit No. OS P 0 Sri' Waiver No.
GADevelopment Services\Building Safety\On Site Water and Wastewater\Forms\Client Forms\Permit Application.doc
PO Box 771203, Eagle River, AK 99577 – Phone: (907) 854-9115 Page 1 of 2
AK Built Construction & Design, LLC
General Contracting - Engineering - Project Administration
May 14, 2024
Municipality of Anchorage
Development Services Department
On-Site Water and Wastewater Section
PO Box 196650
Anchorage, AK 99519
RE: Olson Heights, Block 1, Lot 3 – Septic System Initial Permit Request
A permit is requested to install a conventional septic system for the subject property. The designed system
will serve a proposed 5-bedroom, single-family home. The subject property is vacant with no existing
structure or existing on-site septic system. An initial system is designed for the subject property and a
replacement field of equal capacity is shown with the designed system.
Wells
The subject property does not have an existing water well. Neighboring parcels are served by private
water wells. In the future, the subject property will be served by a private water well. Separation distances
stipulated in Anchorage Municipal Code (AMC) 15.65 shall be maintained for future well-sitting. There are
no wells within 100’ of the designed system septic system. The future well area shown on the plans
maintains a minimum of 100’ from on-lot septic systems and neighboring septic systems.
Soils
AK Built Construction & Design, LLC (AK Built) performed test holes, percolation tests, and groundwater
monitoring on April 5th and May 13th, 2024. Groundwater was not encountered in TH-01 but was observed
at least seven (7) days later at twelve (12) feet BGS. Groundwater was encountered at seven (7) feet below
ground surface (BGS) and observed at least seven (7) days later at four and a half (4 ½) feet BGS in TH-02.
After an initial review by the On-Site Water and Wastewater Section, it was determined an additional test
hole would be required to have a percolation test result within 30-feet of the entire soil absorption
system. TH-03 was excavated on April 29th, 2024. A groundwater seep was noted at the bottom of TH-03.
An application rate of 0.6 gallons/day/square feet shall be used for a conventional wastewater system.
Confirm groundwater conditions at time of construction.
Wastewater disposal systems
The designed wastewater disposal system is a wide trench (5-wide system) with 36” of sewer rock. The
designed system has the following characteristics.
# Bedrooms: 5
Daily Design Flow: 750 gallons/day
Tank Size: 1,500 gallons
Percolation Rate: 30 minutes/inch
Soil Rating: 0.6 gallons/day/square feet
Field Area Required: 1,250 square feet
System Type: Wide Trench (5 Wide) with 36” sewer rock
Minimum Length: 145 feet
Designed Trench Length: (2) 75 feet
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP241054, Deb Wockenfuss, 05/23/24
PO Box 771203, Eagle River, AK 99577 – Phone: (907) 854-9115 Page 2 of 2
AK Built Construction & Design, LLC
General Contracting - Engineering - Project Administration
Designed Field Area: 1,293 square feet
Maximum Excavation Depth (from existing ground) Allowed: 8 feet
Replacement disposal site
The subject property has no existing on-site septic system. As a part of this system design, a reserve field
of equal capacity is identified to show availability of a replacement system. TH-02 represents the soil
characteristics for the reserve field. The percolation rate for TH-02 is faster than one (1) minute/inch and
groundwater was encountered. The replacement system is a bed with 6” of sewer rock and a 2’ sand liner.
The reserve system has the following characteristics. Confirm groundwater conditions at time of
construction. Coordinate with any future developments not known at this time.
# Bedrooms: 5
Daily Design Flow: 750 gallons/day
Tank Size: 1,500 gallons
Percolation Rate: 0-1 minutes/inch
Soil Rating: 0.7 gallons/day/square feet
Field Area Required: 1,071.4 square feet
System Type: Bed with 6” sewer rock
Bed Width: 20 feet
Minimum Length: 53.57 feet
Designed Length: 54 feet
Designed Field Area: 1,080 square feet
Maximum Excavation Depth (from existing ground) Allowed: 0.5 feet
Drainage
There is no surface water located within 100’ of the designed system. There is a storm drainage ditch
along W 135th Ave. The designed system will not have an impact on the roadway ditch.
Topography
The designed system is in the northwest corner of the subject property. The surrounding property
generally slopes from east to west and the area immediately surrounding the drain field is flat. There are
no steep slopes in the vicinity of the designed system.
The designed system does not have probable adverse impacts to adjacent properties.
If you have any questions, please contact me.
Sincerely,
Robert Colles, PE
AK Built Construction & Design, LLC
Project Manager/Managing Member
907-854-9115
rlcolles@akbuilt.net
W
TH
TH
TH
OLSON HEIGHTS
BLOCK 1, LOT 2
OLSON HEIGHTS
BLOCK 1, LOT 4
OLSON HEIGHTS
BLOCK 1, LOT 3
OL
S
O
N
H
E
I
G
H
T
S
BL
O
C
K
2
,
L
O
T
3
OL
S
O
N
H
E
I
G
H
T
S
BL
O
C
K
2
,
L
O
T
4
OL
S
O
N
H
E
I
G
H
T
S
BL
O
C
K
2
,
L
O
T
2
McCABE WEST
LOT 4
McCABE WEST
LOT 5
PROPOSED
5-BEDROOM
HOUSE
R100'
R 100'
R100 '
R1
0
0'
R100'
EXISTING
SEPTIC FIELD EXISTING
SEPTIC FIELD
EXISTING
SEPTIC FIELD
EXISTING
SEPTIC FIELD
38
5
3 90
395
400
3 90
388
389
387
3 87
38
6
38
8
387
3
8
6
RESERVE FIELD
PROPOSED DRIVEWAY
TH-01
TH-02
10'10
'
5'
6'
5'
75' 10
'
1,500-GAL SEPTIC TANK
BCO
DCO
CO
MT
MT
COE
1
3
5
T
H
A
V
E
PERMISSIBLE WELL SITING,
WELL SHALL NOT CONFLICT
WITH FOOTPRINT OF FUTURE
DRIVEWAY
100
'
1
0
0
'
T
O
T
A
N
K
1
0
2
.
