HomeMy WebLinkAboutSHELL #2 LT 4Shell #2 Lot 4 #015-112-14 SUBA17 AL Municipality of Anchorage On -Site Water and Wastewater Program • (907) 343-7904 Page 1 of 3 ONSITE WASTEWATER INSPECTION REPORT Permit Number: OSP131117 PID Number: 015-112-14 Dwelling: H Single Family (SF) ❑ Duplex (D) ❑ Multiple (SF and/or D) Project: ❑ New 0 Upgrade Name: RICHARD REEVES ABSORPTION FIELD ❑ Deep Trench N Shallow Trench ❑ Bed ❑ Mound Address 10707 WHIMBREL DR. ANCHORAGE, AK ❑ Other Phone Number of Bedrooms Soil Rating Total depth from original grade 4 1.0 GPD/SF 4.5 Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade 3.8- Ft_ Gravel depth beneath pipe 0.8 Ft. Subdivision Block Lot SHELL #2 4 Fill added above original grade 0.0 TO 0.5 Ft. Gravel length 20 Ft Township Range Section Gravel width 5 Ft. Beds: Number of Lines NA Distance between lines NA Ft. SEPARATION DISTANCES TO Septic Absorption Lift S Holding Sewer Total absorption area Number of trenches Dist. between trenches From Tank Field Tank Line 100 Fe 1 NA Ft. Well >100' NAtation NA >25' TANK ❑ Septic ❑ S.T.E.P. ❑ Holding ❑ Other Manufacturer Capacity I Surface Water >100' NA NA Gal. Material Number of compartments Lot Line 5' NA NA NA Foundation >10' NA NA LIFT STATION Manufacturer Capacity Curtain Drain >50' NA NA I Gal. Remarks INSTALLED BULL RUN DIVERTER VALVE Pump on level at in. Pump off level at in. High water alarm at in. Pump make and model Electrical Inspections performed by Installer PIPE MATERIAL House to tank rank to drainfreld 3034 A+ HOME SERVICES Drainfield F810 C01MTF810 Inspector ANSON MOXNESS & LARS SPURKLAND BENCHMARK (Assumed elevation) 100 ft Inspection 1" 6/20/13 2w 6/20/13 Location and description a" 6/20/13 a BOTTOM SIDING @ ORENCO CONTROL BOX COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL Engin Conditional Approval: F..4.,q �t'1 Date 0• r � T i . 10 Approve Date -tea UMMITTA 1 `\\\� A \\neoL I 7 ea 9 3 / L S 9 S uv— — Septic 8 LOT 4 Area SLlB'f 5- 8 SWING 77ES A B 4 BDRM ' TANK C.O. C 45' 29' DIV£RT£R D 46' 32' SFR g C DF. C.O. E 34' 24.5 OF. M. r. F 43.5' 40' Septics I �'`t N` A £ D I OF. MON 43' 440. 05 Area O SLWC 2-58 15 F J I DF. C.O. I 47' 34' DF. MT. J 47.5' 34.5 W _ m 5 Area r7 7 �y Tw—A—um RESERVE DRA/NAELD � CONNECTED TO EXISANG SEPT?' SYSTEM INSTALLED BULL RUN DIVERTER \ 7 SHALLOW TRENCH 5' X 20' TOTAL DEPTH 7 FEET \`v FILTER SAND 2 FEET\\l�, SEWER ROCK I FOOT COVER 3-4' 1 Y NOW. SLOPES EXCEEDING 25X WERE NOT OBSERVED WITHIN 50 T£fT DOWN GRADIENT OF WE PROPOSED ABSORPTION FIELD LOCAWN. NOTE• THIS IS NOT A SURVEYED PLAT. WELL & SEPTIC LOCATIONS TAKEN FROM ON-SITE WATER AND WASTE WATER DEPARTMENT DOCUMENTATION. ALL LOCATIONS SHOWN ARE APPROXIMATE. 25 r,25 50 75 100 125 150 SCALE., I' = 50 FL Jl'UNRLAIVU LNU'74 4 KNVG I I SHELL 12 LT 4 I I SEPTIC SYSTEM ASBUKT 203 V 15TH. AVENUE ANCH. AK. 99501 RICHARD REEVES A4 TE, JULY 10, 2013 (907) 279-3916 10707 VHIMBREL DR ANCHORAGE AK 99507 YHL h 17Y GN10+ L'S36 PERMIT R OSPI31117 PID R 015-112-14 SHELL2L4.SC50.DV6 TH VIDE Trench: 5' Wide 20' Long 7' Max. Depth 2' Filter Sand 1' Sewer Rock E.G BEV.=lMr T.P. an IaP.r' T.s W=ral.a' &a& ELEV g&a' a". --gar NO SCALE Trench Elevation (TyP) ClMeLo ts MoniItors Silt Barrier 1 ft of Septic Rock and 2 ft of Filter Sand Run Diverter TD ADVENTEX AVVTS BENCH MARK BOTTOM SIDING O OR£HCO PANEL ASSUMED ELEVATION 100 FELT ISPURKIAND ENGINEERINGI I SHELL 12 LT 4 I I SEPTIC SYSTEM ASBUILT 203 V 15TH. AVENUE RICHARD REEVES BATE, JULY 10, 2013 ANCH. AK. 99501 (907) 279-3916 10707 VHIMBREL BR ANCHURAGE AK 99507 SHEEP 1/2 &1B1 2,536 PERMIT # OSP131117 PID # 015-112-14 SHELL2L4.B3DV6 On -Site Wastewater Disposal System Permit MUNICIPALITY OF ANCHORAGE Development Services Department On -Site Water & Wastewater Program 4700 Elmore Road, PO Box 196650 Anchorage, AK 99519-6650 Telephone: (907) 343-7904 Permit Number: OSP131117 Tax Code Number: 01511214000 Work Type: Septic Permit Effective Dates: June 07, 2013 to June 07, 2014 Design Engineer: SPURKLAND ENGINEERING Subdivision: SHELL #2 61avI13 0113-v 6124113 12:34 Site Legal Address: SHELL #2 LT 4 G:2536 Owner/Address: REEVES RICHARD L & SUSAN R 10707 WHIMBREL DR ANCHORAGE AK 995076518 Site Mailing Address: 10707 WHIMBREL DR, Anchorage Lot Size in Sq Ft: 12000 Total Bedrooms: 4 This permit is for the construction of: Y Disposal Field N Septic Tank N Holding Tank N Privy N Private Well N Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80). 3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either: A. Open and Close on the same day. B. Covered, sealed, and heated to prevent freezing. Received Municipality ofAnchorage 11.0. lkix 11MR) I AwlimuW, Alaska IMAMOR) • T.kphmrc (!X)7)$43,&U)1 * Fax (!M)7) 37.5- !(X) 47(M) nra(Qiw• Slreel • AJWIamugc, ANAai XAM auu�.mnnLaryi . Mayor Mark Begich Iluilding Safety DItislon 9/7/2004 BTH Construction, LLC P.O. Box 110358 Anchorage, AK 99511 Subject: Waiver Request for Shell #2 Subdivision, Lot 4 Waiver Request #WRO40061 Parcel ID #015-112-14 Permit # SW040341 Dear Mr. Harten: Your request for a waiver of the required 10 feet horizontal separation from the absorption field to property line has been approved. app ed scpasation'dissapz"s—,, 5.0 feet. Cprc w+ar� Khd erese✓'vt)�'�3v1i3 This waiver approval applies to the existing absotion fieldAo property line separation only. Any future upgrade to the on-site waste ter sposal system will rcqui all separation distances be met or another approval from is If there are any further concerns or questions regarding this waiver, please call our office at 343-7904. Sincerely, Julie Makela, P.E. Civil Engineer On -Site Water & Wastewater Program Coninlunity, Security, Prosperity MUNICIPALITY OF ANCHORAGE Community Development Department Phone: 907-343-7904 Development Services Division Fax: 907-343-7997 On -Site Water & Wastewater Program ON-SITE SEWER/WELL PERMIT APPLICATION Parcel I.D. Property owner(s) RICHARD REEVES Day phone 242-1784 Mailing address 10707 WHIMBREL DR., ANCHORAGE, AK 99516 Site address SAME Legal description (Sub'd., Block & Lot) SHELL #2 LOT 4 Legal description (Township, Range & Section) Lot Size APPLICATION IS FOR: (® all that apply) Absorption Field E] Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage ❑ Ft. Number of Bedrooms 4 APPLICATION IS AN: TYPE OF DWELLING: Initial ❑ Single Family (SF) 0 (w/wo ADU) Upgrade � Duplex (D) El EllMultiple Dwellings ❑ (SF and/or D) THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR: I certify that the above information is correct. applicable Municipal Codes. of property owner or authorized Permit/Rush Fees: 4 5-36, t° Date of Payment: 614 l3 Receipt Number: 092&-4 Permit No. 06P131117 PennQ App_9-1-12.doc Distance: I further certify that this is in accordance with Waiver Fees: Date of Payment: Receipt Number: Waiver No. SpHrrN aimd EIMgofleerrong Environmental Consulting and Design Municipality of Anchorage May 21, 2013 Development Services Department On Site Water and Wastewater Program 4700 Elmore Road Anchorage, Alaska 99519 Subject: Septic System Installation Permit 10707 Whimbrel Drive Ladies and Gentlemen: I am writing to request an installation permit for the reserve trench at the above referenced property. During a visual inspection of the site on May 14', 2013 the test hole monitoring pipe from 2003 was located. The test hole was dry to a depth of 13 feet. It appears that the reserve field can be installed without any modifications to the approved design. We intend to install a diverter valve so that effluent from the Advantex AWWTS can be cycled between the two fields. The location of the diverter valve will be recorded on the record drawings. If you have any questions or concerns, please contact me at 279-3916. Sincerely, 9X)—/ Lars Spurkland, P.E. Civil Engineer 203 West 15`" Avenue Suite 203, Anchorage, AK 99501, Phone: (907) 279-3916 Fax: (866) 354-1597, Lspurkland@gci.net ., Municipality of Anchorage Development Services Department Bunding Safety Division On.Sile Water and Wastewater Program, 4700 S. Bragaw St P.O. Boz 196050 Anchorage, AK 99519-6650 Page of www.d.onCwrage.ak.us (907) 343.7904 ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT Permit Number. PID Number. a L S - 11 - 14. Nene (k_ Wastewater System: ZiNew ❑ Upgrade Aaee.. SG . t_ ABSORPTION FIELD R10ib Rinmaa a 044 —,;7z z�'o J 0OFFe T.arlr W S�Tmrn❑etl ❑Moab ❑plrr LEGAL DESCRIPTION eaFRa" G' TdiO'°° "°" ° °""0•'°°' elaY IO[ S�mWan. Dpm bppFeMom can aq.r PeGF Crewlewm EaMem ppe :& Ta+^r4 Rrge S.cean FM.ee.e rb. unrw We timer LVVM Ft. 26 F Well: New [I Upgrade cnw.am s rwbm Cwr ou Crr.nraem WmMF. A 6. Q. Tar. Dram. Ca b a. Tar eovpeon rM t N A Ft P" Wbnr 89 F Ft a -a FP I 'Sc. 4 4 0 �.1C. Dn..r oW ae.o sMecwr L..w I - -04--1 204 Ft brrw �T}i -o.a Srr-,ac %,cv4 DNF breMe 4t I Z5 l a4 Y�NO DPM Pni Sar 24 S Fr. GvVH-9t7C. Z t n TANK SEPARATION DISTANCES ❑Septic ❑Holding ❑S.T.E.P. g9 )1 »Or r To Septic Absorption LM Holdup w*dPdvre °d1Of Fran Tank Field Station Tank Sewer Line N Got VM116 r 12$ F NJA r.l 14 a coneam.rb ,QP T' L .2 &.F�wra r I Jos, NIA r -t IA, es IA- LIFT STATION Lam. r s.o' � q rs1<► Dr FouMeear I :4T runp an' Iwr r rune arr Yvr et 1gi.rr rrm r C1 or.A - a �+ N .F � � eT wwp a PFrramM eY Ra BENCH MARK, r1 e2 N E.Z.i C.A-yr YO t(M.40Ft Englrm_ A4 p0 Inspections performed by: L155dr— Oates: 10 lL'-2q--64 2ne .. Development Services Department Approval 6Gc �� rswArt x Re +cs �i wed and approved by ' Date: L& j �i,;ifgf -I= ��, E m 0�1� 'OFESSIa000�o PERMIT NUMBER: 4; , / II SW040341 NOTE: % ` „ ALL WELL AND SEPTIC INFORMATION DEPICTED ON THIS ry , �♦r �. I DRAWING WERE DERIVED FROM MOA RECORDS. THEIR APPROXIMATE •I ` 1 LOCATION HAS BEEN FIELD VERIFIED, HOWEVER A PROFESSIONAL SURVEYOR WILL NEED TO LAYOUT THE PROPOSED INSTALLATI N �� TO AVOID POTENTIAL CONFLICTS. PARCEL ID NO. I•, 015-112-14 5 , `; , PtGE 1 OF 4 o I Ei j `. SCALE: 1'=100' 10' TO"— ! El" Ev t 109 CS tk 179.89 120.00 190.00 109.89100 M6 — 10' UH Er t 1�1'^ / m a ��s �•m LOT 11 rn m SHELL NO. 1 / o $ 12 LOT 11 LOT _ _TI SHELL NO. 2 SH NO. � `/ T DELL NO. 1 • 179.87 i 120.00 / f90.0T 10 1088 � (82-288 I I SHELL NO. 1 1I \ '• I I LOT L \ g I g LOT 2 / . Lor 21 \ g SHELL N0. 2 g $ SHELL N0./2 ♦►-�� SHELL NO. 1 0 • / \ 10, Uli Coot _ .-►(e\ ♦ .ham f • 179.86 % %M. 109.86—LOT 09.86LOT S / W %%4 11 1 SHELL NO.2 /� / 1 > �< ♦ ♦ g LOT 3< L♦�) LOT 9 i g ,_LOT 3 I $I / �-/1 • g o SHE N 2 Y ) SHELL,146. 1 a SHELL N0. 1 `� \ •1 I P' 120.00 'r \ pxoNI I �I/ ,\ . /.♦hr c'Wmm . g \,• II�yLTO_SED� 51YS7EM '.�4a �`♦ ry� ov,•\ Q 109 119.84 64 LOT 4 or, yTEx<j♦"DVN 448 . D. 1REA)MffN OR X/20 FH LOT4LO78KSERVE S-WDSHELL NO. ' 1$HELL N0. X120 LF DRAINFD1LO/SHELL19000 179.81 5.0 0 PHOU 95.00 \ 0 T95.00 109.83 i v \' .. o I� —i / h ♦4�• ♦v� I N0.' LO\ 7 'LOT 6 SHE 5 b r $ / SMELL NO. 1 SHELL N0. 1 HCIL N0. • ♦ \ SHE N0. 1• $a `9.81 1 n ^ I _}�\\ •l . � � to SHE 4L N0. • \ 7r. / I -j tP�E ... s �r t 7 \ J'f�\ 30.00 9 ^ 95.00 I�.• .•"— •.* O'MALLEY \ ROAD � � / / / ; BRIAN T. HARTEN NO. 10068 -CE STH CONSTRUCT/ON, LLC P.O. BOX 110358 ANCHORAGE, ALASKA 99511 PHONE: 336-3447 pBOfESg10N�� AS -BUILT LOT 4, SHELL #2 SUBDIVISION OVERALL SITE PLAN NOR. 1'.100DATE: O6/15/OS ' GRIDS: 2536 1 SCALE: VER. NTS SHEET OWNCR: $I% -M CEDAR HOMES � J PERMiy 1•fUMBE SWO40341 / ,P9CRCE1/I6NO. 015,f12-14 PACE 2OF4 C ;CALE: 1'=30' THIS CLEAW BY ALAWCA .ON 9R/04. T BY JEFF GA! TWE WELL k \ LOT 4 SHELL NO. 2 WI 11l — ..170.00. — .. — . ur�OCATE>i LOT 4 LoocATIOUERANDC'WASAJ ELL N0. 2 LDI, RLS, TO LAY OUT SEPTI STS � J X m 21 O O 6 0 IN-HOUSE GRINDER PUMP (SEPTIC AREA — 0 I �- 0 NOTES: 1. ALL LLL ANI SEPTIC INFORMATION �HOWN IS FROM MOA RE ORDS. \ FIELD VERIFY ALL SEPERATION \\ DISTANCES. LAIC? OUT BY RLS. \\ 2. CONTRACTOR SMALL GRADE \ ALL ISSLOPES WITHIN 50' OF PRIMARY AND RKSERVE \ DRINKJFIELDS SO J} AT THEY ARE'<25X ALL SL RJG 1\ \ I 1 \ II \ I I�• I i `SEPTIC AREA / I e11VAMTrV SLOPE /SiLOP I2-5X , 51207 TH BTH CONSTRUCT/ON, LLC P.O. BOX 110358 ANCHORAGE. ALASKA 99511 PHONE: 336-3447 TREATMENT SYSTEM / I/ RESERVE DRAINF,IELE 5' X 20' NOT CONSTRUC D K\ I o. • \\ I PRIMARY DRAIN&D• 5' IX 20' I I :OMTI/ I 5_..�. 10' (MIN) 9.00 • I Go I _ -14 ................. 9 q BRIAN T TEN NO 8 :• e 1 fj�'�lFq •• • •. :s. E�v���r AS -BUILT LOT 4 SHELL #2 SUBDIVISION SEPTIC SYSTEM DESIGN HOR. 1'-130' DATE: 06/15/05 OWNER: 51%-M CEDAR HOMES GRIDS: 2536 2 SCALE: VER. NTS SHEET \1 J \� LOT 5 \ SHELL NO. 2 \ Co I \ TANK C/O 398 �\ 2&9 MANWAT 468322 \ DOUBLE C/O 443 \j \ I t3 S MT 2 698 4@2 1 LLELL / 361 42A I BTH CONSTRUCT/ON, LLC P.O. BOX 110358 ANCHORAGE. ALASKA 99511 PHONE: 336-3447 TREATMENT SYSTEM / I/ RESERVE DRAINF,IELE 5' X 20' NOT CONSTRUC D K\ I o. • \\ I PRIMARY DRAIN&D• 5' IX 20' I I :OMTI/ I 5_..