HomeMy WebLinkAboutTHOMAS L BOYLE BLK 1 LT 1AThornas L. Boyle Block Lot 1 A #015-282-31 v®llnres ® � Est, FEB 1 J 2015 Inspection Report_1-1-12. oc Municipality of Anchorage Community Development Department Page 1 of 3 On -Site Water and Wastewater Program 4700 Elmore St. • P.O. Box 196650 Anchorage, AK 99519-6650 • http://wwW.muni.org/onsite • (907) 343-7904 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP141507 �' umber: 015-282-31 ❑ New ❑✓ Upgrade Name: Richard &Jan Schmidt ABSORPTION FIELD ❑✓ Deep Trench ❑ She Trench ❑ Bed ❑ Mound Address 11601 Wagner Street, Anchorage, AK 99516 ❑ Other Phone Number of Bedrooms Soil Rating Total depth from original grade 3 1 GPD/SF 13 Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade 4 Ft. Gravel depth beneath pipe 9Ft. Subdivision Block Lot Thomas L Boyle 1 1A Fill added above original grade 0 Ft. Gravel length 25 Ft. Township Range Section Gravel width 2.5FL Beds: Number of Lines N/A Distance between lines N/A Ft. SEPARATION DISTANCES To From Septic Tank Absorption Field Lift Station Holding Tank Sewer Line Total absorption area - 450 Ftp Number of trenches 1 Dist. between trenches NA Ft. Well 100+ 100+ NIA N/A N/A TANK ❑ Septic ❑ S.T.E.P. ❑ Holding ❑ Other Manufacturer Anchorage Tank Capacity 1 OOOGaI. Surface Water 100+ 100+ NA NIA Material Steel Number of compartments 2 Lot Line 41.8 13.5 NA N/A NA Foundation 90.0 146.1 NA N/A ' LIFT STATION Manufacturer Capacity Gal. Curtain Drain 50+ 50+ NA NIA Remarks Pump on level at in. Pump off level at in. High water alarm at in. -. Pump make and model Electrical Inspections performed by Installer PIPE MATERIAL House to tank 3034 drainfeld Tank to 3034 A+ Home Services Drainfeld 3034 CO/MT 3034 Inspector Pannone Engineering Services BENCH MARK (Assumed elevation) 100ft Inspection �, dates: 1 11/24/14 3`d 11/25/14 2"" 11/25/14 4" 1 Location and description NW corner of structure (garage) COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL Engineers Stamp Conditional Approval: Date ' OF AC, h i ���� • • • :Q�g���t#' ,t. 49 Steve} •Et.' anriorile Approved Date CE 814 Inspection Report_1-1-12. oc C LEGEND W -WATER LINE/ \ WELL RADIUS ' / t SS NEW SEPTIC / GRAVEJ/PIT _ ' NO WELLS'OR SEPTICS i i i % \1 AA c WELL (E� w � "a 3BR HOUSE \ z I LOT 1A 104.6 0P( (F) DRAIN FIELD (E)�` ' IN FAILURE - RE -USE AS RESERVE X � 8 UPGRADED DRAIN FIELD C0 \c \ 25LF x 25W x 9.0'ED x 13.0 22'9 'ED Fc, c\ ui SS \ 0V CO2.\ \ v. y nF--55/ \ \ CO21000g SEPTIC TANK (E)� FC2 c VERIFIED INTEGRITY AND REPLACED NOTES: RECORD DRAWING PLAN c �M2 WITH 10009 SEPTIC TANK. TH-1 CC \ \ � E i I � t 1B, 1 PANNONE ENG SVC, LLC P.O. BOX 100217 ANCHORAGE, AK 99510 r PHONE (907) 272-8218 FAX (907) 272-8211 %c� * 44 THOMAS L. BOYLE, BLOCK 1, LOT 1A RICHARD & JAN SCHMIDT Ste 11601 WAGNER STREET ANCHORAGE, AK 99516 r. •y 4.; Ni 03/06/15 P.I.D. NO 015-282-31 n V Pannone PERMIT NO. CE 8149 OSP141507 r �OFESSION�'�" Sheet 1��"�� 2 OF 3 A B DC01 83.78 74.36 C01 90.11 80.80 CO2 95.60 86.60 DCO2 97.90 89.20 DV 98.40 90.20 CO3 100.90 93.40 FC1 151.10 146.90 M1 150.60 146.10 M2 162.20 155.40 FC2 1162.90 156.30 r. •y 4.; Ni 03/06/15 P.I.D. NO 015-282-31 n V Pannone PERMIT NO. CE 8149 OSP141507 r �OFESSION�'�" Sheet 1��"�� 2 OF 3 SPECIAL PROVISIONS TO SPECIFICATIONS 1 . ALL CONSTRUCTION WAS INSTALLED AS SPECIFIED IN THE MOST CURRENT EDITION OF THE MUNICIPALITY OF ANCHORAGE STANDARD SPECIFICATIONS (MASS) FOR COMPONENT PARTS AND MATERIALS USED IN CONSTRUCTION OF ON-SITE WASTEWATER DISPOSAL SYSTEMS AND ATTACHED SPECIAL PROVISIONS. 