0
2
'
10'x190' CEA & ATU UTILITY EASEMENT,
CENTERED ON PROPERTY LINE
10' CEA & ATU UTILITY
EASEMENT
FLOW SPLITTER
TH-03
16
'
20
'
54'
FILL LIMITS, TYP
FI
L
E
P
A
T
H
:
C
:
\
U
s
e
r
s
\
c
o
l
l
e
\
O
n
e
D
r
i
v
e
-
A
K
B
u
i
l
t
C
o
n
s
t
r
u
c
t
i
o
n
&
D
e
s
i
g
n
\
A
K
B
u
i
l
t
\
P
r
o
j
e
c
t
s
\
0
0
3
1
.
0
1
W
i
l
s
o
n
O
l
s
o
n
H
e
i
g
h
t
s
B
l
k
3
L
o
t
1
\
A
C
A
D
\
0
0
3
1
.
0
1
-
S
i
t
e
P
l
a
n
.
d
w
g
PL
O
T
D
A
T
E
:
5
/
1
4
/
2
0
2
4
AK BUILT
CONSTRUCTION & DESIGN, LLC
PO BOX 771203
EAGLE RIVER, AK 99577
(907)854-9115
CERTIFICATE OF AUTHORIZATION
#204451
OL
S
O
N
H
E
I
G
H
T
S
,
B
L
O
C
K
1
,
L
O
T
3
SE
P
T
I
C
S
Y
S
T
E
M
D
E
S
I
G
N
AN
C
H
O
R
A
G
E
,
A
L
A
S
K
A
AK
B
U
I
L
T
P
R
O
J
E
C
T
N
O
:
0
0
3
1
.
0
1
SA
M
A
N
T
H
A
&
K
E
N
D
A
L
L
W
I
L
S
O
N
3OF
SHEET:
5/14/2024
DATE:
SHEET TITLE:
Robert Colles, PE
No. CE-163739REGISTEREDPROFESSIONALE N GINEER
5/14/2024
SEPTIC SYSTEM (E)
WELL (E)
BUILDING (E)
BUILDING (P)
SEPTIC SYSTEM (P)
CULVERT (E)
WELL RADIUS (E)
PROPERTY LINE
EASEMENT
W
LEGEND:
00 20' 40'
N
SITE PLAN
1
ABBREVIATIONS:
BCO BUILDING CLEAN OUT
CO CLEAN OUT
DCO DOUBLE CLEAN OUT
(E) EXISTING
GAL GALLON
MT MONITORING TUBE
(P) PROPOSED
TH TEST HOLE
NOTE:
1. THE EXISTING LOT IS VACANT AND UNDEVELOPED. A
RESERVE FIELD IS SHOWN TO IDENTIFY SUFFICIENT
AVAILABLE AREA FOR REPLACEMENT OF THE DESIGNED
SYSTEM WITH AN EQUIVALENT CAPACITY FIELD.
2. RESERVE FIELD SHALL BE A MOUND STYLE BED SYSTEM
REQUIRING A PUMP CHAMBER AND PRESSURE
DISTRIBUTION TO MAINTAIN GROUND WATER
SEPARATION REQUIREMENTS.
3. McCABE WEST LOT 4 IS SERVED BY A PRIVATE WELL
LOCATED 100'+ AWAY FROM DESIGNED SYSTEM.
4. OLSON HEIGHTS BLOCK 1, LOT2 SEPTIC SYSTEM IS 100'+
FROM DEPICTED PERMISSIBLE WELL SITING AREA.
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP241054, Deb Wockenfuss, 05/23/24
FI
L
E
P
A
T
H
:
C
:
\
U
s
e
r
s
\
c
o
l
l
e
\
O
n
e
D
r
i
v
e
-
A
K
B
u
i
l
t
C
o
n
s
t
r
u
c
t
i
o
n
&
D
e
s
i
g
n
\
A
K
B
u
i
l
t
\
P
r
o
j
e
c
t
s
\
0
0
3
1
.
0
1
W
i
l
s
o
n
O
l
s
o
n
H
e
i
g
h
t
s
B
l
k
3
L
o
t
1
\
A
C
A
D
\
0
0
3
1
.
0
1
-
N
o
t
e
s
.
d
w
g
PL
O
T
D
A
T
E
:
5
/
1
4
/
2
0
2
4
AK BUILT
CONSTRUCTION & DESIGN, LLC
PO BOX 771203
EAGLE RIVER, AK 99577
(907)854-9115
CERTIFICATE OF AUTHORIZATION
#204451
OL
S
O
N
H
E
I
G
H
T
S
,
B
L
O
C
K
1
,
L
O
T
3
SE
P
T
I
C
S
Y
S
T
E
M
D
E
S
I
G
N
AN
C
H
O
R
A
G
E
,
A
L
A
S
K
A
AK
B
U
I
L
T
P
R
O
J
E
C
T
N
O
:
0
0
3
1
.
