HomeMy WebLinkAboutRAVENCREST LT 4Ravencrest Lot 4 #015-232-39 Municipality of Anchorage Page 1 of 3 Development Services Department Onsite Water and Wastewater Program 4700 South Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 www.cl.anchorage.ak.us (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT Permit Number. SWO50409 PID Number. 015.232-39 Rrt JMD Construction Wastewater System: New Ar 10200 Hillside Drive Anchorage, AK 99516 ABSORPTION FIELD 244.7994 Four 5' Wide Trench LEGAL DESCRIPTION sw P." lar D.PM ham or,r Paa. .8 GPD/FP 5 Ft. abrL La' $1oM1Yr1' DorbP9a OWrrlhr11ap.W ptla. rr oegae "" Por. 4 Ravencrest 1 Ft. 4 FL 70arrtpRipe: sacoan: FM amen aoow rVW vada. crawl 3-4 Ft. 96 Ft. Well: New Grtr agllt. lMniOer a Ir't. D.wro OSlreen Int. 5 Ft. 1 Ft Clttftti. (Pmeq, A Is, CC Tar Dwft casae to TMal ab poa, area Pe» Mrrut, Private 236 FI. 236 FL 960 Fe ASTM 3034 PVC OoPer Out DnI1eQ stoup wrr Ltr: . 4d. Alpine 11/3/05 210 FL Sanders and Sanders 111412005 YM 9 Pune setr: ct+p Ao Cr . >2 TANK GPM FI. Ft SEPARATION DISTANCES ® Septic ❑ Holding ❑ S.T.E.P. ❑ Other. To SepticAbsorption Uft Holding lutilwiPtivate 7 From Tank Field Station Tank severune Anchorage Tank 1,250 WON >100, >100' NIA NIA >25' Steel Two (2) s.r.w wrr >100' >100' NIA WA LIFT STATION — NONE ON LOT to LOW >5' >10' N/A NIA Gr Fa.r.�r, >5' >10, NIA NIA �a a st. b in In. cM or. None Noted Pury Mw a tbar EMcaul e.P.an+. Prta by Ft r BENCH MARK insulation Over Septic I ank and Absorption I rent . an w Garage Slab. 100.0 FL Engineer's Stamp Inspections performed by: AH Dates: 1r 1114105 49t^ 0 2"a 1114105 ; ......13 V C�-A E E """.�S0°; Department of Ith and man les approval : Reviewed and approved by: a Date: n Z d6Z���1 No. CL-435' i\F } -- E�He m - } ® j R i ._ w._a &� a% k- � | � | i 7 k [ � �& \\0r § n © !k D `;� , �z q §!2t �, E \5' 0 \O q§ (\§\ �03 r"0 . \ \§§\ � \} § . !« , , . � r---------------- � Ssu SSU % .� �� ,�v ���-% .see : _ o - $ : ■`�. :222 __ � \�� � Municipality of Anchorage Page 3 of 3 DEVEOPMENT SERVICES DEPARTMENT 4700 South Bragaw Street Anchorage, AK. 99519.6655 - 343-7904 Onsite Wastewater Disposal System or Well Inspection Report Permit Number. SW050409 PID No. 015-232-39 ru U S H N N E U PROFILE AS -BUILT - Scale: I"- 10 FROM : JMD—CONSTRUCTIONing FAX NO. : 9073463164 Dec. 19 2WS 09:44AM P2 ALPINE DRILLING & ENTERPRISES Permit Number: #SW050409 Date of Issue: 0-31-05 Date Started: 11-1-05 Date Completed: 11-3-05 Legal Description: Ravencrest Lot 4 Property Owner Name & Address: JMD Construction 10200 Hillside Drtve Anchoraee. Alaska Parcel Identification Number: -015-235-39 Is well located at approved permit location? ® Yes ❑ No 99516 Borehole Data: Depth (ft) Method of Drilling ® air rotary ❑ cable tool Soil Type, Thickness & Water Strata From To Casing type: steel stick-up 0 2 Wall Thickness: inches organics & silt 2 3 Diameter: 6 inches ..... Depth: 236 feet sandy silt 3 17 Liner Type: sr7t gravepy silt sandy grave! gravelly silt 17 21 100 142 21 100 142 199 Diameter: inches Depth: feet Casing stickup above ground:,2 feet Static water level (from ground level): 210 feet pumping level.236 feet after 2 hours pumping 9 gpm silty gravel wet 199 209 Recovery Rate:. gpm gravelly silt 209 228 Method of Testing: pLrli Well Intake Opening Type: silty water sand & gravel 228 .236 ® Open End ❑ Open Hole ❑ Screened Start feet Stopped feet ❑ Perforations Start feet Stopped feet Grout Type: bentoniregrunules Volume: jtg Depth: Start Q feet Stopped 2 feet Pump: Intake Depth feet Pump size hp Brand Name Well Disinfected Upon Completion? ® Yes Q N6 Method of Disinfection: chlorine tablets Comments: Weil Driller. Alpine Drilling & Enterprises PO Box 110496 Anchorage AK 99511 Attention: The well driller shall provide a well log to the property owner within 30 days of completion and the property MUNICIPALITY OF ANCHORAGE Development Services Department \� On -Site Water B Wastewater Program 4700 South Bragaw Street \\V V P.O. Box 196650, Anchorage, AK 99519-6650 (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM I WATER SUPPLY PERMIT Initial Permit Number: SWO60409 Legal Description: RAVENCREST LOT 4 Date Issued: Oct 31, 2005 Expiration Date: Oct 31, 2006 Parcel ID: 015-232-39 Design Engineer: 0014 Anderson Engineering Site Address: 5850 RAVEN ROOST CIRCLE Owner Name: JMD CONSTRUCTION Lot Size: 45025 SO. FT. Owner Address: 10200 HILLSIDE DR Total Bedrooms: 5 Permit Bedrooms: 5 ANCHORAGE. A 99516 - This permit is for the construction of. ❑Q Disposal Field ❑✓ Septic Tank ❑ Holding Tank ❑ Privy ❑✓ Private Well ❑ Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations ( 18AAC80 ). 