On -Site Water and Wastewater Program
4700 Elmore St. • P.O. Box 196650 Anchorage, AK 99519-6650 • http://www.muni.org/onsite • (907) 343-7904
ON-SITE WASTEWATER INSPECTION REPORT
Permit Number: OSPI21249 PID Number: 018-241-27 [Z] New ❑ Upgrade
Name:
Timothy &Pauline Peters
ABSORPTION FIELD
❑ Deep Trench ❑✓ Shallow Trench ❑ Bed ❑ Mound
Address
2436 Clements Drive, Anchorage, AK 99514
❑ Other
Phone
Number of Bedrooms
Soil Rating
Total depth from original grade
4
1.2 GPD/SF
9 Ft.
LEGAL DESCRIPTION
Depth to pipe invert from original grade
2 Ft.
Gravel depth beneath pipe
7Ft.
Subdivision Block Lot
Turnagain Park #2 2 2
Fill added above original grade
- 1.2-3 Ft
Gravel length
36 Ft.
Township Range Section
-
Gravel width -
5Ft.
Beds: Number of Lines
Distance between lines
I Ft.
SEPARATION DISTANCES
To
Septic
Absorption
Lift Station
Holding
Sewer
Total absorption area
Number of trenches
-
Dist. between trenches
From
Tank
Field
Tank
Line
504 Fe
TWO
>14 Ft.
_
wlen >100'
>100'
N/A
N/A
>25,
TANK n Septic ❑ S.T.E.P. ❑ Holding ❑ Other
_
Manufacturer
Anchorage Tank
Capacity
1,250Gal.
surface Water >100'
>100'
NIA
N/A
Material
Steel
_
Number of compartments
Two
-
_
fi 2.5'2.5'
^N/A`
N/A
Lct Line
NA
--- -- r --
—
--
LIFT STATION
Foundation >5'>10'
NIA
N/A
Manufacturer Capacity
Curtain Drain None
Noted
GV.i.
" Pump on leve! at
Pump off level at
Hlgn water alarm at
Remarks See Lot Line Waiver.
in.
in.
-
Pump make and model
Electrical Inspections performed by
PIPE MATERIAL House to tank D3034 Tank to D3034
drainfield
Installer
_
A Plus Home Services
Drainfield F810 COiMT D3034
Inspector A Harala
BENCHMARK (Assumed elevation) 96.8ft
Inspection .+
8/17/13 a 8/17/13
Location and description
dates, 2
'"
Garage Slab.
3" 8/18/13 4
COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL
Engineer's Stamp
OF.,4
Conditional Approval: Date
`P.•'•�\�=pp 'qSs®,
H
49T
j.. .............
p, MICHAEL E. ANDERSON =
0 s. CE -4381 �; _` 0
Date
+#N%"R iw�0;40,
Approve ��
Inspection Repor_1-1-12.doc
Municipality of Anchorage
DEVEOPMENT SERVICES DEPARTMENT
4700 Bragaw Street Anchorage, AK. 99519-6655-343-7904
Permit No. OSP121249 On -Site Wastewater Disposal System or Well Inspection Report
yo
TURNAGAIN PARK SUBD., NO. 2
LOT 2, BLOCK 2
Lot 1
.-I N �1
�yo56 NO Well
R
She
Lot 12
�LQ,
00,,E
do�Q
X00 ��i
r
o/
Four B
edroom Home
>xi
/ Alternate
/ Site
A
/
a
0
96
�y6 A
Lot 3
A B
S1 46.4' 86.8'
S2 52.1' 90.2'
C4 61.5' WT
Al 43.8' 38.7'
C5 53.3' 82.1'
M2 1 68.51195,2'
C6 I 68.6' 99.0'
C7 66.3 88.5'
FSV 1 52.2' 85.0'
PLAN AS -BUILT
SCALE 1" = 40'
Page 2 of 3
P.I.D. No. 018-241-27
Municipality of Anchorage Page 3 of 3
DEVEOPMENT SERVICES DEPARTMENT
4700 Elmore Road Anchorage, AK. 99519-6655 - 343-7904
On -Site Wastewater Disposal System or Well Inspection Report
Permit Number: OSP121249 PID No. 018-24149
M
a S
U � F
Finished Grade
Ensdng Grade
U
WE
83.8
95.5
LRnI.J
5
94.8
92.8
U
Drainfeld Rock 90.8
75.8 II 18' (Trench Length) '
No Groundwater u
8-15-12
EAST TRENCH
M
U
94.0
92.8 II II n
ina and Finished \ II II II
-------------
Drainfield Rock 89.9
— 82.9
75.8 ... �.......,.. _.,..�...,
No Groundwater
8-15-12
WEST TRENCH o..............
;..........49t...............
:...............................z
:fir ; .MICHAEL E. ANDERSON
PROFILE AS -BUILT No. CE43n
No Scale ��.'t�f, ..-Jr/Z;�¢'�''
Alpine Drilling & Enterprises
Well LL-onfll
Q;P1X01gq say a
Permit Number: Date of Issue: Parcel Identification Number: 01824127000
Date Started 9-17-12 Date Completed: 9-17-12 Is well located at approved permit location? x Yes n No
Legal Description: Tumagain Park #2 Block 2 Lot 2 Well #2
Property Owner Name & Address: Peters Timothy P & Pauline M
2436 Clements Drive
Anchorage, Alaska 99515
Borehole Data:
Soil Type, Thickness & Water Strata
Depth (ft)
From To
Method of Drilling x air rotary ❑ cable tool
Casing type: steel
stick-up
0
3
Wall Thickness:.025 inches
silt
gravelly silt
3
5
5
29
Diameter: 6 inches Depth: 121 feet
Liner Type:
Diameter: _ inches Depth: _ feet
Sill
29
35
Casing stickup above ground: 3 feet
Static water level (from ground level): 93 feet
cobbly gravelly sill 35 65
gravelly sand
65
97
Pumping level: 121 feet after
silty sandy gravel
97
104
2 hours pumping 15 gpm
Recovery Rate: 15 gpm
water sand & gravel
104
121
Method of Testing:i li
Well Intake Opening Type:
x Open End ❑ Open Hole
❑ Screened Start _ feet Stopped _ feet
❑ Perforations Start _ feet Stopped _ feet
Grout Type: Bentanite granules Volume: 2 bps
Depth: Start 0 feet Stopped ? feet
Pump: Intake Depth _ feet
Pump size _ hp Brand Name
Well Disinfected Upon Completion? x Yes ❑ No
Method of Disinfection: chlorine tablets
Comments:
Well Driller: Alpine Drilling & Enterprises
PO Box 110496
Anchorage AK 99511
Development Services Department
Building Safety Division
• On -Site Water & Wastewater Program
4700 Elmore Road
P.O. Box 196650
Mark Begich Anchorage, AK 99507
Mayor www.muni.org/onsite
(907)343-7904
Pump /Installation Log
r %t raf±aT
Well Drilling Permit Number�e�**»'i" Date of Issue• t o?
