Municipality of Anchorage Page 1 of 3
Development Services Department
On -Site Water and Wastewater Program
4700 South Bragaw Street
P.O. Box 196650 Anchorage, AK 99519-6650
wwwr.ci.anchorage.ak.us (907) 343-7904
ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT
Permit Number: SWO50142 PID Number: 051-801-55
Name:
S inell Homes
Wastewater System: New
Address:
1900 W. Northern Lights Anch. AK 99518
ABSORPTION FIELD
Phone: Number of Bedrooms:
Shallow Bed
344-5678 Five 5
LEGAL DESCRIPTION
Soil Rating:
1
Total Depth from original grade:
GPDIFI'
+1 Ft.
Black: Let: Subdivision:
Depth to pipe bottom from original grade:
Gravel depth beneath pipe:
8 15 The Tablelands
+.5 Ft.
.5 Ft.
Township: Range: Section:
Fill added above original grade.
Gravel Length:
3-5 Ft.
53 Ft.
Well: AWWU Water System
Gravel width:
15
Number of lines:
3
Distance between lines:
Ft.
5 FL
Classification (Private, A, B, C):
Total Depth:Cased
to:
Total absorption area:
Pipe Material:
Ft.
Ft.
795 Ft=
ASTM 3034 PVC
Driller,
Date Drilled:
Static Water Level:
Installer
Data Installed:
FL
Paisano's Dirtworks
7/14-20/2005
Yield :
Pump Set at:
Casing eight Above Ground:
TANK
GPM
Fl.
Fl.
SEPARATION DISTANCES
Advantex Treatment System
To
Septic
Absorption
Lift
Holding
ubliclPrivate
Manufacturer:
Capacity inGallons:
From
Tank
Field
Station
Tank
Sewer Line
Anchorage Tank
2,000
well
>200'
>200'
>200'
N/A
>25'
Material:
Steel
Number of Compartments:
Two (2)
Surface Water
>100'
>100'
>100'
N/A
LIFT STATION
Let line
>5'
>10'
>5'
N/A
ize:
500 Gal.
an ac rw..
Anchorage Tank/Orenco
Foundation
>5'
>10'
>5'
NIA
'Pump on' level at:
'Pump off level at:
High, alarm at:
28 in.
28 in.
34 in.
Curtain Drain
None
Noted
Pump Make B Model
Orenco
Electrical Inspections performed by:
Allied Alaska Electric
Remarks:
BENCH MARK
Location and Description:
Finished Floor
Assumed Elevation:
100.0 Ft.
Engineer's Stamp
.�**SS1ttg1kiOF 4
�y
Inspections performed by: TLK dates: 1'l 7/14/05
..... '....;19tn
1 yyl
/o�$OII Qyoi Pig e:t0.lfiWr bY 6�J�/06 2"d 7/20/05
Department Health Human
it MI% NDER50 �
0` '
of and Services approval
PP
� revel=
s No. CE -4381
1<�,p'••.lt-so-D,�^'F�'�
rftonalI t
Reviewed an roved b ® w'c /t1Qkela WA Date: �//04
��p� pROFEss :•��
r4 FE S\
(Rev. IM9)
A . rove �!
ANDERSON ENGINEERING
P.O. BOX 240773
ANCHORAGE, AK 99524
522-7773 677-7766 (FAX)
MEMORANDUM
DATE: November 4, 2012
TO: Jeff Poet
FROM: Mike Anderson, P.E.
SUBJECT: The Tablelands, Block 8, Lot 15
Septic System Permit No. SWO50142
Topsoil and seeding has taken place on the septic system area serving the subject lot.
Revegetation is complete and there is no danger of erosion to the slopes of the
completed mound. The conditional status of the inspection report should be removed.
C7
Ax-� 6 � t'•vy�66
Ol
S
.W ( t
d
Lr):
f
•�1�,s..
�{ t
2
_
+i•
O
d001 8VO NYS
too,
IL
0
n
XTL I ALK.00.00 N
oo M.v
Lt'til��
\ '1N9 3 30 '1 .St
_
eth O)
I C
iG in f O
II% O
Z U
'
\Y6
�
n
`m
stn "
C
Z
0 U
\
N
\\\
to O >
LL,
O CLQ 0
i 00
\
c W pt N
m y
H
QU"
V)U
o�ON
�O
8
rMQ
.O Z O)"
C)
Z 0
N J
nJW
_ME��
gig
` a�
o
Q 6
M
$�
w 3
J H
m Q
o
T
��r7
J
Q CO f0
Q J
C`.1
< "
�3
~
[EEE9
1
00
N
O
o>�
Cn
L
t0
O
.LC'8St N..69.0.00 N
E
7
2
01
a
Municipality of Anchorage
DEVEOPMENT SERVICES DEPARTMENT
4700 South Bragaw Street Anchorage, AK. 99519-6655 - 343-7904
On -Site Wastewater Disposal System or Well Inspection Report Page 3 of 3
Permit Number. SM50142
TEM -
PID No. 051-801-55
R� I 2' EPS Insulntlon
—I g
ADVANTEX
TANK
PROFILE AS -BUILT
Scale: NONE
)J
�� !limos
November 5, 2005
Anderson Engineering
Attn: Mike Anderson
P.O. Box 240773
Anchorage, AK 99524
EGEC -M CA L
CONTRACT/NG
FAX: (907) 677-7766
Subject: Lift Station Inspections at properties stated below.
This letter is to confirm that the lift station(s) at:
• Lot 2, Block 9 —The Tablelands
• Lot 15, Block 8 — The Tablelands
were wired by a licensed Journeyman Electrician in accordance with the 2002 National Electric
Code requirements.
If you would like any further information, please feel free to call our office at the numbers listed
below.
Thank you.
Sincerely,
ALLIED ALASKA ELECTRIC, L.L.C.
Janette L. Brown,
Vice President/CFO
cc: file
P.O. Bax 876310, Wasilla, Alaska 99687 (907) 373-3893 ofe / (907) 232-8687 cell / (907) 373-3894 fax
T•d 468E-ELE (LOS) OIJ10aT3 RMSUTH PaTTTH dTD:20 s0 40 ^aFP
MUNICIPALITY OF ANCHORAGE
Development Services Department
On -Site Water & Wastewater Program
4700 South Bragaw Street
P.O. Box 196650, Anchorage, AK 99519-6650
(907) 343-7904
ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT
Initial
Date Issued: May 26, 2005
Expiration Date: May 26, 2006
Permit Number: SWO50142 Parcel ID: 051.801-55
Legal Description: THE TABLELANDS SUBDIVISION BLOCK 8 LOT 15
Design Engineer: 0014 Anderson Engineering Site Address: 22422 SAMBAR LOOP
Owner Name: SPINELL HOMES, INC. Lot Size: 40001 SO. FT.
