Permit Number: OSP121059
Tax Code Number: 01513226000
Work Type: WellSeptic
Permit Effective Dates: April 25, 2012
On-Site Water & Wastewater System Permit
MUNICIPALITY OF ANCHORAGE
Development Services Department
On-Site Water & Wastewater Program
4700 Elmore Road, PO Box 196650
Anchorage, AK 99519-6650
Telephone: (907) 343-7904
Initial
to April 25, 2013
Dep}wtment
Design Engineer: ANDERSON ENGINEERING
Subdivision: KASILOF HILLS
Site LegalAddress: KASILOF HILLS BLK 7 LT 21 G:2541
Owner/Address: GARDNER LESLIE D 50% &
REDFIELD KLISTA M 50% PMB 177 PO BOX 219 DUVALL WA 980190219
Lot Size in Sq Ft: 47281
Total Bedrooms: 4
Site Mailing Address: 10041 STROGANOF DR, Anchorage
This permit is for the construction of:
Y Disposal Field Y Septic Tank N Holding Tank N Pdvy Y Private Well N Water Storage
All construction must be in accordance with: 1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater
Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80).
3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services
Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours).
4. From October 15 to April 15, a subsurface soil absorption system under construction dudng freezing weather must either:
A. Open and Close on the same day.
B. Covered, sealed, and heated to prevent freezing.
MUNICIPALITY OF ANCHORAGE
Community Development Department
Development Services Division
On-Site Water & Wastewater Program
Mayor Dan Sullivan
Phone: 907-343-7904
Fax:907-343-7997
ON-SITE SEWERNVELL PERMIT APPLICATION
FOR A SINGLE FAMILY DWELLING
Parcel I.D. 015-t32-26
Property owner(s): Crown Pointe, Inc. Day phone: 229-1886
Mailing address: P,O, Box 112313 Anchorage, AK 99511
Site address: Kasilof Blvd. at Stroganof Drive Anchorage, AK 99516
Legal description (Sub'd., Block & Lot): Kasilof Hills, Block 7, Lot 21
Legal description (Township, Range & Section)
Lot Size: 47,28t Sq. Ft. Number of Bedrooms: Four (4)
THIS APPLICATION IS FOR:
([~ all that apply)
Absorption Field X
Septic Tank X
Holding Tank []
Privy []
Private Well X
Water Storage []
THIS APPLICATION IS AN:
Initial X
Upgrade []
Renewal []
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
I certify that the above information is correct. I further certify that this application is being made
for a Single Family Dwelling and is in accordance with applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit/Rush Fees:
Date of Payment:
Receipt Number:
Permit No.
Waiver Fees:
Date of Payment:
Receipt Number:
Waiver No.
C:~Users~AndEng\Desktop\Mike\Kasilof Hills\Permit Application Lot 21 .docC:\Users~AndEng\Desktop\Mike\Kasilof Hills\Permit
Application Lot 21 .doc
ANDERSON ENGINEERING
P~Oi BOX 240773
ANCHORAGE, AK 99524
522,7773 677:7766 (FAX)
April 19, 2012
Municipality of Anchorage
Development Services Department
On-Site Water and Wastewater Program
4700 South Bragaw Street
Anchorage, AK 99519-6650
Subject:
Lot 21, Block 7, Kasilof Hills Subdivision
Septic System Design and Permit Application
Impacts to Adjacent Properties
Dear Onsite Services Engineer:
The owner of Lot 21, Block 7, Kasilof Hills Subdivision intends to construct a new four-
bedroom home on the lot. We are therefore requesting a permit be issued for the
construction of a new well and septic system to accommodate the home. The attached
Site Plan and backup documentation identify the location and configuration of the
proposed well and septic system along with the alternate site. Also identified on the
plans are the existing wells and septic systems on surrounding lots. No conflicts exist
between the proposed septic system and well or septic systems and wells on adjacent
lots. Drainage arrows are shown on the site plan showing the grade and direction of
flow on the lot. The drainage pattern will not be changed as a result of this project.
The test holes placed on the lot in the area of the absorption trench and alternate site
indicate silty sand and gravel (SM/GM). The percolation rate of the soil was determined
to be from 3 to 30 minutes per inch. No groundwater was found during the placement
of the test holes and none was noted during the monitoring period. An application rate
of .8 gallons per day per square foot was used in the design of the absorption system
as a blended rate. The new trench and alternate site are to be constructed almost
entirely in TH No. 1 which indicated a rate of 3 minutes per inch. We are proposing to
place a new 1,250-gallon septic tank and a 63' long by 3' wide by 6' effective depth
absorption trench to treat and dispose of the effluent generated in the house. The
elevation of the distribution line in the absorption trench will be 3' below the surface and
the total depth will be 9'. A minimum of 3' of fill or 2" of insulation and 2' of fill will be
placed over the absorption trench and 4' over the septic tank.