Parcel Identification Number: 01624127000
Legal Description
Block 2, Lot 2 Turnagain Park #2
Pump Installation Date: 6/30/2013
Pump Intake Depth Below Top of Well Casing: 113 feet
Pump Manufacturer's Name: Orundfos
Pump Model: 10 SQE 15-330
Pump Size 1 112 hp
Pitless Adapter Burial Depth: NIA feet
Pitless Adapter Manufacturer's Name: NIA
Pitless Adapter Installer: NIA
Well Disinfected Upon Completion? Q Yes ❑ No
Method of Disinfection: chlorine tablets
Comments:
Pump Installer Name: Aarow Pump & well Service, LLC
P.O. Box 110496
Anchorage, AK 99511-0496
Property Owner Name & Address:
Tim & Pauline Peters
2436 Clements Dr.
Anchorage, AK 99515
Attention: The pump installer shall provide a pump installation log to the DSD within 30 days of pump installation.
5p
CF •q�qs�,
„�'• 49th00
y �j
*: j.
00
00V. Fred Walatka. ff /
0� c'IN • 3255 - S Jrt��
!1 �p ••, ••gyp �'�
111 �ftsslaua.
EASEMENTS OF RECORD, OTHER THAN
THOSE SHOWN ON THE RECORDED
PLAT ARE NOT SHOWN HEREON.
Plot plan
BE
\
Jo -
l
RECERTIFIED 5
AS -BUILT NO
8351K
Lot 12
SCALE: 1"= 30'
Anchorage Recording District, Alaska, and that the
improvements situated thereon are within the property lines
and do not overlap or encroach on the property lying
adjacent thereto, that no improvements on the property lying
adjacent thereto encroach on the premises in question and
that there are no roadways, transmission lines or other
visible easements on said property except as indicated
hereon.
Dated at Anchorage, Alaska
this 11th day of August ,2014.
FRED WALATKA & ASSOCIATES
Engineers and Surveyors
(907-248-1666)
-- Municipality of Anchorage -
Community Development Department
On -Site Water and Wastewater Program
4700 Elmore St. • P.Q. Box 196650 Anchorage, AK 99519-6650 • http:/Iwww.muni.orgtonsite • (907) 343-7904
Well
Legal Address: ,..�'` �., �„ ZI
Subdivisioni�/'r%•,� Blocker Lot
T R Section
On-site Water & Wastewater Program codified contractor performing the wall decommissioning:
Na Signature:
Signature:
Well decommissioning date /7 /,� Method ofdacnmmissioning: AMC 15.55.0601-1 a. ❑ b. ❑ C.
Location: Use the space below to provide a drawing of the property showing the following items;
• North arrow -
• Decommissioned waC
• OthTwo septer arate
swing -tie
onthe
disiRproperty,
• Two separate swing -tie distances for each well shown on the drawing,
Note: The swing -tie distances shall he measured from either permanent structures or the property corners.
� I
F
;k 16-
Alpine Drilling & Enterprises
Well Log
Permit Number: #SWOSP111121 Date of Issue: 7-12-11 Parcel Identification Number: 01824127000
Date Started: 7-9-11 Date Completed: 7-9-11 Is weil located at approved permit location? x Yes ❑ No
Legal Description: Tumagain Park #2 Block 2 Lot 2
Property Owner Name & Address: Peters Timothy P & Pauline M
2436 Clements Drive
Anchorage, Alaska 99515
Borehole Data: Depth (ft) Method of Drilling
Soil Type, Thickness & Water Strata From To x air rotary ❑cable tool
stick-up
silt
gravelly silt
silt
cobbly gravelly silt
gravelly sand
silty sandy gravel
water sand & gravel
0
1.5
9
27
31
58
71
98
Casing type: steel
1.5 Wall Thickness:.025 inches
9 Diameter: 6 inches Depth: 101 feet
Liner Type:
27 Diameter: inches Depth: feet
31 Casing stickup above ground: 1_5 feet
58
71
98
101
Static water level (from ground level): 84 feet
Pumping level: 101 feet after
2 hours pumping 6 gpm
Recovery Rate: 6 gpm
Method of Testing: air li t
Well Intake Opening Type:
x Open End ❑ Open Hole
❑ Screened Start feet Stopped feet
❑ Perforations Start feet Stopped feet
Grout Type: Bentonite granules Volume: 2 bes
Pump: Intake Depth feet
Pump size _ho Brand Name
Well Disinfected Upon Completion? x Yes ❑ No
Method of Disinfection: chlorine tablets 11
Comments:
Well Driller: Alpine Drilling & Enterprises
PO Box 110496
Anchorage AK 99511
On -Site Water & Wastewater System Permit
Permit Number: OSP121249
Tax Code Number: 01824127000
Work Type: WellSeptic Renewal
Permit Effective Dates: August 24, 2012 to August 24, 2013
Design Engineer: ANDERSON ENGINEERING
Subdivision: TURNAGAIN PARK #2
Site Legal Address: TURNAGAIN PARK #2 BLK 2 LT 2G-3033
Owner/Address: PETERS TIMOTHY P & PAULINE M
2436 CLEMENTS DRIVE ANCHORAGE AK 995154139
Site Mailing Address: 14495 OLD SEWARD HWY, Anchorage Lot Size in Sq Ft: 17500
Total Bedrooms: 4
This permit is for the construction of:
Y Disposal Field Y Septic Tank N Holding Tank N Privy Y Private Well N Water Storage
All construction must be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater
Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80).
