Loading...
HomeMy WebLinkAboutSKYHILLS PH 3 BLK 3 LT 29kyhl'olls Phase 3 Block 3 Lot 29 #011-122-61 C1, Municipality of Anchorage Page 1 of 3 Development Services Department On -She Water and Wastewater Program 4700 South Bragaw Street P.O. Box 196650 Anchorage. AK 99519-6650 www.d.anchorage.ak.us (907) 3437904 ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT Permit Number. SW030128 PID Number. 011.122-61 N.ma: James and Patti DonleyWastewater System: New Aaa.w 8323 Sky Mountain Circle Anchorage, AK 99502 ABSORPTION FIELD F'""" w of sea as n: Deep Trench 243.3078 Four 4 LEGAL DESCRIPTION smr R.i.q: 1.2 Total Dep, ham wvnei praWs: GPOTe 11 FL 6b Lal: SbdrAs«c D.phbpWm h«n&Vp araW: 13nv WPM hpP.: 3 29 Sky Hills Phase 3 3 FL 8 FL To.nev: ROW: Cr LOVIN 3.4 Ft. 32 Ft. Well: Municipal Water System GrwN wNh: 5.8 Nu all 1 Dmrrw Wlwsen "s. fl. FL Cb W"M (Prune, A 9, Cr T" Dept[ Cewa W. oW .owrpan «w W. tww 512 FIS ASTM 3034 PVC D� au Dnnsa su K w«« Levu: ��1i7W ICA) 7/22.23/2003 FL 99C Tnq: Pure set k Cae•w 400AAbove cresta TANK GPM fl. Ft SEPARATION DISTANCES O septic 17 Holding O S.T.E.P. 0 Other. To From Septic Tank Absorption Field Lift Station Holding Tank ubtwprtvate sew Anchorage Tank Y 1250 Well >200' >200' NIA NIA >25' Steel Two (2) sM+ wae, >100' >100' WA WA LIFT STATION — NONE ON LOT t.au» >5' >10' NIA WA cN FOL.dri >5' >10' NIA NIA h hP""a''"'"' WO .« m h None Noted Ekarr+i Yupeanra p.lormW ay CM nl}Y1 R~U: BENCH MARK Front Porch Slab 100.0 FL Engineer's Stamp Inspections performed by: MEA Dates: 10 712212003 °z 49th ^�; � 2ne 712312003 . '� �1 MICNAEL E. ANDERSON Department of Health and Human Services approval P PP . �j No. CE -4381 f .j 1f, %.•y RN 1imwed and approved by Date: 'Mrr r'G • ♦44ePF0 (R `•, ���: Municipality of Anchorage DEVEOPMENT SERVICES DEPARTMENT 4700 South Bragaw Street Anchorage, AK. 99519655 - 343-7904 On -Site Wastewater Disposal System or Well Inspection Report Permit Number. SW030128 ^C sh C 5%8" REE^AR (TYP C%R PLAT) 4C. D Ar 16.1 52 II 9 20.4 C3 V` A f Mt O n> Alter e C4 Site 55.4 G_tr. / I11 TH B I a I 0 0 5%8" REE^AR (TYP C%R PLAT) 4C. D J 6neerv' �O. r F O. \1S Bedroom LOWEST FF - 199' S1 S2 M1 <31 A I B St R 16.1 52 26.8 20.4 C3 30.5 f Mt I \ Alter e C4 Site 55.4 1; TH B I J 6neerv' �O. r F O. \1S Bedroom LOWEST FF - 199' S1 S2 M1 <31 A I B St 20.2 16.1 52 26.8 20.4 C3 30.5 23.5 Mt 43.2 45.2 C4 62.5 55.4 N S700'00" 159.58' PLAN AS -BUILT SCALE 1' = 40' LOT 29, BLOCK 3, SKYHILLS SUBD., PHASE 3 Page 2 of 3 PID No. 011-122-61 Municipality of Anchorage Page 3 of 3 DEVEOPMENT SERVICES DEPARTMENT 4700 South Bragaw Street Anchorage, AK. 99519-6655 - 343-7904 On -Site Wastewater Disposal System or Well Inspection Report Permit Number. SW030128 PID No. 011-122.61 ru Cq S Y PROFILE AS -BUILT - Scale: r - 10' ro W Q n U -U O M f/j M6 i W LIJ� 0) 0) O N \ L= O P° M � Nook Wzc3wWozrow r>az .6 Ui"CZD a Li 5 (/) - F- U O (n Q Q= ZZ S O O u Z U LLJZ S L, � N =aW L�OZQNZ V) FS - Of _>ixOU2ow00 o v }. Z N J of Q m F- J W Y U Q w Q p V I S N CO F- t- U H O p m ~ W W N X W W' m W Z W zwof=)O:::) Z CLF-- w�=mNm o wWWwFO~U=GH w U = U O� M N Z W Z Q O D )-�U W ZO om m Q_ Z F- W Z_ W W O~ Z Q� O O J OU F Q m Z O W oU V) P>d ��Fa- Q Z S of Z w a Z W N J _dr(U cu 7S W L� ? > d' p N d Q Q V \ r) f '- 'U) 0 S V) p z i �F�go Q� o o� z N m¢ v o �y� N W L7 V) W W N �O N O Q L� (O O S O N w^ U Q a o c Q Municipality of Anchorage Development Services Department ue* Building Safety Division *A1 On -Site Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.muni.org/onsite (907)343-7904 ON-SITE SEWER/WELL SUBMITTAL COMMENT SHEET To: Anderson Engineering Legal description: Sky Hills #3. Block 3__Lot 29 The attached paperwork has been reviewed and is being returned for the following reasons: ❑ Original signature or stamp missing on ❑ Calculation error in design. _ ❑ Additional soils information