0
1
SA
M
A
N
T
H
A
&
K
E
N
D
A
L
L
W
I
L
S
O
N
3OF
SHEET:
5/14/2024
DATE:
SHEET TITLE:
Robert Colles, PE
No. CE-163739REGISTEREDPROFESSIONALE N GINEER
5/14/2024
DESIGN NOTES
2
SYSTEM DESIGN:
1. DESIGNED SYSTEM IS FOR OLSON HEIGHTS, BLOCK 1, LOT 3. MUNICIPALITY OF ANCHORAGE (MOA) PARCEL
ID 1823104000.
2. DESIGNED SYSTEM WILL SERVE A PROPOSED 5-BEDROOM, SINGLE FAMILY HOME.
3. THREE TEST HOLES WERE EXCAVATED TO COLLECT SOIL, PERCOLATION, AND GROUND WATER DATA FOR
THE DESIGNED SYSTEM AND RESERVE FIELD.
4. SEPTIC TANK CAPACITY IS A MINIMUM OF 1,000-GALLONS PLUS 250-GALLONS FOR EACH BEDROOM OVER
THREE.
4.1. 1,000 GAL+ 250 GAL x (5 BDRM - 3 BDRM) = 1,500 GAL.
4.2. SEPTIC TANK SHALL BE A 1,500-GALLON CAPACITY TANK.
5. DISPOSAL FIELDS SHALL BE DESIGNED TO ACCEPT 150-GALLONS OF WASTEWATER PER BEDROOM PER
DAY.
5.1. DESIGN FLOW = 150 GPD/BDRM x 5 BDRM = 750 GPD.
6. THE MINIMUM EFFECTIVE ABSORPTION AREA OF A DISPOSAL FIELD SHALL BE CALCULATED USING THE
WASTEWATER APPLICATION RATE CORRESPONDING TO THE PERCOLATION RATE IN ANCHORAGE
MUNICIPAL CODE (AMC) 15.65 TABLE 2.
6.1. PERCOLATION RATE = 30 MIN/IN.
6.2. APPLICATION RATE = 0.6 GPD/SF (PER AMC 15.65 TABLE 2).
6.3. MINIMUM EFFECTIVE ABSORPTION AREA = 750 GPD / 0.6 GPD/SF = 1,250 SF
7. DISPOSAL FIELD SHALL BE A WIDE TRENCH.
7.1. TRENCH WIDTH (W) = 5 FT
7.2. EFFECTIVE DEPTH (D) = 3 FT
7.3. SIZE FACTOR = (W + 2) / (W + 1 + 2D) = (5 + 2) / (5 + 1 + (2 x 3)) = 0.58
7.4. MINIMUM FIELD LENGTH (L) = (ABSORPTIONS AREA / W) x SIZE FACTOR = (1,250 SF / 5 FT) x 0.58 = 145 FT
7.5. MINIMUM FIELD SIZE IS 5-FEET WIDE, 3-FEET SEWER ROCK, AND 145-FEET LONG. USE TWO TRENCHES
AT 75-FEET LONG.
MATERIALS SPECIFICATIONS:
1. WASTEWATER DISPOSAL SYSTEM COMPONENTS AND MATERIALS SHALL BE APPROVED BY THE MOA IN
ACCORDANCE WITH THE CURRENT EDITION OF MOA'S PUBLICATION "STANDARDS AND SPECIFICATIONS
FOR COMPONENT PARTS AND MATERIALS USED IN CONSTRUCTION OF ON-SITE WASTEWATER DISPOSAL
SYSTEMS".
2. COMPONENTS INCIDENTAL TO THE SEPTIC SYSTEM INCLUDING BUT NOT LIMITED TO PIPING, FITTINGS,
PUMPS AND VALVES THAT ARE LISTED OR LABELED BY A MOA APPROVED ACCREDITED THIRD PARTY
LISTING AGENCY FOR THE INTENDED USE DO NOT REQUIRE THE MOA SUBMITTAL/APPROVAL PROCESS.
3. SEPTIC TANKS SHALL BE CONSTRUCTED FROM DURABLE, CORROSION-RESISTANT MATERIALS, INCLUDING
CONCRETE, FIBERGLASS, OR PLASTIC. SEPTIC TANKS CONSTRUCTED FROM STEEL SHALL BE COATED ON
BOTH THE INTERIOR AND EXTERIOR WITH AN APPROVED POLYURETHANE LINING OR SUPERIOR MATERIAL.
4. ALL SEPTIC TANKS SHALL BE FITTED WITH WATERTIGHT COUPLINGS, APPROVED BY MOA, AT THE
PUMP-OUT ATTACHMENTS AND ON THE INLET AND OUTLET OF THE TANK.
