HomeMy WebLinkAboutPARK HILLS #1 BLK 2 LT 11Park Hills #1 Block 2 Lot 11 #017-112-59 Municipality of Anchorage On -Site Water and Wastewater Section - (907) 343-7904 Page 1 of 3 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP191252 PID Number: 017-112-59 Dwelling: FE -1 Single Family (SF) El with ADU El Duplex (D) El Two Single Family Project: 1771 New 11K Upgrade Name TAMMY COOPER ABSORPTION FIELD 1771 Deep Trench El Wide Trench El Bed E> ound Site Address 14727 PARK HILLS *ANCHORAGE, AK El Other Ze Phone Number of Bedrooms Soil Rating depth f original grade 14 GPD/SF ITotal Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade Ft. Gravel depth beneath pipe Ft. Subdivision Block Lot PARK HILLS #1; BLOCK 2, LOT 11 Fill added above original gr Ft., Gravel length Ft. Township Range Section Gravel width Ft. Beds: Number of Lines Distance between lines Ft. SEPARATION DISTANCES ToSeptic Absorption Lift Station Holding SewerTotal a rption area Number of trenches Dist. between trenches From Tank Field Tank Line Ft2 Ft. Well 100,+ TANK ®❑ Septic El S.T.E.P. El Holding El Other Manufacturer INFILTRATOR Capacity 1530 Gal. Surface Water 100,+ 000, Material Number of compartments Lot Line 51+ NA HDPE 2 Fou Foundation 10,+ LIFT STATION Manufacturer Capacity Remarks OLD TANK DECOMMISSIONED PER Gal. UPC PER CONTRACTOR Alarm location Electrical installed by PIPE MATERIAL House to tank D3034 dTankto rainfleidD3034 Installer ARM SEPTIC SERVICES Drainfield EXISTING CO/MTD3034 inspector TIM ECKLUND AND DAVID GARNESS BENCH MARK (Assumed elevation) 100.00 ft Inspection 15, 7/30/2019 Location and description dates: 2 nd TOP OF GARAGE SLAB 31d - 4'h ON-SITE WATER AND WASTEWATER SECTION APPROVAL Engineer's Ptamp Conditional Approval: Date wry �0 C)4 T ...... ......... .......... ....... Ile f ��!e A. or s S,** CE —.7953 Septic System Approved Date 0 00), Note: this approval does not include well permit requirements. Dr 0 fesslo #AECC864 1-cev uoluz/ 10) PERMIT NUMBER: OSP191252 WELL RADAII AND LOT LINE WAS NOT FLAGGED DURING CONSTRUCTION; RECORD DRAWING PARCEL INUMBER: 017-111 2-59 APPROXIMATE LOCATION OF EXISITNG \ DRAINFIELD PER MOA RECORDS DBL3&4 \ NEW IM -1530 INFILTRATOR SEPTIC TANK Nll\NOUT FOR DRAIN AROUND TANK; APPROXIMATELY 10' OF H DRAINAGE SOCK CONVERTS TO SOLID D3034 13 FEET FROM S _ DRAINFIELD. ELEVATION OF SOCK DRAIN IS AT MIDLINE OF TANK / AS REQUESTED BY THE MOA ONSITE DEPARTMENT. SEE / ATTACHED TEXT FROM NATHANIEL AT ARM SERVICES. DRAIN — LOCATION AND PLACEMENT WAS DISCUSSED WITH THE MOA _ ONSITE DEPARTMENT EMPLOYEE REBECCA CARROLL, P.E. �—APPROXIMATE DBL2 DURING INSPECTION ON 79.9 MH 72.5 84.1 ST1 81.9 92.7 DBL3 84.8 FCO PER AS BUILT SURVEY (ATTACHED) DBL4 1 OUTFALL LOCATION PER ` :,• i- A \ CONTRACTOR; SEE ATTACHED IMAGE • :� _ �+ DRIVEWAY a " .� ''a:� .a.a.�.,• EXISTING ' •.. BEDROOM HOUSE I B ' I DBL1 67.1 78.9 DBL2 68.1 79.9 MH 72.5 84.1 ST1 81.9 92.7 DBL3 84.8 95.3 DBL4 1 85.9 1 96.3 O z z �OwS w w W. 0 w w W W r \ / / N / 20' TELE & ELEC. EASEMENT PARK HILLS; TRACT B a )' Neilkll:lm 1.4 10 leckwil a 149 10 3701 E. TUDOR ROAD, SUITE 101 -ANCHORAGE, AK 99507 • PHONE (907) 337-6179 -FAX (907)338-3246 - WEBSITE:, PREPARED FOR: PHONE NUMBER: TAMMY COOPER - LEGAL DESCRIPTION: PARK HILLS #1; BLOCK 2, LOT 11 TYPE OF WORK: I, SEPTIC TANK RECORD DRAWING SITE PLAN PAGE NUMBER: 2OF3 DRAWN BY: D.J.G. DATE: 5/19/2020 1"=40' Not OF AV ♦ Ar All 44. 4. 4. . 000 0 1 rey A. Gariess 4,r 4. ♦AN, •.,,s,. LICENSE I.. `ss •• #AECC884 / PERMIT NUMBER: PARCEL ID NUMBER: OSP191252 RECORD DRAWING 017-112-59 TOP OF TANK AT INLET = 91.64 INVERT OF BUNG AT INLET = 91.02 m INSULATION PER CONTRACTOR IM -1530 2 -COMPARTMENT INFILTRATOR SEPTIC TANK ST1 FINAL GRADE = 94.83-95.17 GA"MN'r-"JSS'jr"-JNGIN'I'PlJE"KING GROUP, Ltd ENGINEERING , SALES , CONSULTING.. . .. .. 3701E TUDOR ROAD, SUITE 101 *ANCHORAGE, AK 99507 -PHONE (907)337-6179 -FAX (907)338-3246 -VVESSITE:games s,ng� , n-nng.com PREPARED FOR: NE E NUMBER: TAMMY COOPER T_O NUMBER: PAG30F3 LEGAL DESCRIPTION: DRAWN BY: PARK HILLS #1; BLOCK 2, LOT 11 D.J.G. TYPE OF WORK: DATE: I,, SEPTIC SYSTEM RECORD DRAWINGS 8/19/2019 — TOP OF TANK AT OUTLET = 91.52 INVERT OF BUNG AT OUTLET = 90,67 ....... ... I.. . .. ....... 0 .. . ....... ....... .. . 0 . 0 0 0 �-;o # C) ........... ............ . .n_ ey Ga ess 14�)_a Aw 'w # c -7 3 �Air LICEN • "R0lwlw #AECC8 44 luaSlk .o AT&T ^ 10:37 AM L• 0 96% ti> Here's what it looked like. The red is sock hose, the green is d3034. There is a 45 at the Ela transition, sock hose is A'Oi.ct approximately 10ft long./000"�� Distance from edge of df to edge of drain (rock and pipe) is greater than 10ft, approximately 13ft. riMessage • ID O A D v v � �O Z X m rrn v -, r- rn O A 0 s-�,> 00 Dz AO m Ci O m X v cn V i 1, Z I � w 0 'n �rn � w OzD ,i�'7 cn M 0 f ren 0 (n m r O n O O -C A r- M j v 0 z zZC= o-n>z r- M L) v 0 M -q o 0 1 I s', l 4 f s - ..ZOL _ ' � � o• 1. . � �' rna� D. m A A D v v � �O Z X m rrn v -, r- rn O A 0 s-�,> 00 Dz AO m Ci O m X v cn V i 1, Z I � w 0 'n �rn � w OzD ,i�'7 cn M 0 f ren 0 (n m r O n O O -C A r- M j v 0 z zZC= o-n>z r- M L) v 0 M -q o 0 1 I �% tOT 11 SEPTIC `NNF 8C 36A' 36-4' C4GEYQ: 5fr-TIC STANDPIPE j C=�Nrr-,�?7 #CO –0 VW ER WELL Ft"'cE—X—X— V 1Y LOT 12 SY� Q � J ' 4-0' E ISTtNG HOUSE 51.5' �'y -'-"-2ff HOUSE DETAIL EE = 0' 250H 5[reet Aochorape. Aaska 99501 survey Dapanment Phcmz:5614-SZ91 MaW ne inc Phone: 243-gSi:95 Cci€Lic t !2r {t AECC 668 ORDERED BY: ROB CAr%4PBELl,ARM Sir1'tV:CES 313.1' LEGAL DESCRIPTION: AOS -BUILT LOQ E 1, BLOCK 2, PARI[ HILLS SUBDIVISION ADDITION NO. I DRAWN GATS: 5115'2020 'W-GRKORDEF: `P1+yi$2-196 2w,21,, DRAWN 8Y: AP�.-- CHECKED BY: - SC vWGRsD: _ SW3337 SCALE- V. - 40' — FRfPiS: 81 7r26 REF- 20Ni?5 413 94.4?------ 0 4.4?------ 2D` 7ELEC0',•}••M- & ELECTRIC EA EMEN i TRACT S 0<w U Lu Lu y QD N W LO r^ Lu v ,'� 49TH*'' tl r -LS-12034 ��3fog5§4i!ri1 �"a NO E; T1? S ORNA9i'! G SHALL NOT BE MODI RED FOR USE ASA }LOT PL .N WITHOUTTHE EXPUSSED W,RII IT kk! CONSTNLT 0�7 LC LAN TECH - ADDRESS, 14727 PAR: HILLSCIR. PARCEL.: Gel -1`2 -SS 5 1R'r"KV C-t-k7IFICA'ION: L COL.Wi EC'r.. INC HAC-. NDUL. E.7 A P% -HSI 7,u4:EY Or -1=E 5 ROVERTr R5 DPAV4L? ASCCERTVRES ?['AT HE ❑.fPR^'rEi�s ! 145 S1TJ--T,.v :HEREON MY ;S'STI-1- TFsE PRGFER n' ONES AIN a '4 E NICRO 5CHME T5 EXIST 0 THE-q'F--A.N NO -,G `.LUSKI ABY ?i'u TE: IT I5 TAF GVMEPS €SPO SI iLI v TO D. Ev,--iNc ?F'E-EXISTE";CE OF AW E,iIENi _Y+n, COVENLAh'YS. Fl:-5Ti2lcs Io -is GR RIUk-L-O: -sJ,34 T L.'SGS WHICH DO %.0' APPEAR ON –.rcl RECORDED "JO "IS'1510ti %-A.T 11.1DERLNG CIP.ClUmSTA N', S SNCiu.._ A' DATA F} REON RE JSED FOR i�?��: c3;Csa4i'�.?OR ESTn6L§5� M- PRO?E.M L 111!Fs O rG•R PLOT -PLAN PURPCFSES. �,J"i FACilr OF MUNICIPALITY OF ANCHORAGE � \ On-Site Water&Wastewater Program S;� Ir IPO Box 196650 4700 Elmore Road gjk / Anchorage,Alaska 99519-6650 Phone:(907)343-7904 Fax:(907)343-7997 r. ' " J httpa/www.muni.org/onsite , „.7 / Department NN-HOapVE On-Site Wastewater Disposal System Permit Permit Number: OSP191252 Effective Date: 6/26/2019 Work Type: SepticTank Upgrade Expiration Date: 6/25/2020 Tax Code Number: 01711259000 Site Legal Address: PARK HILLS#1 BLK 2 LT 11 G:3137 Site Mailing Address: 14727 PARK HILLS CIR, Anchorage Owner: COOPER LAWRENCE J &TAMMY L Lot Size in Sq Ft: 63339 Design Engineer: GARNESS ENGINEERING GROUP LTD Total Bedrooms: 4 This permit is for the construction of: ❑ Disposal Field El Septic Tank 0 Holding Tank 0 Privy 0 Private Well 0 Water Storage All construction shall be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80) 3. The wastewater code requires inspections during the installation. The engineer shall notify the Development Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather shall be either: a. Opened and Closed on the same day, or b. Covered, sealed, and heated to prevent freezing Special Provisions: If a subsurface drain is installed to lower the groundwater around the tank it is to meet all required separations. Show the location on the asbuilt drawing. • 48 Received By: Date: 61 (9. Issued By: i�_ . / Date: ♦ Z 13 MUNICIPALITY OF ANCH •� '°'�� O ' •T � • ., fr� Community Development Department // 'hone: 907-343-7•b4 Development Services r` Fax: 907- 343-7997 On-Site Water& Wastewater Program `<< �, Mayor Dan Sullivan 0! 