3, The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling (907)343-7904(24 hours). ( Not required for a Water Supply Permit only). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. Received Date: /0 -3/ -0:5 Issued BA Date: o 1 KX Municipality of Anchorage Development Services Department ; Building Safety Division On -Site Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519650 www.cl.anchorage.sk.us (907) 343-7904 ON-SITE SEWER/WELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. a I S - Z 72 - ?3 Permit Number SW Property owner(s) JMD Construction Day phone 244.7994 Mailing address (1)10200 Hillside Drive Anchorage, AK 99516 Mailing address (2) Raven Roost Circle Zip Code Legal description (Lot, Block & Sub'd.) _ Lot 4, Ravencrest Subdivision Legal description (Section, Township & Range) Lot Size 45,205 SF Acres/Sq.Ft. THIS APPLICATION IS FOR: Number of Bedrooms . Five (5 ) Sewer Only ❑ Well Only ❑ Sewer and Well ® Water Storage ❑ Sewer Upgrade ❑ THIS PROPERTY CONTAINS: Hot Tub ❑ Jacuzzi ❑ Swimming Pool ❑ Water Softening Unit ❑ Therapy Pool ❑ certify that the above Information is correct. I further certify that this application Is being made for a Single Family Dwelling and Is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit Fees: /% Waiver Fees: Date of Payment /0 � o & S Date of Payment: Receipt Number. O7 472- �(L Receipt Number. (Rev. 12100) ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, AK 99524 522-7773 677-7766 FAX MEMORANDUM DATE: October 24, 2005 TO: Kathy FROM: Mike Anderson, P.E. SUBJECT: Lot 4, Ravencrest Subdivision Well and Septic System Design and Permit Application The owner of Lot 4, Ravencrest Subdivision has requested the permit for the well and septic system be amended to include a five -bedroom home as opposed to the originally requested permit for a four-bedroom home. The amended sheets for the five -bedroom home are attached. Please substitute these sheets for those previously submitted. Thank you for your assistance and please let me know if you have any questions. ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, AK 99524 522-7773 677-7766 FAX October 20, 2005 Municipality of Anchorage Development Services Department On -Site Water and Wastewater Program 4700 South Bragaw Street Anchorage, AK 99519-6650 Subject: Lot 4, Ravencrest Subdivision Septic System Design and Permit Application Impacts to Adjacent Properties Dear Onsite Services Engineer: The owner of the subject property intends to construct a new five -bedroom home on the lot. We are therefore requesting a permit be issued for the construction of a new well and septic system to serve the new home. No conflicts exist with adjacent septic systems or wells and the proposed septic system and well on this lot. The attached Site Plan and backup documentation identify the location and configuration of the proposed well, septic system and alternate site. The current drainage pattern is identified on the Site Plan. The drainage pattern will be maintained after development of this lot is complete. Test holes were recently placed on the lot, which indicated clean poorly graded to silty sand with some gravel (SM/SP) in the area of the absorption trench and alternate site. The accepting soils were tested and found to have a percolation rate of between 6 and 15 minutes per inch in the accepting soils. Groundwater was encountered at depths ranging between 9.7' and 17'. Our design includes the placement of a new 1,500 - gallon septic tank along with a 94' long by 5' wide by 4' effective depth absorption trench to collect and treat the sewage generated in the house. The bottom of the trench will be 5' below the surface. The distribution pipe will be 1' below the surface. A minimum of 3' of cover will be placed atop the trench and a minimum of 4' of cover will