Municipality of Anchorage
Community Development Department Page 1 of 3
On -Site Water and Wastewater Program
4700 Elmore St. • P.O. Box 196650 Anchorage, AK 99519-6650 • http://www.muni.org/onsite • (907) 343-7904
ON-SITE WASTEWATER INSPECTION REPORT
Permit Number: OSPI21295 PID Number: 011-221-27 ❑ New 21 Upgrade
Name:
Jamie Cooper West
ABSORPTION FIELD
❑ Deep Trench E Shallow Trench ❑ Bed ❑ Mound
Address
P.O. Box 534 Willow, AK 99688
❑ Other
Phone
Number of Bedrooms
Soil Rating
Total depth from original grade
4
1.2 GPD/SF
8 Ft.
LEGAL DESCRIPTION
Depth to pipe invert from original grade
4 Ft.
Gravel depth beneath pipe
4Ft.
Subdivision Block Lot
Seacliff 3 8A
Fill added above original grade
2-3 Ft,
Gravel length
51 Ft.
Township Range Section
Gravel width
5Ft.
Beds: Number of Lines
Distance between lines
I FL
SEPARATION DISTANCES
To
Septic
Absorption
Holding
Sewer
Total absorption area
Number of trenches
Dist. between trenches
From
Tank
Field
Lift Station
Tank
Line
510 Ft'
I Ft.
Well
>200'
>200'
N/A
N/A
>25,
TANK El Septic ❑ S.T.E.P. ❑ Holding ❑ Other
Manufacturer
Anchorage Tank
Capacity
1,250Gal.
Surface water
>100'
>100'
N/A
NIA
Material
Number of compartments
Lot Line
>5'
>10'
N/A
NIA
Steel
Two
NA
Foundation
>5'
>10'
N/A
N/A
LIFT STATION
Manufacturer
Capacity
Curtain Drain
None
Noted
Gal.
RemarksExisting Absorption Pit Decommissioned in
Pump on level at
in.
Pump off level at
in.
High water alarm at
in.
Accordance with Municipal Code.
Pump make and model
Electrical Inspections performed by
PIPE MATERIAL Housetotank D3034 Tankto
Installer drainfield D3034
PCN, Inc. Drainfield HDPE CO/MT D3034
Inspector MEA BENCHMARK (Assumed elevation) 100.Oft
Inspecttiones: im 10/13/12 2"tl Location and description
10/14/12
3'" a Garage Slab.
COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL
..l�,L,gs
Conditional Approval: Date
49TH '•�
10.or
..........................nN
MICHAEL I- A7'40W4W
W
I. .•� �E-43
���i
�� 1qf •. -...0�Approv
Date l It 'VorEssit �
�,t
Inspection Re—1-1-12.doc
Page 2 of 3
PID No.:011-221-27
Municipality of Anchorage
DEVEOPMENT SERVICES DEPARTMENT
4700 Elmore Road Anchorage, AK. 99519-6655 - 343-7904 Permit Number: OSP121295
A I B
S1
43.5'
26.7'
S2
8.4'
48.4-133.3-
33.3'C4
C4
C5
Mt 1 68.8' 50.7'
SEACLIFF SUBDIVISION
LOT BA, BLOCK 3
17,282 S.F.
70,700 00
` t
Existing Absorption Crib \ \
Abandoned in Accordance with
Municipal Code. `
FCD 2� ��rvs 4r
Foor ,,
tae
wore'
LEGEND
SV — SepticVent
CO — Clean Out
MT — Mondor Tube
TH — Test Hole
C
\ 49th .`
.....i.;I............... If..._...^........