3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services
Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either:
A. Open and Close on the same day.
B. Covered, sealed, and heated to prevent freezing.
Special Provisions: This renewal permit is also Change Order 2 to initial permit OSP111121,
Change Order 2 includes waiver OSP121250, allowing the drainfield and septic tank to be a
minimum of 1.5 feet from the Lot 3 property line, and the well to be 87 feet from the absorption field
on Lot 1.
Received
Issued By
Fa i
MUNICIPALITY OF ANCHORAGE
Development Services Department
;
On -Site Water & Wastewater Program
'
4700 Elmore Road, PO Box 196650
1)c l,o- rtrn .nt
Anchorage, AK 99519-6650
Telephone: (907) 343-7904
Work Type: WellSeptic Renewal
Permit Effective Dates: August 24, 2012 to August 24, 2013
Design Engineer: ANDERSON ENGINEERING
Subdivision: TURNAGAIN PARK #2
Site Legal Address: TURNAGAIN PARK #2 BLK 2 LT 2G-3033
Owner/Address: PETERS TIMOTHY P & PAULINE M
2436 CLEMENTS DRIVE ANCHORAGE AK 995154139
Site Mailing Address: 14495 OLD SEWARD HWY, Anchorage Lot Size in Sq Ft: 17500
Total Bedrooms: 4
This permit is for the construction of:
Y Disposal Field Y Septic Tank N Holding Tank N Privy Y Private Well N Water Storage
All construction must be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater
Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80).
3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services
Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either:
A. Open and Close on the same day.
B. Covered, sealed, and heated to prevent freezing.
Special Provisions: This renewal permit is also Change Order 2 to initial permit OSP111121,
Change Order 2 includes waiver OSP121250, allowing the drainfield and septic tank to be a
minimum of 1.5 feet from the Lot 3 property line, and the well to be 87 feet from the absorption field
on Lot 1.
Received
Issued By
Fa i
C. W
11TOINTATITRIUMA
Community Development Department, Phone: 907-343-7904
Development Services Division Fax: 907-343-7997
On -Site Water & Wastewater Program
Mayor Dan Stailivan
ON-SITE SEWER/WELL PERMIT APPLICATION
FOR A SINGLE FAMILY DWELLING
Parcel I.D. 018-241-27
Property owner(s): Timothy and Pauline Peters Day phone: 351-3059
Mailing address : 2436 Clements Drive Anchorage, AK 99515
Site address: Old Seward Highway Anchorage, AK 99515
Legal description (Sub'd., Block & Lot): Turnagain Park No. 2, Block 2, Lot 2
Legal description (Township, Range & Section)
Lot Size: 17,500 Sq. Ft. Number of Bedrooms: Four (4)
THIS APPLICATION IS FOR: THIS APPLICATION IS AN:
(M all that apply) Initial ElAbsorption Field X
Septic Tank X
Upgrade ❑
Holding Tank ❑ Renewal X
Privy ❑
Private Well X
Water Storage ❑
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
Well to Absorption Trench and Absorption Trench/Septic Tank to Lot Line.
I certify that the above information is correct. I further certify that this application is being made
for a Single Family Dwelling and is in accordance with applicable Municipal Codes.
nature
property owner or authorized agent)
Permit/Rush Fees: 10� Waiver Fees:
Date of Payment:
Date of Payment: —
Receipt Number: Receipt Number: —
Permit No. as 0) Waiver No. OSPIst S�6
C:\Users\AndEng\Desktop\MikelCross View EstatWPermit Application Lot 1 H2L.docC:\Users\AndEng\Desktop\MikelCross View
Estates\Permit Application Lot 1 H2L.doc
Community Development Department
Development Services Division
On -Site Water & Wastewater Program
Mayor Dan Sullivan
ON-SITE SEWER/WELL PERMIT APPLICATION
FOR A SINGLE FAMILY DWELLING
Parcel I.D. 2 7
Property owner(s) % I t"f N`l +- 1 0t cr P`T07P_ S Day
Mailing address `L C"Iis [)L\u:' i
Site address h'i t oc. dim(
Legal description (Sub'd., Block & Lot)L.v
Phone: 907-343-7904
Fax: 907-343-7997
rr:h( �= r�l` fief`s i5
Legal description (Township, Range & Section)
Lot Size !%t S Ce" Sq. Ft. Number of Bedrooms Fr___Agt _ Ql
THIS APPLICATION IS FOR:
(® all that apply)
Absorption Field
Septic Tank KSI
Holding Tank ❑
Privy ❑
Private Well 19,
Water Storage ❑
THIS APPLICATION IS AN:
Initial �1
Upgrade ❑
Renewal ❑
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
6 `�=� C"ti.• i'C SC` dam . n r t I IZ` /� Ct I _ C..U. j
I certify that the above information is correct. I further certify that this application is being made
for a Single Family Dwelling and is in accordance with applicable Municipal Codes.
(Signature of property owner or authorized agent)
�Pen*,Rush Fees
ate of Payment
Receipt Number:
j 75 - 1
Permit No. L .,i' I t 11; )-
Waiver Fees. I L -`7k_'
Date of Payment.
Receipt Number.'c
Waiver No.
G:\Building\On SiteTorms\Client FormsTermit App _010411.doc (Rev. 1/11)
�—
C0�Z
Municipality of Anchorage
P.O. Box 196650 0 4700 Elmore Road
Anchorage. Alaska 99519-6650 0 (907) 343-7904 0 Fax (907} 343-7997
http:11www.m un i.oM1Onsite
Development Services Division
On -Site Water and Wastewater Program
DEpertment
**** VARIANCE/WAIVER REVIEW ****
Waiver#: OSP121250 COSA#: Permit#:OSPI21249
PID#: 018-241-27
Legal Description: Turnagain Park #2. Block 2, Lot 2
Engineer: Anderson Engineering
Applicant: Timothy and Pauline Peters
Your request for a waiver of the required 10 feet(absorption field) and 5 feet(sepfic tank)
horizontal separation from the absorption field and septic tank to the property line has been
approved. The approved separation distance is 1.5 feet.
Your request for a waiver of the required 100 feet horizontal separation from the absorption field
to the private well has been approved. The approved separation distance is 87.0 feet.
This waiver approval applies to the proposed absorption field and septic tank, and well only.
Any future upgrade to the on-site wastewater disposal system will require all separation
distances be met or another approval from this department.
® The affected adjacent property owner(s) have been given a 7 day notice regarding this
waiver.
❑ Notarized letter(s) of non -objection have been received from the owner(s) of the affected
adjacent property.
