HomeMy WebLinkAboutMUIRWOOD PARK BLK 4 LT 7'0 Muirwood Park Block 4 Lot 7 #011-422-84 Municipality of Anchorage Page 1 of 3 Development Services Department On-Site Water and Wastewater Program 4700 South Bragaw Street P.O. Box 196650 Anchorage. AK 99519-6650 www.cl.anchorage.ak.us (907) 343.7904 ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT Permit Number: SW030068 PID Number: 011-422.84 Crown Pointe Inc. Cro Wastewater System: New Address P.O. Box 112313 Anch. AK 99511 ABSORPTION FIELD Phone N,~ of Bedrooms 5' W ide Trench 345.6277 Five 5 Sou Raung Toni Depth from w9ml Wade LEGAL DESCRIPTION 1.2 GPD/Ft' 9 Ft. B.mk La subd.wvon Depth to ppe boltptn troth W.WnM Wade Gave depth beneath p.pe. 4 7 Muirwood Park 5 Ft. 4 Ft. Tbwnsh.p Range section Ful adoed above ongrwl Wade Dra+e Length 0.1 Ft. 65.5 Fl. QIM,e w.dth. Nuhro d lines Pstanoe between Imes Well: Municipal Water System 5 Ft. 1 FI. Claevl.Uaon 1pnuale. A. S. CI: Total Depth, eawto ptalabwpbW aN F.Pe 1BNl. Ft. Ft. 655 Ftp ASTM 3034 PVC Q.Iler Date Dulled' Stat; W ata Leel inW.W. M—.atabed. Sanders and Sanders 61212003 Ft. yield Puns Set al Cavng Heghl Above OoteW TANK rpm FI. Ft SEPARATION DISTANCES 0 septic ❑ Holding ❑ S.T.E.P. ❑ Other: To Septic Absorption Lift Holding ubhUPnvale hanuvacture,Y' Anchorage Tank 1,500 From Tank Field Station Tank Sewer Line Wel >200' >200' NIA NIA >25' t Stee el uh r d.va,tmenp Two (2) >100' >100' NIA NIA LIFT STATION — NONE ON LOT surllade Wel& Lot Um >5' >10' NIA NIA Da, LMhuT3cmrer >5' >10' N/A NIA Fourbalgn in In m. None Noted Purnp Maks Mode Eleck.ul Inapecbons wimmed or cwl3n Man Re11k'kk BENCH MARK ora w end U,iWIP110" Back Deck Northeast Corner. 100.0 Ft. Engineers Stamp Odk1 V 444 ma" �p ,........ q �i C7 #0 Inspections performed by: A Harala sl Dates: 1 6/2103 49th , t �0 - .`.... 2n 612/03 Department of Health and Human Services approval :..y..)..._ ..... ............... rA 1, UTHAEL E. ANDERSONc,r 0, % No. cE-.set Reviewed and approved by: Date:•��4I��oPESSIaP�•� Municipality of Anchorage DEVEOPMENT SERVICES DEPARTMENT 4700 South Bragaw Street Anchorage, AK. 99519-6655 - 343-7904 On -Site Wastewater Disposal System or Well Inspection Report Permit Number: SW030068 N 89'50112"E 52.82' Page 2 of 3 PID No. 011-422-84 � � MUIRWOOD PARK SUBDIVISION :tso \ LOT 7, BLOCK 4 41,507 S.F I 0 I I I I I � I a \ I I `rte. A B S1 22.025.2 S2 28.9 26.0 \ C14 C4 68.6 26.7 00 M1 62.5 25.5 �'• C5 28.9 55.9 n w I zt 41 � � I I o ~ I 00 o I Altern \ `' M I TH4 z C4 .o C5 I 52 to rn Sl B �' 20' 1 I n I A n I � m A.C. DRIVE o Five Bedroom o I House I I I I n I SP'T Uj o I 64.4'o N 90'00'00"E 167.19' z PLAN AS -BUILT SCALE 1• = 40' Municipality of Anchorage Page 3 of 3 DEVEOPMENT SERVICES DEPARTMENT 4700 South Bragaw Street Anchorage, AK. 99519-6655 - 343-7904 On -Site Wastewater Disposal System or Well Inspection Report Permit Number: SW030068 x-97.5 / N ycum C6 UU UU 1,500 Gatton kptic Tank PID No. 011-422-84 v S Ln U 1- S U PROFILE AS -BUILT - Scale: 1" - 10' • ' MUNICIPALITY OF ANCHORAGE Z Development Services Department On -Site Water & Wastewater Program 4700 South Bragaw Street P.O. Box 196650, Anchorage, AK 99519-6650 (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT Initial Permit Number: SW030068 t,,Legal Description: Muirwood Park Block 4 Lot 7 ' Design Engineer: 0014 Anderson Engineering Owner Name: Crown Pointe, Inc. Owner Address: PO Box 112313 Anchorage , AK 99511 - Date Issued: Apr 08, 2003 Expiration Date: Apr 07, 2004 Parcel ID: 011-422-84 Site Address: PO Box 112313 Lot Size: 41507 SQ. FT. Total Bedrooms: 5 Permit Bedrooms: 5 This permit is for the construction of: ❑✓ Disposal Field ❑✓ Septic Tank ❑ Holding Tank ❑ Privy All construction must be in accordance with: 1. The attached approved design. ❑ Private Well ❑ Water Storage 2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations ( 1BAAC72 ) and Drinking Water Regulations ( 18AAC80 ). 3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. Received By: Issued By: r✓�.,-lam �� Date: 4 -IO -03 6 �1� Date: /,q Municipality of Anchorage Development Services Department Building Safety Division On -Site Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (907) 343-7904 ON-SITE SEWER/WELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. C) 1 ( -qA0_—g `I Permit Number SW 030068 Property owner(s) Crown Pointe Inc. Day phone 345.6277 Mailing address (1) P.O. Box 112313 Anchorage AK 99511 Mailing address (2) Zip Code Legal description (Lot, Block & Sub'd.) Lot 7 Block 4 Muirwood Park Subdivision Legal description (Section, Township & Range) Lot Size 41.507 SF Acres/Sq.Ft. Number of Bedrooms Five (5) THIS APPLICATION IS FOR: Sewer Only ® Well Only ❑ Sewer and Well ❑ Water Storage ❑ Sewer Upgrade ❑ THIS PROPERTY CONTAINS: Hot Tub ❑ Jacuzzi ❑ Swimming Pool ❑ Water Softening Unit ❑ Therapy Pool ❑ I certify that the above information is correct. I further certify that this application is being made for a Single Family Dwelling and is in accordance with applicable Municipal Codes. OL (Signature of property owner or authorized agent) ee' Permit Fees: 400 aiver Fees: Date of Payment: tl- s - 0.3 Date of Payment: Receipt Number: SS' Z $� Receipt Number: (Rev. 12/00) ANDERSON ENGINEERING P.O. BOX 240773; ANCHORAGE, AK 99524 522-7773 522-6779 (FAX) March 28, 2003 Municipality of Anchorage Development Services Department On -Site Water and Wastewater Program 4700 South Bragaw Street Anchorage, AK 99519-6650 Subject: Lot 7, Block 4, Muirwood Park Subdivision Septic System Design and Permit Application Impacts to Adjacent Properties Dear Onsite Services Engineer: The owner of Lot 7, Block 4, Muirwood Park Subdivision intends to construct a five - bedroom home on the lot. We are therefore requesting a permit be issued for the construction of a new septic system to serve the home. The attached Site Plan and backup documentation identify the location and configuration of the new septic system and alternate site and the parameters used in the design. Also identified on the plans are the proposed water service line location, test hole locations and well and septic systems on the surrounding lots. The subdivision is currently served by the Municipal water system. Drainage arrows are also shown and current drainage patterns will be maintained after construction. The test hole placed near the location of the proposed absorption trench indicated clean gravel with varying amounts of silt and a percolation rate of 2.7 minutes per inch. No ground water was found during placement of the test hole and none was noted during the monitoring period. We are therefore proposing to place a new 1,500 -gallon septic tank and a new 63' long by 5' wide by 4' effective depth absorption trench. The total depth of the trench will be 7' below the surface with the distribution pipe at 3' below the surface. Sufficient fill will be placed to prevent freezing of either the septic tank or the absorption trench. The ground surface on the lot slopes as shown on the site plan from south to north at flat to 5% slopes. The absorption trench will be