�. 10' (MIN) 9.00 • I Go I _ -14 ................. 9 q BRIAN T TEN NO 8 :• e 1 fj�'�lFq •• • •. :s. E�v���r AS -BUILT LOT 4 SHELL #2 SUBDIVISION SEPTIC SYSTEM DESIGN HOR. 1'-130' DATE: 06/15/05 OWNER: 51%-M CEDAR HOMES GRIDS: 2536 2 SCALE: VER. NTS SHEET \1 J HOUSE SIZE: 4 BEDROOMS SOILS PERCOLATION RATE: < 1 MIN ANCH, THEREFORE UTILIZE A 2' SAND FILTER. ASSUME SAND FILTER HAS A PERCOLATION RATE OF 1-5 MIN ANCH. ABSORPTION AREA: ADVANTEX SYSTEM HAS A CATEGORY III ALLOWABLE APPLICATION RATE WHICH IS 6 GPD/SF. 4 BEDROOMS X 150 GPD/BEDROOM = 600 GPD 600 GPD 100 SF 6 CPD/SF TRENCH LENGTH = AREA WIDTH = 100 SF 5 FT PERMIT NUMBER: SW040341 PARCEL ID NO. 015-112-14 PAGE 3 OF 4 NO REDUCTION FACTOR AVAILABLE FOR CATEGORY III LOADING RATE U = 20 LF a w DOUBLE TANK CLEAN011T9 �Y 4' MONITORING TUBE a (TYPICAL) C)l 1` -,—d ------------ - 5' NDE - NOTE TWE PRESSURE LINE FROM THE LIFT STATION TO THE SEPTIC TANK WAS FITTED WITH A 5 WATT/FT SELF-LIMITWA FEAT TRACE AS ADDITIONAL FREEZE PROTECTION. 4" PVC CLEANOUT, TYPICAL 4" PERFORATED DRAINFIELD PIPING -----------� I 1 O 1 L— — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — - -I 20 FEET LONG - 1 ELEV • 10'5.92 PLAN VIEW MT /— NATIVE BACKFILL FINAL GRADE, MOUND TO PREVENT PONDING AFTER SETTLEMENT Y BOARD FOAM SILT BARRIER, AMOCO 2002 OR EQUAL. TEMPORARY BENCH MARK (TBM) TOP OF NORTH NEIGHBOR'S REAR DECK/PORCH. ASSUMED ELEVATION . 100.00 -3ID 6" OF SEWER ROCK i �� OF-,44q\\I ELEV . 10238 -y.$ -313 % •t�.••'• �[j� ci1,f. 11 ELEV • 10188 -y, (f -4D ,. ,•.,�,. 6" OF SEWER ROCK *��•49TH l7CT 9 olf !�V • �* •; "•�; _ ;a 24" OF FILTER SAND �,,.♦x.vyy.q{�,,,,� ELEV . SSW -j4 -bID' •; ; BRIAN T. 8 -CEN �- 5 FEET WIDE -� �1 t,fc f NO 10068- � ;�10 1 6 -Trio •� i `1\', Fo PROFESSIOH�� -•� BTH CONSTRUCT/ON, LLC P.O. BOX 110356 ANCHORAGE. ALASKA 99511 PHONE: 336-3447 AS—BUILT LOT 4, SHELL #2 SUBDIVISION SEPTIC SYSTEM DESIGN CALCULATIONS AND DETAILS NOR. 1""40' GATE: 06/15/05 GRIDS: 2536 SCALE: VER. NTS SHEET f 4 ONNER: 5x -M CEDAR HOMES PERMIT NUMBER' SW040341 AdvanTeX Treatment System. 6" SCH40 PVC ADVANTEX AX20 FILTER POD AX 20 Series -Mode la CLEANOUT TOP RBV ELEV. - 10359 PARCEL IO N0. 015-112-14 30 -INCH INSULATED RISER PACE 4 OF 4 ELECTRICAL CONNECTIONS TO BE PERFORMED BY A OUALIFIED. CR LICENSED ELECTRICIAN. aE#ZrCtLiaOgiRCt00� � BTERRISW 80N EL G 2" VENTS RETURN LINE 1 TO DRAINFIELD 6" SCH40 PVC 1 CLEANOUT W/ 2" VENT 6" JIM CAP FINAL GRADE. PROVIDE ADVANTEX AX20 POSITIVE GRADE AWAY FROM FILTER POD ADVANTEX INSTALLATION. 6" PVC COUPLING TOP TAMC ELEV • 101.50SOLVENT WELDED TO OP MANWAY ADAPTER TANK. ._.... ELEV • IOLW INLETyyb�-tt^l-R OR AN r —� 2" 40 PSI DIRECT BURY BOARD FOAM __- - _ _ _ _ _ _ _ _ TO BE INSTALLED ABOVE SEPTIC TANK AND TO EXTEND 4 FEET BEYOND THE EDGE OF TANK IN ALL DIRECTIONS EXCEPT DIRECTLY 4 BEDROOM UNDER THE ADVANTEX F�B6'`f�55 TANK FILTER POD. THIS WILL ALLOW $� HEAT LOSS FROM TANK TO REACH THE FILTER POD. OPTIONAL SLIDE A SECTION OF 6" SCH40 PVC OVER INLET PIPING TO PROVIDE SHEAR PROTECTION FOR PIPE BETWEEN EDGE OF EXCAVATION AND TANK CONNECTION RM CONST IAMON, LLC P.O. BOX 110358 ANCHORAGE, ALASKA 99511 PHONE: 336-3447 BOTTOM OF TANK ELEV - 9b.IT AS -BUILT OF, gCTHI* 9s�*lll ...................... BRIAN T. HARTEN s� "•, NO. 10068 -CE Ii,\\� pROFES310��r LOT 4. SHELL #2 SUBDIVISION ADVANTEX UNIT DETAILS HOR. NTS DATE: 06/15/05 CRIDS: 2536 SCALE: HER. NTS SHEET 1 OWNER: SIX -M CEDAR HOMES From +19078308507 Thu May 19 17:37:14 2005 Page 1 of 1 DJG Inspection Report Municipality of Anchorage, Building Safety Division 4700 South Bragaw INSPECTION: VOICE 343-8300 INSPECTION: FAX (907)249-7777 INFO: 343-7982 Name kovin Permit 05-8078 Address 10707 WHIMBREL DR Phone 2501100 Legal LT 4 Inspection Date 5/2 012 0 0 5 AM Subdivision SHELL #2 Comments or Directions Septic Lift Thanks Kovin Inspection Retro Electrical ReInspsatlon N NO NONCOMPLIANCE OBSERVED [] CORRECTIONS ESSENTIAL AS EXPLAINED BELOW WILL RE-EXAMINE AT NEXT INSPECTION [] DO NOT CONCEAL UNTIL REINSPECTION 1 COMMENTS: (for Inspector use only) Inspector ✓ /r �J w%' 4 4 /�// i i Date: " �/ Mayor Municipality of Anchorage Department of Health and Human Services 825 V Street P.O. Box 196650 Anchorage, Alaska 99519-6650 httplhn d.anchorage.ak.us Permit Number: #SW 40341 Date of Issue: 08/16/04 Parcel Identification Number: 015-112-14 Date Started: 12-01-04 Date Completed: 12-23-04 !s welf located at approved permitloca{ion? ® Yes ❑ No Legal Description: Lot 4. Shell Sub. #2 Property Owner Name & Address: Matt Mathews 2804 Northem Lights Anchorage, Alaska 99517 -Dorehole'Data: Soil Type, Thickness & Water Strata 'Depth (ft) From To Method of Drilling -ED aur rotary -E] cable toot Casing type: steel Stick-up 0 2 Wall Thickness: .250 inches silt 2 5 Diameter: 4 inches Depth: 289 feet gravelly s& 5 Y9 Liner* Type: silt cobD y grave! cobbJygraveJ silty sand si! cobbl ty y gravel 29 SS 96 115 65 86 115 . 159 Diameter: inches Depth: feet Casing stickup above ground: 2 feet Static water level (from ground level): 204 feet Pumping level: 289 feet alter 2 hours pumping 20 gpm silt 159 185 Recovery Rate: 20 gpm gravelly sill 185 191 Method of Testing:tatm cobbly gravel w/bldrs 191 220 Well Intake OpeningType: gravelly sandy silt silt silty water sand &gravel silt water sand & gravel 220 260 265 272 286 260 265 272 285 289 ® Open End ❑ Open Hole ❑ Screened Start feet Stopped feet ❑ Perforations Start feet Stopped feet Grout Type: bentonite it 8 Volume: j Depth: Start Q feet Stopped 9 feet Pump: Intake Depth feet Pump size _bp Brand Name Well Disinfected Upon Completion? ® Yes ❑ No I% Method of Disinfection: chlorine tablets Comments: Il/ �s y� ` Well Driller. Alpine Dr Enterprises PO Box � 96 Anchorage Alaska 99511 Attention: The well driller shall provide a well log to the property owner within 30 days of completion and the property .—.... __.1.. ..8 .0 ..__-01. . __..0 I_... d. - �.— .f I1.. 6.1, a 1r._...... 0_ —1.1 .. in 1.— . t.__...�..•... '. Roberti. bell US& 801 West Fireweed Lane • Anchorage, Alaska 99509-1801 (907) 2745257 • FAX (907) 272-7501 June 14, 2005 Municipality of Anchorage Development Services Department Building Safety Division On -Site Water & Wastewater Program 4700 South Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 RE: Lot 4 Shell #2 Subdivision Septic System Inspection Report To Whom It May Concern: F. Robert Bell and Associates (FRBA) was retained by BTII Construction, LLC to provide third party inspection services on the above referenced septic system construction. Two inspections were performed by FRBA. The first inspection took place at on September 27, 2004. The drainfield was excavated and ready for filter sand and washed rock. The inspector was present to witness the installation of the filter sand and washed rock. The second inspection took place on September 28, 2004. The Advantcx tank was installed, and being backfilled with clean sand. A second inspection later in the day allowed the inspection of the filter pod, transport piping and filtrate return line piping. The drainfield piping and connections to the septic tank were also inspected during this inspection. Upon both inspections, we found the construction to be in compliance with the plans and specifications as approved by the MOA for this project. Workmanship and quality of construction were more than adequate. If you have any questions regarding our inspection services, or this correspondence, please feel free to contact me at 274- 5257. Regards, Craig Shavlik , EIT F. Robert Bell and Associates MUNIC1PAL17YOFANCHORAGE J/X Igo Development Services Department On -Site Water & Wastewater Program 4700 South Bragaw Street P.O. Box 196650, Anchorage, AK 99519-6650 (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM /WATER SUPPLY PERMIT Initial Date Issued: Aug 16, 2004 Expiration Date: Aug 16, 2005 Permit Number: SW040341 Parcel ID: 015-112-14 Legal Description:lSHELL-#2 SUBDIVISION LOT 4 Design Engineer: 0836 Brian T. Harten Site Address: NHN WHIMBREL DRIVE Owner Name: MATT MATTHEWS Lot Size: 12000 SO. FT. Owner Address: NHN WHIMBREL DRIVE Total Bedrooms: 4 Permit Bedrooms: 4 ANCHORAGE, AK 99507 - This permit is for the construction of: 0 Disposal Field E Septic Tank ❑ Holding Tank ❑ Privy ❑✓ Private Well ❑ Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specked in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72 ) and Drinking Water Regulations (18AAC80 ). 3, The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 ( 24 hours). ( Not required for a Water Supply Permit only). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. 5. The following special provisions. Due to close proximity of existing wasterwater disposal systems on adjacent properties, the location of waterwater disposal systems on adjacent properties must be field verified prior to well installation. The minimum separation distance between the well and all wastewater disposal systems shall be 100 feet. Received By. Date: \ Municipality of Anchorage • Development Services Department Building Safety Division On -Site Water and Wastewater Program 4700 South Bragaw SL P.O. Box 196650 Anchorage, AK 99519-6650 www.muni.orglonsite (907)343-7904 ON-SITE SEWER/WELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. 01511214-000 Permit Number SW Property owners) Matt Matthews, Six -M Cedar Homes Day phone 244-5270 Mailing address (1) 2804 West Northern Lights, Suite 6 Mailing address (2)�KPW Whtvy1brek QY1 ve� Zip Code ^9V&W CR50'1 Legal description (Lot, Block & Sub'd.) Lot 4 Shell No. 2 Legal description (Section, Township & Range) Lot Size 12,000 Acres/ THIS APPLICATION IS FOR: Number of Bedrooms 4 Sewer Only ❑ Well Only ❑ Sewer and Well [a Water Storage ❑ Sewer Upgrade ❑ THIS PROPERTY CONTAINS: Hot Tub 0 Jacuzzi El Swimming Pool ❑ Water Softening Unit ❑ Therapy Pool ❑ I certify that the above information is correct. I further certify that this application is being made for a Single Family Dwelling and is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) W(''r'r P4TTNE_'j S Permit Fees: o .� ees: 4'1l°Sy' Date of Payment: 0 3 Date of Payment: "AOCL( Receipt Number. 6u l'U, ,i Receipt Number. irs'77t]1_2�1 %SCA.1 (Rev. 12100) BTH CONSTRUCTION, LLC EXCAVATION & ENGINEERING P.O. Box 110358 • Anchorage, AK 99511-0358 PhonelFax:336-3447 • E-mail: bth@gcl.net August 3, 2004 Municipality of Anchorage Development Services Department Building Safety Division On -Site Water & Wastewater Program 4700 South Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 RE: Proposed Well and Septic Design Lot 4, Shell Addition No. 2 Subdivision ADVANTEX TREATMENT SYSTEM To Whom It May Concern: General The proposed 4 bedroom house will be served by a private well and an on-site septic system. One test hole was excavated on this property by the previous owner in June of 2003 by Gamess Engineering Group, a copy of this test hole record is attached. Both the primary and the replacement drainfields have been designed around the 30 foot radius of the test hole. Due to limited space constraints on the subject lot, we are proposing the installation of an Advantex treatment system and 5 -wide trench type drainfield to meet the wastewater disposal requirements of the proposed structure. Comments regarding this design are summarized as follows: Solis See attached soils log which details soil classifications, groundwater observations and percolation test results. Drainfield Design Percolation tests provided percolation rates of <1 minutes per inch at the design depths. The Advantex system has received Category III approval for an application rate of 6.0 GPD/SF which will be used for trench calculations for this system. Trench Design: Number of Bedrooms: Design Flow: 150 GPDBR Max. Application Rate: Absorption Area Required: Total Depth: Effective Depth: Width: Trench Length: 4 X 4 BR = 600 GPD 6.0 GPD/SF 100 SF 3.0 feet (max) 0.5 feet 5.0 feet 20.0 feet (conservative) Orenco Package System The septic tank with the Advantex Treatment System will be manufactured/assembled by Anchorage Tank & Welding to meet the latest design criteria established by Orenco Systems, Inc. This system shalt be outfitted with all the required controls, floats and alarms as required by the Municipality of Anchorage. August 3,2004 Lot 4 Shell No. 2 Well and Septic Design Submittal Surface Waters There are no surface waters within 100 feet of the proposed septic system. Topoaraphv The western half of the lot is principally level, with approximately 5% slope from west to east. The lot then slopes upward toward the southeast comer of the lot, where the proposed drainfield will be located. These slopes are approximately 15 to 20%, with the drainfield site itself incurring minimal sloping. The slopes on the proposed lot will be minimized during construction, and are not a concern for this project. Groundwater and Bedrock No groundwater or bedrock were encountered on the subject property. Closina The development of this property will not preclude the adjacent properties capacity to construct future wastewater systems. I am unaware of any adverse impacts this installation would have on any existing adjacent wells or septic systems. If you have any questions or comments on this design, please feel free to contact me at 230-3992. Regards, Brian T. Harten, P.E., BTH Construction, LLC Attachments: 1. 