HomeMy WebLinkAboutRABBIT CREEK VIEW & HEIGHTS BLK 7H LT 8ARabbit Creek View & Heights Block 7H Lot 8A #020-571-09 Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program, 4700 Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 Page 1 of 2 www.ci.anchorage.ak.us (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT Permit Number: SW000222 PID Number: 020-$71-09 Michael Hauke Wastewater System: [] New [] Upgrade 7921 Susan Cir. ABSORPTION FIELD 830140T§- 4 [] DeepTrench [] ShallowTrench [] Bed [] Mound [] Other: Soi~ Rating: Total Depth from original grade: LEGAL DESCRIPTION ePe/~t' BMab: Lot: Subdivision: Depth to pipe bot~m from original grade: Gravel depth beneath pipe: 8A 7H Rabbit Creek Heights Ft, Ft. Township: Range: Section: Fill added above original grade: Gravel Length: Ft. Ft. Well: [] New [] Upgrade Gravelwidth: Ft. Number°fl' .... [Distance betv,~enlin;i:. Class}flcabon (Private, A, S, C): Total Depth: Cased to: Total absorption area: Pipe Material: EXIST'G PRIVATE Ft. pt, Ft' 3034 PVC Driller: Date Drilled: Static Water Level: Installer: Date Installed: Ft. OWNER 7/412009 Yield: GPM PumpSetat: Ft. CasingHelghtAboveGround: pt. TAN K SEPARATION DISTANCES [] septic [] Holding [] S.T.E.P. [] Other: T~ To Septic Absorption Lift Holding ~ubl[c/Private Manufacturer: Cape. city: From~ Tank Field Station Tank Sewer Line Anchorage Tank 1250 aa,. we,, 107.3' Steel 2 Sun. DeW.e, 100+ ~ / LIFT STATION Lot Line 42' e,,. !4t..~'l'?' 'Pump on" level at: 'Pump off' level at: I High water alarm at: Foundation Cur[ain Drain 100' / ~ Pump Make & Model Elecfricel ,nspec[ions performed by: Septic Tank upgrade only BENCH MARK Door Jam 100.0 Ft. Engineer's Stamp Inspections pedormed by: PANNONE LNG, SVC, LLC Dates: 1~ 7,4,2009 2nd 7/412009 Development Services Department Approval Conditional Approval Date: ~....~ ........ i.....~ '~= ,,,,;~,,i .............one:~ ;'~ Reviewed and approved b ' Date: ,~ -.~-//"~ D E S I O ~'"P'A~. AiV~T ~k'S ..... . ................. PRIM/RY SEPTIC S-'K...~,.~M '"--... ~'AAI~K SIZE: 1,250 gollon'~TEP ...... . ........ PERC'~TE: 16-~0 MPI ~ .. .. ' SOIL I~AT~N~ 0.6 gpd/SF x~,, - ..... .. .... AB~ RQ? 1~0 SF ....... TIE"E~ I~ O FIEL~OGETHER ..... :.. ABAN~ )0~ '~QER TRE~ '~T~ ' 1986i SYSTEM'~'~80 SF "-~ ~ H, WATE~"~' ..... ~IN ~O-,~ OF '~~ · . ~ SYSTEM L~'~AE~QN ~ ~ '--~ .. / · - ~/ ~ ........ ~~~ ........ ~ EXISTG"- BE~.. " / / / 4 BR / / ...... L2B~OUS¢'""~ .... ABANDO'N-~FR CODE .... ~ao ~ / l / I ~ A" ....... ......... '"'--. , - ...... EXIST G ~ ~ ~ EXIST 6 WELL ~ ~ ~ SWING TIES 9/13/09 ~ECORD DRAWING PHONE (907) 272-8218 FAX (907) 272-8211 ~ ".~ ~g,t: ..... ¢=50' Rabbit Creek Hts, Block 7H, L8A ~-571-o~ Michael Hauke ~ ~' CE 8149 .' ~ ~ERMIT NO. PLAN Anchorage, AK 99,516 ~'; ...... , Sheet -~ ~ 2 OF 2 MUNICIPALITY OF ANCHORAOE Deve/opment Services Department On-Site Water & Wastewater Program 4700 South Bragaw Street P.O. Box 196650, Anchorage, AK gg519-6650 (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT Upgrade Date Issued: Oct 06, 2008 Expiration Date: Oct 06, 2009 Permit Number: S~080222 Parcel ID: 020-571-09 Legal Description: R~;~EK HEIGHTS SUBDIVISION BLOCK 7H LOT 8A Design Engineer: 0062 PANNONE ENGINEERING SERVI( Site Address: 7921 SUSAN CIRCLE Owner Name: MICHAEL HAUKE Lot Size: 219001 SQ. FT. Owner Address: 7921 SUSAN CIRCLE Total Bedrooms: 4 Permit Bedrooms: 4 ANCHORAGE , AK 99516- This permit is for the construction of: [] Disposal Field [] Septic Tank [] Holding Tank [] Privy [] Private Well [] Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations ( 18AAC80 ). 3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only ). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. Received B~ Date: Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program 4700 Bragaw Street P.O. Box 196650 Anchorage, Alaska 99519-6650 www.muni.org/onsite (907) 343-7904 ON-SITE SEWER/VVELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. Property owner(s). Michael Hauke Mailing address7921 Susan Circle, Anchorage AK Site address 7921 Susan Circle, ANchora.qe AK .Day phone 830-4076 Zip Code 99516 Zip Code 99516 Legal description (Sub'd., Block & Lot) Rabbit Creek Hei.qhts S/D Block 7H Lot 8A Legal description (Township, Range & Section) Lot Size 21,901 sq. Ft. Number of Bedrooms 4 THIS APPLICATION IS FOR ([~ all that apply): Absorption Field [] Septic Tank [] Holding Tank [] Privy [] Private Well [] Water Storage [] THIS APPLICATION IS AN: Initial [] Upgrade [] Renewal [] I certify that the above information is correct. I further certify that this application is being made for a Single Family Dwelling and is in accordance with applicable Municipal Codes. Pannone Engineering Services, LLC ..~¢~~.