constructed parallel with the slope as much as possible in conformance with Municipal requirements. All components of the new septic system will be constructed a minimum of 100' from any surface water and wells in the area and 10' from the water service line on the lot. If the system is constructed in accordance with our design the following statements apply: The system, if constructed as designed, will have no adverse impact on the wells Lot 7, Block 4, Muirwood Park March 28, 2003 Page Two in the area or those to be constructed in the future. 2. The system, if constructed as designed, will have no adverse impact on existing septic systems in the area or those to be constructed in the future. 3. The system, if constructed as designed, will have no adverse impact on reserve space, either surface or subsurface, on any lots located in the area. 4. The system, if constructed as designed, will have no adverse impact on drainage patterns in the area. The current drainage pattern will be maintained. Sincerely, e Michael E. Anderson, P.E. Attachments 49th ?:.�.._.... 0 WCHAE_ E. ANDE450V•� •i fes.•. Ko. CE -438' ..••'t:�i No. EE -4381 105' 100' N 89'50'12"E 52.82' 5/8" REBAR (TYP PER PLAT) I I— N to i I w Li c a o ~ 0 O N z P v �O 4.1% 50 '00. S • a \ s a 'r,pOo Of �O Alternate Site 63' Lon x 5' Vi e O TH 4 -a K 4' Ef Depth Absorpti n Trenc q 1,50 Gallon 110•tj 26 Septic nk V. N 2d 1 110' x rn 7 A C� FIN. FLR. • • ? ` .' . •. .. vp i EL. - 112• A.C.. DRIVE ' , b rT o FIVE BEDROOM HOME N to 110' x x 110' a w 0 0 o I 0 0 o N 90'00'00"E 167.19' 15 SITE PLAN SCALE 1" = 40' 64.5' z 110' sal` •,., �r-----------------i• 1 ar S7r- ` i 1 •' \.1. �•..1.. .1 1 � � , 11• 1 b , ' 4os3e.Sq. ft: � � 1 0 t• -VACANT', •,i'•;•, ,, S3 vi ¢ , 50 ZOpW L_ 4� t9: ; / 54 \ j X85.2 0 A :c. . SCALE 1,1 .s 213 =100 �. 00 t j ti� e PAM low TH 4045`:';.,'.`:,;.:;'. 00 . 1 CwCIF50.00' :. t` •t` ,'...••' '' .. SS% \ v':::,, t .,.L=Q32.18` , R.— ' ♦ L� : .! ; ' ;•'l :„2 i56l! This � 'Y o ,t� `a' ' :`..: , •: •:•':•� . , t t�t, �: . 1 N90 00:00. VJ 272' 40431'•,Sq:(tl't , i' 57 C 1 4 ... :>Z �'.,:° � ;• i tip OF qC 'it,, is ; ..r TH- 9 r : ,.. 40.398 'sq:rt`, ' i j �o �t c r i f i G7,.•• 11 i;'r i»r• •.. 't- 1r i "t `�'.:TH-10 - • i ' } '• 1 '.WN O�^' 11 7 ��' PIH 0'• 1s t:o SB WOHAE.E ..ANDERSDN••74�ii !.,'ii" NO) r''�/f ; •.$82'49'33'W No. CE-43314 5.9 TA IS Isk lk to ` 1 t; VACANT TW'-B : { w p VACANT40.00l3q:r o 61 ii -•o . . -------- _'.:'�,_._ _ ---- L=31.42' ' °: 4 • ••. i'• .`:\�\\; � `. 1 ----- b.. a. R=20.00 238.5t' t` ` `t N90'00.00 "W 485.0191'(RdcMi) ` '�' `' • :: Kiltir"AiPI `on An LOT 7,- BLOCK 4, MUIRWOOD PARK DESIGN FACTORS: 5 Bedroom House Perc. Rate: 2 - 5 Min./Inch Application Rate: 1.2 GPD/SF SYSTEM REQUIREMENTS: 5' Wide Trench System 1,500 Gallon STEP Tank 4' Drain Field Rock 5 Bedrooms X 150 GPD/1.2 GPD/SF (Application Rate) = 625 SF of Absorption Area 625 SF/5 LF (Width)" .5 (Red. Factor) = 62.5 LF Trench Length Therefore: Construct a 63' Long X 5' Wide Absorption Trench With a 4' Effective Depth. Flow Line Elevation in Trench to be 3' Below Original Ground Surface. Total Depth to be 7' Below Existing Ground. Maintain 10' Separation From Water Service Line on the Lot. Place 2" of Direct Bury Insulation and 2' of Fill Over Absorption Trench or Provide Minimum 3' of Cover to Prevent Freezing. Provide 4' of Cover Over Septic Tank. 2'6" 6" 4'0" Natural Backfill .51011 Geotextile Fabric 4" Perforated PVC (ASTM 3034) Drainfield Rock TYPICAL WIDE TRENCH SECTION (NO SCALE) NOTE: Grade Area Over Trench to Drain Away. Minimum 6' Separation From Bedrock. Minimum 4' Separation From Groundwater. Minimum 100' From Wells in the Area. Minimum 100' Separation From Surface Water or Streams. �>} , 49th ee //r ___1 "M rn F, i. MICH. ANDERSON : •� �C,/ff�.