Owner Address: 22422 SAMBAR LOOP Total Bedrooms: 5 Permit Bedrooms: 5
PETERS CREEK. AK 99567 -
This permit is for the construction of:
❑✓ Disposal Field ❑✓ Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage
All construction must be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations (18AAC72 ) and Drinking Water Regulations (18AAC80 ).
3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling
(907) 343-7904 ( 24 hours). ( Not required for a Water Supply Permit only).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
must be either: A. Open and closed on the same day.
B. Covered, sealed, and heated to prevent freezing.
Received By.
Issued By.
Date: 5�-- yl_o
�. is _40=
Municipality of Anchorage
-� Development Services Department
Building Safety Division:' 7
On -Site Water and Wastewater Program s ..
4700 South Bragaw St.
P.O. Box 196650 Anchorage, AK 99519-6650
www.ci.anchorage.ak.us
(907)343-7904
ON-SITE SEWER/WELL PERMIT APPLICATION
FOR A SINGLE FAMILY DWELLING
Parcel I.D. bsI—sol_ 55 Permit Number SW
Property owner(s) Spineil Homes, Inc. Day phone 344-5678
Mailing address (1)1900 W. Northern Lights Blvd. Suite 200 Anchorage, AK 99517
Mailing address (2))Ag99, Sambar Loop Zip Code
Legal description (Lot, Block & Sub'd.) Lot 15, Block 8, 11K jAf3LLLA)Q05
Legal description (Section, Township & Range)
Lot Size 40.001 SF Acres/Sq.Ft. Number of Bedrooms Five (5)
THIS APPLICATION IS FOR:
Sewer Only ® Well Only ❑
Sewer and Well ❑ Water Storage ❑
Sewer Upgrade ❑
THIS PROPERTY CONTAINS:
Hot Tub ❑ Jacuzzi ❑
Swimming Pool ❑ Water Softening Unit ❑
Therapy Pool ❑
certify that the above information is correct. I further certify that this application is being made for a
Single Family Dwelling and is in accordance with applicable Municipal Codes.
(Signature of property owner or authorized agent)
Date of Payment:
Receipt Number: it (ill I.`J Receipt Number:
(Rev. 12/00)
ANDERSON ENGINEERING
P.O. BOX 240773
ANCHORAGE, AK 99524
522-7773 522-6779 FAX
May 26, 2005
Municipality of Anchorage
Development Services Department
On -Site Water and Wastewater Program
4700 South Bragaw Street
Anchorage, AK 99519-6650
Subject: Lot 15, Block 8, The Tablelands Subdivision
Septic System Design and Permit Application
Impacts to Adjacent Properties
Dear Onsite Services Engineer.
The groundwater level on Lot 15, Block 8, The Tablelands Subdivision has
unexpectedly risen making our original design for the septic system for this property no
longer usable. We are therefore proposing to place an Advantex Septic Treatment
System for a five -bedroom home on the property. The attached Site Plan and backup
documentation identify the location and configuration of the new septic system and
alternate site and the parameters used in the design. Also identified on the plans are
the location of the surface drainage, test holes and water service on the lot. The
system will not conflict with those on the surrounding lots. Drainage arrows and spot
elevations are shown indicating the current drainage patterns. The drainage patterns
will be maintained after construction.
The test holes placed on this lot revealed silt with some sand. The percolation rate in
the upper layers ranged from 40 minutes to 60 minutes per inch. Groundwater was
recently noted at 3' below the surface. We are therefore proposing to place a five -
bedroom Advantex Treatment System. The terrain of.the lot is such that gravity flow
from the filter to the absorption bed is not possible and a second lift station will be
required. The absorption bed will be 50' long x 15' wide for a total absorption area of
750 square feet. The bed will be constructed at the existing ground level. Approximately
1' of clean coarse sand will be required to replace the organic layer removed below the
bed and to level the bed area.
The ground surface on the lot slopes as shown on the site plan from west to east at
shallow slopes. The absorption bed will be constructed parallel with the slope as much
as possible in conformance with Municipal requirements. All components of the new
Lot 15, Block 8, The Tablelands
May 26, 2005
Page Two
septic system will be constructed a minimum of 100' from any surface water and 10'
from the water service on this and adjacent lots.
If the system is constructed in accordance with our design the following statements
apply:
1. The system, if constructed as designed, will have no adverse impact on the wells
in the area or those to be constructed in the future.
2. The system, if constructed as designed, will have no adverse impact on existing
septic systems in the area or those to be constructed in the future.
3. The system, if constructed as designed, will have no adverse impact on reserve
space, either surface or subsurface, on any lots located in the area.
4. The system, if constructed as designed, will have no adverse impact on drainage
patterns in the area. The current drainage pattern will be maintained.
Sincerely,
Michael E. Anderson, P.E.
Attachments
dOOI avewvs
0
o
ooL'9 & -a ,9Z'Zft ,KtS,fODO N Z1'91-7
\ 'L'153 '3 8 -1.91
(Lw
\ s
\
\
`8
\M
V1�
> y�
L_ b I c
00
9 I
a CLu
e
(n O cL _ '�. �'� W
J
JL� bo<cn Fn vi• ` LJ
C) s z _
o zci m-- —� �--i
w
N � O ae
w �— € N
J
W
2
H
,Lf'91;1 N,69,L0.00 N ���•' *' •..; 'f •��I
u
•1U%•' O,'
LOT 15, BLOCK 8, THE TABLELANDS
SUBDIVISION
DESIGN FACTORS: SYSTEM REQUIREMENTS:
Five Bedroom Home
Raised Bed System
Perc. Rate: 40 Min.Anch
Advantex Treatment System for 5 Bedroom Home
Application Rate: 1 GPD/SF
500 Gallon Lift Station
1' (Min.) Coarse Sand
5 Bedrooms X 150 GPD/1 GPD/SF(Application
750 SF/15 SF (Width) = 50 LF Bed
Rate) = 750 SF Absorption Area
Length
THEREFORE: Construct a 50" Long x 15' Wide Raised Absorption Bed as Shown Below.
