ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT
Permit Number. SWO50358 PID Number: 015-172-07'
Name:
Juliann L. Burke
Wastewater System: ❑✓ New ❑ Upgrade
Atltlrass:
11400 Our Road Anchorage, AK 99516
ABSORPTION' FIELD
Pho.: 346-1793 Number a Bedroom:
Q
: 0 peep Trench m Shallow Trench ❑ Betl ❑Mound ❑Other.
LEGAL DESCRIPTION
Sell Haling:
Total Dept tmm anginal grace:
.8 GPD/FP
7 Ft.
Block: 3 Lm: 1 Subdivision:
Greenland
Depth to pipe bosom fmm anginal glade:
Gmvel depth beneath pipe:
3.0
Ft.
4.0 Fl.
Township: Range: Section:
Fill addled above anginal gmde:
Gravel Length:
2-5 Ft.
76 Ft.
Well: ❑.Nead ❑ Upgrade
Gravel width:
e
Numbaaflines: pidance behvaen lines:
5 Ft.
Total absorytion area
2 10 _ F:.
Plpe Material
Classgicanon (Pnvale,A, B, C):
Total Deplh:
Cased b
Existing
Ft.
FL
- 760 FtF
ASTM D3034 PVC
Mile,.
onlled:
Slafic Water Leval:
Installer
�DtJ
pate installed
FL
.%raiul7 a/ (fi
9122-23/05
Yield:Pump
Set at.
Casing Height Above Ground
GPM
Fl.
F1:
TANK
SEPARATION DISTANCES
® Septic ❑ Holding ❑ S.T.E.P.
To
Septic
Absorption
Lift
Holding
ubliclPrvateMauactumc
capaary:
From
Tank
Field
Station
Tank
Sewer Line
.
Anchorage Tank - i; 1'il�.):.
1,250 Gal:
Well
>100'
>100'
N/A
N/A
>25'
Material:
Steel
Numberof Compartments:
Two
Sudme Water
100'
>100'
N/A
N/A
LIFT St ION
Manufacturer
Lot Line
>5'
>10'
N/A
N/A
Gal.
'Pump on' level at
°Ppfdp JgVe ab
Hgh water alarm at
Foundation
>5'
>10'
N/A
N!A'
n.
n.
n.
Curtain Drain
one
Noted
Pump Make&Matlel
Electrical Inspections pertannetl by:
Remarks:
"o ....'
BENPl.WXR
Location antlep)iml:.'t
Garage Slab
Assumed Ele,cation:
1000..00 Ft.
A. Honorer '1`
°`sft, ��I
Inspections performed by: Dates: 1a` 9/22/2Q05 t d
OF
9/22/2005
.•'
2nd
�hP.�.•
���¢
�'�;-g
Development Services Department Approval
d�
Conditional Approval Date:
•••• ••••• •••• •• ...
.............. .. ...........
�•
4Aj�o U
Reviewed and approved by: Date: �a' �' 1
pRo• NA���
(Rev. "06)
It
i
Municipality of Anchorage
DEVEOPMENT SERVICES DEPARTMENT
Page 2 of 3
4700 Elmore
Road Anchorage, AK. 99519-6655 -
343-7904
Permit Number: SWO50358
114th AVENUE
015-172-07
i
S 89'38 27"E 100.00'
N
m o
o
o O
`a�
C
o
Y
3
m
1n
b
C7 ®
THI
b
0
M2
Q
A 9
O i
31 45.9' 49-2'
S2 54.9 58.3'
ce
C4 709' 60.0'
C5 78.2' 80.2'
TH2
M1 73.9' 78.0'
®
O
C6 90.0' 90.7'
i
C7 119.6' 13.5'
C4 1
M2 115.2' 110.0'
SV
SV 58.7' 62.0'
S2
S1
FCO
GREENLAND SUBDIVISION
0 A
LOT 1, BLOCK 3
Four
Bedroom
Home Grovel. Drive
27,000 S.F.
WfLL
••��i
-•�p�P(E,�........
•`•
S 89'11 44
49th. •
A....... ................. ........
7b�lG-�...........
PLAN
AS -BUILT
..........................