~ (Signature of property owner or authorized agent) Permit/Rush Fees: Date of Payment: Receipt Number: (Rev. 11/05) Waiver Fees: Date of Payment: Receipt Number: Pannone Engineering Services, LLC Consulting Engineers (9071 272-82~8 July 21, 2008 P.O. Box 102954 Anchorage, Alaska, 99510 (907) 272-8211 Fax Municipality of Anchorage Development Services Department On-Site Water & Wastewater Program 4700 S. Bragaw Street P. O. Box 196650 Anchorage, Alaska 99519 Subject: Rabbit Creek Heights S/D Block 7H, Lot 8A Septic System Permit Upgrade Request Ladies and Gentlemen: I am writing in response to your comments dated April 24, 2008. Comment: Why do the slope arrows drawn not match the contours? Response: Contour Data was unavailable in 2005 when slope data was presented. Contours govern. Comment: The proposed trenches are not parallel to either slope notation. Response: Proposed field rotated 5 degrees to make parallel to slope. Comment: Have the existing systems had an adequacy test? Response: Both existing system were tested and found adequate for four bedrooms. Comment: After the "Review Only" drawings have been reviewed and you are notified that there are no additional comments, the "For Construction" drawingmust be submitted before the permit is issued. The permit won't be issued until the two sets of drawings have been compared. Response: Acknowledged. When we receive that there are no more comments, we will issue "for Construction Drawings: Comment: It looks like there was a lot line waiver for the bed. Please show their location accurately on the site plan. Response: Revised drawing Comment: 6" of top soil and vegetation required on proposed system. Response: Revised Sections Comment: New perc test required and water monitoring required to replace test submitted in 2005. Personnel from the Onsite Department are to witness the perc test. Response: New soils test and percolation test performed in May of 08. Your department was called on May 17, 2008 when I was notified an excavator was available. Results of new test is attached. Page 2 of 3 Design Parameters The proposed systems will serve a new four-bedroom house. Currently the lot is developed. The existing house was constructed as a two bedroom house. The Owner plans to add two additional bedrooms to the house. The lot is served by a private water supply that is to be reused. The existing septic systems shall be reused by tying the two fields together and the installation of a 1250 gallon septic tank and a flow splitter between the two fields. The lower trench of the 2005 system will be abandoned in place. The surrounding developed lots am served by private water systems. The private wells are located over 100 feet from the proposed soil absorption system. 1. Soils. Two test holes were excavated in August of 2005. And a new test hole in May of 2008. See the attached soil logs. Ground water was monitored through the spring high ground water period of 2008 and was monitored at a depth of 8 feet on August 22, 2005in test holes 1 & 2 and at 4.6 feet in test hole 3 in 2008. Bedrock was not encountered in the test holes. It is my opinion, based on the results of the percolation tests and overall soils appearance; an application rate of 4.0 gallons/day/square feet should be used, using an advanced treatment system meeting Category I1/treatment, for the reserve system calculations. The primary field should use an application rate of 0.6 gpd/sf using a conventional system. Primary System a. Percolation Rate: b. Application Rate: c. Design Flow: d. Min. Absorption Area: 16 to 30 Min Per Inch 0.6 gpd/sf 600 gallons per day 1000 sf e. Tie two existing fields together, abandon lowest field (125sf) f. 1986 field: 780 sf g. 2005 field: 375 sf h. Effective Absorption Area: 1155 sf i. Septic Tank Size: 1250 gallon. Reserve Soil Absorption System Design. a. Percolation Rate: 16 to 30 Min Per Inch b. Application Rate: 4.0 gpd/sf c. Design Flow: 600 gallons per day d. Min. Absorption Area: 150 sf e. Total Depth: 0 feet f. Effective Depth: 0.5 feet g. Width: 5.0 feet h. Minimum Length: 30 feet i. Design Length: 30 feet j. Effective Absorption Area: 150 sf k. Septic Tank Size: 1,500 gallon STEP & AX 20 Pod. 4. Surface Water: There is no surface water within 100 feet of the proposed septic tank and the existing drain field. The proposed drain field upgrade will maintain at least 100 feet from all surface water and drainage ditches. W:\PES Work Files\Letters\Rabbit Creek Hts B7H L8A_012.doc Page 3 of 3 5. Topography: The average topography in the area of the proposed septic system is approximately 16 percent based on contour information. The proposed installation will be greater than 50 feet from the shoulder of the steep slopes. 6. Drawing Markings: The Drawings are marked "For MoA Review Only". When written notification that the review is complete and that there are no further comments is received from MoA On-Site Department, the note will be removed and "Issued for Constmction" drawings will be issued. The proposed installation will not affect the future development of the surrounding or existing lots. There are no wells or septic systems within 100 feet of the proposed septic location. If you have any questions or concerns, please contact me at 272-8218. Sincerely, ~~'I'""~' ...~.....~ ............ v. ~ annone g Steven R. Pannone, P.E. Owner/Civil Engineer Attachments: W:\PES Work Files\Letters\Rabbit Creek Hts B7H LSA_012.doc PARAMETERS " ' '" ' .... DESIGN -- ---. -- '" TANK'SI~ .'.E: 1,250 gallon STEP~.. ............... -._. -..~. PERC. R ~,¥B~ 16-50 MPI ~x '" "/ 'SOIL RA' ING['~O';'6~gpd/SF ...... '" -....:.~.~'~.~ "- AR~,"'~.q ,D.: 1000 '8¢... ........ ' .... '"' TIE EXIS ~ 6-FIELDS T~)GETHER ..~~ ABANDO ,I LO'~R--ERENCH"".-. ~TH, WATE~"~ 1986 S'(gTEM: 78~'SE. '%...... , 2005 S'~STEM: 375 ........ '-. / \ 0N'5/].~'/08 .......... <* "' '0"$H, WATER @ :~4" "'TOTA~ A ,'EA: 1,155F ............ ~.....~. . - - FR'CFr~c-~F$¥~S-~E~- - - .. _ '"'--. " ...... PROPOSED a-"D,~ RESERVE-S','STE,'~i ". ABANDON EXST G FEILD~ ~ ..... . ........ 50 LFX 5'WX 5"~'D'BASEB (~'~' CA1 ........ "- CA®t%N.L__ _" ........... '" -- .... ~< ..... -~'~.~ -- --~BURIED OTIt~ITIES-~' ~4O~.~ADVANCED TREATMENT~S¥$~.EM ALTER~A~BRESERVE ~"---.. ~ "~ ~G_cAS ......... ~~1 ABANDO~E 3 (575 S..) "-% --.