be placed atop the new septic tank. The ground surface on the lot slopes at varying grades toward the northeast near the absorption trench as shown on the Site Plan. The absorption trench will be constructed parallel with the slope of the ground surface as much as possible in conformance with Municipal requirements. The new septic system will be constructed a minimum of 100' Lot 4, Ravencrest October 20, 2005 Page Two from the well on the adjacent lot. It will also be constructed a minimum of 100' from any surface water in the area. If the system is constructed in accordance with our design the following statements apply: The system, if constructed as designed, will have no adverse impact on the wells in the area or those to be constructed in the future. 2. The system, if constructed as designed, will have no adverse impact on existing septic systems in the area or those to be constructed in the future. 3. The system, if constructed as designed, will have no adverse impact on reserve space, either surface or subsurface, on any lots located in the area. 4. The system, if constructed as designed, will have no adverse impact on drainage patterns in the area. The current drainage pattern will be maintained. Sincerely, lvlu� EJ2 , Michael E. Anderson, P.E. Attachments 49:n '�* 4'CHAEL E. ANDERSON LOT 4, RAVENCREST SUBDIVISION DESIGN FACTORS: SYSTEM REQUIREMENTS: Five Bedroom House 5' Wide Trench System Perc. Rate: 6 to 15 Min./Inch 1,500 Gallon Septic Tank Application Rate: .8 GPD/SF 4' Drainfield Rock 5 Bedrooms X 150 GPD/.8 GPD/SF (Application Rate) = 937.5 SF Absorption Area 937.5 SF/5 SF/LF•.5 (Red. Factor) = 93.75 LF Trench Length THEREFORE: Construct an Absorption Trench 94' Long x 5' Wide x 4' Effective Depth. Flow Line Elevation in Trench to be 1' Below Original Ground Surface. Total Depth to be 5' Below Existing Ground. Provide 4' Cover Over Septic Tank and 3' Cover Over Absorption Trench. TYPICAL NOTE: Natural 6„ Backfill A 4'a' 5' Geotextile Fabric 4" Perforated PVC (Holes Down) Drainfield Rock DE TRENCH SECTIO"' (NO Grade Area Over Trench to Drain Away. Minimum 6' Separation From Bedrock. Minimum 4' Separation From Groundwater. Minimum 100' Separation From Wells in the Area. Minimum 100' Separation From Surface Water or Streams: MUNICIPALITY OF ANCHORAGE DEVELOPMENT SERVICES DEPARTMENT 4700 SOUTH BRAGAW STREET ANCHORAGE. AK 99519-6650 SOILS LOG - PERCOLATION TEST LEGAL DESCRIPTION: Lot 4. Ravencrest Subdivision PERFORMED FOR- JMD Construction DATE: 10/7/2005 PROJECT No - PARCEL IDTECHNICIAN: A. Harala DEITTI TEST IIOLE # 1 (rte) 1OG/OL READING GROSS TIME (MINUTES) NET TIME (MINUTES) PTH TO DEPTH WATER aLUI't SITE PLAN 2 TEST HOLE PRESOAKED PRIOR TO TESTING: 1 16:52 11.94" CHARGE :Y...f. 2 17:22 30 14.69" 2.75" 3 3 17:23 11.56" RECHARGE 4 17:53 30 14.88" 3.31" 4 Silty Sand 17:54 11.75" RECHARGE SM 18:24 30 15" See Site Plan FL g Less Silt v) SP/SM 9 ;.:1 _• . 10 11 12 13 14 15 16 17 18 19 COMMENTS: WAS GROUND WATER EN000MTRED`? Yes $ IFYES®WIIATDFI-ni? 9.7' See Site Plan DEITII OF WATER AFTER MONITORING: 9.3' DATE OF MONITORING: 10/15/200 Dark Gray :.® DATE READING GROSS TIME (MINUTES) NET TIME (MINUTES) PTH TO DEPTH WATER NET DROP (INCHES) 10/12 TEST HOLE PRESOAKED PRIOR TO TESTING: 1 16:52 11.94" CHARGE 2 17:22 30 14.69" 2.75" 3 17:23 11.56" RECHARGE 4 17:53 30 14.88" 3.31" 5 17:54 11.75" RECHARGE 6 18:24 30 15" 3.25" PERCOLATION RATE•!_(MIN/INCI I) FERC. I TOLE DIA. 6 (INCI IES) TEST RUN BETWEEN. 4 FT. Rnd_�j_FT. TEST HOLE PRE SOAKED PRIOR TO TEST. TEST PERFORMED BY ANDERSON ENGINEERING SOILS TECHNICIAN. 1, MICI IASL E. ANDERSON CERTIFY TI IAT THIS WAS PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPLE GUIDELINES IN EFFECTON THIS DATE: /V -"'O4- • MUNICIPALITY OF ANCHORAGE ..���������,. DEVELOPMENT SERVICES DEPARTMENT ���� .���P••..,,, 4700 SOUTH BRAGAW STREET ANCHORAGE, AK 99519-6650 . SOILS LOG - PERCOLATION TEST i•.... ....... ...._.._..-........ : t NICIIAEL E ANDERSON j;!3, �j i t 7e 4''��e. NO. EE-4� LEGAL DESCRIPTION: Lot 4, Ravencrest Subdivision i PERFORMED D Construction •••����•...:`'• RF PE 0/7/2005 PROJECT No PARCEL ID, #• TECHNICIAN: A. Harala Profeeelwal En mean Sten pi D17MI TEST I IOLE # 2 Ir«q 18:12 30 12.38" 1 OG/OL SLOPE SITE PLAN 2 3 Q:r.