needed. _ ❑ Water monitoring results Inadequate. ❑ Discrepancy in Information submitted. _ ❑ Topographic Information missing or inadequate. ❑ Incomplete; missing ❑ Incomplete; missing _ ❑ Additional adequacy test information needed. ❑ Water sample unacceptable. _ ❑ Measured/proposed distances/dimensions missing. ❑ Locations of all soils, percolation and water monitoring tests not shown. _ ❑ Proposed system too deep for soils information submitted. ❑ Well log required. ❑ Omission In narrative. _ ❑ Insufficient fill over tank or field._ ® Other. On-site wastewater disposal system must be installed by an approved installer. Name of reviewer. Julie Makela. P.E. Date: 2/4/2005 Please supply the necessary information and re -submit your request. LEAVE THIS FORM ATTACHED TO THE PAPERWORK Ga c oc\6Fse s1 <-\ •�c� c r• o c c.ccd�c� kb MUNICIPALITY OF ANCHORAGE Development Services Department On -Site Water d Wastewater Program 4700 South Bragaw Street P.O. Box 196650, Anchorage, AK 99519-6650 (907) 343-7904 ONSITE WASTEWATER DISPOSAL SYSTEM PERMIT Initial Date Issued: May 14, 2003 Expiration Date: May 13, 2004 Permit Number: SW030128 Parcel ID: 011-122-61 Legal Description: 43KY HILLS PHASE 3 SUBDMSION BLOCK 3 LOT 29 Design Engineer. 0014 Anderson Engineering Site Address: 8323 SKY MOUNTAIN CIRCLE Owner Name: JAMES A. & PATTI E. DONLEY Lot Size: 40119 SQ. FT. Owner Address: 8323 SKY MOUNTAIN CIRCLE Total Bedrooms: 4 Permit Bedrooms: 4 ANCHORAGE. AK 99502 - This permit is for the construction of: ❑✓ Disposal Field ❑? Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage All construction must be In accordance with: 1. The attached approved design.. 2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations (18AAC80 ). 3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours). ( Not required for a Water Supply Permit only). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either. A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. 7/2. 2/03 Fiver. Cps-L.E0 i¢N0 6AA1rJ iO MOvE TKC FIEZ-D FROM rHF L.,rxsr S/DF 0Jc H&N SE TO rttE 5"r�T 5r01!, SOjA.f HA✓E PEEN DONE 4N40 X} ivEw OF S 163AV GLM BE S aOn. i n.Cd 7-141.7 R.r rp RN Uay. 9 Received By: Issued By: Date: (� Date: Municipality of Anchorage Development Services Department Building Safety Division On -Site Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (907) 343-7904 ON-SITE SEWER/WELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. 011.122.61 Permit Number SW 030/28 Property owner(s) Jim and Patti Donley Day phone 243.3078 Mailing address (1) 6614 Chevignv Street Anchorage, AK 99502 SITE FAaiBagaddress (2) 5323 SkY NottvrAim CIRCLE Zip Code 995-02 Legal description (Lot, Block & Sub'd.) Lot 29, Block 3, Sky Hills Subdivision, Phase 3 Legal description (Section, Township & Range) Lot Size 40.119 SF Acres/Sq.Ft. THIS APPLICATION IS FOR: Number of Bedrooms Four (4) Sewer Only ® Well Only ❑ Sewer and Well ❑ Water Storage ❑ Sewer Upgrade ❑ THIS PROPERTY CONTAINS: Hot Tub ❑ Jacuzzi ❑ Swimming Pool ❑ Water Softening Unit ❑ Therapy Pool ❑ I certify that the above information is correct. I further certify that this application is being made for a Single Family Dwelling and is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit Fees: Waiver Fees: Date of Payment: 5A /n -T Date of Payment: Receipt Number: Receipt Number. (Rev. 12/00) ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, AK 99524 •7773 522-6779 (F MEMORANDUM DATE: July 23, 2003 TO: Dan Roth FROM: Mike Anderson, P.E. SUBJECT: Lot 29, Block 3, Sky Hills Subdivision, Phase III Revised Septic System Design and Site Plan We have revised the design for the septic system for the subject lot as discussed with you earlier. The existing test hole completed during subdivision development is within 30' of the new trench. Soils encountered were fine sands with silt identical to those found in other test holes on the lot. The percolation rate was verified at less than 5 minutes per inch. The trench sidewall sloughed during construction and the trench varies from 5' to 8' wide with an effective depth of 8' and a length of 32'. Should absorb water until the next ice age. Please let me know if you have further questions. 