❑ Adjacent properties are not affected by this waiver.
..................I.............................................. a........... 0.
Waiver is Granted: X Waiver is not Granted:
Date: g a o2 Approved by i
Name of Reviewer
...............................................................................
Rec#: 006008 Amount: $1,050.00 Date Paid: 5/23/2011
**** VARIANCE/WAIVER REVIEW ****
coo
ANDERSON ENGINEERING
P.O. BOX 240773
ANCHORAGE, AK 99524
522-7773 677-7766 (FAX)
August 15, 2012
Municipality of Anchorage
Development Services Department
On -Site Water and Wastewater Program
4700 South Bragaw Street
Anchorage, AK 99519-6650
Subject: Lot 2, Block 2, Turnagain Park Subdivision No. 2
Septic System Design and Permit Application Renewal
Permit Number OSP 111121
Dear Onsite Services Engineer:
We are hereby requesting the well and septic system permit for Lot 2, Block 2,
Turnagain Park Subdivision No. 2 be renewed for a second year. All provisions of the
original design remain the same with the exception that the subsurface soil materials
near the front of the lot were found to be much cleaner and more conducive for the
development of a septic system. A recent test hole revealed silty gravel with sand to a
depth of 17'. No groundwater was found and none has developed during the
monitoring period. The percolation rate of the soil is 5 minutes per inch.
The existing well on the lot will be decommissioned in accordance with Municipal Code.
The new well will be placed 87' from the adjacent absorption trench on Lot 1 which is
nearly 20' further than the previous well location. The new septic system location is
much more efficient than the original plan. The alternate site will remain at the original
location.
If the system is constructed in accordance with our revised design the following
statements apply:
1. The system, if constructed as designed, will have no adverse impact on the wells
in the area or those to be constructed in the future.
2. The system, if constructed as designed, will have no adverse impact on existing
septic systems in the area or those to be constructed in the future.
3. The system, if constructed as designed, will have no adverse impact on reserve
space, either surface or subsurface, on any lots located in the area.
c0a
Lot 2, Block 2, Turnagain Park Subdivision No. 2
August 15, 2012
Page Two
4. The system, if constructed as designed, will have no adverse impact on drainage
patterns in the area. The current drainage pattern will be maintained.
Sincerely,
Michael E. Anderson, P.E.
Attachments
�: 49th �•••':�
MICHAEL E. ANDERSON
No. CE -4381 •
COa
ANDERSON ENGINEERING
P.O. BOX 240773
ANCHORAGE, AK 99524
522-7773 677-7766 (FAX
August 15, 2012
Municipality of Anchorage
Development Services Department
On -Site Water and Wastewater Program
P.O. Box 196650
Anchorage, AK 99519-6650
Subject: Lot 2, Block 2, Turnagain Park Subdivision No. 2
Separation Distance Waiver
Absorption Trench to Lot Line
Dear On Site Services Engineer:
The new septic system absorption trenches proposed for construction on Lot 2, Block 2,
Turnagain Park Subdivision No. 2 will be placed 1.5' from the southeast lot line and 4.5'
from the northwest lot line In addition, the septic tank will be 4' from the southeast lot
lien. The new system is more than 10' from the neighboring system and meets all
separation distance requirements. The lot is small and fronted on the northwest by the
Old Seward Highway right of way. The entire system will be more than 100' from all
private wells in the area. We therefore recommend the lot line waiver be issued as
described above.
Sincerely,
Michael E. Anderson, P.E.
co.12
ANDERSON ENGINEERING
P.O. BOX 240773
ANCHORAGE, AK 99524
522-7773 677-7766 (FAX)
August 15, 2012
Municipality of Anchorage
Development Services Department
On -Site Water and Wastewater Program
4700 Elmore Road
Anchorage, AK 99519-6650
Attention: On Site Services Engineer
Subject: Lot 2, Block 2, Turnagain Subdivision No. 2
Separation Distance Waiver Well to Absorption Trench
Dear On Site Services Engineer:
Lot 2, Block 2, Turnagain Subdivision No. 2 along with the lots on either side are only 100' in
width. The well on the lot to the northwest was placed in the middle of the lot apparently with
little regard to the effect of the 100' setback on Lot 2. In addition, the septic system on Lot 1
was placed without regard to the location of a possible well on Lot 2. Very little area remains on
Lot 2 for the placement of both a well and septic system making the lot undevelopable without a
waiver from the well on Lot 2 to the absorption trench on Lot 1. The well is currently located 87'
from the closest edge of the absorption trench. We are therefore requesting a waiver be issued
allowing the well to remain in its proposed location so the lot can be developed.
We anticipate the well will be approximately133' deep with casing the entire depth based on the
depths of wells already in place in the subdivision. The well will be drilled through what appears
to be very dense silt with gravel and sand the entire depth. Test holes on the lot indicate nearly
impervious material for the first 10'. Soils from 10' to 24' were found to percolate at rates
approximating 60 minutes per inch. The aquifer level is anticipated to be at least 93' below the
ground level where the pump will be placed. The intake to the pump will probably be found
more than 117' below the bottom elevation of the septic tank.
The absorption trench on Lot 1 is served by a Biocycle Tank, which is considered a Category II
Wastewater Treatment System and is much more effective in the treatment of septic effluent
prior to disposal to the environment than a standard septic system. In most cases the effluent
from a Biocycle Tank contains less than 10% of the contaminants that can be expected from a
standard septic tank.
The original ground surface on the lot slopes away from the well and toward the septic tank at
an approximate 10% slope. The original topography of the lot will be contoured with the
construction of the house and the well head will be contoured for any surface water to drain
away. The ground elevation at the absorption trench is approximately 20' lower than the well
C D1�
Lot 2, Block 2, Turnagain Park No. 2
August 15, 2012
Page 2 of 2
head. We assume the water gradient slopes away from the well at a slope similar the original
ground surface.
Water samples will be taken from the well once it is drilled to determine whether contamination
from any source in the area is occurring. We are confident the Biocycle system will have no
impact on the quality of the water to be produced on Lot 2 for several reasons. The first and
primary being the treatment from the tank itself before the effluent is discharged to the
environment. We are also confident sufficient dense soil exists between the bottom of the
absorption trench and the aquifer to prevent contamination from occurring.
ADEC POINT ANALYSIS (ESTIMATED)
Bottom of Tank to Highest Water Table — 83' 5.90 Points
Soil Absorption Type — Silt 3.50 Points
Permeability — Perc. Rate > 50 Min./Inch 3.00 Points
Water Table Gradient - +10% 6.00 Points
Horizontal Separation — 87' 2.50 Points
TOTAL POINTS 20.90
Almost sure to be free from any form of contamination from household sewage.
Attached are logs from wells in the area, Site Plan and other drawings showing the proximity of
the existing septic system to the well. We hereby request the waiver be issued and the permit
to construct a well and septic system on Lot 2 be approved.
Sincerely,
r o
Michael E. Anderson, P.E.
Attachments
�'•' 49th,••••
MICHAEL E. ANDERSON
._ NO. CE-43Bi
NOTE:
Existing Well on Lot 2 to
be Decommissioned in
Accordance with Municipal
Code.
100' Proteotive
i Well Radius \
i
/
/
Od ;boa 5 i NtW59'00'E 121.01 (R) N89'59'00"E 104.Al (R)
Existing W II
xisting We
Lost 12 /
l�
$i� I
/ Lot
o a ae�
/ Existing Well \ z / m
100' \ Protective �� • _ o II Well Radius
�'ly- Proposed Lo I 2 / ' �o a, _— z
\ ,N,p1Nr 887' Well / $ — — _
0� 00 =
0
Four ��n / / ®/ S Lot 1 1 \ 3
\ Bedroom
Home
h Existing Z
Well me >0�OQO .3 \
O a
<1E Lot 3 R
0
.o ��"
S O'o +,� �y� Existing ell
O
y
yO \ cow I1 N89'56'59"E 29.57 �
G1 �oo.
SYSTEM DESIGN
1,250 Gallon Septic Tank °o�. LEGEND /
w/2 — 18' Long x 3' \ " SV — Septic Vent
Wide x 7' Effective Depth CO — Clean Out /
Absorption Trenches. Flow MT — Monitor Tube /
Splitter Required. \ TH — Test Hole
FCO — Found fon Cleanout
SITE PLAN
SCALE V'= 60'
\ �FSV _Flew Splitter Vavle
ALTERNATE SITE
Advantex Treatment
System w/20' Long x 3'
Wide x 8' Effective Depth
Absorption Trench.
NOTE:
Well Radii in the Area to
be Staked by a
Registered Land Surveyor
Prior to Construction.
U
LOT 2, BLOCK 2, TURNAGAIN PARK SUBDIVISION NO. 2
DESIGN FACTORS: SYSTEM REQUIREMENTS
Four Bedroom Home Deep Trench System
Perc. Rate: 5 Min./Inch 1,250 Gallon Septic Tank
Application Rate: 1.2 GPD/SF 7' Drainfield Rock
4 Bedrooms X 150 GPD/1.2 GPD/SF (Application Rate) = 500 SF Absorption Area
500 SF/14 SF/LF = 35.7 LF Trench Length
THEREFORE: Construct 2-18' Long x 3' Wide x 7' Effective Depth Absorption Trenches
at the Location Shown. Flow Line Elevation in Trenches to be 2' Below Original Ground Surface. Total
Depth to be 9' Below Existing Ground. Provide 4' Cover Over Septic Tank and 3' Cover Over Absorption
Trenches. Maintain 100' Separation from Wells in the Area. Place a Flow Splitter Valve in the
Configuration Show to Insure Even Flow to Each Trench.
Natural
Backfill
1'6" Geotexthe
Fabric
Fabric
g^ U I " Perforated
t PVC (Holes Down)
T0"
3'
Drainfield Rock
TYPICAL DEEP TRENCH SECTION •..���
(NO SCALE) ��..P�E.OF 741
NOTE: Grade Area Over Trench to Drain Away.: �y
Minimum 6' Separation From Bedrock. .... 49th.....•........:,....::.
Minimum 4' Separation From Groundwater. iYs'�czt<',r✓i
Minimum 100' Separation From Wells in the Area. ���; MicHne�e nnoeRsory
Minimum 100' Separation From Surface Water or Streams
MUNICIPALITY OF ANCHORAGE
DEVELOPMENT SERVICES DEPARTMENT
4700 BRAGAW STREET ANCHORAGE, AK 99519-6650
SOILS LOG - PERCOLATION TEST
LEGAL DESCRIPTION: Lot 2, Block 2, Turnagain Park No. 2
PERFORMED FOR: Tim Peters
DATE: 8/1/2012 PROJECT No.:
PARCEL ID#: TECHNICIAN: JKB
(feet) TEST HOLE # 3 I
(fee[)
1
2
3
4
5
6
7
8
9
1C
IJ
I
I
1
1
1
1
1
Grass/Organics SLOPE
�4.
Silty Gravel
with Sand
GM
e E e
Q:.
^e.a
9
e.
BOH
COMMENTS:
2%1
49th_
MICHAEL E. ANDERSON
Pmkss3onal
SI I E ELAN
SEE SITE PLAN
Y
GROUN D WATER ENCOUNTER ED? NO
IF YES @WT DEPTH° %of
DEPTH CMONONITORIA`G None 0 1O/a
DATE GP MONITORING. 8/15/12 E
DATE
READING
GROSS TIME
(MINUTES)
NET TIME
(MINUTES)
DEPTH of
WATER
(INCHES)
NET DROP
(INCHES)
8/3/12
TEST HOLE PRESOAKED PRIOR TO TESTING:
1
2:15
1.88°
CHARGE
2
2:45
30
8.13"
6.25"
3
2:46
1.63"
RECHARGE
4
3:16
30
7.63"
6.00"
5
3:17
1.75"
RECHARGE
6
3:47
30
7.75"
6.00"
PERCOLATION RATE: 5 (MINANCH) PERC. HOLE DIA.--8--(INCHES)
TEST RUN BETWEEN: 4_0 FT. and 5.0 FT.
TEST HOLE PRE SOAKED PRIOR TO TEST.