2. SCOPE OF WORK: INSTALLED SOIL ABSORPTION SYSTEM. REPLACED SEPTIC TANK. 3. GROUNDWATER WAS ENCOUNTERED AT A DEPTH OF 19 FEET BELOW EXISTING GRADE AS EVIDENCED BY THE SOIL TEST HOLE. NO APPARENT WATER TABLE WAS OBSERVED IN ANY OF THE EXCAVATIONS LESS THAN 19 FEET BELOW EXISTING GRADE. FILTER FABRIC 4" 0 DRAIN PIPE DRAIN ROCK 6" ABOVE PIPE INV TH-1 EL. 79.1 OR/OL -1.5 777 4.0 -4.0 Sw � EL 75.1 9.0 sw ' EL 66.1 6.0 -19.0 �_ I EL. 60.1 w o as > > a ¢ I z �V U U OU O J O O EL. 85.6 o s g o EL. 79.1 i EL. 81.6- 1000g NEW EL. 75.1 EL. 80.8 SEPTIC TANK EL. 80.8 / EL. 75.1 EL 66.1 - EL. 66.1 DESIGN PARAMETERS PRIMARY/RESERVE SEPTIC SYSTEM NO. BEDROOM: 3 (450 gpd) TANK SIZE: 1000g - ABBRI VIATIONS DCO DOUBLE CLEAN OUT PERC RATE: 1 MPI DV DIVERTER VALVE SOIL RATING: 1 GPD/SF CU COPPER FS FLOW SPLITTER AREA ROD: 450 SF DIP DUCTILE IRON PIPE SYS. TYPE: WIDE TRENCH 9.0'ED TH TEST HOLE BFG BELOW FINISH GRADE MIN LENGTH: 25 LF FC FOUNDATION CLEAN OUT OG ORIGINAL GRADE T# TANK CLEAN OUT NO. FG FINISH GRADE USED: - C# CLEAN OUT N0. TS&V TOPSOIL AND VEGETATE NIC NOT IN CONTRACT 25 LFx2.5'Wx9.O' E.D., 13.0' TD - M# MONITOR TUBE NO. TOTAL AREA: 450 SF - R.I. RIGID INSULATION NOTES: ���� \'\ Date RECORD DRAWING PANNONE ENG SVC, LLC OF•A/-.,, 03/06/15 P.O. BOX 100217 ANCHORAGE, AK 99510 S PHONE (907) 272-8218 FAX (907) 272-8211 Scale *: 49 ........ ... .... P.I.D. NO THOMAS L. BOYLE, BLOCK 1, LOT 1A/. 015-282-31 RICHARD & JAN SCHMIDT Steven an'none PERMIT NO. 11601 WAGNER STREET 't♦��i CE 8149 t 49.'�_r osP141507 DESIGN DETAILS ANCHORAGE, AK 99516 Sheet �il��oi�ssio�� 30F3 � \\ ��` On -Site Wastewater Disposal System Permit MUNICIPALITY OF ANCHORAGE Development Services Department On -Site Water & Wastewater Program 4700 Elmore Road, PO Box 196650 Anchorage, AK 99519-6650 Telephone: (907) 343-7904 Permit Number: OSP141507 Tax Code Number: 01528231000 Work Type: Septic Upgrade Permit Effective Dates: November 21, 2014 to November 21, 2015 Design Engineer: PANNONE ENGINEERING SERVICE Subdivision: THOMAS L BOYLE Site Legal Address: THOMAS L BOYLE BLK 1 LT 1A G2734 Owner/Address: SCHMIDT RICHARD A & JAN A 11601 WAGNER STREET ANCHORAGE AK 995162020 Site Mailing Address: 11601 WAGNER ST, Anchorage This permit is for the construction of: Lot Size in Sq Ft: Total Bedrooms: 1/Z. q11 y 1130 ll1-2�/5 �M fi'as 49492 3 Y Disposal Field Y Septic Tank N Holding Tank N Privy N Private Well N Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80). 