�.. 4".' Silty Sand :,a:_ a:; SM c See Site Plan 5 o .:Q �. Silt Lenses a 6 :;:„ : a� 7 'a fn 8:;Q.;-' Less Silt U)`•;•• SP/SM 9 IO WAS GROUND WATER ENCOUNTERED? Yes "Q'�,•% IFYES©WHATDEFTH? 17' See Site Plan DEFTn OF WATER AFTER MONITORING: 13.7' 12 DATE OF MONITORING: 10/15/2005 ri Dark Gray DEPTH TP DATE READING GROSS TIME NET TIME NET DROP WATER (MINUTES) (MINUTES) (INCHES) (INCHES) t0/12 TEST HOLE PRESOAKED PRIOR TO TESTING: 15 1 " CHARGE 16:40 9.75 �`c e 16 17:10 30 12.25" 2.5" 17—:b:!....` y' y) 3 17:11 9.63" RECHARGE 17:41 30 12.12" 2.49" 18 BOH 5 17:42 9.88" RECHARGE 19 20 PERCOLATION RATE12(MIN/INCII) FERC. I [OLE DIA. 6 (INCIIES) TEST RUN BETWEEN�FT. and-5—FT. COMMENTS: TEST HOLE PRE SOAKED PRIOR TO TEST. TEST PERFORMED BY ANDERSON ENGINEERING SOILS TECHNICIAN. 1, MICI IASL E. ANDERSON CERTIFY TI IAT THIS WAS PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS DATE: / y — T•e ' 0 or' 18:12 30 12.38" 2.5" ON-SITE WASTEWATER DISPOSAL SYSTEM CONSTRUCTION AND MATERIAL SPECIFICATIONS SUBJECT: LOT 4, RAVENCREST SUBDIVISION GENERAL: The scope of this project includes the procurement and placement of a new 1,500 -gallon septic tank at the location shown on the Site Plan. Work also includes the construction of a new 94' long X 5' wide X 4' effective depth absorption trench at the location also shown on the Site Plan. The distribution line in the trench will be placed at V below the existing ground surface. Total depth of the trench will be 5' below the existing ground surface. A separation distance of 100' from any well and 100' between the septic tank and absorption trench and any surface water must also be maintained. In addition, a separation distance of 10' between components of the septic system and any water service line is required. A minimum of 3' of fill is required over the absorption trench and 4' over the septic tank. In lieu of the required fill 2" of insulation and 2' of fill may be placed. 2. Construction shall be in accordance with the approved site plan, design drawings, Municipal Permit with any special provisions or conditions, and all applicable State and Municipal Wastewater Disposal Regulations. 3. The Contractor shall be responsible for obtaining all underground utility locates and for the layout of the septic system and verification of the location of all tot lines. The Contractor must also verify the location of wells in the area and assure that the separation distances are met. 4. Unless specifically agreed otherwise, the contractor shall be responsible for final grading areas subsequently depressed from soil settling. Property owner shall be responsible for revegetation of affected areas unless specifically agreed otherwise. 5. Contractors installing wastewater disposal systems must be certified by the Municipal Department of Health and Human Services for system installations. Owners installing their own systems must receive prior approval from D.H.H.S. before beginning system installation. SEPTIC TANK INSTALLATION 1. A new 1,500 -gallon septic tank must be procured from an approved source and installed at the location shown. 2. A septic tank is to be constructed by a certified septic tank manufacturer. Construction shall include two 4" cleanouts for pumping access. ON-SITE WASTEWATER DISPOSAL SYSTEM CONSTRUCTION AND MATERIAL SPECIFICATIONS SUBJECT: LOT 4, RAVENCREST SUBDIVISION GENERAL: The scope of this project includes the procurement and placement of a new 1,250 -gallon septic tank at the location shown on the Site Plan. Work also includes the construction of a new 75' long X 5' wide X 4' effective depth absorption trench at the location also shown on the Site Plan. The distribution line in the trench will be placed at 1' below the existing ground surface. Total depth of the trench will be 5' below the existing ground surface. A separation distance of 100' from any well and 100' between the septic tank and absorption trench and any surface water must also be maintained. In addition, a separation distance of 10' between components of the septic system and any water service line is required. A minimum of 3' of fill is required over the absorption trench and 4' over the septic tank. In lieu of the required fill 2" of insulation and 2' of fill may be placed. 2. Construction shall be in accordance with the approved site plan, design drawings, Municipal Permit with any special provisions or conditions, and all applicable State and Municipal Wastewater Disposal Regulations. 3. The Contractor shall be responsible for obtaining all underground utility locates and for the layout of the septic system and verification of the location of all lot lines. The Contractor must also verify the location of wells in the area and assure that the separation distances are met. 4. Unless specifically agreed otherwise, the contractor shall be responsible for final grading areas subsequently depressed from soil settling. Property owner shall be responsible for revegetation of affected areas unless specifically agreed otherwise. 5. Contractors installing wastewater disposal systems must be certified by the Municipal Department of Health and Human Services for system installations. Owners installing their own systems must receive prior approval from D.H.H.S. before beginning system installation. SEPTIC TANK INSTALLATION A new 1,250 -gallon septic tank must be procured from an approved source and installed at the location shown. 2. A septic tank is to be constructed by a certified septic tank manufacturer. Construction shall include two 4" cleanouts for pumping access. Lot 4, Ravencrest October 20, 2005 Page 2 of 3 3. The septic tank shall be sufficiently bedded to prevent settling or shifting of the tank. 4. All standpipes on the septic tank shall extend a minimum of 12 inches above final grade. 5. Tanks installed without 4' of cover shall have a minimum of 2" of direct burial insulation. 6. A foundation cleanout shall be installed one to four feet from the building foundation. Two cleanouts are required between the tank and the drainfield. 7. Final grading over the tank shall be such that a positive slope exists away from the septic tank. DRAINFIELD CONSTRUCTION: 1. The drainfield shall be constructed to the dimensions shown on the design. The bottom of the trench shall be within 2" of level. 2. Distribution piping must be placed level with perforations down atop a level bed of drainfield rock. Rock should then be placed over the pipe to provide a minimum of 2" of cover. 3. A silt barrier or geotextile fabric must be placed between the drainfield rock and the natural soil backfill. 4. Monitor tubes must be 4" in diameter and installed at the locations shown on the design. The portion below ground must be perforated. 5. Contractor shall verify the septic tank and drainfield are a minimum 100' away from any private water wells in the area, 150' from a Class "C" Well or 200' from any community well. 6. Direct bury insulation must be placed over the distribution system if less than 3' of backfill depth is available. Finish grade over the trench must be mounded to prevent settlement or depressions. 7. Grade area surrounding the absorption trench to drain away. 8. A minimum 2' of accepting soil is required below the drainfield rock for a 5' wide trench. Contractor shall verify this condition prior to placement of the rock. All pockets of unacceptable materials must be removed and replaced. Lot 4, Ravencrest October 20, 2005 Page 3 of 3 MATERIAL SPECIFICATIONS: 1. Septic tanks must be constructed by a Municipally approved septic tank manufacturer. 2. The following pipe materials are approved for use in septic system installations in the Municipality of Anchorage: Cast Iron (perforated and solid), ASTM D3034 or P.V.C. (perforated and solid), ASTM F810 or H.D.P.E. (perforated, but not solid) and ASTM D2662 or A.B.S. (perforated and solid). 3. Insulation shall be at least 2" thick extruded direct burial polystyrene (Dow Chemical Co. Styrofoam HI or equal). 4. Septic tank inlets and outlets shall be fitted with watertight couplings (Caulder, Fernco, or equal). 5. A permeable geotextile fabric (Typar, Mirafi or equal) must be installed between the final drain rock layer and the native soil layer. 