TEST PERFORMED BY ANDERSON ENGINEERING. 1, MICHAEL E. ANDERSON CERTIFY THAT THIS TEST
WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS
DATE: 8/15/2012
col
Municipality of Anchorage
Development Services Department
Building Safety Division
yE On -Site Water and Wastewater Program
4700 Elmore Road
P.O. Bax 191 Anchorage, AK 99507
www-ci anchorage.ak.us
(907) 343-7904
Soils Log - Percolation Test
Performed For: Timothy Peters
Legal Description: Tumagain Park Suhd., No. 2, Lot 2, Block 2 Township, Range, Section:
s Mma
7- t'f -ens'c'
WAS GROUND WATER
ENCOUNTERED? `O
Xxx e
IF YES, AT WHAT DEPTH? L
{r DeptU fa.Wetar After p
�y r M.mtodag? E
C.J �'� /..5`jr Date: It
' L?
May 20,
Reading
Date
Gross Time
Nel Tlme
Depth to Water
Net Drop
May 21, 14
1 t1
�.
.m II
19A
d Mr
��Iv
15-4
Iz+`R PERCOLATION RATE 54 (mimm&incr,) PERC HOLE DIAMETER 7 "
V� _Y TEST RUN BETWEEN 10 FT AND 10112 pT
COMMENTS TEST CAVITY was presoaked on May 20th
TEST HOLEg1
PERFORMED BY: A. Harala i CERTIFY THAT THIS TEST WAS
PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE:
col
Municipality of Anchorage
Development Services Department
Building Safety Division
On -Site Water and Wastewater Program
4700 Elmore Road
P.O. Box 106650 Anchorage, AK 99507
www ci anchcmae.ak.us
(907)343-7904
Soils Log - Percolation Test
Performed For: Timothy Peters
Date Performed: Apol 27, 2011
Legal DDAription: Tumagain Park Bubo., No. 2, Lot 2, Black 2 Township, Range, Section:
I>Q1
Site Plan
PERCOLATION RATE 54 (minuteslinch) PERC HOLE DIAMETER 7"
�^ TEST RUN BETWEEN 10 FT AND 101/2 FT
COMMENTS TEST CAVITY was presoaked for 1 day prior to testing -
TEST HOLE #2 -
PERFORMED BY: A. Harala i CERTIFY THAT THIS TEST WAS
PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE:
WAS GROUND WATER
I
p
APR 28, 11
ib15
A 14
ENCOUNTERED?
rr
11'zl
14;44
IF
YES, AT WHAT DEPTH?
S
L
11:4
v Iiw
`f•
bI1YL
Depth to Water Attar
xx
lam.
Monitoring?
l Cji 511) Date:VV
R E
i
7-ts
Reading
Date
Gross Time
Net Time
Depth to Water
Net Dro
PERCOLATION RATE 54 (minuteslinch) PERC HOLE DIAMETER 7"
�^ TEST RUN BETWEEN 10 FT AND 101/2 FT
COMMENTS TEST CAVITY was presoaked for 1 day prior to testing -
TEST HOLE #2 -
PERFORMED BY: A. Harala i CERTIFY THAT THIS TEST WAS
PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE:
p
APR 28, 11
ib15
A 14
to -44 v
rr
11'zl
14;44
11:4
v Iiw
`f•
PERCOLATION RATE 54 (minuteslinch) PERC HOLE DIAMETER 7"
�^ TEST RUN BETWEEN 10 FT AND 101/2 FT
COMMENTS TEST CAVITY was presoaked for 1 day prior to testing -
TEST HOLE #2 -
PERFORMED BY: A. Harala i CERTIFY THAT THIS TEST WAS
PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE:
SpuMand Eno�'nsn"Onp
. Environmental Consulting and Design7�'z
1117
SEPTIC SYSTEM DESIGN
Municipality of Anchorage July 8, 2011
DevelopiileiltSerf ices DePal'tnlcDt
Oil Site Water and Wastewater PrOgnUrt
4-700 South Bragaw Street
,Anchorage, Alaska 99519
Subject: Septic System
Ladies and Gentlemen:
rhe old septic system at Turnagain Park #2 Block 2 Lot 1 was abandon per MOA requirements. 'rhe old
drain field is not connected to the existing BioCycle AWW rS.
If you have any questions or concerns, please contact me at 279-3916.
LaE4rP)drk'1wtd, P.L.
Civil Engineer
203 West 15'h Avenue Suite 203. Anchorage-, AK 99501, Phone' (907)279-.1916
Fax- (866) -454-1597, Lspurldandoo, gei.net
Septic)EE��
/
Area /
/
/ Septics
Area
BLOCK 1
2
TC
5.0'
13.0'
1
INSTALLED BIOCYCLE
82.5'
3-BEDROOMTRENCH /
TOTAL LENH 36
71.5' C
TOTAL DEPT 1 T
ROCK 7.0 F
COVER 3.0 FT /
o
\
A
L
TC
5.0'
13.0'
1
D 74.5'
82.5'
i
\E 69.5'
71.5' C
I
-¢- Well
A( J
0 7estMle C \'// / ♦
:o +♦/♦
\ R ABANDONED EXISTTND—SY
VACEN T
9�
d
r \
C
9�
25 0 25 50 75 100 125 150
SCALE, I' -- 50 FT \
Septi
Area
\
kr Lars-�urkr5/1
ic!
3
Well
rt � TH�BEN SPURKLAN➢.. ,(�
C �u
No. cE-2225
TOBBEN SPURKLAND P.E. TURNAGAIN PARK 12 LOT I BLOCK 2 SEPTIC SYSTEM ASBUILT
203 W 15711. AVENUE DATE. • DECEMBER 6, 2005
ANCH. AK. 99501 J. R. MASDS£N
907 279-3916 11 2320 CLEMENTS DRIVE SHEET- 2/3 GRID: 3033
PERMIT # EW05OXXX PID # 018 -241 -XX TAP2020120 WG
Rim T
tom':- at g
r •�. x
�-
-,✓'.ate'"
a E N
*, t
Rx
S;
r
C
�u
t MR,
`
w J s
�
n
a
ah
6
x' a`w
2 £ a n@
ANI-,IN
r ` i x UP,
'# °�',#�
ak
Ca
k
}:�.s.t
• = a a e _ i M'41 �p
:r E�
5
n
a.
