HomeMy WebLinkAboutVALLI VUE ESTATES #2 BLK 4 LT 32Valli Vue Estates #2 Block 4 Lot 32 #015-341-62 Municipality of Anchorage _ °. Development Services Department C Building Safety Division On -Site Water and Wastewater Program, 4700 Bragaw St. P.O. Box 196650 Anchorage. AK 9951M50 Page 1 of 3 www.ci.anchorage.sk.us (907) 3417904 ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT Permit Number. SW060176 PID Number. 015.341.62 ;*a Wastewater System: ❑ New ® Upgrade Adn..a: It Troe Drive ABSORPTION FIELD Ph" NM a Belo . Mi 4 ® Deep rnrr+l O Stww+Tlarcm O Bed D Mgrq O Omr: ` TOW D.pmkaamarrWale LEGAL DESCRIPTION 6.0 cpoFP 9 Ft. ek%k La SW Mnm' DOM to PM bMW Bmi orgrrl wom C✓wM dWM brewth pW 4 32 Valli VUe 3 Ft. 6.4 Fi 70wrnlnp Rarlpa SecLan Fa adds`abo.e onplW pada G.a.et Lrpm: 2 Ft. 44 Ft. Well: New ❑ Upgrade P9 2.3 New. I 1 Distrrabweew, rw 0 Ft. FL CWa6 w (Ptrvoe. A a. cl' TOW Dom: raved to Total abeorpt o ares Pp Moo" Exist'a AWWU Ft. I Ft 528 Fe 3034 PVC OnIMr Doe Dnlled Swic Wow Le,* YMrNr. Doe wo4Nd Ft A+ Home Services 81212006 Ynld Pwp sr r t.wq tb.yx Mo"e ('Kol.td TANK GPM FL FL SEPARATION DISTANCES ❑ Septic ❑ Holding ® S.T.E.P. ❑ Other. To Septic Absorption Lift Holding lublWPrtvate mwxda. 'r From Tank Field Station Tank sewerune Existlg Gal 200+ 200+ 200+ 200. Mrrw t'il.eb.! a crrortmrlte wee S'Oncewrer 100+ 100+ LIFT STATION LAX LLr 38.9 9.2 �e cal Exist'g . 9.6 9.6 'Pury m' le..i o 'Pw ar r.« at . ,,? Ny, wtr Nrm K FovMoan In to h 75+ 75+ pum M" s Model Ewvral lmpect o prtom*d t>r C~ n.m D rn "a"'rk` BENCH MARK lnrwwn ra DaeaVbon Garage Slab r..w. 100.0 Ft Engineer's Stamp Inspections performed by: PANNONE ENG. SVC, LLC Dates: 1" 81212006 �..�••%N444 8/212006p�.. • . ... • •••.. eeei 2^d Development Services Department Approval �'' . t �A[+♦ Conditional Approval Date: 497H lam, ''�♦♦i :•.... „•„•,•„•••••;7•„„� • ...... •• • i iSlevenR. Pannone: � - 2r - C 7 ♦ '•. ♦ No. CE 6149 ♦♦e« �s'O `J.� Reviewed and approved by:Lff"”,Date: PERMIT NO:SVV06 RECORD DRAWING P.I.D. NO: 015341.62 WASTEWATER DISPOSAL SYSTEM Lot 32, Block 4 Valli Vue S/D 100'CREEK \ SETBACK DEVELOPED = SURVEYED 3 S WAN 200' 0126!<PTICS WAN V) I 10 ETT OPOSED W I I EXISTNOOOgSTEPTANK \ Q) O 1 IIAX20 POD WAOISCHARGE BASIN 1 p N I RIFLED ED INTEGRITY RITY \ \ t g VERIFIED INTEGRITY � �w 3 O A I I SEPTIC ARE/I \ I EXI TG It \ u� 5 w` 4 1591 BR H USE ONNECTED EXIS \\ %Z g I I I NEW 1 1 4" PUMP BASI I DISCHARGE LIN L1 \ �` I10.1 IA 0• , 38.9 \ I IM 2 B t West Tree ��, NOTES: 3) Maintain 10' separation to all 5) Location of house Is based •• OF �� 1) All work shall be performed In lot lines and water lines, unless on a survey as-bultt performed •• � •••••••••••.., 00 accordance with AMC15.65. noted otherwise. by Fred Walatka. C'�Qr'• 1� 6) Water/Sewer crossing shall = .: 0 2) Materials used shall be In 4) Lots served by public water be In accordance with MASS 49 TTM••••••••• • accordance with those specified In systems. No wells within 200' of 50.1.3 6 AW WU DCM Section s � �• •• ••• s ..... j AMC15.65, Wastewater Disposal. proposed system. 31.10. Z • ..••. T PREPARED FOR: PANNONE ENG. SVC, LLC ��1�•-...Steven R. Pannone z Mr. Ward Kruse P. O. BOX 102954 • CE 8 4� 6211 West Tree Drive ANCHORAGE, ALASKA 99510 ���•.•j.•761�/,'°�� Anchorage,AK99518 �y•• 272-8218 -0, 272-8211 Fax ,a�,.:•• 830-5361 DATE: 08-07.06 PLAN SCALE: 1'50' 1 ROUTE NEW FIELD __ ___ vnaoorrr��� AROUND TREE AREA EVEL PED INTAINE 18" RTI CAL NO WE S WAN 200' OR SEPTIC Al CLEARANCE SER WATER 100 FE OF PROPOSED L E. ENTEREJOINTO R WA R LINE. GL ALL JOINT AREA DEVELOPED NO WELLS WAN 200' OR S TICS WAN CO A B 100 FEET OF PROPOSED MI 46.1 23.6 d M2 11.8 22.7 0 lay 30 23 IN ��, NOTES: 3) Maintain 10' separation to all 5) Location of house Is based •• OF �� 1) All work shall be performed In lot lines and water lines, unless on a survey as-bultt performed •• � •••••••••••.., 00 accordance with AMC15.65. noted otherwise. by Fred Walatka. C'�Qr'• 1� 6) Water/Sewer crossing shall = .: 0 2) Materials used shall be In 4) Lots served by public water be In accordance with MASS 49 TTM••••••••• • accordance with those specified In systems. No wells within 200' of 50.1.3 6 AW WU DCM Section s � �• •• ••• s ..... j AMC15.65, Wastewater Disposal. proposed system. 31.10. Z • ..••. T PREPARED FOR: PANNONE ENG. SVC, LLC ��1�•-...Steven R. Pannone z Mr. Ward Kruse P. O. BOX 102954 • CE 8 4� 6211 West Tree Drive ANCHORAGE, ALASKA 99510 ���•.•j.•761�/,'°�� Anchorage,AK99518 �y•• 272-8218 -0, 272-8211 Fax ,a�,.:•• 830-5361 DATE: 08-07.06 PLAN SCALE: 1'50' SlIV130 SIN :31V: 90 -LO -90 :3IV xed 929-ZLZ'd ZZS£-LZZ OLS66 VINSVIV'30V210H0NV 1796ZOL X08'0 •d OII'OAS *VN3 3NONNVd FOUNDATION CLEAN OUT z<-'�" rn m _ CLEANOUT o0 Wm �t -MO OZN < �0 CLEAN oUr N LA k. N l9£9 -o£9 9t966)ry'Q5PJ0L DUV OAN003rIIS3M LlZ9 OVUM PJOM'JW :UOJ 09'dVd3ad LOIOLO P3VIAOb FXST'G DISCHARGE BASIN q. _ c• � y ,•�.. .. T.i-•Ofl � OQ TT 1� O •'.'.r.•. a ('� s�s.•s�ss�rs "Il MOWORTUBE END —1 R AT EACH rn ; In ; Y� a 5 !° 1CL d 3Ea or 0. O 0; Z ,l $ o .•n'r o .":•.1 fie: rn CZ ♦ , S /1 MONITORTME AT —END 8 O/S B0A HIM 4 N30I8 'Z£ 101 W31SAS IVSOdSIO U31VM31SVM S-11VI30 ONIMV�a GU003U 9Lt090MS:ONIMW033d Z9•L4£SLO :ON 'O'1'd Pannone Engineering Services, LLC P.O. Box 102954 Consulting Engineers Anchorage, Alaska, 99510 (907) 272-8218 (907) 272-8211 Fax January7, 2007 Municipality of Anchorage Development Services Department On -Site Water & Wastewater Program 4700 S. Bragaw Street P. O. Box 196650 Anchorage, Alaska 99519 Subject: Lot 32, Block 4 Valli Vue Estates #2 Response to review Comments Ladies and Gentlemen: I am writing in response to comments received January 4, 2007 concerning the record drawing for the above referenced project. The record drawing was originally submitted to your offices on November 16, 2006. I will respond to your comments in the same order as they were presented. Comment: Discrepancy in information submitted. Elevations on Page 3 of Inspection Report Response: Elevations on Page 3 revised. See attached Sheet. Comment: Incomplete; missing brainfield pine Response: Drainfield Pipe clarified on revised sheet. If you have any questions or concerns, please contact me at 227-3522 or 272-8218. Sincerely,4 � �� ...4' . [a 149 `I%%%ILI Steven R. Pannone, P.E. Civil Engineer Attachments: MUNICIPALITY OF ANCHORAGE Development Services Department On -Site Water d Wastewater Program 4700 South Bragaw Street P.O. Box 196650, Anchorage, AK 99519.6650 (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT Upgrade Date Issued: Jun 26, 2006 Expiration Date: Jun 26, 2007 Permit Number: SWO60176 Parcel ID: 015-341-62 Legal Description: VALLI VUE ESTATES #2 BLK 4 LT 32 Design Engineer: 0062 PANNONE ENGINEERING SERVI( Site Address: 006211 WEST TREE DR Owner Name: WARD KRUSE Lot Size: 20614 SO. FT. Owner Address: 6211 WEST TREE DRIVE Total Bedrooms: 4 Permit Bedrooms: 4 ANCHORAGE. AK 99516-6712 This permit is for the construction of: ❑✓ Disposal Field ❑ Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specked in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations ( 18AAC80 ). 3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 ( 24 hours). ( Not required for a Water Supply Permit only). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. Received By: Date: nts t. Issued By �9 � &/ / Wt Date: C G Municipality of Anchorage .� Development Services Department Building Safety Division On -Site Water and Wastewater Program 4700 Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 www.muni.org/onsite (907) 343-7904 ON-SITE SEPTIC/WELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. 01-45--391-0= Property owner(s) t A�� V OLk— c -S Day phone Mailing address L'1,711 ut,C � --r-12�� Zip Code Site address h 2 ( ( LO S-3SI'r— __M Zip Code t_ o -c 3z ,B toc tz y V#A Vila �5T � `.J - Legal description (Sub'd, Block & Lot) Legal description (Township, Section & Range) Lot Size PO to 14 Sq. Ft. THIS APPLICATION IS FOR (®all that apply) Absorption Field Initial Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage ❑ Number of Bedrooms THIS APPLICATION IS AN: Initial �/ re Upgrade Renewal ❑ certify that the above information is correct. I further certify that this application is being made for a Single Famit5�Dwr�(�ng and is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit/Rush Fees: 7'* L/ " - Date of Payment: 5/30 Receipt Number: V 13 (Rev. 11105) Waiver Fees: Date of Payment: Receipt Number: Pannone Engineering Services, LLC P.O. Box 102954 Consulting Engineers Anchorage, Alaska, 99510 on 1 o (907) 272-8211 Fax May 26, 2006 Municipality of Anchorage Development Services Department On -Site Water & Wastewater Program 4700 S. Bragaw Street P. O. Box 196650 Anchorage, Alaska 99519 Subject: Lot 32, Block 4 Valli Vue Estates #2 Septic System Upgrade Permit Request Gentlemen: I am writing to request that a permit to construct an upgraded septic system be issued for this property. The proposed systems will serve an existing four-bedroom house. The lot is served by a community water system and the well is located greater than 200 feet away from the proposed system. 