~ REM~'E"TWO / ~'"'/. ~1~_9' "-- .. ~EXSF'G"~H..WATER~-77 '~. -- ~ '~'---.~ ~ ~'"~V- / ~ / W/'N. O0 FEET OF ....... .. ,. ...... ~' ] /~ '""~ ..... / PROP'S'ED-SYSTEM '~I~ZGSEPTIC~ NEW 1250 G ..... ~ [/ ~ ~ .... ~ ........ '~REA- SEPT C TANK ~ ~... ~ ~ ~ ........ OLD TANK CRUS~EB, - ......... ~ ~ ~ } -~'=..~--~ "' aBURIED HERE ......... ~/ ~-~ ~ · '---L. ' -.~. '---.-.. .... /'- / ~ '---~%m; / %~'780 SF' ' ......... NOTE: AREA REG~D~B..-EQ 1% ~ '-~/~ ~ & 1% .... (-142~ ) ........... ......... ca' ou s "- ..... '"-... ~ / GENERATED~ -, - . / V ~.~ % ...... ~.. / ~ ....... / ,~ . ~"'-..~ INSTALL FLOW '~LITER .......... -., / .............. x6.o/ '- % ............. '"'-. / ~ ........ ' x ~07.~ ~ , ~ ~'" .-.% ...... "~. PROPOPQSBB '--- ~ ~ ..... '--. / , ~ BR / / -~2B~OUS¢'""~.....; ABAN ....... ~ '--.... '"I~BO / / ~ ~ ~ '---.._ '""-~ a "'-. NOTES: ~0~ ~N6 ~C~ ~ ~, 07/30/08 P.O. BOX 102954 ANCHORAGE, AK 99510 ~ ..... ISSUED FOR CONSTRUCTION PHONE (907) 272-8218 FAX (907) 272-8211 ~..' ~;~ Sc~e ~ P.I.D. NO Rabb~t Creek H(s, Block 7H, L8A ~~k'no~e ........ ~;'~2°-571-0~ 7921 Susan Circle ~,2~.. ..~ swxxxxx, PLAN Anchorage, AK 99516 ~¢~ ...... :~ ~ ~OrESS6~ d d ,o~[s: P~O~ ~G ~C, L~ i, 07/30/08 P.o. ,ox ~0~5~ ~,c,o~oE, ~ 0~5~0 ~¢~ ..... ~J~, ~o~,~ ISSUED FOR CONSTRUCTION PHONE (907)272-82'8 FAX (907)272-8211¢~~'~*'t NTS ~oDDit Creek Nts, ~lock Michael HaukeraWlY" CE 8149 -'*~ PERMIT NO. 7921 Susan Circle *t ~" '~C~"~ sw~ DESIGN NOTES Anchoroge, AK 99516 ~l~'z~ ...... ~ Sheet SOILS LOG - PERCOLATION TEST TEST HOLE 3 SM/ SAND & STG FEI~ TH ~CAVATED: 5-16-08 SLOPE WAS GROUND WATER PER PERFORMED :5-30-08 ENCOUNTERED? ~ IF YES, AT WHAT TH 1 DEPTH? -6 X DEPTH TO WATER A~ER MONITORING? - 4.6' DATE: 5-30~8 PERO~TION ~TE 5 (min/inch) PERC HOLE DIAMETER 6 inches TEST RUN BETWEEN 2 ~ AND 3 ~ COMM~N~S: Test hole excAvAted b~ O~c~. Test Hole was p~eso~cd before pe~c test. PERFORMED BY: Mike Weir. I CERTIFY THAT THIS TEST WAS PREFACED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDLINES IN EFFECT ON TH~ DATE OF THIS TEST. P.O. BOX 102954 ANCHORAGE, AK 99510 ~ ...... :~O~j' 07/30/08 ISSUED FOR CONSTRUCT,ON PHONE (907) 272-8218 FAX (907) 272-8211 ~..' ~;~ Scale ~bbE Creek Nts lot SA SOILS LOG Anchorage, AK gg516 l~i~¢~S,~~ Sheet SPECIAL PROVISIONS T~)SPECIFICATIONS 1. ALL CONSTRUCTION SHALL BE INSTALLED AS SPECIFIED IN THE MOST CURRENT EDITION OF THE MUNICIPALITY OF ANCHORAGE STANDARD SPEC'IFICATIQNS (MASS) FOR COMPONENT PARTS AND MATERIALS USED IN CONSTRUCTION OF ON-SITE WASTEWATER DISPOSAL SYSTEMS. 2. ALL WORK SHALL BE IN ACCORDANCE WITH THE ATTACHED SPECIFICATIONS. 5. SCOPE OF WORK: 4-BEDROOM HOUSE UPGRADE, NEW 1250g SEPTIC TANK, ABANDON EXISTING TANK PER CODE~ CONNECT TO EXISTING BEDS, ~. GROUNDWATER IS NOT EXPECTED TO BE ENCOUNTERED DURING EXCAVATION, AS EVIDENCED BY THE SOIL TEST HOLE INFORMATION ABOVE 20 FT. IF AN APPARENT WATER TABLE IS OBSERVED IN ANY OF THE EXCAVATIONS LESS THAN 14 FEET BELOW EXISTING GRADE, NOTIFY THE ENGINEER IMMEDIATELY. 5. EXISTING TANK SHALL BE ABANDONED IN ACCORDANCE WITH THE CODE BY PUMPING, CRUSHING, AND FILLING WITH COMPACTED CLEAN EARTH MATERIAL. ADVANTEX 24" PASSIVE 4" JIM CAP AX20 POD iNSULaTED AUXILIARY AIR i 4" PUMP-OUTJ cO i ._ OF 6" PIPE . ~ JOVER THIS CONNECTION 14' TO PROVIDE SHEER PROTECTION - EXTEND TO BRIDGE EXCAVATION ADVANTEX SYSTEM FOR RESERVE FIELD DESIGN PARAMETERS ABBREVIATIONS LEGEND RESERVE SEPTIC SYSTEM CU COPPER w w WATER LINE/ NO. BEDROOM: 4 (600 gpd) DIP DUCTILE IRON PIPE WELL RADIUS TANK SIZE: 1,500 gollon STEP TH TEST HOLE PERC. RATE: 16-50 MPI FC FOUNDATION CLEAN OUT --ss ss -- EXIST'G SEPTIC SOIL RATING: 4 9pd/SF T# TANK CLEAN OUT NO. AREA RQD: 150 SF C# CLEAN OUT NO. -- ss -- ss -- NEW SEPTIC SYS. TYPE: 5'-WIDE, 0.5'ED, MIN LENGTH: 30 LF M# MONITOR TUBE NO. USE: R.I. RIGID INSULATION (~ CHAINLINK FENCE 50LFxS'WIDE,O.5'ED, O' TD DCO DOUBLE CLEAN OUT TOTAL AREA: 150 SF DV DIVERTER VALVE FS FLOW SPLITTER NOTES: PAN-NONE BNO SVC, LLC 07/;0/08 P.O. BOX 102954 ANCHORAGE, Al( 99510 ISSUED FOR CONSTRUCTION PHONE (907) 272-8218 FAX (907) 272-8211 ~r~." %,~:.~ Scale ""A"I ~.I.D. NO Rabbit Creek His, Block 7H, L8A -.:S.t.~¢e.n.~;.C~.n.n.C&8.~ Michael Hauke ~-. CE 8149 .'~ ~ERMtT NO. 7921 Susan Circle fl ~..¢~.. ~'~"~ sw×××x×× DESIGN NOTES Anchorage, AK 99516 Sheet Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program, 4700 South Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 Page 1 of 3 www.ci.anchorage.ak.us (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT Permit Number: SWSW050301 PID Number: 020-114-27 Name: Miehn~l KHnkla Wastewater System: [] New [] Upgrade Address: 119n F I-Ill~mnn I~H gf 9.'~ ~Rt.~ ABSORPTION FIELD Phone: Number of Bedrooms: 34,~=7.q64 ? [] Deep Trench [] Shallow Trench [] Bed [] Mound [] Othe~ Soil Rating: Total Depth from original grade: LEGAL DESCRIPTION 0.6 RPr~/FI2 1.5 Ft. Block: Lot: Subdivision: Depth to pipe bottom from origirtal grade: Gravel depth beneath pipe: 7H 8A Rahhit Creek HeiahL~ 1.0 Ft. 0,~ FI Township: Range: Secgan: Fill added above original grade: Gravel Length: 2'3 Ft, 75, 25 Well: [] New [] Upgrade ~ Fi. 2 11,2 Exist'a Private F,. F, S00 n' 3034 PVC n,. A+ Home Services 8/22/2005 Yield:GPM J Pump Set al: Ft. r casing Height Above Ground:Ft. TANK SEPARATION DISTANCES [] septic [] Ho[ding [] S.T.E.P. [] Other: T~ Tc Septic Absorption LiE Holding 'ublic/Private Manu[ac[urer: Capacity: From~ Tank Field Station Tank Sewer Line Anchorage Tank 1000 w~,, 101.1 154.2 75 Steel 2 SudaceWater 100+ 100+ ~ / LIFT STATION Lot Li~ 40 10 G~. ~Pump on" level at: 'Pump off' level at: I High waler alarm al: 28 80 Curtain Drain ~0 ~0 Pump Make & Model Electrical Inspections per~13ned by: Shortened second field to min lenRth due to extreme BENCH MARK weather conditions. 