MUNICIPALITY OF ANCHORAGE
Community Development Department ~//.~ Phone: 907-343-7904
Development Services Division ~ Fax: 907-343-7997
On-Site Water & Wastewater Program
Mayor Dan SulEvat~
ON-SITE SEWER/VVELL PERMIT APPLICATION
FOR A SINGLE FAMILY DWELLING
Parcel I.D. 05t-283-19
Property owner(s): Troy Davis Homes, Inc. Day phone: 357-9394
Mailing address: t66 E. Parks Highway, Wasilla, AK 99654
Site address: 17765 Almdale Avenue Eagle River, A.~
Legal description (Sub'd., Block & Lot): B.,J, JYrLot 112, Sect[on 25, TtSN, R2W
Legal description (Township, Range & Section)
Lot Size: 108,900 Acres Number of Bedrooms: Four (4)
THIS APPLICATION IS FOR:
(~;~ all that apply)
Absorption Field X
Septic Tank X
Holding Tank []
Privy []
Private Well X
Water Storage []
THIS APPLICATION IS AN:
Initial X
Upgrade []
Renewal []
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
I certify that the above information is correct. I further certify that this application is being made
for a Single Family Dwelling and is in accordance with applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit/Rush Fees:
Date of Payment:
Receipt Number:
Permit No.
*¢
171/
Waiver Fees:
Date of Payment:
Receipt Number:
Waiver No.
C:~,Users~And Eng\Desktop\Mike\T15N Lot 112\Permit Application Lot 112.d ocC:\Users~AndEng\Desktop~Mike\Tl5N Lo[ 112\Permit
Application Lot 112.doc
ANDERSON ENGINEERING
P,O, BOX 240773
ANCHO~GEi AK 99524
7766 (F~)
522-7773 677~
August 21, 2012
Municipality of Anchorage
Development Services Department
On-Site Water and Wastewater Program
4700 South Bragaw Street
Anchorage, AK 99519-6650
Subject:
Lot 112, T15N, R2W, Section 25
Septic System Design and Permit Application
Impacts to Adjacent Properties
Dear Onsite Services Engineer:
The owner of Lot 112, T15N, R2W, Section 25 intends to construct a four bedroom
home on the lot. We are therefore requesting a permit be issued for the construction of
a new well and septic system to accommodate the home. The attached Site Plan and
backup documentation identify the location and configuration of the proposed well and
septic system along with the alternate site. No existing wells are closer than 100' from
the proposed septic system. Drainage arrows are shown on the site plan showing the
grade and direction of flow on the lot. The drainage pattern will not be changed as a
result of this project. The new septic system will be placed more than 25' outside the
area identified as Class D Wetlands. No final determination has been made regarding
the presence of wetlands on this lot, but is currently ongoing.
The test holes placed on the lot in the area of the absorption trenches indicated gravel
with sand and silt (GM). The percolation rate of the soil was determined to be 1.2 to
13.3 minutes per inch. Groundwater was found during the placement of the test holes at
depths of 8' and 10' and stabilized at these levels during the monitoring period. An
application rate of .8 gallons per day per square foot was used in the design of the
absorption system and the trenches will be centered around Test Hole No. 2. We are
proposing to place a new 1,500-gallon STEP tank and a total of 106' long by 5' wide by
2' effective depth absorption trenches to treat and dispose of the effluent generated in
the house. The elevation of the distribution line in the absorption trenches will be 1'
below the surface and the total depth will be 3'. A minimum of 3' of fill or 2" of
insulation and 2' of fill will be placed over the absorption trenches and 4' over the STEP
tank.
The ground surface on the Jot in the area of the absorption trenches slopes to the south
Lot 112, T15N, R2W, Section 25
August 2'1, 2012
Page Tw~
and wes~at a~appro~imating 2%. The new trenches will be constructed parallel
with th~slop~'s"~'d'ch a~' possible in conformance wit,h, Municipal requirements. The
new sep~[l~.~~constructed a minimum of 100 from all wells and any surface
water and 10' r~m the proposed and existing water services in the area.
If the system is constructed in accordance with our design the following statements
apply:
]. The system, if constructed as designed, will have no adverse impact on the wells
in the area or those to be constructed in the future.
2. The system, if constructed as designed, will have no adverse impact on existing
septic systems in the area or those to be constructed in the future.
3. The system, if constructed as designed, will have no adverse impact on reserve
space, either surface or subsurface, on any lots located in the area.
4. The system, if constructed as designed, will have no adverse impact on drainage
patterns in the area. The current drainage pattern will be maintained.
Sincerely,
Michael E. Anderson, P.E.
Attachments
93
N89'49'lO"W 328.91
11
APPROXIMATE CLASS D WETLAND BOUNDARY ~
NOTE:
No Separation Distance Conflicts Between
the Well and Septic System on This Lot
and ]hose on Adjacent Lots.
NOTE'.
Well Radius and Easement Une to be
Staked by a Registered Land Surveyor
Prior to Construction.
3 DPD/SF ApplicaUon
Rate.
/
/
1,500 Gallon
LEGEND
MT - Monitor Tube
FCO - Foundation Cleon Out
TH - Test Hole
CO - Clean Out
MH - Man Hole
\
\
\
\
/
/
/
/
/
8
S89'49'50"E 528.91
ALMDALE AVENUE
NOTE:
No Areas of Excessive Slope or Surface
Water are WibS[n 100' of Any Par[ of the
New Septic System.
SITE
PLAN
i"~ ::: 49~:h
MICHAEL E, ANDERSBN
No, CE-438!
SCALE 1' = 50'
BLM LOT 198A, SECTION 18, T15N, R1W
DESIGN FACTORS: SYSTEM REQUIREMENTS:
Four Bedroom Home 5' Wide Trench System
Perc, Rate: 13.3 Min./Inch 1,500 Gallon STEP Tank
Application Rate: .8 GPD/SF 2' Drainfield Rock
4 Bedrooms X 150 GPD/.8 GPD/SF (Application Rate) = 750 SF Absorption Area
750 SF/5 SF/LF*.70 (Red. Factor) = 105 LF Trench Length
THEREFORE: Construct a 2-53' Long x 5' Wide x 2' Effective Depth Aborption Trenches at the
Location Shown. Flow Line Elevation in Trenches to be 1' Below Original Ground Surface. Total Depth
to be 3' Below Existing Ground. Provide 3' of Cover Over Trenches and 4' Over Tank or Provide
2" of Insulation and 2' of Cover. Maintain 10' Separation From Water Services in the Area.
Natural
Backfill
Topsoil and Seed
-- Geotextile Fabric
4" Perforated
-- PVC (Holes Down)
-- Drainfield Rock
5~
TYPICAL DEEP TRENCH SECTION
--
NOTE' Grade Area Over Trench to Dra'n Away
' . . , .
Mlmmum 6 Separation From Bedrock.
Minimum 4' Separation From Groundwater.
Minimum 100' Separation From Private Wells in the Area.
Mimmum. . 100, Separation. From Surface Water or Streams.. ·
Mlmmum 10 Separation From Water Service L~ne.
~700
MUNICIPALITY OF ANCHORAGE
DEVELOPMENT SERVICES DEPARTMENT
BRAGAW STREET ANCHORAGE, AK g951c)-6650
LEGAL DESCRIPTION:
PERFORMED FOR:
DATE: 7/50/12
PARCEL ID#:
DEPTH
(feet)
OB/OG
1
2
3
4
5 SILTY SAND
WITH GRAVEL
6 SM
?
8
9
SOILS LOG - PERCOLATION TEST
BLh'I LOT 112, TISN, R2W, SECTION 25
1i
TROY DAVIS HOMES. INC.
PROJECT No.:
TECHNICIAN:
TEST HOLE 1 ]
WAS GROUND WATER ENCOUNTERED? __
IF YES ~ WHAT DEPTHV
DEPTH OF WATER AFTER MONITORING:
20¸
B0H @ 15'
JKB
SLOPE
YES
DATE OF MONITORING: 8/8/2012 ~
SITE PLAN
SEE SITE PLAN
DEPTH TO
DATE READING GROSS TIME NET TIME WATER NET DROP
(I'"IINUTES) (~'IINUTES) (INCHES) (INCHES)
TEST HOLE PRESOAKED PRIOR TO TESTING:
8/3 1 1:12 3.00"
2 1:42 30 5.25" 2.25"
3 1:43 2.88"
4 2:13 30 5.13" 2.25"
5 2:14 2.50"
6 2:44 30 4.75" 2.25"
PERCOLATIONSt&TE: 13.3 .C~rNnNCH) PERC. HOLE DIA. 6" (iNCHES)
TEST RUN BETWEEN: 5.0 FT. and 6.0 FT.
COMMENTS: TEST HOLE PRE SOAKED PRIOR TO TEST.
TEST PERFORMED BY ANDERSON ENGINEERING. I, MICHAEL E. ANDERSON CERTIFY THAT
THIS WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS
DATE:. 8/8/12
A700
DEPTH
(fe~t)
1
2
3
4
5
6
g
9
11
20¸
MUNICIPALITY OF ANCHORAGE
DEVELOPMENT SERVICES DEPARTMENT
BRAGAW STREET ANCHORAGE, AK 99519-6650
SOILS LOG - PERCOLATION TEST
LEGAL DESCRIPTION: BLP1 LOT 112, TISN, R2W, SECTION 25
PERFORMED FOR:
DATE: 7/30/12
PARCEL ID#: d K B
OB/OG
SILTY SAND
WITH GRAVEL
SH
BOH @ I1'
TROY DAVIS HOMES. INC.
PROJECT No.:
TECHNICIAN:
TEST HOLE 2 ]
WAS GROUND WATER ENCOUNTERED? __
IF YES ~ WHAT DEPTH? 8'
DEPTH OF WATER AFTER MON]TOPdNG: 8'
DATE OF MONITORING: 8/8/2012
SLOPE
YES
SITE PLAN
SEE SITE PLAN
DEPTH TO
DATE READING GROSS TIME NET TIME WATER NET DROP
(MINUTES) (MINUTES) (INCHES) (INCHES)
TEST HOLE PRESOAKED PRIOR TO TESTING:
8/3 I 1:17/1:27 10 1.25"/9.75" 8.50"
2 1:28/1:38 10 1.5o"/]o.oo'8.50"
3 1:39/1:49 l0 1.25"/9.75" 8.50"
4 1:50/2:00 10 1.oo"/9.5o" 8.50"
5 2:01/2:11 10 l.SO"/lo.oo' 8.50"
6 2:12/2:22 10 1.oo"/9.5o" 8.50"
PERCOLATION RATE:I.2 (MIN/INCH) PERC. HOLEDIA. 6" ~INCHES)
TEST RUN BETWEEN: 3.0 FT. and 4.0 FT.
COMlvlENTS: TEST HOLE PRE SOAKED PRIOR TO TEST.
TEST PERFORMED BY ANDERSON ENGINEERING. I, MICHAEL E. ANDERSON CERTIFY THAT
THIS WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS
DATE 8/8/12