3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either: A. Open and Close on the same day. B. Covered, sealed, and heated to prevent freezing. Received Issued By RUSH ,�10 MUNICIPALITY OF ANCHORAGE *& Community Development Department Phone: 907-343-7904 Development Services Division Fax: 907-343-7997 On -Site Water & Wastewater Program ON-SITE SEWER/WELL PERMIT APPLICATION Parcel I.D. 015-282-31 Property owner(s) Richard & Jan Schmidt Day phone Mailing address 11601 Wagner Street, Anchorage, AK 99516 Site address 11601 Wagner Street Legal description (Sub'd., Block & Lot) Thomas L Boyle, Block 1, Lot 1A Legal description (Township, Range & Section) Lot Size 49,492 Sq. Ft. Number of Bedrooms 3 APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: (® all that apply) Absorption Field ❑x Initial ❑ Single Family (SF) ❑X Septic Tank ❑X Upgrade ❑x (w/wo ADU) Duplex (D) El Holding Tank ❑ Renewal ❑ Multiple Dwellings ❑ Privy ❑ (SF and/or D) Private Well ❑ Water Storage ❑ THIS APPLICATION INCLUDES A VARIANCE 1 WAIVER REQUEST FOR: Distance: I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes. (Signature of property owner or Permit/Rush Fees: -d 10 1410 Waiver Fees: Date of Payment: Receipt Number: Permit No. Permit App__- :'-.,:c: Date of Payment: Receipt Number: Waiver No. Pannone Engineering Services LLC Steven R. Pannone, Principal Registered Professional Engineer E-mail: steve(@Panen¢ak.com November 18, 2014 Municipality of Anchorage Development Services Department On -Site Water & Wastewater Program 4700 Elmore Rd. P. O. Box 196650 Anchorage, Alaska 99519 Subject: Thomas L Boyle, Block 1, Lot 1A Septic System Permit Request Ladies and Gentlemen: I am writing request a permit to construct an upgrade three (3) bedroom septic system on this property. Currently the lot is developed. The existing drain field is in failure and will be re -used as a reserve. The existing 10008 septic tank will be verified and will be replaced with a new 1000g septic tank if it is found to be leaking. The surrounding lots are served by private wells that are over 100' from this system. Soils. Pannone Engineering Services performed one test hole on this lot in November of 2014, and groundwater was monitored for seven days. Ground water was observed at a depth of 19.0 feet below the ground elevation in the test hole monitor tube. It is my opinion, based on the results of the soils tests and overall soils appearance; an application rate of 1 gallons/day/square feet should be used for a conventional wastewater system. 1. Soil Absorption System Design. a. See Sheet 2 of the design package. 2. Surface Water: There is no surface water within 100 feet of the proposed septic tank and drain field. The proposed drain field upgrade will maintain at least 100 feet from all surface water and drainage ditches. 3. Topography: The existing topography slopes from east to west at approximately 15%. There are no steep slopes in the vicinity of the drain field. Mailing: P.O. Box 100217, Anchorage, AK 99510-0217 Physical: 332 East Manor, Anchorage, AK 99501 Telephone: (907) 272-8218 FAX: (907) 272-8211 Page 2 of 2 4. Drawing Markings: The Drawings are marked "For MoA Review Only". When written notification that the review is complete and that there are no further comments is received from MoA On -Site Department, the