410; L On-Site Sewer/Well Permit Application For A Single Family Dwelling Parcel I.D. 017-112-59 Property owner(s) TAMMY COOPER Day phone Mailing address 14727 PARK HILLS"ANCHORAGE.AK 99516 Site address 14727 PARK HILLS*ANCHORAGE,AK 99516 Legal description (Sub'd, Block & Lot) PARK HILLS#1; BLOCK 2. LOT 11 Legal description (Township, Section & Range) Lot Size Sq.Ft. Number of Bedrooms 4 APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DEWELLING: (®all that apply) Initial ❑ Single Family (SF) Absorption Field ❑ Upgrade (w/wo ADU) Septic Tank ® Duplex(D) ❑ Renewal ❑ Holding Tank Multiple Dwellings ❑ Privy 7 (SF and/or D) Private Well Water Storage n THIS APPLICATION INCLUDES A VARIANCE/WAIVER REQUEST FOR: N/A Distance: - I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal codes. GARNESS ENGINEERING GROUP, Ltd. (Signature of property owner or authorized agent) Permit/Rush Fees: latqlq Waiver Fees: A25Date of Payment: n a5 Date of Payment: Receipt Number: 09,145136 Receipt Number: Permit No. (35P1c119159 19159 Waiver No. (Rev.01/11) Quanics GARNESS ENGINEERING GROUP, Ltd Advanced TV ENGINEERING SALES CONSULTING Dealer June 19m, 2019 Municipality of Anchorage Development Service Department On-Site Water & Wastewater Program 4700 Elmore Road Anchorage, AK 99507 Ref: Proposed Septic Tank Upgrade for Park Hills #1; Block 2, Lot 11 To whom it may concern: The subject lot is served by a private well and a private septic system. Per our client (ARM Services), the existing premier plastic septic tank is in a state of failure and must be replaced. We are proposing to decommission the existing septic tank per UPC and install a new IM-1530 Infiltrator HDPE septic tank. See attached design drawings for tank location and other MOA requirements. We are unaware of any adverse impacts this installation would have on adjacent wells or septic systems. If you have any questions, please contact us at 337-6179. Thank you for your assistance. racer:ly, Jeffre A a e P> ., M.S. Presi. -n 3701 East Tudor Road, Suite 101 *Anchorage,Alaska 99507-1259 Phone: (907)337-6179*Fax: (907)338-3246*Website: www.garnessengineering.com . / / / GEG,Ltd.HAS AN 8 PAGE SPECIFICATION LETTER PER MOA RECORDS,THE GROUNDWATER IN THE TESTHOLE WAS THAT PERTAINS TO THIS DESIGN.BY PROCEEDING APPROXIMATELY 8.5 FEET BELOW GRADE.DURING THE INSTALLATION NOTE:THE CONTRACTOR SHALL FORWARD WITH THIS INSTALLATION,THE OF THE PROPOSED SEPTIC TANK,IF GROUNDWATER IS FOUND TO BE HAVE THE NORTH LOT LINE,AND ALL ENGINEER,WELL DRILLER,CONTRACTOR AND HIGHER THAN THE INVERT OF THE OUTLET LINE,A DRAIN WILL BE WELL RADII FLAGGED BY A PROPERTY OWNER AGREE THAT THEY HAVE INSTALLED AROUND THE HDPE TANK.THE PROPOSED DRAIN MUST BE A REGISTERED LAND SURVEYOR READ THESE SPECIFICATIONS AND AGREE TO \ MINIMUM OF 10 FEET FROM THE EXISTING DRAINFIELD PRIOR TO CONSTRUCTION. /ACCEPT THE TERMS AND CONDITIONS OUTLINED. I ASSUMED LOCATION OF DRAINFIELD PER SEPTIC CLEANOUTS ON SURVEY AND MOA RECORDS S PARK HILLS#1;BLOCK 2,LOT 10 \ •:;+. .. EXISTING SEPTIC TANK TO BE DECOMMISSIONED PER UPC;PROPOSED TWO COMPARTMENT 1530 INFILTRATOR SEPTIC TANK;INSTALL DOUBLE • • CLEANOUTS BEFORE AND AFTER - r ••;----.: . // FCO PER MOA .•.••' • RECORD DRAWINGS / • ' /X \ \�\ / / N ..•' \ / / •'• .... •. / •••••• \ :.: • .c.: / \ •,. ./• •• r.-!:.'.:•i.•t• ��' PARK HILLS#1;BLOCK 2,LOT 12 • ••• • �• 41 DRIVEWAYt•'i••bi•••• • I I 1 I I 100'WELL RADIUS I 1 ....„„,....../"_,, EXISTING 4 '''-i---_....... BEDROOM HOUSE I 100' ELL RADIUS I I j .. 1 I i I I c\I 1 \\ / SLE: / 0 \ \ / 1"=40' \ \ / \ ‘ ��•'," '11,1 - ../ to ...,N.. A Ar---// i ,i, ".... .• GARNESS ENGINEERING GROUP, Ltd fI( ENGINEERING 'SALES CONSULTING 0 /I•� 3 • • 701 E.TUDOR ROAD,SUITE 101•ANCHORAGE,AK 99507•PHONE(907)337.6179•FAX(907)338-3246.WEBSITE:wwwrn.gamessengirbering.co ••• PREPARED FOR: PHONE NUMBER: PAGE NUMBER: 0 Cn •; -, " - •- S " TAMMY COOPER 907-688-9433 (ARM) 2 OF 2 ••61 '/ C 79 3 .' a PROJECT/LEGAL DESCRIPTION: DRAWN BY: .�l•••• 6 ( f= PARK HILLS#1; BLOCK 2, LOT 11 D.J.G. �1 ♦ •'••• 9•0'�•�,4•4 TYPE OF WORK: DATE: •♦11rnF`S`; ns,•• DESIGN OF SEPTIC TANK UPGRADE 6/19/2019 LICENSE 11 Municipality of Anchorage Page of 3 DEPARTMENT OF HEALTH AND HUMAN SERVICES ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 0 Anchorage, Alaska 99519-6650 • Telephone: 343-4744 On -Site Wastewater Disposal System and/or Well Inspection Report Permit Number: -S k/ 980 y g0 PID Number: o17 -//a -S9 Name: / 6EOR6ic 3 dleee✓ Adp,,Jes Wastewater System: D New N1 Upgrade Address: 1q,-71-7 pfjee Nlus C/Kec� ABSORPTION FIELD Nc R - / - v Y� Phone:, / & •l No. of Bedrooms'. ❑Deep Trench ❑Shallow Trench 6. Bed ❑Mound O Other LEGAL DESCRIPTION Soil Rating: 60 Total Depth froyym inal grade: v GPD/ . Ft. d,Vorig Lot: Block: Subdivision: Depth to pipe bosom fmm original grade: Gravel depth beneath pipe / L(S / a Ft. 01-1 Ft. Township: Range: Section: Fill added above original grade: S Gravel length: 62 _/ • Ft. Ft. WELL: ❑New ❑ Upgrade Gravel width: c Number of lines: Distance be wan litres: 1 S J Ft. 33 7• Ft. Classification (Private. A,B,C): Total Cased To: Total absorption area: Pipe materiI: P a1E r fSTrNG Ft. Ft. /D S SQ.Ft. /M %3O F&/0 Driller: Date Drilled: Static Water Level: Installer: Date installed: Ft. \\ Viela'. Pump Set at: Casing Height Above Ground'. TANK GPM Ft. Ft. SEPARATION DISTANCES ® Septic ❑ Holding O S.T.E.P. To septic Absorption Lift Homing PubliciPrivate Manufacturer:Capacity in gallons: From Tank Field Station Tank Sewer lines t1j C M / 3 0 WeIF10L) -t QL/�� --- — 0).5 i- Material: _ 1-1 ��c Y r//)// Number of Compartments: 111 Surface LIFT STATION Water 0 i 0o/t Lot // Size in gallons: Manufacturer: Line Foundation (L /_ / / 9s, 'Pump on" level at: "P ' level at: High water alarm at. Curtain /%/ //// Pump Ma odel Electrical Inspections performed by: Drain /JOKE f.VAI -' Remarks: Ex,sr,,(. Steve.-IIL r.4 -K BENCHMARK Location and Description: ls�r+Pk4 G,Qv (1�4Q . �.,rt7 .9a /� M = i CO c -T �A•: AN O4Nra.0 rt.y.ISTIrf. Lh.;�r�:-fr¢,,n )�� G.ARne..E r/q.a.� .^e•r,..r A. Assumed Elevation: T /iftiC-1•l AB gvDa�24 P�/L r•a e,.s..,r Liy /GiPt 1 6FliL GRaw cli tr4 GrervNo t.•,d rot .: i �t ., •• .,, S '+ P✓ac.4.0 VIVOCA 5CW401 Aar.K Pill A, L4.vEl,r�vC ,ry�f1 111 S d S ENGINEERING Inspections performed by: 17034 Eagle Riyer Leen R,,A Me s: 1st -C. Eagle River, Alaska 99577 2nd-/ - /a - 99 I -P ROBERT r '7or COWAN7,4v,- elf i IV -J% 1'c.'` CE•8801 w Department of Health and Human Services approval It'i` F;;. Reviewed and approved by: Date: ]2-013 (flee. 9/91) MOA 25 SW980480 PAGE 2 OF 3 Municipalit of Anchorage DEPARTMENT OF HEALTH AND HUMAN SERVICES ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 Anchorage, Alaska 99519-6650 • Tele hone 343-4744 ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT LEGAL LOT 11, BLOCK 2, PARK HILLS #1 CNEW OED O2 WELL - 20' TELEPHONE TRACT B 4 NEW 1300 GAL. P WELL P.I.D. NO. 017-112-59 E TANK PROP WELL FCO EASEMENT SCALE 1- - 40' 31A'�t�e�RFs7 p ROBERT C. COWAN �C ' CE -8801 PAGE 3 OF 3 Municipalit of Anchora e DEPARTMENT OF HEALTH AND HUMAN SERVICES ENVIRONMENTAL SERVICES DIVISION P.D. Box 196650 Anchorage, Alaska 99519-6650 • Tele hone: 343-4744 ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT LEGAL LOT 11. BLOCK 2, PARK HILLS #I1 P.I.D. NO. 017-112-59 95.6' FC 14.5' 19.5' % ST1 80.0' 139 - 5T2 STI sTz 140.5' - DBL1 85.0' 141.5' - DBL FINAL GRADE 142.0' - C01 101.0' !/ MT1 105.5' 154.5' - CO2 160.5' .._ „ . 191.0 - NEW 91.3' 300 GAL 91.1' S.T. MT 159.5' 94'1 11T2CO1 CO2 MTI 93.0' Qe 9 g.� 2' INSULATION 90.5' SEWER ROCK 89.8' 90.4' 89.9' 15' 84.3' WATER FOUND N. T. S. 79.3' BOH ENGIg4! � 1(P OF 2 * l ROBERT C. COWAN f Q pct CE -8801 �4 til%`,""i ;rye - ST1 80.0' 139 - 5T2 83.0' 140.5' - DBL1 85.0' 141.5' - DBL 86.5' 142.0' - C01 101.0' 145. ' MT1 105.5' 154.5' - CO2 160.5' 196. - 191.0 - Cpm MUNICIPALITY OF ANCHORAGE Department of Health and Human Services On -Site Services Program 825 L Street, Room 502 P.O. Box 196650, Anchorage, AK 99519-6650 (907) 343-4744 ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT Upgrade Permit Number: SW980480 Legal Description: PARK HILLS #1 BLK 2 LT 11 (,\Ccy-\ Date Issued: Dec 30, 1998 Expiration Date: Dec 30, 1999 Parcel ID: 017-112-59 Design Engineer: 0003 S & S Engineering Site Address: 014727 PARK HILLS CIR Owner Name: Georgie & Jerry Barnes Lot Size: 63339 SQ. FT. Owner Address: 14727 Park Hills Circle Total Bedrooms: 4 Permit Bedrooms: 4 Anchorage , AK 99516-4246 This permit is for the construction of: LSI Disposal Field [✓] Septic Tank L Holding Tank LI Privy ❑ Private Well ❑ Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations ( 18AAC80 ). 3. The engineer must notify DHHS at least 2 hours prior to each inspection. Provide notification by calling (907) 343-4744 ( 24 hours ). ( Not required for a Water Supply Permit only ). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. 5. The following special provisions. Vertical separation between existing absorption field and groundwater must be verified to be a minimum of 4' to keep the trench in service. Received By: Date: I } / ' 9 g Issued By: Date:/ 2 _90.9e s&s\ lineeRing ROBERT C. COWAN, P.E. CIVIL ENGINEERS (907)694-2979 FAX(907)694-1211 December 15, 1998 HEALTHAUTHOPoTY APPROVALS MUNICIPALITY OF ANCHORAGE Department of Health and Human Services P.O. Box 196650 SEWER&WATER Anchorage, AK. 99519 MAIN EXTENSIONS REFERENCE: Lot 11, Block 2, Park Hills #1 Subdivison SEWER&WATER INSPECTION Request you issue a permit to install a septic system to serve the four bedroom dwelling on the referenced property ENGINEERING STUDIES A test hole was excavated and percolation test performed. The approximate location of ANDREPORTS the test hole is located on the attached site plan. At the time of excavation 12/12/98 water was found at 8.5'. After seven days of ground WELLINSPECTION water monitoring the water level was at & FLOW TEST We do not anticipate any adverse effects on neighboring wells, septic systems, reserve areas or drainage patterns by the installation of the proposed septic system. The SITE PIANS construction of this system will not prevent any future development on any of the adjacent properties. ROAD DESIGN If you require additional information, please contact us. Sincerely, BORTEST / Robert C. Cowan, P.E. PERCOLATION RCC/rdp TEST Enclosure STRUCTURAL& MECHANICAL INSPECTIONS ONSITE WASTEWATER DISPOSAL SYSTEM DESIGN 17034 NORTH EAGLE RIVER LOOP • SUITE 204 • EAGLE RIVER, ALASKA 99577 EG" LOT 11, BLOCK 2, PARK HILLS S41) #1 ORARM W: ECKEO W. GATE: SHEET: 0;: A/ R.D.P. r R.C.C. 12-15-98 1 OF .!�E.................. • ... • • is,�1, STRUCTURES. EASEMENTS, OR ENCROACHMENTS ,:'1,�/f"'••`.% dA Engineering DESIGN CRITERIA: I SHOWN ON THIS SITE PLAN ARE AS SHOWN ON✓ iTL'P ✓,.» .. . 4 BDRM = 600 GPD AN AS-BUILT SURVEY DRAWN BY: A SOILS = 0.6 GPD/SO.fT. GERALD V. RANDALL JR. AA .. / IT IS THE RESPONSIBILTY OF THE CONTRACTOR 'I 600 0.6 = 100d SQ.FT. REQ"D. A ROBERT C. COWAN f TO VERIFY EASEMENTS, REOUIREO SEPARATION At,''p'S C r / /{v a 17034 EAGLE RIVER LOOP READ DISTANCES, AND PROPERTY LINES PRIOR TO +•+t`r�y EAGLE RIVER, 7)694 29777 LOT 17 / V CONSTRUCTION. ' -., PHONE/ (,ALASKA 9979 ..,.. FAXj (907)694-1111 IOo' H WELL ELL RADTU3 Q' _ . EXISTING TRENCH CONTRACTOR IS REQUIRED TO BED CRITERIA " OBTAIN UTILITY LOCATES G MT EXISTING 1250 GAL SEPTIC TANK ARK TO ANY EXCAVATION 2.5' DEEP i / (TO BE PUMPED, CRUSHED AND ABANDONED) t 1' M.O.A. APPR. SAND 5 DIVERTER VALVE Z 0.5 EFFECTIVE y O PROPOSED 1250 GAL. SEPTIC TANK N 15' WIDE / w 67' LONG CO K ,o O ROPOSED BED MT. 0, LOT 10 A TH AE,P 'Sf, Co ' I C YT INSTALL @BJ DBL CO (PROPOSED d� WELL Z CL LOT 12 �c^� w p 1p0 In 4� lreu. 1fE1.Lq �o 0 LOT 13 C m I I O ILO J II v �- - - 20' TELEPHONE k ELECTRICAL EASEMENT ALL PORTIONS OF SYSTEM THE EAC'NEER NAY VARY THE 11117H LESS THAN 3.5' OF EXACT GIMENSgNS ANA 0ESGN COVER REQUIRE INSULATION. TRACT B NES To MEEEETFSTTEE' iE c F`0Ns. T 11, BLOCK 2 PARK HILLS S D #1 CHECKED Bv: MIE: SHEET: Z.D.P. R.C.C. 12-15-98 2 OF 2 I7 N EAW WEA ILD► DMD CO MT J F MOUND SLOPE W TO EXCEED 3:1 0 v; z FINAL GRADE 4' Dill BCH 40 PVC 7 ** LXVKM. BARD SIDE VIEW 67' X 15' BED SYSTEM �o ROBERT C. COWAN i `Y f �g CE -8801 s 4" PERFORATED MONITOR PIPE 4" SOLID CLEANOUT PIPE MOUND SLOPE NOT �TO EXCEED 3:1 �owciRAi. GRADE 0.5 4• RRl TO GROUND WATER moi? -rs�h Municipality of Anchorage DEPARTMENT OF HEALTH &HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG - PERCOLATION TEST PERFORMED FOR: D `iRQi BARNS DATE PERFORMED: 1 }� I 1, D 1-�OT LEGAL DESCRIPTION: 7"1A/d K N Il L S $It Township, Range, Section: DEPTH SLOPE SITE PLAN (FEET) 2 3 4 5 13 14 15 16 17 18 19 S'Lr y / CA4U4-«y SA�p Hl t- S' l T- R. W1. H. S �rY GQave� y SA,.o WAS GROUND WATER ENCOUNTERED? Y S S IF VES, AT WHAT L DEPTH? •/> p E Geo 10 Water After ' i I a/ I 1/-16 Magltering? bete: N�1Y Date Gross Net Time Time Depth to Water Net Drop R4 ASK 1 ,I5 0 _ _ MENEENEEME G.. }6 y}, }:. .,d .. E��ia t/.. „ / r/y . S . U 7 ,/ 1 7,M .. a S- u ' 6 J 7'. 7/ NoEEENEEN MENEENEMEN ��iaasMEMENEEMEN Reading Date Gross Net Time Time Depth to Water Net Drop R4 ASK 1 ,I5 0 _ _ G.. }6 y}, }:. .,d .. 71) t/.. „ / r/y . S . U 7 ,/ 1 7,M .. a S- u ' 6 J 7'. 7/ 20 L PERCOLATION RATE 'S' TEST RUN BETWEEN i /T COMMENTS (mmutes/mch) PERC HOLE DIAMETER FT AND X i FT a a a cr.,....�.-....... l A LiZrz PERFORMED BV:� p ,,�. A �4� ggS7� I CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE VftlJ1tL'[ISTPfTE111NCTMUN(CIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: 72.008 (Rev. 4/85) • WATER WELL RECORD y STATE OF ALASKA DEPARTMENT OF NATURAL RESOURES Division of Geological a Geophysical Surveys LOCATION OF WELL (Plea's complete either la, It, or Ic.) Io. Borough Subdivision Lot Block Ib. I/4 gtrs. Anch Park Hil 11 2 _.f_or_ot— Ic1I DISTANCE AND DIRECTION FROM ROAD INTERSECTIONS Street Address and Arta of Wall Location Drilling Permit No. A.D.L. No. Section No. Township N Range S ❑❑ S. OWNER OF WELL: Address: E❑ Marldion W❑ R & H Const. 2. WELL LOG Material Type Faat Blow S urlota Top Boflom a. WELL DEPTH: (final) nL _ft. 1ST S. DATE OF COMPLETION — — 2—$,�,_ silt gravel w/boulders 0 30 6. ❑Cable tool )MRatary ❑Driven ❑Duo C] Auger ❑Jefted ❑Bared ❑Other: hard pan 50 40 gravely—hard pan lenses with 7. 1189Si® Domestic ❑ Public Supply ❑ Industry ❑ Irrigation ❑ Netharge ❑ Commerical ❑ Test Well ❑ Other: cobbles 40 7 a el bravely H2O f lb 6 d15 CASING: in. ❑ Threo of DepthWelded.ight be.� ft. diom. 55 in. to_ �r ft. Depth Stickup ft. 1 tl 1 76 well producing 10 gpm 9. FINISH OF WELL: Type: M �'mely+ lotlMssSl: Sat between 1019 _ ft. and 7_ ft. Backfilling Grovel pact _—_— 10. STATIC WATER LEVEL: ", ft. 411-4 ❑ Above or ® Below land surface Dale Equipment used: I I . PUMPING LEVEL below land surface and Yl ft. O ft. after _bra. pumping I V g. p. m. _ft, after_hrs. pumping -9-P m. 12.GROUTING Well Grouted: ❑ YesXQ No Material: ❑ Neat Cement ❑ OtMr: 13. pump: (if arallabta) NP Length of Drop Pipe 7), 1 fl. capacity 1�g. p.m. USubm. ❑ Jet ❑ Centriflcal ❑ Other te.REMARNS: Perforated @ 691 - 711 16. WATER WELL CONTRACTORS CERTIFICATION: IS. Water Temperature This well was drilled under my jurisdiction and this report is true to the bast of my knowledge and belief; laskaltlow-3Kell/Verna s Drilling & Eat AA 337 Reg,0.rad Business Name Contract License Number aa,. .1,1222_41- Avio/n Street Anchorage, Alaska 16 Sigma : f/yylnfy A --__ - __ Date: Authorized 'Representollve Form 02-WWR(11/8I) Copy Distribution: WHITE -State OGGS, PINK-Oriller, CANARY -Customer ❑ F ❑ C Aft MUNICIPALITY OF ANCHORAGE !�I DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTION ENVIRONMENTAL ENGINEERING DIVISION 825 L Street - Anchorage, Alaska 99501 Telephone 264.4720 ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT NAME PHONE ❑NEW N _ , ❑ UPGRADE MAILIN DDRESS 811 61,SFIOPA - 9 ysa LEGAL DESCRIPTION , 4 < L_L of -7-1 IQ - LOCATION NO.OF EDROOMS Well Absorption area Dwellin PERMI NO. Um DISTANCE TO: Awl M — - 7 _ it Q Manufacturer_ Maters No. of partments y Li . p yY�in gallons V IF HOMEMADE: Inside lengt �- Width Liquid depth d Y DISTANCE TO: Well Dwelling PERMIT NO. JU2 O FQ- Manufacturer Material Liquid capacity in gallons Well Foundation-Nearegt f ine 11 PE MIT NO. ' T5 DISTANCE TO: 1 J LL 2 No. of lines yy Long of a ch line Total lent of lines Trenc wi th Distance between lines ' E w L Zl inches Q HTop f tile to fi ish grade c.I ^84 a ena, ben--Jjath the h Total of %area rit / O WiN Y7 WIA ( it inches 5 7' Length k�SV WidthLTMN 41 pth P W f7 • 41.- Type of crib Crib di t Crib depth Total effective absorption ! Lu y Well Building foundation Nearest lot line •• DISTANCE TO: r•••• J Class Depth Driller Distance to lot line • J • : - THOS+ DISTANCE TO: Building foundation Sewer line Septic tank rplii n aT!I l OTHER PIPE MATERIALS 93 CAST R M 27 • SOIL TEST RATING152-9 INSTALLER Cnel j u�� r REMARKS u Ltd 0--'/-z ACc 0,110C war rvvaL,WW/ TJR �U,4V - -3 ` 44:1 OC -T $ APPROVED - DATE LEGAL /,S7 72-013 (Rev. 3/78) a '14q J1_4 MUPJ I C I FALL I TY OF ALV CCH0FZAC3E DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION 825 L STREET, ANCHORAGE, AK 99501 264-4720 C]hJ—S I TE '3 EWE Ft &. WEL L._ F'EF2M I T PERMIT NO: 640882 DATE ISSUED: 10/16/84 APPLICANT: ROBERT RUNKEL R & H CONSTR. INC. ADDRESS: 4811 BISHOP WAY ANCHORAGE, AK 99508 CONTACT PHONE: 3.38-1674 LEGAL. DESCRIP: LOT SIZE: MAX BEDROOMS: SUBDIVISION: PARE':: HILLS #1 SECTION: 34 TOWNSHIP: 12N 63399 (SQ.FT. OR ACRES) 4 LOT: 11 BLOCK: 2 RANGE: 3W Listed below are the options available to you in designing your septic system. Choose the option that best fits your site. * DEPTH TO PIPE BOTTOM < 3.5 FT. REQUIRES INSULATION ** DEPTH TO PIPE BOTTOM < 4.0 FT. MAY REQUIRE A LIFT STATION �t* GRAVEL LENGTH :> 75 FT. REQUIRES MULTIPLE RUNS (NOT EXCEEDING 75 FT. EACH) ** 'TANk: MUST HAVE AT LEAST TWO COMPARTMENTS I certify that: 1. I am familiar with the requirements for on-site sewers and wells as set forth by the Municipality of Anchorage (MOA) and the State of Alaska. 2. I will install the system in accordance with all MOA codes and regulations, and in compliance with the design criteria of this permit. 1. I will adhere to all MOA and State of Alaska requirements for the set back distances from any existing well, wastewater disposal system or public sewerage system on this or any adjacent or nearby lot. 4. I'understand that this permit is valid for a maximum of 4 bedrooms And any enlargement will require an additional permit. IF A LIFT STATION IS INSTALLED IN AN AREA COVERED BY MOA BUILDING CODES, THEN (1) AN ELECTRICAL PERMIT AND INSPECTION MUST BE OBTAINED; (2) AS-BUILTS WILL NOT BE APPROVED WITHOUT AN ELECTRICAL INSPECTION REPORT; AND (3) THE ELECTRICAL WORE: MUST BE DONE BY A LICENSED ELECTRICIAN. SIGNED APPLICANT: ROBERT RUNKEL- R & H CONSTR. INC. ISSIJED BY 6Lc,-d-et DATE: DATE:-. v nv TFIELVCH W _ L?RA I P4 DEPTH TO PIPE BOTTOM (FT.) 3.0 * 3.0 ** GRAVEL DEPTH (FT.) 3.0 3.0 TOTAL DEPTH (FT.) 6.0 6.0 GRAVEL WIDTH (FT.) 2.5 5.0 GRAVEL LENGTH (FT.) 102.0* 71.0 GRAVEL VOLUME (CU.YDS.) 33.1 46.1 TANK SIZE (GALS) 1,250.0 ** 1,250.0 *� SOIL RATING (SQ.FT./BR) 152 152 * DEPTH TO PIPE BOTTOM < 3.5 FT. REQUIRES INSULATION ** DEPTH TO PIPE BOTTOM < 4.0 FT. MAY REQUIRE A LIFT STATION �t* GRAVEL LENGTH :> 75 FT. REQUIRES MULTIPLE RUNS (NOT EXCEEDING 75 FT. EACH) ** 'TANk: MUST HAVE AT LEAST TWO COMPARTMENTS I certify that: 1. I am familiar with the requirements for on-site sewers and wells as set forth by the Municipality of Anchorage (MOA) and the State of Alaska. 2. I will install the system in accordance with all MOA codes and regulations, and in compliance with the design criteria of this permit. 1. I will adhere to all MOA and State of Alaska requirements for the set back distances from any existing well, wastewater disposal system or public sewerage system on this or any adjacent or nearby lot. 4. I'understand that this permit is valid for a maximum of 4 bedrooms And any enlargement will require an additional permit. IF A LIFT STATION IS INSTALLED IN AN AREA COVERED BY MOA BUILDING CODES, THEN (1) AN ELECTRICAL PERMIT AND INSPECTION MUST BE OBTAINED; (2) AS-BUILTS WILL NOT BE APPROVED WITHOUT AN ELECTRICAL INSPECTION REPORT; AND (3) THE ELECTRICAL WORE: MUST BE DONE BY A LICENSED ELECTRICIAN. SIGNED APPLICANT: ROBERT RUNKEL- R & H CONSTR. INC. ISSIJED BY 6Lc,-d-et DATE: DATE:-. v nv COMMENTS PERFORMED BY: 72.006 (6/79) 'G M) 5 i#y 5."yy y/aoe �-fawrl. �n �frslitf,J;r•el .o,,,f r /rnnef 1d&n Oli{e0`5 WAS GROUND WATER Y ENCOUNTERED? c S ?r' l7•i4� IF YES. AT WHAT - DEPTrI? Reading Date Gross Time SOILS LOG' "(c' Depth to Water • ' • � ( l d v % UNICIPALITY OF ANCHORAGE • DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION L PERCOLATION TEST — I 625 L. Street, Anchorage, Alaska 99501 2644720 3.35 ,37 LOG — PERCOLATION TEST tNC �,,/ FOR: �`'"'�Wk [SSOIIL,S, DATE PERFORMED A �9 PERFORMED ,70 — LEGAL DESCRIPTION. iG /����s'ar I t oIT ibl�G��•.n)c SLOPE SITE PLAN Salt 3-1/3— r/ �-� COMMENTS PERFORMED BY: 72.006 (6/79) 'G M) 5 i#y 5."yy y/aoe �-fawrl. �n �frslitf,J;r•el .o,,,f r /rnnef 1d&n Oli{e0`5 WAS GROUND WATER Y ENCOUNTERED? c S ?r' l7•i4� IF YES. AT WHAT - DEPTrI? Reading Date Gross Time Net Time Depth to Water Net Drop 7 NCO -71 7 % 1 / e70 — I I 3.35 ,37 tNC 'S'.3S — ,70 — I t c rN 0 3-1/3— r/ Ci } 3' I ._ t 20 s l z , PERCOLATION RATE rimer e. .ocTnrccn -9 A d4nS I/ic/gy �J- [): rive, G£ 8 • '� Municipality of Anchorage On -Site Water and Wastewater Program ^„ r (907) 343-7904 5 A F£ T Y _ Certificate of On -Site Systems Approval Parcel I.D. 017-112-59 Expiration Date: 1. GENERAL INFORMATION: Complete legal description PARK HILLS #1: BLOCK 21 LOT 11 Location (site address) 14727 Park Hills Circle *Anchorage 99516 Current Property owner(s) Larry Cooper Day phone 250-7530 Mailing address Real Estate Agent 2. TYPE OF DWELLING: ® Single Family (w/wo ADU) ❑ Duplex ❑ . Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 4 Day phone 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Individual Well ® Individual Individual Water Storage ❑ Holding Tank ❑ Community Class Well ❑ Community ❑ Public Water System ❑ Public Sewer ❑ WaiverNariance request for. Distance: Received by: Date: COSA to be released to the engineer, unless otherwise requested by the engineer. COSA Fee $ 5 5 G Waiver Fee $ Date of Payment -1Z y �22 Date of Payment Receipt Number O 913 6 G Receipt Number COSA # a s c a n Waiver # C�j 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm: Gamess Engineering Group, Ltd (GEG) Phone: 907-337-6179 Address: 3701 East Tudor Road, Suite 101- Anchorage, Alaska 99507 Engineer's Printed Name: Jeffrey A. Garness Date: f 2� In conducting this evaluation, GEG provided an engineering evaluation of the well and/or septic system in accordance with the guidelines and regulations established by the Municipality of Anchorage and industry practices. The reported results describe the condition of the system/s on the dates of the evaluation. Separation distances were measured to readily identifiable features. Hidden defects or encroachments may exist that were not identified during the evaluation. The operational life of all wells and septic systems depend upon a variety of variables, including but not limited to, soil conditions, groundwater levels (that may fluctuate during the year), quality of construction (materials and workmanship), and the water usage of the family utilizing the system/s. These conditions can vary, and are outside the control of GEG. Satisfactory test results do not guarantee future performance of the system/s; therefore, GEG makes no warranty (express or implied) regarding the future performance of the well or septic system. GEG makes no representation whether an alternative well or septic system can be installed on the property in the event either of the current systems fail to perform adequately in the future. The content of this report is for the sole benefit of the person/party that retained GEG to perform the evaluation. Reliance upon the information provided in this report by any other person or party (including subsequent property purchasers) is not authorized, nor will it confer any legal right whatsoever. o ��..• "° T) Q u � •y """' ;� � • .. • • • • • • • • . • • • • . • . r , Gor nP Q �.�• .j F 9 e1 o t asst° �o #AECC884 6. DSIGNATURE _ System #1 Approved for bedrooms System #2 Approved for bedrooms Disapproved r.0nditioonal approval for bedrooms, with the following E' •e stipulations: Y`ea afi4'i t-,,- S �,t��''r 0'*•�_ �� I�-PGt V` I•�e�fi rid L � I o O By: J tom,.. ('c`�� Original Certificate Date: �—Z7 z CiZZ I The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage Is not responsible for errors or omissions in the professional engineer's work. 7. ATTACHMENTS: COSA Checklist Septic System Advisory Well Flow Advisory OFlII 1;i Nitrate Advisory Arsenic Advisory J�—ON- 3717E `9 Other WATER AND m WAST'_v'ATER Z^ J� PROGF;AM 'moi O,o� /�•• �J\�� 0j Legal Description: PARK HILLS #1; BLOCK 2, LOT 11 Parcel ID: 017-112-59 If more than 1 septic system on lot: COSA Checklist # of Structure served by this system A. WELL DATA Adequacy test date 2/24/22 ❑ Well log is filed with Onsite (or attached) Well production at time of test 5.7+ gpm Date drilled ""27"4 NIA Water storage tank volume gallons Total depth *115.1+ ft Well disinfected for coliform test? ❑ Yes OR No Cased to UNKNOWN ft Coliform bacteria is Negative ❑ Sanitary seal is functioning correctly Nitrate mg/L Nitrate less than MRL (ND) ❑ Wires are properly protected Arsenic ug/L PArsenic less than MRL (ND) Casing height (above ground) 12+ in. Collected by GEG, LTD. Date of flow test for COSA 2/24/22 Date of SampleZ )-- Static water level at beginning of test 114.2 ft. Any rejuvenation treatment (past 12 months) -YES Comments *PER GEG INSPECTION - WELL DEEPENED AT SOME POINT, NO DOCUMENTATION IN MOA RECORDS B. TANK DATA Age of tank(s) 3 years Tank type/material Measured operating fluid level in septic tank ❑ Standpipes/foundation cleanout per record drawing Date of pumping 2— �-- D. ABSORPTION FIELD DATA BED C. LIFT STATION ❑ Required maintenance corn Age of lift stationy Lift station mated aV� Which system tested (date installed) "12/99 Adequacy test date 2/24/22 ❑ ALL standpipes present per record drawing Results DPass For 4 bedrooms Total measured depth from grade 4.04 ft (max) Fluid depth prior to test 5 in Measured depth to pipe invert from grade *2.0$ ft (min) Water added 609 gal ❑ N/A — pressurized field 5.5 ❑ Monitor tubes go to bottom of effective. If not, state New depth in 45 depth into effective r •• Elapsed time min p ❑ Code -required soil cover over field Final fluid depth 5 in ❑ System presoaked Absorption rate 600+ gpd (Required if vacant for greater than 30 days prior to Any rejuvenation treatment (past 12 months) -YES date of test) Gallons introduced N/A gallons if yes, enter date 6!14/19 -PRESENT Comments/Deficiencies: *INSULATED WITH Y OF FOAM - SEE EMAIL FROM OWNER REGARDING FREEZING **SOUTH Mr IN BED IS KINKED & UNABLE TO BE MEASURED -DRAINFIELD HAS LATERAL AERATION SYSTEM - NO PLUMBING LEAKS OR BACK-UPS NOTED DURING TESTING. ALL CLEANOUTS STAYED DRY THROUGH OUT TESTING - DRAINFIELD IS APPROACHING THE END OF ITS USEFUL LIFE i! COSA Checklist yellow sheet E. SEPARATION DISTANCES From Private Well on Lot to: (Please enter distances if less than required or if community well) Septic Tank/Uft Station on Lot > 100' ❑✓ Yes if No Community Sewer Manhole/Cleanout > 100' Cj Yes if No ft I 7v Yes if No ft Neighboring Tank > 100' Yes if No ft Private Sewer/Septic Line > 25' 0 Yes if No ft Absorption Field on Lot > 100' Yes if No ft Holding Tank > 100' S Yes if No ft Neighboring Absorption Fields > 100' Surface Water > 100' 0 Yes Animal Containment > 50' R Yes if No ft 0 Yes if No ft Manure/Animal Excreta Storage > 100' Community Sewer Main > 75' [E] Yes if No ft n Yes if No ft From Septic/Holding Tank on Lot to: (Please enter distances if less than required) Building Foundations > 10' M Yes if No ft Surface Water > 100' Yes if No ft Property Line > 5' ❑✓ Yes if No ft Wells on Adjacent Lots: Absorption Field > 5' �✓ Yes if No ft Private Wells > 100' R✓ Yes if No ft Water Main > 10' Cj Yes if No ft Community Wells > 200' Q Yes if No ft Water Service Line > 10' Yes if No ft If septic tank is under driveway comment below From Absorption Field on Lot to: (Please enter distances if less than required) Building Foundation > 10' [7, Yes if No ft If absorption field is under driveway comment below Property Line > 10' Yes if No ft Wells on Adjacent Lots: Water Main > 10' Q Yes if No ft Private Wells > 100' Q Yes if No Water Service Line > 10' M Yes if No ft Community Wells > 200' S Yes if No Surface Water > 100' 0 Yes if No ft F. ENGINEER'S COMMENTS G. ENGINEER'S CERTIFICATION / certify that 1 have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. COSA Checklist yellow sheet ',J ' A. Gar ss; CE 79 3 oil- 0"P � e �Op�� r.. �-7i ��v�,,.��ApG a bro f ession000 #AEccssa �4O000�� ft ft Erik Widger From: Larry Cooper <cfo@ak.net> Sent: Thursday, March 3, 2022 5:17 PM To: Erik Widger Cc: Sonja Blewett Subject: Re: 14727 Park Hills Circle - 2022 COSA Erik: I understand it was noted that the soil over our drain field may be thinner than desirable. I want to formally assure you that in the 17 years we have lived in this house there has never been an event of freezing in the drain field or any other component of our septic system. That includes many periods over the years where we had deep freezes across the city of Anchorage without snow covering the ground for any kind of insulation. Please let me know if there are questions in regard to this that I can answer. Thanks, Larry Larry J. Cooper 14727 Park Hills Circle Anchorage, Alaska 99516 907-250-7530 On Mar 3, 2022, at 12:57 PM, Erik Widger <erik@garnessengineering.com> wrote: Hello, In order to submit your COSA to the MOA we will need the following items: 1 Jeff Garness From: ARM Septic Services LLC <ARMServicesAK@outlook.com> Sent: Thursday, March 3, 2022 2:19 PM To: Jeff Garness Subject: Re: 14727 park hills The drainfeild was surcharged and overflowing out of the ground when we first got on site a few years ago. Mariah Sent from my iPhone On Mar 3, 2022, at 2:12 PM, Jeff Garness <Jeff@garnessenginee ring.com> wrote: Was the drainfield failed? .... .............................. From: ARM Septic Services LLC <armservicesak@outlook.com> Sent: Thursday, March 3, 2022 12:44 PM To: Erik Widger <erik@garnessengineering.com> Cc: Sonja Blewett <Sonja@garnessengineering.com>; Jeff Garness <Jeff@garnessengineering.com> Subject: 14727 park hills Hello, Please see attached invoice for park hills and what we did back in 2019 for tank replacement and aeration of laterals. Thanks, Mariah Campbell Member ARM Septic Services, LLC Ph: (907) 688-9433 Cell: (907) 317-8834 Email: ARMServicesAK(ftutlook.com Website: www.ARMServicesAK.com Facebook: www.facebook.com/ARMServicesAK/ 1 ARM Septic Services, LLC U 17933 Old o"nr"�mw"� � Ohugiak,AK 99567 (9O7)G88-S433 ARK8SemioeeAKpoud|ook.00m vmww.ARK8GomireoAK.com Tammy Cooper 14727Park Hill Cr Anchorage, AK 99516 � 1828 06/14/2019 Due on receipt Excavation Tank Only 1 13,735.95 13,735.95 Estimate for installation of new 4 bedroom septic tank and d lateral aeration system. _r "n P�auen»adondo�ntha to this 'ion of work. contract. ;� 50% down required, Remaining balance due upo pi 14727Park Hill Cr. " Site Work -Engineering design, drawings, and submittal for Permit -MOA permit fee -Inspections f septic tank -Engineers record drawings -Submittal o4records package bothe MOA materials | Top soil and seed _HY[dnlJettinQsewer lines .-- AoJsminterest charge will apply mall invoice over 30 days lam. PAYMENT BALANCE DUE ARM Septic Services, LLC 1 2,134.00 2,134.00 1 1,993.75 1,993J5 | 1.50| 275.00 412.50 18,276.20 ��^����� �r� v -o rn n = ? o mvm N oN �. P m(Dm w Na15ID � °' D ` ID N r wLn �3 � � 0 � 0 n 0 D 0m M LA G1 Q z Z z z D �� m z�im�+ 35; m- o�? m4 X 0 0 Z> 0, N T z LnLn •Dv iZ > O=D iZ=m= 20>21 �o=mm �c^z cn O C 0 = NLn W Q r Ln n Q7 z m m !-IA mZ� Z Z n 'z2.i mo Zoe:r i G)o 1 -TZ- XZ v+IDn o o�� AXE D =mom Ln oz nW� c 3'7 n m m :pm f�'l�=LZIa r 0 :Dm_i-I TZDQ 0 N <ezo m a- m m -={ G to W N No Z N CD Z m > n v Gt fl m a Zr ZO m Qv n� O' ' r= a 43 Ci ;o --i v -{0,n 6 > <o � rn -Ov Amon lognz to mr—MITI ZO z�im�+ 35; m- o�? m4 0-°z 0 Z> 0, N 5>Gi z iCG)Zm omm0 m=i zOZ�? v •vi5 m Ln z S iZ > O=D iZ=m= 20>21 �o=mm �c^z L O = tTr-0z ��O �o�^z =on . CZnm Z= 90< m r Ln n Q7 z m m !-IA mZ� Z Z n 'z2.i mo Zoe:r �7 m X O 1 -TZ- XZ v+IDn n "9 0 !v,;av,Z uiizoo �=0�,n m�Z D =mom Ln oz nW� c 3'7 n m m :pm f�'l�=LZIa r 0 :Dm_i-I TZDQ O ;1 <ezo >MOm Z m2 m 28.1' G) w 91 3r— m ' B.2` 30.3' w os 9 w 3.9' 0 3.9' w �d Z co v, W rn CD Ln m4 r) m Z G) n n r L O m Q' co z Lq m �z 30.3' w os 9 w 3.9' 0 3.9' w �d Z co v, W CD m4 r) m n n m0 L 1 m Q' z 20' TELECOMM. & ELECTRIC EASEMENT S00° 00'00"E 156.64' Municipality of Anchorage • Development Services Department Building Safety Division On -Site Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.muni.orglonsite (907)343-7904 CERTIFICATE OF HEALTH AUTHORITY APPROVAL FOR A SINGLE FAMILY DWELLING Parcel I.D. 017-112-59 1. GENERAL INFORMATION HAA # (O Ll OO;;Z Expiration Date: S'— a4 —0t Complete legal description Lot 11; Block 2; Park Hills Subdivision #1 Location (site address or directions) 14727 Park Hills Circle Anchorage, AK 99516 Current Property owner(s) Pam Buffington Day phone 301-5671 Mailing address same Lending agency Mailing address Real Estate Agent Mailing Address Day phone Lisa Herrington Day phone 646-0525 702 Barrow St. Anchoraqe, AK 99501 Unless otherwise requested, HAA will be held by DSD for pickup. 2. NUMBER OF BEDROOMS: 3. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Individual Well ❑✓ Individual On-site ❑✓ Individual Water Storage ❑ Individual Holding tank ❑ Community Class Well ❑ Community On-site ❑ Public Water System ❑ Public Sewer ❑ The Municipality of Anchorage Development Services Department (DSD) Issues Certificates of Health Authority Approval (HAA) based only upon the representations given in paragraph 4 by an independent professional civil engineer registered in the State of Alaska. Certificates of Health Authority Approval are required for the transfer of title (except between spouses) for properties served by a single-family on-site wastewater disposal and/or water supply system. DSD also issues HAAs upon request to homeowners. Certificates of Health Authority Approval are valid for 90 days from the date of issue for properties served by a private or Class C well and may be reissued with new water sample results. (Certificates may be reissued for a period of up to one year with valid water samples.) Certificates are valid for one year for properties served by Class A or B wells or a public water system. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 4. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Health Authority Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is(are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm S & S Engineering Address 17034 N. Eagle River Loop Ste. 204 Eagle River, AK 99577 Engineer's Printed Name Robert C. Cowan Phone 694-2979 Date o / 8 /o y OF to a .) 7 ! 5. DSD SIGNATURE I� �1 ROBERT C. COWAN Fti 1 / 4 0".. C: - 8801 a :- Approved for bedrooms. y sr�^�, :!<;' Disappr v ttacp Conditional approval for bedrooms, with the following stipulations: Additional Comments ''- nN-RITE; WATER AND Attachments: HAA Checklist X Maintenance Agreements Septic System Advisory Supplemental Engineer's Report Well Flow Advisory Other By: Original Certificate Date:. ^ •� 1� - 0 Lf (Rea 01102) vlunicipality of Anchorage • ' Development Services Department % Building Safely Division 1 On -Site Water & Wastewater Program 47CO South Bragaw Sl. P.O. Box 196650 Anchorage, Al 99519-6650 www.ci.anchorage. ak. us (907) 343-7904 HEALTH AUTHORITY APPROVAL CHECKLIST Legal Description: 407- 11 13LacK A PACK Parcel ID: A. WELL DATA Well type PR wnrti If A, B, or C provide PW SID # Well Log &N) _Y y f Date completed 11 /017/Yy Sanitary seal 61N) Y -r) Wires properly protected ON) YE5 Total depth 130+ ft. Cased to 90 t ft. Casing height (above ground) 18 t in. FROM WELL LOG AT INSPECTION Date of test 1 ! }7 SY ;1. // 0 /O y Static water level %S ft. /Oro _._ ft. Well production I D 9 P.M. —_ S- H 9 P M WATER SAMPLE RESULTS: Coliform 0 colonies/100 ml. Nitrate 0- ( mg./I. Arsenic: A. Date of sample: -d�/%N B. SEPTIC/HOLDING TANK DATA Tank Type/Material 5ei'?i4L/ HDPE Tank size 13 "0 gal. Number of Compartments 7;) - Foundation cleanout®N) Yd s Depression over tank (YO NO Date of pumping 1 0 /1 7 10 3 Pumper I S 4-4 C- S C. ABSORPTION FIELD DATA Other bacteria O . colonies/100 ml. Collected by:T_ Rg€NGINEERING 17034 Eagle River COP Road No. 2U r.