6. All drain rock shall be .5" to 2.5" in diameter with less than 3% passing the #200 sieve. INSPECTIONS: Municipal Ordinance requires a minimum of two inspections. These inspections must be conducted under the supervision of a professional engineer registered in the State of Alaska. The first inspection must be conducted after the excavation of trenches, beds or pits and before the installation of any gravel. A septic tank may be set in place, but may not be backfilled. The second inspection must be conducted after the placement of the geotextile fabric, gravel, distribution piping, standpipes, cleanouts and insulation. No backfill should be in place at the time of inspection. Contractor shall provide a copy of all field survey layout and construction notes for use in preparing the certified as -built of the completed system. \ Municipality of Anchorage -- Development Services Department Building Safety Division On -Site Water and Wastewater Program` 4700 South Bragaw St. SAO ` �' P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (907)343-7904 ON-SITE SEWER/WELL SUBMITTAL COMMENT SHEET To: ANDERSON ENGINEERING Legal description: RAVENCREST LOT 4 The attached paperwork has been reviewed and is being returned for the following reasons: ❑ Original signature or stamp missing on ❑ Calculation error in design. _ ❑ Additional soils information needed. ❑ Water monitoring results inadequate. _ ❑ Discrepancy in information submitted. ❑ Topographic information missing or inadequate. ❑ Incomplete; missing ❑ Incomplete; missing ❑ Additional adequacy test information needed. ❑ Water sample unacceptable. _ ❑ Measured/proposed distances/dimensions missing. _ ❑ Locations of all soils, percolation and water monitoring tests not shown. ❑ Proposed system too deep for soils information submitted. ❑ Well log required. _ ❑ Omission in narrative. _ ❑ Insufficient fill over tank or field._ ® Other. SITE PLAN SHOWS HOUSE 4 BEDROOM AND TANK 1250, NEED TO CORRECT FOR PROPOSED 5 BEDROOM HOME Name of reviewer: JOE GOODALL Date: 10/26/2005 Please supply the necessary information and re -submit your request. LEAVE THIS FORM ATTACHED TO THE PAPERWORK Municipality of Anchorage • -� Development Services Department Building Safety Division On -Site Water and Wastewater Program 4700 Bragaw Street P.O. Box 195650 Anchorage, AK 99519-6650 www.muni.org/onsite (907) 343-7904 CERTIFICATE OF ON-SITE SYSTEMS APPROVAL FOR A SINGLE FAMILY DWELLING Parcel I.D. 015-232-39 1. GENERAL INFORMATION COSA # D D I Expiration Date:_W 106 Complete legal description Lot 4, Ravencrest Subdrvision Location (site address) 5650 Raven Roost Cirde Current Property owner(s) JMD Construction Day phone 5244-7994 Mailing address 10200 Hinside Drive Anchorage, AK 99516 Lending agency Day phone Mailing address Real Estate Agent Day phone Mailing Address Unless otherwise requested, COSA will be held by DSD for pickup. 2. NUMBER OF BEDROOMS: Four (4) 3. TYPE OF WATER SUPPLY: Individual Well Q Individual Water Storage ❑ Community Class Well ❑ Public Water System ❑ TYPE OF WASTEWATER DISPOSAL: Individual On-site 0 Individual Holding Tank ❑ Community On-site ❑ Public Sewer ❑ The Municipality of Anchorage Development Services Department (DSD) issues Certificates of Onsite Systems Approval (COSA) based only upon the representations given in paragraph 4 by an independent professional civil engineer registered In the State of Alaska. Certificates of Onsite Systems Approval are required for the transfer of title (except between spouses) for properties served by a single-family on-site wastewater disposal and/or water supply system. DSD also issues COSAs upon request to homeowners. Certificates of Onsite Systems Approval are valid for 90 days from the date of issue for properties served by a private or Class C well and may be reissued with new water sample results. (Certificates may be reissued for a period of up to one year with valid water samples.) Certificates are valid for one year for properties served by Class A or B wells or a public water system. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 4. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, 1 verify that my investigation, based on procedures outlined in the Certificate of Onsite Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Finn Anderson Engineering Phone 522-7773 Address P.O. Box 240773 Anchorage, AK 99524 Engineer's Printed Name Michael E. Anderson, P.E. Date W5/2006 . . . LIZ 49th 5 5. DSD SIGNATURE ♦ No. cE-43m f,/' Approved for bedrooms. �� -se-o: Disapproved. •�e�'��:; n•'• Conditional approval for bedrooms, with the following stipulations: Attachments: COSA Checklist X Septic System Advisory Well Flow Advisory Nitrate Advisory Arsenic Advisory Maintenance Agreements Supplemental Engineer's Report Other By: /9/V—Original Certificate Date: 2 06 M". 7 VJSm Municipality of Anchorage Development Services Department Building Safety Division OnSlte Water 6 Wastewater Program 47W Bregaw Street P.O. Box 198650 Anchorage, AK 6951958W www.munLorglonsite (907)343-7904 CERTIFICATE OF ON-SITE SYSTEMS APPROVAL CHECKLIST Legal Deacripdon: LaK lIm a untSubdlymm Parcel ID: 015-=-39 A. WELL DATA Well type vrw t It A. B, or C provide PWSID 0 _ Well Log (YM) y Date completed »roues Sanitary seal (YIN) N Wires properly protected (YIN) y Total depth ne fL Cased t0 R R Casing height (above ground) >24 in. FROM WELL LOG AT INSPECTION Date of test 11rm2005 Static water level 210 t< R Well production 9 g.p.m. 9 - p.m -WATER SAMPLE RESULTS: Colporm colonlnMW mL Nitrate mg/L Other bacteria colonies1100 ml- LArsenic: Arsenic._ mgn Date of sample: sr2srzaos Collected by: MEA B. SEPTICIHOLDING TANK DATA Tank TypefMaterial sepic s" Date Wiled I 2005 Tank size 1.m gal. Number of Compartments?wO Cleanout (Y" y Foundation cleanout (YIN) Y Depression over tank (YM) N High water alarm (Y" N Date of pumping New CO w Pumper C. ABSORPTION FIELD DATA Date installed iWAN Sop rapng (g.p.d./R1 or ft=/bdnn):e G_MW System type IF wide Tmnch Length BB fL Wldth !i fL Gravel below pipe 4 R Total depth fL EH absorption area see a Monne ft tube Y Depression over field N Date of adequacy test New Carni. Results (Pass/Fall) For _ bedroorns Fluid depth in absorption field before test in. Water added gal. New depth in. Elapsed Time: min. Final fluid depth in. Absorption rate >= g.p d. Any MJuvenation treatment (past 12 mo.) (YIN &type) If yes, give date D. LIFT STATION Date installed Size in gallons Manhole/Access (YIN) 'Pump on' level at _ in. 'Pump cfr level at _ in. High water alarm level at in. Datum Cycles tested Meets etarm b dmA rewremerds7 E. SEPARATION DISTANCES SEPARATION DISTANCES FROM WELL ON LOT TO: Septic tankllilt station on lot >'W On adjacent kft >1W Absorption field on Ict >i(V On adjacent lots >1W Public sewer main WA Public sewer manhole/cleanout NIA Sewer /septic service Ins >25' Holding tank wA Animal containment areas WA Manure/animal excreta storage areas NIA SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Building foundation >9 Property we >9 Absorption field >5 Water main WA Water service One >10 Surface water >1W Wells on adjacent lots 11,1W SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Ply fine >1a Building foundation >10' Water main wA Water Service One >10' Surface water >1W DMeway. p ridngMahlde afarage >5' Curtain drain Nana Nowd Wells on adjacent lois >1W F. COMMENTS: G. ENGINEER'S CERTIFICATION I certlry that I have determined through fhekf inspections and review of MunkW records that the above systems are in conformance w8h MOA COSA gukfelines in effect an this date. Engineer's Printed Name UdUW E AnderaM P.E. Date 5@5MON COSA Fee $_ Date of Payment Receipt Number, (Rev. 1IMM 31 V4WM Fee S Data of Payment Receipt Number Jun. 2. 1006 11:30AM anderson engineering No. 1814 P. 1 MEMORANDUM DATE: June 2, 2006 TO: Jeff Poet FROM. Mike Anderson, P.E. SUBJECT: Lot 4, Ravencrest Subivision Well Location Revision Certificate of On Site System Approval The well on Lot 4, Ravencrest Subdivision was not placed until after the house on the lot was built. The location of the house limited the access for the well rig. A steep hill Is located on the northwest portion of the lot making the original location Inaccessible with the house in place. The location of the well was moved approximately 50' to the southeast at the discretion of the well driller to allow access for the drilling rig. The placement of the well at the revised location will have no impact on wells and septic systems on the adjacent lots. Please advise if you have further questions. SGS Ret. #: Client Name: Project Name: Client Sample ID: Matrix: PWSID Sample Remarks: 1062623 Anderson Engineering Raven