5. A SEPTIC TANK SHALL HAVE A 20" MINIMUM DIAMETER MANWAY RISER SERVING THE FIRST
COMPARTMENT. THE RISER, INCLUDING THE COVER, SHALL BE INSULATED WITH 4" MINIMUM INSULATION
EXTENDING 48" BELOW GRADE OR TO THE TANK INSULATION. THE INSULATION SHALL BE OF AN APPROVED
TYPE SUITABLE FOR BELOW GRADE APPLICATIONS. EXPOSED INSULATION ABOVE GRADE SHALL BE
PROTECTED FROM UV DAMAGE. THE RISER LID SHALL BE SECURED TO PREVENT UNINTENDED ACCESS.
6. PIPE AND FITTINGS SHALL BE IN ACCORDANCE WITH NOTE 1 AND "PIPE AND FITTINGS MATERIAL" TABLE.
7. PIPES USED IN GRAVITY DISPOSAL SYSTEMS SHALL BE 4" IN DIAMETER.
8. CLEAN OUTS SHALL BE LONG SWEEP.
9. SEWER ROCK/DRAIN ROCK SHALL BE COARSE, WASHED AGGREGATED THAT MEASURES 12" TO 2" IN
DIAMETER WITH NO MORE THAN 1% PASSING THE No. 200 SIEVE.
10. BEDDING MATERIAL FOR SEPTIC TANKS SHALL BE PER MANUFACTURER'S REQUIREMENTS.
11. FILTER FABRIC USED AS A SILT BARRIER IN THE CONSTRUCTION OF ABSORPTION FIELDS SHALL BE A
PERMEABLE GEOTEXTILE APPROVED FOR THE APPLICATION.
12. INSULATION USED IN THE CONSTRUCTION OF SEPTIC SYSTEMS FOR THE PURPOSES OF FREEZE
PROTECTION OF DISPOSAL FIELDS AND SEPTIC SYSTEM COMPONENTS SHALL BE MINIMUM TYPE IV
EXTRUDED OR EXPANDED POLYSTYRENE, 25 PSI COMPRESSIVE STRENGTH.
PIPE AND FITTINGS MATERIAL
PIPE TYPE OR ASTM
DESIGNATION
APPROVED AS PERFORATED
DISPOSAL FIELD PIPE OR
SOLID COLLECTOR PIPE
APPROVED AS CLEAN
OUT OR STANDPIPE
CAST IRON **YES YES
ASTM D3034 (PVC)YES YES
ASTM F789 (PVC)YES YES
ASTM D1785 (PVC)**YES YES
ASTM D2665 (PVC)**YES YES
ASTM D2751 (ABS)YES NO*
ASTM D2661 (ABS)**YES YES
ASTM F628 (ABS)**YES YES
ASTM F810 (HDPE)YES NO
* D2751 MAY BE APPROVED AS STANDPIPE MATERIAL IF THE MINIMUM WALL THICKNESS
IS 0.18", SDR 23.5.
** UNDERGROUND DWV PIPE MATERIALS LISTED IN UPC TABLE 701.1 (2012).
CONSTRUCTION SPECIFICATIONS:
1. SEPARATION DISTANCES AS IDENTIFIED IN THE "SEPARATION DISTANCES" TABLE SHALL BE MAINTAINED.
NOTIFY THE ENGINEER OF DISCOVERIES MADE DURING CONSTRUCTION THAT IMPACT SEPARATION
DISTANCE REQUIREMENTS.
2. FLAG AND SURVEY ALL PROPERTY LINES, WELL RADII, AND EXISTING FIELD SEPARATIONS PRIOR TO START
OF CONSTRUCTION.
3. LAYOUT ALL FIELD COMPONENTS AND LOCATIONS PRIOR TO START OF CONSTRUCTION. NOTIFY THE
ENGINEER IF CONFLICTS EXIST.
4. GROUNDWATER MONITOR TUBES SHALL REMAIN IN PLACE UNTIL CONSTRUCTION BEGINS. ABANDON
GROUNDWATER MONITOR TUBES BY CUTTING ONE FOOT BELOW GRADE AND ABANDON IN PLACE. IF THE
GROUNDWATER MONITOR TUBE IS WITHIN FIVE FEET OF THE DISPOSAL FIELD, REMOVE THE
GROUNDWATER MONITOR TUBE IN IT'S ENTIRETY.
5. TANKS WITH TWO TO FOUR FEET OF COVER SHALL BE INSULATED WITH A MINIMUM OF 2" OF APPROVED
INSULATION PLACED IMMEDIATELY ABOVE THE TOP OF THE TANK. TANKS SHALL NOT HAVE LESS THAN
TWO FEET OF COVER.
6. A SEPTIC TANK SUBJECT TO BUOYANCY FORCES SHALL BE ANCHORED OR BALLASTED AS REQUIRED TO
PREVENT FLOTATION REGARDLESS OF THE LIQUID LEVEL IN THE TANK.
7. A SEPTIC TANK SHALL HAVE A 4" MINIMUM STAND PIPE PROVIDING ACCESS TO OTHER COMPARTMENTS
NOT SERVED BY THE MANWAY RISER.
8. PROVIDE AIR TIGHT CAPS ON ALL CLEAN OUTS AND MONITORING TUBES.
9. PROVIDE A BUILDING CLEAN OUT INSTALLED ONE TO FOUR FEET FROM THE BUILDING FOUNDATION.
10. A DOUBLE CLEAN OUT SHALL BE PROVIDED WITHIN TEN FEET OF THE SEPTIC TANK OUTLET. THE
OPPOSING CLEAN OUTS SHALL BE ORIENTED SUCH THAT THE CLEAN OUT CLOSEST TO THE TANK SHALL
BE TO CLEAN THE LINE AWAY FROM THE SEPTIC TANK, AND THE CLEAN OUT FURTHEST FROM THE TANK
SHALL BE ORIENTED TO ALLOW CLEANING TOWARD THE SEPTIC TANK. THE CLEANOUTS SHALL BE
LOCATED ON UNDISTURBED SOIL.