note will be removed and "Issued for Construction" drawings will be issued. The proposed installation will not affect the future development of the surrounding or existing lots. There are no surrounding wells within 100 feet of the proposed septic location. We have applied to the ADEC for a separation distance waiver from the class 'A' well. If you have any questions or concerns, please contact me at 272-8218. Sincerely, Steven R. Pannone, P.E. Owner/Civil Engineer Mailing: P.O. Box 100217, Anchorage, AK 99510-0217 Physical: 332 East Manor Ave, Anchorage, AK 99501 Telephone: (907) 272-8218 FAX: (907) 272-8211 \ LEGEND V / W WATER LINE/ i WELL RADIUS GRAVEJLPIT SS NEW SEPTIC � � NO WEIOR SEPTICS Ad 41 1 6A v WELL (E� _ T HOUSE / �. LOT 1'A (E) f < DRAIN FIELD (E) IN FAILURE RE—USE AS RESERVE I qA UPGRADE DRAIN FIELD (P) 23LF x 23''N x 9.0'ED x 13.0'EE ,E 10008 SEPTIC TANK (E) A VERIFY INTEGRITY AND REPLACE "N\ —Z T % ,_� WITH 1000g SEPTIC TANK (P) 1 1 .9 ,// IF FOUND TO BE LEAKING. �i TH-1 1,68 Ew\v 1B r S WELL lF) �7�7�7 7���7 7T 4— NOTES: \ 1 NOTES: Pt11`I1VONE ENG SVC, LLC ���F A ��� - Date FOR CONSTRUCTION �lG P.O. BOX 100217 ANCHORAGE, AK 99510 .. '� . ........ 11/21/14 1 PHONE (907) 272-8218 FAX (907) 272-8211 i��p.�y+� Scale TH ........ .. .. .... P.I.D. NO THOMAS L. BOYLE, BLOCK 1, LOT 1A .. ......... ....: / 015-282-31 RICHARD & JAN SCHMIDT Steven.R. Pannon PERMIT NO. 11601 WAGNER STREET ��,Pcs• GE 8149 �/ OSP141507 PLAN ANCHORAGE, AK 99516 <<1RF�HOSSSIONP� Sheet l1 OF 3 SPECIAL PROVISIONS TO SPECIFICATIONS 1. ALL CONSTRUCTION SHALL BE INSTALLED AS SPECIFIED IN THE MOST CURRENT EDITION OF THE MUNICIPALITY OF ANCHORAGE STANDARD SPECIFICATIONS (MASS) FOR COMPONENT PARTS AND MATERIALS USED IN CONSTRUCTION OF ON—SITE WASTEWATER DISPOSAL SYSTEMS AND ATTACHED SPECIAL PROVISIONS. 2. SCOPE OF WORK: INSTALL SOIL ABSORPTION SYSTEM. VERIFY INTEGRITY OF EXISTING SEPTIC TANK AND REPLACE IF FOUND TO BE LEAKING 3. GROUNDWATER WAS ENCOUNTERED AT A DEPTH OF 19 FEET BELOW EXISTING GRADE AS EVIDENCED BY THE SOIL TEST HOLE. IF AN APPARENT WATER TABLE IS OBSERVED IN ANY OF THE EXCAVATIONS LESS THAN 19 FEET BELOW EXISTING GRADE NOTIFY THE ENGINEER IMMEDIATELY. TH OR/OL - ' snf/ 4.0 -a.D Sw 9.0 sw 6.0 -19.0 z w S � m w Z n nn n 1000g SEPTIC TANK DESIGN PARAMETERS FILTER FABRIC 4" 0 DRAIN PIPE -DRAIN ROCK o" A60VC PIPE INV PRIMARY/RESERVE SEPTIC SYSTEM NO. BEDROOM: 3(450 gpd) TANK SIZE: 1000g ABBREVIATIONS DCO DOUBLE CLEAN OUT PERC RATE:1 MPI CU COPPER DV DIVERTED VALVE SOIL RATING: 1 GPD/SF DIP DUCTILE IRON PIPE FS FLOW SPLITTER AREA ROD: 450 SF TH TEST HOLE BFG BELOW FINISH GRADE SYS. TYPE: WIDE TRENCH 9.0'ED CG ORIGINAL GRADE MIN LENGTH: 25 LF FC FOUNDATION CLEAN OUT T# TS&V TANK CLEAN OUT NO. FG FINISH GRADE USE: CLEAN OUT NO. TOPSOIL AND VEGETATE 25 LFx2.5'Wx9.0' E.D., 13.0' TD m# M# MONITOR TUBE N0. NIC NOT IN CONTRACT TOTAL AREA: 450 SF R.I. _ RIGID INSULATION NOTES: PANNONE ENG SVC, LLC FOR CONSTRUCTION P.O. BOX 100217 ANCHORAGE, AK 99510 PHONE (907) 272-8218 FAX (907) 272-8211 THOMAS L. BOYLE, BLOCK 1, LOT IA RICHARD & JAN SCHMIDT 11601 WAGNER STREET DESIGN DETAILS ANCHORAGE, AK 99516 11/21/14 *:49TH *q' NTS P.I.D. NO • •Steven •F2, •Pannone P••. CE 8149 .