&918 River, Alaska 99577 Date installed Cleanouts &) iX/91 `t yes High water alarm (Ye_ N O Date installed 1 �1 7 9 q Soil rating p.d./ft r ft2/bdrm)0- (� System type ISE A _ Length G7 ft. Width is fl. Gravel below pipe d- S ft. Total depth __�J_ ft. Eff. absorption area 100 9-ft2 Monitoring tube YES Depression over field WO Date of adequacy test X11010 1tResults Pass ail) PR s S For __y_ bedrooms Fluid depth in absorption field before test in Water addedG0-gal, New depth Iq in. 1 Elapsed Time:ia7 min. Final fluid depth in. Absorption rale >_ __%v d g.p.d. Any rejuvenation treatment (past 12 mo.) (Y/N & type) Nsv�t k"I" If yes, give date D. LIFT STATION Date installed "Pump on" level at in. Datum E. SEPARATION DISTANCES Size in gallons "Pump Cycles tested SEPARATION DISTANCES FROM WELL ON LOT TO. Septic tank/lift station on lot 1 00 ,+- Absorption field on lot %00 r� Public sewer main N( R r High water alarm level at Meets alarm & circuit requirements? On adjacent lots On adjacent lots /00 -j- /00 ',A Public sewer manhole/cleanout N14 Sewer /septic service line a S -0- Holding tank N AA SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Building foundation 7t. Property line 37 Absorption field +' i Water main N 1A Water service line / 0 ,4- Surface water / 00 •t Wells on adjacent lots /00 '4 SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Property line 37 Building foundation Q S Water main N A Water Service line /orf' Surface water /00 r+ Driveway, parking/vehicle storage 3( - Curtain b Curtain drain Norve. KI O - Wells on adjacent lots / 0 0 + F. COMMENTS G. ENGINEER'S CERTIFICATION I certify that l have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA HAA guidelines in effect on this date. Engineer's Printed Name i 03 t:••LT <. C o w/4AJ Date a 8/0i HAA Fee Date of Payment a�r9�oY Receipt Number 0 M SV0 7 1 (Rev. 12/01) Waiver Fee $ Date of Payment Receipt Number t T k ROEERT C COWAN i �? `"C� CE - 8801 r.``" in. LA LOT 12 49TH �bat�M. Oraye LS -10392 �+ Po_ ..... _b� NOTE: SNOW AND ICE MAY CONCEAL MINOR SURFACE FEATURES. LOT 10 m' m m m � LOT 11 66.4 ........ 5/m W: i w/GVB "".,00 hot nal appear m IM nearded wAEIN+Ian plat NOTE O <Ycum+loncww should any data hereon be aced fa F � . on or to, establishing property line Nab ! TWt a yam_ %— R — ,.B a A Zoe I %0%TY CERMCATION: Ulf TECH hoe aanductwd a of he property as drown a thiher, phrl�oWowing and that 4no . ana mal the Mppyr lines n +I[uw[wd uv property lines and no wrinexA- an ere wlet Nom MMS- [anCRETE- tn- - T z O JO 62�i1 I w ,D EXISTING MWSE N wA1O1 IW ai 3 J41 W e O k7N -V0 IW -1 o 20' TELE. & ELEC. EASEMENT N 89'53'50" W 141.19- 41.19TRACT TRACTB PAM BUFFINGTON with DYNAMIC PROPERTIES. INC. 440 WEST BENSON BLVD. N 103 ANCHORAGE, ALASKA 99503 NOR% OME6 Nitt BER: n!y . 16. 2004 1 2004 -L -35A ,:f '" t. ofS y i+ EM ntv, Te tk only 1a t'ltl.. lne of any esernenb, wesnonlR a r"plat 5/m W: i w/GVB "".,00 hot nal appear m IM nearded wAEIN+Ian plat NOTE O <Ycum+loncww should any data hereon be aced fa F 123, 1=a' ALMOL AYOIwIIEN, on or to, establishing property line Nab ! TWt a yam_ %— R — %0%TY CERMCATION: Ulf TECH hoe aanductwd a of he property as drown a thiher, phrl�oWowing and that 4no . ana mal the Mppyr lines n +I[uw[wd uv property lines and no wrinexA- an ere wlet Nom MMS- [anCRETE- tn- - T ha mestw al+l *that than Mlb. MAWt aAVO _ RPMstu�orvEs- FNGINEERS AS—BUILT OF: IFOALOMISPIp,: wA1O1 561-6626 562-5291 LOT 11, BLOCK 2, '° PARK HILLS SUBD. ADD. N0. 1 k7N /A A Parcel I.D. # MUNICIPALITY OF ANCHORAGE Ak • DEPARTMENT OF HEALTH & HUMAN SERVICES Division of Environmental Services On -Site Services Section ExTa P.O. Box 196650 Anchorage, Alaska 99519-6650 343-4744 CERTIFICATE OF HEALTH AUTHORITY APPROVAL FOR A SINGLE FAMILY DWELLING` 017-112-59" HAA # tV YA n\ C_Yr. l S 1. GENERAL INFORMATION Complete legal description Lot 11, Block 2, Parkhills #1 Location (site address or directions) Property owner Mailing address Lending agency Mailing address Agent Address 14727 Park Hills Circle Georgie & Jerry Barnes 14727 Park Hills Circle, Anchorage, Unless otherwise requested, HAA will be held for pickup. 2. NUMBER OF BEDROOMS: 4 3. TYPE OF WATER SUPPLY: Individual well xxx Community well Public water Day phone . AK 99516 Day phone Day phone 345-6478 NOTE: If community well system, provide written confirmation from State ADEC attest- ing to the legality and status of system. 4. TYPE OF WASTEWATER DISPOSAL: Individual on-site XXX Holding tank Community on-site Public sewer NOTE: If community wastewater system, provide written confirmation from State ADEC attesting to the legality and status of system. 72-025 (Rev 1M) Front MOA#21 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation of this Health Authority Approval application shows that the on-site water supply and/or wastewater disposal system is safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I furtherverify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is in compliance with all Municipal and State codes, ordinances, and regulations in effect on the date of this inspection. Name of Firm 5$ 5 ENGINEERING Phone el y_ a ry-7 G� Address Eagle River, Alaska 99577 Engineer's signature Date /�/ �. 6. DHHS SIGNATURE _ ✓ Approved for ��bedrooms. Disapproved. Conditional approval for Additional Comments 0 4UTI0 OF Si 1 a V bedrooms, with the following stipulations: Date 1. % The Municipality of Anchorage Department of Health. and Human Services (DHHS) issues Health Authority Approval Certificates based only upon the representations given in paragraph 5 above by an independent professional engineer registered in the State of Alaska. The DHHS does this as a courtesy to purchasers of homes and their lending institutions in order to satisfy certain federal and state requirements. Employees of DHHS do not conduct inspections or analyze data before a certificate is issued. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. #MS IBa+. lAt� Back MOA Q1 RCEE^.T C. CO'NAN �? CE - U01 , bedrooms, with the following stipulations: Date 1. % The Municipality of Anchorage Department of Health. and Human Services (DHHS) issues Health Authority Approval Certificates based only upon the representations given in paragraph 5 above by an independent professional engineer registered in the State of Alaska. The DHHS does this as a courtesy to purchasers of homes and their lending institutions in order to satisfy certain federal and state requirements. Employees of DHHS do not conduct inspections or analyze data before a certificate is issued. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. #MS IBa+. lAt� Back MOA Q1 zLCEIVED Municipality of Anchorage IAN .1999 oe* DEPARTMENT OF HEALTH & HUMAN SERVICES ' Environmental Services Division MUNICIPALITY OF ANCHO 825 L Street, Room 502 • Anchorage, Alaska 99501 • ( 12*RvICES DIVISION Health Authority Approval Checklist Legal Description: Lo T 11 f3 L -ac a a PARa N"`t'0/ Parcel I.D.: OI 7 - /l1 A. WELL DATA Well type ✓° R I \"f rf- If A, B, or C, attach ADEC letter. ADEC water system number Log present &N) i zi 5 Date completed I I/} 7 S 7 Total depth 7 6 Cased to Sanitary seal ON) -Y4, f Date of test Static water level Well production FROM WELL LOG it /a7 /S`/ WATER SAMPLE RESULTS: Gr' g.p.m. Casing height (above ground) Wires properly protected/N) AT INSPECTION 3/ g8 /o b 3 Yr _� g.p.m. Coliform Nitrate r 17 c Other bacteria i Collected b Date of sample: f � r Y R y: S & S ENGINEERING 17 U34 age River Loop Road No. 2o4 B. SEPTIC/HOLDING TANK DATA Eagle River, Alaska 99577 Date installed ) ' � I `1 11 Tank size 1 3 d 1) Number of Compartments � Cleanoutsfy�N,) y4 I Foundation cleanout (JY N) Y c J Depression (41) ^ High water alarm (Y6; Date of Pumping �1a - ^ 4 Pumper - C. ABSORPTION FIELD DATA Date installed 1 /i IJ Soil rating g.p.d./ft' r ftz/bdrm) System type '1) Length (D I Width I S Gravel thickness below pipe S Total depth Y Effective absorption area I o u s Fr Z Monitoring Tube presenI Y/N) 1 * 13 Depression over field (Y& ^ Date of adequacy test I"/ 4 - rw w Results (Pass/Fail) Fluid depth in absorption field before test (in.); Fluid depth Peroxide 72-026 (Rev. 3/96)` (ins) Minutes later: months)(Y/N) Immediately after For. Zi bedrooms rate = g.p.d. If yes, give date D. LIFT STATION Date installed Manhole/Access (Y/N) _ High water alarm level at' E. SEPARATION DISTANCES "Pump 'Datum SEPARATION DISTANCES FROM WELL ON LOT TO: Septic/holding tank on lot / 6 0 t Absorption field on lot / 00 Public sewer main Size in gallons "Pump off" level at' On adjacent lots On adjacent lots Public sewer manhole/cleanout / 0 0 4 Sewer /septic service line °L ' Lift station r 14 SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: 'rt Foundation 76 Property line -7 Absorption field Water main/service line 10 Su4ace water/drainage /o u t Wells on adjacent lots 10 o 4 - SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Property line 3'7 Building foundation `t Water main/service line Surface water Curtain drain rJ 0 a 4 K V° w F. ENGINEER'S CERTIFICATION Driveway, parking/vehicle storage area Wells on adjacent lots I certify that I have determined thru field inspections and review of Municipal in conformance w'th A ggguidelin in effect on this date. Signature Engineer's Name i d!3 E� i �- Co �,4,v Date 1/1 S / 9 Ci HAA Fee $ � Z' O Waiver Fee $ Date of Payment y — /�f Date of Payment Receipt Number �� / Receipt Number 72-026 (Rev. 3196)' oc � JJ f M 'O. t ROEERt r are •MUNICIPALITY OF ANCHORAGE • DIVISION OF ENVIRONMENTAL HEALTH DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION APPLICATION FOR HEALTH AUTHORITY APPROVAL. CERTIFICATE 1. General Information Application Date March 4, 1985 (a) Legal Description (include lot, block, subdivision, section, township, range) Park Hills #1 Lot 11 Block 2 Sec 34 R3W T12N Location (address or directions) Park Hills Circle (b) Applicants Name R & H Construction Telephone - Home Business 344-8042 Applicants Address c/o GEOLAB 1131 E. 76th Ave. #101 Anchorage, AK 99502 (c) Applicant is (check one) Lending Institution ; Owner/builder XX ; Buyer = ; Other (explain); (d) Lending Institution Telephone Ad3Tgss (e) Real Estate Co. S Agent Address Telephone (f) Mail the HAA to the following address: Anchorage, Alaska 99502 2. Type of Residence Single -Family Multi -Family Number of Bedrooms 3. Water Supply Other (describe) Individual Well Q Community Q Public Q Note: If community well system, must have written confirmation from the State Department of Environmental Conservation attesting to the legality and status. 4. Sewage Disposal Onsite =1 Public Community Holding Tank Q Note: If community well system, must have written confirmation from the State Department of Environmental Conservation attesting to the legality and status. [Page 1 of 2] • • f 5. Engineering Firm Providing Inspections, Tests, File Search, Data and Information As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation of this Health Authority Approval shows that the on-site water supply and/or wastewater disposal system is safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that, based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is in compliance with all Municipal and State codes, ordinances, and regula- tions in effect on the date of this inspection. Name of Firm GEOLAB Telephone 344-8042 Address 1131 E. 76th Ave. #101 Anchorage, Alaska 99502 +r Date March 4. 1985 r_•Cr 6. DHEP Approval Approved for Approved (ENGINEER SEAL) bedrooms Disapproved Terms of Conditional Approval CAUTION Conditional ��+IHOM22'0 r A:iyyi. GMiX F:/i THE MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION (DHEP) ISSUES HEALTH AUTHORITY APPROVAL CERTIFICATES BASED SOLELY UPON THE REPRESENT- ATIONS GIVEN IN PARAGRAPH 5 ABOVE BY AN INDEPENDENT PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF ALASKA. THE DHEP DOES THIS AS A COURTESY TO PURCHASERS OF HOMES AND THEIR LENDING INSTITUTIONS IN ORDER TO SATISFY CERTAIN FEDERAL AND STATE REQUIRE- MENTS. EMPLOYEES OF DHEP DO NOT CONDUCT INSPECTIONS OR ANALYZE DATA BEFORE A CERTIFICATE IS ISSUED. THE MUNICIPALITY OF ANCHORAGE IS NOT RESPONSIBLE FOR ERRORS OR OMISSIONS IN THE PROFESSIONAL ENGINEER'S WORK. (DHEP SEAL) RR4/ej/D18 [Page 2 of 21 7-19-84 • CIPALITY OF ANCHORAGE (MOA) HEALTH AUTHORITY APPROVAL (HAA) CHECKLIST - FEBRUARY 1984 A. WELL DATA Legal Description: Park Hills #1 Lll B2 Sec 34 R3W T12N Well Classification Individual If A, B, or C, D.E.C. Approved(Y/N) Well Log Present (Y/N) Yes Date Ccapleted 11/27/84 Yield 10 gpm Total Depth 76' Cased to 76' Depth of Grouting None Static Water Level 65' Pump Set At 70' Casing Height Above Ground 18" Sanitary Seal on Casing (Y/NY" Electrical Wiring in Conduit (Y/N) Yes Depression Around Wellhead (Y/N No Separation Distances from Well: To Septic/Holding Tank on Lot 152' ; On Adjoining Lots 100'+ To Nearest Edge of Absorption Field on Lot 165' ; On Adjoining Lots100'+ To Nearest Public Sewer Line NA To Nearest Public Sewer Clearout/Manhole NA To Nearest Sewer Service Line on -Lot NA Water Sample Collected By AEc-S Date ?/I S/RS Water Sample Test Results Satisfactory •.n t B. SEPTIC/HOLDING TANK DATA Date Installed 10/18/84 Size 1250 gal No, of Compartments 2 Standpipes (Y/N) Yes Air -tight Caps (Y/N) Yes Foundation Cleanout (Y/N)Yes Depression over Tank (Y/N) No Date Last Pumped NA - new system Pumping/Maintenance Contract on File (Y/N) NA for Holding Tank High -Water Alarm (Y/N) NA Temporary Holding Tank Permit (Y/N) Separation Distances from Septic/Holdirg Tank: To Water -Supply Well 152' To Building Foundation 130' To Property Line 10' To Disposal Field 10' To Water Mair,/Service Line NA To Stream, Pond, Lake, or Major Drainage Course NA Convents Receipt # 3 2) Date Paid: Amount: JS — (Page 1 of 21 2-15-84 C. ABSORPTION FIELD DATA Soils Rating in Absorption Strata 1r,2 cn_ft_/RR Type of System Design Wide Drain Date Installed 10/18/84 Length of Field 71' Width of Field 5.01 Depth of Field*3,-5', due to tonoaraohv. Gravel Bed Thickness -�l Square Feet of Absorption Area 608 sq. ft. Standpipes Present (YM) yes Depression over Field (YM) No Date of Last Adequacy TestNone - new system Results of Last Adequacy Test NA Separation Distance from Absorption Field: To Water -Supply Wall 165' To Buildirg Foundation 150' To Property Line 10' To Existing or Abandoned System on Lot None On Adjoining Lots 1001+ To Water Main/Service Line NA To Cutbank(if present) NA To Stream/Pond/Lake/or Major Drainage Course NA To Driveway, Parking Area, or Vehicle Storage Area 50' COmments * Irregular topography. Insulated where less than 4' D. LIFT STATION Date Installed Size in. Gallons "Pump Or." Level at High Water Alarm level at Tested for Electrical Codes(YM) Comments Dimensiors Manhole/Access (YM) "Pump Off" Level at Vert (YM) Pumping Cycles during Adequacy Test. Meets MDA ** Check Permitted Bedroom Rating Against HAA Request ** I certify that I have checked, verified, or conformed to e on the da of th' inspection. d Signed Date 3 7S CczTpany GEOLAB MOA No. ST85-007 KBl /d5/s (Page 2 of 21 /VIM�� do A"-,' 2-15-84 :�t