99-140 PERMIT NO. SW030128 SKYHILLS 'SUBD.1 PHASE 3 LOT 29, BLOCK 3 40,119 S.F. 206' ELEVATIONS BASED ON -1972 NGS DATUM 1TYP) w/ 5/8' REBAR (TYP PER PLAT) 630• Ac �RNf S �t'755je 02 30 , a3, 05. t / Site o e 50' n x 5' ide 150' T I x.4' Effective Depth Abso ti Tren U, N l Zoe• x -0., \13' - / Fb411NC h PROPOO \ Four Bedroom PATrEt2N I n i I TM B Home o N I 1.250 Gc1Io ' o' I Septic Tank oter f (ane en'1Ce / 206' ~� T s � F R' r O)� F TP 28 3B Lowm FF - 199' 1,250 Ga%lon Septic Tank 32' Long x 5' Wide X 8' Effective Depth Absorption Trench N 90'00'O0'E 159.58' 210' SITE PLAN SCALE 1' = 40' 9th N1 E ONOEXS@1: Municipality of Anchorage Department of Health & Human Services 825 L Street, Anchorage, AK 99502-0650 SOILS LOG - PERCOLATION TEST Performed For: Bob Klein Date Performed: 9/28/99 Legal Description: tot 28 Block Z Sky Hille Phase III 11 I OG/PT 7 1 Sand, Silt Some Gravel SP Was Groundwater Encountered? No If Yet, What Depth? Depth to Water After Monitoring None Date: 10/10/99 SP Fine Sand Some S:%! 406 OF 11 r 1 491H •*�o I r .w - OCNAEL L ANDERSON o �1l6n : CE -4381 I Reading Date' Gross Time Net Time Depth To Net Water Drop 1 28 -Sep 15:22 .5" 2 15:32 10 2.5" 2" 3 15:33 ..5" 4 15:43 10 2.5" 2" 5 15:44 .25" 6 15:54 10 2.25" 2" it®�%;��� �: Perc. Rate: 5 MinJlnch Perc. Hole Diameter: 6" Bottom of Test Run Between 6 Ft. and 7 Ft. Hole Comments: Percolation Cavity Presoaked Prior to Testing. Performed By: Fd Sanderson. nderson. I, Mi hs 1 F Anderson Certify That This Test Was Performed In Accordance With All State and Municipal Guidelines In Effect On This Date: 10/25/99 ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, AK 99524 522-7773 522-6779 FAX May 7, 2003 Municipality of Anchorage Development Services Department On -Site Water and Wastewater Program 4700 South Bragaw Street Anchorage, AK 99519-6650 Subject: Lot 29, Block 3, Sky Hills Subdivision No. 3 Septic System Design and Permit Application Impacts to Adjacent Properties Dear Onsite Services Engineer: The owner of Lot 29, Block 3, Sky Hills Subdivision No. 3 intends to construct a new four-bedroom home on the lot. The subdivision is currently served by the Municipal water system. We are therefore requesting a permit be issued for the construction of a new septic system to serve the home. The attached Site Plan and backup documentation identify the location of and configuration of the new septic system and alternate site and the parameters used in the design. Also identified on the plans are the test hole locations and the septic systems on the surrounding lots. Drainage arrows and spot elevations are shown indicating the current drainage patterns. The drainage patterns will be maintained after construction. The test holes placed near the location of the proposed absorption trench and alternate site indicated clean sand with some gravel and varying amounts of silt and percolation rates approximating 2 to 5 minutes per inch. No ground water was found during placement of the test holes and none was noted during the monitoring period. We are therefore proposing to place a 1,250 -gallon septic tank and a 50' long x 5' wide x 4' effective depth absorption trench. The distribution pipe will be placed 5' below the existing surface and the total depth will be 9'. Sufficient fill will be placed over the septic tank and absorption trench to prevent freezing. The ground surface on the lot slopes as shown on the site plan from north to south at varying slopes. The back of the lot slopes steeply to