1. Soils. A single test hole was excavated on May 19, 2006. See the attached soils log. Ground water was monitored for seven days through mid-May. A known high ground water period. Ground water was not encountered in the test holes and did not appear in during the monitoring period. Bedrock was not encountered in the test hole. A percolation tests was performed. It is my opinion that the overall soils appearance of the soils, an application rate of 6 gallons/day/square feet should be used using an advanced treatment system. 2. Trench Design. a. Percolation Rate: b. Application Rate: c. Number of Bedrooms: d. Design Flow: e. Min. Absorption Area: f. Total depth: g. Effective Depth: h. Width: i. Reduction Factor: j. Minimum Length: k. Design Length: 1. Effective Absorption Area: m. Septic Tank Size: 1-5 Min Per Inch 6 gpdpsf 4 600 gallons per day 100 sf 9 feet 6.0 feet 2-3 feet 0.0 8.3 feet 44 feet 528 sf 2000 gallon STEP W/AX20 Pod. Page 2 of 2 3. Surface Water: There is no surface water within 100 feet of the proposed system. The proposed systems will maintain at least 100 feet from all surface water and drainage ditches. 4. Topography: The average topography in the area of the proposed septic system is approximately 5 percent. The northern portion of the lot drops off at approximately 15 to 20 percent. The proposed system will be installed along the southern property line. The existing 2,000 STEP tank and discharge basin was installed in 2003. They will be inspected for corrosion and replaced if excessive corrosion is found. The proposed discharge line to the new field will maintain a vertical separation to the water line of over 18 inches. The proposed installation will not affect the future development of the surrounding or existing lots. There are no wells or septic systems within 100 feet of the proposed septic location. If you have any questions or concerns, please contact me at 227-3522 or 272-8218. Sincerely, Steven R. Pannone, P.E. Civil Engineer Attachments: Q\Work\Letters\32-4 Valli Vue.002.doc PERMIT NO:SW06 DESIGN DRAWING P.I.D. NO: 015.341-62 WASTEWATER DISPOSAL SYSTEM Lot 32, Block 4 Valli Vue SID I I I 100' CREEK SET-BACK---� Z SURVEYED N F if w I I EXIST9300og STEP TANK N o IAX20 POD WIDISCHARGE BASIN 0 ur INSTALLED IN 2003 c g VERIFY INTEGRITY u- 0 l I EXISTG 0 Z / 3 u- SEPTIC AREA /[ U, r E LL XISTC t 4BR HOUSI I t 0 S i 11 ZZ West Tree D NEW 1 AREADEVELOPED / 0 WELLS WAN 200' OR SEPTICS WAN \00 FEET OF PROPOSED ONNECT TO EXISTG ,� UMP BASIN/ \ PROPOSED UPGRAD -- --_ t4L x6E EDx2-3'W, 9' TD AREAE PED AINTAIN 18' VE CAL NO WELLS WAN 200' OR SEPTICS WA ROUTE NEW FIELD CLEARANCER WATER 100 FEET. OF PROPOSED AROUND TREE L E, CENTER PIPE JOINT O R� WA R LINE. GLU�ALL JOINTS AREA DEVELOPED NO WELLS WAN 200' OR SEPTICS WAN 4. 100 FEET OF PROPOSED \ c¢S O 0 M 23 N 30 NOTES: 3) Maintain IV separation to all 5) Location o1 house is based 1) All work shall be performed In lot lines and water lines, unless on a survey as -built performed accordance with AMC15.65. noted otherwise. by Fred Walatka. 6) Water/Sewer crossing shall 2) Materials used shah be In 4) Lots served by public water be In accordance with MASS accordance with those specified In systems. No wells within 200' of 50.1.3 3 AW WU DCM Section AMC15.65, Wastewater Disposal. proposed system. 31.10. PREPARED FOR: PANNONE ENG. SVC, LLC Mr. Ward Kruse P. O. BOX 102954 6211 West Tree Drive ANCHORAGE, ALASKA 99510 Anchorage, AK 99516 272-8218 P, 272-8211 Fax 830.5361 DATE: 5.25-06 PLAN PERMIT NO:SW06 DESIGN DRAWING DETAILS P.I.D. NO: 015341.62 WASTEWATER DISPOSAL SYSTEM Lot 32, Block 4 Valli Vue S/D OM3 NOV31V 3WU U011MM •. Ci m Vi v io m t LL W _ @ 0. W 0i.W o Z ,• J w 1 0N3NOV31V I` '�:.; .•. ,,. b 39111NO11NOr1 O —lo T � D� b ^ b s s 0 M MSVB 30WH=0 O N r N � N • NONV3IO N 2 O �<ii �of yao w Im NV3» R cx� W W 0) > ? �`�•�` �....,,• •��. IM.,•� 1NY= 0\P,••••• N011VOM10! TM 1� 49 .�} M.....t... ..................s..... • ••••. •••• • ............•••.`.10 * Steven R. Pannone I PREPARED FOR: Mr. Ward Kruse PANNONE ENG. SVC, LLC P. O. BOX 102954 i' f 6211 West Tree Drive ••� Anchorage, ANCHORAGE, ALASKA 99510 • ••'•• :•� 40II,, 53age,AK99516 227-3522 P, 272-8218 Fax DATE: 5-2IIIIISM ;\��\• DETAILS SCALE: NTS PERMIT NO:SWO5 DESIGN DETAILS P.I.D. NO: 015-34"2 WASTEWATER ABSORPTION SYSTEM Lot 32, Block 4 Valli Vue SID DESIGN CALCULATIONS Number of Bedrooms -4 Total Bedrooms -4 Design flow -150 gal/br/day, Total flow - 600g/day To OR TANK SIZE: 2000 gallon Advantex tank (EXISTG) SOIL ABSORPTION SIZE: Advantex Sewer System AX20 Pod - Class III System Perc Rate= 1-5 mintiinch Application Rate= 6 GPD/SF Size Required= 600 GPD/6 GPD/SF = 100 SF Use Deep Trench, 6' effective 44' Long by 2-3' Wide 44 LF x 6' x 2-3'= 528 SF Total Mr. Ward Kruse 6211 West Tree Drive Anchorage. AK 99516 830.5361 PANNONE ENG. SVC. P. O. BOX 102954 ANCHORAGE, ALASKA 99510 272-8218 PHONE & FAX CALCULATIONS SOILS LOG -PERCOLATION TEST •♦�P� OF ���� a��♦♦ .............. PANNONE ENGINEERING SERVICES AV P.O. BOX 102954 �.�j♦♦ ANCHORAGE, AK 99510 �" """"' """" '' ""0 z (907) 272.8218 ♦ i f♦�•;Ste "n R. Pannone ♦ t�l�'• �y81�49� �� PERFORMED FOR: Ward Kruse DATE PERFORMED: 5-19.06f♦P'o' • o'�-3. ••°•�i r0 _`may LEGAL DESCRIPTION: LOT 32, Block 4 Valli Vue SID ♦��9�,- • ;m;�:.•♦ TEST HOLE 1 SLOPE 51re P 1 OR TOPSOIL 33 15 2 ML Brown Sifts 3 41 2 1596 \ \ 5 1 1 8 1 1 / SM Brown/Grey Sitty 8 SAND 1 / TH1 I g 9 59L�e e Driv 5% 10 11 X TEST 12 HOLE 13 SM SILT Sandy WAS GROUND WATER SLOPE 14 ENCOUNTERED? N 15 IF YES, AT WHAT TH 1 BOH DEPTH? -w 16 DEPTH TO WATER AFTER 17 MONITORING? Dry 18 DATE: 5-006 ap 19 READING DATE GROSS NET DEPTH TO NET TIME TIME WATER DROP 20 5.19.05 13:01 — 31/4' — 13:11 10 9 11C 6 1/41 13:11 — 3 718• — 13:21 10 10 118' 61141 13:21 — 31/2• — 13:31 10 9 3/41 6 114' PEROLATION RATE 1.6 (miMnch) PERC HOLE DIAMETER 6 inches TEST RUN BETWEEN 5.0 FT AND 6.0 FT COMMENTS: Test hole excavated by A+ Home Servbces. Test Hole was presoaked before pert test. PERFORMED BY: Steven R. Pannone, P.E. I CERTIFY THAT THIS TEST WAS PERFORMED 1N ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDLINES IN EFFECT ON THE DATE OF THIS TEST. 31.09.05 Railway Crossings When the sanitary sewer main crosses existing or proposed railways, the sanitary sewer shall be designed in accordance with the criteria set forth in Part 5 of the American Railway Engineering Association manual. A copy of the referenced manual can be obtained from the Engineering Division of the -Alaska Railroad. All railway crossings shall be installed in accordance with the Alaska Railroad permit requirements. 31.10 Sanitary Sewer Mains/Connections in Relation to Water Mains/Connections There shall be a minimumiten=(1Q) J90t !horizontal -W, ighteea'(18).: 0cbes_yertical Lseparation jmeasured from the outside of pipe) etween >.sanitary.sewer ;;and water_, Ctnams/servjces 31.11 Wells All wells located within 200 feet of the project limits shall be clearly and accurately shown on the plans. The State of Alaska Department of Environmental Conservation (ADEC) well classification (A, B, C, Private Water Source), and the minimum separation distance (radii) for sanitary sewer pipe -to -well and sanitary sewer manhole/cleanout-to-well shall be graphically shown for each well. The minimum separation distances shall be in accordance with the State of Alaska Wastewater Disposal Regulations 18 AAC 72.015, Table A and the State of Alaska Drinking Water Regulations 18 AAC 80.030, Table A, or as specified by MOA, Department of Health and Human Services. All wells within 200 feet of the project limits shall be located by a field survey. If the minimum separation distances cannot be maintained, the engineer is required to prepare all necessary waiver requests for submittal to ADEC. AWWU shall review and concur with the waiver request prior to the engineer submitting to ADEC. The engineer will be required to comply with all conditions of approval. -30- 2004 AWWU DESIGN AND CONSTRUCTION PRACTICES MANUAL ASTM D256 Test methods for D -C Resistance of Plastics and ANSI Electrical Insulating Materials Fittings for Water ASTM D2321 Recommended Practice for Underground Installation ANSI of Thermoplastic Sewer Pipe Water and Other Liquids ASTM D3034 Specification for Type of PSM Poly (Vinyl ANSI Chloride) (PVC) Sewer Pipe and Fittings ASTM D3035 Specification for Polyethylene (PE) Plastic Pipe Rubber -Gasket Joints for Ductile -Iron and Gray -Iron (SDR -PR) Based on Controlled Outside Diameter ASTM D3350 Specification for Polyethylene Plastic Pipe and Ductile -Iron Pipe, Centrifugally Cast in Metal Fittings Materials A21.51 AASHTO M45 Sand for Cement Mortar AWWA C104/ Cement -Mortar Lining for Ductile -Iron Pipe and ANSI A21.4 Fittings for Water AWWA C105/ Polyethylene Encasement for Ductile Iron Piping for ANSI A21.5 Water and Other Liquids AWWA C110/ Ductile -Iron and Gray -Iron Fittings, 3 In. Through ANSI A21.10 48 In., for Water and Other Liquids AWWA C111/ Rubber -Gasket Joints for Ductile -Iron and Gray -Iron ANSI A21.11 Pressure Pipe and Fittings AWWA C151/ Ductile -Iron Pipe, Centrifugally Cast in Metal ANSI A21.51 Molds or Sand -Lined Molds, for Water or Other Liquids AWWA C901 Standard for Polyethylene (PE) Pressure Pipe and Tubing, 1/2 In. Through 3 In., for Water Service Article 1.3 Required Clearance from Water Mains During construction of a sewer line, a water main may be encountered and field changes may be necessary to meet the required minimum vertical separation distance of eighteen inches (180) or a horizontal distance of ten feet (10'). In such cases, refer to Division 70, Section 70.16 "Sewer Encasement", and 70.17 "Relocate Water Main.' Article 1.4 Surveys Survey shall be performed by the Contractor as per Division 65, Construction Survey of these Specifications. Page 2 Standard Construction Specs. Division 50 Municipality of Anchorage Development Services Department *A. Building Safety DivisionOn-Site Water and Wastewater Program 1. 