•.e - PERMIT NO. OSP141507 Sheet 2 OF 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 BOH DATE PERFORMED: 11/11/2014 TEST HOLE OR/ ORGANICS/ OL ORGANIC SILTS GM/ SILTY GRAVEL SW I WITH SAND SW WELL GRADED SAND SOILS LOG - PERCOLATION TEST SLOPE X TH WAS GROUND WATER ENCOUNTERED? N IF YES, AT WHAT DEPTH? -DRY DEPTH TO WATER AFTER MONITORING? -19.0' DATE: 11/18/2014 LOT -'IA L. \ / I \ -�a T TH-1 — 4.1 SLOPE TH X READING DATE CLOCK NETTIME WATERTIME LEVEL READING NETDROP 1 11/11/14 10:50 --- 4.08 --- 2 10:54:30 4.5 MIN 10.08 6" 3 10:55 --- 4.08 --- 4 11:01 6 MIN 10.08 6" 5 11:01 --- 4.08 --- a 11:07:10 6 MIN 10.08 6" PEROLATION RATE 1 (min/inch) PERC HOLE DIAMETER 6 inches TEST RUN BETWEEN 4 FT AND 5 FT COMMENTS: Test hole excavated by A+ HOME SERVICES. Prec hole was presoaked. Test run for at least one hour. Last 3 readings reported PERFORMED BY: Steven R. Pannone, P.E. I CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDLINES IN EFFECT ON THE DATE OF THIS TEST. NOTES: PANNONE ENG SVC LLC _ �`oF a �>, Date FOR CONSTRUCTION ' �% ..Lq 1)(I 11/21/14 P.O. BOX 102954 ANCHORAGE, AK 99510 S PHONE (907) 272-8218 FAX (907) 272-8211 1iaj�yl) Seale * -'AQ TH *J NTS THOMAS L. BOYLE, BLOCK 1, LOT 1A RICHARD & JAN SCHMIDT 11601 WAGNER STREET SOILS LOG ANCHORAGE, AK 99516 "'S'Z' "' I P-1-0. 015-282-2- 31 Steven R.Pannorie PERMIT NO. I�P CE 8149 OSP 141507 AW 3 OF MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTION ENVIRONMENTAL ENGINEERING DIVISION • 825 L Street - Anchorage, Alaska 99501 Telephone 264.4720 ONSITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT NAME PHOAN,E� �i,NEW IS 349-z526 ❑UPGRADE MAILING ADDRESS CA: SOK 1:74Z LEGAL DESCRIPTION Lor I F� L� LOCATION Etn S NO. OF BEDROOMS vF=F Well DISTANCE TO: / Absorption area / Dwelling i PERMIT NO. 830IEjp O �Y 1-2 W Q N~ Manufacturer r-- Material No. of compt�rtmenis L Liq, ca acit in gallons IF HOMEMADE: Inside length �� Width -Liquid depth d DISTANCE TO: Wall Dwelling PERMIT NO. JV$ z _?� Manufacturer Li uid capacity qin gallons W = DISTANCE TO: Well a / Founda inn IT / Nearest lot line PERMIT NO$,3o O J W = 2 W No. of lines Length of each ling Total length of lipcs Tren h w dih Distance between lines h I inches 0 f Top of tile to finish grade Material beneath tile Total effective absorption area Oii O0, inches 8 W Length Width Depth PERMIT NO. c7 C, f- Type WQ. of crib Crib diem Crib depth Total effective absorption area W DISTANCE T0: Building foundation Nearest lot line J W Class Oe th1 Q V Driller Distance to lot line PERMIT NO. 6iac)3OI a C i DISTANCE TO: Building foundation Sewer line Septic tank 1O r Absorption area(s) / OTHER PIPE MATERIALS SOIL TEST RATING 17-5 szL FT 489fn INSTALLER 10 W — CAf�tS 6 t _ REMARKS s? 83 wS.aL ,(�G•Or•7-I�� 40 �:' Air •.7 G NO e 101GE .• 49 O -..... . . . # •• '•• V DEPT. OF- NVIR0N AZNT RO 2C I N ": EpCE^� a%sC� JUL ' APPROVED,4L/:�••., .••.•••.' �4z/- ��`, DATE LEGAL l.w_ ry• »n.