settlement ponds near the old Sand Lake pit. The absorption trench will be constructed at the front of the lot parallel with the slope as much as possible in conformance with Municipal requirements. All Lot 29, Block 3, Sky Hills No. 3 May 7, 2003 Page Two components of the new septic system will be constructed a minimum of 100' from any surface water and 10' from the water service line on the lot. If the system is constructed in accordance with our design the following statements apply: 1. The system, if constructed as designed, will have no adverse impact on the wells in the area or those to be constructed in the future. The subdivision is currently served by the Municipal water system. 2. The system, if constructed as designed, will have no adverse impact on existing septic systems in the area or those to be constructed in the future. 3. The system, if constructed as designed, will have no adverse impact on reserve space, either surface or subsurface, on any lots located in the area. 4. The system, if constructed as designed, will have no adverse impact on drainage patterns in the area. The current drainage pattern will be maintained. Sincerely, �Y EA. -J, Michael E. Anderson, P.E. Attachments 0 WCIi LEI E. ANJERSO4 No CE -4381 j • ; (,` TP 10-7-A 10-3-e LGg1 C3j �'�� 10 W 1 ' G` /qri i _ \\\ 40.182 sq.ftV i Ela_ 1 ' `-- I 33 00�t�N ��-3- 22-3-A22 11 I 1 a 40,525 sq.ft. \ N 45,103 sq.ft.cc �y w>P n n G ip to 27-3-e \\\lA� �� U Ty 1 \ Sid a3 -3-A 1 In 0 1 0 OS C� 10' ORAOIACE ANO ,^,.ASL 1 0 ` 43,6.3Z51sq.ft. 5q2 S9'>> rv� \C.T1�11yo EASEMENT I p 1 ' .41 2 41.166611sq.ft. rte \ C` CS �` ` ` S7;;Tg31. ` ` m �tir� �w / J`- W J208. 4 w T O 10' STOVE a: TP `.I I 1 i by ^� 73-3-C 73_3-9 23-3-A - G / TRNL EASEMENT( I ' 1 �y1 fill O' 1 STOVE =0' ORAINA�EASEMENT G^^' / `20' TRAIL 32 ;0 �' 1 _v 1 MAINTENANCE 1� �SBf $8'47' EASEMENT J Tr o� I EASEMENT ro - E. - 40,418 sq.ft.I O ---05.47'- _ a7-3-Aj11n ro 10' SLOPE:'/- IK 1,1 2EASEMEN70 CE EASEMENT TM TIP 24 G •s,• e I.� 1 7. 3-90 70A 41,347 sq.ft. 0 1 S7 ,a' 1 �� 6'07'52•E 1° 31. 29' ' ��T!' _ G�0 J0. �e al -3-A 40.350 3q.1t. .� 1 J0: Q1 1 A—� , d •M N ` F I ' ' 1 i i / / 8► E •EJ 3 WI i\ 225.11' �� / : • ti^ .���a� 1.• h pT •'• wr 30 PO Q�oi 4''y 1 � C is 26 �1~ t• h-/{T/}1s ••• i /'^d THIS PROJECT ;Q m 41,436 sq.tt. N co C1 I 1 a 26-3-a VACANT � �: lye ^- � cu ;0 1 `" ` c i TRACT A I / ; y 3-r: M m V ;n 107,780 sq.ft. . Mass%%11 1 126-3-A •� C7? G�� SA •, I I ��'A 9144 1 i 5y1 9q?1 oAl� f. 3"E 49th amity, {I : • ••,>���j 1 � + 49th � 1 m 27 N . 1P 159.�i8' : Jd. ��..jJ; •• 1 1 xi�41.892 sq.ft. r, •. os• ilr;7•� x•S �%... 4.I 1 A o o 27-3-• VACANT :` c^. % :•MICHAEL E ANDERSON. C: 1 !3 28 •. f't No. CE -4381 11TIP�• r^ 44,797 sq.ft. 6> ?O •41•'•..,,. ++�•`�•,`Ir.� i 1 !�C O 441 1V"'i�� ; q�.,..,. 00 27-3-9 11 V! CEA EASEMENT (SEE NOTE 10) ---- 10' UTILITY EASEMENT -_- ���` _4_4_°1A- -- - J. 30� 1------ - - -- -- �------174.12'---_ ------- ---'--328.77------- 99-140 SKYHILLS SUBD., PHASE 3 LOT 29, BLOCK 3 40,119 S.F. 206' ELEVATIONS BASED ON 1972 NGS DATUM (TYP) ftZ— 5/8' REBAR (TYP PER PLAT) / C. OR4f S >�755�, 50 Long x 5' P' de 150' x 4' ;Effective Depth T Absorption Trency, Zoe• x I I / I ,Four Bed TH B Home It 1 o,°„ i 1®250 Gallon o I Septic Tonk C! / o er v er ! Line Ice 206' ~— \ 10 2"' T S `F f` ' F FA LOWEST FF - 199' 210' X 199' x 199' �I SITE PLAN SCALE 1' = 40' EXrSTINC #PROPOSED DRA11yACE PATTERN 2 f Qts. 150' 159.58 41a ._.. RT .s! AEL E. ANDER: No. CE -4781 oN 1 , \ u, C. OR4f S >�755�, 50 Long x 5' P' de 150' x 4' ;Effective Depth T Absorption Trency, Zoe• x I I / I ,Four Bed TH B Home It 1 o,°„ i 1®250 Gallon o I Septic Tonk C! / o er v er ! Line Ice 206' ~— \ 10 2"' T S `F f` ' F FA LOWEST FF - 199' 210' X 199' x 199' �I SITE PLAN SCALE 1' = 40' EXrSTINC #PROPOSED DRA11yACE PATTERN 2 f Qts. 150' 159.58 41a ._.. RT .s! AEL E. ANDER: No. CE -4781 LOT 29, BLOCK 3, SKY HILLS SUBDIVISION, PHASE 3 DESIGN FACTORS: SYSTEM REQUIREMENTS: Four Bedroom House 5' Wide Trench System Perc. Rate: 2.5 Min.Anch 1,250 Galton Septic Tank Application Rate: 1.2 GPD/SF 4' Drainfield Rock 4 Bedrooms X 150 GPD/1.2 GPD/SF (Application Rate) = 500 SF Absorption Area 500 SF/5 LF (Width)' .5 (Red. Factor) = p0 LF Trench Length THEREFORE: Construct a 50' Long x 5' Wide x 4' Effective Depth Absorption Trench. Flow Line Elevation in Trench to be 5' Below Original Ground Surface. Total Depth to be 9' Below Existing Ground. Maintain 10' Separation From Water Service Line on Lot Natural Backfill 4'6" Geotextile 6" t 4" Perforated t PVC (Holes Down) 4'0" I I 11>� Drainfield Rock 5' TYPICAL 5' WIDE TR (NO SCALE) ENCH SECTION NOTE: Grade Area Over Trench to Drain Away. Minimum 6' Separation From Bedrock. Minimum 4' Separation From Groundwater. Minimum 10' Separation From Water Service Line. Minimum 100' Separation From Surface Water or Streams. Municipality of Anchorage Department of Health & Human Services 825 L Street, Anchorage, AK 99502-0650 SOILS LOG - PERCOLATION TEST Performed For: Bob Klein Date Performed: Legal Description: I of 99 Block 3 Sky Hillc Phase III SLOPE SITE PLAN 7�00EMW 0 aP Ln dP 7 8 Date Gross Time 0'*: . 4918 1500... 1 Was Groundwater 9 .5" Fine Sand Encountered? No 16 10 If Yet, What Depth? 10 9:56 Some Silt Depth to Water .5" 4 After Monitoring None 11 5.5" 5- Date: 10/10/99 1 9/29/99 5 5% L P E Reading Date Gross Time 0'*: . 4918 1500... 1 4f�k�i .5" Q o : MICHAEL E. ANDERSON o- d 16 10 CE -4301 . . 17 9:56 41, .5" 4 10:06 10 5.5" 5- 5 18 Bottom of 6 Hole 10 9/29/99 5 5% L P E Reading Date Gross Time Net Time Depth To Net Water Drop 1 29 -Sep 9:45 .5" 2 9:55 10 5.5" 5" 3 9:56 .5" 4 10:06 10 5.5" 5- 5 10:07 .25" 6 10:17 10 5.25" 5" Perc. Rate: 2 Min./Inch Perc. Hole Diameter: 6" Test Run Between 6 Ft. and 7 Ft. Comments: Percolation Cavity Presoaked Prior to Testing. Performed By: Fd Sanderson. I, Michael . Anderson, Certify That This Test Was Performed In Accordance With All State and Municipal Guidelines In Effect On This Date: 10/25/99 T Municipality of Anchorage Department of Health & Human Services 825 L Street, Anchorage, AK 99502-0650 SOILS LOG - PERCOLATION TEST Performed For: Bob Klein — Date Performed: 9/29199 Legal Description: I of 29 Block 3- Sky Hills Phase 111 SLOPE SITE PLAN 1 OG/PT 2 3 TESTHOLE No. O 29-3-13 4 5 Fine Sand 71 1 Some Silt 8 Date Gross Time .,•OF At%1a fj Depth To Net Water Drop 1 Was Groundwater 9 .5" Encountered? No 15 10 If Yet, What Depth? 10 F SP Depth to Water 16 4 After Monitoring None 11 2.5" 2" Date: 10/10/99 13 Date Gross Time .,•OF At%1a fj Depth To Net Water Drop 1 1E-•••.....Cq _��'� • I�J•;s�I�e 14No .5" 4911' % •.v 15 10 2.5" 2" 3 F f+ : µIrJra EL t. A\CE0.50N; 16 4 `�'•, CE -4331. 17 2.5" 2" 4441 0 11:37 18 11:47 10 19� I Bottom of Hole 58 ?S$r Reading Date Gross Time Net Time Depth To Net Water Drop 1 29 -Sep 11:15 .5" 2 11:25 10 2.5" 2" 3 11:26 .5" 4 11:36 10 2.5" 2" 5 11:37 .25" 6 11:47 10 2.25" 2" Perc. Rate: 5 MinJlnch Perc. Hole Diameter: 6" Test Run Between 6 Ft. and 7 Ft. Comments: Percolation Cavity Presoaked Prior to Testing. Performed By: Fd Sanderson. I, Mi .ha .I E Anderson Certify That This Test Was Performed In Accordance With All State and Municipal Guidelines In Effect On This Date: 10/25/99 Sheet5 ON-SITE WASTEWATER DISPOSAL SYSTEM CONSTRUCTION AND MATERIAL SPECIFICATIONS SUBJECT: LOT 29, BLOCK 3, SKY HILLS SUBDIVISION PHASE 3 GENERAL: The scope of this project includes the procurement and placement of a new 1,250 -gallon tank at the location shown on the site plan. Work also includes the construction of a new absorption trench 50' long by 5' wide by 4' effective depth also at the location shown on the Site Plan. The total depth of the trench will be 9' below existing ground and the distribution pipe will be placed at 5' below the surface. All components of the new absorption trench and septic tank must be constructed a minimum of 100' from any surface water or 10' from the water service line on the lot. A minimum of 4' of cover is required over the septic tank and 3' over the absorption trench. In lieu of cover 2" of direct bury insulation and 2' of cover may be placed. 