PLAN AS BUILT
SCALE 1' = 30'
MICHAEL E. ANDERSON
Municipality of Anchorage Page 3 of 3
DEVEOPMENT SERVICES DEPARTMENT
4700 Elmore Road Anchorage, AK. 99519-6655 - 343-7904
On -Site Wastewater Disposal System or Well Inspection Report
Permit Number: OSP121295
PID No. 011-221-27
PROFILE AS -BUILT
No Scale
E
Permit Number:
Tax Code Number:
Work Type:
On-Site Wastewater Disposal System Permit
OSP121295
01122127000
Septic
MUNICIPALITY OF ANCHORAGE
Development Services Department
On-Site Water & Wastewater Program
4700 Elmore Road, PO Box 196650
Anchorage, AK 99519-6650
Terephone: (907) 343-7904
Upgrade
Permit Effective Dates: September 24, 2012 to September 24, 2013
Design Engineer: ANDERSON ENGINEERING
Subdivision: SEACLIFF
Site LegalAddress: SEACLiFF BLK 3 LT 8A G:2424
Owner/Address: WEST JAMIE COOPER
PO BOX 534 WILLOW AK 996880534
Site Mailing Address: 5117 SHORECREST DR, Anchorage
Lot Size in Sq Ft:
Total Bedrooms:
17282
4
This permit is for the construction of:
Y Disposal Field Y Septic Tank N Holding Tank N Privy N Private Well N Water Storage
All construction must be in accordance with: 1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater
Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80).
3. The wastewater code requires inspections during the installation. The engineer must notif~ the Development Services -
Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either:
A. Open and Close on the same day.
B. Covered, sealed, and heated to prevent freezing.
Date:
MUNICIPALITY OF ANCHORAGE
Community Development Department
Development Services Division
On-Site Water & Wastewater Program
Phone: 907-343-7904
Fax: 907-343-7997
ON-SITE SEWERNVELL PERMIT APPLICATION
Parcel I.D. 01%221-27
Property owner(s) Jamie Cooper West
Mailing address P.O. Box 534 Willow, AK 99688
Day phone
Site address 5117 Shorecrest Drive Anchorage, AK
Legal description (Sub'd~, Block & Lot) Seacliff, Block 3, Lot 8A
Legal description (Township, Range & Section)
Lot Size 47,282 Sq. Ft. Number of Bedrooms Four (4)
APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING:
([~ all that apply)
Absorption Field [] Initial [] Single Family (SF) []
(w/wo ADU)
Septic Tank [] Upgrade []
Duplex (D) []
Holding Tank [] Renewal []
Multiple Dwellings []
Privy [] (SF and/or D)
Private Well []
Water Storage []
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
Distance:
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit/Rush Fees:
Date of Payment:
Receipt Number:
Permit No.
Waiver Fees:
Date of Payment:
Receipt Number:
Waiver No.
Permit App_9-1-12.doc
ANDERSON ENGINEERING 1
PiO~ BOZ 240773
~.CHORAGE AK 99524
$22-7~73
September 11,2012
Municipality of Anchorage
Development Services Department
On-Site Water and Wastewater Program
4700 Elmore Road
Anchorage, AK 99519-6650
Subject:
Lot 8A, Block 3, Seacliff Subdivision
Septic System Design and Permit Application
Impacts to Adjacent Properties
Dear Onsite Services Engineer:
The existing septic system on the subject lot was originally constructed in 1966 and is
undocumented. It has failed and must be replaced. We are therefore requesting a
permit be issued for the upgrade of the septic system to accommodate the four-
bedroom duplex on the lot. The attached Site Plan and backup documentation identify
the location and configuration of the existing and proposed septic systems. The existing
septic crib will be decommissioned in accordance with Municipal Code and a new 1,250
Gallon Septic Tank placed at the location shown. A new absorption trench will be
constructed in accordance with Municipal Code. Also identified on the plans are the
locations of the existing well on this and adjacent lots and adjacent septic systems. No
conflicts exist between the proposed septic system and the wells on this or adjacent
lots. Protective radii are shown to the adjacent wells. Drainage arrows are shown
indicating the current drainage patterns. The drainage patterns will be maintained after
construction.
The test hole placed on the lot indicated Well Graded Gravel with Sand and Silt
(GM/SM) the entire depth. The percolation rate was determined to be less than 5
minutes per inch. We have designed the new trench with an application rate of 1.2
gallons per date per square foot. No groundwater was found in the test hole and none
developed during the monitoring period. We are proposing to place a 50' long trench
by 5' wide with a 4' effective depth. The total depth of the system will be 8' with the
distribution line at 4' below the existing surface.
The ground surface on the lot is virtually fiat in the area of the proposed absorption
trench. The trench will be placed parallel to the contours of the ground as much as
Lot 8A, Block 3, Seacliff
September 11, 2012
Page Two
possible and in conformance with design criteria. A minimum of 100' will be maintained
between all components of the septic system and the existing well and from any
surface water in the area.
If the system is constructed in accordance with our design the following statements
apply:
The system, if constructed as designed, will have no adverse impact on the wells
in the area or those to be constructed in the future.
The system, if constructed as designed, will have no adverse impact on existing
septic systems in the area or those to be constructed in the future.
The system, if constructed as designed, will have no adverse impact on reserve
space, either surface or subsurface, on any lots located in the area.
The system, if constructed as designed, will have no adverse impact on drainage
patterns in the area. The current drainage pattern will be maintained.
Sincerely,
Michael E. Anderson, P.E.
Attachments
1 0A
2O
9A
21
6
7A
VACANT
22A
AREA NAP
SCALE 1' = 100'
/
/
/
/
/
/
/
/
/
/
/
/
r',,- z
~-0
ox
_d
o
o ~
E
7
I
LOT 8A, BLOCK 3 SEACLIFF SUBDIVISION
DESIGN FACTORS: SYSTEM REQUIREMENTS:
Four Bedroom Duplex 5' Wide Trench System
Perc. Rate: 1-5 Min./Inch 1,250 Gallon Septic Tank
Application Rate: 1.2 GPD/SF 4' Drainfield Rock
4 Bedrooms * 150 GPD/Bedroom ~ 600 SF Absorption Area
600 SF/1.2 GPD/SF/5 SF (Width) .5 (Red. Factor)= 50 LF Trench Length
THEREFORE: Construct a 50' Long x 5' Wide x 4' Effective Depth Absorption Trench at the Location
Shown. FlowlJne Elevation to be 4' Below the Existing Ground Elevation. Total Depth to be 8' Below
Existing Ground. Provide 4' of Cover Over Septic Tank and 3' of Cover Over Absorption Trench.
Maintain 200' Separation From Class A Well in the Neighborhood.
Geotextile Fabric
4" Perforated
PVC (Holes Down)
Drainfleld Rock
TYPICAL 5' WIDE TRENCH SECTION
4700
MUNICIPALITY OF ANCHORAGE
DEVELOPMENT SERVICES DEPARTMENT
BRAGAW STREET ANCHORAGE, AK 99519-0050
DEPTH
(feet)
1 OL/OG SLOPE
2--
3
4
5
SILTY GRAVEL
6 WITH SAND
GM/SM
?
8 DRY
9
11
20-
SOILS LOG - PERCOLATION TEST
LEGAL DESCRIPTION: LOT 8A, BLOCK 5, SEACLIFF SUBDIVISION
PERFORMED FOR: JAI'41E COOPER WEST
DATE: 8/25/2012 PROJECT No.:
PARCEL ID#:. TECHNICIAN: IdEA
I TEST HOLE1 I
BOH @ IL,'
SITE PLAN
SEE SITE PLAN
WAS GROUND WATER ENCOUNTERED? NO
IF YES ~ WHAT DEPTH?.__ S
DEPTH OF WATER AFTER MONITORING: NONE ~ 2 °/o -- .-
DATE OF MONITOPJNG: 9/10/2012
DEPTH TO
DATE READING GROSS TIHE NET TIME WATER NET DROP
(HINUTES) (MINUTES) (INCHES) (INCHES)
TEST HOLE PRESOAKED PRIOR TO TESTING:
9/1 1 2:12 .?5"
2 2:42 30 8.50" 7.75"
3 2:43 .63"
4 3:13 30 8.38" 7.75"
5 3:14 1.00"
6 3:34 30 8.75" 7.75"
PERCOLATION RATE: 3.9 (MIN/INCH) PERC. HOLE DIA. 10" .(INCHES)
TEST RUN BETWEEN: 3.5 FT. and 4.5 FT.
COMMENTS: TEST HOLE PRE SOAKED PRIOR TO TEST.
TEST PERFORMED BY ANDERSON ENGINEERING. I, MICHAEL E. ANDERSON CERTIFY THAT
THIS WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUN1CIPLE GUIDELINES IN EFFECT ON THIS
DATE: 9/11/2012