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 wvw.muni.org/onsite (907)343-7904 ON-SITE SEWER/WELL SUBMITTAL COMMENT SHEET To: Pannone Engineering Services Legal description: VALLI VUE ESTATES #2 BLK 4 LT 32 The attached paperwork has been reviewed and is being returned for the following reasons: ❑ Original signature or stamp missing on _ ❑ Calculation error in design. _ ❑ Additional soils Information needed. _ ❑ Water monitoring results inadequate. ❑ Discrepancy in Information submitted. ❑ Topographic information missing or inadequate. _ ❑ Incomplete; missing _ ❑ Incomplete; missing _ ❑ Additional adequacy test information needed. ❑ Water sample unacceptable. _ V® Measured/proposed distances/dimensions missing. Note distance to Class A well. ❑ Locations of all soils, percolation and water monitoring tests not shown. ❑ Proposed system too deep for soils information submitted. ❑ Well log required. ❑ Omission in narrative. ❑ Insufficient fill over tank or field._ ® Otherl,i Please give construction details regarding crossed water and sewer pipe. ...A..—k1 tnilel— nve ,ennvaintianal treatment. but—should sav—ads 3 A signed AWWTS maintanance agreement is required before the permit is issued. Still neer/ec? Please supply the necessary information and re -submit your LEAVE THIS FORM ATTACHED TO THE PAPERWORK Municipality of Anchorage I\' Department of Health and Human Services l� Building Safety Division -- On-Site Water and Wastewater Program. 4700 South Bregaw Street P.O. Box 196650 Anchorage, AK 99519.6650 Pagel of 3 www.d.anchorage.ak.us (907) 343.7904 ON-SITE WASTEWATER DISPOSAL SYSTEM ANDIOR WELL INSPECTION REPORT Permit Number: SW SW020172 PID Number: 015-341-62 Wine Wastewater System: ❑ New ® Upgrade Ward CrI17e "ddfm 9516 ABSORPTION FIELD Phone: N~ N Balloane: ® class Trend, t3 shallow Trench O Bed o LAMM o other: Sol Raung: Total Dean bon "mil WOO: LEGAL DESCRIPTION Block: Lel: subdivision: Depth to ape baso "M original grad!: Gravel depth beneath pipe: To.hwp: Range: seam: Fa added above original gig: Gnaw Langin: Gnw Width: - Nurntw d Wines: awns Oeaaeen arra: Well: ❑ New ❑ Upgrade Lrsvaotion (Pi,nr. A B. c): I Total Depth: Ft. coed to: I r, Total absorption Mee: 200 Fe Pipe Material: F810/3034 OVID Driller: Cele Drilled: SWkwalerlaw: IorpM: Date Installed: I I Fl, A+ Home Services 911812003 Yald: PiMp set at: Casing Height Abma Grand: TANK GPM FL Fl. SEPARATION DISTANCES ❑ Septic O Holding ❑ S.T.E.P. ® Other. ADVANTEX To Septic Absorption Lift Holding ubpUPr,vate Ma's" Ch"a" Anchorage Tank cap"Ir. 2000 Gal. From Tank Field Station Tank Sewer Lim Mal"lel NU~ Of corparlmenn: we. NIA NIA NIA NIA Steel 2 103 135 111 LIFT STATION sanl pewale, Sao: Mariondunr Laver 36 10.0 36 250 Gel. Anctank/Orenco 'Plano of level al: 'Pwnp oT level at: vigil welts alarm N: Faaralrn 8 26 44 M 41 In 46 In 100+ 100+ 100+ Piro Make a Model Elecill Impecbons WON-11d by Dural" Drain R'N BEN(% MARK 1 New 2000 al tank is coated to STI-P3 standards. e) I.oulwn and DesMpupri: 2) Existing tank abandoned by pumping dry, opened, Front Porch AssMrra FJevsuon: limed, and filled with soil. 100.0 FL Engineers Stamp F�1 .� \� =",gip . ................ i i♦i . �;•' , Inspections performed by: Pannone Eng. SVC Dates: 1"912712002 : { c 49TH M.....i. .. ...................� 2nd0912712002 Department of Health an Huma erlf;l �7/,�proval ♦ Steven R • Ponnone � ♦� T^� Date: 7 by j)%•*. N^.CE 8ta9 � Reviewed and approved ♦ F Q ... ♦eee�'ESStQ� +� PERMIT NO, SW020172 15 RECORD DRAWING WASTEWATER DISPOSAL SYSTEM LOT 32, BLOCK 4 VALLI VUE S/D I / i I P.I.D. N0i 015-341-62 16 1 100' CREEK(� I SET—BACK S* it ' SURVEYED I 133 G1ii A DIINEDTINSYSTEM PLACE I I � I I I I I I ii I I I I 1 5BR 101 Util Esnt 1 1 I -----------{--1 I West Tree D it v SWING TIES C0 A B C TI 2L7 122 LI 30.0 14.4 L2 27.6 9.0 CS 48.3 3L1 r l,•• i 4981 W/AX20 NEW NOTE, 1) AL IN AC 2) MP 2 3 ACCUI REVISED 030504 1 .i 5. ' E ST'G TEM T AIN HBE PE FFORMED \ AMC1565. 3 O cuel I c iu 3) CONNECT P T TAN L1NL �u MLIJ- POINT OF DRAI FIELD. TYPICAL. 4) MAINTAIN 10' SEPARATION TO ALL LOT LINES. 5) LOT SERVED BY CLASS WATER SERVICE. NO WELLS WITH IN 200' OF PROPOSED SYSTEM. 6) INSTALL ADVANTEX SYSTEM PER MFG E MOA INSTRUCTIONS 6 INSTRUCTIONS. ion R. -PannonaleAw Ware Cruze No. CE 8149 rF�� 6211 West Tree Drive Q$Q,.•P�r� Anchorage, AK 99516 •••..... • itw ,T§\ 346-2203 HM 742-5360 Wk PANNONE ENG. SVC, LLC P. O. BOX 102954 ANCHORAGE, ALASKA 99510 RECORD PERMIT NO, 020172 RECORD DETAILS P.I.D. NOi 015-341-62 WASTEWATER ABSORPTION SYSTEM LOT 32, BLOCK 4 VALLI VUE S/D NOTE) 1) ALLWORK SHALL BE PERFORMED IN ACCORDANCE WITH AMC15.65. 2) MATERIALS USED SHALL BE 1N ACCORDANCE WITH THOSE SPECIFIED IN AMC15.65, WASTEWATER DISPOSAL. 3) CONNECT POST TANK LINE TO MID- POINT OF DRAIN FIELD. TYPICAL. 4) INSTALL DRIVEWAY AT LEAST 5 FT AWAY FROM DRAINFIELD. DO NOT INSTALL DRIVEWAY OVER DRAINFIELD. 5) MAINTAIN 10' SEPARATION TO ALL LOT LINES. ar 'a Y N C 00 0 \ 3.0 5 0' N N ~ O N �C, 1 Drawing G\Work\32-4VallVue.DWG z E] F-4 W V) Cu n R. Pannon t?e jr Wnrc Cruze $165Fr p. 6211 West Tree Drive '' �� Anchorage, AK 99516 346-2203 Hn %_ * 0 742-5360 Wk vis lAl %ntl Im = vlvs lAl N=VW4W v m S. Pannone Eng. Svc., LLC P. O. BOX 102954 ANCHORAGE, ALASKA 99510 RECORD �n unlll � I uH4 '"1'I C•I�wtl \ I f.�el1 ! I-� I at to • • 1 :J PIMMMtlm YM Wad Cram DATE PERPORlMCD: 3-25-03 wllwkALDR81» gmww: lot 8'1. Block 4 Vaffiwe D/D Two= I m ogmlo• I-- 2- 3- 4- 5- 6- 7— sa4667 w�.t a- 9- 10- 11- 12- 13- 14— 9101114la14 Nrown id 16 16 DOH 17 le 19 JO iSteven R. Pannone/ PMWL& l01I RATE 16 fmtnit=W PV= Hold DIAMM 6l2chm TIM ROIL BEWr=f 6 PT' and 7 IT OomoMM Ted bole ezmvabed by A+ Home Setdoe& Ted Hole wasyaeaoalned beftle P= tewt. Permit Number: SW020172 MUNICIPALITY OF ANCHORAGE ':� UO Development Services Department On -Site Water 8 Wastewater Program 4700 South Bragaw Street P.O. Box 196650, Anchorage, AK 99519-6650 (907) 343-7904 ONSITE WASTEWATER DISPOSAL SYSTEM PERMIT Initial Date Issued: Jun 13, 2002 Expiration Date: Jun 13, 2003 Parcel ID: 015-341-62 Legal Description: VALLI VUE ESTATES #2 BLK 4 LT 32 Design Engineer: 0062 Pannone Engineering Services Site Address: 006211 WEST TREE DR Owner Name: Mr. Ward Kruse Lot Size: 20614 SO. FT. Owner Address: 6211 WEST TREE DRIVE Total Bedrooms: 3 Permit Bedrooms: 3 ANCHORAGE, AK 99516-6712 This permit is for the construction of: ❑✓ Disposal Field Q Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72 ) and Drinking Water Regulations ( ISAAC80 ). 3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only ). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. 8//5/0? SFS E,vG /a EC n C rS �K6u0eD OE s iG � rr7 s eAyvoyS M rEV g�is�vz A7rAck6v, Received By: Issued By: -79 %7! Date: 6 L�s EMU- ,.. / Municipality of Anchorage Development Services Department Building Safety Division On -Site Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.enchorage.ak.us (907) 343-7904 ON-SITE SEWER/WELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. 