2. Construction shall be in accordance with the approved site plan, design drawings, Municipal Permit with any special provisions or conditions, and all applicable State and Municipal Wastewater Disposal Regulations. 3. The Contractor shall be responsible for obtaining all underground utility locates and for the layout of the septic system and verification of the location of all lot lines. 4. Unless specifically agreed otherwise, the contractor shall be responsible for final grading areas subsequently depressed from soil settling. Property owner shall be responsible for revegetation of affected areas unless specifically agreed otherwise. 5. Contractors installing wastewater disposal systems must be certified by the Municipal Department of Health and Human Services for system installations. Owners installing their own systems must receive prior approval from D.H.H.S. before beginning system installation. SEPTIC TANK INSTALLATION A new 1,250 -gallon septic tank must be procured from a certified septic tank manufacturer if the existing tank is found to be defective. 2. A septic tank is to be constructed by a certified septic tank manufacturer. Construction shall include two 4" cleanouts for pumping access. 3. The septic tank shall be sufficiently bedded to prevent settling or shifting of the tank. Lot 29, Block 3, Sky Hills No. 3 May 7, 2003 Page 2 of 3 4. All standpipes on the septic tank shall extend a minimum of 12 inches above final grade. 5. Tanks installed without 4' of cover shall have a minimum of 2" of direct burial insulation. 6. A foundation cleanout shall be installed one to four feet from the building foundation. Two cleanouts are required between the tank and the drainfield. 7. Final grading over the tank shall be such that a positive slope exists away from the septic tank. DRAINFIELD CONSTRUCTION: 1. The drainfield shall be constructed to the dimensions shown on the design. The bottom of the trench shall be within 2" of level. 2. Distribution piping must be placed level with perforations down atop a level bed of drainfield rock. Rock should then be placed over the pipe to provide a minimum of 2" of cover. 3. A silt barrier or geotextile fabric must be placed between the drainfield rock and the natural soil backfill. 4. Monitor tubes must be 4" in diameter and installed at the locations shown on the design. The portion below ground must be perforated. 5. Contractor shall verify the septic tank and drainfield are a minimum 100' away from any private water wells in the area, 150' from a Class "C" Well or 200' from any community well. 6. Direct bury insulation must be placed over the distribution system if less than 3' of backfill depth is available. Finish grade over the trench must be mounded to prevent settlement or depressions. 7. Grade area surrounding the absorption trench to drain away. 8. A minimum 2' of accepting soil is required below the drainfield rock for a 5' wide trench. Contractor shall verify this condition prior to placement of the rock. All pockets of unacceptable materials must be removed and replaced. MATERIAL SPECIFICATIONS: 1. Septic tanks must be constructed by a municipally approved septic tank manufacturer. Lot 29, Block 3, Sky Hills No. 3 May 7, 2003 Page 3 of 3 2. The following pipe materials are approved for use in septic system installations in the Municipality of Anchorage: Cast Iron (perforated and solid), ASTM D3034 or P.V.C. (perforated and solid), ASTM F810 or H.D.P.E. (perforated, but not solid) and ASTM D2662 or A.B.S. (perforated and solid). 