NICHREL E. AN8ERS0N•;�j
•% No. cE-a3e1
•�1 ' .�
SCALE V = 40'
^d—,(�.j{''•
Municipality of Anchorage
DEVEOPMENT SERVICES DEPARTMENT
4700 Elmore Road Anchorage, AK. 99519-6655 - 343-7904
On -Site Wastewater Disposal System or Well Inspection Report
Permit Number: SWO50358
Page 3 of 3
PID No. 015-172-07
an.c
N(7
UU
Eu'... FlnlahM
Gmuna Gmune
1,250 Gallon
Septic Tank
91.2 91.05
N
U H U
U
TRENCH 1
TRENCH 2
PROFILE AS -BUILT
No Scale
90.4
89.3
2-
Z•s -
Municipality of Anchorage �AtGINETR y ♦d
Development Services. Department w*
Building
1k, 49—d ,�
_ Building Safety Division to �,/y'�'��l/�
Onsite Water and Wastewater.Program � * '•• * ••••••••••�
4700 South Bragaw St. - x : AMCHAEL L ANDERWIN a4 a,
P.O. Box 196650 Anchorage, AK 99519-6650�r �4i •• CE -4387
www���o
.ci.anchorace.ak.us - +®f�J —� �'+'
• Cs
(907) 343.7904 - �
f •.....r.• 0�
o
Sail's Log Percolation Test
Performed For: .--�r P IsKIE—_ - Date Performed: 41 O
eg ' tion:. ypr 7� W Hldf prownship, Range,' Section:,
Z: Slope - - - Site Plan
y
8@pftr 7
1 LJ
1 p
y/
6- o f Q
9'
s a
10-
11- S!
12- Z $r
13- , l'
14-
COMMENTS
ENC(
IF YES, A'
Depth 1
Mc
PERCOLATION RATE
TEST RUN BETWEEN
Mf ch) PERO HOLE DIAMETER
AND FT
PERFORMED BY: CERTIFY THAT THIS TEST WAS
PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE:
Reading - Date Gross Time
Net Time
Depth to Water
Net Drop
I -5:l-1
/
'Tgz' I
---
(5!Lm . 1
3—r.
I j2, 61
3,Iz-
��
0 1
14
PERCOLATION RATE
TEST RUN BETWEEN
Mf ch) PERO HOLE DIAMETER
AND FT
PERFORMED BY: CERTIFY THAT THIS TEST WAS
PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE:
MUNICIPALITY OF ANCHORAGE
Development Services Department
On -Site Water & Wastewater Program
4700 South Bragaw Street
P.O. Box 196650, Anchorage, AK 99519.6650
(907) 343.7904
-z2- os & /z:;
2,;00
7: ;p
6�: 30
ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT
Upgrade
Date Issued: Sep 20, 2005
Permit Number: SWO50358
Legal Description: GREENLAND BLK 3 LT 1
Design Engineer: 0014 Anderson Engineering
Owner Name: JULIANN L. BURKE
Owner Address: 11400 OUR ROAD
ANCHORAGE. AK 99516-1644
Expiration Date: Sep 20, 2006
Parcel ID: 015-172-07
Site Address: 011500 OUR RD
Lot Size: 27000 SO. FT.
Total Bedrooms: 4 Permit Bedrooms: 4
This permit Is for the construction of:
0 Disposal Field E Septic Tank Holding Tank F] Privy ❑ Private Well F-1 Water Storage
All construction must be In accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations ( 18AAC80 ).
3, The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by catling
(907)343-7904(24 hours). ( Not required for a Water Supply Permit only).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
must be either: A. Open and closed on the same day.
B. Covered, sealed, and heated to prevent freezing.
Received By.
Date:
40-2-/-0 S
Issued By' III Date: a'-
Municipality of Anchorage
Development Services Department
Building Safety Division
On -Site Water and Wastewater Program
4700 South Bragaw St
P.O. Box 196650 Anchorage, AK 99519-6650
www.ci.anchorage.ak.us
(907) 343-7904
wwn
ON-SITE SEWERIWELL PERMIT APPLICATION
FOR A SINGLE FAMILY DWELLING
Parcel I.D. )15-1 P "0 ? _Permit Number SW
Property owner(s) Juliann L. Burke Day phone 346-1793
Mailing address (1)11400 Our Road Anchorage, AK 995164644
Mailing address (2) 11400 Our Road Zip Code
Legal description (Lot, Block & Sub'd.) Lot 1 Block 3 Greenland Subdivision
Legal description (Section, Township & Range)
Lot Size 27,000 SF Acres/Sq.Ft. Number of Bedrooms Four (4)
THIS APPLICATION IS FOR:
11
Sewer Only
171Well
Only
11
Sewer and Well
13Water
Storage
Sewer Upgrade
THIS PROPERTY CONTAINS:
11Hot
Tub
1:1Jacuzzi
❑
Swimming Pool
E]Water
Softening Unit
Therapy Pool
❑
I certify that the above information is correct. I further certify that this application is being made for a
Single Family Dwelling and is in accordance with applicable Municipal Codes.