2" rigid insulation over tank & Back stoop field. Installed double flow splitter to split flow 75/25. ^ssu=ed E~ew,on: ' I00.0 All monitor tubes slotted w/saw. : Engineer's Stamp Inspections performed by: Pannone Eng., LLC Dates: 1't8/22/2005 . .,..,..~.,..,~ 2"d0s/22/2005 ~~.~.~ Development Services De/p~t approval '~',~'~?~'~' Reviewed and approved by: t ~ ~- Date: 'Z~ O~ ~.u2,~c~,,,.(.~:-~r~,-. (Rev. 12/0(I) ~d ~ ~'~>~) .......... PERMIT NO: SW050301 RECORD DRAWl N G P.I.D. NO: 020-114-27 WASTEWATER DISPOSAL SYSTEM SWING TIES LOT 8A BLOCK 7H RABBIT CREEK HTS S/D, co A B NOWELLS or SEPTICS FC 17/I 7.5 T1 32.3 29.6 W/IN 100 FEET OF T2 35.4 24.2 -- ~ -- - PI:{OPOSED~Y-STENF DC 36.4 ~7 ~ DV 37.4 27.5 ~ ~ k% ~I~L ........ __ ~ ~7m --~ ~ - % NBURIED UTILITIES Mt 89.2 95.9 C2 93.2 80.5~%~ ~ , ~ REPLACEMENT SAS M2 94.8 82.2 I 'k~ ~ ~ / 75LFx5'Wx0.5 ED, 1.5' TD Ma ~00.8 0~.4 2$kFxS'Wx0.5'[D, ~.5'TD C4 ~0.2 ~.2 TH2- FLOW SPLICERS. / ,BOTH LEVEL.(FS)-~ ~1(o/ ¢ ~'~~.; 10.0 NO WELLSORSEPTIOS ,0 ¢ W W/IN~00FEETOF ~ ~~ ~ OLD TANK CRUSHED ...... T~ D~ /~ ,, ' -- ~~ -- ;~ ~ EXIST'G BEDS /" ~/'~EW 1000g J ~~ ~ L o IN FAILURE /' ¢./ SEPTIC TANK-~ / / ~~ ,Yo 154.2 / / %~% / 1) All wo~ shall be pe¢ormed in 2, Materials used shallbe in /'00' 1~~ '~ EXlST'G 1000g ac~rdance ~th those specified in lines and water lines, unless noted .~!~7'G [~ ~ othe~ise. //~ELL ~~ ~ ~ ~ '/ X,ST'e 4) Lo' se~ed by commun,~ water ~.~ WELL ~ % ~ ~ - . ¢ / systems. No wells ~hin 100' of ~ $ ~ ~ ~ ~ ~ ~ ~ ~ ~ / ] DEIGN CALCULATIONS: uIr . , ~RCOLATION~TE:16-30MPI / //APPLICATION ~TE: 0.6 GPDSF ' ~/(250 SF/BR) ? //¢ BEDROOMS: 2 ~ ¢ 5-WIDE TRENCH: 0.5' EFF / / / t00 LFx 5' Wx 0.5 ED, 1.5' TD ~ ~ ~ ~ ./" /'/ TO,-ALAREA:o00SF ~.....i.....,(.~......~.....~ /./ /* ~ 1000g SEPTIC TANK (IF RQD) ...... ~.~.~ PREPARED FOR: PANNONE ENG. SVC, LLC ~.~ ~Steven R. Pannone ~ ~ Michael Kunkle P.O. BOX 102954 '~% CE 8149 ..**~ 1120E. HuffmanRd, Suite23 ANCHO~GE, ALAS~ 99510 '**:~"~9~ ~ An~omge, AK 99515 '~ ~%% ~ 345-7964 227-3522 P, 272~218 Fax ~;~ DATE: 8-2805 I PLAN ~ Illl~ SCALE: 1"=40' I PE.U~T.O: SW05030~ RECORD DRAWING DETAILS P.I.D. NO: 020-114-27 WASTEWATER DISPOSAL SYSTEM LOT 8A BLOCK 7H RABBIT CREEK HTS S/D, ' ":':' ~i , ..~ PREPARED FOR: PANNONE ENG. SVC, LLC Michael Kunkle P. O, BOX 102954 '~%~ ~ ~ 1120 E, Huffman Rd, Suite 23 .,-~~.....~.~~ ~ ANCHO~GE, ALAS~ 99510 Anchorage, AK 99515 'e~ .~,:.~..~_ ~ 227-3522 P, 272-8218 Fax ,i~,~~.~ 345-79~ DATE: 8-28-05 DETAILS a ~ ~SCALE: NTS MUNICIPALITY OF ANCHORA GE Development Services Department On-Site Water & Wastewater Program 4700 South Bragaw Street P.O. Box 196650, Anchorage, AK 995¢9-6650 ¢07) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT Upgrade Permit Number: SW050301 Legal Description: RABBIT CREEK HEIGHTS BLK 7 LT 8 Design Engineer: 0062 Pannone Engineering Services Owner Name: MICHAEL KUNKLE Owner Address: 1120 EAST HUFFMAN, SUITE 23 ANCHORAGE , AK 99515-0000 Date Issued: Aug 18, 2005 Expiration Date: Aug 18, 2006 Parcel ID: -9-26-; ;4-27 Site Address: 007921 SUSAN CIR Lot Size: 21901 SQ. FT. Total Bedrooms: 2 Permit Bedrooms: 2 This permit is for the construction of: [] Disposal Field [] Septic Tank [] Holding Tank [] Privy [] Private Well [] Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations ( 18AAC80 ). 3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only ). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. Received By: Issued By: Date: Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program 4700 South Bragaw St. P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (907) 343-7904 ON-SITE SEWEPJVVELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. 020-1t4.27 Permit Number SW Property owner(s) Michael Kunkle Mailing address (1) t120 East Huffman, Suite 23 Day phone 345-7964 Mailing address (2) Anchorage, AK Zip Code 99515 Legal description (Lot, Block & Sub'd.) L8A, BTH rabbit Creek Hts Legal description (Section, Township & Range) Site Address 7921 Susan Circle Lot Size 21901 Acres/Sq. Ft. Number of Bedrooms 2 THIS APPLICATION IS FOR: Sewer Only Sewer and Well Sewer Upgrade THIS PROPERTY CONTAINS: Hot Tub Swimming Pool Therapy Pool [] Well Only [] [] Water Storage [] [] Jacuzzi [] [] Water Softening Unit [] I certify that the above information is correct. I further certify that this application is being made for a Single Fa.~mil_v D~g and is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit Fees: Date of Payment: Receipt Number: (Rev. 12/00) Fees: Date of Payment: Receipt Number: Pannone Engineering Services~ LLC Consulting Engineers (907) 272-8218 P.O. Box 102954 Anchorage, Alaska, 99510 (907) 272-8218 Fax August 18, 2005 Municipality of Anchorage Development Services Department On-Site Water & Wastewater Program 4700 S. Bragaw Street P. O. Box 196650 Anchorage, Alaska 99519 Subject: Lot SA, Block 7H Rabbit Creek Heights S/D Septic System Upgrade Permit Request Ladies and Gentlemen: I am writing to request a permit to construct an upgraded septic system be issued for this property. The proposed systems will serve a proposed three-bedroom house. The existing bed, installed in 1986, is in failure. A diverter valve will be installed between the two fields. The existing 1000-gallon septic tank will be inspected and replaced if necessary. The lot is served by a private water system. 1. Soils. See the attached soils log. Ground water was monitored for 7 days. No ground water was measured in the monitor to a depth of ! 0-12 feet below ground surface. Bedrock was not encountered in the test hole. It is my opinion that the overall soils appearance of the soils, an application rate of 0.6 gallons/day/square feet should be used using standard treatment system. Trench Design. a. Percolation Rate: 16-30 Min Per Inch b. Application Rate: 0.6 gpdpsf c. Number of Bedrooms: 2 d. Design Flow: 300 gallons per day e. Min. Absorption Area: 500 sf f. Total depth: 1.5 feet g. Effective Depth: 0.5 feet h. Width: 5 feet i. Reduction Factor: 0 j. Minimum Length: 100 feet k. Design Length: 150 feet 1. Effective Absorption Area: 750sf m. Septic Tank Size: 1000 gallon (if required) Cont'd on page 2 C: \Work\Letters\8A-7H Rabbit Crk Hts.001.doc Page 2 3. Surface Water: There is no surface water within 100 feet of the proposed system. The proposed systems will maintain at least 100 feet from all surface water and drainage ditches. 4. Topography: The average topography in the area of the proposed septic system is approximately one percent in the area of the existing SAS and 10-12 percent in the area of the proposed upgrade SAS. The proposed installation will not affect the future development of the surrounding or existing lots. There are no wells or septic systems within 100 feet of the proposed septic location. If you have any questions or concerns, please contact me at 227-3522 or 272-8218. Sincerely, Steven R. Pannone, P.E. Civil Engineer Attachments: C: \WORK\LETTERS\8A-7H RABBIT CRK HTS.001 .DOC PERMITNO: DESIGN DRAWING P.I.D. NO: 020-114~27 WASTEWATER DISPOSAL SYSTEM LOT 8A BLOCK 7H RABBIT CREEK HTS S/D, I AREA UNDEVELOPED NO WELLS OR SEPTICS W/IN 100 FEET OF PROPOSEEFS'FSTEIW ~ ~\ \ BURIED UTILITIES · ~ ~ \ ~ PROPOSED REPLACEMENTSAS ~ ~. / \,~ \ ~ ~ 2 EA-75LFx5'Wx0.5 ED, 1.5 ~ ~ EXIST G SEPTIC TH2- ~ / AREA 1~ ~ ¢% / / % , ~ 100 [ ~o~ ~ ~ ~ L ~ ~ ~ ~%' I.-o/ NO WELLS OR SEPTICS . k ~lu~ W/IN100FEETOF ~ ~ I~ ~__~ ~ PROPOSED SYS~M / ~ ~, ~ ~ ~¢ ~ , ~o/~ ~ ~ ~ ~ IN FAILURE 1) ~1 work shall be pe¢ormed in 1 *~ * ~ ~ ' ~ NSTALL BALL-~PE a~ordance with AM015.65. '-;'- '' /!% DIVERTER VALVE 2) Materials used shall be in ~ ~ ~ % ' ~ accordan~withthosespedfied in ~( 's ~ % ~EXIS~G1000g AMC15.65, Wastewater Disposal. / EXI~ ~ ~ SEPTIC TANK , L 2S~SE ~ ' VERIFY INTEGRIW 3)Main~in 10 separation toalllot ~ ~ ~ ~ . · EX ~ T'G ~ '/¢ ~ 4) Lots ,e~d by ~mmun,~ water . /¢ .~J~ ~ -- systems. No wells wi~in 100' of .... ~N~'~' ' ~ ....... T ........... proposed system. ~ ~ ) /' ~ / BESIGN CALCULATIONS: ¢ ~ ~ PERCOLATION RATE: 16-30 MPI ~ ~ APPLICATION ~TE: 0.6 GPDSF (250 SF~R) / / '~ BEDROOMS: 2 ¢ 5-WI~RE~b.5' EFF ~ ~¢~ ~ DEPTH ~ ~ % ~ ¢ ~. 100 LFx 5' Wx 0.5 ED, 1.5' TD ~ "' ~ ~ 1000g SEPTIC TANK (IF RQD) '"'... SVC,,,C '~~¢~'~~. 1120Anchomge,E. HuffmanAK 99515Rd' Suite 23 ANCHO~GE, ALAS~ 99510 ',,~ ~~. 345'7964 DATE:227-35228-16-05 P' 272'~218 Fax a~ SCALE: 1":50' PLAN PERMITNO: DESIGN DRAWING DETAILS P.~.D.,O: 020-~4-27 WASTEWATER DISPOSAL SYSTEM LOT 8A BLOCK 7H RABBIT CREEK HTS S/D, ~ ~ 5 ~ Ill ~ '- ~ ~ I~1 II1~?'~:'. g Z I I .......... ~ ..... ~ PREPARED FO~: PANNONE ENG. SVO, LLO ~~::: ;~I Michael Kunkle P.O. BOX 1020~ ¥~%, _~ .~'.~ 1120E. HuffmanRd, Suite23 ~e~-,,~,.,,,~ ANCHO~GE, ALAS~ 99510 ~.~,~, ~ ~chomge, ~ 99515 ~ ~' ~ 345-7964 227-3522 P, 272-8218 Fax · ~ ~ ~~ DATE: 8-15-05 DETAILS PERFORMED FOR: LEGAL DESCRIPTION: TEST HOLE 1 OR SM/ GM BOH SOILS LOG - PERCOLATION TEST PANNONE ENGINEERING SERVICES P.O. BOX 102954 ANCHORAGE, AK 995'10 (907) 272-8218 Mike Kunkle DATE PERFORMED: 8-11-05 LOT SA, Block 7H Rabbit Creek Hts S/D TOPSOIL Brown St]fy SAND & GRAVEL Silly GRAVEL W/Silt marbling SLOPE X TEST HOLE WAS GROUND WATER ENCOUNTERED? N IF YES, AT WHAT DEPTH? -0-' SITE PLAN TH2 - 7 SLOPE TH1 DEPTH TO WATER AFTER MONITORING? DATE: 8-18-05 WATER READING DATE CLOCK NET TIME LEVEL NET DROP TIME READING I 8-11~)5 11:52 6" O" 2 12:02 10MIN 5~' 5/8" 3 12:02 6" 0" 4 12:12 10 MIN 53" 5/8" 5 12:12 6" O" 6 12:22 10 MIN 53' 5/8" PEROLATION RATE 16 (rain/inch) PERC HOLE DIAMETER 6 inches TEST RUN BETWEEN 2 FT AND 3 FT COMMENTS: Test hole excavated by A+ Home Svc. Test Hole was presoaked before perc test. PERFORMED BY: Steven R. Pannone~ P.E. I CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDLINES IN EFFECT ON THE DATE OF THIS TEST, :)ERFORMED FOR: LEGAL DESCRIPTION: TEST HOLE 2 OR SM/ GM GM BOH SOILS LOG - PERCOLATION TEST PANNONE ENGINEERING SERVICES P.O. BOX 102954 ANCHORAGE, AK 99510 (907) 272-8218 Mike Kunkle DATE PERFORMED: 8-11-05 LOT 8A Block 7H Rabbit Creek Hts S/D Top Soil Silty SAND & GRAVEL Silty Gravel W/ pebbles SLOPE CTEST dOLE \ TH2 WAS GROUND WATER ENCOUNTERED? N IF YES, AT WHAT DEPTH? DEPTH TO WATER AFTER MONITORING? DATE: 8-18-05 SLOPE TH 2 X PEROLATION RATE 16 (min/inch) PERC HOLE DIAMETER 6 inches TEST RUN BETWEEN 5 FT AND 6 FT COMMENTS: Test hole excavated by A+ Home Services. Test Hole was presoaked before perc test. PERFORMED BY: Steven R. pannone~ P.E. I CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDLINES IN EFFECT ON THE DATE OF THIS TEST. i MUNICIPALITY OF ANCHORAGE . ~ DEPII~rMENT OF HEALTH AND HUMAN SERVII~I~ Environmental Health Division ~' 825 "L" Street, Anchorage, Alaska 99502, Telephone 264-4720 '~ ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT Name A~dre~ [ ~0 SEPTIC ABSORPTION Phone{s) No. edrooms WELL Township, Range, Section ~ ' 7[/~(~ ~ ~- / dr,veway,AS'BUILT DIAGRAM [Show ocallon ol well, septic system, prope~y hnes, [oundat,On,water bod,es, etc.) TA.KS ~ SEPTIC ~ HOLDING reeC Mater,al ¢&~f NO. of Comments TYPE OF SYSTEM Q TRENCH ~BED Q W. DRAIN U OTHER ~,.~. WELLS ~RIVATE ~ OTHER {Identilv} Fl FT ., , REMARKS: - 72-0t3 ~3/85) DEPARTMENT OF ~EALTH AN~:ENVZR~NMEMTAL PROTECTION . . . 825 L STRE~T~ ANCHORAGE~ AK ~501 . ,NO: ~860008 ENGINEERED DESIGN bl/O~/8~ PHONE: GARY L KUT'IL 1444o ECHO ~TRE~T 544-9605 8A~, DEGCR,!R: ~ ~,. , i TOWNSHIP: 11N RANGE: ~ ~I.Z.E.,, 22028 (SQ.FT.' OR ACRES) ~T;LOCATION:..' SUSAN AVENUE ~'~J~* ~m ~ami,liap· with. the~requiremmnts £or on-site sewers and wells ~? , ~th, by the. Municipality o~ Anchorage (MOA) and the State~o~A{aska~ ~ I°will-install the system in accordance with all MOA codes and compliance with the.design criteria o~ this permit. to all MOA and State o~ A~aska requirements ~or the ~et~ any existing well~ waste~ater dispdsal s~stem or pob~!~ ~y~te~l on this or any adjacent or nearb~ lot. ,,--. STATION IS INSTALLED IN AN AREA COVERED BY MOA BUILDING CODES~ PERMIT AND INSPECTION MU~T BE OBTAINED;C(2) [.,'BE APPROVED WITHOUT AN ELECTRICAL INSPECTION RERORI; AND ,(5~,~H~ NUST BE DONE BY A LICENSED ELECTRICIAN. .. t'~I¢~NT. GAR.Y L DATE: ') ALASKA ENVIRO~MENTAL · CONTROL SERVICES, INC. ].200 West 33rd Avenue, Suite B ANCHORAGE, ALASKA 99503 (907) 561-5040 CALCULATEDBY ~ CHECKED BY DATE ~:}~.' .',~ i' DEPARTMENT OF HET~LTH ~ND ENVIRONMENTAL PROTECTION ~.~ · T~ ~.~R ~ ~.~LL P~ · T 850~4~ EN81NEERE~ DES ICN 08/~/84 GARY KUTIL- 1~40 ECHO STREET AN~HORAOE, ~AK 544-~05 SECTION: i TONNSHIP: llN RAHGE: 5N 220~8 (SQ. FT. OR ACRES) f.¥ ~ha~ a~.w,ith the requirements fod~on-site sewers and w~l~ ~ ¥ ~he Muntcipal,ity o[ Anchorage (MOA) and ~he 8%ate ~ ~ll ~in~all ~he system in accordance ~i'th ail MOA c~de~ in,compliance ~i~h th~design criteria o~ ~his pep~i~. i~l adher~ tQ ail MOA a~d State o~ Alaska reqUil~emen%s-'~or L .. ,distances f~om any existing ~ell'~ ~astewa~e~ dispo~a! sy~m ~ ....i~i~erage system on ~hi,s or any adjacen~ o~.nea~by lot. I8 I~STALLED IN AN AREA COVERED BY MOA 'BUIL~ PERMIT AND INSPECTION MUST BE'_OBTAINED! NITHOUT AN ELECTRICAL INSPECTION R~PORT~ MU8T BE DONE A LICENSED ELECTRICIAN. DATE= DATE: ALASKA erlUIROIqmE?rlTAL COIqTROL ~n§in¢¢rinq ~- ~nuiro~m~,tal SPECIFICATIONS FOR BED WASTEWATER TREATMENT SYSTEM - LOT 8 BLOCK 7, RABBIT CREEK HEIGHTS 1.0 GENERAL 1.1 THE DRAWINGS, SHEETS i THRU 5, SHALL BE PART OF THIS SPECIFICATION. 1.2 SeRUlCeS, IRC. ALL MATERIALS AND WORKMANSHIP SHALL MEET THE R~QUIREMENTS OF THE MUNICIPALITY OF ANCHORAGE, DEPARTMENT OF HEALTH & HUMAN SERVICES (DHHS), THE CONDITIONS OF THE PERMIT, AND ALL APPLICABLE RULES AND REGULATIONS CURRENTLY IN EFFECT. 1.3 ALL EXCAVATIONS AND DEPTHS ARE ADVISORY, AND ARE TO BE VERIFIED OR MODIFIED IN THE FIELD BY A DHHS APPROVED INSPECTOR. 1.4 IT IS THE RESPONSIBILITY OF THE INSTALLER TO ADHERE TO APPROVED DESIGNS FOR INSTALLATION, TO MAINTAIN THE SPECIFIED SEPARATION DISTANCES, AND TO HAVE THE APPROPRIATE INSPECTIONS. 1.5 THE SEPTIC TANK AND BED SHALL BE A MINIMUM OF i00 FEET FROM PRIVATE WELLS OR ANY BODY OF WATER, 150 FEET FROM CLASS C WELLS, AND 200 FEET FROM CLASS A OR B WELLS. LESS THAN THE REQUIRED SEPARATION DISTANCE MUST HAVE PRIOR APPROVAL OR WAIVER FROM THE APPROPRIATE AGENCY. [.6 IF THE INSTALLATION IS NOT INSPECTED BY AN AECS ENGINEER, AECS WILL NOT BE RESPONSIBLE FOR THE DESIGN. 2.0 2.1 2.2 SEPTIC SYSTEM THE EXISTING SEPTIC TANK MAY BE USED, IF IT MEETS THE CAPACITY REQUIREMENTS FOR THE RESIDENCE AND THE APPROVAL OF DHHS. IF NOT, THEN SPECIFICATIONS 2.2 THROUGH 2.6 APPLY. THE SEPTIC TANK SHALL BE A UPC-APPROVED TWO-COMPARTMENT TANK, CONSTRUCTED OF 12-GAUGE STEEL WITH BITUMASTIC COATING, SET LEVEL ON UNDISTURBED SOIL, AND INSULATED WITH AN OVERLYING LAYER OF 2 INCH BURIAL TYPE POLYSTYRENE. 2.3 THE SEPTIC TANK SHALL BE A MINIMUM OF 5 FEET FROM THE 1200 LU~sl $3rd Aucnue Suite ~, Anchoraq¢, Alaska 9950:~, [907] 561-51~0 2.4 2.5 HOUSE FOUNDATION, AND A MINIMUM OF 5 PEET FROM THE ABSORPTION AREA. PIPING SHALL BE FITTED WITH A MECHANICAL WATERTIGHT CALDER COUPLING ON THE OUTLET AND INLET OF THE SEPTIC TANK. PIPING SHALL BE 4-INCH SOLID PVC ASTM D3034 OR CAST IRON, SLOPED A MINIMUM OF i/4 INCH PER FOOT WITH A MINIMUM OF 4 FEET OF COVER. CLEANOUTS SHALL BE INSTALLED AS DESIGNATED AND CAPPED WITH AIR-TIGHT RAIN CAPS (JIM CAPS OR EQUIVALENT), AND EXTEND A MINIMUM OF 2 FEET ABOVE GROUND LEVEL. 3.0 SEEPAGE BED 3.1 3.2 3.3 3.4 3.5 3.6 THE SAND SHALL HAVE AN EFFECTIVE SIZE OF 0.4 TO 0.6 MM AND A UNIFORMITY COEFFICIENT OF NOT MORE THAN 4. THE GRAVEL FOR THE BED SHALL BE 0.5 TO 2.5 INCH, SCREENED ROCK WITH LESS THAN 3% PASSING ~200 SIEVE RESIDUAL. ALL SUBSTITUTES MUST HAVE PRIOR DHEP APPROVAL. THE BOTTOM OF THE EXCAVATION SHALL BE LEVEL AND RAKED WITH THE BACKHOE BLADE TO INSURE THAT THE BOTTOM HAS NOT BEEN COMPACTED DURING EXCAVATION. THE DISTRIBUTION PIPE SHALL BE 4-INCH RIGID PVC WITH A MINIMUM CRUSH STRENGTH OF 1500 LBS. ALL PIPES SHALL BE LAID LEVEL, AND SPACED ACCORDING TO THE DRAWINGS. MONITOR STANDPIPES SHALL BE PLACED AS SHOWN IN THE DRAWINGS. THEY SHALL BE RIGID PVC ASTM D-3034, OR OR 4 INCH DIAMETER CAST IRON. THE SECTION SHOWN WITH HOLES MAY BE EITHER DRILLED 0.5 INCH HOLES ON THE 6 INCH CENTERS ON OPPOSITE SIDES OF THE PIPE, OR A SECTION OF REGULAR PERFORATED SEWER PIPE MAY BE CLAMPED TO THE SOLID SECTION WITH A NO-HUB COUPLING OR SOLVENT