The ground surface on the lot in the area of the septic system slopes to west at a grade
of 20%. The new trench will be constructed parallel with the slope as much as possible
Lot 21, Block 7, Kasilof Hills Subdivision
April 19, 2012
Page Two
in conformance with Municipal requirements. The new septic system will be
constructed a minimum of 100' from all wells and any surface water and 10' the
proposed and existing water services in the area.
If the system is constructed in accordance with our design the following statements
apply:
The system, if constructed as designed, will have no adverse impact on the wells
in the area or those to be constructed in the future.
The system, if constructed as designed, will have no adverse impact on existing
septic systems in the area or those to be constructed in the future.
The system, if constructed as designed, will have no adverse impact on reserve
space, either surface or subsurface, on any lots located in the area.
The system, if constructed as designed, will have no adverse impact on drainage
patterns in the area. The current drainage pattern will be maintained.
Sincerely,
Michael E. Anderson, P.E.
A~achmen~
8
/'
~3
18
21
7
Well
21
10
19
,/
Existing
Well
9
Existing
Well
7
PLAT NO. 66-96
KASILOF HILLS SUBDIVISION
LOT 2~1, BLOCK 7
47,28~ S.F.
Proposed Well
Four
Bodroom
Home
G. SLAB
EL. = 488'
~[:D 30 1 250 Gallon
47' Long x 3' Wide
x B' Effective Depth o
~ ~ <~ Site
LEGEND
MT - Monitor Tube
FC0 - Foundation CleonI~ut ,
TH - Test Hole '
ExistingWell <'~o
NOTE:
,oo, o, Any Port of the SITE PLAN
New Septic System.
SCALE 1' = 50'
LOT 21, BLOCK 7, KASILOF HILLS SUBDIVISION
DESIGN FACTORS: SYSTEM REQUIREMENTS:
Four Bedroom House Deep Trench System
Pero. Rate: 6-15 Min./Inch 1,250 Gallon Septic Tank
Application Rate: .8 GPD/SF 8' Drainfield Rock
4 Bedrooms X 150 GPD/.8 GPD/SF (Application Rate) = 750 SF Absorption Area
750 SF/16 SF/LF = 46.875 LF Trench Length
THEREFORE: Construct a New 47' Long x 3' Wide x 8' Effective Depth Absorption Trench.
Flow Line Elevation in Trench to be 3' Below Original Ground Surface. Total Depth to be
11' Below Existing Ground. Place 2" of Insulation and 2' of Cover Over Absorption Trench
or Provide 3' of Cover Over Trench. Place 4' of Cover Over Septic Tank.
Natural
Backfill
Geotextile Fabric
4" Perforated
PVC (Holes Down)
-- Drainfield Rock
3~
TYPICAL DEEP TRENCH SECTION
NOTE' Grade Area Over Trench to Drain Away. ~
Mimmum 6. Separation From Bedrock. ~.,,~.;~,,;~....:~..~
Minimum 4 Separation From Groundwater.
Minimum 100' Separation From Wells in the Area. ~.~\ MICHAEL E ANDERSON
Minimum 100' Separation From Surface Water or Streams. '.;~¢~}..
MUNICIPALITY OF ANCHORAGE
DEVELOPMENT SERVICES DEPARTMENT
&700 SOUTH BRAGAW STREET ANCHORAGE, AK 99519-6650
SOILS LOG - PERCOLATION TEST ]
DEPTH
(feet)
1
2
3
4
5
6
7
8
9
LEGAL DESCRIPTION:
PERFORMED FOR:
DATE: 6/6/2012
PARCEL ID#:
LOT 21, BLOCK 7, KASILOF HILLS SUBDIVISION
CROWN POINTE HOMES
PROJECT No.:
TECHNICIAN:
[ TE T.OLE # 3 I
OL/OG
SILTY SAND WITH GRAVEL
GM/SM
BOH
J. BERKRAM
WAS GROUND WATER EN COUNTEP,~D?