11. SINGLE SEGMENTS OF SUBSURFACE DISPOSAL FIELDS SHALL NOT EXCEED 100 FEET IN LENGTH.
12. THE LONG AXIS OF A DISPOSAL FIELD SHALL FOLLOW THE CONTOURS OF THE ORIGINAL GROUND.
13. THE HORIZONTAL SEPARATION DISTANCE BETWEEN THE CLOSEST EDGES OF WORKING OR
DECOMMISSIONED SUBSURFACE DISPOSAL FIELDS, OR SEGMENTS OF SUBSURFACE DISPOSAL FIELDS,
SHALL BE AT LEAST TWICE THE DEPTH OF THE DRAIN ROCK BELOW THE LEVEL OF THE DRAINPIPE, BUT
NOT LESS THAN SIX FEET.
14. THE BOTTOM OF THE TRENCH SHALL BE LEVEL WITHIN 4". THE BOTTOM OF A WIDE TRENCH OR BED
DISPOSAL FIELD SHALL BE LEVEL WITHIN 2" BEFORE PLACEMENT OF DRAIN ROCK.
15. AFTER EXCAVATION HAS EXPOSED THE DESIGNATED INFILTRATIVE SURFACE, ANY NATIVE SOIL THAT IS
SMEARED SHALL BE SCARIFIED TO IMPROVE ITS POROSITY BEFORE PLACEMENT OF DRAIN ROCK.
16. PERFORATED DISTRIBUTION PIPE USED IN A SUBSURFACE DISPOSAL FIELD SHALL BE LAID LEVEL AND
BEDDED WITH DRAIN ROCK EXTENDING A MINIMUM OF 2" ABOVE THE TOP OF THE DISTRIBUTION PIPE, AND
LEVEL ACROSS THE ENTIRE WIDTH OF THE DRAIN FIELD.
17. NON-PRESSURIZED SUBSURFACE DISPOSAL FIELD PIPING SHALL HAVE A 4" DIAMETER CLEAN OUT
CONNECTED TO BOTH ENDS OF EACH PERFORATED SEGMENT. CLEANOUTS WITHIN 20 FEET AND IN LINE
WITH THE DOUBLE CLEAN OUT DOWNSTREAM OF THE SEPTIC TANK MAY BE OMITTED.
18. AT LEAST ONE 4" DIAMETER MONITORING TUBE SHALL BE INSTALLED IN EACH SEPARATE DISPOSAL FIELD
SEGMENT TO ALLOW MEASUREMENT OF THE FLUID LEVEL IN THE DISPOSAL FIELD. MONITOR TUBES SHALL
NOT BE CONNECTED TO THE DISTRIBUTION PIPE NETWORK. THE PORTION OF A MONITOR TUBE
EXTENDING DOWN FROM THE LEVEL OF THE HORIZONTAL DISTRIBUTION PIPES TO THE BOTTOM OF THE
DRAIN ROCK SHALL BE PERFORATED. THE PORTION OF THE MONITOR TUBE ABOVE THE HORIZONTAL
DISTRIBUTION PIPES SHALL BE NON-PERFORATED. MONITOR TUBES SHALL BE LOCATED AT ALL ANGLE
POINTS OF DISPOSAL FIELDS TO MARK THE LOCATION OF THE ABSORPTIONS SYSTEM. PRESSURIZED
TRENCH DISPOSAL FIELDS THAT DO NOT HAVE CLEAN OUT PIPES SHALL HAVE A MONITOR TUBE WITHIN
ONE FOOT OF EACH END OF INDIVIDUAL TRENCH SEGMENTS. PRESSURIZED BED DISPOSAL FIELDS THAT
DO NOT HAVE CLEAN OUT PIPES SHALL HAVE A MONITORING TUBE WITHIN ONE FOOT OF EACH CORNER
OF THE BED.
19. AN APPROVED PERMEABLE GEOTEXTILE SILT BARRIER SHALL BE INSTALLED COVERING THE ENTIRE TOP
SURFACE OF THE DRAIN ROCK PRIOR TO BACKFILL.
20. THE DISPOSAL FIELD COVER SHALL BE A MINIMUM OF TWO FEET DEEP, OVER THE TOP OF THE DRAIN
ROCK. IF THE DISPOSAL FIELD COVER IS LESS THAN THREE FEET, THE DISPOSAL FIELD SHALL BE
INSULATED WITH 2" OF APPROVED RIGID BOARD INSULATION. MINIMUM SOIL COVER OVER THE INSULATION
SHALL BE ONE FOOT.
21. THE FINISH GRADE OVER A SUBSURFACE DISPOSAL FIELD SHALL BE MOUNDED A MINIMUM OF 6" ABOVE
ADJACENT GROUND TO PREVENT THE FORMATION OF A DEPRESSION AFTER THE BACKFILL HAS SETTLED.