Remove Existing Piping in Existing Organic Material under Bed and Replace with Coarse Sand.
Place Distribution Piping at .5' Above Original Ground Surface. Provide 2" of Insulation
and 2' of Cover Over Bed or 3' of Cover. Place Topsoil and Seed on Outer 6" of Mound.
4
2" Insulation & 2' Cover (Min.) 1
•5' O O O
S Drainfield Rock 1" PVC
1'
Min. Remove Organics and Replace
With Clean Sand (See Specification)
2.5' 5' 5' 2.5'
NOTE: See Specifications for Clean Coarse Sand.
TYPICAL RAISED BED SECTION •
(NO SCALE) .�� P�•"
C;0
NOTE: Grade Area Surrounding Bed to Drain Away.
Minimum 6' Separation From Bedrock. :....;:. 49th
Minimum 4' Separation From Groundwater. �n
Minimum 200' Separation From Wells in the Area. i""':"""'"""'""""GGA!++
Andemm
Minimum 100' Separation From Surface Water or Streams. �0. :Michael E. -4381
♦ J, No. CE -4381 i
Minimum 10' Separation From Water Service Line. �� „•.,_ � „
0
z
H
V3
-- -- • 7J Mfg
v { g: O 0
{ MC Mrrr
8nkO
e a a ryr
07 Rd
e rr M O
NN 6!?
N O
•M04
Q CL
a C H C
z- a o
rr CD
,110
n CCD
f-4 JS
>< €� CD o
�v.
+ + sn �-
CD cn
CD 0
CD
r+.
• c
ADVANTEX AX -20
SEPTIC SYSTEM ANCHORAGE TANK WELDING, INC.
m
g
i
y
'^
'
�
o
�
`;
voo voncuvu+e onrve
o
STANDARD
MUNICIPALITY OF ANCHORAGE
DEVELOPMENT SERVICES DEPARTMENT
4700 SOUTH BRAGAW STREET ANCHORAGE, AK 99519-6650
SOILS LOG - PERCOLATION TEST
LEGAL DESCRIPTION: LOT 15, BLOCK 8, TABLELANDS S/D
PERFORMED FOR- SPINELL HOMES
DATE: 4/11/2005 PROJECT No • M0518
PARCEL ID,#- TECHNICIAN: M. ELDRIDGE
DEPTII TEST HOLE # 1
(rat)
I
2
READING
OB/OG SLOPE
TIGHT COMPACTION
3
NET DROP
(INCHES)
I
4/11/05
4
13
SILTY SANDS W/GRAVELS
1
GM
MEDIUM COMPACTION
5
CHARGE
SM -GM 0%
6
2
1400
7
16—
0.75"
8
BOH
17
9
11.25'
IO
WAS GROUND WATER ENCOUNTERED? YFS
4
19
IF YES 9 WHAT DEPIIO ID
I I
0.75"
DEPTII OF WATER AFTER MONITORING: S'
5
DATE OF MONITORING: SmIlI 5
12
READING
G OSS TIMEJ
MINUTES)
TIGHT COMPACTION
DEPTH of
OF
NET DROP
(INCHES)
I
4/11/05
SILTY SANDY GRAVELS
13
1
GM
14—
41516
12.0"
CHARGE
is-
2
1400
30
16—
0.75"
BOH
17
1400
11.25'
18
4
19
30
10.5'
0.75"
SITE PLAN
THI
O O
TH2
SFE FUTUR= ASBUILT
DATE
READING
G OSS TIMEJ
MINUTES)
NET TIME
(MINUTES)
DEPTH of
OF
NET DROP
(INCHES)
I
4/11/05
TEST HOLE PRESOAKED PRIOR TO TESTING:
1
1330
12.0"
CHARGE
2
1400
30
11.25'
0.75"
3
1400
11.25'
4
1430
30
10.5'
0.75"
5
I430
12.0"
RECHARGE
6
1500
30
11.25'
0.75"
PERCOLATION RATE5(MIN/INCII) FERC. }TOLE DIA. 6 (INCHES)
TEST RUN BETWEEN: 5.5 FT. and—L. 5 FT.
COMMENTS: NO IMPERMEABLE LAYERS ENCOUNTERED. TEST HOLE PRE SOAKED PRIOR TO TEST.
TEST PERFORMED BY VETECII ENGINEERING TECHNICAL SERVICE. I, MICHAEL E. ANDERSON CERTIFY THAT
THIS WAS PERFORMED IN ACCORDANCE WITI I ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS
DATE:
MUNICIPALITY OF ANCHORAGE
DEVELOPMENT SERVICES DEPARTMENT
4700 SOUTH BRAGAW STREET ANCHORAGE, AK 99519-6650
SOILS LOG - PERCOLATION TEST
LEGAL DESCRIPTION• LOT 15, BLOCK 8, TABLELANDS S/D
PERFORMED FOR: SPINELL HOMES
DATE: 4/11/2005 PROJECT No • M0518
PARCEL ID,;y TECHNICIAN: M. ELDRIDGE
DEPTII TEST HOLE # 2
(fcct)
OB/OG
`7
4 SILTY SANDS W/GRAVELS
MEDIUM COMPACTION
5 SM -GM
6
7
8
9
SITE PLAN
THI
O O
TH2
SEE FUTURE ASSUILT
IO WAS GROUND WATER LNCOUNTEREIr Yrs_
IF YES g MIAT DEPII? iP
11 DEPTH OF WATER AFTER AIONITOROIG: P 0%
DATE OF MONITORING: 3/134003
12
13
14
15
16
17
18
19
TIGHT COMPACTION
SILTY SANDY GRAVELS
GM
"®�
DATE
READING
G OSS TIME
MINUTES)
NET TIME
(MINUTES)
DEPTH of
WATER
(INCHES)
NET DROP
(INCHES)
4/11/05
TEST HOLE PRESOAKED PRIOR TO TESTING:
1
1340
12.0"
CHARGE
2
1410
30
11.375"
0.625"
3
1410
11.375"
4
1440
30
10.75"
0.625"
S
1440
12.0"
RECHARGE
6
1510
30
11.375"
0.625"
PERCOLATION RATE• 48 (MN/INCH) FERC. }TOLE DIA. 6 (INCHES)
TEST RUN BETWEEN. 5.5 FT. and 6.5 FT.
COMMENTS: NO IMPERMEABLE LAYERS ENCOUNTERED. TEST HOLE PRE SOAKED PRIOR TO TEST.