SLOPE
NO
NONE
DATE OF MONITORING: 6/7/06
- .................................-ff..-djj -....~.~
SiTE PLAN
SEE SITE PLAN
DEPTH To
DATE READING GROSS TiME NET TIME WATER NET DROP
(MINUTES) (MINUTES) (INCHES) (INCHES)
6/6/12 TEST HOLE PRESOAKED PRIOR TO TESTING:
I Eft3 1.25"
2 2:&3 30 7.75" 6.50"
3 2:44 1.58"
4 3:lA 30 7.63" 6.25"
5 3:15 1.25"
6 3:45 30 7.50" 6.25"
PERCOLATION RATE:A.8 .0MIN/INCH)PERC. HOLEDIA. 8 _(INCHES)
TESTRUN BETWEEN:./+,0 FT. and. 5.0 FT.
COMMENTS: TEST HOLE PRE SOAKED PRIOR TO TEST.
TEST PERFORMED BY ANDERSON ENGINEERING TECHNICIANS. I, MICHAEL E. ANDERSON CERTIFY THAT
THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON
THIS DATE: 6/6/12
--~i~ --*~. · . · ~ ... ~ 4 ~i"'9,' ............
J~OIL LO(; - F£RQ,OLATION T[STI
LEGAL
DE~JCRIPlqON:
.,.-SOIL CLAS$1Fi~A'TIONS ',,L
GW ~ OR6 -... ..... ~' ,,,
~t GP ML
6C ! OL x~, ,,
_GROUNDWATER,, } l/ t I H/CZ/.~"'/ ,./
. JIUI,~i~Jj (CAR SIZE) j DRY 2/e/2005 -~'"';~ ~ l
~itlt, ft S~D[ or tH, / 1 "' \
' ..... '"" ' ':'
Th'4e (MIN,,UTF.$ EAD~N6 , ,(INCHES)
12 ~/200~ 1 $:00 -
~ 4-.-~.~ ,~, 3:20 .- $- I
9 .s:4o ~ -
11 3:~0 8" ; _
18-~ J g,, 12 .... ,,oo ,lO J ..... ~':"' ' '
19J ] PERCOLATION F~TE ,3.a ..(MIN./INCH) PER(:. IIOL-~ OlA. 6 · ONCHE$
IJ J '1 EST RUN 8E [W~:EN. _ 4,0 ::F-. AND :~0 FT.
20
..... A F'-Ol.J~ ~0L~ PRE$O,,~ WAS P~"F~FO~H[D: II y~$ []
SOILS LOGGED BY~ , JQDY iCAUS F'L:RCOLA'TION TEST PERFOB~ED BY: ROB
COHMENTS: , ,
PERFORMED BY OEG, Ltd. I. JEYFREY A, GARNE$$, CERTIFY THAT THiS WAS ~PEI~FQRblED IN ACCORDANCE
WITH ALL STATE AND MUNICIPAL 8UIDELINE$ IN EFFECT ON THIS DATE: ~-¢'~Jj'e.6~
DEP.TH TO
GROUNDWATER DATE
j~-OII. L, OG -,PERCOLATION TEST~ ~l[._.~j.~.~ ........
PERF F : LES ¢a~ . [-? ,3 ,.' -~
~TEST HOLE #21 °'°"~
GW
GP
GM
GC
SW
DEPTH TO '
ROUNDWATER
DRY
__ DRY
DATE JREADIN(
1..l
t
PEF~COLATION RATE
ORG
ML
CL
OL
MM
OH
l
CLOCK NET TIME
TI~tE (MINUTES
4:0~, - ,,.
4~35 30
30 (MIN./INCH)
WATER L'E. vEL NET DROP
RF_.~,D J~g, (INCHES)
PERC, HOL ~ D;A. ~NCHES)
TEST RL,LN B~TWEEN 4.,$ Fr. AND ..... ,5.0 .r:T.
A FOUR HOUR PF~SOAI~ WAS PER,~ORM~D: I YF$ ~ NO:
SOILS LOGGED IB¥;, dODY N~AU~ ..... PERCOL~,TIQN TESF PERFORMED BY: RC~l ~PB£LL .
COMMENTS; .,
PERFORM~'D ~Y ~£G, Ltd, {, JEFFREY A, GARN~S, CERTIFY THAT THIS WAS PERFORMED ~N ACCORDANCE
WITH ALL STATE AND MUNiCiPAL GUIDELINES tN EFFECT ON THIS DATe: _
ON-SITE WASTEWATER DISPOSAL SYSTEM
CONSTRUCTION AND MATERIAL SPECIFICATIONS
SUBJECT: LOT 21, BLOCK 7, KASlLOF HILLS SUBDIVISION
GENERAL:
The scope of this project includes the procurement and placement of a new
1,250-gallon septic tank at the location shown on the Site Plan. Work also
includes the construction of a new 63' long X 3' wide X 6' effective depth
absorption trench at the location also shown on the Site Plan. The
distribution line in the trench will be placed at 3' below the existing ground
surface. Total depth of the trench will be 9' below the existing ground
surface. The new absorption trench and septic tank must be placed a
minimum of 100' from all private wells and any surface water in the area and
10' from the water service line proposed for the lot. A minimum of 3' of cover
is required over the absorption trench and 4' of cover over the septic tank.