22. UPON COMPLETION OF CONSTRUCTION ALL CLEAN OUTS AND MONITOR TUBES SHALL BE ABOVE FINAL
GRADE A MINIMUM OF TWO FEET, A MAXIMUM OF 4 FEET, BE WATER TIGHT, AND LOCATED BY SWING-TIE
MEASUREMENTS TO ALLOW YEAR-ROUND LOCATION AND ACCESS.
SEPARATION DISTANCES
SEPTIC TANK SOIL ABSORPTION
SYSTEM
PROPERTY LINE 5 FEET 10 FEET
WATER MAIN/WATER
SERVICE LINE 10 FEET 10 FEET
BUILDING FOUNDATION 10 FEET 10 FEET
DECKS/STAIRS >30" ABOVE
GRADE 5 FEET 10 FEET
SURFACE WATER 100 FEET 100 FEET
PRIVATE WELL 100 FEET 100 FEET
PUBLIC WATER SUPPLY SEE 18 AAC 80 SEE 18 AAC 80
>25% SLOPE >10' TALL -50 FEET
>25% SLOPE <10' TALL -25 FEET
SUBSURFACE DRAIN -GREATER OF 10 FEET OR
TWO TIMES GRAVEL DEPTH
SOIL ABSORPTION SYSTEM -GREATER OF 6 FEET OR TWO
TIMES GRAVEL DEPTH
WATER TABLE -4 FEET
IMPERMEABLE LAYER -6 FEET
INSPECTIONS:
1. AN ON-SITE WASTEWATER DISPOSAL SYSTEM SHALL NOT BE BACKFILLED,
COMPLETED, OR USED UNTIL THE ENGINEER HAS INSPECTED AND TAKES NO
EXCEPTION TO THE INSTALLATION.
2. NOTIFY THE ENGINEER 48 HOURS IN ADVANCE OF ANTICIPATED CONSTRUCTION.
3. THE ENGINEER WILL MEET WITH THE CONTRACTOR PRIOR TO CONSTRUCTION TO
DISCUSS THE FOLLOWING,
3.1. PRECONSTRUCTION MEETING TO DISCUSS CONSTRUCTION PROCEDURES AND
DESIGN REQUIREMENTS.
3.2. VERIFY SITE CONDITIONS CONFORM TO THE DESIGN PLANS AND PERMIT.
3.3. VERIFY THE PROJECT LAYOUT CONFORMS TO THE DESIGN PLANS AND PERMIT.
4. THE ENGINEER SHALL PERFORM A BOTTOM OF HOLES INSPECTION FOR THE SEPTIC
TANK AND DISPOSAL FIELD.
5. THE DISPOSAL FIELD REQUIRES THE FOLLOWING INSPECTIONS,
5.1. AFTER EXCAVATION OF ALL NATIVE MATERIAL HAS BEEN COMPLETED, BUT PRIOR
TO PLACEMENT OF FILTER SAND AND/OR DRAIN ROCK. THE PURPOSE OF THIS
INSPECTION IS TO ALLOW VERIFICATION THAT THE NATIVE MATERIAL CONFORMS
TO THE SOILS LOG AND THE EXCAVATION IS TO THE CORRECT DEPTH.
5.2. AFTER THE PLACEMENT OF FILTER SAND, IF UTILIZED.
5.3. AFTER THE PLACEMENT OF DRAIN ROCK, AND INSTALLATIONS OF DISTRIBUTION
LINES, CLEAN OUTS, AND MONITOR TUBES, BUT PRIOR TO PLACEMENT OF
INSULATION, SILT BARRIER, OR BACKFILL.
5.4. AFTER THE SYSTEM HAS BEEN BACKFILLED TO VERIFY FINAL GRADING AND THE
LOCATION OF ALL STAND PIPES.
6. THE SEPTIC TANK REQUIRES THE FOLLOWING INSPECTIONS,
6.1. AFTER THE TANK IS SET IN PLACE WITH DISTRIBUTION PIPES AND CLEAN OUTS
INSTALLED, BUT PRIOR TO BACKFILL.
6.2. AFTER THE TANK HAS BEEN BACKFILLED TO VERIFY FINAL GRADING, ELECTRICAL
EQUIPMENT INSTALLATION, AND THE LOCATION OF ALL STAND PIPES.
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP241054, Deb Wockenfuss, 05/23/24
TH
TH
TH
OLSON HEIGHTS
BLOCK 1, LOT 2
OLSON HEIGHTS
BLOCK 1, LOT 3
McCABE WEST
LOT 4
PROPOSED
5-BEDROOM
HOUSE
RESERVE FIELD
PROPOSED
DRIVEWAY
90
°22.5°
22.5°SPLT
TE
E
TE
E
P-
1
P-
2
P-3
P-4
P-5 P-6
P-9
P-8
P-11
P-7
P-10
5'
6'
5'
10
'
10'
10
.
2
'
10
'
R
1
0
0
'
75'
CO
CO
DCO
BCO
1,500-GAL SEPTIC TANK
MT
MT
TH-01
TH-02CUT MT 1' BELOW GRADE,
ABANDON IN PLACE.