F
(Signature of property owner or authorized agent)
Permit Fees: f 'i60 = f o /7S '7 R.*J IkNaiver Fees:
Date of Paymentl t�S Date of Payment
Receipt Number. i `f �O Receipt Number.
(Rev. 12/00)
Sep -20. 2005 1:00PM anderson engineering No.0506 P. 1
DATE:
TO:
WITH:
FROM:
MEMO
9/2012005
Joe Goodall
MoAIOnSite Water and Wastewater
Mike Anderson
SUBJECT: Lot 1, Block 3, Greenland Subdivision
Septic System Construction Permit
The culvert .cuff ently crossing Lot 1, Block 3, Greenland Subdivision was installed
several years ago by the City to protect the house on the lot from storm water flows
from the east. The culvert is normally dry and has remained dry over the past several
weeks during periods of heavy rain. It Is not influenced by subsurface water,flow.
The elevation of the distribution line in the proposed absorption trench system will be
lower than the flow line elevation of the culvert. It will be difficult to Impossible for septic
effluent to encroach into the culvert flow line. The absorption trenches will be
constructed as far from the culvert as possible to avoid any possible contamination
problems in the future.
Please let me know If you have further questions.
ANDERSON ENGINEERING
P.O. BOX 240773
ANCHORAGE, AK 99524
September 19, 2005
Municipality of Anchorage
Development Services Department
On -Site Water and Wastewater Program
4700 South Bragaw Street
Anchorage, AK 99519-6650
Subject: Lot 1, Block 3, Greenland Subdivision
Septic System Design and Permit Application
Impacts to Adjacent Properties
Dear Onsite Services Engineer:
The existing absorption system on the subject lot has failed and must be upgraded.
We are therefore requesting a permit be issued for the upgrade of the septic system to
accommodate the four-bedroom home on the lot. The attached Site Plan and backup
documentation identify the location and configuration of the existing septic tank and
proposed septic systems. Also identified on the plans are the locations of the existing
well. No conflicts exist between the proposed septic system and the wells on adjacent
lots. Drainage arrows are shown indicating the current drainage patterns. The
drainage patterns will be maintained after construction.
The test hole placed on the lot at the location of the new absorption trenches indicated
silty gravel and sand (GM/SM). The percolation rate was determined to be 12 minutes
per inch. We are proposing to construct a 1,250 gallon septic tank and 2 — 38' long by
5' wide absorption trenches with 4' of gravel beneath the distribution pipe. The
distribution pipe in the trench will be placed at 3' below the surface with the total depth
at 7'. A Flow Splitter Valve will be placed to assure even flow to each of the new
trenches.
The ground surface on the lot slopes slightly to the northwest at a grade of 5%. The
new trenches will be constructed parallel with the slope as much as possible in
conformance with Municipal requirements. The new septic system will be constructed a
minimum of 100' from the existing well and any surface water in the area.
If the system is constructed in accordance with our design the following statements
apply:
Lot 1, Block 3, Greenland Subdivision
September 19, 2005
Page Two
1. The system, if constructed as designed, will have no adverse impact on the wells
in the area or those to be constructed in the future.
2. The system, if constructed as designed, will have no adverse impact on existing
septic systems in the area or those to be constructed in the future.
3 The system, space, eitherlf constructed as surface or subsurface on any lots located in the arened, will have no adverse a. on reserve
4. The system, if constructed as designed, will have no adverse impact on drainage
patterns in the area. The current drainage pattern will be maintained.
Sincerely,
Michael E. Anderson, P.E.
Attachments
/
114th Avenue
I
100.00
I
\5%
I
� �th
2-38' Long x B Wide a•
4' Effective Depth r
I
x
gbsorptZ Trenches
:�� YN'JMEL E. NIOEAEQ
H1
I
1a ®
1,\51
I
Splitter o
Valve r-
N
5%
as
(�
Iw
1,250 Gallon
L
Septic Tank
I
0
5aI
Foistingg Concrete
Septic Iank
Pump and Fill
Sand
YAM
I
Four
®
edoom
Bedroom
Existing
I
Well
Existing
Well
/
100.00
I
_
I
OF
...••g
113th Avenue
� �th
SITE PLAN
.. .