8 9107i
MUNICIPALITY OF ANCHORAGE
tiblr�r'Ila 1/:
•
Development Services Department Ph• 907-343-7904
On-Site Water & Wastewater Section F:%•07-343-79• ti
Certificate of On-Site Systems Approval 0/ 6 8 L 9
Parcel I.D. 018-241-27 Expiration Date: la-s-
1.
s1. GENERAL INFORMATION
Complete legal description Turnagain Park #2 Block 2 Lot 2
Location (site address) 14495 Old Seward Hwy, Anchorage, AK 99515
Current property owner(s) Timothy & Pauline Peters Day phone
Mailing address 14495 Old Seward Hwy, Anchorage, AK 99515
Real estate agent Dave Windsor Day phone 907-727-3300
2. TYPE OF DWELLING:
® Single Family (w/wo ADU)
❑ Duplex
LI Multiple Dwellings (Single Family and/or Duplex)
3. NUMBER OF BEDROOMS: Lf
4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL:
Private Well l Private Septic lX�
Water Storage ❑ Holding Tank ❑
Community Well ❑ Community ❑
Public Water System ❑ Public Sewer ❑
Waiver request for: Distance:
Received by: — -. Date: 101A II
COSA to be released to the engin r,unless otherwise requested by the engineer.
COSA Fee $ 52f Waiver Fee $
Date of Payment loft/1 Date of Payment
Receipt Number Oega21) Receipt Number
COSA# 05CIZl6 J Waiver#
5. STATEMENT OF INSPECTION BY ENGINEER
As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based
on procedures outlined in the Certificate of On-Site Systems Approval Guidelines for this application, shows that the
on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of
bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the
Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater
disposal system is (are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in
effect at the time of installation.
Name of Firm Forge Engineering Phone 907-522-7773
Address PO Box 240773, Anchorage, AK 99524
Engineer's Printed Name Benjamin Schiller, PE Date 9/27/18
oF
0 49 TH / o\ .*'/
6. DSD SIGNATURE % •-- �•• •••�;• •••-
System #1 Approved for bedrooms �.__ Benj m' Schiller _.
System #2 Approved for bedrooms �1i`%rF�..9/27/1s2.•������
Disapproved i�1F�PROFESSI�Nv
Conditional approval for bedrooms, with the following stipulations:
�J �N.SIT °
woWAsERAND
pRoGwA1�R
RAMcp
.0
.4SERVtCL`'�\
/ �3 2 ^1
By: � Original Certificate Date: / 0
The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On-Site Systems Approval (COSA) based only upon the
representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is
not responsible for errors or omissions in the professional engineer's work.
7. ATTACHMENTS:
COSA Checklist X Nitrate Advisory
Septic System Advisory Arsenic Advisory
Well Flow Advisory Other
COSA Checklist blue sheet
If more than 1 septic system is on the lot:
COSA Checklist# of
Structure served by this system
Certificate of On-Site Systems Approval Checklist
Legal Description: Turnagain Park #2 Lot 2 Block 2 Parcel ID: 018-241-27
A. WELL DATA
Well type Private If A, B, or C provide PWSID# Well Log (Y/N) Y
Date completed 9/17/12 Sanitary seal (Y/N) Y Wires properly protected (Y/N) Y
Total depth 121 ft. Cased to 121 ft. Casing height(above ground) >24 in.
FROM WELL LOG AT INSPECTION
Date of test 9/17/12 10/24/17
Static water level 93 ft. 94 ft.
Well production 15 g.p.m. 5.4 g.p.m.
WATER SAMPLE RESULTS:
Coliform Neg colonies/100 mL Nitrate 0.139 mg/L
Arsenic ND ug/L Date of sample: 9/17/18 Collected by: Forge Engineering
B. SEPTIC/HOLDING TANK DATA
Tank Type/Material Septic/Steel Date installed 8/18/13
Tank size 1250 gal. Number of Compartments 2 Cleanouts (Y/N) Y
Foundation cleanout(Y/N) Y Depression over tank (Y/N) N High water alarm (Y/N) N
Date of pumping 9/22/18 Pumper Sanitary Pumpers
C. ABSORPTION FIELD DATA
Date installed $/17/13 Soil ratingd./ft2 or ft2/bdrm) 1.2 GPD/SF System type
Shallow Trench
@ (g•P• Y YP
Length 2 I ft. Width 5 ft. Gravel below pipe 7 ft.
Total depth 11 ft. Eff. absorption area 504 ft2 Monitoring tube Y Depression over field N
Date of adequacy test 10/24/17 Results (Pass/Fail) Pass For 4 bedrooms
Fluid de th in absor tion field before test 56/62 in. Water added 915 73/68
p p gal. New depth in.
Elapsed Time: 1 440 min. Final fluid depth 56/63 in. Absorption rate >= 600 g p d
None
Any rejuvenation treatment(past 12 mo.) (Y/N &type) If yes, give date
D. LIFT STATION
Date installed Size in gallons Manhole/Access (Y/N)
"Pump on" level at in. "Pump off' level at in. High water alarm level at in.
Datum Cycles tested Meets alarm&circuit requirements?
E. SEPARATION DISTANCES
WELL ON LOT TO:
Septic tank/lift station on lot X100' On adjacent lots >100'
Absorption field on lot 00 On adjacent lots >100
Public sewer main >75' Public sewer manhole/cleanout >100'
Sewer/septic service line >25 Holding tank
Animal containment areas Manure/animal excrete storage areas >100
SEPTIC/HOLDING TANK ON LOT TO:
1* 5'
Building foundation Property line 2'5 Absorption field
Water main
>10' Water service line >10' Surface water >100'
Wells on adjacent lots 100'
ABSORPTION FIELD ON LOT TO:
1*
Property line 2'S Building foundation 10 Water main 10
Water Service line Surface water >100 Driveway, parking/vehicle storage
10'
Curtain drain None Noted Wells on adjacent lots >100'
F. COMMENTS
Waiver OSP121250 for separation distances between tank & field to property line.
G. ENGINEER'S CERTIFICATION
`�t\\\\d
I certify that I have determined through field inspections and OFA .,qlkk
review of Municipal records that the above systems are in �,`P�- -S'
conformance with MOA COSA guidelines in effect on this date. op:
1.--'t-At
Engineer's Printed Name
Benjamin Schiller, PE ' 49 TH �� /
Date 10/2/18 % � "' o
r - Benj mJ Schiller 0
. �
f C 12592 -��
�ck�rl9-.-10/2118 ..��;�.�
�ItiF�PROFESSIO0�4.�
COSA brown sheet 10-10-12.doc
1�`' RAGS 8Lr
• Municipality of Anchorage s
On -Site Water and Wastewater Program
(907) 343-7904
Certificate of On -Site Systems Approval
Parcel I. D. 018-241-27 Expiration Date: "/ hy/,_�'
1. GENERAL INFORMATION
Complete legal description Turnagain Park # 2, Block 2, Lot 2
Location (site address) 14495 Old Seward Highway Anchorage, AK 99514
Current Property owner(s) Tim & Pauline Peters Day phone
Mailing address 2436 Clements Avenue Anchorage, AK 99514
Real Estate Agent Day phone
2. TYPE OF DWELLING:
Q Single Family (w/wo ADU)
❑Duplex SUBMITTAL
[IMultiple Dwellings (Single Family and/or Duplex) OCT 2 9 2014
3. NUMBER OF BEDROOMS: Four
4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL:
Individual Well Q Individual Q
Individual Water Storage ❑ Holding Tank ❑
Community Class Well ❑ Community ❑
Public Water System ❑ Public Sewer ❑
Waiver/Variance request for. Distance:
Received
COSA to be
requested by the engineer.
Date- (P `I -I — IS
COSA Fee $ 80 Waiver Fee $
Date of PaymentO) Wl lq rgrq Date of Payment
Receipt Number 0 G Receipt Number
COSA# ������ Waiver#
5. STATEMENT OF INSPECTION BY ENGINEER
As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation,
based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application,
shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate
for the number of bedrooms and type of structure indicated herein. I further verify that based on the information
obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water
supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes,
ordinances, and regulations in effect at the time of installation.
Name of Firm Anderson Engineering Phone 522-7773
Address P.O. Box 240773 Anchorage, AK 99524
Engineer's Printed Name Michael E. Anderson, P.E. Date 10/29/14
OF 16#
6. DSD SIGNATURE'^••• • 0••' L.. ° ......
System #1 Approved for bedrooms 0 MI I .............
IS°° °°°° °°°
�, MI ° l�E ANOE2SON �_ c>4
System #2 Approved for bedrooms P; sem.,+ CE -4381 ."Z'
09 FqF • ?'0 -7�F t}O•'��
Disapproved0 ROFESS1p4
a
♦ P a
Conditional approval for bedrooms, with the following stipulationsre®®®+®®
By: 19.. 1iv� Peet Original Certificate Date: l^
Th nicipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only
upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality
of Anchorage is not responsible for errors or omissions in the professional engineer's work.
7. ATTACHMENTS:
COSA Checklist X Nitrate Advisory
Septic System Advisory Arsenic Advisory
Well Flow Advisory Other
COSAbluesheet f :+ c
If more than 1 septic system is on the lot:
COSA Checklist #_of
Structure served by this system
Certificate of On -Site Systems Approval Checklist
Legal Description: Turnagain Park # 2, Block 2, Lot 2 parcel ID: 018-241-27
A. WELL DATA
Well type Private If A, B, or C provide PWSID #
Date completed 9-17-12 Sanitary seal (Y/N) Y
Total depth L21 ft. Cased to 121 ft.
FROM WELL LOG
Date of test 9-17-12
Static water level 93
Well production 15
WATER SAMPLE RESULTS:
Coliform colonies/100 mL
Arsenic ND ug/L Date of
B. SEPTIC/HOLDING TANK DATA
Tank Type/Materia,) Septic/Steel
ft.
9
Tank size 1,250 gal. Number of Compartments 2
Foundation cleanout (Y/N) Y Depression over tank (Y/N) N
Date of pumping New Const. Pumper
Well Log (Y/N) Y
Wires properly protected (YIN) Y
Casing height (above ground) >18 in.
AT INSPECTION
ft.
Collected by: Anderson Engrg.
Date installed 8/17/13
Cleanouts (Y/N) Y
High water alarm MN) N
C. ABSORPTI LSD TA
Date iristalle8118/13 oil rating (g.p.d./ftZ or ftZ/bdrm) 1.2 GPD/SF System type Deep Trench
Length 2 ft. Width 3 ft. Gravel below pipe 7 ft.
Total depth 12-13 ft. Eff. absorption area 504 ftZ Monitoring tube Y Depression over field N
Date of adequacy test New Const. Results (Pass/Fail) For _ bedrooms
Fluid depth in absorption field before test in. Water added gal. New depth in.
Elapsed Time: min. Final fluid depth in. Absorption rate >= g.p.d.
Any rejuvenation treatment (past 12 mo.) (Y/N & type) N If yes, give date
D. LIFT STATION No Add On Manhole - Gravity Flow to Absorption Trench.
Date installed
"Pump on" level at in.
Datum
E. SEPARATION DISTANCES
WELL ON LOT TO:
Septic tankAift station on lot
Absorption field on lot
N/A
Public sewer main
Size in gallons
"Pump off" level at
Cycles tested _
>100'
>100'
Sewer /septic service line >25'
Animal containment areas >50'
SEPTIC/HOLDING TANK ON LOT TO:
in.
Manhole/Access (YIN) _
High water alarm level at
Meets alarm & circuit requirements?
On adjacent lots >100'
On adjacent lots 871*
Public sewer manhole/cleanout N/A
Holding tank N/A
Manure/animal excrete storage areas >100'
Building foundation >5 Property line 2.5
**
Water main >10, Water service line >10'
Wells on adjacent lots >100,
ABSORPTION FIELD ON LOT TO:
:
Property line 2.5** Building foundation
Water Service line >10' Surfacewater >100'
Curtain drain None Noted Wells on adjacent lots >100'
Absorption field >51
Surface water >100'
Water main
N/A
Driveway, parking/vehicle storage > 10'
F. COMMENTS
*See Waiver Well to Absorption Trench. **See Lot Line Waiver.
Second Water Sample Taken 6/10/15 - Results Negative for Coliform.
G. ENGINEER'S CERTIFICATION
I certify that I have determined through field inspections and M P,"
review of Municipal records that the above systems are in �G7•^�, g� ,y
conformance with MOA COSA guidelines in effect on this date. i .'E S
�......... W. ,.
Engineer's Printed Name Michael E. Anderson, P.E. j,,,,,,,,, ,,,,,,, .,...
%° MICHAEL E. ANDERSON
Date 6/17/2015 I� mss•,, 4E-4381
,tiIIIII�riFES ''
OOSA brown sheet -1 0-10-1 2.doc
in.