0-1-341-62 Permit Number SW OZ O / 72 Property owners) Mr. Ward =e_Day phone 742.5360 Mailing address (1) 6211 West Tree Drive Mailing address (2) Anchorage AK _Zip Code 99516 Legal description (Lot, Block & Sub'd.) Lot 32 Block 4 Valli Vue Est X02 Legal description (Section, Township & Range) Lot Size I /ol`I/Acres/ F X3 2A Number of Bedrooms 3 THIS APPLICATION IS FOR: Sewer Only ❑ Well Only ❑ Sewer and Well ❑ Water Storage ❑ Sewer Upgrade THIS PROPERTY CONTAINS: Hot Tub ❑ Jacuzzi ❑ Swimming Pool ❑ Water Softening Unit ❑ Therapy Pool ❑ I certify that the above information is correct. I further certify that this application is being made for a Single Family Dwelling and is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit Fees: 1400 CU Waiver Fees: Date of Payment: (P I 01 OZ Date of Payment: Receipt Number. �00� Receipt Number: (Rev. 1]100) Pannone Engineering Svc, LLC Consulting Engineers August 15, 2002 Municipality of Anchorage Development Services Department On -Site Water & Wastewater Program 4700 S. Bragaw Street P. O. Box 196650 Anchorage, Alaska 99519 P.O. Box 102954 Anchorage, Alaska, 99510 (907)272-8218 Fax Subject: Lot 32, Block 4 Valli Vue S/D Septic System Replacement Permit Request - Failed Septic System Gentlemen: I submitted a permit application on June 1, 2002 for the subject lot. Your department issued a permit for the installation of a newAdvantex system based on my design. The initial design was based on a three-bedroom house. The Owner has informed me that his house has beenremodeled to a five -bedroom house. I am resubmitting the design showing afive-bedroom system. The Owner still intends to utilize an Advantex system, but it will have a 2000 -gallon tank to service the five -bedroom house. The drain field was increased in size to handle the effluent from a five bedroom house. I request your department modify the permit to allow installation of the five bedroom system per the revised design. If you have any questions or concerns, please contact me at 227-3522 or 272-8218. Sincerely, 4yr» teven R. Pannone, P.E. JD. Civil Engineer fo Steven R. Penn( '�' No. CE 8149 Attachments: HASTEVZWORD DOCUMENTS324VALLIVUE.002.DOC 0 PERMIT NO, DESIGN WASTEWATER DISPOSAL SYSTEM LOT 32, BLOCK 4 VALLI VUE S/D I ` I � . I � I � I I I j 100' CREEK I SET -BACK- I SURVEYED E;P SYSTEM I IN FAILURE 4NDON IN PLACE I I I I EXIST'G j 5BR HOUSE I I West Tree Dr vi e ADVANT SEF W/AX20 I 1 I PROPOSED DRA j 25LFx2'x5 I I I 23 I I P.I.D. NO, 015-341-62 /z T'G NOTE, 1) ALLWO SHAL BE PE ORME] IN ACCORD CE WI AMC1 65. 2) MATERIAL USED HALL E IN ACCORDANCE ITH T SE SP CIF] IN AMC15.65, ASTEW TER DI PO! 3) CONNECT P T TAN LINE 0 [allD TEM IN 30 Work\DRAWING\32-4Vn11lu .DM/G POINT OF AI FIELD. TYPIC - 4) MAINTAIN 10' SEPARATION T ALL w, 5) LOT LINES. •••`� 5) LOT SERVED BY CLASS WATER SERVICE. """"•• NO WELLS WITH IN 200' OF PROPOSED SYSTEM. 6) INSTALL ADVANTEX SYSTEM PER MFG 4E• 49TM •�. 6 MOA INSTRUCTIONS & INSTRUCTIONS. .• ... ••1 PREPARED FOR, PANNONE ENG. SVC, LLC ,en R. Ponnonee/�� Worc Cruze P. O. BOX 102954 No. CE Slg9 ' N 6211 West Tree Drlve ANCHORAGE, ALASKA 99510 5 • 99516 �d�'''�• Anchorage, AK 227-3522 P, 272-8218 Fax ••..•e�.�•• 346-2203 Hn .�xs5l __• 742-5360 Wk DATE, 6-1-02 1 DESIGN i ' 16 /z T'G NOTE, 1) ALLWO SHAL BE PE ORME] IN ACCORD CE WI AMC1 65. 2) MATERIAL USED HALL E IN ACCORDANCE ITH T SE SP CIF] IN AMC15.65, ASTEW TER DI PO! 3) CONNECT P T TAN LINE 0 [allD TEM IN 30 Work\DRAWING\32-4Vn11lu .DM/G POINT OF AI FIELD. TYPIC - 4) MAINTAIN 10' SEPARATION T ALL w, 5) LOT LINES. •••`� 5) LOT SERVED BY CLASS WATER SERVICE. """"•• NO WELLS WITH IN 200' OF PROPOSED SYSTEM. 6) INSTALL ADVANTEX SYSTEM PER MFG 4E• 49TM •�. 6 MOA INSTRUCTIONS & INSTRUCTIONS. .• ... ••1 PREPARED FOR, PANNONE ENG. SVC, LLC ,en R. Ponnonee/�� Worc Cruze P. O. BOX 102954 No. CE Slg9 ' N 6211 West Tree Drlve ANCHORAGE, ALASKA 99510 5 • 99516 �d�'''�• Anchorage, AK 227-3522 P, 272-8218 Fax ••..•e�.�•• 346-2203 Hn .�xs5l __• 742-5360 Wk DATE, 6-1-02 1 DESIGN PERMIT NO, DESIGN DETAILS WASTEWATER ABSORPTION SYSTEM LOT 32, BLOCK 4 VALLI VUE S/D NOTE, 1) ALLWORK SHALL BE PERFORMED IN ACCORDANCE WITH AMC15.65. 2) MATERIALS USED SHALL BE IN ACCORDANCE WITH THOSE SPECIFIED IN AMC15.65, WASTEWATER DISPOSAL. 3) CONNECT POST TANK LINE TO MID- POINT OF DRAIN FIELD. TYPICAL. 4) INSTALL DRIVEWAY AT LEAST 5 FT AWAY FROM DRAINFIELD. DO NOT INSTALL DRIVEWAY OVER DRAINFIELD. 5) MAINTAIN 10' SEPARATION TO ALL LOT LINES. ao T Cu Cu N V a a a u eU �Q o K • L d Drawing C,\Work\32-4ValiVue.DWG N N en n. runnvnc. Wnrc Cruze CE 8149 °N� 6211 West Tree Drive Anchorage, AK 99516 346-2203 Hn FES51��� 742-5360 Wk P.I.D. NO, 015-341-62 3Hn1 baimoN 00 NV31 ifla NY313 00 NV313 !n0 NV310 1n0 NV313 1n0 NV313 NOUVQNnoi �4 f Y 6 � yWy, Y Li N LJ J l� C3 Ce Cl. Pannone Eng. Svc., LLC P. 0. BOX 102954 ANCHORAGE, ALASKA 99510 DESIGN PERMIT NOi SW DESIGN DETAILS P.I.D. NO, WASTEWATER ABSORPTION SYSTEM LOT 32, BLOCK 4 VALLI VUE S/D r INSTALL 4' RIGID INSULATION OVER TANK & DRAINFIELD. EXTEND R.I 2' BEYOND SIDE OF TANK. INSTALL R.I. AROUND AX -20 FILTER. ADVANTEX TANK DETAIL DESIGN CALCULATIONS Number of Bedrooms - 5 Total Bedrooms - 5 Design flow - 150 gal/br/day, Total flow - 750 g/day TANK SIZE, 2000 gallon Advantex tank W/Auxilary Pump Add-on SOIL ABSORPTION SIZEi Advantex Sewer System AX20 Pod - Class III System Perc Rate= 16-30 min/inch Application Rate= 4 GPD/SF Size Required= 750 GPD/4 GPD/SF = 187.5 SF &.!��P�y ""4#0. Use Deep Trench, 5' effective 19 if Req'd 49TM GV ':�• Single Trench, 25 If. • • PREPARED FOR: PANNONE ENG. SVC. ASteven R.�Pannone! x Ware Cruze e & P. ❑. BOX 102954 • No,2C.�E�8149 ,: 6211 West Tree Drive ANCHORAGE, ALASKA 99510 ,. Anchorage, AK 99516 272-8218 PHONE & FAX 346-2203 Hn 742-5360 Wk DATE, 6-1 DESIGN Pannone Engineering Services, LLC P.O. Box 102954 Consulting Engineers Anchorage, Alaska, 99510 (907) 272-8218 (9071272-8218 Fax June 9, 2002 Municipality of Anchorage Development Services Department On -Site Water & Wastewater Program 4700 S. Bragaw Street P. O. Box 196650 Anchorage, Alaska 99519 Subject: Lot 32, Block 4 Vali Vue S/D Septic System Replacement Permit Request Gentlemen: My firm was contacted to investigate the possibility of a failed septic system serving this lot. The existing trench was inundated with liquid when I arrived. The system is indeed in failure. A single test hole was excavated on April 22, 1998 on the lot next door for that lots upgrade. The proposed replacement trench will fall inside this test hole's 30 radius. The soils report and a percolation test result is attached. Ground water was monitored for seven days. No bedrock was encountered in the test hole. No ground water was encountered in the test hole or at the monitoring on May 25, 1998. Due to the limited area available on the lot, I propose using an Advantex Treatment System, (AX20 Pod), with an auxiliary pump discharge unit to lift the effluent to the disposal area. The lot is approximately 21,538 square feet in size. Lot 32 slopes to the north at approximately 1-3 percent in the area of the test holes, and then steepens to approximately 10 percent on the northern portion of the lot. A creek flows along the north property line. The 100' creek set back was staked. The proposed installation will be located on the western portion of the lot. The lot is served by AWWU water system. The proposed location is greater than 200 feet away from existing neighboring wells and 25 feet from the water service lines. The surrounding wells are located greater than 200 feet from the proposed installation. The proposed installation will not affect the future development of the surrounding or existing lots. See the attached design. If you have any questions or concerns, please contact me at 227-3522 or 272-8218. Sincerely, —Steven . Pannone, P.E. Civil Engineer Attachments: C:\Work\Letters\32-4Vali Vue.001.doc DESIGN P.I.D. NO, 015-341-62 WASTEWATER DISPOSAL SYSTEM LOT 32, BLOCK 4 VALLI VUE S/D West Tree I , t ` I , 100' CREEK <, I SET -BACK - SURVEYED \ I IE SYSTEM IN FAILURE aNDON IN PLACE I t i EXIST'G 3BR HOUSE 1 Drive D ADVANT SEP SYST W/AX20 POD I 1 1 PROPOSED DRA 20LFx2'x5 I 23 i NOTE' 1) ALLWO SHAL BE PE ORM' IN ACCORD CE WI AMC1 65. 2) MATERIAL USED HALL E IN ACCORDANCE IN T SE SP CIF; IN AMC15.65, ASTEW TER DI PM 3) CONNECT P T TAN LINE O MID - Work\DRAWING\32-4VatlY .DWG POINT OF DRAI FIELD. TYPIC 4) MAINTAIN 10' SEPARATION T ALL �' LOT LINES. OF�� 5) LOT SERVED BY CLASS WATER SERVICE. ���P�• »»•. �� NO WELLS WITH IN 200' OF PROPOSED SYSTEM. JA 49M ♦ 6) INSTALL INSTRUCTIONS SYSTEM PER MFG t 49L" i & MOA INSTRUCTIONS 6 INSTRUCTIONS. yen R. Pannone?Wore Cru No. CE 8149 6211 West Tree Drive O+ 2609-,,r' 1K z Anchorage, AK 99516 »• �� 346-2203 Hn FSSI�� 742-5360 Wk w PANNONE ENG. SVC, LLC P. O. BOX 102954 ANCHORAGE, ALASKA 99510 227-3522 P, 272-8218 Fax 4TEi 6-1-02 DESIGN PERMIT NO, DESIGN DETAILS WASTEWATER ABSORPTION SYSTEM LOT 32, BLOCK 4 VALLI VUE S/D NOTE, 1) ALLWORK SHALL BE PERFORMED IN ACCORDANCE WITH AMC15.65. 2) MATERIALS USED SHALL BE IN ACCORDANCE WITH THOSE SPECIFIED IN AMC15.65, WASTEWATER DISPOSAL. 3) CONNECT POST TANK LINE TO MID- POINT OF DRAIN FIELD. TYPICAL. 4) INSTALL DRIVEWAY AT LEAST 5 FT AWAY FROM DRAINFIELD. DO NOT INSTALL DRIVEWAY OVER DRAINFIELD. 5) MAINTAIN 10' SEPARATION TO ALL LOT LINES. Drawing G\Work\32-4VnOVue.DWG R. Pannone! Fm - Warc Cruze 6211 West Tree Drlve ,.� Anchorage, AK 99516 • 346-2203 Hn FE55�_• 742-5360 Wk 1M] NV313 3eni Naimo inO NV31 ino NUM ino hv= It+COLI ino NV3M inG NV313 Nutivamm.j P.I.D. NO, 015-341-62 m M V J W J F-1 LL 0 C� Pannone Eng. Svc., LLC P. O. BOX 102954 ANCHORAGE, ALASKA 99510 ?7? -APIA. PHONE & FAX DESIGN PERMIT NO, SV DESIGN DETAILS P.I.D. NO, WASTEWATER ABSORPTION SYSTEM LOT 32, BLOCK 4 VALLI VUE S/D INSTALL 4' RIGID INSULATION OVER TANK & DRAINFIELD. EXTEND R.I 2' BEYOND SIDE OF TANK. INSTALL R.I. AROUND AX -20 FILTER. ADVANTEX TANK DETAIL DESIGN CALCULATIONS Number of Bedrooms - 3 Total Bedrooms - 3 Design flow - 150 gal/br/day, Total flow - 450 g/day TANK SIZE, 1500 gallon Advantex tank W/Auxilary Pump Add-on SOIL ABSORPTION SIZE, Advantex Sewer System AX20 Pod - Class III System Perc Rate= 15-30 min/inch Application Rate= 5 GPD/SF Size Required= 450 GPD/3 GPD/SF = 150 SF Use Deep Trench, 5' effective `% ��� 9 tf Req'd 0 Single Trench, 20 lf. Steven R. annone. r PREPARED FOR: PANNONE ENG. SVC. JVarc Cruze P. O. BOX 102954 No. CE 8149 °� Drive 6211 Vest Tree Dri,, ANCHORAGE, ALASKA 99510 d Anchorage, AK 99516 �1 "'•• •"".� 346-2203 Hn 272-8218 PHONE & FAX 4,'�1-. 742-5360 Wk DATE rn6-1-025 am crei c DESIGN ailty NuMel T & HUM a HEA � DEPARTMENT OF HEALTH d HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-OOW SOILS LOG —PERCOLATION TEST PERFORMED FOR! '-A QOU 1 L La"r-r':i DATE P LEGAL DESCRIPTION: L-411 xqyAtu VVF^ Township. S OPEge. Section. , SITE PLAN 1 2 3 4 6 6 7 8 9 10 11 12 13 14 16 16 17 16 19 O12 4&v I C SAAfty gtL•T 4 'Mikca d6tZAVIC"L 1M L I S t L-r,S WASO WATER ENC 1j ry ENCOUNTERED? IF VES, AT WHAT ^� DEPTH? "a' d wow Mum,,,_ a S/ WYMrIIpT �� 3� 3 21) U PERCOLATION RATE Z (mmutesanth) PERC MOLE DIAMETER S0 TEST RUN BETWEEN 6 FT ANO SFT COMMENTS -.04M ►EFFORMED SV: 2 ! ) iV A 4 .lzl� ZRF •'ERTIFV THAT THIS TEST WAS PERFORMED IN c��zZ�4t� ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE DATE 72-001 JAW A/6) W MAWR 110 M.1/7111mwr� 21) U PERCOLATION RATE Z (mmutesanth) PERC MOLE DIAMETER S0 TEST RUN BETWEEN 6 FT ANO SFT COMMENTS -.04M ►EFFORMED SV: 2 ! ) iV A 4 .lzl� ZRF •'ERTIFV THAT THIS TEST WAS PERFORMED IN c��zZ�4t� ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE DATE 72-001 JAW A/6) Pannone Engineering Services, LLC P.O. Box 102954 Consulting Engineers Anchorage, Alaska, 99510 ._-_. - (9071272-8218 Fax RECERCULATING SEPTIC TANK AND TRICKLE FILTER SPECIFICATIONS Lot 32, Block 4 Valli Vue Subdivision 1. GENERAL STATEMENT OF WORK 1.1 The work and plans covered by these specifications consist of furnishing all labor, materials, tools, transportation, and equipment necessary to complete an recalculating septic tank with trickle filter system as described herein and on the attached Contract Drawing. All work under this project shall comply with current Municipality of Anchorage (MOA) Regulations and shall conform to the following: • Three (3) Bedroom Private House 1.2 The Contractor shall carefully examine the project documents, have full knowledge thereof, have investigated the site and be satisfied with all conditions affecting the work. The Contractor shall notify the Engineer IMEDIATELY if conditions are encountered during the site investigations that affect the work. Any failure of the Contractor to become acquainted with the available information will not relieve the Contractor from the responsibility of performing the work as stated in these specifications. 1.3 The Contractor shall call for locates of utilities. Damage to utilities by the Contractor if locates are not called for is the responsibility of the Contractor. 2. MATERIAL 2_1 Tank: Septic: Tank shall be a two (2) compartment tank of at least the minimum size indicated on the drawings and shall be MOA approved. The compartments shall have a separate 4" clean-out riser. 2.2 Manhole Riser or Lift Station Tank: An additional second compartment manhole riser shall be capable of being equipped with the following: a. A junction box (Nema 4x) or equal, bonded or attached to the pump basin. b. UL listed electrical cord grips, installed in the J -box. C. An additional tank (MOA Approved) may be provided for the effluent pumping assembly and the items above. 2_3 Effluent Pumping Assembly, Controls, Alarm & Piping: a. Effluent pumping assembly shall be of approved materials, including: A 110 volt or equal UL listed effluent pump; High-density PVC cylinder housing the pump, with level controls and screen, serving as a baffle to prevent the screen from clogging; All piping shall be PVC or other non corroding material approved by the MOA. Pannone Engineering Services, LLC consulting Engineers P.O. Box 102954 ge, Alaska, 99510 b. Pump controls and alarm system shall be an approved system with the following options: - Event Counter - Elapsed Time Meter Program Timer - 10 Watt Heater - Remote alarm panel option xvith a minimum of 80 dB sound pressure at 24 inches, operating temperature 30 AC to 65 AC, and continuous sound to be located in the house. - Oil tight visual alarm with push -to -silence feature. Automatic audio alarm reset. - 15 amp motor rated toggle switch, double pole, double throw with three positions; Manual (man), Automatic (auto), and off. - Nema 4x rated fiberglass enclosure with hinged cover, or equal. - All controls to be installed per manufactures instructions. - Control panel to be installed on outside wall of home within sight of septic/lift station. c. Piping from septic tank to the trickle filter is to be 1 '/4" PVC schedule 40 solvent weld piping properly bedded and sloped to drain back to the lift station. Insulation board shall be placed over the line where the cover is less than four feet. d. The Air Compressor shall be a Thomas Linear Series model No. 5060-A or 5070V -A or MOA Approved equal. 2_4 Trickle Filter a. Trickle Filter Pod shall be AX20 manufactured by Orenco Systems Inc. and distributed by Anchorage Tank & Welding. b. Install all materials according to manufacturers instructions and in accordance with MOA regulations. 2.5 Soil Absorption System a) The drain field shall be constructed as shown on the drawings and in accordance with all applicable regulations described in Municipality of Anchorage AMC Title 15.65, "Wastewater Disposal Regulations" (MOA). b) Gravel to be used in the soil absorption system shall be well graded rocks and cobbles with size ranging from '/s" to 2 '/z" and approved for use in soil absorption systems by MOA. c) Perforated pipes shall be F810 LDPE or PVC 3034pipe, with two rows of perforations and shall be approved for use in soil absorption systems by MOA. d) Clean-out pipes and monitor tubes shall be 3034 PVC solid pipe. e) Clean-out caps shall be rubber "Jim Caps" securable with adjustable metal bands. Friction fit caps will not be accepted. Pannone Engineering Services, LLC Consulting Engineers rnnm nvn 47 f 4 PART 3 EXECUTION 3.1 LOCATION AND GRADE P.O. Box 102954 age, Alaska, 99510 1(171272-8218 Fax a) The septic tank shall be placed at the locations and elevations as shown on the Drawings. b) The drain field shall be placed in the location shown on the Drawing, with minor adjustments allowed to minimize excavation and accommodate the existing terrain. The drain field piping shall remain level over the length of the drain field. c) Dewatering may be required for all excavations that penetrate the groundwater surface. Dewatering costs shall be incidental to the excavation. If ground water is encountered during the excavation for the septic system, notify the engineer immediately. 3.2 EXCAVATION a) General: The Contractor shall accomplish all excavation required by the drawings through whatever substances encountered, to the depth as shown on the plans. All excavation shall be accomplished in accordance with the State of Alaska safety code and other applicable safety requirements. b) Water Removal: Water is expected in the limits of excavation as evidenced by the soil test pit information. If an apparent water table is observed in any of the excavations less than 5 feet below existing grade, notify the engineer immediately. 3.3 INSTALLATION A. Septic Tank 1. After excavation the tank shall be placed on undisturbed soil on a level grade at a depth as indicated on Drawings. Backfill around the tank with structural fill. Fill shall be installed in 12 inch lifts, compacted to 95% maximum density. Any damage to the protective coating during installation shall be repaired as recommended by the manufacturer. 2. The tank inlet shall be set at the elevation shown on the drawings. Care shall be taken during installation to ensure the proper elevation drop between the inlet and the outlet. Install flexible "fumco" rubber fittings at connection from tank to inlet and outlet pipes as indicated on Drawings. B. Joining Pipe Sections 1. Pipes shall be joined to one another, to the polyethylene fittings, cleanouts, and electrofusion couplings. Pannone Engineering Services, LLC P.O. Box 102954 Consulting Engineers Anchorage, Alaska, 99510 ron7l 272-R21 R (907) 272-8218 Fax 2. Cleanouts: (1) All earthwork and fill necessary to install the cleanouts shall be considered incidental. 3. Jointing: a. Fit the heat channel in place, ensuring that ends are deburred and square to allow easy passage of electrocal or glycol heat trace. b. Fit the insulation half -shells snugly in place. Band with strapping to hold tightly in place. c. Heat Shrink Coupling: Cover entire exposed joint plus an overlap of four inches on pipe coated on either end. Heat in accordance with manufacturer's instructions. 