:�� YN'JMEL E. NIOEAEQ
SCALE 1" = 40'
•••0 Nod CEJ°°
LOT 1, BLOCK 39 GREENLAND SUBDIVISION
DESIGN FACTORS:
Four Bedroom House
Pero. Rate: 12 Min./inch
Application Rate: .8 GPD/SF (Average)
SYSTEM REQUIREMENTS:
5' Wide Trench System
1,250 Galion Septic Tank
4' Drainfield Rock
4 Bedrooms X 150 GPD/.8 GPD/SF (Application Rate) = 750 SF Absorption Area
750 SF/5 SF • .5 (Red. Factor) = 75 LF Trench Length
THEREFORE: Construct 2-38' Long x 5' Wide x 4' Effective Depth Absorption Trenches.
Flow Line Elevation in Trench to be 3' Below Original Ground Surface. Total Depth to be
7' Below Existing Ground. Provide 4' Cover Over Septic Tank and 3' Cover Over Trench.
3' Cover
Over Trench
Natural
Backfill
7611 I 4Fabri xtile
Fabric
6„ O 4" Perforated
PVC (Holes Down)
4'0"
5'
Drainfield Rock
TYPICAL 5r WIDE TRENCH SECTION ....• OF
• ••��.�
(NO SCALE) •.�p(E... .......... ���i
C9 i
a r i q
NOTE: Grade Area Over Trench to Drain Away. 49th
0.3„
Minimum 6' Separation From Bedrock.
Minimum 4' Separation From Groundwater. �: ,,,,,„,....„.............�!`!�
Minimum100' Separation From Wells in the Area. "�E AN0ER5OH t
Minimum 10' Separation From Water Services. i'm`•., No. `E"°' r' ;
Minimum 100' Separation From Surface Water or Streams. �q•.,,�. /9 OC ' 4�.
Depth I r
(Feet) ��+^
1. 1.1�5Fr(
"I-,,I(flM
VArle,
Sr
11-
Municipality of Anchorage
GM
Development Services Department
Building Safety Division
12-
13-
on -she Water and Wastewater Program ,
�itl
. 4700 South Bragaw Sl. .' I
IU'Cg
P.O. Box 196650 Anchorage, AK 9919.6650 I
14.
•^ienchorao ag k.u4
AAMC
(907) 343-7904
Soils Log - Percolation Test
���`�
Date Perrc
t'
Performed For.
17-
Legal Description:
Township, Range, Section:
Monitoring? tip E
Depth I r
(Feet) ��+^
1. 1.1�5Fr(
"I-,,I(flM
VArle,
Sr
11-
%
GM
Net Drop
Iy:zB
12-
13-
�itl
IU'Cg
;o
14.
.
AAMC
15
1- T-
16-
17-
Monitoring? tip E
19-
,
COMMENTS
L AN09"W
.4381 a:
Site Plan
WAS GROUND WATER
'
Depth to Water
Net Drop
Iy:zB
ENCOUNTERED? a
IU'Cg
;o
IF YES, AT WHAT DEPTH? U
•
.yo'
Depth to Wator After ..,�t� 'P
VjK&'
Monitoring? tip E
Data:404)
II*�/4)
Reading , Date
PERCOLATION RATE
TEST RUN BETWEEN
Gross Time
Net Time
Depth to Water
Net Drop
Iy:zB
IU'Cg
;o
L•,
.L,c�aP
.yo'
(mNN.yntJt) PERC HOLE DIAMETER
FT :AND FT
�J,C�.�iCjRTIFY THAT THIS TEST WAS
PERFORMED BY: •�F
PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: �%���/ ^IQ
ON-SITE WASTEWATER DISPOSAL SYSTEM
CONSTRUCTION AND MATERIAL SPECIFICATIONS
SUBJECT: LOT 1, BLOCK 3, GREENLAND SUBDIVISION
GENERAL:
The scope of this project includes the work to pump and backfill with
sand the existing concrete septic tank on the lot. Work will then
include the procurement and placement of a new 1,250 -gallon septic
tank and the construction of 2 new absorption trenches each 38' long
by 5' wide by 4' effective depth also at the location shown on the Site
Plan. The total depth of the trenches will be 7' below existing ground
and the distribution pipe will be placed at 3' below the surface. All
components of the new septic tank and absorption trench must be
constructed a minimum of 100' from any surface water and 100' from
the well on this and adjacent lots. A minimum of 4' of cover is required
over the septic tank and 3' over the absorption trench. In lieu of cover
2" of direct bury insulation and 2' of cover may be placed. A Flow
Splitter Valve must be placed to assure even flow to each of the new
trenches.
2. Construction shall be in accordance with the approved site plan,
design drawings, Municipal Permit with any special provisions or
conditions, and all applicable State and Municipal Wastewater
Disposal Regulations.