Construction shall be in accordance with the approved site plan, design
drawings, Municipal Permit with any special provisions or conditions, and all
applicable State and Municipal Wastewater Disposal Regulations.
The Contractor shall be responsible for obtaining all underground utility
locates and for the layout of the septic system and verification of the location
of all lot lines. The Contractor must also verify the location of wells in the
area and assure that the separation distances are met.
Unless specifically agreed otherwise, the contractor shall be responsible for
final grading areas subsequently depressed from soil settling. Property
owner shall be responsible for revegetation of affected areas unless
specifically agreed otherwise.
Contractors installing wastewater disposal systems must be certified by the
Municipal Building Safety Division On-Site Water and Wastewater Program
for system installations. Owners installing their own systems must receive
prior approval from the On-Site Water and Wastewater Program. before
beginning system installation.
SEPTIC TANK INSTALLATION
1. A new 1,250-gallon septic tank must be procured from an approved source
and installed at the location shown.
2. A septic tank is to be constructed by a certified septic tank manufacturer.
Construction shall include two 4" cleanouts for pumping access.
Lot 21, Block 7, Kasilof Hills
April 19, 2012
Page 2 of 3
DRAINFIELD CONSTRUCTION:
1.
The septic tank shall be sufficiently bedded to prevent settling or shifting of
the tank.
All standpipes on the septic tank shall extend a minimum of 12 inches above
final grade.
Tanks installed without 4' of cover shall have a minimum of 2" of direct burial
insulation.
A foundation cleanout shall be installed one to four feet from the building
foundation. Two cleanouts are required between the tank and the drainfield.
Final grading over the tank shall be such that a 3ositive slope exists away
from the septic tank.
The drainfield shall be constructed to the dimensions shown on the design.
The bottom of the trench shall be within 2" of level.
Distribution piping must be placed level with perforations down atop a level
bed of drainfield rock. Rock should then be placed over the pipe to provide a
minimum of 2" of cover.
A silt barrier or geotextile fabric must be placed between the drainfield rock
and the natural soil backfill.
Monitor tubes must be 4" in diameter and installed at the locations shown on
the design. The portion below ground must be perforated.
Contractor shall verify the septic tank and drainfield are a minimum 100' away
from any private water wells in the area, 150' from a Class "C" Well or 200'
from any community well.
Direct bury insulation must be placed over the distribution system if less than
3' of backfill depth is available. Finish grade over the trench must be
mounded to prevent settlement or depressions.
Grade area surrounding the absorption trench to drain away.
A minimum 2' of accepting soil is required below the drainfield rock for a 5'
wide trench. All pockets of unacceptable materials must be removed and
replaced.
Lot 21, Block 7, Kasilof Hills
April 19, 2012
Page 3 of 3
MATERIAL SPECIFICATIONS:
1. Septic tanks must be constructed by a municipally approved septic tank
manufacturer.
2. The following pipe materials are approved for use in septic system
installations in the Municipality of Anchorage:
Cast Iron (perforated and solid), ASTM D3034 or P.V.C. (perforated and
solid), ASTM F810 or H.D.P.E. (perforated, but not solid) and ASTM D2662
or A.B.S. (perforated and solid).
3. Insulation shall be at least 2" thick extruded direct burial polystyrene (Dow
Chemical Co. Styrofoam HI or equal).
4. Septic tank inlets and outlets shall be fitted with watertight couplings
(Caulder, Fernco, or equal).
5. A permeable geotextile fabric (Typar, Mirafi or equal) must be installed
between the final drain rock layer and the native soil layer.
6. All drain rock shall be .5" to 2.5" in diameter with less than 3% passing the
#200 sieve.
INSPECTIONS:
Municipal Ordinance requires a minimum of two inspections. These inspections
must be conducted under the supervision of a professional engineer registered
in the State of Alaska. The first inspection must be conducted after the
excavation of trenches, beds or pits and before the installation of any gravel. A
septic tank may be set in place, but may not be backfilled.
The second inspection must be conducted after the placement of the geotextile
fabric, gravel, distribution piping, standpipes, cleanouts and insulation. No
backfill should be in place at the time of inspection.
Contractor shall provide a copy of all field survey layout and construction notes
for use in preparing the certified as-built of the completed system.