4 page septic system design package 2. Single Family On-site Wastewater Disposal System Installation Specifications 3. Test hole log dated 6/23/2003 by Jeff Gamess, P.E. BTH CONSTRUCTION, LLC EXCAVATION & ENGINEERING P.O. Box 110358 • Anchorage, AK 99511-0358 Phone/Fax:336-3447 • E-mail: bth@gd.net August 13, 2004 Julie Makela, P.E. Municipality of Anchorage Development Services Department Building Safety Division On -Site Water & Wastewater Program 4700 South Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 RE: Proposed Well and Septic Design Lot 4, Shell Addition No. 2 Subdivision ADVANTEX TREATMENT SYSTEM Dear Ms. Makela, Attached please find my revised design drawings for the above referenced property. Additionally, I have addressed all of your plan review comments, more specifically as follows: 1. Original signature/stemp missing on soil log percolation test. Mr. Matthews has obtained an original copy of this soil log from Jeff Gamess, P.E., and it is attached to this submittal. 2. Please show location of drain field monitoring tubes and cleanouts on page 2 of the septic system design. These items have been shown on the design drawings. 3. Missing the maintenance agreement for Advantex Treatment system. typically submit this document with the as-builts and request for HAA. However, per your request, Mr. Matthews has completed the form and a copy is attached. Please note this form will need to be transferred to the new property owner as the intention is to build this house for sale. 4. Please provide measured distances to all wastewater disposal systems and animal enclosures or containment areas within 200 feet of the proposed on-site wastewater disposal system and water well. have added additional information regarding adjacent wastewater disposal systems, animal enclosures or containment areas within 200 feet of the proposed on-site water and wastewater system. The majority of this information was acquired through MOA record drawings, with field verification as to their approximate location, as is standard practice. Any measured distances required can be scaled from these drawings. Please note that due to space constraints on the subject property, I have required the on-site water and wastewater components for this property to be laid out by a professional surveyor to eliminate potential conflicts with the adjacent properties. 5. The lift station must be located no less than 100 feet from the proposed and existing private water wells. This requirement applies only to external, wastewater lift stations. This system utilizes a small sump with grinder pump to transport the wastewater to the septic tank/Advantex system. As this sump is August 13, 2004 Lot 4 Shell No. 2 MOA Design Review Comment Response located within the building envelope, it is not subject to the separation distances required for true lift stations. 6. Is reserve drain freld going to be constructed during Initial wastewater disposal system Installation? If so, please Indicate location of drain field diverter valve. No, the reserve drain field is not scheduled for construction at this time. 7. Usual observations and field measurements during site visit Indicate that existing cut -bank located west of proposed drain field may be greater than 25%. The drain field must be located a minimum of 50 feet uphill from any cut -bank or change In slope of 25% or more. am aware of the slope set back requirements. It is my intention to bring this slope into conformity during construction of the drain field. A note specifying this requirement has been added to the design drawings. hope this satisfies any questions or concerns you have regarding this design. If you have any further questions or suggestions, please feel free to contact me at 230-3992. Regards, Brian T. Harten, P.E., BTH Construction, LLC 10' Tel.c k EI.c E.ml 179.89 jLLj--1 / m / LOT SHELL N0. 2 179.87 I I LOT SHELL NO. 2 \ 179.66 4♦ I / 1900 n 1 /f Y�lY SHELL NO. 2 \ / LOT 6 v`v$ LOt 7 ' SHELL N0. 1SHELL NO. 1 h , a �; ' • Li''S8ry ' c 4Y� Y E �Lj is SH N0. Q 119.84 • F9.81 I bl em � h l 14f h `? 0LOT 10' Tel.c k EI.c E.ml 179.89 jLLj--1 / m / LOT SHELL N0. 2 179.87 I I LOT SHELL NO. 2 \ 179.66 / I 10' Tel.c k EI.c E.ml 179.89 jLLj--1 / m / LOT SHELL N0. 2 179.87 I I LOT SHELL NO. 2 \ NOTE: 1 ALL WELL AND SEPTIC INFORMATION DEPICTED ON THIS DRAWING WERE DERIVED FROM MOA RECORDS. THEIR APPROXIMATE LOCATION HAS BEEN FIELD VERIFIED, HOWEVER A PROFESSIONAL SURVEYOR WILL NEED TO LAYOUT THE PROPOSED INSTALLATIQ4 TO AVOID POTENTIAL CONFLICTS. 1 SCALE: g8 179.66 / Q / 1900 n LOT /f v SHELL NO. 2 \ / LOT 6 v`v$ LOt 7 ' SHELL N0. 1SHELL NO. 1 h , a bIf L H LL NO.� .q SHELL NO. 1 / a �.. or /1111 W.• Y ` �Lj x SH N0. Q 119.84 • F9.81 I 4 • em � h l I h `? 0LOT 190.00 *8 In ♦ 120.00 1 I SHELL NO. s / c c NOTE: 1 ALL WELL AND SEPTIC INFORMATION DEPICTED ON THIS DRAWING WERE DERIVED FROM MOA RECORDS. THEIR APPROXIMATE LOCATION HAS BEEN FIELD VERIFIED, HOWEVER A PROFESSIONAL SURVEYOR WILL NEED TO LAYOUT THE PROPOSED INSTALLATIQ4 TO AVOID POTENTIAL CONFLICTS. 1 SCALE: g8 1"=100' % 0 LF DRAINFIETD SHELL Q / 1900 n 120.00 190.00 _ v HOJ5.00IIT_95.00 \ / LOT 6 v`v$ LOt 7 ' SHELL N0. 1SHELL NO. 1 h m \ �s>•m LOT 11 a bIf L H LL NO.� .q SHELL NO. 1 / a �.. or - LOT P / -- ` P• r• SH N0. Q `� F9.81 I •OSS ` mos � `1 190.00 / In ♦ 120.00 LOT 10 SHELL NO. 1 s / c c 8 LOT 2 c SHELL NOJ2 X4,1,♦ C � OWALLEY\F / 10 E -rte uS y� � \ \ nJ.Oq w \ %% \ > II<" . \ LOT 3 < L r� LOT 9 Q e SHE N. 2 ;w\ SHELL N6 1 9' 1A20.00 og ' •"_ , 19000 <♦ BTH CONSTRUCT/ON, LLC P.O. BOX 110358 ANCHORAGE, ALASKA 99511 PHONE: 336-3447 ADVANTEX<� 1•'2 M1br OA SYSTEM ,�� ? RY 5-WIDE�i . 8 LF DRAINFlELD•OSp _ ...e r IJ T-RE�VE 5 -MADE LO s 1L % 0 LF DRAINFIETD SHELL Q / 1900 n v HOJ5.00IIT_95.00 \ / LOT 6 v`v$ LOt 7 ' SHELL N0. 1SHELL NO. 1 h I $ NO.� bIf L H LL NO.� � �.. or - ` P• r• F9.81 I `TO> S? `1 / In SNE4L NO. s / 7 \ 30.00 OWALLEY\F BTH CONSTRUCT/ON, LLC P.O. BOX 110358 ANCHORAGE, ALASKA 99511 PHONE: 336-3447 ADVANTEX<� 1•'2 M1br OA SYSTEM ,�� ? RY 5-WIDE�i . 8 LF DRAINFlELD•OSp _ ...e r IJ T-RE�VE 5 -MADE LO s 1L % 0 LF DRAINFIETD SHELL Q / 1900 n HOJ5.00IIT_95.00 / LOT 6 LOt 7 ' SHELL N0. 1SHELL NO. 1 h T\ \ I g 104 8s 109.89 IOO B5 t0' UIN Err,l m OT 1 _ ELL NO. 1 1088 (82-21 I \ BI LOT 21S SHELL NO. 1 \ 10' Ulc E.m! 4109.86 ♦ . I SLOT 3 elry SHE'LL NO. I/ LOT 4 SHELL NO. 1 LOT 5 /FI SHELL NO. 1 �^ gn � • TH ag 11 • BRIAN T. HARTEN ; NO. 10068 -CE PROFESSIDMO� LOT 4, SHELL #2 SUBDIVISION OVERALL SITE PLAN NOR. "-100' DATE: 08/13/04 GRIDS: 2536 1 SCALE: VER. NTS SHEET of OWNER: S% -M CEDAR HOMES � 4 "—OEPTIC AREA — //� 0 I 0 NOTES: 1. ALL LL AN SEPTIC / I \ INFORMATION HOWN IS LOT 4\\ \ FROM MOA RE ORDS. SHELL NO. 2 \ \ FIELDIVERIFY ALL SEPERATION \ DISTANCES. \ / o I 0 \ CONTRACTOR SMALL GRADE ALE: 1"= MOA RECOF CLEANOUT. LOCATE TO PRIOR TO I pe m .. M� i� J LOT 4 IN OFI SHELL LINE 120.00 _ PROPOSED 4 -BEDROOM HOUSE IN-HOUSE I.•:•::•::::: '.:.... GRINDER PUMP \ ALL ISLOPES WITHIN 50' OF \pR114ARY AND R SERVE DRAINFlELDS SOHAT THEY \ A'RE'<257 \ 1 \I \ \\ •; p I \ � SHELL N0. 2 \ �� 9� :1 NO a ,: (—SEPTIC AREA _ SLOPE /SLOPE 2-57. , 07 � 1 / i / RESERVE GRAINFIELD 5' X 20' / D. CID \\ I 0 MT I I THf 1 1.4PRIYARY DRAINFlL), 5' 20' OMT I L— CIO 10, I 10' 9.00 -- 1 1 E_ 0F..Ale��►�, APPROX.`LOCATION 0F HORSE COR"L TO BE RELOCATED 25 SOUTH OF NOR \LOT LINE. \ Bm CONSTRUCT/ON, LLC I LOT 4 SHELL #2 SUBDIVISION SEPTIC SYSTEM DESIGN P.O. BOX 110358 ANCHORAGE. ALASKA 99511 PHONE: 336-3447 HOR. 1'.30' DATE: 08/13/04 GRIDS: 2536 2 SCALE: VER.NTS SHEET of OWNER: $I% -M CEDAR HOMES � 4 \\ •; p LOT 5 \ BRIAN T TEN % \ \\ SHELL N0. 2 \ �� 9� :1 NO a ,: Bm CONSTRUCT/ON, LLC I LOT 4 SHELL #2 SUBDIVISION SEPTIC SYSTEM DESIGN P.O. BOX 110358 ANCHORAGE. ALASKA 99511 PHONE: 336-3447 HOR. 1'.30' DATE: 08/13/04 GRIDS: 2536 2 SCALE: VER.NTS SHEET of OWNER: $I% -M CEDAR HOMES � 4 HOUSE SIZE: 4 BEDROOMS SOILS PERCOLATION RATE: < 1 MIN/INCH. THEREFORE UTILIZE A 2' SAND FILTER. ASSUME SAND FILTER HAS A PERCOLATION RATE OF 1-5 MIN/INCH. ABSORPTION AREA: ADVANTEX SYSTEM HAS A CATEGORY III ALLOWABLE APPLICATION RATE WHICH IS 6 GPD/SF. 4 BEDROOMS X 150 GPD/BEDROOM - 600 GPD 600 GPD = 100 SF 6 GPD/SF TRENCH LENGTH AREA NO REDUCTION FACTOR AVAILABLE FOR CATEGORY III LOADING RATE WIDTH 100 SF 5 FT 0 20 LF a w �^ 4" PERFORATED DRAINFIELD PIPING i Y 4" MONITORING TUBE a 4" PVC CLEANOUT, (TYPICAL) LTYPICAL----------- -----------5' WIDE o e - o 0 0 0 o 0 �I 20 FEET LONG - PLAN VIEW MT � NATIVE BACKFILL FINAL CRADE, MOUND TO PREVENT PONDING AFTER SETTLEMENT 2" DIRECT BURY BOARD FOAM SILT BARRIER, AMOCO 2002 OR EOUAL. R -s- .I OF SEWER ROCK Illim• 60i W •+:+i . Mr•:s:!. miw—mL 24" OF FILTER SANI �- 5 FEET WIDE -� BTH CONSTRUCT/ON, LLC P.O. BOX 110358 ANCHORAGE, ALASKA 99511 PHONE: 336-3447 ,��• OF..q�9�11 49TH •9Tk 1� :....... ......... .:.. BRIAN T. HARTEN / 1 9�, �,• NO. 10068 -CE 111,\`EO PROF SSIONI'�?' LOT 4, SHELL #2 SUBDIVISION SEPTIC SYSTEM DESIGN CALCULATIONS AND DETAILS NOR. 1•_40• DATE: 08/13/04 OxNER: SX -M CEDAR HONES GRIDS: 2536 3 SCALE: VER. NTS SHEET /Of 4 ADVANTEX AX20 FILTER POD AdvanTW Treatment System CLEANOUT 6' SCH40PVC AX 20 Series - Mode 1a 2" VENT 6" SCH40 PVC CLEANOUT W/ 6" JIM CAP 6" PVC COUPLING SOLVENT WELDED TO TANK. INLET VENT ADVANTEX AX20 FILTER POD 4 BEDROOM FIBERGLASS TANK OPTIONAL SLIDE A SECTION OF 6" SCH40 PVC OVER INLET PIPING TO PROVIDE SHEAR PROTECTION FOR PIPE BETWEEN EDGE OF EXCAVATION AND TANK CONNECTION BTH CONSMIMON, LLC P.O. BOX 110358 ANCHORAGE. ALASKA 99511 PHONE: 336-3447 INSULATED RISER ELECTRICAL CONNECTIONS TO BE PERFORMED BY A QUALIFIED, LICENSED ELECTRICIAN. TRATE RETURN LINE ORENCO LIFT STATION PACKAGE AS SUPPLIED BY ANCHORAGE TANK. (IF REQUIRED) —. TO DRAINFIELD FINAL GRADE. PROVIDE POSITIVE GRADE AWAY FROM ADVANTEX INSTALLATION. 2' 40 PSI DIRECT BURY BOARD FOAM _ TO BEINSTALLED ABOVE SEPTIC TANK AND TO EXTEND 4 FEET BEYOND THE EDGE OF TANK IN ALL DIRECTIONS EXCEPT DIRECTLY UNDER THE ADVANTEX FILTER POD. THIS WILL ALLOW HEAT LOSS FROM TANK TO REACH THE FILTER POD. `\ ��`• OF"AZXqs 11 Irt.�4`tsY.L�crrt.. BRIAN T. HARTEN 9 NO. 10068 -CE Q LOT 4, SHELL #2 SUBDIVISION ADVANTEX UNIT DETAILS NOR. N7S DATE: 08/13/01 GRIDS: 2536 4 SCALE: VER. NTS SHEET of ONNER: $I% -M CEDAR HOMES ,-of 4 DEPTH TO GROUNDWATER DATE DRY 6/16/2003 DRY 6/23 2003 ♦ / 0064 I 1 E POGEO c \\ �5EP11C I AREA ALASKA �cn� Re�G PASO N VATER 4.J1. NVASTIENVATER � /��7 ♦ I / CONSULTANTS, INC. + . i/ I „ _ / LCYT SOIL LOG - PERCOLATION TEST 0 SHELL S%D LEGAL DESCRIPTION: � � SHELL SUBDIVISION 12; LOT 4QO P e e A. ness.- WILMA SPEARIN 6/16/2003 O�0'•.• —7953 ,,• `Fpp PERFORMED FOR: DATE: 0/sem• '• ........•'�p4� DEPTH(feet) ==_= ORGANICSTEST oo`oo���oo •�' HOLE 1 1 •�•• ••••••• PAGE 1 OF 2 ••� �! SOIL CLASSIFICATIONORGGWS 2 •�..�,• 3 ..;•,• — — GP ML •� �• : ��'••'• GM CL 4 • •�•• e' GC OL •...• .. > . SW MH 5--o ...• • • • • SP CH �.'•':• . ••. SM x : OH 6 ..;.•.• •. ••.• SC 7 ••..• 8— ••• ., �.•. 9 •••• .•. ••'� 10 ••••• ,� ...,. ' •••• 11 .•;.�.• 12 .•;.