3. The Contractor shall be responsible for obtaining all underground utility
locates and for the layout of the septic system and verification of the
location of all lot lines. The Contractor is also responsible to assure
the separation distance from wells and surface water in the area is
maintained. The engineer will accept no responsibility for Contractor
errors.
4. Unless specifically agreed otherwise, the contractor shall be
responsible for final grading areas subsequently depressed from soil
settling. Property owner shall be responsible for revegetation of
affected areas unless specifically agreed otherwise.
5. Contractors installing wastewater disposal systems must be certified
by the Municipal Department of Health and Human Services for
system installations. Owners installing their own systems must receive
prior approval from D.H.H.S. before beginning system installation.
Lot 1, Block 3, Greenland Subdivision
September 19, 2005
Page 2 of 4
SEPTIC TANK INSTALLATION
A new 1,250 -gallon septic tank must be procured from an approved
manufacturer and placed at the location of the existing tanks.
2. A septic tank is to be constructed by a certified septic tank
manufacturer. Construction shall include two 4" cleanouts for pumping
access.
3. The septic tank shall be sufficiently bedded to prevent settling or
shifting of the tank.
4. All standpipes on the septic tank shall extend a minimum of 12 inches
above final grade.
5. Tanks installed without 4' of cover shall have a minimum of 2" of direct
burial insulation.
6. A foundation cleanout shall be installed one to four feet from the
building foundation. Two cleanouts are required between the tank and
the drainfield.
7. Final grading over the tank shall be such that a positive slope exists
away from the septic tank.
DRAINFIELD CONSTRUCTION:
1. The drainfield shall be constructed to the dimensions shown on the
design. The bottom of the trench shall be within 2" of level.
2. Distribution piping must be placed level with perforations down atop a
level bed of drainfield rock. Rock should then be placed over the pipe
to provide a minimum of 2" of cover.
3. A silt barrier or geotextile fabric must be placed between the drainfield
rock and the natural soil backfill.
4. Monitor tubes must be 4" in diameter and installed at the locations
shown on the design. The portion below ground must be perforated.
5. Contractor shall verify the septic tank and drainfield are a minimum
100' away from any private water wells in the area, 150' from a Class
"C" Well or 200' from any community well. The Contractor is solely
responsible to assure these separation distances are met.
Lot 1, Block 3, Greenland Subdivision
September 19, 2005
Page 3 of 4
6. Direct bury insulation must be placed over the distribution system if
less than 3' of backfill depth is available. Finish grade over the trench
must be mounded to prevent settlement or depressions.
7. Grade area surrounding the absorption trench to drain away.
8. A minimum 2' of accepting soil is required below the drainfield rock for
a 5' wide trench. Contractor shall verify this condition prior to
placement of the rock. All pockets of unacceptable materials must be
removed and replaced.
MATERIAL SPECIFICATIONS:
1. Septic tanks must be constructed by a municipally approved septic
tank manufacturer.
2. The following pipe materials are approved for use in septic system
installations in the Municipality of Anchorage:
Cast Iron (perforated and solid), ASTM D3034 or P.V.C. (perforated
and solid), ASTM F810 or H.D.P.E. (perforated, but not solid) and
ASTM D2662 or A.B.S. (perforated and solid).
3. Insulation shall be at least 2" thick extruded direct burial polystyrene
(Dow Chemical Co. Styrofoam HI or equal).
4. Septic tank inlets and outlets shall be fitted with watertight couplings
(Caulder, Femco, or equal).
5. A permeable geotextile fabric (Typar, Mirafi or equal) must be installed
between the final drain rock layer and the native soil layer.
6. All drain rock shall be .5" to 2.5" in diameter with less than 3% passing
the #200 sieve.
INSPECTIONS:
Municipal Ordinance requires a minimum of two inspections must be
completed during the construction of the septic system. These
inspections must be conducted under the supervision of a professional
engineer registered in the State of Alaska. The first inspection must be
conducted after the excavation of trenches, beds or pits and before the
installation of any gravel. A septic tank may be set in place, but may not
be backfilled. The Contractor must notify the engineer 4 hours prior to the
inspection to prevent delays.
Lot 1, Block 3, Greenland Subdivision
September 19, 2005
Page 4 of 4
The second inspection must be conducted after the placement of the
geotextile fabric, gravel, distribution piping, standpipes, cleanouts and
insulation. No backfill should be in place at the time of inspection.
Contractor shall provide a copy of all field survey layout and construction
notes for use in preparing the certified as -built of the completed system.
His measurements must include verification that the proper separation
distances have been met. A certified surveyed as -built may also be
required to assure the proper separation distances are met from wells in
the area. The as -built will also include separation distances from streams
or surface water in the area.