4. Installation: a. Install insulation half -shells and heat -shrink wrap at pipe connections. Maximum gap in half -shells shall be 'A inch. b. Lower assembled insulated pipe carefully into trench. Do not allow joints to deflect greater than the elastic capacity of the heat shrink sleeves. If sleeves are found to be damaged, reduce the deflection and repair the damages sleeves. c. Tolerances: (1) Lay mains to indicated line and grade. Perform earthwork in accordance with the Drawings. (2) Minor Changes in Direction: Pipe deflection will be allowed for small changes in direction, provided that the pipe bending radius is less than 30 times the diameter of the outer jacket of the insulated pipe system. C. Drain Field a) The drain field area shall be excavated to the elevation and dimensions as shown on Drawing. Remove all organic and silt material to the top of the well -graded sand layer. After excavation, the open bed shall be protected from surface runoff to prevent the entrance of silt and debris. Under no circumstances shall the use of heavy equipment be permitted on the drain field surface. All smeared or compacted surfaces shall be raked to a depth of 1 inch, and loose material removed, before any of the drain rock is placed. b) After all organic and silt material is removed, sand bedding shall be placed to an elevation shown on the drawings. Sand shall not be compacted. c) The bottom of the bed should be as level as practical. d) The gravel -less system and distribution piping shall be installed as shown on the drawings. e) The drain field shall then be backfilled with sand bedding to a depth of 1.0 above gravel -less system. Filter fabric and insulation shall be placed over the sand bedding. Pannone Engineering Serolces, LLC P.O. Box 102954 lting Engineers Anchorage, Alaska, 99510 Consu (907) lti 8218 (9071272-8218 Fax Backfill above insulation with material excavated from the building pad to the elevation shown. The material shall be mounded over the drain field as shown on Drawings. Backfill of drain field shall not be compacted. D. Close -Out A. Contractor shall submit unqualified as -built drawings and certificates on MOA approved forms to the Engineer, and MOA for approval to Operate. MUNICIPALITY OF ANCHORAGE Hear�: and Environmental Protec 'in i Fourth Floor West 825 L Street Anchorage, Alaska 99501 264-4720 INSPECTION_ REPORT ON-SITE SEWAGE DISPOSAL SYSTEM PHONE-2--ie-13 03 NAME TOjr MAILING ADDRESS %� �� _'5 '07 LOCATION LEGAL DESCRIPTION _. ZTf SEPTIC TANK: �`pJ NUMBER OF DISTANCE C •0&%0&v^ MATERIAL S COMPARTMENTS FROM WELL RX0. MANUFACTURER ` INSIDE LENGTH INSIDE WIDTH LIQUID DEPTH LIQUID CAPACITY GALLONS. TILE DRAIN FIELD: TOTAL LENGTH / p!� � FOUNDATION a.?O / NEAREST LOT LINE �O / OF LINE 33 DISTANCE FROMY/ELY-�U Q DISTANCE BETWEEN LINES TRENC14 YJIDTFI�V IN. TOTAL EFFECTIVE # of Lines ABSORPTION AREA �J SQ. FT. LENGTH OF EACH LINE 3.3 DEPTH OF FILTER ii " MATERIAL DENEAT14 TILE IN. ABOVE TILE IN. UC PTII: TOP OF TILE TO FINISH GRADE . SEEPAGE PIT: DIAMETER _ OR WIDTH _. LENGTH. DEPTH Log Crib Rings_ Crib Size: DIAMETER_—DEPTH__ DISTANCE FROM: WELL TOTAL EFFECTIVE SQ. FT. BUILDING FOUNDATION_. NEAREST LOT LINE ABSORPTION AREA (WALL AREA) Well Class: Com"^ Depth: Well Distance TO: Lot Line Bldg: Sewer Line: Pipe Materials: UJ - # of Bedrooms:— Installer:Remarks: 5111 TF 1 /�,� k APPROVED.. — _. �— DATE / 11 I - DEPARTMENT OF HEALTH AND ENVIRONMENTALPOOTECTION 825 '� STREET, ANCHORAGE, AK.. 91' • 27D-2511 rpt-J—L• I TE �E4JEFt. F'EF<'t7 I T PERMIT NO. r 7744= ) APPLICANT JOSE PRADO P 0 BOX 5787 LOCATION WET O' LOT SIZE LEGAL L12 B4 VALLI VUE EST TYPE OF SOIL ABSORBTION SYSTEM IS: TRENCH w30 ANL �. rf Ijo- ,6 -7 7 Oi11.t�tS 20514 SQUARE FEET MAXIhUJM NUMBER OF BEDROOM= _ _ SOIL EATING CSO FTrBR)= 130 THE REQUIRED SIZE OF THE SOIL ABSORPTION SYSTEM IS: C•EF'TF 1= ��� LEt�1��TH= --- f:3F F: %'EL C•EF'TH= - THE LENGTH DIMENSION IS THE LENGTH CIN FEET) OF THE TRENCH DRACE OFFTHED THE DEPTH OF A TRENCH OR PIT IS THE DISTANCE BETWEEN THE GROUND AND THE BOTTOM OF THE EXCAVATION CIN FEET). THERE IS NO SET WIDTH FOR TRENCHES. THE GRAVEL DEPTH IS THE MINIMUM DEPTH OF GRAVEL BETWEEN THE OUTFALL PIPE AND THE BOTTOM OF THE EXCAVATION (IN FEET). F :F=G!L� I RED cEF T I C THty1F_:: � I cE= 1c -1C r-3HLL_1:)r 5 F-sHt-F_:�f=l GE F'LFit-iT r_lF'T I Clr-j--------- A PACKAGE PLANT MAY BE INSTALLED AT THE PERMITTEE'S OPTION SUBJECT TO THE FOLLOWING CONDITIONS: 1. EITHER.. A CLASS I OR II NSF AP'P'ROVED PLANT MAY BE INSTALLED. 2. A CONTINUOUS MAINTENANCE AGREEMENT IS REQUIRED. IF A MAINTENANCE AGREEMENT IS NOT KEPT CURRENT YOU MAY BE REQUIRED TO ENLARGE THE SOIL ABSORPTION SYSTEM AND/OR YOU MAY BE SUBJECT TO PROSECUTION. ------ ------------------------- TFJ�1 C ^ I tJ�_.F'E��T I ��t�l=• HRE F<.E�v!�_1 I F:EC• --- BACKFILLING OF ANY SYSTEM WITHOUT FINAL INSPECTION AND APPROVAL BY THIS DEPARTMENT WILL BE SUBJECT TO PROSECUTION. MINIMUM DISTANCE BETWEEN A WELL AND ANY ON-SITE SEWAGE DISPOSAL SYSTEM IS 100 FEET FOR A PRIVATE WELL OR: 200 FEET FOR A PUBLIC WELL. OTHER R..EQUIREMENTS MAY APPLY. SPECIFICATIONS AND CONSTRUCTION DIAGRAMS ARE AVAILABLE TO INSURE PROPER INSTALLATION. F'F=FVrl I T EV:F• I FQEw<o C•ECEh1F3EFQ =AL, �? r I CERTIFY THAT 1: I AM FAMILIAR: WITH THE REQUIREMENTS FOR ON-SITE SEWERS AND WELL= AS SET FORTH BY THE MUNICIPALITY OF ANCHORAGE. 2: I WILL INSTALL THE SYSTEM IN ACCORDANCE WITH THE CODES. I UNDERSTAND THAT THE ON-SITE SEWER SYSTEM MAY REQUIRE ENLARGEMENT IF THE RESIDENCE IS REMODELED TO INCLUDE 1-1100�RE THAN 3 BEDROOMS. SIGNED:- AF'F'LICANT -PLIC----------------------�-"--------- _ 0 ,� �yC �`'-----DATE- d ^ aZ v -� V3. 0 ISSUED iED BY - -- X/ 0: ----- , GARS' P@,..AYMR VENTURMS CONSULTING GEOLOGIST 13O% 476-M, STAR ROUTE A • ANCHORAGE. ALASKA 99507 • PHONE 344-7071 Date 6 1 Vi '11 Performed Legal Description Depth (feet) SOILS LOG ) ose� I 3-2-1 int k 4- Ua IIe,,-,, U1 e -u Cs-IAeS --2- S M 5avv Gas e ct ., eke Lien sltE) ) jPins-c Gqtw <<, c �-e�j s , Total Depth feet in CW Was groundwater encountered r� ? What depth ? Depth to bedrock % Z 0 How determined !12 06,a VC (15 ? Respectfully submitted, e f Gary F. Player Consulting Geologist 8- G M 1 -10- -12- -14- G w -16 . -1 F3- -20- ct ., eke Lien sltE) ) jPins-c Gqtw <<, c �-e�j s , Total Depth feet in CW Was groundwater encountered r� ? What depth ? Depth to bedrock % Z 0 How determined !12 06,a VC (15 ? Respectfully submitted, e f Gary F. Player Consulting Geologist 'lo (YlLI L-.� ►sa ��cao� ��. ► Asa L Grp QI�t�-v. an �(La eaV1Fl �lc,c2 WL LI 9 t. MUNICIPALITY OF ANCHORAGE Ll DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTION 99801 S78 L Sww - Anchorow, Alaska • ENVIRONMENTAL ENGINEERING DIVISION 2,..e Telephone 264.4720 NV MBER OF BEDROOMS ❑ One ❑ Four ❑ Other FOR APPROVAL OF INDIVIDUAL WATER AND SEWER FACILITIES REQUEST ❑ MULTIPLE FAMILY DIRECTIONS: Complete NI parts on pap 1. lneampleb requests will not be Precwwd- %save allow ten 110) days for processing. 1. PROPERTY OWNER —N 3una �v'dp eS sa.< PK6LJo PHONE MMLING ADDRESS / 67 F% since June 1975. For wells drilled prior to that date, give well PROPERTY RESIDENT (If different from abovel HO E tONE PH 2, BUYER mos >~ calfindividualoversite,giveetiondate MAILING ADDRESS If system is over two (21 Years old an adeq cy test is required ears NO TI UTION "ip,d 4. iL!fo e 1 2_ .k dam' Z1, AAx PHONE r?�BSs�!/ MAILING ADDRESS ♦ REAL AGEN,T�/ S tjo3--•V MAILING ADDRESS S. LEGAL DEEjCRIPTION Ll L0� STREET LOCATION w�s1 The 2,..e 0. TYPE OF RESIDENCE NV MBER OF BEDROOMS ❑ One ❑ Four ❑ Other SINGLE FAMILY ❑ Two ❑ Five ❑ MULTIPLE FAMILY Three ❑ Six 7. WATER SUPPLY ❑ INDIVIDUAL' -ATTACH WELL LOG. A well log is required for all wells drilled COMMUNITY since June 1975. For wells drilled prior to that date, give well 0 PUBLIC UTILITY depth (attach log if available.) 0. SEWAGE DISPOSAL SYSTEM 7 calfindividualoversite,giveetiondate (W INDIVIDUAL/ON-SITE" If system is over two (21 Years old an adeq cy test is required ears ❑ PUBLIC UTILITY by this Department. NOTE: THE INSPECTION FEE MUST ACCOMPANY EACH REQUEST BEFORE PROCESSING CAN BE INITIATED. 