TEST PERFORMED BY VETECII ENGINEERING TECHNICAL SERVICE. 1, MICHAEL E. ANDERSON CERTIFY THAT
THIS WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS
DATE:
ON-SITE WASTEWATER DISPOSAL SYSTEM
CONSTRUCTION AND MATERIAL SPECIFICATIONS
SUBJECT: LOT 15, BLOCK 8, THE TABLELANDS SUBDIVISION
GENERAL:
1. The scope of this project includes the procurement and placement of a
new Five Bedroom Advantex Treatment System, which includes a
2,000 gallon tank with 2 AX -20 Pods to serve the new home on the lot.
A second lift station will also be required. System will be placed at the
location shown on the Site Plan. The new septic system also includes
the construction of a new 50' long X 15' wide X 1' effective depth
absorption bed at the location also shown on the Site Plan and at the
configuration shown. The distribution line in the bed will be placed 1'
above the existing ground surface. The total depth of the bed will be
V below the surface. A minimum of 1' of clean coarse sand will be
required to replace the organics excavated from the surface of the
property under the bed area. The new system must be placed a
minimum of 10' from the water service on the lot and those on
adjacent lots and 100' from any surface water located near or on the
lot.
2. Construction shall be in accordance with the approved site plan,
design drawings, Municipal Permit with any special provisions or
conditions, and all applicable State and Municipal Wastewater
Disposal Regulations.
3. The Contractor shall be responsible for obtaining all underground utility
locates and for the layout of the septic system and verification of the
location of all lot lines.
4. Unless specifically agreed otherwise, the contractor shall be
responsible for final grading areas subsequently depressed from soil
settling. Property owner shall be responsible for revegetation of
affected areas unless specifically agreed otherwise.
5. Contractors installing wastewater disposal systems must be certified
by the Municipal Department of Health and Human Services for
system installations. Owners installing their own systems must receive
prior approval from D.H.H.S. before beginning system installation.
SEPTIC TANK INSTALLATION
The Advantex Treatment System must be installed in conformance
with specifications and regulations furnished by the manufacturer,
Anchorage Tank and Orenco Systems Incorporated. No variances
from the manufacturers specifications will be allowed without
permission from the manufacturer and Municipal representatives.
Lot 15, Block 8, The Tablelands
May 26, 2005
Page 2 of 4
2. A septic tank is to be constructed by a certified septic tank
manufacturer. Construction shall include two 4" cleanouts for pumping
access.
3. The septic tank shall be sufficiently bedded to prevent settling or
shifting of the tank.
4. All standpipes on the septic tank shall extend a minimum of 12 inches
above final grade.
5. Tanks installed without 4' of cover shall have a minimum of 2" of direct
burial insulation.
6. A foundation cleanout shall be installed one to four feet from the
building foundation. Two cleanouts are required between the tank and
the drainfield.
7. Final grading over the tank shall be such that a positive slope exists
away from the septic tank.
DRAINFIELD CONSTRUCTION:
1. The drainfield shall be constructed to the dimensions shown on the
design. The bottom of the bed shall be within 2" of level.
2. Distribution piping must be placed level with perforations down atop a
level bed of drainfield rock. Rock should then be placed over the pipe
to provide a minimum of 2" of cover.
3. A silt barrier or geotextile fabric must be placed between the drainfield
rock and the natural soil backfill.
4. Monitor tubes must be 4" in diameter and installed at the locations
shown on the design. The portion below ground must be perforated.
5. Contractor shall verify the septic tank and drainfield are a minimum
100' away from any private water wells in the area, 150' from a Class
"C" Well or 200' from any community well.
6. Direct bury insulation must be placed over the distribution system if
less than 3' of backfill depth is available. Finish grade over the trench
must be mounded to prevent settlement or depressions.
7. Grade area surrounding the absorption trench to drain away.
8. A minimum 2' of accepting soil is required below the drainfield rock for
a 5' wide trench. Contractor shall verify this condition prior to
Lot 15, Block 8, The Tablelands
May 26, 2005
Page 3 of 4
placement of the rock. All pockets of unacceptable materials must be
removed and replaced.
MATERIAL SPECIFICATIONS:
1. Septic tanks must be constructed by a municipally approved septic
tank manufacturer.
2. The following pipe materials are approved for use in septic system
installations in the Municipality of Anchorage:
Cast Iron (perforated and solid), ASTM D3034 or P.V.C. (perforated
and solid), ASTM F810 or H.D.P.E. (perforated, but not solid) and
ASTM D2662 or A.B.S. (perforated and solid).
3. Insulation shall be at least 2" thick extruded direct burial polystyrene
(Dow Chemical Co. Styrofoam HI or equal).
4. Septic tank inlets and outlets shall be fitted with watertight couplings
(Caulder, Femco, or equal).
5. A permeable geotextile fabric (Typar, Mirafi or equal) must be installed
between the final drain rock layer and the native soil layer.
6. All drain rock shall be .5" to 2.5" in diameter with less than 3% passing
the #200 sieve.
SAND GRADATION:
1. Sand used to level the new absorption bed must have the following
gradation:
50% Passed the No. 4 Sieve
2% Passed the No. 100 Sieve
1% Passed the No. 200 Sieve
2. The sand source must be approved prior to use.
INSPECTIONS:
Municipal Ordinance requires a minimum of two inspections. These
inspections must be conducted under the supervision of a professional
engineer registered in the State of Alaska. The first inspection must be
conducted after the excavation of trenches, beds or pits and before the
installation of any gravel. A septic tank may be set in place, but may not
be backfilled.
Lot 15, Block 8, The Tablelands
May 26, 2005
Page 4 of 4
The second inspection must be conducted after the placement of the
geotextile fabric, gravel, distribution piping, standpipes, cleanouts and
insulation. No backfill should be in place at the time of inspection.
Contractor shall provide a copy of all field survey layout and construction
notes for use in preparing the certified as -built of the completed system.
ANDERSON ENGINEERING
P.O. BOX 240773
ANCHORAGE, AK 99524
522-7773 522-6779 FAX
April 23, 2005
Municipality of Anchorage
Development Services Department
On -Site Water and Wastewater Program
4700 South Bragaw Street
Anchorage, AK 99519-6650
Subject: Lot 15, Block 8, The Tablelands Subdivision
Septic System Design and Permit Application
Impacts to Adjacent Properties
Dear Onsite Services Engineer:
The owner of Lot 15, Block 8, The Tablelands Subdivision intends to construct a new
five -bedroom home on the lot. We are therefore requesting a permit be issued for the
construction of a new septic system to serve the new home. The subdivision is
currently served by a community water system. No conflicts exist with adjacent septic
systems or wells and the proposed septic system on this lot. The attached Site Plan
and backup documentation identify the location and configuration of the proposed
septic system and alternate site. The current drainage pattern is identified on the Site
Plan. The drainage pattern will be maintained after development of this lot is complete.
Test holes recently placed on the lot indicated silty gravel with minor amounts of sand in
the area of the absorption trench and alternate site. The accepting soils were tested
and found to have a percolation rate of between 40 minutes per inch and 60 minutes
per inch. The system is designed with an application rate of .3 GPD/SF. Groundwater
was found in the test holes during placement at 10' below the surface and was
monitored during the ensuing period at 7.5' below the surface. Our design includes the
placement of a new 1,500 -gallon septic tank along with 2 - 84' long and by 15' wide
absorption beds to collect and treat the sewage generated in the house. The bottom of
the beds will be 2.5' below the surface. The distribution pipe will be 2' below the
surface. A flow splitter valve will be installed to insure even flow to each bed. A
minimum of 3' of cover will be placed atop the beds and a minimum of 4' of cover will be
placed atop the new septic tank.
The ground surface on the lot slopes at varying grades from north to south as shown on
the Site Plan with steep slopes near the south end of the lot. The absorption beds will
Lot 15, Block 8, The Tablelands Subdivision
April 23, 2005
Page Two
be constructed parallel with the slope of the ground surface as much as possible in
conformance with Municipal requirements. The new septic system will be constructed a
minimum of 10' from the water service proposed for the lot and on adjacent lots. It will
also be constructed a minimum of 100' from any surface water in the area.
If the system is constructed in accordance with our design the following statements
apply:
The system, if constructed as designed, will have no adverse impact on the wells
in the area or those to be constructed in the future.
2. The system, if constructed as designed, will have no adverse impact on existing
septic systems in the area or those to be constructed in the future.
3. The system, if constructed as designed, will have no adverse impact on reserve
space, either surface or subsurface, on any lots located in the area.
4. The system, if constructed as designed, will have no adverse impact on drainage
patterns in the area. The current drainage pattern will be maintained.
Sincer�ely,
j
Michael E. Anderson, P.E.
Attachments
/ 49th ! \ l
WICNeEL E. ANDERSON
4 No. CE -419+ .
d001 avewvs
0
n
o .9Z'Zti A�fS,C0.00 N
\ 'L9S3 3 W U ,St
________ _____ ____________—__
\•3
��
Yo
\\ a a
\M %
ZO
;
�a
z
'
Q
>'"
00 in
L _
18 •
1
1 oy
o
m�
dr
8N
n
c
�'
L
r %
J
e
o
O
I L4 m
a z
m
W�
vmy z
r--
---�
z
C==
=-=C
t --i
LLI
CD O
— —
QJ
�
rr
>r
w
-
E
e
•
.LC*9SI M.GS.MDO N ��•P ,
-V,6�6.... v
3
LOT 15, BLOCK 8, TABLELANDS SUBDIVISION
DESIGN FACTORS: SYSTEM REQUIREMENTS:
5 Bedroom Home Shallow Bed System
Perc. Rate: 31-60 Min./Inch 1,500 Gallon Septic Tank
Application Rate: .3 GPD/SF 1' Total Depth Drainfield Rock
5 Bedrooms X150 SF/Bedroom/.3 GPD/SF(Application Rate) = 2,500 SF Absorption Area
2,500 SF/15 LF (Width) = 166.67 LF Bed Length
THEREFORE: Construct 2 - 84' Long x 15' Wide Shallow Beds as Shown Below.
Place Distribution Piping at 2.5' Below Original Ground Surface. Provide 3' of Cover
Over Bed and 4' of Cover Over Septic Tank. In Lieu of Fill Provide 2' of Insulation
and 2' of Fill. Place Diverter Valve to Insure Even Flow to Each Bed.
Existing Ground
Geolextile Fabric
.5' O O
5' Drainfield Rock
Underlying GM
2.5' 5'
5'
L BED SECTION
NOTE: Grade Area Surrounding Bed to Drain Away.
Minimum 6' Separation From Bedrock.
Minimum 4' Separation From Groundwater.
Minimum 200' Separation From Wells in the Area.
Minimum 100' Separation From Surface Water or Streams.
Minimum 10' Separation From Water Service Line.
N
2.5'
4' PVC
MUNICIPALITY OF ANCHORAGE
DEVELOPMENT SERVICES DEPARTMENT
4700 SOUTH BRAGAW STREET ANCHORAGE, AK 99519-6650
SOILS LOG - PERCOLATION TEST
LEGAL DESCRIPTION: LOT 15, BLOCK 8, TABLELANDS S/D
PERFORMED FOR- SPINELL HOMES
DATE: 4/11/2005 PROJECT No • M0518
PARCEL ID,#• TECHNICIAN: M. ELDRIDGE
DEPTH TEST HOLE # 1
(fcct)
09/OG
4 SILTY SANDS W/GRAVELS
MEDIUM COMPACTION
5 SM -GM
6
7
s
9
SLOPE
lOWAS GROUNDWATER EVCONITERFD? YPS_
IF YES (q NTUT DFJ'TIC Id
OEM OF WATER AFTER MONRORDIG: 15'
I I DATE OF MONITORING: 4IS1003
12
READING
GROSS TIME
(MINUTES)
TIGHT COMPACTION
D ATER F
(INCHES)
NET DROP
(INCHES)
4/11/05
SILTY SANDY GRAVELS
13
1
GM
14-
41516
12.0"
CHARGE
15-
2
1400
30
16
0.75'
BOH
17
1400
11.25"
SITE PLAN
THI
O O
TH2
SEE FUTURE AS9UILT
DATE
READING
GROSS TIME
(MINUTES)
NET TIME
(MINUTES)
D ATER F
(INCHES)
NET DROP
(INCHES)
4/11/05
TEST HOLE PRESOAKED PRIOR TO TESTING:
1
1330
12.0"
CHARGE
2
1400
30
11.25'
0.75'
3
1400
11.25"
4
1430
30
10.5"
0.75"
5
1430
12.0"
RECHARGE
6
1500
30
11.25"
0.75"
PERCOLATION RATELLO--(MINANCII) FERC. HOLE DIA. 6 (INCHES)
TEST RUN BETWEEN:: 5.5 FT. and 6.5 FT.
COMMENTS: NO IMPERMEABLE LAYERS ENCOUNTERED. TEST HOLE PRE SOAKED PRIOR TO TEST.
TEST PERFORMED BY VETECII ENGINEERING TECHNICAL SERVICE. I, MICHAEL E. ANDERSON CERTIFY THAT
THIS WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS
DATE:
MUNICIPALITY OF ANCHORAGE
• " DEVELOPMENT SERVICES DEPARTMENT
4700 SOUTH BRAGAW STREET ANCHORAGE, AK 99519-6650
SOILS LOG - PERCOLATION TEST
LEGAL DESCRIPTION: LOT 15, BLOCK 8, TABLELANDS S/D
PERFORMED FOR: SPINELL HOMES
DATE: 4/11/2005 PROJECT No • M0518
PARCEL ID#• TECHNICIAN: M. ELDRIDGE
DEPTH TEST HOLE # 2
(reel)
OB/OG
2
3
4 SILTY SANDS W/GRAVELS
MEDIUM COMPACTION
5 SM -GM
6
7
8
9
0%
SITE PLAN
THI
O 0
TH2
SFE FUTURE AS9UILT
WAS GROUND NATER ENCOUNTERED? yys_
10 IF YES C% WHAT DEI'nr IV
DEMI OF NATER AFTER MONITORING: 7.5- `/S OHIO
I I DATE OF MONITORING: 411512M5 I}tC(
12
13
14
15
16
17
18
19
TIGHT COMPACTION
SILTY SANDY GRAVELS
GM
'®�
DATE
READING
GROSS TIME
(MINUTES)
NET TIME
(MINUTES)
DjnEjgTERP
(INCHES)
NET DROP
(INCHES)
4/11/05
TEST HOLE PRESOAKED PRIOR TO TESTING:
I
1340
12.0"
CHARGE
2
1410
30
11.375"
0.625"
3
1410
11.375•
4
1440
30
10.75"
0.625"
5
1440
12.0"
RECHARGE
6
1510
30
11.375"
0.625"
PERCOLATION RATE; 48(MI'J/INCII) PERC. }TOLE DIA• 6 (NC}IES)
TEST RUN BETWEEN. 5.5 FT. and 6.5 FT.
COMMENTS: NO IMPERMEABLE LAYERS ENCOUNTERED. TEST HOLE PRE SOAKED PRIOR TO TEST.
TEST PERFORMED BY VETECII ENGINEERING TECHNICAL SERVICE. 1, MICHAEL E. ANDERSON CERTIFY THAT
THIS WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS
DATE:
ON-SITE WASTEWATER DISPOSAL SYSTEM
CONSTRUCTION AND MATERIAL SPECIFICATIONS
SUBJECT: LOT 15, BLOCK 8, THE TABLELANDS SUBDIVISION
GENERAL:
The scope of this project includes the procurement and placement of a
new 1,500 -gallon septic tank at the location shown on the Site Plan.
Work also includes the construction of 2 new absorption beds each 84'
long X 15' wide also at the location also shown on the Site Plan and at
the configuration shown. The distribution line in the beds will be
placed at 2' below the existing ground surface. The total depth of the
beds will be 2.5'. A flow splitter valve must be placed to insure even
flow to each bed. The new tank and absorption beds must be placed
a minimum of 10' from the water service on the lot. They must also be
placed a minimum of 100' from any surface water.
2. Construction shall be in accordance with the approved site plan,
design drawings, Municipal Permit with any special provisions or
conditions, and all applicable State and Municipal Wastewater
Disposal Regulations.
3. The Contractor shall be responsible for obtaining all underground utility
locates and for the layout of the septic system and verification of the
location of all lot lines.
4. Unless specifically agreed otherwise, the contractor shall be
responsible for final grading areas subsequently depressed from soil
settling. Property owner shall be responsible for revegetation of
affected areas unless specifically agreed otherwise.
5. Contractors installing wastewater disposal systems must be certified
by the Municipal Department of Health and Human Services for
system installations. Owners installing their own systems must receive
prior approval from D.H.H.S. before beginning system installation.
SEPTIC TANK INSTALLATION
A new 1,500 -gallon septic tank must be procured from an approved
source and installed at the location shown if the existing septic tank is
found to be defective.
2. A septic tank is to be constructed by a certified septic tank
manufacturer. Construction shall include two 4" cleanouts for pumping
access.
3. The septic tank shall be sufficiently bedded to prevent settling or
shifting of the tank.
Lot 15, Block 8, The Tablelands
April 23, 2005
Page 2 of 3
4. All standpipes on the septic tank shall extend a minimum of 12 inches
above final grade.
5. Tanks installed without 4' of cover shall have a minimum of 2" of direct
burial insulation.
6. A foundation cleanout shall be installed one to four feet from the
building foundation. Two cleanouts are required between the tank and
the drainfield.
7. Final grading over the tank shall be such that a positive slope exists
away from the septic tank.
DRAINFIELD CONSTRUCTION:
The drainfield shall be constructed to the dimensions shown on the
design. The bottom of the bed shall be within 2" of level.
2. Distribution piping must be placed level with perforations down atop a
level bed of drainfield rock. Rock should then be placed over the pipe
to provide a minimum of 2" of cover.
3. A silt barrier or geotextile fabric must be placed between the drainfield
rock and the natural soil backfill.
4. Monitor tubes must be 4" in diameter and installed at the locations
shown on the design. The portion below ground must be perforated.
5. Contractor shall verify the septic tank and drainfield are a minimum
100' away from any private water wells in the area, 150' from a Class
"C" Well or 200' from any community well.
6. Direct bury insulation must be placed over the distribution system if
less than 3' of backfill depth is available. Finish grade over the trench
must be mounded to prevent settlement or depressions.
7. Grade area surrounding the absorption trench to drain away.
8. A minimum 2' of accepting soil is required below the drainfield rock for
a 5' wide trench. Contractor shall verify this condition prior to
placement of the rock. All pockets of unacceptable materials must be
removed and replaced.
Lot 15, Block 8, The Tablelands
April 23, 2005
Page 3 of 3
MATERIAL SPECIFICATIONS:
1. Septic tanks must be constructed by a municipally approved septic
tank manufacturer.
2. The following pipe materials are approved for use in septic system
installations in the Municipality of Anchorage:
Cast Iron (perforated and solid), ASTM D3034 or P.V.C. (perforated
and solid), ASTM F810 or H.D.P.E. (perforated, but not solid) and
ASTM D2662 or A.B.S. (perforated and solid).
3. Insulation shall be at least 2" thick extruded direct burial polystyrene
(Dow Chemical Co. Styrofoam HI or equal).
4. Septic tank inlets and outlets shall be fitted with watertight couplings
(Caulder, Femco, or equal).
5. A permeable geotextile fabric (Typar, Mirafi or equal) must be installed
between the final drain rock layer and the native soil layer.
6. All drain rock shall be .5" to 2.5" in diameter with less than 3% passing
the #200 sieve.
COARSE SAND:
1. Coarse Sand must be graded as follows:
50% Passing No. 4 Sieve
3% Passing No. 100 Sieve
1% Passing No. 200 Sieve
INSPECTIONS:
Municipal Ordinance requires a minimum of two inspections. These
inspections must be conducted under the supervision of a professional
engineer registered in the State of Alaska. The first inspection must be
conducted after the excavation of trenches, beds or pits and before the
installation of any gravel. A septic tank may be set in place, but may not
be backfilled.
The second inspection must be conducted after the placement of the
geotextile fabric, gravel, distribution piping, standpipes, cleanouts and
insulation. No backfill should be in place at the time of inspection.
Contractor shall provide a copy of all field survey layout and construction
notes for use in preparing the certified as -built of the completed system.
Municipality of Anchorage
Development Services Department
+� Building Safety Division
On -Site Water and Wastewater Program
4700 South Bragaw St.
P.O. Box 196650 Anchorage, AK 99519-6650
www.muni.org/onsite
(907)343-7904
ON-SITE SEWER/WELL SUBMITTAL COMMENT SHEET
To: Anderson Engineering
Legal description: The Tablelands Subdivision. Block 8 Lot 15
The attached paperwork has been reviewed and is being returned for the following reasons:
❑ Original signature or stamp missing on —
❑ Calculation error in design. _
® Additional soils information needed. Proposed and reserve drainfield extend beyond 30 feet
test hole radius.
® Water monitoring results inadequate. Shallower groundwater observed than reported on soil
❑ Discrepancy in information submitted. _,
❑ Topographic information missing or Inadequate.
❑ Incomplete; missing _
❑ Incomplete; missing _
❑ Additional adequacy test information needed.
❑ Water sample unacceptable. _
❑ Measured/proposed distances/dimensions missing.
❑ Locations of all soils, percolation and water monitoring tests not shown.
❑ Proposed system too deep for soils information submitted.
❑ Well log required.
❑ Omission in narrative.
❑ Insufficient fill over tank or field._
❑ Other. _
Name of reviewer: Julie Makelo. P.E.
Date: 5/3/2005
Please supply the necessary information and re -submit your request.
LEAVE THIS FORM ATTACHED TO THE PAPERWORK
rrtr'e. AellI
Municipality of Anchorage a
-. Development Services Department
Building Safety Division
on -Site Water and Wastewater Program
4700 South Bragaw St.
P.O. Box 196650 Anchorage, AK 99519-6650
www.ci.anchorage.sk.us 343- ge.ak.us �•
• � (907)343-7904
CERTIFICATE OF HEALTH AUTHORITY APPROVAL 4/
FOR A SINGLE FAMILY DWELLING
Parcell.D. 051-801-55 HAA# 05WLlI
Expiration Date: Lellr5lgimiln
1. GENERAL INFORMATION
Complete legal description Lot 15 Block 8 The Tablelands Subdivision
Location (site address or directions) 22422 Sambar Loop
Current Property owner(s) Soineli Homes, Inc. Day phone 344-5678
Mailing address
Lending agency
Mailing address
Real Estate Agent
Mailing Address
1900 Northern Northern Llahts Blvd. Anchorane. AK 99517Blvd. Anchorane. AK 99517
Unless otherwise requested, HAA will be held by DSD for pickup.
2. NUMBER OF BEDROOMS:
3. TYPE OF WATER SUPPLY:
Individual Well
Individual Water Storage
Community Class Well
Public Water System
Five 5
Day phone
Day phone
TYPE OF WASTEWATER DISPOSAL:
❑
Individual On-site
❑
Individual Holding tank
❑
❑
Community On-site
❑
®
Public Sewer
❑
The Municipality of Anchorage Development Services Department (DSD) Issues Certificates of Health Authority
Approval (HAA) based only upon the representations given In paragraph 5 by an independent professional civil
engineer registered in the State of Alaska. Certificates of Health Authority Approval are required for the transfer of
title (except between spouses) for properties served by a single family on-site wastewater disposal and/or water
supply system. DSD also Issues HAAs upon request to homeowners. Certificates of Health Authority Approval are
valid for 90 days from the date of Issue for properties served by a private or Class C well and may be reissued with
-new water sample results less than 30 days old. -(Cer ificates may be reissued for a period of up to one year with"'
valid water samples.) Certificates are valid for one year for properties served by Class A or B wells or a public water
system. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's
work.
4. STATEMENT OF INSPECTION BY ENGINEER
As certified by my seal affixed hereto and as of the validation date shown below, 1 verify that my investigation,
based on procedures outlined in the Health Authority Approval Guidelines for this application, shows that the on-
site water supply and/or wastewater disposal system Is(are) safe, functional and adequate for the number of
bedrooms and type of structure Indicated herein. I further verify that based on the Information obtained from the
Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or
wastewater disposal system is(are) in compliance with ail applicable Municipal and State codes; ordinances,
and regulations In effect at the time of installation.
Name of Firm Anderson Engineering Phone 522-7773
Address P.O. Box 240773 Anchorage, AK 99524
Engineer's Printed Name Michael E. Anderson, P.E. Date 12/20/2005
5. DSD SIGNATURE
Approved for bedrooms.
Disapproved.
Conditional approval for ,5_ bedrooms, with the following stipulations:
aan
inches of top soil on the mound absorption bed and vegetating the mound
absorption bed sufficiently,_Fre, r. ii erosion in array a e w th AM(• 1F 65
The work shall be completed.not later than June 15, 2006. Final COSH and final
-Lis Work-44--comPlated-_
Additional Comments
Attachments:
HAA Checklist X
Septic System Advisory
Well Flow Advisory
AND
7e
.SEVIvESQ�1���\,.
Maintenance Agreements''-!,, :
Supplemental Engineer's Report
Other
By: t ' ` ti ` Original Certificate Date:
(Ra. 12M)
..�� Municipality of Anchorage
Development Services Department
Building Safety Division
On -Site Water & Wastewater Program
4700 South Bragaw St.
P.O. Box 188850 Anchorage, AK 99519-850
www.et.anchorage.ak.us
(907)343-7904
HEALTH AUTHORITY APPROVAL CHECKLIST
A. WELL DATA
Weil type _
If A, B, or C provide PWSID #_
Well Log (YIN)
Date completed _
Sanitary seal (YIN) _
Wires properly protected (YIN)
Total depth ft
Cased to ft.
Casing height (above ground)
In.
FROM WELL LOO
AT INSPECTION
Date of test
Static water level
R
fL
Wall production
g.p.m.
9 -
p.m -WATER SAMPLE RESULTS:
Coliform colonles/100 ml. Nitrate mg.A.
Other bacteria colonies/100 ml.
Date of sample:
Collected by -
S. SEPTICIHOLDING TANK DATA
Tank Type/Materlal _ STEP/Steel
Date instaned 7114/2005
Tank size 2,000 gal
Number of Compartment g
Ckaanouts (YIN) Y
Foundation cleanout (Y/N).y
Depression over tank (YIN) jy
High water alarm (Y/N) Y
Date of pumping
Pumper New Construction
C. ABSORPTION FIELD DATA
Date Installed 7/14_2n/ftUrating (g.p.d.eorte/bdnn)I OPD/SF System type AdvaMex/Bed
Length 63 it Width 16 fL Gravel below pipe .6 M
Total depth 1 fL Eft. absorption area Zjtfe Monitoring tube X Depression over field IN
Date of adequacy test Results (Pass/Falq For _ bedrooms
Fluid depth in absorption field before test _ in. Water added_ gal. - New depth_ in.
Elapsed Time: _ min. Final fluid depth _ in. Absorption rate >s g.p.d.
Any rejuvenation treatment (past 12 mo.) (YM 6 type) N If yes, give date
D. LIFT STATION
Date installed 3/14/2005 Size in gallons 600 Manhole/Access (YIN) Y
'Pump on" level at It In. 'Pump ofr level at al In. High water alarm level at 94 In.
Dabrm Bottom of Tank Cycles tested New Construction Meets alarm & circult rmiuirenu ms? Y.
E. SEPARATION DISTANCES
SEPARATION DISTANCES FROM WELL ON LOT TO:
Septic tankAift station on lot N/A
Absorption fleld on lot N/A
Public sewer main N/A
Sewer /septic service One N/A
On adjacent lots N/A
On adjacent lots N/A
Public sewer manhoMJdeanout N/A
Holding tank N/A
SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO:
Building foundation >S Property One 317 Absorption field >1'
Water main >10' Water service One >10' Surface water >100'
Wells on adjacent lots >200'
SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO:
Property One >11Y Building foundation >1V Water main >10'
Water Service One' >10' Surface water >100' Ddveway. par *toddle storage >9
Curtain drain None Noted Wells on adjacent lots >21V
F. COMMENTS
0. ENGINEER'S CERTIFICATION
1 cer* that I have defemdned through field inspections and 4 49th
review of Munldpal records that the above systems are In
conformance nrfih MOA HAA guldelloes In effect on this date.
awun c ivaumr
Engineer's Printed Name Michael E. Anderson. P.E. Na�_'_',,,���,..
Date 12/2012005 44•,ehs
HAA Fee S 67
Date of Payment /z,- Zo - VS
Receipt Number '
(Rev, 1zVM
,lkta,oS, y� i�
ao
Waiver Fee
Date of Payment
Receipt Number
HOMES, Inc.
January 9, 2006
Re: James & Bianca Cross
Lot 15 Block 8 Tablelands
22422 Sambar Loop
Chugiak, AK 99654
To Whom It May Concern:
In signing below, the above-mentioned buyers release Spincll Homes, Inc. and accept full
responsibility to cover the mound or their septic system with six inches of topsoil and
seed it in accordance with AMC 15.65.
All work must be completed by June 15, 2006.
d
uyer
Buy
Spinel homes, Inc.
q (o
D to
_I h/GYo
Date
1l910to
Date
Before me this day of January 2006, appeared James and Bianca Cross and
Chemene Brcincr.
Qp�.'•OTA •••o��I �
N Ry�'
g iu'„ pUBLIG r' o
OF P'N'
1900 W. NORTHERN LIGHTS BLVD. • SUITE 200 • ANCHORAGE, ALA*Xj9S9 iS44-5678 • FAX: 344-1976
30'
b
0
z
�n
J
41 1
n
"=30'
ml
SOUS♦
37li •••: *�10
Air
..y AA Ga
LS -6091 •.' �R♦
• J
�fOssional $-GiN
Municipality of Anchorage
Development Services Department
• '� Building Safety Division : !�`_
On -Site Water and Wastewater Program = �''
4700 South Bragaw St. s r
P.O. Box 196650 Anchorage, AK 99519-6650
www.muni.org/onsite
(907)343-7904
ON-SITE SEWER/WELL SUBMITTAL COMMENT SHEET
To: Anderson Engineering
Legal description: The Tablelands Subdivision, Block S. Lot 15
The attached paperwork has been reviewed and is being returned for the following reasons:
❑ Original signature or stamp missing on
❑ Calculation error in design. _
❑ Additional soils information needed. _
❑ Water monitoring results inadequate.
❑ Discrepancy in information submitted.
❑ Topographic information missing or Inadequate.
® Incomplete; missing maintenance agreement signed by buyer
® Incomplete; missing manholes on as -built survey, water elevation on profile plan
❑ Additional adequacy test Information needed.
❑ Water sample unacceptable. _
❑ Measured/proposed distances/dimensions missing.
❑ Locations of all soils, percolation and water monitoring tests not shown.
❑ Proposed system too deep for soils information submitted. _
❑ Well log required.
❑ Omission in narrative.
❑ Insufficient rill over tank or field._
® Other. the upper six inches of the mound absorption bed must consist of top soil and be
sufficiently vegetated to prevent erosion.
Name of reviewer: Julie Makela. P.E.
Date: 12/23/2005
Please supply the necessary information and re -submit your request.