Municipality of Anchorage
Community Development Department Page 1 of 3
On-Site Water and Wastewater Program
4700 Elmore St. • P.O. Box 196650 Anchorage, AK 99519-6650 • http://www.muni.org/onsite • (907) 343-7904
ON-SITE WASTEWATER INSPECTION REPORT
Permit Number: None PID Number: 051-293-36 ❑✓ New ❑ Upgrade
Name:
Paul and Kathy Mallory
ABSORPTION FIELD
❑ Deep Trench ❑✓ Shallow Trench [—]Bed []Mound
Address
15894 South Birchwood Loop Chugiak, AK 99567
❑ Other
Phone
Number of Bedrooms
Soil Rating
Total depth from original grade
2
1.2 GPD/SF
5.3 Ft.
LEGAL DESCRIPTION
Depth to pipe invert from original grade
3.3 Ft.
Gravel depth beneath pipe
2.OFt.
Subdivision Block Lot
53
Fill added above original grade 0
Ft.
Gravel length
36 Ft.
Township Range Section
15N 1 W 30
Gravel width
5Ft.
Beds: Number of Lines
Distance between lines
I Ft.
SEPARATION DISTANCES
To
Septic
Absorption
Lift Station
Holding
Sewer
Total absorption area
Number of trenches
Dist. between trendies
I
From
Tank
Field
Tank
Line
257 Ftp
One
Ft.
well
70"
84"
N/A
NIA
>25'
TANK O Septic ❑ S.T.E.P. ❑ Holding ❑ Other
Manufacturer
Klondike Concrete
Capacity
I 1,000Gal.
Surface water
>100'
>100'
NIA
N/A
Material
Number of compartments
Lot Line
>5'
>10'
N/A
NIA
Concrete
Two
NA
Foundation
>5'
>10'
N/A
N/A
LIFT STATION
Manufacturer
Capacity
Curtain Drain
None
Noted
-
Gal.
I I IN
Remarks ""See Waiver. Systems ndocumented.
Pump on level at
in.
Pump off level at
in.
High water alarm at
in.
Measurements Determined from Field Investigation
and Owner Furnished Information.
Pump make and model
Electrical Inspections performed by
Installer
PIPE MATERIAL Housetotank D3034 Tank to
drainfield D3034
James Polyefko/Tim Montgomery
Drainfield F810 CO/MT D3034
Inspector AH - Field Investigation
BENCH MARK (Assumed elevation) 100.Oft
Inspection .,
8/12/11 8/26/11
Location and description
dates: 2nd
a" 9/21/11 a'"
Yurt Finished Floor Slab.
COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL
�Amok t1blihill1
Conditional Approval: Date
T
�.....................
MICHAEL E. ANDERSON : 4?
R %'.• LE - 4381
Approve Date
+'t\POFEW
ispecnon nepory 1-i-t2mc
Municipality of Anchorage Page 2 of 3
DEVEOPMENT SERVICES DEPARTMENT
4700 South Bragaw Street Anchorage, AK 995196655 - 343-7904 PID No. 051-293-36
LOT 45
DRIVEWAY TO SOUTH LOT
BIRCHWOOD LOOP 46A
� 5 89'37'14"E 329.67'
C)
C7
0
O
O
STEEL FENCE
0LOT 53
�
Do C
= 109,860 S. F.
D (n SHED
C
CD
YURT LOT
C 52A
O n
z G 30.0' ]3.5• FCO
p
cz 29.2'
m .. GRAV-EL C3/MT
52 zs.t• n.o• �� :. r---�-----
Z DRNEWAY.,
i
a \
Of LIGHT, 'POLE \\ Sj
\\ P0ic 0 Taln�Cn
z
® i o
u o
N ExV'e1,iln9 I
! N
N
W
OVERHEAD ELECTRIb,
LINES
W
N
\/ ?
\ \ LOG CABIN / (P
LOT
-- 52C
I
I
I
Existing
Irrigation
Well
� I
cW !
oA �
to 0
o N 89-4,3'22-W 330.49' LOT 56B
LOT
o LOT 56A OF r��O+♦♦♦ 1
. P............
':♦
�...,. ..,49th /
PLAN AS BUILT ' ��`° '
♦�'; MICHAEL,E. ANDERSON
SCALE 1" = 50' ♦♦1�T�n •, No. CE-43at�i
♦♦♦ ��pROFESSIONP���•
Municipality of Anchorage Page 3 of 3
DEVEOPMENT SERVICES DEPARTMENT
4700 Elmore Road Anchorage, AK. 99519-6655 - 343-7904
On -Site Wastewater Disposal System or Well Inspection Report
Permit Number: None PID No. 051-293-36
7
N lUl.b N
/ N
1,000 Gallon
Septic Tank 972
x
9-21-11
W (Trench Length)
NOTE:
Trench Depth Could Only be Verified to 2' Below the Distribution Line.
Owner States Trench is 4.5' Below Line.
PROFILE AS -BUILT
No Scale
Municipality of Anchorage
Development Services Division
On -Site Water and Wastewater Program
**** VARIANCE/WAIVER REVIEW ****
Waiver#: OSV141255 COSA#: Permit#:
PID#: 051-29336
Legal Description: T15N R1 W Sec30 Lot 53
Engineer: Anderson Engineering
Applicant: Paul and Kathy Mallory
Your request for a waiver of thesequired 100 feet horizontal separation from the absorption field
to the private well has been approved. The approved separation distance is 84 feet.
Your request for a waiver of the required 100 feet horizontal separation from the septic tank to
the private well has been approved: The approved separation distance is 70.0 feet.
This waiver approval applies to the existing septic system only. Any future upgrade to the on-
site wastewater disposal system will require all separation distances be met or another approval
from this department.
❑ The affected adjacent property owner(s) have been given a 7 day notice regarding this
waiver.
n Notarized letter(s) of non -objection have been received from the owner(s) of the affected
adjacent property.
0 Adjacent properties are not affected by this waiver.
....... •.............a........... .■•i....•... ••. a ....•.•. u. ...................
Waiver is Granted: X Waiver is not Grant :
Date: Approved by:
arae of Reviewer
..._............................................ . ..M....:...■...
..... ....■.......
ANDERSON ENGINEERING
P.O. BOX 240773
ANCHORAGE, AK 99524
522-7773 : 677-7766(
February 10, 2015
Municipality of Anchorage
Development Services Department
On -Site Water and Wastewater Program
4700 South Bragaw Street
Anchorage, AK 99519-6650
Subject: T15N, R1W, Section 30, Lot 53
Septic Tank to Well Encroachment Waiver
Dear Onsite Services Engineer:
4111629—
711 -?AY
Allogaol-)LG
osQryiass
0,5sI a93,3(P
The existing septic tank on Lot 53 of Section 30, T15N, R1 W is located 70' from the
existing well on the lot. In addition, the southwesterly corner of the absorption trench is
84' from the well. The lot has been operating in this configuration for many years and
recent water tests show no presence of nitrate/nitrite content in the well. A waiver is
therefore required to allow the tank to remain in its current location less than 100' from
the well.
The septic tank is constructed of concrete and appears to be water tight. It was
uncovered and inspected in August of 2012 and found to be structurally sound and
water tight.. The tank is located down slope from the existing well and any effluent that
might surface from the septic tank or absorption trench would flow away from the well
and toward the front of the lot. The surface grade is 7% away from the well. Surface
effluent contamination of the well is virtually impossible.
Underlying soils on the lot are silty gravels (GM) based on documentation completed
during the verification of the suitability of the septic tank and the inspection of the
absorption trench. The well on this lot is 61' deep with water infiltration at 35' below the
surface. It was probably drilled in 1973 when the original buildings on the lot were
constructed. It is unknown whether the lot was ever placed in service as no septic
system or sewer service to the buildings originally constructed on the lot could be
found. In addition, no information regarding the well can be found, but an inspection
was recently completed and as built documentation prepared. Owner provided
information indicates the well and initial placement of the septic tank was made in 1973
at the request of the Seventh Day Adventist Church.
The overwhelming justification for the issuance of a waiver between the well and the
T1 5N R1 W SEC 30 Lot 53
February 10, 2015
Page Two
septic system is the water quality results. No detection of nitrate or nitrite content was
found in the water. No coliform, bacteria or arsenic was found either. We are
confident based on the long term performance of the existing septic tank and
absorption trench and the water quality from the well that contamination from the septic
system is not likely. We therefore recommend that the waiver allowing the existing
septic tank to remain 70' from the well and the absorption trench 84' from the well be
granted.
ADEC POINT ANALYSIS
Bottom of Tank to Highest Water Table — 8' 1.00 Points
Soil Absorption Type — Sand/Gravel w/Silt 2.50 Points
Permeability — Silt or Sandy Gravel 2.00 Points
Water Table Gradient - +7% 5.90 Points
Horizontal Separation — 70' 1.80 Points
TOTAL POINTS 13.20
No Bacteriological Pollution Possible, but Chemical Pollution Possible but
Unlikely from Household Chemicals.
Sincerely,
1v 1^� Z
Michael E. Anderson, P.E.
ARCTIC PUMP & WELL INC.
�yry Jim Sullivan
PO HoxAK 97
AK
1 Y Eagle River, 99577
mr�t (907) 688-2510
(907) 258-2510
(907) 745-2510
auwCa,,eci.net
Pump Installation Log
Well Drilling Permit Number: SW
Parcel Identification Number:
Date of Issue:
Arctic Pump & Well, Inc.
Page I of I
Legal Description:T15N Rl W S30
Property Owner Name & Address:
Lot:53
Paul Mallory
Block:
15894 S Birchwood 1p
QQSF7
Pump Installation Date: 4-28-12
Pump Intake Depth Below Top of Well Casing: 54 Feet
Pump Manufacturer's Name: Tait
Pump Model: 5P37
Pump Size: 1/2 hp
Pitless Adapter Burial Depth: feet
Pitless Adapter Manufacturer's Name:
Pitless Adapter Installer: NONE
Well Disinfected Upon Completion? Yes
Method of Disinfection: Chlorine
Comments:
9.5 static
2'stick up
15' casing
Water infiltration 35'and 41'
61' Total depth
Pump Installer Name:
Arctic Pump & Well, Inc.
Arctic Pump & Well, Inc.
Page I of I
i
SGS Ref.#
1142975001
Client Name
Anderson Engineering
Project Name/#
15894 S. Birchwood Loop
Client Sample ID
15894 S. Birchwood Loop
Matrix
Drinking Water
Printed DateTime
Collected Date/Time
Received Date/Time
Technical Director
07/15/2014 9:14
07/08/2014 19:00
07/09/2014 9:07
Stephen C. Ede
Sample Remarks:
E. Coli
Negative 1
100mL SM21 9223B A
07/09/14 MEV
Allowable
Prep Analysis
Parameter
Results LOQ
Units
Method Container ID Limits
Date Date Init
Metals by ICP/MS
Arsenic
ND 5.00
ug/L
EP200.8 C (<10)
07/09/14 07/10/14 EAB
Waters Department
Total Nitrate/Nitrite-N
ND 0.100
mg/L
SM21 450ONO3-F B (<10)
07/11/14 CDE
Microbiology Laboratory
E. Coli
Negative 1
100mL SM21 9223B A
07/09/14 MEV
Total Coliform
Negative 1
100mL SM21 9223B A
07/09/14 MEV
15894 Birchwood Loop Road Septic System
The history of the septic system is as follows. In 1973 the 1000 gallon dual compartment
tank was installed for the Seventh Day Adventist Church by the late James Polyefko, a licensed
septic system installer in the Eagle River/Chugiak area. The tank was manufactured by Klondike
Concrete with reinforced concrete. There are two concrete lift off access holes in the top, each 2'
x Tin size. Each compartment has a 6" above ground pump out.
The drain field was upgraded in 1993 by the owner Tim Montgomery who at the time worked
for Strata Construction. During his tenure with the company he installed over 20 septic systems.
He was assisted by his father Bill Montgomery who was a licensed septic installer in the area for
many years. The drain field he installed is a 5 foot wide trench, 36 feet long. There is 4 1/2' to 5'
of sewer rock beneath the standard ABS perforated drain field pipe. The drainpipe was covered
with 6" of sewer rock and then covered with Typar to prevent introduction of dirt into the
drainfield. The Typar was then covered with dirt to a depth of 3 1/2'.
Before the septic tank was connected to the Mallory home, it was fully excavated, inspected
for leakage, pumped and cleaned. There was no evidence of leakage, cracks or other defects.
When JR Septic pumped the exposed tank, the technician was impressed with the condition of
the tank. The ABS drainpipes going from the residence to the tank are insulated with 8" of foam
board above to prevent freezing and two clean outs are installed in the drain pipe, one in the
house and one outside. Hook up to the tank was performed by Pomeraning Excavation. The
system has been in continuous use for three years with no issues whatsoever, and the well test
was clean both before the purchase of the property and again at the application of this waver.
There is no indication the log cabin ever had plumbing. The owner states that no septic system ever
served the log cabin. No septic system other than the one shown on the drawing could be found on the lot.
The Septic Tank was constructed in 1973 by Klondike Concrete. At that time Klondike was an approved septic tank
supplier and concrete tanks were in use throughout Anchorage. It was uncovered and inspected and found to be
watertight and structurally sound. It is more than 40 years old and still sound verifying it was constructed to adequate
standards.
The aforementioned information was obtained from both field inspections and in discussions with the current owner.
We cannot guarantee the information from the owner or previous owners is accurate.
� F,
Michael E. Anderson, P.E.
OF
4E1 E. ANDERSON :,2
CE -4381 2®
r-11 -t5'. ��d
ec
30-
On -Site Wastewater Disposal System Permit
MUNICIPALITY OF ANCHORAGE
Development Services Department
On -Site Water & Wastewater Program
4700 Elmore Road, PO Box 196650
Anchorage, AK 99519-6650
Telephone: (907) 343-7904
Permit Number:
OSP121134
Tax Code Number:
05129336000
Work Type:
Septic Upgrade
Permit Effective Dates: June 25, 2012 to June 25, 2013
Design Engineer:
ANDERSON ENGINEERING
Subdivision:
T1 5N R1 W SEC 30
Site Legal Address: T15N R1 W SEC 30 LT 53 G:0755
Owner/Address: MALLORY PAUL & KATHY
15894 SOUTH BIRCHWOODLP CHUGIAK AK 995676954
Site Mailing Address: 15894 S BIRCHWOOD LOOP RD, Chugiak Lot Size in Sq Ft:
Total Bedrooms:
This permit is for the construction of:
,,,ent
c,
I)eparr.ment
108900
3
Y Disposal Field Y Septic Tank N Holding Tank N Privy N Private Well N Water Storage
All construction must be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater
Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80).
3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services
Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either:
A. Open and Close on the same day.
B. Covered, sealed, and heated to prevent freezing.
Special Provisions:
1. The wells are not documented and are not eligible for COSA approval without further
investigation and possible upgrade.
2. Proposed system too deep for soils information submitted. The Engineer needs to do an
additional perc test in the GM layer prior to the construction of the septic field. Please submit
stamped and signed results with the As -built Inspection Report. If the results require a design
change, construction of the system will stop pending On -Site review and approval.
Received By:
Issued By:
Date:
Date: e, r Z
MUNIUPAUTY OF A HCHORAGE
Community Development Department Phone: 907-343-7904
Development Services Division Fax: 907-343-7997
On -Site Water & Wastewater Program
Mayor Dan Sullivan
ON-SITE SEWER/ WELL PERMIT APPLICATION
FOR A SINGLE FAMILY DWELLING
Parcel I.D. 051-293-36
Property owner(s): Paul and Kathy Mallory
Mailing address: 15894 S. Birchwood Loop Chugiak, AK 99567
Site address: Same
Day phone: 444-5978
Legal description (Sub'd., Block & Lot): P.LM Lot 53, Section 30, T1 5N, R1
Legal description (Township, Range & Section) _
Lot Size: 108,900 S.F. Number of Bedrooms
Three (3)
THIS APPLICATION IS FOR: THIS APPLICATION IS AN:
(® all that apply)
Absorption Field X Initial EJ
Septic Tank X Upgrade X
Holding Tank ❑
Renewal ❑
Privy ❑
Private Well ❑Water
Storage ❑
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
I certify that the above information is correct. I further certify that this application is being made
for a Single Family Dwelling and is in accordance with applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit/Rush Fees: Waiver Fees: _
Date of Payment: r!n!l3 jc.� Date of Payment:
Receipt Number: ()M55Receipt Number:
Permit No. QSPl,) / (3L/ Waiver No.
C:\Users\AndEng\DesktopWike\T15N JohnsonTermitApplication Lot 102.docC:\UsersWndEng\Desktop\Mike\T15N
JohnsonTermit Application Lot 102.doc
ANDERSON ENGINEERING
P.O. BOX 240773
ANCHORAGE, AK 99524
522-7773 677-7766 (FAX)
June 12, 2012
Municipality of Anchorage
Development Services Department
On -Site Water and Wastewater Program
4700 South Bragaw Street
Anchorage, AK 99519-6650
Subject: BLM Lot 53, Section 30, T15N, R1
Septic System Design and Permit Application
Impacts to Adjacent Properties
Dear Onsite Services Engineer:
The owner of BLM Lot 53 intends to construct a new three-bedroom home on the lot at
some point in the future. They are currently living in a yurt on the property. The existing
septic tank and a section of the existing absorption trench fall within the 100' protective
well radius. We are therefore requesting a permit be issued for the construction of a
new well and septic system to accommodate the home that will be constructed outside
the radius. The attached Site Plan and backup documentation identify the location and
configuration of the existing and proposed septic systems along with the wells on the
Two wells currently exist on the lot with the second used entirely for landscaping
purposes. Drainage arrows are shown on the site plan showing the grade and direction
of flow on the lot. The drainage pattern will not be changed as a result of this project.
The test holes placed on the tract in the area of the absorption trenches indicated clean
gravel (GP/GM) material with some silt. The percolation rate of the soil was determined
to be 2.4 minutes per inch. No groundwater was found during the placement of the test
holes but was noted at 12' below the surface during the monitoring period. An
application rate of 1.2 gallons per day per square foot was used in the design of the
absorption system. We are proposing to place a new 1,000 -gallon septic tank and 2-
20' long by 5' wide by 4' effective depth absorption trenches to treat and dispose of the
effluent generated in the house. The elevation of the distribution line in the absorption
trenches will be 2' below the surface and the total depth will be 6'. A minimum of 3' of
fill or 2" of insulation and 2' of fill will be placed over the absorption trench and 4' over
the septic tank.
The ground surface on the lot in the area of the absorption trench slopes to the
northwest at 7%. The new trenches will be constructed parallel with the contours of the
BLM Lot 53, Section 30, T1 5N, R1 W
June 12, 2012
Page Two
slope as much as possible in conformance with Municipal requirements. The new
septic system will be constructed a minimum of 100' from all wells and any surface
water and 10' from the proposed and existing water services in the area.
If the system is constructed in accordance with our design the following statements
apply:
1. The system, if constructed as designed, will have no adverse impact on the wells
in the area or those to be constructed in the future.
2. The system, if constructed as designed, will have no adverse impact on existing
septic systems in the area or those to be constructed in the future.
3. The system, if constructed as designed, will have no adverse impact on reserve
space, either surface or subsurface, on any lots located in the area.
4. The system, if constructed as designed, will have no adverse impact on drainage
patterns in the area. The current drainage pattern will be maintained.
Sincerely,
-P-4'6'L'
E- C - �'
Michael E. Anderson, P.E.
Attachments
W 0-
:�• 49th••••••:
MICHAEL E. ANDERSON
k. NO. CE -4381
14. f fWESSICt�iO
—I Ln
�O 0
D C
—I 7
D �
C
cn
0
z
(n
C CO
CO�5
0 C
00
- o
mCj)
r O
0
C
un
0
M
O
i
M
Ln
rnG
y
z
z
Existing
Irrigation
Well
LOT 45
14"E 329.67'
LOT 53
109,860 S.F.
/
DRIVEWAY TO SOUTH
BIRCHWOOD LOOP
20.2'x20.4'
SHED
STEEL FENCE
2-20' Long x 5' Wide
x 4' Effective Depth
Absorption Trenches _
co `
Co MT
OVV
C(
_Co®MTTHSFSV
/
/
/
/
GRAVEL___
DRIVEWAY
-
_
\
\
c
LIGHT POLE Septic \
\
/
ALTERNATE SITE
\\
/
f
Advontex Treatment
System with 13' Long x
5' Wide x 4' Effective
Depth Absorption Trench.
I
Exist
Exist'
I
® I
�\
/
ttTRIIC
\ �\
13.6'x17' LOG CABIN
\ \\ 4)0 "+,,,r,
\ USeas fcta�e.
/
per M� '
t '
L GEND
I------��/
MT - Monitor Tube
NOTE'
FCO - Foundation Clean Out I No Areas of Excessive Slope or Surface
TH - Test Hole
CO - Clean Out
Water ore Within 100' of An Part of the
I Y
FDV - Flow Diverter Valve
I New Septic System. No Wells or
/ Wastewater Systems on Adjacent Lots
/ Conflict with the Proposed Septic System.
N
89'43'22"W 330.49'
LOT 56A
SCOPE OF WORK
Expose Existing Septic Tank and Verify
Suitable for Relocation. Decommission
Absorption Trench in Accordance with
Municipal Code. Relocate Septic Tank and
Construct 2-20' Long x 5' Wide x 4'
Effective Depth Absorption Trenches. Place
Flow Diverter Splitter Valve to Insure Even
Flow.
SITE PLAN
SCALE 1" = 50'
LOT
46A
LOT
52A
N
O
O
N
N
W
rr
W
W
N
N
LOT 560
�:• ••; .
®�: ;z}1
AV49th
/. j}}, ...... �......n..,.,.
i
................................................
MICHAEL E. ANDERSON f
No. CE -4381 :�Zi
AV
"'k -Zj -1 Z,••••' �FaC'i
♦� �z)�R�FESSI4��i��•
LOT
52C
LOTI1
BLM LOT 53, SECTION 30, T15N, R1 W
DESIGN FACTORS: SYSTEM REQUIREMENTS:
Three Bedroom Home 5' Wide Trench System
Perc. Rate: 2-5 Min./Inch 1,000 Gallon Septic Tank
Application Rate: 1.2 GPD/SF 4' Drainfield Rock
3 Bedrooms X 150 GPD/1.2 GPD/SF(Application Rate) = 375 SF Absorption Area
375 SF/5 SF/LF-.5 (Red. Factor) 37.5 LF Trench Length
THEREFORE: Construct 2-20' Long x 5' Wide x 4' Effective Depth Aborption Trenches at the
Location Shown. Flow Line Elevation in Trench to be 2' Below Original Ground Surface. Total Depth
to be 6' Below Existing Ground. Provide 3' of Cover Over Trench and 4' Over Tank or Provide
2" of Insulation and 2' of Cover. Maintain 10' Separation From Water Services in the Area.
Place Flow Splitter Valve to Insure Even Flow to Each Trench.
Natural
Backfill
1'6"
Geotextile
Fabric
6" 0 4" Perforated
PVC (Holes Down)
MI
5'
Drainfield Rock
TYPICAL DEEP TRENCH SECTION
(NO SCALE)
NOTE: Grade Area Over Trench to Drain Away.
Minimum 6' Separation From Bedrock.
Minimum 4' Separation From Groundwater.
Minimum 100' Separation From Private Wells in the Area.
Minimum 100' Separation From Surface Water or Streams.
Minimum 10' Separation From Water Service Line.
*•— -44�
ar �y ,
.:
49th
.....
79- -. Michael E. Fu
►,ted,, : No. CE4381 ���
♦����;;OFES S=� ��•
Municipality of Anchorage
Development Services Department
Building Safety Division
• �r On -Site Water and Wastewater Program
4700 Elmore Road
P.O. Box 196650 Anchorage, AK 99507
www.ci.anchoraoe.ak.us
(907) 343-7904
a MICHAEL F_ d>,t DWS"ON r8
Soils Log - Percolation Test
Performed For: {� V K WO�2-C/ Date Performed: !V
T
Legal Description: Section 30 T1 5N. R1 W. Lot 53 _ Township, Range, Section:
1-
2-
4-
5-
6-
7-
10-
11-
12-
13-
14-
15-
16-
17
18-
19-
20-
Depth
(Feet) G L
,,)rze Tian
T
6
YA._�j - 64k A, V-A
roll
WAS GROUND WATER
Date
ENCOUNTERED?
No
Depth to Water
s
IF YES, AT WHAT DEPTH?
XXX L
Depth to Water After
P
— Iv P
Monitoring?
E
Date:
Z I
Reading
Date
Gross Time
Net Time
Depth to Water
Net Drop
�Iv II
�3�1?. tiv
a A i,w
4: I � fr
/V mw
13•��3�3 �
��p to ''
.S1 II•�
.I I�
I
u
PERCOLATION RATE (minuteslinch) PERC HOLE DIAMETER 7 "
TEST RUN BETWEEN FT AND' ;L• J�r;_ FT
COMMENTS TEST CAVITY was presoaked prior to Percolation -
PERFORMED BY: A. Harala I CERTIFY THAT THIS TEST WAS
PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE:
Jim Sullivan
PO Box 770197
Eagle River, AK 99577
5IS ' HR (907) 688-2510
1 �1739! (907) 258-2510
(907) 745-2510
� an
w',%,Llci.net
Well Drilling Permit Number: SW
Parcel Identification Number:
Date of Issue:
Arctic Pump & Well, Inc.
Page 1 of I
Legal Description:T15N RlW S30
Property Owner Name & Address:
Lot:53
Paul Mallory
Block:
15894 S Birchwood 1p
QQ567
Pump Installation Date: 4-28-12
Pump Intake Depth Below Top of Well Casing: 54 Feet
Pump Manufacturer's Name: Tait
Pump Model: 5P37
Pump Size: 1/2 hp
Pitless Adapter Burial Depth: feet
Pitless Adapter Manufacturer's Name:
Pitless Adapter Installer: NONE
Well Disinfected Upon Completion? Yes
Method of Disinfection: Chlorine
Comments:
9.5 static
2'stick up
15' casing set into bedrock
Water infiltration 35'and 41'
61' Total depth
Pump Installer Name:
Arctic Pump & Well, Inc.
Arctic Pump & Well, Inc.
Page 1 of I