* ,• •'••• 13- 3 15 15 16- s171819 17- 18- PERCOLATION RATE <1 (MIN./INCH) PERC. HOLE DIA. 6 (INCHES) 19 TEST RUN BETWEEN 7.5 FT. AND 8.0 FT. 20 A FOUR HOUR PRESOAK WAS PERFORMED: ❑ YES ENO SOILS LOGGED BY: SUSAN OSWALT PERCOLATION TEST PERFORMED BY: JOSEPH MARCHEITI COMMENTS: AKWWC, INC. 1, JEFFREY A. GARNESS, CERTIFY THAT THIS WAS PERFORMED IN ACCORDANCE PERFORMED BY WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE: DEPTH TO GROUNDWATER DATE DRY 6/16/2003 DRY 6/23 2003 ♦ / DATE READING CLOCK TIME NET TIME (MINUTES) WATER LEVEL READING NET DROP (INCHES) 6/18/2003 ♦ / ♦ I 1 E POGEO SHELLS �2 \ \\ �5EP11C I AREA �cn� Re�G PASO i � /��7 ♦ I / I rSEPTIC � i/ I „ , / LCYT SHELL S%D � � DATE READING CLOCK TIME NET TIME (MINUTES) WATER LEVEL READING NET DROP (INCHES) 6/18/2003 E POGEO Re�G PASO BTH CONSTRUCTION, LLC EXCAVATION & ENGINEERING P.O. Box 110358 • Anchorage, AK 99511-0358 PhonalFax.336J447 • E-mail: bth@gcinet Single Family On-site Wastewater Disposal System Construction and Material Specifications Subject Property: Lot 4, Shell No. 2 Subdivision Date: August 3, 2004 General: The scope of the project includes the procurement and installation of a 4 -bedroom capacity Advantex Treatment System at the location depicted on the attached site plan drawings. The scope of work also includes the installation of a new drainfield comprised of 1 trench, 5 feet wide x 20 feet long with 2 feet of filter sand and 0.5 feet of effective septic rock below the distribution piping. The location of the drainfield is shown on the attached site plan drawings. The total depth of the field will be 3.0 feet below existing ground. All components of the proposed septic system must be constructed a minimum of 100 feet from any surface water or water wells in the area. A minimum of 4 feet of earthen cover is required over the septic tank and a minimum of 3 feet of earthen cover is required over the drainfield. In addition to the required earthen cover, 2' thick, 40 psi, direct bury board foam shall be installed directly over all installed piping. 2. Construction shall be in accordance with the approved site plan and design drawings and any special provisions noted on the Municipal well and/or septic permit. All materials, components, workmanship and construction practices shall comply with the Municipality of Anchorage's latest ordinances regarding wells and septic systems, as well as MOA, Development Services Department, On-site Water and Wastewater Program (DSD) policies. 3. The contractor is responsible for obtaining all underground utility locates, layout of the proposed system and verifying and maintaining all required separation distances to lot lines, surface water, wells, steep slopes, etc. 4. The property owner shall be responsible for final grading any depressions formed from settlement of the backfill material. The property owner is also responsible for revegetation of all areas disturbed by septic system installation activities. 5. Contractors installing wastewater disposal systems must be certified to do so by the MOA DSD, On -Site Water and Wastewater Program. Property owners installing their own systems must receive advanced approval from MOA DSD prior to system installation activities. 6. The contractor shall ensure that ALL materials being used are in compliance with the most current guidelines established by the Municipality of Anchorage. Please refer to 'Standards and Specifications for Component Parts and Materials Used in Construction of On -Site Wastewater Disposal Systems', dated December 2000, as provided by MOA DSD, On -Site Water and Wastewater Program. Septic Tank Installation: 1. A new septic tank, of the size specified in the design drawings, shall be procured from a qualified manufacturer/supplier if the existing septic tank is found to be defective. Construction shall include two 4' diameter cleanouts for pumping access. In the case of Advantex Treatment Systems, refer to Lot 7A Block 1 Drake subdivision Notes and specifications March 31, 2004 Page 2 of 4 the attached design drawings for the size and type of tank to be installed. Installation of these systems will follow the installation procedures outlined in the Advantex installation manual. 2. The burial rating of the tank shall be adequate for the actual burial depth encountered. 3. The tank shall be level and sufficiently bedded to prevent settling or shifting of the tank. 4. All standpipes on the tank shall extend a minimum of 12 inches above the final grade. 5. Tanks installed with less than 4 feet of cover shall be insulated. See general note 1. 6. The sewer service line from the house to the tank shall have a minimum slope of 2% unless prior approval is obtained from the engineer. 7. The inlet and outlet lines form the tank shall be bedded in drainrock or the soil shall be adequately compacted to prevent future settlement of the soil. 8. Septic tank inlets, outlets and cleanouts shall be fitted with watertight couplings (Femco, Caulder, or equal.) 9. A clean-out shall be installed 1 to 4 feet from foundation. 10. Post tank clean -outs shall be installed per MOA requirements. Does not apply to pressurized lines. 11. In areas with high groundwater, the septic tank shall be sufficiently anchored to resist buoyant forces when there is not adequate soil cover to resist the uplift force. The contractor shall refer to the engineer for direction regarding this matter. 12. The tank backfill shall be graded sufficiently to ensure positive drainage away from the tank. 13. All holding tanks and lift stations shall have an audible and visible alarm inside the residence being served. 14. All lift stations shall be wired in compliance with all MOA guidelines and the Uniform Electrical Code. A municipal electrical permit and inspections must be obtained in areas where required by the MOA. 15. The contractor shall verify that the septic tankflift station water well, 150' from any class 'C' well and 200' from separation distances must also be maintained. DrainNeld Construction: is a minimum of 100' from any residential any community water wells. Additional The drainfield shall be constructed per the dimensions outlined in the design drawings. If any discrepancies are noted, contact the Engineer immediately for clarification. 2. All drainfield trenches shall be installed parallel to slope contours. 3. The bottom of all trenches shall be within 2" of level. If the sidewalls or bottom of the excavation become smeared, they must be raked or scarified prior to placement of drainfield filter sand or septic rock. Lot 7A Block 1 Drake Subdivision Notes and Specifications March 31. 2004 Page 3 of 4 4. A minimum of 2 feet of accepting soils is required below the drainfield rock for a 5' wide trench. The contractor shall verify this condition prior to placement of the septic rock. All pockets of unacceptable materials shall be removed and replaced. 5. The trench or bed must be a minimum of 5 feet from the test hole excavation. 6. All distribution piping must be installed level with the perforations facing downward, atop a level bed of drainfield rock. Septic rock shall then be placed atop the distribution piping to provide a minimum of 2 inches of cover above the piping. The septic rock shall not be 'pyramided" over the top of the pipe, but shall be installed level across the entire width and length of the trench or bed. 7. A silt barrier or geotextile fabric must be placed between the drainfield rock and the native backfill. Installation of rigid board foam DOES NOT eliminate the need for the silt barrier. The silt barrier shall cover the entire drainrock surface. 8. Monitor tubes must be 4' in diameter and installed in the locations depicted on the design drawings. The portion of the monitoring tube below the septic rock must be perforated and the portion above the septic rock shall be solid. The monitoring tube shall extend a minimum of 12" above finished grade. 9. Backfill over the final gravel layer must not be less than 2 feet. Insulation must be installed when the backfill depth is less than 3 feet. 10. Drainfield trench backfill shall be mounded to prevent depressions from forming due to subsequent settlement of the backfill material. Grade areas adjacent to the drainfield to direct surface runoff away from the absorption trench. 11. The contractor shall verify that the drainfield 150' from any class 'C' well and 200' from distances must also be maintained. Materia! Spec cations: is a minimum of 100' from any residential water well, any community water wells. Additional separation 1. The contractor shall ensure that ALL materials being used are in compliance with the most current guidelines established by the Municipality of Anchorage. Please refer to 'Standards and Specifications for Component Parts and Materials Used in Construction of On -Site Wastewater Disposal Systems', dated December 2000, as provided by MOA DSD, On -Site Water and Wastewater Program. This document details the basic standards and specifications for the following septic system components: Septic tanks. Lift Stations. Holding Tanks. Pipe Materials. Insulation. Lot 7A Block 1 Drake Subdivision Notes and Specifications March 31, 2004 Page 4 of 4 Inspections: 1. A minimum of two inspections are required by the Municipality of Anchorage. These inspections must be conducted under the supervision of a Professional Engineer licensed to practice in the State of Alaska. The first inspection must take place upon completion of the excavation for trenches, beds or pits and before the installation of any filter sand or drainrock. A septic tank may be set in place, but may not be backfilled. A tank may be set in place, but cannot be backfilled. The second inspection must be conducted after the placement of the filter sand, drainrock, monitoring tubes, standpipes, cleanouts, filter fabric and insulation. No backfill should be in place at the time of inspection. 2. The contractor shall provide a legible copy of all field notes relating to system layout and construction to the Engineer for use in preparing the record drawings for the proposed septic system. 3. The contractor shall coordinate all inspections with the Engineer. A minimum of 24 hours notice is required prior to start of construction. If necessary, a pre -construction meeting will be held on-site. -Municipality of Anchorage Development Services Department • +� "_ ; , .,Building SafetyDivision + `� ,.Onsite Water and Wastewater Program 4700 South Bragaw St. 5 " " P.O. Box 196650 .:Anchorage, AK 99519-8850 www.muni.org/onsite (907) 343-7904 ON-SITE SEWER/WELL SUBMITTAL COMMENT SHEET To: BTH Construction: LLC Legal description:'ShellAddition N6.:2 Subdivision. Lot 4 attached paperwork has been reviewed and Is being returned for the following reasons r ✓The : ® Original signature or stamp missing onaoil loa-eereolotion test k❑ Calculation error in design � -. ❑ 'Addittonai.&oils mformatiRn needed_ _ :, Water monitoring vresulWinaiiequate. _ ,.: ❑ ; Discrepancy in information submitted. `• To ra hoc Information mi§sin or inad uate ❑ ' Pog p— g---� ® ,.Incomplete; missing Please show location of dram field monitoring tubes and eieanouts on 'page 2 of the septic system design. - tt i ✓ .. : ® ete;na AdvantexAncompiTreatment System . ❑ Additional adequ gy test4nf6nnation needed _ ❑ " , Water sampie,unac oeptable: ®' Measure dlproposed ,distanceS%dimensionsmissing Plcaie provide •measy red distances 11 to all wastewa er des" 3a1 e s and ani bi.-enclosui-es or contalh eat areas :within 200 eet o the oroobs =d ons t�Tfc }vdsf tyotir di3oosa. I iyem.and wafer we I ❑ 1;0*6ns o'a(I soils; p�t;olatign ant- wgtor monitoring tests not shown [� 'Proposedsyiqem tope -leap for n s sails into . . ❑ Weil log regtr�ted ❑ ; omission in narrative. Qrisuffieloilfiillovertink.pf eld.,�., ® `Other. 1:j�+,he diff tafion `urgust ,be located no less than 100',feet from the or000sed and existing private :water wells -2. 3s reserve drain field golno to be constructed during initial , wastewater distiosal system lnstallatiion? Is ao. 'please indictate location of Broin `field I dives r valve'-. 3 isunl observations and field easure en sduri site visitindicate that existing cut -bank locate west of proposed drain field may be greater jhan 25' -percent. The a. drain .field rout be located n minimum ofa0 feet uphill from any cut -bank or change jn, slope a of 25,pement or more, + Name of reviewer:: Julie Makela, P. E, Date: 8/5/2004 Piease`supply`the necessary information and re=submit your request. ` LEAVE THIS FORM ATTACHED TO THE PAPERWORK , i , BTH CONSTRUCTION, LLC EXCAVATION & ENGINEERING P.O. Box 110358 • Anchorage, AK 99511-0358 Phone/Fax:3363447 • E-mail: bth@ganef September 1, 2004 Mr. Dan Roth Municipality of Anchorage Development Services Department Building Safety Division On -Site Water & Wastewater Program 4700 South Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 RE: Request for Lot Line Waiver Lot 4, Shell Addition No. 2 Subdivision ADVANTEX TREATMENT SYSTEM Dear Mr. Roth: We are requesting a lot line waiver for the above, permitted on-site water and wastewater system, in order to construct the primary drainfield within five (5) feet of the east and south lot lines of the subject property (see attached sketch.) This request is due to the limited space available for the primary and reserve drainfields on the small lot. While it is possible to install the system as designed, we feel it would better serve the future owner to maximize the area available in the event that a replacement system would be necessary. have evaluated the potential impact on the adjacent properties, as shown on the attached sketch, and am unaware of any adverse impacts this construction would have on the adjacent properties to construct replacement wastewater facilities in the future. Even if the adjacent properties were to seek and obtain 5 foot lot line waivers, all wastewater disposal fields would still maintain the minimum separation of ten (10) feet. If you have any questions or comments regarding this request, please feel free to contact me at 230-3992. Regards, Brian T. Harten, P.E., BTH Construction, LLC LOT 4 SHELL NO. PROPOSED 4 -BEDROOM 1 1 I I I 2 1 7. / 1' F �I TREATMENT SYSTEM HOUSE / I IN-HOUSE ` ' /� ;RINDER PUMP 5.0' D. 0 \ / \ v °! 10.0' \ SLOPE // O MT / 1�-20X// �PRIM JRY DRAINFIELD. TH / � 5' x 20' RESER4,6RAINIELD. .0. / / \ 5'X20' O T / =� 120.00 \ .. _c0 5.a' \ HORSE CORRAL. �\ APPROX. LOCATION LOT 5 \ SHELL NO. 2 \\ i� i \ / SURVEYE6 ,LOCATION / OF SEPTIC TANDPI�ES. TRENCH/TANIk CONFIGURATION IS ASSUMED AS\ HOWN. / ISO. \ \ {{ / Coq lYs\ I %A/Y, l (( RAO�S c \ � / O I O I I 1 LOT 8 I SHELL NO. 1 I I 9500 1 IREQUEST A LOT LINE WAIVER TO REDUCE SETBk1CK FROM EA AND SOUTH LOT kINES FROM 1 \x. _ TO 5'. �49TH�'s�*1�1 .... .............. —'% BRIAN T. HARTEN : 9 •• N0. 10068 -CE BTH CONSMICT/ON, LLC P.O. BOX 110358 ANCHORAGE. ALASKA 99511 PHONE: 336-3447 \ LOT 7 \ SHELL NO. 1 \ \ \ LOT 4 SHELL #2 SUBDIVISION LOT LINE WAIVER REQUEST HOR. 1'-20' 1DATE; 09/01/04 (GRIDS: 2536 iSHEET T Of/ SCALE: VER. NTS OWNER: SIX -1 CEDAR HOMES Municipality of �S" 1 P.O. Ik)x IIXR&) - Anehnnige, Alaska!XFi1946N) • Tclephonc UX)7):"3-Kto1 • Fnx (!X)7) 33:1-K_IX) WL '. 371X1 nrngn�r S(rcct • anchontg., Alaska QrA)7 . rcwa.nnmLnry; Mayor Jlark Begich I3uilding Safety Dit4sion 9/7/2004 BTH Construction, LLC P.O. Box 110358 Anchorage, AK 99511 Subject: Waiver Request for Shell #2 Subdivision, Lot 4 Waiver Request #WR040061 Parcel ID #015-112-14 Permit # SWO40341 Dear Mr. Harten: Your request for a waiver of the required 10 feet horizontal separation from the absorption field to property line has been approved. The approved separation distance is 5.0 feet. This waiver approval applies to the existing absorption field to property line separation only. Any future upgrade to the on-site wastewater disposal system will require all separation distances be met or another approval from this department. If there are any further concerns or questions regarding this waiver, please call our office at 343-7904. Sincerely, Julie Makela, P.E. Civil Engineer On -Site Water & Wastewater Program Community, Security, Prosperity Municipality of Anchorage Development Services Department .� Building Safety Division On -Site Water and Wastewater Program` 4700 Bragaw Street s . . r . P.O. Boz 196650 Anchorage, AK 99519-6650 www.ci.anchomge.akus (907)343-7904 Waiver Review Worksheet WR#: j RO40061 PIDN: 015-112-14 HAM _ Permitil: SM40341 Date Received: 911/2004 Legal Description: Shell #2 Subdivision Lot 4 Engineer. BTH Construction, LLC Brian T. Harten. P.E. Applicant Matt Matthews Waiver Requested: Lot Line Waiver Criteria: Geology Points: A. Water Table B. Soil Sorption C. Permeability D. Water Table Gradient E. Horizontal Separation Total: Waiver is Granted: _1'11� Waiver is not Granted: List Conditions or Reasons for above: Date: 91TIC20CA BY me of Revl%ver Rec#: SW57703 Amount: $176 Date Paid: 0�•4t� � / . �� t . � a 'a 1 r • MARMW or �. y � 1 �lr rn w ,. ,+ � 3, `{f �� � Tk1 r�ijy /..1 1.� i'I �I i. '4 f � `�• a' Orr "►('+o t I�t•iirRi X71 it .•T• ary ofi i i r � t - `4 r7r ♦..,� •- `� � � 1 7 1. .�r ii/dv Arrt �.if= ,� �;. .�f�`j) ei�'i 77T. F1 �i � t 1 l I �A• rr i l,:.j. .J i ;• 'll i'r,tr., ��p� ir'•6:g * !-, .;r"raI r,r .�Y fi17 �� r): ` '• fl •. f' Yi •i 1 � L� •• y. � - 4� 5 � , air •-:.• '� r • . �'l. i * ', r � ;r :Y. •. .'.� S._'Tr��. ." f • Myr% t,i I 1 .. , :r i / A F. w r I�rli tel. s.��ry 1 F•�•— !'. ll�lr 1 •S r_ ��� .;b r r s 1 fias rS i L Ir 9111-, dkn- ��f,j.�rKl.v♦a r.-._ r. r .. ..; t/7.lbf �- .. ,-: ..� ; � 't,t.';!�_'Z/.' , MYbrr � • w 1 Y'� _ � . 1 � 8 d13�1 3 11'•.'� a + " � 1. t' ��T - .� i.,. rl, r r ,. i / r �,r 44Yw4,w r •' i. r , 'rlle.i�'' C �� � ,t S ' � •ry i) •� s r � '. .,1 1 . , 1 Ir,r • .. � T -i7J i j , .• rl } S, • 5 ,� tr 1!� 1 t ,h^ � L�1 � a - i' � I♦.. `^! ter.' '( _ 71,,1 �': 3 1�. �� � .-•.=._.t �� � ) � lea' ' ' \. -rw } ,I\ i T 5 � ia. yr ♦., `•.Is a C, 11 ; !! T IF. f`.t. a'.:15�. a.�. ` ,I 1. i ,..5 }f `,1'a'jSSj ^ » .'. 1 t ' • 1: 1 11 /•riFli9C i` .. ;y � (i. w+ r� ?"S. �•"""s._'}' iff'ti� r•` t�.,-� 1�1 0`� �.*�J�7 �a 1S a: t �y l._ t ..— ! -I-�« __ t,,( `�.1!( .�� • � t _.z•7 �t S ; ��f(r .. � Jr 'JJYY � Tw, ••a'a tar •.�_ `rn 3CS'�•' '. �.ICI'♦f •.,+• rJ'}i• IF IF :ti Sl a i7 i r IF �'- I ,:�_ ..` h37.•.iF �,� ' \ � f• / a t 1 �Qn ' �1� '� i� 1..4 , - � i !/ ij• i \l`S J r .I stili i :� ° t! S: Lt'[�11 -. ,• 1 r--��-rr to-. r..r � r r 1t♦.t �a 52* •12 �I�; xi l F' p _ ' ..���...wr� pt ^,fyl ; f.': tJt. .� 1♦ '?V r } .� t4J J } ".t� `♦ '. ate•, ± r .I_i -.-.f" 'r � ll �.•...._ r r 1 j � • . JN/ •.. a ri t /-"TjJA J . ��•rala: 111 by♦M�.... �y+I r �t N,`Y.,L� :L�`'� J' J sr'i>:'�n \ J.�( i gI, :I� -r .l• r - r it • ,l rl, � � ' w Y S' \ •/�yl �'^� i1�i-' y r �L M r. � * 1 -,aa / • v ` 1 �/.� r ti r I I \ I -. J 'a.. p1 u ., 1/ r;� � :. d;a • �":i � _� 5sy"} 'iV� ,`- ,.' ••, rt 1 t({ `l� lIr) .1 �'� i. S,S t • _ IF J.}Y�LAji\ - J I.I-'♦ r ^ t.l•St+F" 'r1 I 1 ar " •� 31 t i',ri' 1 '1% 1 „"'r 1 ' ♦Ir w'ri 1 ! tl tif11\ 1)'�1 rr r., r `! ,,� ! i1 t f ( i` t� � 1 T ,'! 1 t i 1 r l r J '� (, •' Y i` .... .� J /. �i +r', r1l Y r �: 1 �r•, :-'.� �A'�jY 1j;. �.�r l,f _!� x. Yd 1 I t } SS �-�+ Is .err I � t 1 }ht �t t t•: 6 C+{' 1:• _a. )I� i A„wr i♦ • +/ .� •.�1.' i •�->t a ( i I .y r i • !• •1 , t 1 i yrl ♦ is .f 1•r ,•I I. �t , s p _�, lir .t'I ♦. T'` 1 l i 1 � , � ..j `- ...' '•//5 (� �. r .Ir rriri art. / r1,:i � /,�t” �'♦T1 r. Jti:„ ,t.I %.; IF .• 1 I � f � i I' i , - �y (n�l, A ±t!� j` i,�. 1 r � lit �t't �• r �, •I 'r r � rC�.� •• �'• � ( a � , \ fY4 r 1tir;a ,t. � 1 , `. / '.�a �"�'••( r 11�f � ) a i ;k ht.v} ('✓r,.:, a'�• ;t• rY .w'w.' Jl4 Fi Yral5'' t•: ' r , _ Mid ♦ r. .•4a ) 5-. (J • /:,^,, n, e 1 1 \tIIL+ 'i C '/ • e. A"w `A . 1 y e1 4r. 1 tl 9^ a i f a t r•t 7 1 r, t dl • `i, r 1 r t•• 3..tw �� t s' 1 1 +� , � TY / < e' �' I aJ [ r{A i C ;i I s • (• U , 'r[� I•. � . h1 •. S� .1 J � ? '_.. � j d 7 • l r A Y r ♦ t .,. • r( , . r 1 a 1} ,� a i Y' • a Via\ 9. i1 L, aJ'4� !�'v.? . rl - r rl��aa tU� '�'.I} �rE r.�• A��� r �:..• Y)3.I1JY.._ "'y.. rli t Yilv1 .{ `' r ;', r ,.4 1 rlY / wr• ^ � Ir�i LS, .IIFI»I/•� .. .«y a'"" �.� ' Yi' Y' i•.. fie' 1 / J • I e tl, rS< l � r. \ � *n •�� �/� ,�M�$/r Ia', S r /I rI-f � w�`,� r•1 sr ruy i, �'i '`•�b 'Ln It .rf \�) �q .�, a 4r !7.i't :r ,ah .t 11 5 •ja 1 Sa �h1'' 1�.t"i ''%f v♦ w. a IF " .5 .tri♦ i as tl R .. ,i!'� 1 . e J :••�. Yr 9� �.�• r ra \ s: / r ' ' Ir •1 1 e S \l a •'( }�, , i.�> 5r{ n:r P. 1 �15 � y irr{�,y! , !. • i�r� � t.t �I i 1 " �i ./�",r 'r; I,l, s�r r� ,J. a "� �I. �'�"It.} Ya ti'j '• ' •'•7F \N 1`-, 1 , ) .r I," Tj ,' ` - ram - d , /. �'` 't •r ! �. r— FFr: /•. i { r i • r v. I'.� ! li�'`.� 1. .41i. ri i 1t . y � / �'t . ( � to . t' � ! gill' •e, 5 ` 1 Is r `n' �•I f{. M. ` •w♦• I �!` l71. "t , r Jiir a , t ( i' IJ; t1 1 .i+� . _aLt S t���lir`l� I:Si n r7.r .a 4i e ( ' i1 ,JtJ �,i %.� t s�' 52 J 5. ��• '.r err h: Thr 1 ,.;. �... ,It - ., a p' �t7. Y: � sr •� •:�� r / ri•y i'1 r'"�� + r .f' •a w• :' • _ .-,1 ,. ,'. �,� i• t ••� �•a r '" Ji li }� i j'i , J .r1 �, .,• .. :_ �y�... 7 r .fir t'� t•1 r r" . a �� Y 5y r t .r.}I`1,} z ) Ja T rjr " , �r'r3 •��%..!!TII I' wyy' —d IA ! h a 1ji'a 1L t^'4 '•, rilt f� . tRY t•,. f 1 ♦i�"1: }:ati •�O�.i•*r '� ♦..sa.' � � li� �11r 1� � r' � t.%r �, a• � re L t ` � a � r �a ♦ .P i.••t..;♦ p (•i N .a ,\.iµ7) 1. • a i. 5 ,.J I at,/. i. MrI•- g�: JI :7i• i7 :' t r�J i1 �r Ll fat �/�ir , ) .i �, 1 rt' !}� 1 r1 �i � J ♦`t 7 i C aa. } • ( ! /t.1} t, h.�ri ' `f:J �,'S l♦ }ri J1 :!Ir •]ah a.aV ..r .' •,J rlla )r r �i•P. . S,' y a• ,,t.`n V IF IN ft- VS1 071 ' i"IF Ith, v.,;�1,+.5,. Ii :% ir✓ J . r 1�` 1' r • 4 •� •La'w t 1 ` r• a r l J i • .. 'i.�' %SFI a� • ' 1 .i � 'r i ® Municipality of Anchorage r On -Site Water and Wastewater Program (907) 343-7904 S a 1' E T Y Certificate of On -Site Systems Approval Parcel I.D. 015-112-14 1. GENERAL INFORMATION: Complete legal description SHELL #2; LOT 4 Location (site address) 10707 Whimbrel Drive *Anchorage Expiration Date: a CI Current Property owner(s) Christopher Peters Day phone 947-4444 Mailing address Real Estate Agent 2. TYPE OF DWELLING: ❑X Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 4 Day phone 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Individual Well ® Individual Individual Water Storage ❑ Holding Tank ❑ Community Class Well ❑ Community ❑ Public Water System ❑ Public Sewer ❑ Waiver/Variance request for: Distance: Received by: Date: COSA to be released to the engineer, unless otherwise requested by the engineer. COSA Fee $ Sid Date of Payment %/oh l 11 1 Receipt Number _005 -37 r COSA# 055-Z112?$L-I Waiver Fee $ Date of Payment Receipt Number Waiver # 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm: Garness Engineering Group Ltd (GEG) Phone: 907-337-6179 Address: 3701 East Tudor Road Suite 101- Anchorage, Alaska 99507 Date: ZI Engineer's Printed Name: Jeffrey A Garness In conducting this evaluation, GEG provided an engineering evaluation of the well and/or septic system in accordance with the guidelines and regulations established by the Municipality of Anchorage and industry practices. The reported results describe the condition of the system/s on the date/s of the o Qf evaluation. Separation distances were measured to readily identifiable features. Hidden defects or G ��. encroachments may exist that were not identified during the evaluation. The operational life of all wells '• and septic systems depend upon a variety of variables, including but not {invited to, soil conditions, /(�;'r i groundwater levels (that may fluctuate during the year), quality of construction (materials and (Y/Yj. . t ..... ..... • .. • _ . workmanship), and the water usage of the family utilizing the system/s. These conditions can vary, and are outside the control of GEG. Satisfactory test results do not guarantee future performance of the system/s; therefore, GEG makes no warranty (express or implied) regarding the future performance of f reg A. G rness,- the well or septic system. GEG makes no representation whether an alternative well or septic system �i P CE -7 3 �G of currents stems fail to perform adequately in can be installed on the property in the event either o. y �ti�t:gg the future. The content of this report is for the sole benefit of the person! art that retained GEG to on the information provided in this report by any other person or perform the evaluation. Reliance up�Ua�orsto °curl urchasers) is not authorized, nor will it confer any leg es party (including subsequent property p`�¢(((((((((l(�������``��'� whatsoever. `�\Q���(Y OFAA�_�(�r//r #AECC884 6. DSD SIGNATURE _ j2 ON-SITE _1 System #1 Approved for ? bedrooms �-� m% WATER AND System #2 Approved for bedrooms WAST ivVATER O Disapproved PROGRAM Conditional approval forbedrooms, with'Fowing stip~s: SERU�G.��� -- Please Co,4ad nAor Tal 7JT)))))t k nt e bQ W l TVA o. Mod n4fn4l" C e Co✓►1�24LC-1' By: Original Certificate Date: The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 7. ATTACHMENTS: COSA Checklist Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other COSA Checklist Legal Description: SHELL #2; LOT Parcel ID: 015'112-14 If more than I septic system on lot: COSA Checklist # —of Structure served by this system — A. WELL DATA [01Well log is5|edwith Onsite (or attached) Date drilled 1212»104 Total depth 2OS _�ft Cased to 289 ft EN] Sanitary seal is functioning correctly FN_1 VVinss are properly protected Casing height (above ground) 18+ in. Deh* offlow t6/16/21est for Static water level atbeginning oftest 1851 Comments B. TANK DATA � m Age ofhank(a) 17years `~ Tanhtyps/mahario| SE~ICISTE" Measured operating fluid level inseptic tank _____ * Stand pipao/foundaUoncleanout per record drawing Date of pumping SEE ATTACHED MAINTENANCE Well production sdtime oftest 4+ gpm Water N/A gallons Well disinfected for coliform test? Fl Yes FEW No ��Coliform bacteria is Negative Nitrate 1.9H8 mg/L 0 Nitrate |eao than MRL (ND) Ansenioua/L FO-1Arsenic less than MRL (ND) Collected by GEG, LTO. Date ofSample 6/16/21 C. LIFT STATION �� == Required maintenance completed Age oflift station 17 years Lift station material oTeeL Comments: ADVANTEX D. ABSORPTION FIELD DATA F- Which system tested (date installed) 9128104 Adequacy test date */16/21 �ALLandpipospsoentperreoordre�ing * Results bedrooms�� Total measured depth from grade 7.33 (max) Fluid depth prior totest O in Measured depth topipe invert from grade 3_^.33 Water ateradded O44gal Fl MA\- pressurized field New depth O /n L-4-�� Monitor tubes go to bottom of effective. If not, state Elapsed time 0 min depth into effective . ---- �� Code -required soil cover � Final fluid depth in ��System presoaked 80O+ Absorption rate ____gpd (Required ifvacant for greater than 3Odays prior to Any rejuvenation treatment (past 12months w0NE ) date of test) ^°15O Gallons introduced ga||ons If yes, enter N/A ' ---- Comments/Deficiencies: TESTED EAST TRENCH ONLY WEST TRENCH FULL UPON ARRIVAL 'BOTH MTS EXTENDS PARTIALLY INTO SAND ''pm`SOAKPERFORMED DIRECTLY BEFORE TEST COSA Checklist yellow sheet From Private Well onLot to: (Please enter distances ifless than required orifcommunity well) SeodoTank8-�ShaUononLotp107 *501+ ifNoft CommundySewer K8anho|eXC�anout>1O0' Community ' — Yen if No F-1YesifNoft [�lYea ifNoft Neighboring Tank >1OO' ��Yes if No ^^ ft Private Sewer/Septic Line >35'[J]Yes ifNoft Absorption Field onLot >1UO' MYes ifNo°50'+ ft Holding Tank >1DO' MV Yes ifNoft Neighboring Absorption Fields > 100' F-1Yes Animal Containment >5O' Yes if No ft MV Yes if -- Manure/Animal Excretal Storage >1OU' Community Sewer Main >75' ��Yas ifNoft r,/] Yes ifNoft From Soptio/HoNingTank onLot to: (Please enter distances if less than required) Building Foundations >10' Yes ifNoft SurhsceWater >1UU' Yes if No *50'+ft Property Line > 5' Yea if No —'—' ft Wells onAdjacent Lots: Absorption Field > 5' Yes if No ft Private Wells > 100' Yes if No ^5U'+ ft Water Main >1O' F/IYas ifNoft Community Wells >2UU' ��Yeo ifNoft Water Service Line > 10' M Yes if No ft If septic tank is under driveway comment below From Absorption Field onLot to: (Please enter distances Jless than required) Building Foundation >1O' 111 Yes ifNoft |fabsorption field isunder driveway comment below Property Line >1O' F-1YesifNoft Wells onAdjacent Lots: Water Main >10' Yea ifNoft Private Wells >1D0' El Yes if No °50'+ ft Water Service Line >1U' Yeo ifNoft Community Wells >20O' 0Yes ifNoft Surface Water >1OO' F-1Yes if No °50'+ ft F.ENGINEER'S COMMENTS **ITIS 9R+TO[]R4INF|ELD(WAIVER REQUESTED IN 2006) ON SHELL #2; LOT 8.MEASURED 115'T]UNDOCUMENTED SEPTIC SYSTEM PIPE {}NSHELL #2;LOT 0.NO RECORDS AVAILABLE SO SEPERATION DISTANCE CANNOT BE VERIFIED ***WR#040061 / certify that / have determined through field inspections and review ofMunicipal records that the above systems are /nconformance with MOA COSA gUidelines in effect on this date. COSA Checklist yellow sheet #AECu884 Ub1'LlltU1Zi lb: lb bbbbl/U CZ121l2021 09:11 Am torage Tank 1® Run 10110011 a ■AA ■ t■ ■I■■ ■ ■ an ■■ ■ 1■■ i0■ Arr_Ub ( AX$07 277 1715 393 650 P ®®go on A A Boom MR ® go ■ p NOUN an FA'avanTow" Field Maintenance Repor) Annual Ins _)ectian Prn;xuty 0Wr.x/,rra0h!110 M Chris Peters 31te AdJnri7e 10707 Whimbre Drive, Anchorage AK 99516 ,,x9ita to t Cburity 113AX�104217 SAID40341 Retrieve O&M irrt : b-,aily flcW . Recirc ratio ---- Timor r:caangst This is a COS'\ Inspection. Please switch :irainfields. Perform Fit:rad a�f�l ;plingfOCsserKeti�ra5 MTU (18 . NTU�) oil (r,-9) 00 (2.6} C?dhr cf 5m1p1e Typic:31 IN u -ty C EartlSp �_ tuts ldy Non•typicei s Itfiria ( CctHernlrerlei:ey Oily film in PVP U YesW IFoant in talcs: f ,� ye: 9No ChOOk CArltrtl) P 101 Recirc Antps Di9G1tz,Y,o rUnps J_ Audible aril vi3WA K dial ttvi (tr..irrrrrki ramyl 7-1 Ye ❑ t�'o InspectlClean Pu 'rip ay4tem Clu'-ndcn Larry Betts t -"AUL ern P',0011001 AncharacgeTank 907-212-3543 Cbato�k 1Yhonb (9t�7) 947-4444 Pod , RTU ONL d ..,. O�Bn nr LuM, lmy,)ctian 203795 RTU 103862 10/2 712020 Measure Sludge/Scum Sludge stuen 1 ;I, (:Rtnportrtlent Gurkn l�v PrevOU9 Currorll Fn vib,.a^ 2nd a:omparirrlON. Current Previous current Prcrto.,^ --- - - -- - - -- .................. .... --------- - �__ --------� 1e�;6�R i,l�itr�r> afiva lTAx Filt€tr Odor./'Nontnl _ Pklt1w!n4 @10111,2t!fff orTnfrt Fxr_!!-: vs Sritlgingipwding,. onclMnor (_.J Excessive Inspeat/clein Discharge PIAMP System lnspet:t RleerlL,a [_ Splice Borc L Float OordO C Inspoct/Servica Other Syc tem CrSlTi{JCAftntS Inspect Clesn rai^,at'feckion Equipment: %� 17isp ob"ervaticns InSr.)".. Laterela/Crtflces !- (J Pod 00tiom IJP if Intake Vent Inspect, Clean Flow's -. r Pump f f. IrtxCcl, Clean sr.,al i,fricrataf�irific-11 Additional Services Rendare d I� Clawed WIxtile gheotn? i__. Replaced UV itoms? Reploct` MLIed cthor itOrtd? I Parts Used: W = Warre.ITty, 8 = alilablo (J'` 1ppropriete selection) W a 1#ain NumbEIr R1c�c�CrieY#90112 Ji ,,., -- ----------� Final/Safety Inspection RSV rr in:tollkd dr§ 9oltOcl on fvlklryit0ltl rcG9nP1CC'll:r�; floats calves cloLd control Ixrncl renclivaled SurnmatyfRocornmend2tions [I Systorr perrornting; no furthiv action rkedcd ttnk fi xd puntparl2 CD C, -)Il fOr -*rvii r_" Signature---- -- Date —j_ r F27 010n19996ated f,D1•rvt to 1 *866384-74 4 Inspect Clcan R;serlUd . . . .... . ..... . Splice Lox ...... .......... •- Float Cords ..... ............. Floats .......... ............. Pump .......... ............. . 'L Siobjf:i,kt Filter .... . .. . ......... L oicd:ub;Pumlava,It ............ f R0cir(AA-1Un9 Spli' --2r WIVe....... �arnrncnEs_,� �C..J Clu'-ndcn Larry Betts t -"AUL ern P',0011001 AncharacgeTank 907-212-3543 Cbato�k 1Yhonb (9t�7) 947-4444 Pod , RTU ONL d ..,. O�Bn nr LuM, lmy,)ctian 203795 RTU 103862 10/2 712020 Measure Sludge/Scum Sludge stuen 1 ;I, (:Rtnportrtlent Gurkn l�v PrevOU9 Currorll Fn vib,.a^ 2nd a:omparirrlON. Current Previous current Prcrto.,^ --- - - -- - - -- .................. .... --------- - �__ --------� 1e�;6�R i,l�itr�r> afiva lTAx Filt€tr Odor./'Nontnl _ Pklt1w!n4 @10111,2t!fff orTnfrt Fxr_!!-: vs Sritlgingipwding,. onclMnor (_.J Excessive Inspeat/clein Discharge PIAMP System lnspet:t RleerlL,a [_ Splice Borc L Float OordO C Inspoct/Servica Other Syc tem CrSlTi{JCAftntS Inspect Clesn rai^,at'feckion Equipment: %� 17isp ob"ervaticns InSr.)".. Laterela/Crtflces !- (J Pod 00tiom IJP if Intake Vent Inspect, Clean Flow's -. r Pump f f. IrtxCcl, Clean sr.,al i,fricrataf�irific-11 Additional Services Rendare d I� Clawed WIxtile gheotn? i__. Replaced UV itoms? Reploct` MLIed cthor itOrtd? I Parts Used: W = Warre.ITty, 8 = alilablo (J'` 1ppropriete selection) W a 1#ain NumbEIr R1c�c�CrieY#90112 Ji ,,., -- ----------� Final/Safety Inspection RSV rr in:tollkd dr§ 9oltOcl on fvlklryit0ltl rcG9nP1CC'll:r�; floats calves cloLd control Ixrncl renclivaled SurnmatyfRocornmend2tions [I Systorr perrornting; no furthiv action rkedcd ttnk fi xd puntparl2 CD C, -)Il fOr -*rvii r_" Signature---- -- Date —j_ r F27 010n19996ated f,D1•rvt to 1 *866384-74 4 A 119/14/20'20 "PLUS PAGE 02 05:11 3686770 399 789 � BEER no 11115 am now N Mon 0 cam E no R a M 1112111111 0 a .1 MW 0 0 low so vMM ra 0 a 12,11 R�WvzlnTax Field maintenance Repod Unscheduled pmporvj oWnk'rPhMk1n;z 4 Chris Peters QpArat(5r Larry Betts $ft. Address 10707'vVhjm1I:ire1 DO a, Anchorage AK 99516 C,,,umy ID 0 Pod 9 AX GKN 11) q SWO40341 203795 104217 Dispatcher commiard i 08M 3/20.20 12"00 AIVI D,.ite:—. 1. _T1M0!_'_ Please install the ric N motherboard. Notification of site v inti tion Matle by V4aOCE)rnrl , monitoring SWOM Made by HoMeOwf W cthor site condition at tiers , of call AlarM Tank Overflow ()d*r._ Sowage 13,,WkuP other Field Zampling/obs( rvations ti�ceasary [_ Not neogs!321Y Iq (6-9) 00(2-61 Odor of Semple. Typical Musty E] Earthy []Moldy Nun -typical Sulfide C1 Cabbage C Decay C'--dvVAC'.r'3 at site Alarm On L I Yes V, No (If yes, alarm tyf� — Tank Liquid Level E, I No—at MI-Ilgh r3 LOW [3 puMb p operationaI2 Vv No CircLIR Breakers I-Jor,lrc ........ ) Tripped f -On FlOff Discharge i Tripped YEI On Off ConlrOls, Tripped 0, or, d off V00MI ATRTU BO:srd: applicablO DQr ,Ijmerit the parjol stat s by shading the appropriate Inputs and outputs as iry cated by the yellow and rod LEDs, Iripute 05 (9) 12) 11 outputs t 03) 01(r 7 off Fling (Green L(M) "'v plow 907-272-3543 contmat phony (907) 947-4444 D.RIQ of Wt Inspection 0712-9/2020 -Related Services Flenderod, warranty. 8 = Billable W approprioto selection) 17 Sy=rp performingi no further aQtlorl needed 0 Addttlollal service n"ded Finai/Safety flispection, Yes No Lids b9fted On? (if damaged, cQmmOht Control Panel reactivated? as ❑ No 01mult Breaker's; Ej off ❑ Off Recirri C^bon n off Dischargo: [D On Time at Site Travei-riMC, Total Time $Jgnatum Date Time 6U0 Fax completed form t* 1 -6 � Erik Widger From: Larry Betts <907septicman@gmail.com> Sent: Wednesday, July 07, 2021 10:56 AM To: Erik Widger The system on 10707 Whimbrel drain field line has been jetted and drain fields change over Larry Betts. L& S Services MUNICIPALITY OF ANCHORAGE ADVANCED WASTEWATER TREATMENT SYSTEM MAINTENANCE AND REPAIR AGREEMENT THIS MAINTENANCE AND REPAIR AGREEMENT, herein the "AGREEMENT" made and entered into as of this 1 Day of j UL -1 of 20 7- t , by and between - DHP CLA-,pr, r 3,44ro,4 SAIeAD , herein the "OWNER," and the Municipality of Anchorage, herein the "MUNICIPALITY", in accordance with Anchorage Municipal Code (AMC) 15.65.365. In consideration of the mutual covenants contained herein, the patties to this Agreement agree as follows: 1. Advanced Wastewater Treatment Systems. The Municipality grants permission to the Owner to utilize and operate an Advanced Wastewater Treatment System (AWWTS), described as AWAPTCY - AX located at (legal description) SN ELL_ %W 2,, 1-.K 2. Maintenance, Repairs and Alterations. (Owner is required to read, understand and initial each section) Q Throughout the term of this Agreement, the Owner shall enter into a service agreement with an AWWTS service and maintenance provider approved by the Municipality or the manufacturer's representative. The AWWTS shall be maintained in a satisfactory condition capable of performing as designed and producing treated septic effluent in accordance with the equipment's approval for operation in the Municipality. It shall be the responsibility of the Owner during the term of this Agreement to pay for all repair(s), maintenance, adjustment(s), replacement costs, and inspection costs. This includes an annual maintenance fee (typically $400 to $600). Owner agrees that only maintenance and repair personnel approved by the Municipality or the manufacturer's representative will inspect and make any necessary maintenance, repairs or permitted alterations to the system. Owner acknowledges that regular maintenance of an AWWTS reduces the potential failure of the system, which could include sewage backup and costly repairs or drainfield replacement. (rev. 05/18/2018) Paget of 3 I Owner acknowledges that the Municipality may request records of maintenance and repairs from the manufacturer's representative or maintenance provider. CV Owner acknowledges that the fine for failing to maintain and repair an AWWTS may be assessed in accordance with AMC 14.60.030. 