72.01019/78) 72-010 1Rev. 3/78) 4 THIS SIDE FOR OFFICIAL USE ONL INSPECTION APPOINTMENTS DATE RECEIVED IME TIME TIME DATE DATE DA INSPECTOR INS ECTOR INSPE O DIRECTIONS: 1. TYPE OF RESIDENCE NUMBER OF BEDROOMS ffl' SINGLE FAMILY ❑ ONE THREE ❑ FIVE ❑ OTHER ❑ MULTIPLE FAMILY ❑ TWO ❑ FOUR ❑ SIX 2. WATER SUPPLY PERMIT NUMBER ❑ INDIVIDUAL DEPTH OF WELL COMMUNITY ❑ PUBLIC UTILITY DATE DRILLED Connection Verified LOG RECEIVED 3. SEWAGE DISPOSAL SYSTEM PERMIT NUMBER 1ffMDIVIDUAL/ON-SITE ❑PUBLIC UTILITY DATEINSTALLED Connection Verified /O /77 (�ptic Tank or ❑Holding Tank I ALLER 'w Size: zw If Tank is homemade /'SwAO give dimensions: SOILS RATING Vto TYPE OF TA K MANUF RER TOTAL ABSORCuQEnt— NA EA MATERIAL d. DISTANCES !6 SsPtk folding Toni, AtNorpt{on Area r Lim WELL T0: m M Abamption Ana to naarat Lot Line 5 COMMENTS "PROVED FOR � BEDROOMS ❑ CONDITIONAL APPROVAL (letter must accompany certificate) ❑ DISAPPROVED DATE BY Tine -7-/7-78 LEGAL DESCRIPTION l J 72-010 1Rev. 3/78) Municipality of Anchorage On -Site Water & Wastewater Program (907)343-7904 CERTIFICATE OF ON-SITE SYSTEMS APPROVAL Parcel I.D. 015-341-62 Expiration Date: — 1. GENERAL INFORMATION Complete legal description VALLI VUE ESTATES #2 BLOCK 4 LOT 32 Location (site address) Current Property owner(s) Mailing address Real Estate Agent 6211 WEST TREE *ANCHORAGE 99507 SUSAN KRUSE Day phone 6211 WEST TREE *ANCHORAGE 99507 2. TYPE OF DWELLING: Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 5 4. TYPE OF WATER SUPPLY: Day phone iAl JUL 1 1 2014 830-5360 TYPE OF WASTEWATER DISPOSAL: Individual Well ❑ Individual On-site 0 Individual Water Storage ❑ Individual Holding tank ❑ Community Class Well ❑ Community On-site LJ Public Water System 0 Public Sewer ❑ W aiverNariance request for: Received by: Date: �3Z% S COSA to be released to the engineer, unless otherwise requested by the engineer. Distance: — COSA Fee $ S` "A , Waiver Fee $ I / Date of Payment 1 It-lbq (l xa Date of Payment Receipt Number t�b1� Receipt Number COSA# 0`--t-1`ii -�)Z6 Waiver# 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, f verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. /further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm GARNESS ENGINEERING GROUP, Ltd. Phone 337-6179 Address 3701 E. TUDOR ROAD, SUITE 101 `ANCHORAGE, AK, 99507 / Engineer's Printed Name JEFFREY A. GARNESS, P.E. Date �,_/ 1 `f Engineer's Comments: In conducting this evaluation. GEG. LtD. attempted to provide a thorough, conscientious engineering analysis of the system in accordance with ADEC and MOA DSD Guidelines & Regulations. The reported results described the performance of the system under the conditions encountered at the lime of the test, and separation. distances measured to readily identifiable features. The operational life of all wells and septic systems depend on the local soils condition, groundwater levels that may fluctuate during the year, and the water usage of the family being served by the system. These conditions are outside the control of the evaluator of the system. Satisfactory test results do not guarantee future performance of the system, nor do they guarantee that there are no hidden defects or encroachments. GEG, LTD. can therefore not provide any warranty or future estimate of how long the system will continue to meet the operational requirements crib& ADEC or MOA DSD. The content o1 thus report is for the sole benefit of the owner listed above. Any reliance upon cruse of this report by any otherperson or partyis not authorized, nor will it confer any legal right whatsoever. 6. DSD SIGNATURE System #1 Approved for bedrooms. System #2 Approved for bedrooms. Disapproved. Conditional approval for bedrooms, with the following stipulations: kil"'1 ITE I vvtii r_rn AND WASTEWATER o PROGRAM_ pOLouel 0,2 O /tea. 1. is 124 021)") mfg I-/7-03_ / Original Certificate Date: 3 ' 9 — //5 The MuKcipafy`orXnc6@i,age Develop, emir Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 7. ATTCHMENTS: COSA Checklist Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other mom ronnn>i If more than 1 septic system is on the lot: COSA Checklist # Of Structure served by this system Certificate of On -Site Systems Approval Checklist Legal Description: VALLI VUE ESTATES #2 BLOCK 4 LOT 32 A. WELL DATA PUBLIC WATER Well type Date completed Total depth ft. Date of test Static water level If A, B, or C provide PWSID# Sanitary seal (Y/N) Cased to ft. FROM WELL LOG WATER SAMPLE RESULTS: Coliform colonies/100 ml. B. SEPTIC/HOLDING TANK DATA Tank T e/Material *STEP ft. Parcel ID: 015-341-62 Well Log (YIN) Wires properly protected Casing above ground) in. AT INSPECTION ft. g.p.m. Nitrate mg./L. Collected by: *ADVANTEX SYSTEM W/ A SINGLE AX -20 POD. YP Tank size 2000 gal. Number of Compartments 2 Foundation cleanout (YIN) YES Depression over tank (YIN) NO Date installed 2003 Cleanouts(Y/N) YES High water alarm (YIN) YES Date of pumping ADVANTEX Pumper ADVANTEX C. ABSORPTION FIELD DATA *BELOW EXISTING GRADE 9/18/2003 4 DEEP TRENCH Date installed 8/2/2006 Soil rating (g.p.d./Wor /bdrm 6 System type DEEP TRENCH 20 5 Length 44 ft. Width 2-3 ft. Gravel below pipe 6.4 ft. *8.5 200 Total depth *9 ft. Eff. absorption area 528 ft2 Monitoring tube YES Depression over field NO Date of adequacy test 6/23/14 Results (Pass/Fail) **PASS For 5 bedrooms Fluid depth in absorption field before test 0_5 in. Water added 1575gal. New depth 66 in. Elapsed Time: 220 min. Final fluid depth 59 in. Absorption rate >= 750+ g.p.d. Any rejuvenation treatment (past 12 mo.) (YIN & type) NONE If yes, give date **TESTED 2006 DRAINFIELD.�2003 DRAINFIELD DID NOT PASS ADEQUACY TEST 6/5/2014, tnrT�� D. LIFTSTATION * SEE ATTACHED MAINTENANCE REPORT Date installed 9/27/02 Size in gallons 250 Manhole/Access (YIN) YES "Pump on" level at 44 in. "Pump off' level at 41 in. High water alarm level at 46 in. Datum BOTTOM OF TANK Cycles tested *3 Meets alarm & circuit requirements? YES E. SEPARATION DISTANCES SEPARATION DISTANCES FROM WELL ON LOT TO:° Septic tank/lift station on lot On adjacent lots Absorption field on lot On adjacent lots Public sewer main Sewer /septic service line Holding tank manhole/cleanout Anim ment areas Manure/animal excrete storage areas SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Building foundation 5'+ Property line 5'+ Absorption field 5'+ Water main 10+ Water service line *10' Surface water. Wells on adjacent lots 200'+ SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Property line 10'+ Building foundation 10'+ Water main 10+ Water service line *10' Surface water 100'+ Driveway, parking/vehicle storage 1'+ Curtain drain NONE KNOWN Wells on adjacent lots 200'+ F. COMMENTS *SEWER SERVICE LINE AND WATER SERVICE LINE OVERLAP PER INSPECTION REPORT. NOTE: THE SINGLE AX -20 POD 0 IS NOT ADEQUATELY SIZED FOR FIVE C S -,.p S ADS G. ENGINEER'S CERTIFICATION BUT WAS APPROVED BY THE M.O.A. FOR THIS PARTICULAR INSTALLATION i certify that I have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. Engineer's Printed Name JEFFREY A. GARNESS Date -717-b* (Rev. 11/05) GARNESS ENGINEERING GROUP, Ltd CIVIL & ENVIRONMENTAL ENGINEERS July 1, 2014 Municipality of Anchorage Development Service Department On -Site Water & Wastewater Program 4700 Elmore Road, P.O. Box 196650, Anchorage, Ak 99519-6650 REFERENCE: Valli Vue S/D #2; Block 4, Lot 32: Configuration of Advantex System for a Five Bedroom House. To whom it may concern: The subject lot is served by a community well and a private septic system consisting of a 2000 gallon S.T.E.P. tank with an Advantex AX -20 treatment system and two individual drainfields. The Advantex system and one drainfield were installed in 2002 (SW020172). Another drainfield was installed in 2006 (SW060176). The 2002 install was permitted and approved as a five bedroom system by your department. The 2006 upgrade was listed as four bedrooms on the inspection report. Per the homeowner, the house currently has five bedrooms. We request that you approve the system for 5 bedrooms in its current configuration. The following items are justification for granting this approval: Your department previously approved the system as five bedrooms in 2002. While the AX -20 treatment pod is not large enough to treat 750 gpd to Category III standards, the likelihood of the household consistently using even 600 gallons per day is remote. The average water usage for a four bedroom residence is typically between 250 and 300 gpd. Therefore, it is reasonable to assume that the water usage for a five bedroom residence is less than 300-400 gpd. The 2006 drainfield, which was tested for the current C.O.S.A. approval, has an absorption area of 528 square feet and is oversized by a factor of 4.2 for a 5 bedroom system. (6.0 gpd/ft', minimum 125 W for 5 bedroom system, 528 ft2 actual) In short, the drainfield has adequate size to absorb 750 gallons per day. It passed a 5 bedroom adequacy test on 6/23/2014. In short, the system appears to be sufficient to serve the regular needs of this house and given that your department has previously approved the existing system as 5 bedrooms, we request that your department grant a C.O.S.A. for five bedrooms. 3701 East Tudor Road, Suite 101 "Anchorage, Alaska 99507-1259 Phone: (907) 337-6179 " Fax: (907) 338-3246' Website: www.garnessengineering.com If you have any questions, please contact us at 337-6179. Sincerely, .E., M.S. 3701 East Tudor Road, Suite 101 *Anchorage, Alaska 99507-1259 Phone: (907) 337-6179 * Fax: (907) 338-3246 * Website: www. garnessengineering.com Page 2 of 2 From: ANCH`TANK &WELDING INC f 04/23/2014 20:23 6626770 277 3715 Iiiiiiiii Kong III shows III so 5 E NNMENS ■ Now ■■■■n 07/02/2014 10:01 APws 226 346 a ■N■ ■■ E ONE EI OR K no . ■ ■ NONE ■ ^civalnTL=xO Field Maintenance Report Annual Insnection #157 P.001/001 PAGE 09 AnchorageTank 907-272-3543 rweny Qviowhxkinpe• pW (6.91 �P'r r Current Ward Kruse 2nd Compartment Mike Blakeslee �p7rr ...Cyti sae Add. PI'9vieU5 Cenlacl Phone 6211 Wast Tree Drive, Anchorage AK 99507 Bloiubee Finer ................. 907-346-2203 me" PI Comry 10M Porte fYrl1 WIILc Defe el Leet lnnPxflun AX -100181 SW060176 200656 RTU101287 08/07/2013 Retrieve OAM Info Ro:im redo -rimer seningsl Perform Field Sampling/06servatlons NTtI (t 5 s NTUs) pW (6.91 00 (2-E) Current Sputa Box .................. 