Crest, L4 Raven Crest, L4 Drinking Water SGS Environmental Services Inc 200 W. Potter Drive Anchorage, AK 99518 Tel: (907) 562-2343 Fax: (907) 561-5301 All dates/ imes are Alaska Standard Time Printed DateMme: 05/31/06 16:30 Collected DateTme: 0525/06 12:20 Received DateTme: •05/25/06 12:29 Technical Director. A Stephen Eda' Released Allowable Prep Analysis Parameter Results PDL Units Method Limits Date Date Init Bacteria 10 OB, No Coli 9222B 0525/06 0525/06 of Nitrate 0.97 0.10 mg/kg EPA 300.0 10.00 0525/06 0525MG alr Sun Java System Communications Express - Please View Frame 1 Page 1 of 1 From 'Taylor, Forest (Anchorage)' <Forest.Taylor@sgs.com> Sent Wednesday, May 31, 2006 4:46 pm To Mike Anderson <andengr@gci.net> Subject 1062623 Attachments i2&23 Preliminary PDF Raven Crest, L4 Mike, 22K The arsenic test is paid for and scheduled for analysis on tonight's instrument run. I should have some sort of results for you by early afternoon. I am sorry for any inconvenience this may cause you. Forest Taylor, Project Manager SGS Environmental Services, Alaska 200 W. Potter Drive Anchorage, AK 99518 p: 907-562-2343 ddl: 907-550-3207 f: 907-561-5301 SGS sends analytical reports via the Internet as Portable Document Format (PDF) files. Reports in this format, with authenticated electronic signatures, are considered official reports. No hard copy reports will be sent either by fax or U.S. Postal Service unless otherwise requested. You may distribute your PDF files electronically or as printed hardcopies, as long as they are distributed in their entirety. Information in this email and any attachments is confidential and Intended solely for the use of the individual(s) to whom it is addressed or otherwise directed. Please note that any views or opinions presented In this email are solely those of the author and do not necessarily represent those of the Company. Finally, the recipient should check this email and any attachments for the presence of viruses. The Company accepts no liability for any damage caused by any virus transmitted by this email. All SGS services are rendered in accordance with the applicable SGS conditions of service available on request and accessible at http:/Avww.sgs.corntterms—and—conditions.htm https://mailstore-3.gci.nctfframc.html?Rsecurity=falsc&lang=en&popupLevel=undcfincd&... 6/l/2006 Municipality of Anchorage Development Services Department • '- Building Safety Division Onsite Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.muni.orglonsite (907)343-7904 ON-SITE SEWER/WELL SUBMITTAL COMMENT SHEET To: Mike Anderson Legal description: Ravencrest Lot 4 The attached paperwork has been reviewed and Is being returned for the following reasons: ❑ Original signature or stamp missing on ❑ Calculation error in design. _ ❑ Additional soils information needed. _ ❑ Water monitoring results inadequate. ® Discrepancy in information submitted. Well location moved from permitted site. ❑ Topographic information missing or inadequate. _ ® Incomplete; missing Water samples. ❑ Incomplete; missing ❑ Additional adequacy test information needed. ❑ Water sample unacceptable. _ ❑ Measured/proposed distances/dimensions missing. ❑ Locations of all soils, percolation and water monitoring tests not shown. ❑ Proposed system too deep for soils information submitted. ❑ Well log required. _ ❑ Omission in narrative. _ ❑ Insufficient fill over tank or field._ ❑ Other. _ Name of reviewer: Poet Date: 6-1-06 Please supply the necessary information and re -submit your request. LEAVE THIS FORM ATTACHED TO THE PAPERWORK 00 N I O O N _0 V) �m v / N i -0N W J Ld 'It ry z Q ry ar V,•., os �� .._% jr v r °° AIQ0 4L : • • c rn . 0 i c .16'411M.91,f0A0 N t0'• : L`5;.6N I • I I I � I I I I I I I I I I I I I w �a� •, ' • F'•O~ W0tp2 • I O z V w Wtn p Z} p W N W I iQZQIa]=NQ0Z� ¢ a0 I I N QW 0oc9�Ld Hz to ��3jo�z 0 � I Z I ao 3`rwLO(n Zil ii N I 9 i <pN WUO ZWZN XONO +oa z ¢FW �v U Fr OZ�C<r o w I'b h F-OXNNEn V W Vi2Wp p z ,f 9Z t o b4 U U VI ZO W� W=WOO W U I^ Z woww�p� ��� W z 0wwWisHzZnI 0 > Y'' I pair LiLdm U z ® I Xuj Ckf0 i>CL0m a Oi —n -W — O U`Q OS W N O 3 I J Z p� z I U) to CD O�rnd J I _ �QN o ,� O M ¢ZU w W I�d3�p m o ro (n I N=d r oI I Q N'Ita ai ai I y� .e0'oZ1ea.fl.e0.00 N 0 LO