02 Owner agrees to grant the Municipality reasonable access to test and inspect the AWWTS. The Municipality will give at least 24-hour notice. Owner agrees that any sale or transfer of title of the property will not occur without a new Certificate of On -Site Systems Approval. Owner agrees that the AWWTS installation and maintenance requirements as provided by the AWWTS vendor/installer and approved by the Municipality are the governing guidelines for the construction, maintenance and repair of the Owner's AWWTS. Owner agrees to maintain remote monitoring of the AWWTS as required by the AWWTS approval. 3. Term. The term of this Agreement shall begin on the date of approval by the Municipality to operate the installed system, or upon transfer of title, and shall continue while the AWWTS is operational or until title is transferred. 4. Nonwaiver. The failure of the Municipality at any time to enforce a provision of this Agreement shall in no way constitute a waiver of the provisions, nor in any way affect the validity of the Agreement or any part hereof, or the right of the Municipality thereafter to enforce every provision hereof. 5. Amendment. This Agreement shall only be amended by authorized representatives of the Owner and Municipality. Any attempt to amend this agreement by either an unauthorized representative or unauthorized means shall be void. 6. Jurisdiction: Choice of Law. Any civil action arising from this Agreement shall be brought in the Superior Court for the Third Judicial District of the State of Alaska at Anchorage. The laws of the State of Alaska shall govern the rights and obligations of the parties under this Agreement. 7. Severability. Any provisions of this Agreement decreed invalid by a court of competent jurisdiction shall not invalidate the remaining provisions of the Agreement. (rev. 05/18/2018) Page 2 of 3 QWNEI;V� D By: (signature) Date: L u z hncl�v (print name) STATE OF ALASKA ) ss. THIRD JUDICIAL DISTRICT ) The foregoing instrument was acknow[edged before me this day of 2011, b i Stare o_fAlaska ( � NARY PUBLIC FOR ALASKA NOTARY PUBLIC My Commission expires: Peyton Tifton My Carrnissfon Expires Doc 22, 2024 MUNICIPALITY: By: A� 6azee (signature) AC e CCa &rrO G ( (print name) Date: 7101,9q11 �% Title: (rev. 05/18/2018) Page 3 of 3 Parcel I.D. 015-112-14 R-9, VE Municipality of anchorage �. On -Site Water and Wastewater Program (907) 343-7904 -- Certificate of On -Site Systems Approval 1. GENERAL INFORMATION Complete legal description Location (site address) Shell #2, Lot 4 10707 Whimbrel Dr. Expiration Date: 9 - 1-t /_�- Current Property owner(s) Richard & Susan Reeves Day phone Mailing address 10707 Whimbrel Dr. Anchorage, AK 99507 Real Estate Agent 2. TYPE OF DWELLING: 0 Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 4 Day phone 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Individual Well Individual Individual Water Storage ❑ Holding Tank ❑ Community Class Well ❑ Community ❑ Public Water System ❑ Public Sewer ❑ WaiverNariance Received by: _ COSA to be released to unless otherwise requested by the engineer. COSA Fee $ 62-4 -t- 31 S• "o DateofPayment Receipt Number b'C>0.14 COSA # I o,1 Date: Lei ! M o Waiver Fee $ Date of Payment Receipt Number Waiver # 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. In conducting an adequacy test, I attempt to provide a thorough, conscientious engineering analysis of the system in accordance with MOA COSA guidelines and regulations. The reported results describe the performance of the system under the conditions encountered at the time of the test, and separation distances measured to readily identifiable features. The operational life of all wells and septic systems depend on the local soil condition, ground water levels that may fluctuate during the year, and the water usage of the family being served by the system. These conditions are outside the control of the evaluator of this system. All systems eventually fail and satisfactory test results do not guarantee future performance of the system, nor do they guarantee that there are no hidden defects or encroachments. Therefore we cannot provide any warranty for future performance, nor can we estimate remaining life of the system. The content of this report is for the sole benefit of the owner listed above. Name of Firm Pannone Engineering Services LLC Phone (907) 272-8218 Address P.O. Box 100217, Anchorage Ak. 99510 Engineer's Printed Name Steven R Pannone Date 2/9/2015 F OF 6. DSD SI NATURE PRI"'" �V'}; Wd System #1 Approved for bedrooms • Seven 06nr System #2 Approved for bedrooms ¢��9�. CE -8349 Disapproved ��QI�OFE55 Conditional approval for bedrooms, with the following stipulations: By: Id' Original Certificate Date: e� - The - unicYpal Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. ATTACHMENTS: COSA Checklist X Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other COSAbluesheet S _, If more than 1 septic system is on the lot: COSA Checklist # + of 1 Structure served by this system I Certificate of On -Site Systems Approval Checklist Legal Description: Shell #2, Lot 4 �riR���7•r7_� Well type Private If A, B, or C provide PWSID # Date completed 12/23/2004 Sanitary seal (Y/N) Y Total depth 289 ft. Cased to 289 ft. Parcel ID: 015-112-14 Well Log (Y/N) Y Wires properly protected (Y/N) Y Casing height (above ground) 18+ in. FROM WELL LOG AT INSPECTION Date of test 12/23/2004 2/6/2015 Static water level 204 ft. 198 ft. Well production 20 g.p.m. 8.2+ g.p.m. WATER SAMPLE RESULTS: Coliformee colonies/100 mL Nitrate a7 mg/L Arsenic A) D ug/L Date of sample: 2/9/2015 B. SEPTIC/HOLDING TANK DATA Tank Type/Material AdvarlteX/Steel Tank size 1,500 gal. Number of Compartments 2 Collected by: PES Date installed 9/29/2004 Cleanouts(Y/N) Y Foundation cleanout (Y/N) Y Depression over tank (Y/N) N High water alarm (Y/N) Y Date of pumping �/l / JQ1 $ Pumper Qv c l C. ABSORPTION FIELD DATA Date installed /30/2013 Soil rating (g.p.d./ftz or ftZ/bdrm) 6 GPD/SF System type Shallow Trench Length 20 ft. Width 5 ft. Gravel below pipe 0.8 ft. Total depth 4.5 ft. Eff. absorption area 100 ft2 Monitoring tube Y Depression over field N Date of adequacy test 2/6/2015 Results (Pass/Fail) Pass For 4 bedrooms Fluid depth in absorption field before test 0 in. Water added 624 gal. New depth 3 in. Elapsed Time: 110 min. Final fluid depth 0 in. Absorption rate >= 600+ g.p.d. Any rejuvenation treatment (past 12 mo.) (Y/N & type) No If yes, give date D. LIFT STATION Date installed "Pump on" level at Datum — Size in gallons _ in. "Pump off" level at E. SEPARATION DISTANCES WELL ON LOT TO: Cycles tested Septic tank/lift station on lot 100+ Absorption field on lot 100+ Public sewer main 75+ Sewer /septic service line 25+ Animal containment areas 50+ Manhole/Access (Y/N) _ in. High water alarm level at Meets alarm & circuit requirements? On adjacent lots 100+ On adjacent lots 100+ Public sewer manhole/cleanout 100+ Holding tank 100+ Manure/animal excrete storage areas 100+ SEPTIC/HOLDING TANK ON LOT TO: Building foundation 5+ Property line 5+ Water main 10+ Water service line 10+ Wells on adjacent lots 100+ ABSORPTION FIELD ON LOT TO: Property line 5* Building foundation 10+ Water Service line 10+ Surface water 100+ Curtain drain 50+ Wells on adjacent lots 100+ F. COMMENTS *Waiver on File WR# 040061 **As -Built on File G. ENGINEER'S CERTIFICATION 1 certify that 1 have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. Engineer's Printed Name Steven R. Pannone Date 2/9/2015 COSA brown sheet 10-10-12.doc Absorption field 5+ Surface water 100+ Water main 10+ Driveway, parking/vehicle storage 10+ • • � S�everi �?. •E3annorie � • CE -8149 i in. m T ew.utc s MACK REA4 GHLWC SETBAIX 3 120.00' N890 57' 15' - 5 UNDER NO CIRCUMSTANCES SHOULD AN AS -BUILT BE USED FOR CONSTRUCTION OR FOR ESTABLISHING BOUNDARY OR FENCE LINES. THE SURVEYOR TAKES RESPONSIBIUTY FOR THE INI nAL TRANSACTION ONLY AND ASSUMES FINANCIAL LIABILITY ONLY FOR THE COST OF THE SURVEY. LISTED DISTANCES PREVAIL OVER SCALING. REPRODUCTION MAY CAUSE ERRORS IN SCALE. LOT SURVEY SURVEY TYPE SYMBOLS ❑ FOUNDA11014 AS -BUILT SET REBAR DRAINAGE ASPHALT ❑ DNA STRUCTURE AS -BUILT O FOUND RESAR A'�a'''- - CONCRETE ❑ PLOT PLAN ... AS -BUILT ... LOT SURVEY ... TOPOGRAPHY"� WOOD FENCE IDI _ _...._ .._ ___.__ �_ n _______.__., ._ .., ..._ .._,......,.,,.-..'_ 004 ASSUMED ELEV. j( )( )I METAL FENCE ® WOOD DECK IT IS THE RESPONSIBILITY OF THE BUILDER OR OWNER, PRIOR TO CONSTRUCTION, TO VERIFY PROPOSED BUILDING GRADE RELATIVE TO FINISHED GRADE AND UTILITY CONNECTIONS AND TO DETERMINE THE EXISTENCE OF ANY EASEMENTS, COVENANTS OR RESTRICTIONS WHICH DO NOT APPEAR ON THE RECORDED SUBDIVISION PLAT. SURVEY CERTIFICATION i,, PLOT PLAN ��.•7�-�E OF Alm % nmr MIfy awn r na.. 01 x 1 wT.0 . �r . ............. .. MO bt baFl mC bvOM Amen, mE MOn I '•. Iw.. ,a,.,a m wtm��n.a a er a,. KK .�., I � J,' • ae ma.e m bro qm ud w b0 ewt a my wam.ao. ma mous a mn.n.Im. Ae.. e.m ; iS ;' 49th •:.'� ♦� mm..w w. ma aa.�eL FOUNDATION AS—BUILT jay^•'•'";y^"""" I, RO E .bY+n t.. MmY u awl I A h_ I prMntl m -BJt Y OI q vw4f famMGm m Mb bt mJ �....."..............................• ROBERT E. JOHNS. JRFINAL !IL I > o i♦'4!� •'•, - 4121—S STRUCTURE AS-B �4. I, ROWt c +ns r., Awmr a mat A-1-1 m» o.rmn.e m `Ivo — r mwura m nb M nwt a n. d» ••.... .....•• ••• 00 anb �1 ofessionot L 00, 0' �o ozo QJLLI 20.0' o0 EXISTING � 6a. HOUSE ' o M 16.0' z ANT o 03 I m o o 25.2' . 40.0' o� m o CC G CD b o N o 15' - 5 UNDER NO CIRCUMSTANCES SHOULD AN AS -BUILT BE USED FOR CONSTRUCTION OR FOR ESTABLISHING BOUNDARY OR FENCE LINES. THE SURVEYOR TAKES RESPONSIBIUTY FOR THE INI nAL TRANSACTION ONLY AND ASSUMES FINANCIAL LIABILITY ONLY FOR THE COST OF THE SURVEY. LISTED DISTANCES PREVAIL OVER SCALING. REPRODUCTION MAY CAUSE ERRORS IN SCALE. LOT SURVEY SURVEY TYPE SYMBOLS ❑ FOUNDA11014 AS -BUILT SET REBAR DRAINAGE ASPHALT ❑ DNA STRUCTURE AS -BUILT O FOUND RESAR A'�a'''- - CONCRETE ❑ PLOT PLAN ... AS -BUILT ... LOT SURVEY ... TOPOGRAPHY"� WOOD FENCE IDI _ _...._ .._ ___.__ �_ n _______.__., ._ .., ..._ .._,......,.,,.-..'_ 004 ASSUMED ELEV. j( )( )I METAL FENCE ® WOOD DECK IT IS THE RESPONSIBILITY OF THE BUILDER OR OWNER, PRIOR TO CONSTRUCTION, TO VERIFY PROPOSED BUILDING GRADE RELATIVE TO FINISHED GRADE AND UTILITY CONNECTIONS AND TO DETERMINE THE EXISTENCE OF ANY EASEMENTS, COVENANTS OR RESTRICTIONS WHICH DO NOT APPEAR ON THE RECORDED SUBDIVISION PLAT. SURVEY CERTIFICATION i,, PLOT PLAN ��.•7�-�E OF Alm % nmr MIfy awn r na.. 01 x 1 wT.0 . �r . ............. .. MO bt baFl mC bvOM Amen, mE MOn I '•. Iw.. ,a,.,a m wtm��n.a a er a,. KK .�., I � J,' • ae ma.e m bro qm ud w b0 ewt a my wam.ao. ma mous a mn.n.Im. Ae.. e.m ; iS ;' 49th •:.'� ♦� mm..w w. ma aa.�eL FOUNDATION AS—BUILT jay^•'•'";y^"""" I, RO E .bY+n t.. MmY u awl I A h_ I prMntl m -BJt Y OI q vw4f famMGm m Mb bt mJ �....."..............................• ROBERT E. JOHNS. JRFINAL !IL i♦'4!� •'•, - 4121—S STRUCTURE AS-B '•.,, I, ROWt c +ns r., Awmr a mat A-1-1 m» o.rmn.e m `Ivo — r mwura m nb M nwt a n. d» ••.... .....•• ••• ammma. me xwmetwn a mo.n nm.ea anb �1 ofessionot L a. bw rtW 00 Ii4eulenwb bbl VYs j ,'�„•.,,•' maws Otl#�W ONLY THOSE IMPROVEMENTS ABOVE GROUND AND VISIBLE WILL BE SHOWN. FENCES, WELLS, SEPTIC CLEANOUTS, SIDEWALKS, DRIVEWAYS, ETC., ARE SHOWN IN THEIR APPROXIMATE LOCATION, ONLY. SNOW MAY PREVENT SOME IMPROVEMENTS FROM BEING SEEN AND LOCATED. ALL DISTANCES ARE RECORD UNLESS OTHERWISE NOTED. Prepared by Robert E. Johns, Jr. & Assoc. Professional Land Surveyors 1700 Brink Drive. ANCHORAGE, ALASKA 99504 Scale: 1 It _ 30' Rec. Lot—S.F. Rec. Plot File No. Date Surveyed: 03/12/15 °r°�"'Y REJ Checked bJMK Date Drawn: 03/13/15 Grld: 2536 W.D. 15-81 Lot 4 SHELL #2 U0/10/LUlU UJ.00 0000''u Miss on 0 Ems Mongol Impol Miss no so INN 0 omen 262 543 ■ NOR Nunn ■1111 0 no Ron I 11 a No Non 4y2varMwe FMd Mahrimance Report Unscheduled r■ r+.� ■o■ ■ M o AnchorageTank 907-272-35/43 prop" DenRnr.ntnor opmeor Richard 8 Susan Reeves Mike Blakeslee Dna Add" - emtutty a 10707 WMmbrel DrW, Anchorage AK 99516 (907) 562-2315 AY D<N IDr Cw�rylDr Poen pill AML Dm of Law lmpw.11ne 104217 SWO40341 203795 RTU103882 02/19/2015 plepatcher Comments Dotal 03/16/2015 _TIme:08-00AM Broken Lid and wires pulling an alarm pone[ Notlrlcstlon of eke condition 0 Made Ey Vaer mwe Morhoreg RyaEam ❑ Made by Homeowner ❑ owe, Site condition at time of call ❑ Nmml ❑ Tbnk Overflow ❑ Odra ❑ Sewage Backup ❑ Ompr Field Samplirtp/Obaervart(ons []Necaasaty ❑Hotnedesamy NTU d 6 m NrLb)PH (661)) DO f2 e1 Odor of BaAVI& Viaw ❑ Munty ❑ Balt4 ❑ Moldy Non -typical [I Wilde ❑oubblop ❑nwAw Conditions at site /dent On ❑ Ya¢ ❑ No pfYm aimmtype ) Tank Liquid imus! ❑ Normal ❑ High ❑ Law Pump OPxaue=P CI Yat C No Cimult amde nechc........ ❑ mppad ❑ on ❑ off DDchange..... ❑ TrIPPed ❑ 0n .❑ Oe oontroll , . . .. ❑ T1lppad ❑ Qr ❑ OH VC06P ATimf Board; Of Applicable) Document the Panel statue by Ahading the eppmprime Inputs end auhixds ee indicated by the yarrow and red LED& Inptrta Q Dutpum Power 0On❑ Off Fieabing . (Green LED) Fax comple Calaee of Malfunction:0 Machadmi ❑ Pmeasa-R*Idwd Services Parts Ueed: W - Warranty, B - Billable (V apprapdate aafaction) Notos/Final Becommendatlons: ❑ System parfaming; no further action naeWd ❑Addldonal a rAw needed FinalMbatstyInspection: utlo betted An? ❑ Yoe '❑ No Of damaged, aomfnent ) Control Ptnel yawtivated7 ❑ Yea ❑ No - Cimult Breakers: Rechc: ❑ on ❑ Off Discharge: ❑ on ❑ off controls: ❑ on ❑ off Time m Blro 7laral7lrna Tbtal nrna 9agnaturs Data 111-/CS/7 _ T,ma ted form to 1.868.384-7404 02/19/2015 06:32 8686770 FroWANCH TANK 4 WELDIN5 INC 277 3715 mom a Milan a as a molaia allo iif a aiaa■ ■ APLUS PAGE 02 02113/2015 10:34 11941 P.0111/001 261 297 _ a 11 no a MR aaaa I d ■ a n 0 ■ of a a LAcwanTex` Feld Maintenance Report Unscheduled h•ta+:YPrnmm�kbrs lY _---- Riohard 8 Susan Reeves 10707 WhIMbrel DriVe. Anchorage AK 99516 as alro the --.... tevrv6a owe 104217 i51N040341 203795 Otopetaher Oommemta Om, 02113/2016 „Trina; 12:0DAM Please Wduct he WSA lnspeaun. Pannone EngOieerinB would Eke a copy of th'c. Notification of site =mcfition j Mad=- by Wrlcemin.' tkilitving syatw ❑ Made by trcraR rr: e� Omer ..... Site sondMbn at 0111.+ of call Alarm I rank Overfi^.w J Odor I_ 8^nvega Dmoup Li mw _.. Freta Satnpltnglodr.+rvations [ Necelamy 7dv"i Tie weary N1u Dg x N1us1 .;n Is-gl oo �zcl Oder et Sample. Typierd �'.u•ry uEArmV r❑�Moldy Ncn,Mpical Isla I CW&Ag`�I e Dsow conditiant at site, Alwin On - L7 No pryea. warm ty!n, - S TAnk tlq id Loyal Normal IJ High LOW Pump operauomlK v: s M No elaulteraskm iaciro..—,. I SiipPed*n ❑Od oashergo.... 4ippad [i On ❑ Off Camovii,...... i tnppad On ❑ DII 4COW ATM eneM: $ :¢.'haab6l mobbed mApand,ivi I! Y,j by the VoMwand red and outPMa as iv1,� ,! :9 try me Yellow a� red LEOa. InPaks Q il� �� Outpum Power [ on. nn FWhing Ion" LM AnchorageTank 907-272-3543 pAsam Mike Blakeslee Boman nMys (90) 562.2315 nN WUL! pana!Uv WPneam RTU403882 10/25/2013 Pelle Usedi W - Warranty, B • Blaeble (✓ apprapdata aetaefon} Natcs/Fna1 Resomn>endat'wna: _ISyetd polo 'Tic ATntMraQR nCm L Atlddipinl �/� o 0 Flna Safely hupeatlan�:,/ Llds bolted and 1*13 1-1 No in darnaged, eommam Cantrpl Panel reactivelAtll jkyes rhaaR 9reakaR: Reclm;14 on ❑ On vechaw; ] on ❑ air cantrnts; 4 on C on Tims at Sb IAMNITmlo ITmsl Time Time Fax completed form to 1-068-384-7404 1rm �I Municipality of Anchorage Development Services Department Building Safety Division On -Site Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 /LJ�T/✓E4�' www.ci.anchorage.ak.us (907) 343-7904�1 jj SK RTIFICATE OF HEALTH AUTHORITY APPROVAL �+ FOR A SINGLE FAMILY DWELLING Parcel I.D. Q(S- Ila - 14 HAA# D5=51' ,,CUP A kN Expiration Date: 1. GE W9 TffffaFess0r diRections) 1674 �_,r�,..g.gMAM Currpht property vwnefktq! err- Day phone 244 -Tzq c> Mailing address ZgC4 W. rJav_T?h-=Z ,, rs2-, q�� Lending agency Day phone Mailing address Real Estate Agent Day phone Mailing Address Unless otherwise requested, HAA will be held by DSD for pickup. 2. NUMBER OF BEDROOMS: 3. TYPE OF WATER SUPPLY: • TYPE OF WASTEWATER DISPOSAL: Individual Well Individual On-site Individual Water Storage ❑ Individual Holding tank ❑ Community Class Well ❑ Community On-site ❑ Public Water System ❑ Public Sewer ❑ The Municipality of Anchorage Development Services Department (DSD) Issues Certificates of Health Authority Approval (HAA) based only upon the representations given in paragraph 4 by an independent professional civil engineer registered in the State of Alaska. Certificates of Health Authority Approval are required for the transfer of title (except between spouses) for properties served by a single-family on-site wastewater disposal and/or water supply system. DSD also issues HAAs upon request to homeowners. Certificates of Health Authority Approval are valid for 90 days from the date of issue for properties served by a private or Class C well and may be reissued with new water sample results. (Certificates may be reissued for a period of up to one year with valid water samples.) Certificates are valid for one year for properties served by Class A or B wells or a public water system. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 4. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Health Authority Approval Guidelines for this application, shows that the on- site water supply and/or wastewater disposal system is(are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm -971.4 e-aArtreo(nn Jy 4t -- Phone 344 Address ;?e Rose t/a zs-r Awna, Ate. Engineer's Printed Name '_9zi4,.f T 1,44,2r,G,✓ 5. DSD SIG ATURE Approved for L— bedrooms. Disapproved. Date l — it — as Conditional approval for bedrooms, with the following stipulations: Attachments: HAA Checklist X Septic System Advisory Well Flow Advisory -t- (R. 0111) Maintenance Agreements Supplemental Engineer's Report Other Municipality of Anchorage •,. Development Services Department Building Safety Division On -Site Water & Wastewater Program 4700 South Bragaw St. P.O. Box 196850 Anchorage, AK 99519-6650 www.cLanchorage.ak.us . (907)343-7904 HEALTH AUTHORITY APPROVAL CHECKLIST' Legal Description: L.4r- 4 6N6r1_ d p Parcel ID: o/S- //2- /4 A. WELL DATA Well type i?&/*m If A, B, or C provide PWSID tl _ Well Log (Y/N) Yc-�- tfnk=H, Date completed JZ,- Z3 -cm4- Sanitaryseal (YIN) %I Wires properly protected (YIN) Y Total depth lj�_ft. Cased to _Z22_ft. Casing height (above ground) 2¢ E in. FROM WELL LOG AT INSPECTION tJ =cJ Date of test I Z - 23 -04 Static water level ft. Well production 2O g.p.m. g.p.m. WATER SAMPLE RESULTS: Coliform ­4—colonies/100 ml. Nitrate ,+W mg./I.. Other bacteria-4(—colonies/100 ml. Arsenic: 4; mg. 1. Date of sample: te_r -65- Collected by: r= �E B. SEPTIC/HOLDING TANK DATA Tank Type/MaterialA�.�e -ara �� crF�-� Date installed q - Z w - e4 Tank size A gal. Number of Compartments _7 Cleanouts (YIN) Y J �u�, T* ?xbSSLX a S�K- 1 Foun \'A Depression over tank (YIN) nl High water alarm (YIN) YES rZE- Date,ot puri9a ••N 1 Pumper �� <t C. ABSORPTION T-1ELD DATA Date installed L9- z4 -o¢ Soil rating (g.p.d./ftZ or ft2/bdrm) System type <- w t n e Length 26 ft. ` ' Width S ft. Gravel below pipe O. S' ft. Total depth ( ft. Eff. absorption area /?D ft' Monitoring tube Depression over field rJ Date of adequacy test tAjE&,1 Results (Pass/Fail) SASS For 4 be Fluid depth in abso fore test _ in. Wa _ gal. New depth_ in. Elapsed Time: _ treatment (past 12 mo.) (YIN & type) NIA taco SY5rvr1 Absorption rate >= ... D. LIFTSTATION trtS-oe t4,)SE Date `Pump on' level at _ in. E. SEPARATION DISTANCES Size in gallons Cycles tested SEPARATION DISTANCES FROM WELL ON LOT TO High water alarm level at requirements? r � Septic tank/lift station on lot 1/6 On adjacent lots J f e-0 Absorption field on lot 125' 1 On adjacent lots /02. S v Public sewer main 141.4 Public sewer manhole/cleanout Sewer /septic service line <Z% -r,' Holding tank Ni ( A in. SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: r Building foundation 2a• 4S Property line S•4S Absorption field S Water main ..t I^ Water service line �4 ` Surface water > it ar r Wells on adjacent lots join SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Property line S Building foundation 32. Water main N I A Water Service line 97.-5 ` Surface water 7 t 0 ` Driveway, parking/vehicle storage 85 r Curtain drain > rOa Wells on adjacent lots F. COMMENTS r� Laxe, Td :zAJ✓ ' I.JS wI 4- G. ENGINEER'S CERTIFICATION 01 rw/T F . ZfYnuCAni 'fes,\lki, I certify that I have determined through field inspections and - ��►•`��• •••a�.q f+, review of Municipal records that the above systems are in �11P''•• ��, conformance with MOA HAA guidelines in effect on this dale..4M Engineers Printed Name -97.A,_3 T a2ek�— %• •� BQIAN L W1itB1 Date 6 -tom- es HAA Fee $ .� ' S� ��5. 02) Waiver Fee $ ��4pR0EESSt�at� �� Date of Payment y�/D� Date of Payment Receipt Number l0 9J� L� Receipt Number (Rev. 12/01) -- 06-14-05 04:52PM FROM -ME ESI. SCS ENV SERVICES ro1 SGS Ref -If 1053060001 C11ent Name 6711 Construction Project Naimoli! Lot 4 Shell f2 Client Sample W Lot 4 Shell #2 ptatria Drinking Water 9075615301 T-073 P.02/04 F-537 AU Date%Mmes are Alaska Standard Time Printed Dattfrime 06/13/2005 16:02 Collected Datefrime 06/012005 23:30 Received DateMme 06/02/2005 11.20 Technical Director Stephen C. Ede PWSID 0 Sample Remarks: Allowable Prep Analysis Paameter Results PQL Units Method Container ID Limits Date Date Init H.tal• by SCP/HS Arsenic 10.0 U 10,0 ug/L 610210 EP200.8 C 05 06/09/05 SCL tsatars Depaz� OA88 0.100 mIVL EPA 300.0 D (<-10) 06!03105 RIA Nitrate -N Hiezobiolorry Laboratory coUl0om1 SM2092229 A loll 002105 TLF Total Coliform 0 30' 8- 0 z 111=20' P -326A SHELL SUBDIVISION N0. 2 LOT 4 12,000 S.F. (REC) 12,017 S.F. (MEAS) EAST 120.00'(REC) -BU I LT GASTALDI LAND SURVEYING, LLC JEFF A. GASTALDI, R.L.S. 4726 WEST 88TH AVENUE ANCHORAGE, ALASKA 99502 PHONE 248-5454 I GRID DATE 2536 110/18/2004 I F.B. JOB NO. 04-11 1 SHELL14 WEST 120.00'(REC) I HEREBY -CERTIFY. THAT I HAVE SURVEYED THE PROPERTY DEPICTED ABOVE AND THAT NO ENCROACHMENTS EXIST EXCEPT AS INDICATED. R IS THE RESPONSIBILITY OF THE OWNER TO DETERMINE THE EXISTENCE OF ANY EASEMENTS, COVENANTS OR RESTRICTIONS WHICH DO NOT APPEAR ON THE RECORDED SUBDIVISION PLAT. UNDER NO CIRCUMSTANCES SHOULD ANY DATA HEREON BE USED FOR CONSTRUCTION OR FOR ESTABLISHING BOUNDARY OR FENCE LINES. ANCHORAGE RECORDING DISTRICT, ALASKA NOTE: NO CORNERS SET THIS DATE. U K OF A 4 Q p �� ••......• qs �. AV co ....................:. / v: ery A. Gastaldl % LS -6091: 4 �`�"• %...c? ♦ ••�� te\lsLss* X. 0 S 89.58'40"E 120.00- (MEAS) WELL c n � aa.o• o b e.a 20 140- . .�.. 2 0.0• b n 5� O 0 a e.o• EXISTING BUILDING $ 3 GRAVEL DRIVE W n a te.o• co 8 a i? 8 z 40.o• C i S V'�U(r V) bq • n o. SEPTIC n SYSTEM �v 25.4' N 89°57'34"W 120.21 (MEAS) -BU I LT GASTALDI LAND SURVEYING, LLC JEFF A. GASTALDI, R.L.S. 4726 WEST 88TH AVENUE ANCHORAGE, ALASKA 99502 PHONE 248-5454 I GRID DATE 2536 110/18/2004 I F.B. JOB NO. 04-11 1 SHELL14 WEST 120.00'(REC) I HEREBY -CERTIFY. THAT I HAVE SURVEYED THE PROPERTY DEPICTED ABOVE AND THAT NO ENCROACHMENTS EXIST EXCEPT AS INDICATED. R IS THE RESPONSIBILITY OF THE OWNER TO DETERMINE THE EXISTENCE OF ANY EASEMENTS, COVENANTS OR RESTRICTIONS WHICH DO NOT APPEAR ON THE RECORDED SUBDIVISION PLAT. UNDER NO CIRCUMSTANCES SHOULD ANY DATA HEREON BE USED FOR CONSTRUCTION OR FOR ESTABLISHING BOUNDARY OR FENCE LINES. ANCHORAGE RECORDING DISTRICT, ALASKA NOTE: NO CORNERS SET THIS DATE. U K OF A 4 Q p �� ••......• qs �. AV co ....................:. / v: ery A. Gastaldl % LS -6091: 4 �`�"• %...c? ♦ ••�� te\lsLss* X. 0 Municipality of Anchorage Development Services Department • +� Building Safety Division On -Site Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.muni.org/onsite (907)343-7904 ON-SITE SEWER/WELL SUBMITTAL COMMENT SHEET To: Brian Horten Legal description: Shell #2 Subdivision. Lot 4 The attached paperwork has been reviewed and Is being returned for the following reasons: ❑ Original signature or stamp missing on ❑ Calculation error in design. _ ❑ Additional soils information needed. ❑ Water monitoring results inadequate. _ ❑ Discrepancy in information submitted. _ ❑ Topographic information missing or �inadequate. _ ® Incomplete; missing number of kedrooms and well ® Incomplete; missing screws on well seal; signed maintenance agreement from buyer; well Identification tog ❑ Additional adequacy test information needed. ❑ Water sample unacceptable. _ ❑ Measured/proposed distances/dimensions missing. ❑ Locations of all soils, percolation and water monitoring tests not shown. _ ❑ Proposed system too deep for soils information submitted. ❑ Well log required. _ ❑ Omission in narrative. ❑ Insufficient fi over tank or field._ ❑ Other. 1 Plegse verify inspection dates; 2. bsorption field not installed in accordance Name of reviewer: Julie Mokela Date: 6/15/2005 Please supply the necessary information and re -submit your request. LEAVE THIS FORM ATTACHED TO THE PAPERWORK