2nd Compartment Odor of Sample Typical tArdvsy EJ Earthy ❑Moldy Non -typical 6 Sulfide ❑ Cabbage ❑ 0nitY Oily film In PVD ❑vas KIND Foam In tank ❑ Yes ANO Check Control Panel Racirc Amps Discharge Amps Audible and visual alarms wOK Dial tone ltelemetry only) E) yes 9'N. Inspect/Clean PUMP System Comments Clean Measure sludge/Scum Sludea Scum 1st Compartment Inspect Rlser/Lld ................ ...:: Current Sputa Box .................. 2nd Compartment Float Cords ................ �p7rr ...Cyti Floats ....................... PI'9vieU5 Pump............ ............� Bloiubee Finer ................. eiotueo Pump Vault ............ .. Racirculating SDlRter Valve....... Comments Clean Measure sludge/Scum Sludea Scum 1st Compartment Current Previous Current Pravleus 2nd Compartment Currant Pmvlaue Currant PI'9vieU5 Inspect/Clean AdvanTbx Filter Odor: 30 Normal ❑ Pungent Blomat: Normal ❑ Excessive Bddging/Ponding: q Nono/Mlnor ❑ Excessive inspeot/Clean Discharge Pump System Ins�p�^ct Splice Bax eKryR' Float cords — Inspeot/Service Other System Components Inapoot Clean I-AntralaJorficosw q Pod Bottom intake Vent _ Impact Clad tien Flaata ; 6L Pump l 'syL. Inspect Clean Inspect Clean Olslnfecton Equipmont Dispersal I.eterels/Onficas l� ' Cheervanona / Additional Services Rendered ❑ Cleaned tmalla shnets7 Replaced UV It0ms7 E]ReplaceoVtlsed other horns? 0RxS`—% �'^1Q �0 1 Parts Used: W = Warranty. B = Blilable (✓ appropriate selection) W B Item Number Daacrtptron FlrSafety Inspection SV relnstelled Manifold reconnected; slush valves closed Summary/Recommendations System parfomting: no further action needed ❑ Call for service Lids bolted on mrel panel reactivated ❑ Tank needs pumping ❑ Other? �ysrr���it■� Fax completed form to 1-866-384-7404 RM Recerf7-2-141 W 44> � A¢Wdj NO CORNERS SET THIS DATE � ,L.. �F •°. �4t I hereby certify that I have performed a Mortgagee's in- o"s.;e' :A •'•., t+ spection of the following described property• ?; 00 LOT 32, V^W-1 VUt= Ancho�.a,4, J� • h1/� � menta , �tecarding Precincts Alaska, and that the improvo- / s 7i. .CJ . ® menffi situated thereon are within the property lines and do �' P• : F,od w:,..,;".:n :,o ® not overlap or encroach on the property lying adjacent there - E, • NG. 3153-s :�a"'s to, that no improvements on property lying adjacent thereto "r a Q encroach on the premises in question and that there are no 9r�°ro. 5a roadways, transmission lines or other visible easements on .a• l� uF " •PNv`r"° said property except as indicated hereon. C 'J 4 t� OFFS N A` Dated at Anchoram Alaska 94 ;his 23A�'day of Q Al',) LJP.TzY Ig� EASEMENTS OF RECORD, OTHER THAN ° THOSE SHOWN ON THE RECORDED 1, Plsi co PUT ARE NOT SHOWN HEREON. FEED WALATKA & ASSOCIATES Engineers and Surveyors ADVANCED WASTEWATER TREATMENT SYSTEM MAINTENANCE AND REPAIR AGREEMENT BETWEEN MUNICIPALITY OF ANCHORAGE AND ... jo�K �LiGiMAJA_ THIS MAINTENANCE AND REPAIR AGREEMENT" made and entered into as of this Day of of 20_byandbetween Vituh herein the "OWNER," and the Municipality of Anchorage, herein the "MUNICIPALITY." In consideration of the mutual covenants contained herein, the parties to this Maintenance and Repair Agreement agree as follows: 1. Advanced Wastewater Treatment Systems. Municipality grants permission to Owner to utilize and operate an Advanced Wastewater Treatment System (AWWTS), described as located at (legal description). V4LJ; Viwe_ I g��s ,DZ L32- Elk 2. Definitions. Alteration, Any change to the design or function of an A'1NWTS that includes the installation or removal of any parts, components or pieces not included in the original construction permit and design. Certificate of On -Site Systems Approval (COSA). An approval by the Municipality of existing water and wastewater disposal systems given at the time of property sale and title transfer in. accordance with Anchorage Municipal Code (hereinafter, "AMC') 15.65. These approvals certify that the systems are adequate for the homes that they support and meet the codes that were in place at the time of system construction. Damage. Any man-made or natural change in a system that would inhibit the system from perforating as designed. Maintenance and Repair. The scheduled and as needed replacement of existing parts, components and pieces of an AWWTS that were included in the original design which would allow the AWWTS to continue to perform as designed. Permit. An On -Site Wastewater Disposal Permit as required by AMC 15.65 to construct and operate an AWWTS, 3. Term. The terra of this Maintenance and Repair Agreement shall begin on the date of approval by the Municipality to operate the installed system or issuance of a COSA, and shall continue while die AWWTS is in use or is operational or until the property is sold or title is transferred by the owner and a new COSA is issued to the new owner or transferee of the property. 4. Alterations. Installation and Removal of Additional Equipment. Prior to performing any altetatious to an AWWTS, the owner agrees to obtain an On-site Wastewater Disposal Permit from the Municipality in accordance with AMC 15.65, 5. Maintenance and Repairs. A. Throughout the term of this Maintenance and Repair Agreement, the Owner shall maintain their AWWTS in a satisfactory condition capable of producing treated septic effluent in accordance with the equipment's approval for operation in the Municipality. The owner shall eater into a service agreement with an AWWTS service and maintenance provider approved by the municipality and the manufacturer of the A;AIWI S for the entire term of the AWWTS. In addition, it shall be the responsibility of the Owner during the term of this Maintenance and Repair Agreement, and any renewals thereof. at the owner's sole expense, to pay for any and all: (1) repair(s), (2) maintenance, (3) adjustment(s), (4) replacement costs, and (5) inspection costs. B. Owner agrees to comply with all applicable ordinance, laws, regulations, rules and orders for the AWWTS. C. Upon request by the Municipality, the owner agrees to provide the Municipality a written schedule of routine maintenance and repairs which have been performed on the system. When a record of maintenance is documented and maintained by the system vendor, the owner agrees to allow the Municipality access to this information. D. Owner acknowledges that the fire for failing to maintain and repair an AWWTS may be assessed in accordance with AMC 14.60 for improper discharge. E. Owner agrees that only maintenance and repair personnel approved by the Municipality will inspect and make any necessary maintenance, repairs or permitted alterations to the system. F. Owner agrees to grant the Municipality reasonable access to test and inspect the AWWTS upon 24 hours written notice. G. Owner agrees that any sale or transfer of title of the property will not occur without anew Certificate of Ou-Site Systems Approval. H. Owner agrees that the AWWTS installation and maintenance requirements as provided by the AWWTS vendorlinstaller and approved by the Municipality are the governing guidelines for the construction, maintenance and repair of the Owner's AWWTS. 6. Nonwaiver. The failure of either party at any time to enforce a provision of this Maintenance and Repair Agreement shall in no way constitute a waiver of the provisions, nor in any way affect the validity of the Maintenance and Repair Agreement or any part hereof, or the right of such party thereafter to enforce each and every provision hereof. 7. Amendment. A. This Maintenance and Repair Agreement shall only be amended, modified or changed by a writing, executed by authorized representatives of the parties, with the same formality that this Maintenance and Repair Agreement was executed with, and such writing shall be attached to this Maintenance and Repair Agreement: as an amendment. B, For the proposes of any amendment modification or change to the terms and conditions of this agreement, the only authorized representatives of the parties are: a. Owner: b. Municipality: Director. Community l.�evelonment or designated atrthori v C. Any attempt to amend, modify, or change this contract by either an unauthorized representative or unauthorized means shall be void. S. Jurisdiction: Choice of Law. Any civil action arising from this Maintenance and Repair Agreement shall be brought in the Superior Court for the Third Judicial District of the State of Alaska at Anchorage. The laws of the State of Alaska shall govenr the ruts and obligations of the parties under this Maintenance and Repair Agreement, 9. Severability. Any provisions of this Maintenance and Repair Agreement decreed invalid by a court of competent jurisdiction shall not invalidate the remaining provisions of the Maintenance and Repair Agreement. By: �� &7 ," fix_ R =—(signahue) Date: 3',-"! STATE OF ALASKA ss. TH11W JUDICIAL DISTRICT ) The foregoing insfi-ument was aclrnowlodged before me this day of �LtvtL , 20 f 5, by J Uwrt �j ✓ vy �y� -- WOTARelPUBLICFOR ALASKA = NoTaRi M,y Corri&ssion expires" �Il�t . /L)� ! c7 y PUBLIC MIP.VICIPALITY: By ,_(signature) Date: name) Title: