Permit Number:
Tax Code Number:
Work Type:
On-Site Water & Wastewater System Permit
OSP121192
01522174000
WellSeptic
MUNICIPALITY OF ANCHORAGE
Development Services Department
On-Site Water & Wastewater Program
4700 Elmore Road, PO Box 196650
Anchorage, AK 99519-6650
Telephone: (907) 343-7904
Initial
Permit Effective Dates: July 24, 2012 to July 24, 2013
Design Engineer: ANDERSON ENGINEERING
Subdivision: CROSS ViEW ESTATES
Site LegalAddress: CROSS VIEW ESTATES BLK 2 LT 12 G:2737
Owner/Address: COLONY BUILDERS INC
9420 VANGUARD DR ANCHORAGE AK 995070000
Site Mailing Address: 5680 HERITAGE HEIGHTS DR, Anchorage
Lot Size in Sq Ft: 49439
Total Bedrooms: 5
This permit is for the construction of:
Y Disposal Field Y Septic Tank N Holding Tank N Privy Y Private Well N Water Storage
All construction must be in accordance with: 1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater
Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80).
3. The wastewater code requires inspections during the.installation. The engineer must notify the Development Services
Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours).
4. From October 15 to April 151 a subsurface soil absorption system under construction during freezing weather must either:
A. Open and Close on the same day.
B. Covered, sealed, and heated to prevent freezing.
Received By:~ ,~,~..~
,ssued.y:
MUNICIPALITY OF ANCHORAGE
Community Development Depadment
Development Services Division
On-Site Water & Wastewater Program
Mayor Dan Sullivan
Phone: 907-343-7904
Fax: 907-343-7997
ON-SITE SEWER/WELL PERMIT APPLICATION
FOR A SINGLE FAMILY DWELLING
Parcel I.D. 0'15-22'1-74
Property owner(s): Colony Builders Day phone:
Mailing address: 9420 Vanguard Drive Anchorage, AK 99507
Site address: Heritage Heights Drive Anchorage, AK 99518
Legal description (Sub'd., Block & Lot): CroSS View Estates, Block 2, Lot 12
Legal description (Township, Range & Section)
Lot Size: 49,439 Sq. Ft. Number of Bedrooms: Five (5)
THIS APPLICATION IS FOR:
{[] all that apply)
Absorption Field X
Septic Tank X
Holding Tank []
Privy []
Pdvate Well X
Water Storage []
THIS APPLICATION IS AN:
Initial X
Upgrade []
Renewal []
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
I certify that the above information is correct. I further certify that this application is being made
for a Single Family Dwelling and is in accordance with applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit/Rush Fees:
Date of Payment:
Receipt Number:
Permit No.
Waiver Fees:
Date of Payment:
Receipt Number:
Waiver No.
C:~Users~AndEng~Desktop\Mike~Cross View Estates\Permit Application Lot 12 Colony.docC:~Users~AndEng\Desktop~Mike~Cross
View Estates~Perrnit Application Lot 12 Colony.doc
July 11, 2012
Municipality of Anchorage
Development Services Department
On-Site Water and Wastewater Program
4700 South Bragaw Street
Anchorage, AK 99519-6650
Su~e~:
Lot 12, Block 2, Cross View Estates Subdivision
Septic System Design and Permit Application
Impacts to Adjacent Properties
Dear Onsite Services Engineer:
The owner of Lot 12, Block 2, Cross View Estates Subdivision intends to construct a
new five-bedroom home on the lot. We are therefore requesting a permit be issued for
the construction of a new well and septic system to accommodate the home. The
attached Site Plan and backup documentation identify the location and configuration of
the proposed well and septic system along with the alternate site. Also identified on the
plans are the existing wells in the area and septic systems on surrounding lots. No
conflicts exist between the proposed septic system and well or septic systems and wells
on adjacent lots. Drainage arrows are shown on the site plan showing the grade and
direction of flow on the lot. The drainage pattern will not be changed as a result of this
project.
The test hole placed on the lot in the area of the absorption trenches and alternate site
indicate silty sand with gravel (SM/ML). The percolation rate of the soil was determined
to be 31 to 60 minutes per inch. No groundwater was found during the placement of
the test holes and none was noted during the monitoring period. An application rate of
.~,5 gallorl~-'p~r-day per squa~b-fO~t was us~-d-'ih~the design dt'~i~tion ~stem~ ....
We are proposing to place a new 1,500-gallon septic tank and 2-54, long by 3' wide by
8' effective depth absorption trenches to treat and dispose of the effluent generated in
the house. The elevation of the distribution line in the absorption trench will be 4' below
the surface and the total depth will be 12'. A flow splitter valve will be placed to insure
even flow to each trench. A minimum of 3' of fill or 2" of insulation and 2' of fill will be
placed over the absorption trench and 4' over the septic tank.
The ground surface on the lot in the area of the septic system slopes to the northwest
Lot 12, Block 2, Cross Point Estates Subdivision
July 11, 2012
Page Two
at a shallow grade with some cross sloping from the east. The new trenches will be
constructed parallel with the contours of the slope as much as possible in conformance
with Municipal requirements. The new septic system will be constructed a minimum of
100' from all wells and any surface water and 10' the proposed and existing water
services in the area.
If the system is constructed in accordance with our design the following statements
apply:
The 'system, if constructed as designed, will have no adverse impact on the wells
in the area or those to be constructed in the future.
The system, if constructed as designed, will have no adverse impact on existing
septic systems in the area or those to be constructed in the future.
The system, if constructed as designed, will have no adverse impact on reserve
space, either surface or Subsurface, on any lots located in the area.
The system, if constructed as designed, will have no adverse impact on drainage
patterns in the area. The current drainage pattern will be maintained.
Sincerely,
Michael E. Anderson, P.E.
Attachments
CROSS
10' STORM DRAIN ESMT. "]
20' GAS ESMT.
z
5' WALKWAY ESMT. "
ALTERNATE SITE
~xJventex Treatment System
with 40' Long x S' Wide x 8'
Effective Depth Absorption
Trench. (1 GPD/SF)
LEGEND
MT - Monitor Tube
MH - Man Hole
FCO - Foundation Clean Out
TH - Test Hole
CO - Clean Out
PLAT NO. 2006-171
VIEW ESTATES SUBDIVISION
LOT 12, BLOCK 2
49,615 S.F.
HERITAGE HEIGHTS DRIVE
N 89'27'47"E 148.85'
Proposed
Well
A.C. DRIVE
Four Bedroom /
SV ~ Septic Tank #/
x 8' Effect,~ Depth
20' STORM DRAIN ESMT.
10' T. A E. ESMT.
N 89'4~'56"E 166.85'
NOTE:
No Areas of Excessive Slope or Sun'ace
Water ore Within 100' of Any Par[ of the
New Septic System. No Wells or Wastewater
Systems on Adjacent Lots Conflict with the
Proposed Septic System.
SITE PLAN
SCALE 1' = 50'
R=220.00'
?8.00' ~
LOT 12, BLOCK 2, CROSS VIEW ESTATES SUBDIVISION
DESIGN FACTORS: SYSTEM REQUIREMENTS:
Five Bedroom Home Deep Trench System
Perc. Rate: 30-60 Min./Inch 1,500 Gallon Septic Tank
Application Rate: .45 GPD/SF 8' Drainfield Rock
5 Bedrooms X 150 GPD/.45 GPD/SF (Application Rate) = 1,666.7 SF Absorption Area
1,666.7 SF/16 SF/LF = 104.17 LF Trench Length
THEREFORE: Construct 2-54' Long x 3' Wide x 8' Effective Depth Absorption Trenches at the
Location Shown. Flew Line Elevation in the Trenches to be 4' Below Original Ground. Total Depth
to Be 12' Below Existing Ground. Provide 4' of Cover Over Septic Tank and a Minimum of 3'
Cover Over Absorpiton Trenches. Maintain 100' Separation from Wells in the Area. Place Flow
Splitter Valve to insure Even Flow to Each Trench.
Natural
Backfill
Geotextile
Fabric
6" (~) 4" Perforated
PVC (Holes Down)
Drainfield Rock
TYPICAL DEEP TRENCH SECTION
-- (NO SCALE) ~,.~.~....U~'.,....~
NOTE: Grade Area Over Trench to Drain Away. ~!'""
Minimum 6' Separation From Bedrock. ~....~.~,....4..9,t.h......~..~...~.~
Minimum 4' Separation From Groundwater. ~_ ~
M n mum 100' Separation From Wells in the Area ~"~,'? ' '~'~'~";;,;~'~;;-~'" '? ~.' ~
Minimum 100' Separation From Surface Water or'Straams: ~?,--~'-,, No
&700
DEPTH
(feet)
1
2
3
4
5
6--
7--
8--
9--
11
20
MUNICIPALITY OF ANCHORAGE
DEVELOPMENT SERVICES DEPARTMENT
BRAGAW STREET ANCHORAGE, AK 99519-6650
SOILS LOG - PERCOLATION TEST
LEGAL DESCRIPTION:
PERFORMED FOR:
DATE: 7/11/2012
PARCEL ID#:
OB/OG
SILTY SAND
WITH GRAVEL
SM/ML
BOH @ 18'
LOT 12, BLOCK 2~ CRoss VIEW ESTATES SUB.
COLONY BUILDERS
PROJECT No.:
TECHNICIAN:. J- BERKRAM
SLOPE
WAS GROUND WATER ENCOUNTERED? NO
IF YES ~ WHAT DEPTHS__'r~S ~
DEPTH OF WATER AFTER MONITORING: NONE - E 2°/0
DATE OF MONITORING: 7'~'~/2~12 ~
SITE PLAN
SEE SITE PLAN
DEPTH TO
DATE READING GROSS TIME NET TIME WATER NET DROP
(MINUTES) (MINUTES) (INCHES) (INCHES)
TEST HOLE PRESOAKED PRIOR TO TESTING:
7/11 1 10:30 6.25"
2 11:00 3'0 7.25" 2.18"
3 11:01 6.00"
4 11:31 30 6.88" .88"
5 11:32 5.75"
6 12:02 30 6.63" .88"
PERCOLATION RATE: 34 (MIN/INCH) PERC. HOLE DIA. 10"(iNCHES)
TEST RUN BETWEEN: 4.0 FT. and 5.0 FT.
COMMENTS: TEST HOLE PRE SOAKED PRIOR TO TEST.
TEST PERFORMED BY ANDERSON ENGINEERING. I, MICHAEL E. ANDERSON CERTIFY THAT
THIS WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS
DATE:_ 7/11/7012
4700
MUNICIPALITY OF ANCHORAGE
DEVELOPHENT SERVICES DEPARTMENT
BRAGAW STREET ANCHORAGE, AK 90519-6650
SOILS LOG - PERCOLATION TEST
LEGAL DESCRIPTION:
PERFORMED FOR:
DATE: 7/11/2.012~
PARCEL ID#:
DEPTH
(feet)
OB/OG
1
2
3
4
5
6--
7--
8--
9--
10T 12., BLOCK 2, CROSS VIEW ESTATES SUB.
11
20
COLONY BUILDERS
PROJECT No.:
TECHNICIAN:
SILTY SAND
WITH GRAVEL
SH/HL
BOH @ 18'
J. BERKRAM
..-.
Professional Engineers Stamp:
SLOPE
SITE PLAN
SEE SITE PLAN
WAS GROUND WATER ENCOUNTERED? NO
DEPTH OF WATER AFTER MONITORING: NONE · 2%-- .--
DEPTH TO
DATE READING GROSS TIHE NET TIME WATER NET DROP
(MINUTES) (MINUTES) (INCHES) (INCHES)
TEST HOLE PRESOAKED PRIOR TO TESTING:
7/11 1 10:50 6.50"
2 11:20 30 7.00" .50"
3 11:21 5.50"
4 11:51 30 6.00" .50"
5 11:52 3.50"
6 12:22 30 4.00" .50"
PERCOLATION RATE: 60 .(MIN/INCH) PERC. HOLE DIA. 9" (n'4CHES)
TEST RUN BETWEEN: 4.0 FT. and 5.0 FT.
COMMENTS: TEST HOLE PRE SOAKED PRIOR TO TEST.
TEST PERFORMED BY ANDERSON ENGINEERING. I, MICHAEL E. ANDERSON CERTIFY THAT
THIS WAS PERFORMED 1N ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS
DATE: 7/11/2012