JOINT. A RUBBER RAINCAP (JIM CAP OR EQUIVALENT) SHALL BE PLACED OVER THE TOP OF THE PIPE. IF THE FINAL GRADE OVER THE BED IS LESS THAN 4 FEET ABOVE THE GRAVEL, INSULATION IS REQUIRED, USING DOW EXTRUDED BLUE STYROFOAM BOARD. THERE SHALL BE 1 INCH OF INSULATION FOR EVERY FOOT OF SOIL LESS THAN THE REQUIRED 4 FEET OF COVER, BUT THERE MUST BE AT LEAST 18 INCHES OF 3.7 3.8 SOIL EVEN THOUGH INSULATION IS USED. THE SOLID PIPE EXTENDING FROM THE SEPTIC TANK TO THE DRAINFIELD SHALL ALSO HAVE 4 FEET OF COVER OR AN EQUIVALENT LAYER OF INSULATION COMBINED WITH SOIL TO PREVENT FREEZING OF THE LINE. IF INSULATION IS NOT NECESSARY, THEN THE GRAVEL MUST BE COVERED WITH A LAYER OF A NONWOVEN FABRIC (SUCH AS MIRAFAI, FIBRETEX 200 GRADE, POLY-FILTER X, OR EQUIVALENT). THE TOP AND SIDES OF THE BED SHALL BE PLANTED WITH A WHITE CLOVER AND RED FESCUE MIX OR BLUE GRASS. 4.0 INSPECTIONS 4.1 4.2 4.3 THIS BED WILL REQUIRE THREE INSPECTIONS. THE FIRST INSPECTION WILL BE OF THE OPEN EXCAVATION, TO ASSURE THAT THE SYSTEM IS INSTALLED IN PROPER STRATA AND DEPTH. THE SECOND INSPECTION WILL BE PERFORMED AFTER SAND FILL IS INSTALLED, BUT PRIOR TO PLACEMENT OF GRAVEL AND DISTRIBUTION PIPES. THIS INSPECTION WILL VERIFY THAT THE FILLER IS PROPERLY INSTALLED, THAT IT MEETS SPECIFICATIONS AND THAT IT FULFILLS THE INTENTION OF THE DESIGN. THE THIRD INSPECTION WILL BE TO VERIFY THAT DISTRIBUTION PIPES ARE POSITIONED PROPERLY, SUFFICIENT GRAVEL IS PLACED, AND INSULATION/BARRIER MATERIAL IS PRSENT, PRIOR TO BACKFILL. ~' ALASKA ENVIRON~ANTAL S,EETNO OF ~' CONTROL SERVICI~INC. · t 1200 West 33rd Avenue, Suite B CALCULATED BY DATE. ~-~"~/~-- ~" ~- 'ANCHORAGE, ALASKA 9950.3 (907) 561-5040 CHECKED BY DATE. ALASKA ENVIROf~ii~NTAL CONTROL SERVIO~, INC. 1200 West 33rd Avenue, Suite B ANCHORAGE, ALASKA 99503 (907) 561-5040 SHEET NO,/' ~ CALCULATED BY CHECKED BY DATE ALASKA ENVIRONI~II~ITAL CONTROL SERVICEI~RNC. 1200 West 33rd Avenue, Suite B , 'ANCHORAGE, ALASKA 99503 (907) 561-5040 CALCULA~EO BY OF ~ CHECKED BY. DATE ALASKA ENVIRONI~I~TAL CONTROL SERVICII~FINC. 1200 West 33rd Avenue, Suite B ANCHORAGE. ALASKA 99503 (907) 561-5040 JOB SHEET NO CALCULATED DATE Munlclpallly of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST (ENGINEER'S~.~AL) LEGAL DESCRIPTION: ~,1~. ~+~ ~b~ Township, Range, 2 3 4 5 -'7-/? 9- 10- 11 13- 14- 15- 16- 17- 18- 19- 20- COMMENTS WAS GROUND WATER ENCOUNTERED? IF YES, AT WHAT Depth to warn' A~_,t Gro~s Net Oeoth to Net Reading Date Time Time Water Drop +tho I -/-I-z_ Iooo-~ I~ ,S'%C.~! PERCOLATION RATE -j~:2~:~,mm~l~6ch) PERC HOLE DIAMETER 72-008 {Re~ 4 85, WATER WELL RECORD STATE OF ALASKA DEPARTMENT OF NATURAL RESOURES Division of GeologicDI a Deophysicol Surveys Drilling Permit No. LOCATION OF WELL {Please complete either ia, lb or lc.) A.D.L. NO.  OlSTANCE AND DIRECTION FROM ROAD INTER~ECTIONS S. OWNER OF WELL: Rabbit Creek Heights Sub. Address: Street Address and A~eo of Well Location 2 WELL LOG Feet ~elew Surface 4. WELL DEPTH: (final) 5. DATE OF COMPLETION gravely 20 55 boulders 2~-2~' brn till 55 70 ~ m.,~w.i, ~ O,h.~: silt~ sand hard p~ 135 1 ~7 *i~. i.. ~0 .. o.,,~ S,,~k.p -~. cemente~ lenses 1 ~7 1 AP 9. FiN'SH OF WELL: Sial/Mesh Size: Lenglh ~ Above or ~ Below land surface Dote DEPT. U~ MAY Material: ~ Heat Cement ~ Other: 15. Water Temperature o ~ F ~ C Ala~_Now-well/Ve~,s Drilling & ~t ~ ~27 .... '-.--J~ Avion ~chora~e. ~ 99516 Lng c Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program 4700 South Bragaw Street P,O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (907) 343-7904 CERTIFICATE OF HEALTH AUTHORITY APPROVAL FOR A SINGLE FAMILY DWELLING Parcel I.D. 020-tt4-27 1. GENERAL INFORMATION Complete legal description Location (site address or directions) Expiration Date: Lot 8A Block 7H Rabbit Creek Heights 792'1 Susan Circlet Anchorafle~ AK Current Property owner(s) Mailing address Lending agency Michael Kunkle Day phone 345-7964 112 E Huffman Ste 23~ PMB 4t4~ Anchora.qe~ AK 99515 Day phone Mailing address Real Estate Agent Day phone Mailing Address Unless otherwise requested, HAA will be held by DHHS for pickup. HAA picked up by: NUMBER OF BEDROOMS: 2 3. TYPE OF WATER SUPPLY: Individual Well Individual Water Storage Community Class Public Water System Well TYPE OF WASTEWATER DISPOSAL: [] Individual On-site [] [] Individual Holding tank [] [] Community On-site [] [] Public Sewer [] The Municipality of Anchorage Development Services Department (DSD) Issues Certificates of Health Authority Approval (HAA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. Certificates of Health Authority Approval are required for the transfer of title (except bet~veen spouses) on properties served by a single family on-site wastawater disposal and/or water supply system. DSD also issues HAAs upon request to home owners. Certificates of Health Authority Approval are valid for 90 days from the date of issue for properties served by a private or Class C well and may be reissued with new water sample results less than 30 days old. Certificates are valid for one year for properties served by Class A or B wells or a public water system. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation based on procedures outlined in the Health Authority Approval Guidelines for this Health Authority Approval application shows that the on-site water supply and/or wastewater disposal system is safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on- site water supply and/or wastewater disposal system is in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm Pannone En.q. Svc. Phone 272-8218 Address P.O. Box 102954, Anch, AK 99510 Engineer's Printed Name Steven R. Pannone, P.E. Date 10/2012005 Engineers Comments: In conducting an adequacy test, I attempt to provide a thorough, conscientious engineering analysis of the system in accordance with MOA DSD Guidelines & Regulations. The ~,~'~_ reported results describe the performance of the system ander the condiuons encountered at the t~me of the test, ~d separation distances measured to readily identifiable features. The operational life of all wells and septic systems depend on the local soil condition, ground water levels that may fluctuate ~a~ during the year, and the water usage of the family being served by the system. These conditions are ~ outside the control of the evaluator of this system. All systems eventually fail and satisfactory test results ~ ...... do not guarantee future performance of the systc~n, nor do they guarantee that there are no h~ddan defect~.'~.., or encroachments. PES can therefore not provide any warranty for future _nefformance nor ~ive anv. ~,,.. ~ ,_, estimate of how long the system will continue to meet the operational requirements of the ADEC or '~'~.%. MOA DSD. The contant of this r oft is for the sole benefit of the owner listed above. Any rehance u~on or use of th,s report by any other person or party ,s not authorized nor will it confer any legal right whatsoever. *,~- 'u _/C~.~:'"""" 5. S ON^TURE b'~ Approved for ~ bedrooms. Disapproved. Conditional approval for __. bedrooms, with the following stipulations: Additional Comments Attachments: HAA Checklist Septic System Advisory Well Flow Advisory Expiration Date: (Rev. 11/go) X : WASTEWATER : .., Maintenance Agreements z~)))))}))))))l. Supplemental Engineer's Report Other Original Certificate Date: [ cO -~,T ~'- 0 ~- Reissue Date: Pannone Engineering Services, LLC Consulting Engineers (9071 272-8218 P.O. Box 102954 Anchorage, Alaska, 99510 (907} 272-8218 Fax October 20, 2005 Municipality of Anchorage Development Services Department On-Site Water & Wastewater Program 4700 S. Bragaw Street P. O. Box 196650 Anchorage, Alaska 99519 Subject: Lot 8A, Block 7H Rabbit Creek Heights S/D Un-Conditional Health Authority Approval Request Ladies and Gentlemen: I am writing to request that an Un-Conditional Health Authority be issued for the above property. Your Department issued a Conditional Health Authority on September 20, 2005 based on the condition that the Engineer "Monitor water levels in the lower trench thru October 15, 2005. Relocate trench if any liquid appears" I have monitored the liquid levels in the lower trench on a weekly basis since the conditional approval was issued. As of October 15, 2005, the monitor tube in the lower trench has been and continues to be dry. Therefore, I request the issuance of an Un- conditional Approval and authorization to release the monies held in escrow. If you have any questions or concerns, please contact me at 227-3522 or 272-8218. Sincerely, Steven R. Pannone, P.E. Civil Engineer Attachments: C:\Work\Letters\8A-7H Rabbit Crk Hts. 002.doc Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program 4700 South Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 www.ci,anchorage.ak.us (907) 343-7904 CERTIFICATE OF HEALTH AUTHORITY APPROVAL FOR A SINGLE FAMILY DWELLING Parcel I.D. 020-57t-09 1. GENERAL INFORMATION Complete legal description Expiration Date: / ~ - ~ O - cO _5- Lot 8A Block 7H Rabbit Creek Heights Location (site address or directions) 792t Susan Circle, Anchora,qe, AK Michael Kunkle Day phone 345-7964 1120 E Huffman Ste 23~ PMB 414, Anchora.qet AK 99515 Day phone Current Property owner(s) Mailing address Lending agency Mailing address Real Estate Agent Mailing Address Day phone Unless otherwise requested, HAA will be held by DHHS for pickup, HAA picked up by: NUMBER OF BEDROOMS: 2 TYPE OF WATER SUPPLY: Individual Well Individual Water Storage Community Class __ Public Water System Well TYPE OF WASTEWATER DISPOSAL: [] Individual On-site [] [] Individual Holding tank [] [] Community On-site [] [] Public Sewer [] The Municipality of Anchorage Development Services Department (DSD) Issues Certificates of Health Authority Approval (HAA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. Certificates of Health Authority Approval are required for the transfer of title (except between spouses) on properties served by a single family on-site wastewater disposal and/or water supply system. DSD also issues HAAs upon request to home owners. Certificates of Health Authority Approval are valid for 90 days from the date of issue for properties served by a private or class c well and may be reissued with new water sample results less than 30 days old. Certificates are valid for one year for properties served by Class A or B wells or a public water system. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. (Rev. 11/99) 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation based on procedures outlined in the Health Authority Approval Guidelines for this Health Authority Approval application shows that the on-site water supply and/or wastewater disposal system is safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on- site water supply and/or wastewater disposal system is in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm Pannone Enfl. Svc. Phone 272-82t8 Address P.O. Box 102954, Anch~ AK 99510 Engineer's Printed Name Steven R. Pannone, P.E. