ON-SITE WASTEWATER INSPECTION REPORT
Permit Number: OSP131131 PID Number: 020-311-41 ❑✓ New ❑ Upgrade
Name:
Ronald 8 Rebecca Cotheren
ABSORPTION FIELD
❑ Deep Trench Q Shallow Trench ❑Bed Mound
Address
19701 Villages Scenic Parkway
❑ Other
Phone
Iyumber of Bedrooms
Soil Rating
Total depth from original grade
MSG = it z a_
RV = IPaa- 5
6GPD/SF
+j Ft.
LEGAL DESCRIPTION
Depth to pipe invert from original grade
+1.5 Ft.
Gravel depth beneath pipe
0.5 Ft.
Subdivision Block Lot
Villages View Estates West 2
Fill added above original grade
4.0 Ft.
Gravel length
30.0 Ft.
Township Range Section
Gravel width
5Ft.
Beds: Number of Lines
N/A
Distance between lines
N/A Ft.
SEPARATION DISTANCES
To
Septic
Absorption
Lift Station
Holding
Sewer
Total absorption area
Number of trenches
Dist. between trenches
From
Tank
Field
Tank
Line
150 Ftp
1
N/A Ft.
Well
126.5
271.1
212.3
NIA
125+
TANK ❑ Septic p S.T.E.P. ❑ Holding ❑ Other
Manufacturer
Anchorage Tank / Orenco
Capacity
Surface Water
100+
100+
100+
N/A
00.15ba b%Gt2Gal,
Material f
F Of she
Numberofcompartents
Lot Line
61.7
53.0
61.7
N/A
NA
Advantex Septic
Z 2
Foundation
11.7
337.8
258.0
N/A
LIFT STATION
Manufacturer
Capacity
Curtain Drain
50+
50+
50+
NIA
Orenco
500 Gal.
Remarks
Pump on level at
43 in,
Pump off level at
40 in.
High water alarm at
45 in.
Pump make and model
P2005
Electrical Inspections performed by
MOON
Installer
PIPE MATERIAL House to tank 3034 Tdrainfield n eld 3034
Homeowner
Drainfield 3034 CO/MT 3034
Inspector Pannone Engineering Services
BENCHMARK (Assumed elevation) 100ft
Inspection t" 7/18/13
dates: 2 ° 7/25/13
Location and description
3" 7/29/13 e 9/16/14
Top of House Foundation
COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL
Engineer's Stamp
Zlk��
Conditional Approval: DateOF
•.
g�P.
.T.'
*: Llii
4` Cven onnorae i
CE
Approved Date,
inspection Heporm-1-12.doc
TH-21
RESERVE DRAIN FIELD (P) ' "�f' • I _
,
i 301F X 5'W X 0.5'ED X+10TD.• X53.0• /�L I,
W/ ±3' SAND
INSTALLED NEW DRAIN FIELD
30LF X 5'W X 05ED X +1.0'10
/ W/ t3• SAND � 2 I
M1 -TH-22 I.
' -- SHEER
SHE:
DC3
LS
t
TRUE NORj T3
SCALE 1 -6 NEW 1500g S.T.E.P. TANK
- - _ DC2 W/ AX20 POD
_ INSTALLED DCO AFTER TANK
- AND CO EVERY 50LF
---
MSMM SHED 2y ON LINE TO FIELD
- -- 272.3
3
WELL (E)ci
" F I
WELL (E)
I m
NEW 12508 SEPTIC TANK
y WITH DCO 1-)6.n
B __ - �. OCT
Tl
1 - _p
FC , i I
\ k'� W- W NEN 4 BR A \ I'
XI HOUSE
- (+1 RV DUMP) ---
LEGEND ,_ 4
W WATER LINE/ - WELL RADIUS _ - -
-
SS NEW SEPTIC
NOTES: PAMONE ENG SVC, C, LLC +�
OF A \\i 2/1 /
RECORD DRAWING P.O. BOX 100217 ANCHORAGE, AK 99510 - S'(�• Cgsli1 2 12 201'
PHONE (907) 272-8218 FAX (907) 272-8217 p �9++ Scale
49TH
VILLAGES VIEW ESTATES WEST, LOT 2 "�'�_ 020-311-41
RONALD &REBECCA COTHREN Steven 'R. Pannone PERMIT NO.
VILLAGES SCENIC PARKWAY%Pci lCE 8149 �� OSP131131
PLAN ANCHORAGE, AK ��il`fDy'p Sheet
�� "�� 2OF4
A
B
FC
18.8
-
T1
21.2
43.0
T2
24.7
47.2
DC1
27.1
49.5
C1
115.8
123.4
C2
203.6
204.6
DC2
253.2
254.4
T3
259.6
258.3
LS
269.3
267.0
DC3
278.0
276.0
C4
315.9
308.4
CS
350.8
339.2
M.1
353.5
341.7
C6
372.9
364.2
M2
371.6
363.1
TH-21
RESERVE DRAIN FIELD (P) ' "�f' • I _
,
i 301F X 5'W X 0.5'ED X+10TD.• X53.0• /�L I,
W/ ±3' SAND
INSTALLED NEW DRAIN FIELD
30LF X 5'W X 05ED X +1.0'10
/ W/ t3• SAND � 2 I
M1 -TH-22 I.
' -- SHEER
SHE:
DC3
LS
t
TRUE NORj T3
SCALE 1 -6 NEW 1500g S.T.E.P. TANK
- - _ DC2 W/ AX20 POD
_ INSTALLED DCO AFTER TANK
- AND CO EVERY 50LF
---
MSMM SHED 2y ON LINE TO FIELD
- -- 272.3
3
WELL (E)ci
" F I
WELL (E)
I m
NEW 12508 SEPTIC TANK
y WITH DCO 1-)6.n
B __ - �. OCT
Tl
1 - _p
FC , i I
\ k'� W- W NEN 4 BR A \ I'
XI HOUSE
- (+1 RV DUMP) ---
LEGEND ,_ 4
W WATER LINE/ - WELL RADIUS _ - -
-
SS NEW SEPTIC
NOTES: PAMONE ENG SVC, C, LLC +�
OF A \\i 2/1 /
RECORD DRAWING P.O. BOX 100217 ANCHORAGE, AK 99510 - S'(�• Cgsli1 2 12 201'
PHONE (907) 272-8218 FAX (907) 272-8217 p �9++ Scale
49TH
VILLAGES VIEW ESTATES WEST, LOT 2 "�'�_ 020-311-41
RONALD &REBECCA COTHREN Steven 'R. Pannone PERMIT NO.
VILLAGES SCENIC PARKWAY%Pci lCE 8149 �� OSP131131
PLAN ANCHORAGE, AK ��il`fDy'p Sheet
�� "�� 2OF4
VISIONS TO SPECIR
1. ALL CONSTRUCTION WAS INSTALLED AS SPECIFIED IN THE MOST CURRENT EDITION OF THE MUNICIPALITY OF ANCHORAGE
STANDARD SPECIFICATIONS (MASS) FOR COMPONENT PARTS AND MATERIALS USED IN CONSTRUCTION OF ON—SITE
WASTEWATER DISPOSAL SYSTEMS.
2. SCOPE OF WORK: INSTALLED NEW 12509 SEPTIC TANK, 1500g S.T.E.P. TANK WITH AX20 POD, RV DUMP, AND SOIL
ABSORPTION SYSTEM.
3. GROUNDWATER WAS NOT ENCOUNTERED TO A DEPTH OF 5 FEET BELOW EXISTING GRADE AS EVIDENCED BY THE SOIL
TEST HOLE. AN APPARENT WATER TABLE WAS NOT OBSERVED IN ANY OF THE EXCAVATIONS LESS THAN 5 FEET BELOW
EXISTING GRADE.
RIGID INSULATION
FILTER FABRIC
��
4" 0 PERF PIPES '
DRAIN ROCK 6" ABOVE PIPE
3
6" TS&V—,
FINISH GRADES ",/
34.2
y
PT/
DIP
`DRAIN ROCK
w
RIGID INSI
x �
/ -2.0
a-
6.0 27.3
�'o
a�
DRAIN ROCK 6' ABOVE PIPE
M#
MONITOR TUBE NO.
GM
REMOVED ORGANICS
DCO
DOUBLE CLEAN OUT
z
EXISTING GRADE D
FS
t3' SAND
z
o
BELOW FINISH GRADE
0
OR
w�
¢
U
N
SECTION m=
N
a a
ow
DU
w
U
= U
I
nn
r-1
n
w
om
COPPER
DIP
DUCTILE IRON PIPE
w
RIGID INSI
x �
FOUNDATION CLEAN OUT
a-
FILTER Fi
�'o
a�
DRAIN ROCK 6' ABOVE PIPE
n 4" A PERF P
t3
SEE SECTION & PARAMETERS
PROFILE
DESIGN PARAMETERS
PRIMARY/RESERVE SEPTIC SYSTEM
NO. BEDROOM: 4 (600 gpd)
TANK SIZE: 15009 S.T.E.P.
W/ AX20 POD
PERC RATE = <1 MPI -
SOIL RATING: 6.0 GPD/SF
AREA ROD: 100 SF
SYS. TYPE: WIDE TRENCH 0.5' E.D.
MIN LENGTH: 20 LF
USED:
30 LF X 5' WIDE, 0.5" E.D., +1.0' TD
WITH 3' SAND
TOTAL AREA: 150.0 SF
3
To DRAIN NEW 1500 g 35
FIELD 35.0 S.T.E.P. TANK
WI AX20 POD
ABBREVIATIONS
SEPTIC
CU
COPPER
DIP
DUCTILE IRON PIPE
TH
TEST HOLE
FC
FOUNDATION CLEAN OUT
T#
TANK CLEAN OUT NO.
C#
CLEAN OUT N0.
M#
MONITOR TUBE NO.
R.I.
RIGID INSULATION
DCO
DOUBLE CLEAN OUT
DV
DIVERTER VALVE
FS
FLOW SPLITTER
BFG
BELOW FINISH GRADE
OG
ORIGINAL GRADE
FG
FINISH GRADE
TS&V
TOPSOIL & VEGETATE
NOTES: 7��NN N EN SVC LLC
s�kk Date
RECORD DRAWING P•O BOX 1010217 ANCHORAGE AK 99510 5(F.�F A�.lok 2/12/2015
PHONE (907) 272-8218 FAX (907) 272-8211%g�P Scale
j*: 9TH *l) NTS
... .. ........ P.I.D. NO
VILLAGES VIEW ESTATES WEST, LOT 2 / 020-311-41
RONALD & REBECCA COTHREN Steven Pannone PERMIT N0.
P�_ CE 814 ., ���/ OSPI31131
VILLAGES SCENIC PARKWAY I � -z
DESIGN DETAILS ANCHORAGE, AK +1�iF9fa 5.•.pE � Sheet
0 s 3 OF 4
VE S
TI
"PIPEINV
ATION
RIC
E
DRAINV6" TFINISH GRADE0.5 -
Q EXISTING
P , .
DRAIN ROCKI[6'O 2G
REMOVE ORGAN S� I GM
33' SAND
SECTION
NOTES: PANNONE ENG SVC, LLCoF q ��i Date
RECORD DRAWING Sl , 2/12/2015
P.O.POBOX 100217 ANCHORAGE, AK 99510 �� q
PHONE (907) 272-8218 FAX (907) 272-8211 oe4,- Fy+)/ Scale
*: 49T *II INTO
P.LD. No
VILLAGES VIEW ESTATES WEST, LOT 2 / 020-311-41
RONALD & REBECCA COTHREN / S 'PannoR % PERMIT NO.
VILLAGES SCENIC PARKWAY �jlP�� rC�E 8149 OSP131131 hee
DETAILS ANCHORAGE, AK 1116 �J 'pLE St
l t�� 4 OF 4
On -Site Wastewater Disposal System Permit
Permit Number: OSP131131
Tax Code Number: 02031141000
Work Type: Septic
Permit Effective Dates: July 08, 2013
MUNICIPALITY OF ANCHORAGE
Development Services Department
On -Site Water & Wastewater Program
4700 Elmore Road, PO Box 196650
Anchorage, AK 99519-6650
Telephone: (907) 343-7904
to July 08, 2014
Design Engineer: PANNONE ENGINEERING SERVICE
Subdivision: VILLAGES VIEW ESTATES WEST
Site Legal Address: VILLAGES VIEW ESTATES WEST LT 2 G:3738
OwnerlAddress: COTHREN RONALD & REBECCA
7102 AMBER LN #2 ANCHORAGE AK 995040000
Site Mailing Address: 19701 VILLAGES SCENIC PKWY, Anchorage
This permit is for the construction of:
Y Disposal Field Y Septic Tank N Holding Tank N Privy
Lot Size in Sq Ft: 156380
Total Bedrooms: 5
N Private Well N Water Storage
All construction must be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater
Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80).
3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services
Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either:
A. Open and Close on the same day.
B. Covered, sealed, and heated to prevent freezing.
Received By:
Issued By:
Date: 7/917 i
MUNICIPALITY OF
Community Development Department
Development Services Division
On -Site Water & Wastewater Program
Phone: 907-343-7904
Fax: 907-343-7997
ON-SITE SEWER/WELL PERMIT APPLICATION
Parcell.D. 020-311-41
Property owner(s) Ronald & Rebecca Cothren
Mailing address 7102 Amber Ln #2, Anchorage, AK 99504
Day phone
Site address Villages Scenic Parkway
Legal description (Sub'd., Block & Lot) Villages View Estates West, Lot 2
Legal description (Township, Range & Section)
Lot Size 156,380 Sq. Ft. Number of Bedrooms 4+1
APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING:
69 all that apply)
Absorption Field ❑X Initial 0 Single Family (SF) ❑X
(w/wo ADU)
Septic Tank ❑X Upgrade ElDuplex (D) ❑
Holding Tank E]Renewal ElMultiple Dwellings ❑
Privy ❑ (SF and/or D)
Private Well ❑
Water Storage ❑
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
Distant!. 4s5= -
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
property owner or authorized agent)
Permit/Rush Fees:Q�
Date of Payment:
Receipt Number: dU��
Permit No.SpL3,�13/
Permit App_:
Waiver Fees: 4,2-0c)
Date of Payment: % 3
Receipt Number:
Waiver No. 0 5 P /311 R Z
t
Municipality of Anchorage
P.O. Box 196650 • 4700 Elmore Road
Anchorage Alaska 99519-6650 • (907) 343-7904 • Fax (907) 343-7997
htti)://www.muni.orci/Onsite
Development Services Division
On -Site Water and Wastewater Program
n,enc
sin
z r
n
Department
**** VARIANCE/WAIVER REVIEW ****
Waiver#: OSPI31192 COSA#: Permit#:OSP131131
PID#:020-311-41
Legal Description: Villages View Estates West Lot 2
Engineer: Pannone Engineering Services
Applicant: Ron Cothren
Your request for a waiver of the required 50 feet horizontal separation froTAKe--absoption field
to the excessive slope has been approved. The approved separation dista e is 33:4 fet.
O'per -)9
This waiver approval applies to the proposed absorption field only. Any upgrade to the
on-site wastewater disposal system will require all separation distances be met or another
approval from this department.
❑ The affected adjacent property owner(s) have been given a 7 day notice regarding this
waiver.
❑ Notarized letter(s) of nonobjection have been received from the owner(s) of the affected
adjacent property.
® Adjacent properties are not affected by this waiver.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I
Waiver is Granted: X Waiver is not Granted:
Date: 7 /3 Approved by;���
Name of Reviewer
........................................................ ......................
Rec#: 8453G Amount: $200.00 Date Paid: 7/8113
**** VARIANCEIWAIVER REVIEW ****
Pannone Engineering Services Lac
Steven R. Pannone, Principal
Registered Professional Engineer
E-mail: steve@Dpanengak.com
July 8, 2013
Municipality of Anchorage
Development Services Department
On -Site Water & Wastewater Program
4700 S. Bragaw Street
P. O. Box 196650
Anchorage, Alaska 99519
Subject: Villages View Estates West, Lot 2
Septic System Permit Request
Ladies and Gentlemen:
I am writing to request a permit to install a septic system be issued for this property. The proposed
systems will serve a proposed four (4) bedroom house. The house will be served by a 1250 gallon septic
tank which will discharge into a 1500 gallon S.T.E.P. tank with an AX20 pod near the proposed RV pad and
RV dump station. Currently the lot is undeveloped, with the exception of a driveway and well that were
installed in 2001. This lot is served by a private well that is over 100 feet from the existing and proposed
septic system. The surrounding developed lots are also served by private wells that are located over 100
feet from this system.
1. Soils. Five test holes were excavated by Anderson Engineering in May of 2001, and the ground
water monitored for seven days. Groundwater was not observed in the hole monitor tubes after the
seven day monitoring period to a depth of 5.0 feet during the month of May. Bedrock was encountered
at a depth of 5.0 feet in the test hole. It is my opinion, based on the results of the percolation tests and
overall soils appearance; an application rate of 6 gallons/day/square feet should be used for a Cat III
wastewater system, and an application rate of 1 gallon/day/square feet should be used for the
conventional system for the RV dump station.
2. Soil Absorption System Design.
a. See Sheet 2 of the design package.
3. Surface Water: There is no surface water within 100 feet of the proposed septic tank and drain
field. The proposed drain field upgrade will maintain at least 100 feet from all surface water and drainage
ditches.
4. Topography: The topography slopes from east to west at approximately 20% in the area of the
proposed drain field with a slope of approximately 25% that begins 40 — 50 feet below the drain field.
Mailing: P.O. Box 100217, Anchorage, AK 99510-0217
Physical: 332 East Manor, Anchorage, AK 99501
Telephone: (907) 272-8213 FAX: (907) 272-8211
Page 2 of 2
There is a slope of approximately 25%-30% that begins a
See waiver request.
5. Waiver Request: There is a slope of approximately 25%-30° ha'
east of the reserve field. When the reserve field is built fill will be placec
of 4:1 for a distance of 50' from the field to prevent the potential for effI
sheet 4 of 4). 1 request a waiver to the minimum distance from a slope e
to the east of the reserve
begins approximately32_%.to e
d"nhill from the field a slope
enj to daylight (see sqefion on
cee ' % e possible
future construction of the reserve field. Granting this waiver will not affect the health or safety of this lot
or surrounding lots now or in the future.
6. Drawing Markings: The Drawings are marked "For MoA Review Only". When written notification
that the review is complete and that there are no further comments is received from MoA On -Site
Department, the note will be removed and "Issued for Construction" drawings will be issued.
The proposed installation will not affect the future development of the surrounding or existing lots. There
are no wells or septic systems within 100 feet of the proposed septic location.
If you have any questions or concerns, please contact me at 272-8218.
Sincerely,
Steven R. Pannone, P.E.
Owner/Civil Engineer
Attachments
-Soils Log
-Septic System Design
Mailing: P.O. Box 1007217, Anchorage, AK 99510-0217
Physical: 332 East Manor Ave, Anchorage, AK 99501.
Telephone: (907) 272-8218 FAX: (907) 272-8211
MLJ1 NORTH
TH-21
j
RESERVE DRAIN FIELD (P) -
3OLF X 5'W X 0.5•ED X +1.0'TD /
W/ f3SAND / 85.8 - ;H-22 j
DRAIN FIELD (P)
MILE X 5'W X 0.5'ED X +1.0'TD /
202.3
M —M n
1�
M
h
/M 41 _. 1500g S.T.E.P. TANK (P)
_ ? W/ AX20 POD
213.4 INSTALL DCO AFTER TANK
oRIVEWAr AND CO EVERY 50LF
ON LINE TO FIELD
-- NO EXCESSIVE SLOPES
- _ AT DRIVEWAY
WELL (E)�
3 11
\ WELL (E)
n
231.0
w
v w w—*E
I,
LEGEND1250g SEPTIC TANK (P)
INSTALL DCO AFTER TANK
W WATER LINE - AND CO EVERY 50LF ON LINE - 4 BR -- - -
WELL RADIUS HOUSE (P)
SS NEW SEPTIC -
NOTES: PANNONE ENG SVC, LLC of a V� Date
FOR CONSTRUCTION P.O. BOX 100217 ANCHORAGE, AK 99510 ��• 4sll� 5/28/2013
PHONE (907) 272-8218 FAX (907) 272-8211 /�g�Qy+r Scale
j *: 49 r•=so'
.... .... .... P.I.D. NO
VILLAGES VIEW ESTATES WEST, LOT 2=. .. ... 20-311-41
RONALD & REBECCA COTHREN Steven R. PaJ.nnone PERMIT No.
VILLAGES SCENIC PARKWAY �����s. CE 8149� osP131131
PLAN ANCHORAGE, AK �1ll FROFES"-� � .......Sheet
hIeOF 4
SPECIAL PROVISIONS TO SPECIFICATIONS
1. ALL CONSTRUCTION SHALL BE INSTALLED AS SPECIFIED IN THE MOST CURRENT EDITION OF THE MUNICIPALITY OF
ANCHORAGE STANDARD SPECIFICATIONS (MASS) FOR COMPONENT PARTS AND MATERIALS USED IN CONSTRUCTION OF
ON—SITE WASTEWATER DISPOSAL SYSTEMS.
2. SCOPE OF WORK: INSTALL NEW 1250g SEPTIC TANK, 15009 S.T.E.P. TANK WITH AX20 POD, RV DUMP, AND SOIL
ABSORPTION SYSTEM.
3. GROUNDWATER WAS NOT ENCOUNTERED TO A DEPTH OF 5 FEET BELOW EXISTING GRADE AS EVIDENCED BY THE SOIL
TEST HOLE, IF AN APPARENT WATER TABLE IS OBSERVED IN ANY OF THE EXCAVATIONS LESS THAN 5 FEET BELOW
EXISTING GRADE NOTIFY THE ENGINEER IMMEDIATELY.
RIGID INSULATION
FILTER FABRIC
4" 0 PERF PIPE—�
DRAIN ROCK 6" ABOVE PIPE
3
6" TS&V' 1 ��
FINISH
/PT/ L�`-DRAIN ROCK
20 60
SEE SECTION &PARAMETERS
W
om
PROFILE
MGM REMOVE ORGANICS
'z"�
RIGID INSULATION
z
t3' SAND j
EXISTING GRADE -50
o
?
0
BR wo
a
o
t.0
SECTION o�
�o
T# TANK CLEAN OUT NO.
o
OU
L?
L
U
o i„
W
om
SEE SECTION &PARAMETERS
W
om
PROFILE
IUI 4.0
'z"�
RIGID INSULATION
w�
TO INT 15008 S.T. E.P.
�z
FILTER FABRIC
az
NO. BEDROOM: 4 (600 gpd)
OF FIELD TANK (P) W!
t.0
DRAIN ROCK 6" ABOVE PIPE IN
�o
T# TANK CLEAN OUT NO.
AX20 POD
¢z
SOIL RATING: GPD/SF
¢�
AREA ROD: 1000 SF
z
SYS. TYPE: WIDE TRENCH 0.5' E.D.
4" 0 PERF PIPE
MIN LENGTH: 20 LF
DCO DOUBLE CLEAN OUT
DV DIVERTER VALVE
USE:
FS FLOW SPLITTER
30 LF X 5' WIDE, 0.5' E.D., +1.0' TD
YD'o I oollo
WITH 3' SAND
OG ORIGINAL GRADE
TOTAL AREA: 150.0 SF
FG FINISH GRADE
TO ADVANTEX 125 g
SEE SECTION &PARAMETERS
SEPTIC
PROFILE
TANK(P)
ABBREVIATIONS
DESIGN PARAMETERS
CU COPPER
PRIMARY/RESERVE SEPTIC SYSTEM
DIP DUCTILE IRON PIPE
NO. BEDROOM: 4 (600 gpd)
TH TEST HOLE
TANK SIZE: 1500g S.T.E.P.
FC FOUNDATION CLEAN OUT
W/ AX20 POD
T# TANK CLEAN OUT NO.
PERC RATE _ <1 MPI
SOIL RATING: GPD/SF
C$ CLEAN OUT N0.
AREA ROD: 1000 SF
M# MONITOR TUBE NO.
SYS. TYPE: WIDE TRENCH 0.5' E.D.
R. 1. RIGID INSULATION
MIN LENGTH: 20 LF
DCO DOUBLE CLEAN OUT
DV DIVERTER VALVE
USE:
FS FLOW SPLITTER
30 LF X 5' WIDE, 0.5' E.D., +1.0' TD
BEG BELOW FINISH GRADE
WITH 3' SAND
OG ORIGINAL GRADE
TOTAL AREA: 150.0 SF
FG FINISH GRADE
TS&V TOPSOIL & VEGETATE
NOTES:
PAMN EN
P.O BOX 1j010217 ANC ANCHORAGE, 9950
PHONE (907) 272-8218 FAX (907) 272-8211
����
���F.A�q\s�l�
/�GU�p9'`
/,t:49TH
... . ?.. .:..
D/8/2013
FOR CONSTRUCTION
Scale
NTS
P.I.D. NO
VILLAGES VIEW ESTATES WEST, LOT 2
RONALD & REBECCA COTHREN
S'te've'n 'R"Pannone'%PERMIT
020-311-41
NO.
VILLAGES SCENIC PARKWAY
I �P�c� CE 8149 ..��
I
OSP131131
DESIGN DETAILS
ANCHORAGE, AK
_
`l>t�OESSiOP�
Sheet
`�\
2 OF 4
4" JIM
4" PUMP -
SLIDE SEC]
OF 6" F
OVER THIS CONNECT
TO PRO\
SHEER PROTECTILI.-
EXTEND TO
BRIDGE EXCAVATION
ADVANTEX DESIGN
ADVANTEX
FOOT VALVE
DRAIN COVER rSLOPE BASIN
TO DRAIN
PUMP
BASIN NOT
PASSIVE
AIR
VENT
716
1500
GALLON
ANCHORAGE
TANK
RV DUMP STATION
FOOT
& FINISH
GRADE
CON(
DUMP
CONNECTTO
4' SEWER LINE
NOTES:
PAMONE ENG SVC LLC
��
P.O. BOX 100217 ANCHORAGE, AK 99510
PHONE (907) 272-8218 FAX (907) 272-8211
��F A \\k
O
r • �qs��1
* `49 �y*f1l
' 'S'te've'n'R. Pa'nnone'AV
CE 8149
5149 .��
It
�i\ FOROFI .... � �
i\�'\ S9
Date
6/zs/zo13
FOR CONSTRUCTION
Scale
INTS
P.I.D. NO
020-311-41
PERMIT NO.
OSP131131
VILLAGES VIEW ESTATES WEST, LOT 2
RONALD & REBECCA COTHREN
VILLAGES SCENIC PARKWAY
ANCHORAGE, AK
DETAILS
Sheet
3 OF 4
NOTES:
FOR CONSTRUCTION
DETAILS
RESERVE SYSTEM SECTION
FINISH
EXISTING
RIGID IN
FILTER
4" 4 PERF
DRAIN ROCK 6" ABOVE PIPE INV
6"TS&V 4
1 �
0.5
DRAIN ROCK
REMOVE ORGANICS
t3" SAND
PAMONE ENG SVC, LLC
P.O. BOX 100217 ANCHORAGE, AK 99510
PHONE (907) 272-8218 FAX (907) 272-8211
VILLAGES VIEW ESTATES WEST, LOT 2
RONALD & REBECCA COTHREN
VILLAGES SCENIC PARKWAY
ANCHORAGE, AN
-5.0
SECTION
GM
.. HLgsli�
6/28/2013
i��P''•
Scale
--49 TH •*��
INTO
...`—,.. �.... �.. .:..
P.I.D. NO
Steven R. •Pannone j
20-311-41
(9Fc. CE 8149
S r
PERMIT NO.
OSP131131
I�1��RZOFESSION�'�
SheetS,
\\\\����
aOF 4
ooOF At like
ow���rZ
.� 4911•
Munlcipality of Anchorage
Department of Health & Human Services
825 L Street, Anchorage, AK 99502-0650
SOILS LOG - PERCOLATION TEST
Performed For: Kin Shaw Date Performed
Legal Description: tot 2. Mllag -s View West Subdivision
SLOPE SITE P
1 PTIOL
GP
Bedrock
Was Groundwater
9 Encountered? No
If Yes, What Depth?
10 Depth to Water
After Monitoring None
11 Date: 5117/01
sem'. MICHAEL F. ANDERSCN;Q
��•i •.
CE .4381
r411ttil PROFESSlOOFo�♦
See Site Plan
Perc. Rate: >1 MinAnch Perc. Hole Diameter: 6'
Test Run Between 5 Fl. and 6 Ft.
Comments: Percolation Cavity Presoaked Prior to Testing. Water Absorbed Immediately.
Performed By: Alan Harnts I, Michael E. Anderson Certify That This Test Was Performed
In Accordance With All State and Municipal Guidelines In Effect On This Date: 6125101
Municipality of Anchorage
Department of Health & Human Services
825 L Street, Anchorage, AK 99502-0650
SOILS LOG - PERCOLATION TEST
Performed For: Kin Shaw Date Performed:
Legal Description: Lot 2. Viling .s View West Subdivision
SLOPE SITE P
PTfOL
GM
TESTHOLE NO, 22
Some Silt
Bedrock
Was Groundwater
9 Encountered? No
If Yes, What Depth?
10 Depth to Water
After Monitoring None
11 Date: 5/17101
14
15
Reading
49D
4EL E. ANDERSCN o W ,
CE -4381 ;:�`�',
See Site Plan
Perc. Rate: >1 Min./Inch Perc. Hole Diameter: 6"
Test Run Between 5 Ft. and 6 Ft.
Comments: Percolation Cavity Presoaked Prior to Testing. Water Absorbed Immediately.
Performed By: Alan Harala. I, Michael E. Anderson Certify That This Test Was Performed
In Accordance With All State and Municipal Guidelines In Effect On This Date: 6125101
Ronald G. Cothren
7102 Ambler Ln, #2
Anchorage, AK 99504
cell: 570-8232
July 18, 2013
RE: Permit # OSP131131 for Water and Wastewater
MOA, Development Services Division
Water and Wastewater Department
Dear Deb,
Steve Pannone, P.E. advised me to send a letter to the MOA regarding my construction
experience related to sewer systems. He advised this as I would like to complete the
construction for my sewer system for our new home at 19701 Villages Scenic Parkway.
Steve Pannone, P.E. will also be supervising the installation of the system and calling for
an inspection by MOA staff at the appropriate time.
Although my professional license is as a Registered Land Surveyor in Alaska, my college
background includes as BS in Civil Engineering Technology from Oregon Institute of
Technology and a Masters Degree in Civil Engineering from Oregon State University. In
20011 retired after teaching 20 years in the School of Engineering at UAA. During my
tenure at UAA, I worked during the summers performing civil engineering design for
DOWL Engineers, High and Phukan Engineering, and the US Army Corps of Engineers.
After retiring from UAA in 2001, I completed engineering design and geomatic work for
Michael Foster Engineering until 2008. This work included design and construction
management of a sewage lagoon in Glennallen, Alaska and water and wastewater systems
in various locations in Alaska.
I believe that with my experience and with the oversight of Steve Pannone, P.E. that the
waste water system for our new home will be installed in a responsible and professional
manner, meeting all code specifications required.
Thank you for this opportunity to solicit approval from the MOA to install the waste
water system for my home. With this approval, I will be present at all times during the
installation work. No monies will be paid to another person for the installation of the
wastewater system on Lot 2, Villages View Estates West.
R2Respectfully,
- r,�'P/ o .
Ronald G. Cothren
ADVANCED WASTEWATER TREATMENT SYSTEM
MAINTENANCE AND REPAIR AGREEMENT
BETWEEN MUNICIPALITY OF ANCHORAGE
AND CoNALW (!�,_ CO ThF{E�/
THIS MAINTENANCE AND REPAIR AGREEMENT made and entered into as of this
26 of 2013, by and between '1 oNALY) 6.
herein the "OWNER," and the Municipality of Anchorage, herein the
"MUNICIPALITY." In consideration of the mutual covenants contained herein, the
parties to this Maintenance and Repair Agreement agree as follows:
1. Advanced Wastewater Treatment Systems. Municipality grants permission to
Owner to utilize and operate an Advanced Wastewater Treatment System
(AWWTS), described as
located at (legal description).
V, ! I aGyzs V, ,EH1-'�S'4`�,4—eS �l%Xt- L-o� Z
i
2. Definitions.
Alteration. Any change to the design or function of an ANVWTS that
includes the installation or removal of any parts, components or pieces not
included in the original construction permit and design.
Certificate of On -Site Systems Approval (COSA). An approval by the
Municipality of existing water and wastewater disposal systems given at
the time of property sale and title transfer in accordance with Anchorage
Municipal Code (hereinafter, "AMC") 15.65. These approvals certify that
the systems are adequate for the homes that they support and meet the
codes that were in place at the time of system construction.
Damage. Any man-made or natural change in a system that would inhibit
the system from performing as designed.
Maintenance and Repair. The scheduled and as needed replacement of
existing parts, components and pieces of an AWWTS that were included
in the original design which would allow the AWWTS to continue to
perform as designed.
Permit. An On -S ite Wastewater Disposal Permit as required by AMC
15.65 to construct and operate an AWRrf S.
3. Term. The term of this Maintenance and Repair Agreement shall begin on the
date of approval by the Municipality to operate the installed system or issuance of a
COSA, and shall continue while the ANVWTS is in use or is operational or until the
property is sold or title is transferred by the owner and a new COSA is issued to the
new owner or transferee of the property.
4. Alterations, Installation and Removal of Additional Enuipment. Prior to
performing any alterations to an AWWTS, the owner agrees to obtain an On-site
Wastewater Disposal Permit from the Municipality in accordance with AMC 15.65.
5. Maintenance and Repairs.
A. Throughout the tenn of this Maintenance and Repair Agreement, the Owner shall
maintain theirAWLVTS in a satisfactory condition capable of producing treated
septic effluent in accordance with the equipment's approval for operation in the
Municipality. The owner shall enter into a service agreement with an AW WTS
service and maintenance provider approved by the municipality and the
manufacturer of the AWWTS for the entire term of the AWWTS. In addition, it
shall be the responsibility of the Owner during the term of this Maintenance and
Repair Agreement, and any renewals thereof, at the owner's sole expense, to pay
for any and all: (1) repair(s), (2) maintenance, (3) adjustment(s), (4) replacement
costs, and (5) inspection costs.
B. Owner agrees to comply with all applicable ordinance, laws, regulations, rules
and orders for the AWWTS.
C. Upon request by the Municipality, the owner agrees to provide the Municipality a
written schedule of routine maintenance and repairs which have been performed
on the system. When a record of maintenance is documented and maintained by
the system vendor, the owner agrees to allow the Municipality access to this
information.
D. Owner acknowledges that the fine for failing to maintain and repair an AWWTS
may be assessed in accordance with AMC 14.60 for improper discharge.
E. Owner agrees that only maintenance and repair personnel approved by the
Municipality will inspect and make any necessary maintenance, repairs or
permitted alterations to the system.
F. Owner agrees to grant the Municipality reasonable access to test and inspect the
AWWTS upon 24 hours written notice.
G. Owner agrees that any sale or transfer of title of the property will not occur
without a new Certificate of On -Site Systems Approval.
H. Owner agrees that the AWWTS installation and maintenance requirements as
provided by the AW WTS vendor/installer and approved by the Municipality are
the governing guidelines for the construction, maintenance and repair of the
Owner's AWWTS.
6. N onwaiver. The failure of either party at any time to enforce a provision of this
Maintenance and Repair Agreement shall in no way constitute a waiver of the
provisions, nor in any way affect the validity of the Maintenance and Repair
Agreement or any part hereof, or the right of such party thereafter to enforce each and
every provision hereof.
7. Amendment.
A. This Maintenance and Repair Agreement shall only be amended, modified or
changed by a writing, executed by authorized representatives of the parties, with
the same formality that this Maintenance and Repair Agreement was executed
with, and such writing shall be attached to this Maintenance and Repair
Agreement as an amendment.
B. For the purposes of any amendment modification or change to the terms and
conditions of this agreement, the only authorized representatives of the parties
are:
a. Owner: rd NA Lb 6 , C e �4t
b. Municipality: Directorr.Community Development or designated authority
C. Any attempt to amend, modify, or change this contract by either an unauthorized
representative or unauthorized means shall be void.
8. Jurisdiction: Choice of Law. Any civil action arising from this Maintenance
and Repair Agreement shall be brought in the Superior Court for the Third Judicial
District of the State of Alaska at Anchorage. The laws of the State of Alaska shall
govern the rights and obligations of the parties under this Maintenance and Repair
Agreement.
9. Severability. Any provisions of this Maintenance and Repair Agreement decreed
invalid by a court of competent jurisdiction shall not invalidate the remaining
provisions of the Maintenance and Repair Agreement.
OWNER: yy�� / J
By: f 11J- 666`1 � i'c'-- (signature) Date:
CJN/* A-V) G CoT-ti--/2=N (print name)
STATE OT ALASKA )
) ss.
THIRD JUDICIAL DISTRICT )
The foregoing instrument was acknowledged before me this )sw day of
205,byhz;1a
NOTARY PUBLIC FOR ALASKA
My Commission expires: _fir i "i<
MUNICIPALITY:
��11
/i
By: to., (signature)
Deb Z y 5 (print name)
STATE OF ALASKA .
NOTARY PUBLIC
Sheila Collins
My Commission Expires:
Date: 7 l
Title: l_
D
F
L.
r
r.
r
0
F
r
r
F
o Well Owwer.
Job No.: 01-202
rem h NO- MOWN
IN0jM No.: N/A
M -W trilling, Inc.
0.0. Box 110378 *Anchorage, AK 99511•
•907-345-4000 ♦ 907-3415-3287 Fox•
Groundwater Well As -Built A Lop
Shaw, Kln 4Use OfWen: Domestic
of 2. ViUstes View Subdivision Treat IB
Constracdon
oHokDgM: 361' ♦CeshrrShe: 6" o{'ered ro: 47.1' #Alamtld: A 53 Stml
o"MNAod: Air ltot+ry
Pelf.
•Wdl Cawpletlpn• open end x Semew ^ PedbraW Mahod:
♦Serew✓Perforotlow defer"Nbw:
4 CroxiNota: 10" bole drilled to "%6" Coins run to 43.8' mod moulus trcmie Vw and wttb
most cement to surke.
♦W4aDerAop vmp McOod: Airstnge Nola:
4Sm* wear krd (Swl) +1 (♦bowel Ns&W'J top efCa t (MCA
♦WellykldkWal 2 sdlowspdmbare(GPAIJ/se/kweyerAo+i(6Ptgfw 2 Avers
wk1 100% ofdmwdown(DD)It"2kfkkwl(SWL).
#MesAod: Air lift
•nese#fCmxpWArn: 160ember2001 • PUNT lwsNll:
w.n t r.
Deptb In het fYrom
to otusle
Det+Us of ferm+tio+f +etnt fiu et m+leri+ eobr++d herd+nf,
0
TO
3
Casing stickup
3
TO
5
Clay: brown silty
5
TO
15
Boulder vel: brown, Vey SiLtyLcla
15
TO
-.24
Bedrock: broken/weathered, brown clay mixed in
24
TO
193
Bedrock: siltstone/ cla stone Njillitc, blue -black, competent/ hard.
TO
no detectable water
193
TO
199
As above: reddish streak very small water sea
199
TO
368
Bedrock_ as above: blue -black, small water sins radic fractures
TO
TO
TO�
TO
TO
TO.___........____
TO
_
MUNICIPALITY OF ANCHORAGE
Development Services Department
On -Site Water & Wastewater Program
4700 South Bragaw Street
P.O. Box 196650, Anchorage, AK 99519-6650
(907) 343-7904
ON-SITE WATER SUPPLY PERMIT
Initial
Permit Number: SWO10400
Legal Description: VILLAGES VIEW ESTATES TR 1 B
Design Engineer: 0014 Anderson Engineering
Owner Name: Kin Shaw
Owner Address: PO Box 110637
Anchorage , AK e955t5=6555
�i01sI 1— 0 's 7
Date Issued: Sep 27, 2001
Expiration Date: Sep 27, 2002
Parcel ID: 020-311-38
Site Address:
Lot Size: 844149 SQ. FT.
Total Bedrooms: 0 Permit Bedrooms: 0
This permit is for the construction of:
❑ Disposal Field ❑ Septic Tank Holding Tank ❑ Privy
All construction must be in accordance with:
1. The attached approved design.
❑,/ Private Well ❑ Water Storage
2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations ( 18AAC80 ).
3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling
(907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only ).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
must be either: A. Open and closed on the same day.
B. Covered, sealed, and heated to prevent freezing.
5. The following special provisions.
WHEN THE WELL HAS BEEN COMPLETED AND SATISFACTORY WATER PRODUCTION IS DETERMINED,
THE WELL DRILLER SHALL PUT AN APPROVED SANITARY SEAL ON THE WELL HEAD AND NO PITILESS
ADAPTER OR PUMP SHALL BE INSTALLED UNTIL AN APPROVED WASTEWATER DISPOSAL SYSTEM HAS
BEEN CONSTRUCTED.
THIS PERMIT FOR WATER WELL NUMBER 1
Received By:
Issued By:
Date:
Date: J_ 2 7-0/
DATE: September 24, 2001
TO: Dan Roth
FROM: Mike Anderson, P.E.
SUBJECT: Tract 1B, Villages View Estates Subdivision
Proposed Subdivision
The owner of Tract 1 B, Villages View Estates Subdivision is attempting to subdivide the
property into 4 lots. A condition of plat approval is providing evidence of water
availability. We are therefore requesting to place 3 wells on the property at the
locations shown on the attached drawings. If the wells are found to be sufficient, they
will be used to served homes to be constructed on the lots in the future.
Please review the attached drawings and issue the permits so the wells can be placed
on the tract. Let me know if additional information is required.
Municipality of Anchorage
® Development Services Department
Building Safety Division
On -Site Water and Wastewater Program
4700 South Bragaw St.
P.O. Box 196650 Anchorage, AK 99519-6650
www.ci.anchorage.ak.us
(907) 343-7904
ON-SITE SEWER/WELL PERMIT APPLICATION
FOR A SINGLE FAMILY DWELLING
Parcel I.D. 020-311-38 Permit Number SW 0I0W0
Property owner(s) Kin Shaw Day phone 345-9617
Mailing address (1) P.O. Box 110637 Anchorage, AK 99511
Mailing address (2) Zip Code
Legal description (Lot, Block & Sub'd.) Tract 1 B, Villages View Estates ( Well No. 1 )
Legal description (Section, Township & Range)
Lot Size 844,149 SF Acres/Sq.Ft. Number of Bedrooms
THIS APPLICATION IS FOR:
Sewer Only ❑ Well Only
Sewer and Well ❑ Water Storage ❑
Sewer Upgrade ❑
THIS PROPERTY CONTAINS:
Hot Tub ❑ Jacuzzi ❑
Swimming Pool ❑ Water Softening Unit ❑
Therapy Pool ❑
I certify that the above information is correct. I further certify that this application is being made for a
Single Family Dwelling and is in accordance with applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit Fees: Waiver Fees:
Date of Payment:g9 f Date of Payment:
Receipt Number: f �' Receipt Number:
(Rev. 12/00)
SCALE 1" = 200'
Parcel I.D. 020-311-41
Municipality of Anchorage EL `
On -Site Water and Wastewater Program
(907) 343-7904
Certificate of On -Site Systems Approval
Expiration Dater
1. GENERAL INFORMATION
Complete legal description
Villages View Est. West, Lot 2
Location (site address) 19701 Villages Scenic Parkway
Current Property owner(s) Ronald & Rebecca Cothren Day phone
Mailing address
Real Estate Agent
19701 Villages Scenic Parkway. Anchorage, AK 99516
2. TYPE OF DWELLING:
Fx1 Single Family (w/wo ADU)
❑ Duplex
❑ Multiple Dwellings (Single Family and/or Duplex)
Day phone
3. NUMBER OF BEDROOMS:
4+1 RV
4. TYPE OF WATER SUPPLY:
TYPE OF WASTEWATER DISPOSAL:
Individual Well
F
Individual
El
Individual Water Storage
❑
Holding Tank
❑
Community Class Well
❑
Community
❑
Public Water System
❑
Public Sewer
❑
Waiver/Variance
Received by: \ 1 II k V" Date: g q ! 2� S
COSA to be released to the en ner, unless otherwise requested by the engineer.
COSA Fee $ L Waiver Fee $
Date of Payment n 7 �h�/ Date of Payment
Receipt Number /���Vls Receipt Number
COSA # �� / ���y Waiver #
5. STATEMENT OF INSP'-,TION BY ENGINEER
As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined
in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater
disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that
based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply
and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at
the time of installation.
In conducting an adequacy test, I attempt to provide a thorough, conscientious engineering analysis of the system in accordance with MoA COSA
guidelines and regulations. The reported results describe the performance of the system under the conditions encountered at the time of the test,
and separation distances measured to readily identifiable features. The operational life of all wells and septic systems depend on the local soil
condition, ground water levels that may fluctuate during the year, and the water usage of the family being served by the system. These conditions
are outside the control of the evaluator of this system. All systems eventually fail and satisfactory test results do not guarantee future
performance of the system, nor do they guarantee that there are no hidden defects or encroachments. Therefore we cannot provide any warranty
for future performance, nor can we estimate remaining life of the system. The content of this report is for the sole benefit of the owner listed
above.
Name of Firm Pannone Engineering Services LLC Phone (907) 272-8218
Address P.O. Box 100217, Anchorage Ak. 99510
Engineer's Printed Name Steven R Pannone Date 2/2/2015
6. DSD SIGNATURE 7 �V X •"'
_L,L� System #1 Approved for S bedrooms R. FSan ore ""
CE -8149
System #2 Approved for bedrooms �¢�s• y ?�,.,r
Disapproved
Conditional approval for bedrooms, with the following stipulations:
Original Certificate
The/Muriicipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only
upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality
of Anchorage is not responsible for errors or omissions in the professional engineer's work.
ATTACHMENTS:
COSA Checklist X
Septic System Advisory
Well Flow Advisory
COSA blue sheet 5 ..
Nitrate Advisory
Arsenic Advisory
Other
If more the AS system is on the lot:
COSA Checklist # + of +
Structure served by this system +
Certificate of On -Site Systems Approval Checklist
Legal Description: Villages View Est. West, Lot 2 Parcel ID: 020-311-41
A. WELL DATA
Well type Private If A, B, or C provide PWSID #
8/16/2001 Y
Well Log (YIN) Y
Date completed Sanitary seal (Y/N) _ Wires properly protected (YIN)
Y
Total depth 368 ft. Cased to 43.8 ft. Casing height (above ground) 18+ in.
Date of test
Static water level
Well production
FROM WELL LOG'
8/16/2001
1
L
AT INSPECT1614
ft. ft.
g.p.m. Z. Z
WATER SAMPLE RESULTS:
Coliform Neg colonies/100 mL Nitrate 0129 mg/L
Arsenic ND ug/L Date of sample: 1/14/2015 Collected by:
B. SEPTIC/HOLDING TANK DATA
PES
Tank Type/Material Septic/Steel & Advantex/Fiberglass Date installed 7/18/2013
1 250+1,5oo ADv 4 Y
Tank size gal. Number of Compartments _ Gleanouts (YIN)
Foundation cleanout (Y/N) Y Depression over tank (YIN) N High water alarm (Y/N) Y
Date of pumping New Pumper
C. ABSORPTION FIELD DATA
7/29/2013 6 GPD/SF Mounded Shallow Trench
Date installed ,Soil rating (g.p.d./ftz or ftzlbdrm) System type
Length 30 ft. Width 5 ft. Gravel belovy, pipe 0.5 ft.
Total depth 3 ft. Eff. absorption area 150 ftz Monitoring tube Y Depression over field N
Date of adequacy test New Results (Pass/Fail) For 4+'Rv bedrooms
Fluid depth in absorption field before test. New . in. Water added New gal. New depth New in.
Elapsed Time: New. min.. Final fluid depth New in. Absorption rate >= N/A g.p.d.
Any rejuvenation treatment (past 12 mo.) (Y/N & type) No If yes, give date
0
D. LIFTSTATION
Date installed 7/18/2013
"Pu—mp on" level at 43 in.
Datum Bottom of Tank
E. SEPARATION DISTANCES
WELL ON LOT TO:
Size in gallons 500
"Pump off"level at 40
Cycles tested New
Septic tank/lift station on lot 100+
Absorption field on lot 100+
Public sewer main 75+
Sewer /septic service line 25+
Animal containment areas 50+
in.
O
0
Manhole/Access (Y/N) Y
High water alarm level at 45
Meets alarm & circuit requirements? Yes
On adjacent lots 100+
On adjacent lots 100+
Public sewer manhole/cleanout 100+
+folding tank 100+
Manure/animal excrete storage areas 100+
SEPTIC/HOLDING TANK ON LOT TO:
Building foundation 5+ Property line 5+ Absorption field 5+
Water main 10+ Water service line 10+ Surface water 100+
Wells on adjacent lots 100+
ABSORPTION FIELD ON LOT TO:
Property line 10+ Building foundation 10+ Water main 10+
Water Service line 10+ Surface water 100+ Driveway, parking/vehicle storage 10+
Curtain drain 50+ Wells on adjacent lots 100+
F. COMMENTS
*Field to slope waiver for 35 feet on file. WR#OSP131192
G. ENGINEER'S CERTIFICATION
,,Zl certify that f have determined through, field inspections and
review of Municipal records that the above systems are in
conformance with MOA COSA guidelines in effect on this date.
Engineer's Printed Name Steven R. Pannone
Date
COSA brown sheet 10-10-12.doc
2/2/2015
in.