3. Insulation shall be at least 2" thick extruded direct burial polystyrene (Dow Chemical Co. Styrofoam HI or equal). 4. Septic tank inlets and outlets shall be fitted with watertight couplings (Caulder, Fernco, or equal). 5. A permeable geotextile fabric (Typar, Mirafi or equal) must be installed between the final drain rock layer and the native soil layer. 6. All drain rock shall be .5" to 2.5" in diameter with less than 3% passing the #200 sieve. INSPECTIONS: Municipal Ordinance requires a minimum of two inspections. These inspections must be conducted under the supervision of a professional engineer registered in the State of Alaska. The first inspection must be conducted after the excavation of trenches, beds or pits and before the installation of any gravel. A septic tank may be set in place, but may not be backfilled. The second inspection must be conducted after the placement of the geotextile fabric, gravel, distribution piping, standpipes, cleanouts and insulation. No backfill should be in place at the time of inspection. Contractor shall provide a copy of all field survey layout and construction notes for use in preparing the certified as -built of the completed system. Municipality of Anchorage Development Services Department R Building Safety Division On -Site Water and Wastewater Program 4700 Bragaw Street s" ' P.O. Box 196650 Anchorage, AK 99519-6650 www.muni.org/onsite (907) 343-7904 CERTIFICATE OF ON-SITE SYSTEMS APPROVAL FOR A SINGLE FAMILY DWELLING Parcel I.D. 011-122-61 COSA # USC 11 I` Expiration Date: I- 3~ V3 1. GENERAL INFORMATION Complete legal description Lot 29, Block 3, Skyhills Location (site address) 8323 Sky Mountain Circle Anchorage, AK 99502 Current Property owner(s) James and Patti Donley Mailing address Lending agency Mailing address Real Estate Agent 8323 Sky Mountain Circle Anchorage, AK 99502 piling,Address r. Unless othetwise requested, COSA will be held by DSD for pickup. r2.. NUMBER OF BEDROOM& Four (4) Day phone Day phone Day phone 3. TYPE O#•WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Individual Well °. ❑ Individual On-site ✓❑ Individual Water Storage ❑ Individual Holding Tank ❑ Community Class Well ❑ Community On-site ❑ Public Water System ❑✓ Public Sewer ❑ The Municipality of Anchorage Development Services Department (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 4 by an independent professional civil engineer registered in the State of Alaska. Certificates of On -Site Systems Approval are required for the transfer of title (except between spouses) for properties served by a single-family on-site wastewater disposal and/or water supply system. DSD also issues COSAs upon request to homeowners. Certificates of On -Site Systems Approval are valid for 90 days from the date of issue for properties served by a private or Class C well and may be reissued with new water sample results. (Certificates may be reissued for a period of up to one year with valid water samples.) Certificates are valid for one year for properties served by Class A or B wells or a public water system. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 4. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm Anderson Engineering Address P.O. Box 240773 Anchorage, AK 99524 Phone 522-7773 Engineer's Printed Name Michael E. Anderson, P.E. Date 12/10/2011 5. DSD SIGNATURE Approved for l bedrooms. Disapproved. Conditional approval for . bedrooms, with the following stipulations: Attachments COSA Checklist X Septic System Advisory Well Flow Advisory Nitrate Advisory Arsenic Advisory Maintenance Agreements Supplemental Engineer's Report Other By: Original Certificate Date: 1-3-12— // 3-12 IRea 11/05) Municipality of Anchorage �• Development Services Department Building Safety