• NO. CE -4381 ••. jr�4,-7ff 1� P� • RO..... It ' 1��,'P%k Municipality of Anchorage Development Services Department/On-Site Water and Wastewater Program 4700 South Bragaw Street, Anchorage, AK 99516-6650 SOILS LOG - PERCOLATION TEST Performed For: White Raven Development Legal Description: Lot 7.Kincaid Park Subdivision SLOPE 1® OG/PT North 2 3 4 + 5 10 11 12 13 14 15 16 17 18 1 GSM Was Groundwater Encountered? If Yes, What Depth? Depth to Water After Monitoring Date: SP South Date Performed: 1/21102 CITE PI AN No S L O None P 2/28102 E Reading Date Gross Time Net Time Depth To Water Net Drop 22 -Jan 2:06 5.25" 2:21 15 9.13" 3.88" 2:22 5.25" Performed By: Alan Harala_ I; Michael E Anderson Certify That This Test 2:37 15 8.75" 3.5" 2:38 - ::Y !'�.• 5.38' 2:53 15 8.82" 3.44" 2:54 5.25" 3:14 15 8.69" 3.44" M/ 9 Bottom of Hole �` "` Perc. Rate: 6 MinJlnch Perc. Hole Diameter:'8" ;.` Test Run Between 5 Ft. and 6 Ft. 1:;: Comments: Test Cavity was Presoaked Prior to Test. Performed By: Alan Harala_ I; Michael E Anderson Certify That This Test Was Performed In Accordance With All State and Miiri'icipal Guidelines In Effect On This Date: 312102' ' - ::Y !'�.• .. 4� icy '. ht ..' ( to r♦ J�' Municipality of Anchorage Development Services Department/On-Site Water and Wastewater Program 4700 South Bragaw Street, Anchorage, AK 99516-6650 SOILS LOG - PERCOLATION TEST Performed For: White Raven Development Date Performed: Legal Description: Int 7_ Kincaid Park Subdivision SLOPE SITE PLAN OG 1 GP/GM TESTHOLE NO.4 4 Some 5 Cobbles 61 Clean 10 11 12 13 14 15 South Was Groundwater Encountered? No S If Yes, What Depth? L SPIGP Depth to Water O After Monitoring None P Date: 2128102 E 314" - 2" Cobbles Perc. Rate < 5 Min./Inch >51% Sand 18 Bottom of 19 Hole Perc. Rate: 2.7 Min./lnch Perc. Hole Diameter: 10" Test Run Between 5 Ft. and 6 Ft. Comments: Test Cavity was Presoaked Prior to Test. Performed By: Alan Harala. I, Michael E_ Anderson Certify That This Test Was Performed In Accordance With All State and Municipal Guidelines In Effect On This Date: 312102 ff J . 49th G: j Wr� •. VC ALL E. ANDERS-ON W i 4o. CE -4381 • r , 1/21/02 X52.82' L= 9.33' R=10.00 Z =32.18'..: =50.00.... `Y 0, 1. . V 4 w TH ^? n-4 ^ : i 41s407 s.tt.: ' t3 0NC • O A G O N 4.. -3 i N I u, t N90'00'00"E v Reading Date Gross Time Net Time Depth To Water Net Drop 22 -Jan 2:48 6" 3:03 15 .12" 6" 3:04 6" 3:14 10 10" 4" 3:15 6" 3:25 10 9.88" 3.88" 3:27 6" 3:37 10 9.81" 3.81" If ON-SITE WASTEWATER DISPOSAL SYSTEM CONSTRUCTION AND MATERIAL SPECIFICATIONS SUBJECT: LOT 7, BLOCK 4, MUIRWOOD PARK SUBDIVISION GENERAL: 1. The scope of this project includes the procurement and placement of a new 1,500 -gallon tank at the location shown on the site plan. Work also includes the construction of a new absorption trench 63' long by 5' wide by 4' effective depth also at the location shown on the Site Plan. The total depth of the trench will be 7' below existing ground and the distribution pipe will be placed at 3' below the surface. All components of the new absorption trench and septic tank must be constructed a minimum of 100' from any surface water in the area and 10' from the water service line on the lot. A minimum of 4' of cover is required over the septic tank and 3' over the absorption trench. In lieu of cover 2" of direct bury insulation and 2' of cover may be placed. 2. Construction shall be in accordance with the approved site plan, design drawings, Municipal Permit with any special provisions or conditions, and all applicable State and Municipal Wastewater Disposal Regulations. 3. The Contractor shall be responsible for obtaining all underground utility locates and for the layout of the septic system and verification of the location of all lot lines. 4. Unless specifically agreed otherwise, the contractor shall be responsible for final grading areas subsequently depressed from soil settling. Property owner shall be responsible for revegetation of affected areas unless specifically agreed otherwise. 5. Contractors installing wastewater disposal systems must be certified by the Municipal Department of Health and Human Services for system installations. Owners installing their own systems must receive prior approval from D.H.H.S. before beginning system installation. SEPTIC TANK INSTALLATION 1. A new 1,500 -gallon septic tank must be procured from a certified septic tank manufacturer if the existing tank is found to be defective. 2. A septic tank is to be constructed by a certified septic tank manufacturer. Construction shall include two 4" cleanouts for pumping access. 3. The septic tank shall be sufficiently bedded to prevent settling or shifting of the tank. 4. All standpipes on the septic tank shall extend a minimum of 12 inches above final grade. 5. Tanks installed without 4' of cover shall have a minimum of 2" of direct burial insulation. ' Lot 7, Block 4, Muirwood Park March 29, 2003 Page 2 of 3 6. A foundation cleanout shall be installed one to four feet from the building foundation. Two cleanouts are required between the tank and the drainfield. 7. Final grading over the tank shall be such that a positive slope exists away from the septic tank. DRAINFIELD CONSTRUCTION: 1. The drainfield shall be constructed to the dimensions shown on the design. The bottom of the trench shall be within 2" of level. 2. Distribution piping must be placed level with perforations down atop a level bed of drainfield rock. Rock should then be placed over the pipe to provide a minimum of 2" of cover. 3. A silt barrier or geotextile fabric must be placed between the drainfield rock and the natural soil backfill. • 4. Monitor tubes must be 4" in diameter and installed at the locations shown on the design. The portion below ground must be perforated. 5. Contractor shall verify the septic tank and drainfield are a minimum 100' away from any private water wells in the area, 150' from a Class "C" Well or 200' from any community well. 6. Direct bury insulation must be placed over the distribution system if less than 3' of backfill depth is available. Finish grade over the trench must be mounded to prevent settlement or depressions. 7. Grade area surrounding the absorption trench to drain away. 8. A minimum 2' of accepting soil is required below the drainfield rock for a 5' wide trench. Contractor shall verify this condition prior to placement of the rock. All pockets of unacceptable materials must be removed and replaced. MATERIAL SPECIFICATIONS: 1. Septic tanks must be constructed by a municipally approved septic tank manufacturer. 2. The following pipe materials are approved for use in septic system installations in the Municipality of Anchorage: Cast Iron (perforated and solid), ASTM D3034 or P.V.C. (perforated and solid), ASTM F810 or H.D.P.E. (perforated, but not solid) and ASTM D2662 or A.B.S. (perforated and solid). 