FULLY REMOVE MT DURING
RESERVE FIELD CONSTRUCTION
REMOVE MT DURING
FIELD CONSTRUCTION
FLOW SPLITTER
TH-03
RESERVE FIELD FILL LIMITS,
DO NOT CROSS PROPERTY LINE
20
'
54'
FINAL GRADING FILL LIMITS,
DO NOT CROSS PROPERTY LINE
COORDINATE INSTALLATION OF BUILDING
SEWER WITH HOUSE CONSTRUCTION
385.14
Septic System
375
380
385
390
395
375
380
385
390
395
0+00 0+10 0+20 0+30 0+40 0+50 0+60 0+70 0+80 0+90 1+00
90°
22.5°
22.5°
20"Ø MIN, INSULATED RISER
2' MIN, TYP
4"Ø CLEAN OUT, TYP
4"Ø BUILDING
CLEAN OUT
4" COMBO
WYE, TYP
1,500-GAL SEPTIC TANK
EXISTING GROUND
SPLT
FINISH GRADE TO ENSURE
MINIMUM SOIL COVER, TYP
P-1 P-2
P-3
P-4 P-5
2" BOARDSTOCK
INSULATION, TYP
375
380
385
390
395
375
380
385
390
395
0+00 0+10 0+20 0+30 0+40 0+50 0+60 0+70 0+800+84
3'
MT PERFORATED
IN DRAIN ROCK
TEE
7.
8
'
P-11P-10
ELEV:380.61
PIPE TABLE
NAME
P-1
P-2
P-3
P-4
P-5
P-6
P-7
P-8
P-9
P-10
P-11
SIZE
4"
4"
4"
4"
4"
4"
4"
4"
4"
4"
4"
LENGTH
10.89'
6.38'
4.00'
15.23'
39.65'
5.50'
37.50'
37.50'
5.50'
37.50'
37.50'
SLOPE
2.00%
2.00%
2.00%
2.00%
2.00%
0.00%
0.00%
0.00%
0.00%
0.00%
0.00%
INLET LOCATION
N:2593759.0414
E:1675434.7169
N:2593759.0244
E:1675417.0972
N:2593759.0182
E:1675410.7169
N:2593763.0182
E:1675410.7169
N:2593777.0922
E:1675416.5466
N:2593816.7380
E:1675416.3561
N:2593816.7116
E:1675410.8562
N:2593816.7116
E:1675410.8562
N:2593816.7380
E:1675416.3561
N:2593816.7644
E:1675421.8560
N:2593816.7644
E:1675421.8560
INLET ELEV
385.29
384.91
384.78
384.70
384.40
383.61
383.61
383.61
383.61
383.61
383.61
OUTLET LOCATION
N:2593759.0162
E:1675423.8300
N:2593759.0182
E:1675410.7169
N:2593763.0182
E:1675410.7169
N:2593777.0922
E:1675416.5466
N:2593816.7380
E:1675416.3561
N:2593816.7116
E:1675410.8562
N:2593779.2120
E:1675411.0363
N:2593854.2111
E:1675410.6760
N:2593816.7644
E:1675421.8560
N:2593779.2648
E:1675422.0362
N:2593854.2640
E:1675421.6759
OUTLET ELEV
385.07
384.78
384.70
384.40
383.61
383.61
383.61
383.61
383.61
383.61
383.61
375
380
385
390
395
375
380
385
390
395
0+460+50 0+60 0+70 0+80 0+90 1+00 1+10 1+20 1+30
4" SWEEP 90, TYP
SILT BARRIER, TYP
4"Ø PERFORATED PIPE, TYP3'
SEWER ROCK, TYP
TEE
FINISH GRADE TO ENSURE
MINIMUM SOIL COVER, TYP
P-7 P-8
2" BOARDSTOCK
INSULATION, TYP
FI
L
E
P
A
T
H
:
C
:
\
U
s
e
r
s
\
c
o
l
l
e
\
O
n
e
D
r
i
v
e
-
A
K
B
u
i
l
t
C
o
n
s
t
r
u
c
t
i
o
n
&
D
e
s
i
g
n
\
A
K
B
u
i
l
t
\
P
r
o
j
e
c
t
s
\
0
0
3
1
.
0
1
W
i
l
s
o
n
O
l
s
o
n
H
e
i
g
h
t
s
B
l
k
3
L
o
t
1
\
A
C
A
D
\
0
0
3
1
.
0
1
-
S
e
p
t
i
c
P
l
a
n
.
d
w
g
PL
O
T
D
A
T
E
:
5
/
1
4
/
2
0
2
4
AK BUILT
CONSTRUCTION & DESIGN, LLC
PO BOX 771203
EAGLE RIVER, AK 99577
(907)854-9115
CERTIFICATE OF AUTHORIZATION
#204451
OL
S
O
N
H
E
I
G
H
T
S
,
B
L
O
C
K
1
,
L
O
T
3
SE
P
T
I
C
S
Y
S
T
E
M
D
E
S
I
G
N
AN
C
H
O
R
A
G
E
,
A
L
A
S
K
A
AK
B
U
I
L
T
P
R
O
J
E
C
T
N
O
:
0
0
3
1
.