Division \ _ On -Site Water & Wastewater Program 4700 Elmore Road P.O. Box 196650 Anchorage, AK 99507 www.muni.org/onsite (907)343-7904 CERTIFICATE OF ON -.SITE SYSTEMS APPROVAL CHECKLIST z9 Legal Description: Lot Block 3, Skyhills Subdivision No. 3 Parcel ID: 011-122-61 A. WELL DATA Well type AMU Date completed Total depth ft. Date of test Static water level If A, B, or C provide PWSID # Sanitary seal (Y/N) _ Cased to ft. FROM WELL LOG ft. Well Log (Y/N) Wires properly protected (Y/N) Casing height (above ground) in. AT INSPECTION ft. Well production g.p.m. g.p.m. WATER SAMPLE RESULTS: -- Coliform colonies/100 mL Nitrate mg/L Arsenic: _ ug/I Date of sample: Collected by: B. SEPTIC/HOLDING TANK DATA Tank Type/Material Septic/Steel Date installed 7/22/2003 Tank size 1,250 gal. Number of Compartments Two Cleanouts (Y/N) Y Foundation cleanout (Y/N) Y Depression over tank (Y/N) N High water alarm (Y/N) N Date of pumping 7/20/2011 Pumper A Plus Home Services C. ABSORPTION FIELD DATA Date installed 7/23/2003 Soil rating (g.p.d./ft2 or ft2/bdrm)1.2 GPwSF System type Deep Trench Length 32 ft. Width 3 ft. Gravel below pipe 8 ft. Total depth 14-15 ft. Eff. absorption area 512 ftz Monitoring tube Y Depression over field N Date of adequacy test 12/9/2011 Results (Pass/Fail) Pass For 4 bedrooms Fluid depth in absorption field before test 6.5 in. Water added 603 gal. New depth 9 in. Elapsed Time: 120 min. Final fluid depth 6.5 in. Absorption rate >= 600 g.p.d. Any rejuvenation treatment (past 12 mo.) (Y/N & type) N If yes, give date D. LIFT STATION Date installed Size in gallons "Pump on" level at _ in. "Pump off' level at _ in. Datum Cycles tested E. SEPARATION DISTANCES SEPARATION DISTANCES FROM WELL ON LOT TO: Manhole/Access (YIN) _ High water alarm level at Meets alarm & circuit requirements? r1l Septic tank/lift station on lot >100' On adjacent lots >100' Absorption field on lot >100' On adjacent lots >100' Public sewer main NIA Public sewer manhole/cleanout N/A Sewer /septic service line >25' Holding tank N/A Animal containment areas >50' Manure/animal excrete storage areas >100' SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Building foundation >5' Property line >5' Absorption field >5' Water main NIA Water service line >10' Surface water >100' Wells on adjacent lots >100' SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Property line >10' Building foundation >1Y Water main >10' Water Service line >10' Surface water >100' Driveway, parking/vehicle storage >25' Curtain drain None Noted Wells on adjacent lots >100' F. COMMENTS: Property is Served by AW WU Water System. G. ENGINEER'S CERTIFICATION l certify that I have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. Engineer's Printed Name Michael E. Anderson, P.E. Date 12/10/2011 COSA Fee $ 640t to Date of Payment \ )-- \ -,)-- ,i \ C4 Receipt Number 0a G\ (Rev. 11105) Waiver Fee $ Date of Payment Receipt Number r �+ 49m AB S ANDSWN . W CE e 4381 .• �2�'� �2 IC • rr,• E��i pPO FE5510�a 99-140 SKYHILLS SUBD., PHASE LOT 29, BLOCK 3 40,119 S.F. 3 FINAL STRUCTURE AS -BUILT AS -BUILT GASTALDI LAND SURVEYING JEFF A. GASTALDI, R.L.S. 4726 WEST 88TH AVENUE ANCHORAGE, ALASKA 99502 PHONE 248-5454 GRID DATE 2222 5/10/2004 F. B. JOB NO. 04-01 SHS3293 I HEREBY CERTIFY THAT I HAVE SURVEYED THE PROPERTY DEPICTED ABOVE AND THAT NO ENCROACHMENTS EXIST EXCEPT AS INDICATED. IT IS THE RESPONSIBILITY OF THE OWNER TO DETERMINE THE EXISTENCE OF ANY EASEMENTS, COVENANTS OR RESTRICTIONS WHICH DO NOT APPEAR ON THE RECORDED SUBDIVISION PLAT. UNDER NO CIRCUMSTANCES SHOULD ANY DATA HEREON BE USED FOR CONSTRUCTION OR FOR ESTABLISHING BOUNDARY OR FENCE LINES. ANCHORAGE RECORDING DISTRICT, ALASKA j NOTE: NO CORNERS SET THIS DATE. 1 "= 40' OF �1 AW 49- YYYVVV .9 ..................: �`• A ............0 •W : erY A. astaldi IP . srP �S-609 • �° �. rafos'jonat Va" .� fill it