� r RECEIV.ED CUSTOM L=TI ENKINS WELL DRILLING w:...:'ff P.O. BOX 3.142 ECBMUNIgpqL Ty ANCHORAGE. AK 99501 CEPT IO OF gNCHORAGE PHONE 3U-3,91NVIROnsti OF MFA•LitI g NiAL PROTECTION OCT 1 ° t�;T DR I LLER'S WELIREttf ��0� SIZE DEPTH ', CASING DEPTH /� GROUTING DEPTH YIELD STATIC WATER LEVEL AZZ HOW TESTED PUMP INSTALLED .coo TYPE FORMATIONS ENCOUNTERED AND APPROPRIATE DEPTHS / To /P TO .i- .�� To /Zo TO 1e�2 To TO TO TO TO TO TO oO r,MUNICIPALITY OF ANCHORAGE Department : Health and Environmenta rotectionU 825 L Street, Anchorage, AK. 99501 1.- 264-4720 (f Permit # A �n * * * HANDWRITTEN PERMIT WELL AND/GF ON-SITE SEWER PERMIT Applicant: 'T morn '¢ ve-ny Mailing Address: /?o Location: Phone Number: 9'aSZ� Legal Description: L jf♦ t3 ) ,Ile, Lot Size: -- Type of Soil Absorption System Is: Trench: x Drainfield: Seepage Bed: Holding Tank: Maximum Number of Bedrooms: Soil Rating(sq.ft/br) i� S The Required Size of the Soil Absorption System Is: DEPTH LENGTH �. GRAVEL DEPTH �_ WIDTH The length dimension is the length(in feet) of the trench or drainfield. The depth of a trench or pit is the distance between the surface of the ground and the bottom of the excavation(in feet). There is no set width for trenches. The gravel depth is the minimum depth of gravel between the outfall pipe and the bottom of the excavation(in feet). * * REQUIRED SEPTIC(HOLDING) TANK SIZE _ /oo a GALLONS Permit applicant has the responsibility to inform this department during the installation inspections of any wells adjacent to this property and the number of residences that the well will serve. * *.* TWO(2) INSPECTIONS ARE REQUIRED Backfilling of any system without final inspection and approval by this departure: will be subject to prosecution. Minimum distance between a well and any on-site sewage disposal system is 100 fef for a private well or 150 to 200 feet from a public well depending upon the type of public well. Minimum distance from a private well to a private sewer line is 25 feet and to a community sewer line is 75 feet. Well logs are required and must be returned to this department within 30 days of the well completion. Other requirements may apply. Specifications and construction diagrams are available to insure proper installation. * * * PERMIT EXPIRES DECEMBER 31, 1 9 3 3 I certify that: (1) I am familiar with the requirements for on-site sewers and wells as set forth by the Municipality of Anchorage. (2) I will install the system in accordance with codes. (3) I understand at the on-site sewer system may require enlargement if theres'=cei�s'remodeled to include more that 3 bedrooms. Signe3: Issued by: �-} �d(�_ 7 Appli ant Date: 3/ 3nh. SWP/024(1/81) 1/ - l r '. f'r ��,.h ( � l! 7��• 'L- Jiti� � -17 ✓i'�I t �\ ,. i� to V R h o CD X`, vi t co 1320A .. i ;. �It .�. sir � — - • . r�,, : �. �. •' / 1 /' 1 r / G •I I A, t 1 I �� •'� r f s'L ♦ I r': t , I I `• \. �; , , , Irl \� ,..?'. I) �, r, ° - � .>.: :j .. �;•�• (: .. L..qr++ray •' Y r„Y'�' .1 ! �''f :.Yilra��:aY�l/V4 / � � .. ., f '••� ..�'.'r.•'• \• � n•.y�i�iJ.:. 1 i 111 q' e •.1.1:1: MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION 825 L. Street, Anchorage, Alaska 99501 2644720 SOILS LOG — PERCOLATION TEST PERFORMED FOR: 1 I- 1 <( "ER DATE PERFORME LEGAL DESCRIPTION: ,;0J SOILS LOG ❑ PERCOLATION TEST r ..-•. K a 10" r L.L' :.D vt \.I rJ(L•1.[j SLOPE SITE PLAN (<-z) WAS GROUND WATERS ENCOUNTERED} i G L 0 12'Sill_T ��! E IF YES, AT WHAT 13 ' 4L;WL:L 4t„ V\JJ DEPTH? � \ 14 \\\ j-i11'c t:r%x l -t SILT- 15- 16- 17 IL151617 18- 19 20 COMM OF A ILI i a. oxe 4. •'•. No. Iv9u Reading Date 2 IIIIII Depth to Net 3 Time Time Water 4 5 6 b 7 8 9 10 !,. •11 > I ,;0J SOILS LOG ❑ PERCOLATION TEST r ..-•. K a 10" r L.L' :.D vt \.I rJ(L•1.[j SLOPE SITE PLAN (<-z) WAS GROUND WATERS ENCOUNTERED} i G L 0 12'Sill_T ��! E IF YES, AT WHAT 13 ' 4L;WL:L 4t„ V\JJ DEPTH? � \ 14 \\\ j-i11'c t:r%x l -t SILT- 15- 16- 17 IL151617 18- 19 20 COMM OF A ILI i a. oxe 4. •'•. No. Iv9u Reading Date Gross Net Depth to Net Time Time Water Drop b �sPERCOLATION RATE (minutes/inch) TEST RUN BETWEEN FT AND FT PERFORMED BY212 East Intarnational Airport Rd. CERTIFIED BY: �}�nl,, J6,C�ro'� —DATE: 6 -Z– Suite 204 APPLIC``'IT FILLS OUT UPPER HALF-DNLY Time PioDerty Owner �Ytw-� �•SCtt'C_Z -- -".- . - - _ Phone i .. Mailing Address o c zip cod ZJ zG Buyer '-tc ITJtZD 'S-CI1 MIV . Inspector Inspector r, Inspector Address Code - Lending institution IV AT SAL �-� �- � Phone 1lJ rn�(14 Au[ Address c V1ilri� zt-L-i '�ANr-i ••2�1P code\X Lo,r.•, Really Co. 6 Agent ( ) DISAPPROVED Phone Address -- Zip Code 'r` BY: Legal Description 1'"1 Date Sewer Installed Street Location Well Log Received m, Type of Residence Septic Tank Size InglO Family e '�— O Well to Tank 1A ❑ Multiple Family No. of Bedrooms ❑ Other Water Supply o Individual ATTACH WELL LOG. A well lop Is required for all wells drilled since June 1975. Community For wells drilled prior to that date, give well depth (attach log if available). ❑ Public Utility Sewer Disposal Sbindividual Year Individual Installed: (� 3 ❑ Public Ulillty When Connected to Public Utility: �— ❑ Holding Tank NOTE: THE INSPECTION FEE MUST ACCOMPANY EACH REQUEST BEFORE PROCESSING CAN BE INITIATED. Time Time Time Time Date Date Date Date Inspector Inspector Inspector Inspector Field Notes: I•/ -y.0 ( APPROVED BEDROOMS 'CONDITIONS OF APPROVAL ( ) DISAPPROVED ( )OU•t` DATE BY: Soils Rating Date Sewer Installed Well To Absorption Area / Well Log Received m, Septic Tank Size e '�— O Well to Tank 1A rtaa P'aT i September 30, 1903 Thom Fischer SRA Box 1743 Anchorage, AK 99507 Subject: Lot IA, Block 1, Boyle Subdivision ^i A?1UtA MOM In -10-R-3 Approval for the individual sewer and water facilities cannot e granted until the following items have been completed. A well log submitted to this office for our files and review. i ° The depression over the sewer system will need to be filled �� so that surface water drains away from the sewer system. Please notify this Department for a reinspection when the noted discrepancies have been corrected. If there are any further questions, please call this office at 264-4720. Sincerely, Jim Roberts Associate Environmental Specialist JR34/ej/E2 cc: Joanne Tallerico National Bank of Alaska Main Branch C Street Anchorage, AK 995