0
1
SA
M
A
N
T
H
A
&
K
E
N
D
A
L
L
W
I
L
S
O
N
3OF
SHEET:
5/14/2024
DATE:
SHEET TITLE:
Robert Colles, PE
No. CE-163739REGISTEREDPROFESSIONALE N GINEER
5/14/2024
BUILDING (P)
SEPTIC SYSTEM (P)
WELL RADIUS (E)
PROPERTY LINE
EASEMENT
LEGEND:
00 10' 20'
N
SEPTIC SYSTEM DESIGN
3
SEPTIC SYSTEM SEWER LINE
SEPTIC SYSTEM - EAST TRENCH
ABBREVIATIONS:
BCO BUILDING CLEAN OUT
BOH BOTTOM OF HOLE (TEST HOLE)
CO CLEAN OUT
DCO DOUBLE CLEAN OUT
E EASTING
(E) EXISTING
ELEV ELEVATION
GAL GALLON
MIN MINIMUM
MT MONITORING TUBE
N NORTHING
(P) PROPOSED
TH TEST HOLE
TYP TYPICAL
NOTES:
1. PIPE LENGTHS ARE ESTIMATED AND PROVIDED FOR REFERENCE ONLY. CONTRACTOR TO VERIFY
MATERIAL QUANTITIES.
2. UNIFORMLY GRADE THE SITE UPON COMPLETION OF SEPTIC SYSTEM INSTALLATION. MOUND MATERIAL TO
ALLOW FOR SETTLEMENT OF DISTURBED AREAS AND TO MEET MINIMUM SOIL COVER REQUIREMENTS.
ENSURE FILL DOES NOT CROSS PROPERTY LINE. GRADE SLOPES AT 3H:1V.
3. TOPSOIL AND SEED DISTURBED AREAS WITH 4" MINIMUM OF TOPSOIL AND A SEED APPROPRIATE FOR THE
SITE.
4. RESERVE FIELD IS BED STYLE SYSTEM WITH SAND LINER. CONTRACTOR TO SUPPLY EQUIPMENT OF
SUFFICIENT SIZE TO PREVENT MOVEMENT OF EQUIPMENT ACROSS IN-SITU MATERIALS UNDER SEWER
ROCK AT TIME OF FIELD CONSTRUCTION.
5. COORDINATE HOUSE SITE GRADING WITH HOUSE CONSTRUCTION. ENSURE SUFFICIENT SOIL COVER IS
PROVIDED OVER BUILDING SEWER.
SEPTIC SYSTEM - WEST TRENCH
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP241054, Deb Wockenfuss, 05/23/24
TH
TH
TH
KENDALL & SAMANTHA WILSON
OLSON HEIGHTS, BLK 1 LT 3
4/5/24
SEC. 27, T12N, R3W, SM
ROBERT COLLES, PE
5/13/24
TH-01
TH-02
TH-01 CHARACTERISTICS REPRESENTED THIS SHEET.
5/13/24
X
X
1
2
3
4
5
4/5/24
4/5/24
4/5/24
4/5/24
4/5/24
0:30
1:00
1:30
2:00
2:30
0:30 18 18" 2 38"
0:30 17 14" 1 12"
0:30 16 11 16" 15 16"
0:30 16 34" 1"
0:30 16 34" 1"
30 6"
4.5 5
12'
N/A
NO
AK BUILT
OL
SM W/
GRAVEL
BOH
Robert Colles, PE
No. CE-163739REGI STEREDPROFES S I O N A L E N GINEER
5/13/2024
TH-03
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP241054, Deb Wockenfuss, 05/23/24
TH
TH
TH
KENDALL & SAMANTHA WILSON
OLSON HEIGHTS, BLK 1 LT 3
4/5/24
SEC. 27, T12N, R3W, SM
4/12/24
TH-02 CHARACTERISTICS REPRESENTED THIS SHEET. PERCOLATION RATE
5/13/24
X
X
AK BUILT ROBERT COLLES, PE
1 4/5/24 - <0:30 DRY -
4.5'
7'
YES
Robert Colles, PE
No. CE-163739REGI STEREDPROFES S I O N A L E N GINEER
5/13/2024
2 4/5/24 - <0:10 DRY -
3 4/5/24 - <0:05 DRY -
<1 6"
3.5 4
FASTER THAN 1 MIN/IN.
OL
SP W/ GRAVEL
BOH
TH-01
TH-02
TH-03
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP241054, Deb Wockenfuss, 05/23/24
TH
TH
TH
KENDALL & SAMANTHA WILSON
OLSON HEIGHTS, BLK 1 LT 3
4/26/24
SEC. 27, T12N, R3W, SM
ROBERT COLLES, PE
4/26/24
TH-01
TH-02
TH-03 CHARACTERISTICS REPRESENTED THIS SHEET. PERCOLATION
X
X
1
2
3
4
5
4/26/24
4/26/24
4/26/24
4/26/24
4/26/24
<1 6"
3.5 4
6'
YES
AK BUILT
OL
GP-GM
BOH
Robert Colles, PE
No. CE-163739REGISTEREDPROFESSIONALE N GINEER
4/26/2024
TH-03
- <0:30 DRY -
- <0:10 DRY -
- 0:07 DRY 6"
- 0:06 DRY 6"
- 0:07 DRY 6"
- 0:07 DRY 6"6 4/26/24
- 0:06 DRY 6"7 4/26/24
RATE IS 0-1 MIN/IN. TEST PIT DUG FOR PERCOLATION DATA ONLY. GROUNDWATER
SEEP NOTED AT BOTTOM OF HOLE. VERIFY GROUNDWATER AT CONSTRUCTION.
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP241054, Deb Wockenfuss, 05/23/24
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP241054, Deb Wockenfuss, 05/23/24