3. Insulation shall be at least 2" thick extruded direct burial polystyrene (Dow Chemical Co. Styrofoam HI or equal). 4. Septic tank inlets and outlets shall be fitted with watertight couplings (Caulder, Fernco, or equal). Lot 7, Block 4, Muirwood Park March 29, 2003 Page 3 of 3 / 5. A p ermeable 9 eotextile fabric (Typar, Mirafi or equal) must be installed between the final drain rock layer and the native soil layer. 6. All drain rock shall be .5" to 2.5" in diameter with less than 3% passing the #200 sieve. INSPECTIONS: Municipal Ordinance requires a minimum of two inspections. These inspections must be conducted under the supervision of a professional engineer registered in the State of Alaska. The first inspection must be conducted after the excavation of trenches, beds or pits and before the installation of any gravel. A septic tank may be set in place, but may not be backfilled. The second inspection must be conducted after the placement of the geotextile fabric, gravel, distribution piping, standpipes, cleanouts and insulation. No backfill should be in place at the time of inspection. Contractor and notes for use nllprepaaing the rovide a certifieall d asI buil of thle comple ed system.construction Municipality of Anchorage • Development Services Department Building Safety Division On -Site Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (907) 343-7904 CERTIFICATE OF HEALTH AUTHORITY APPROVAL FOR A SINGLE FAMILY DWELLING Parcell.D. 11.422.84 HAA# //ff D3o&oq Expiration Date: 1. GENERAL INFORMATION Complete legal descriptiori Lot 7, Block 4, Muirwood Park Subdivision Location (site address or directions) Park West Circle Current Property owner(s) Crown Pointe, Inc. Day phone 345.6277 Mailing address Lending agency Mailing address Real Estate Agent Mailing.Address . 2- P.O. Box 112313P.O. Box 112313 Anchora�e,AK 99511AK 99511 Unless otherwise requested, HAA will be held by DSD for pickup. 2. NUMBER OF BEDROOMS: 3. TYPE OF WATER SUPPLY: Individual Well Individual Water Storage Community Class Well Public Water System Five 5 Day phone Day phone TYPE OF WASTEWATER DISPOSAL: ❑ Individual On-site ❑ Individual Holding tank ❑ ❑ Community On-site ❑ ® Public Sewer ❑ The Municipality of Anchorage Development Services Department (DSD) Issues Certificates of Health Authority Approval (NAA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. Certificates of Health Authority Approval are required for the transfer of title (except between spouses) for properties served by a single family on-site wastewater disposal and/or water supply system. DSD also issues HAAs upon request to homeowners. Certificates of Health Authority Approval are valid for 90 days from the date of issue for properties served by a private or Class C well and may be reissued with new water sample results less than 30 days old. (Certificates may be reissued for a period of up to one year with valid water samples.) Certificates are valid for one year foi properties served by Class A or B wells or a public water system. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 4. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Health Authority Approval Guidelines for this application, shows that the on- site water supply and/or wastewater disposal system is(are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm Anderson Engineering Phone 522.7773 Address P 0 Box 240773 Anchorage AK 99524 Engineer's Printed Name Michael E. Anderson, P.E. Date 12/212003 4 .., W /i* NICNA0. E. ANDERSON •;i r 5. DSD SIGNATURE ,��' NO. CE -381 Approved for _� bedrooms. ��,;5;.•• Disapproved. Conditional approval for bedrooms, with the following stipulations: Additional Comments f ON-SITE cc: • • "rr li�_1rf1: WASTEWATER S. o•• /1111)1111 Attachments: HAA Checklist Septic System Advisory Well Flow Advisory X Maintenance Agreements Supplemental Engineer's Report Other By: Original Certificate Date: (Rev. 12/00) ............ . . T .................... . _ - ., _� , .�_� ._........ it Municipality of Anchorage .•. • '"' Development Services Department ;{' } °; O Building Safety Division On -Site Water & Wastewater Program j 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (907) 343-7904 j HEALTH AUTHORITY APPROVAL CHECKLIST Legal Description: Lot 7. Block 4, Muirwood Park Subdivision Parcel ID: 011.422.84 A. WELL DATA Well type If A, B, or C provide PWSID # Well Log (Y/N) Date completed _ Sanitary seal (Y/N) _ Wires properly protected (Y/N) I„ 'I Total idepth ft. Cased to ft. Casing height (above ground) in. FROM WELL LOG AT INSPECTION Date of test Static water level ft. I ft Well production g.p.m. g.p.m. WATER SAMPLE RESULTS: Ii Coliform colonies/100 ml. Nitrate mg./I. Other bacteria colonies/100 ml. Date of sample: " Collected by B. SEPTIC/HOLDING TANK DATA i Tank Type/Material SepticlSteel Date installed 61212003 Tank'size 1 1.500 gal. Number of Compartments 2 Cleanouts (YIN) Y I. Foundation cleanout (Y/N) Y r'', Depression over tank (Y/N) N High water alarm (YIN) N Date of pumping Pumper New Construction I C. ABSORPTION FIELD DATA I Date installed 6/212003 Soil rating (g.p.d./ft2 or ft2/bdrm)1.2 GPDISF System type 5' Wide Trench Length 65.5 ft. ; Width 5 ft. Gravel below pipe 4 ft. Total depth 9 ft. Eff. absorption area 655 ft2 Monitoring i tube Y Depression over field N Date of adequacy test Results (Pass/Fail) For _ bedrooms j Fluid'depth In absorption field before test _ in. Water added_ gal. j New depth_ in. Elapsed Time: _ min. j ',Final fluid depth _ in. Absorption rate >= g.p.d. Any rejuvenation treatment (past 12 mo.) (YIN & type) N i If yes, give date D. LIFT STATION Date installed "Pump on" level at _ in. Datum E. SEPARATION DISTANCES Size in gallons "Pump off" level at _ in Cycles tested SEPARATION DISTANCES FROM WELL ON LOT TO: Manhole/Access (Y/N) High water alarm level at Meets alarm & circuit requirements? Septic tank/lift station on lot N/A On adjacent lots NIA Absorption field on lot NIA On adjacent lots NIA Public sewer main NIA Public sewer manhole/cleanout NIA Sewer /septic service line NIA Holding tank NIA SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Building foundation >5' Property line >5' Absorption field >5' Water main >10' Water service line >10' Surface water >100' Wells on adjacent lots >200' SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: i Property line >10' Building foundation >10' Water main >10' Water Service line >10' Surface water >100' Driveway, parking/vehicle storage >5' Curtain drain None Noted Wells on adjacent lots >200' F. COMMENTS i G. ENGINEERS CERTIFICATION ++`Q ,..• ♦ ♦♦ review of at I have determined through field inspections and :♦♦♦ certify ■ 49th Municipal records that the above systems are in ■•••• �' conformance with MOA HAA guidelines in effect on this date. i�.............. MICHAEL E.• ANDERSON, Engineer's Printed Name Michael E. Anderson, P.E.♦� s'•., No. CE -4381 .• Date 121212003 ♦♦♦♦���� •++ HAA Fee $ ''c3'I 5 Waiver Fee $ Date of Payment 17- 0�3 Date of Payment Receipt Number Receipt Number (Rev. 12100) i in.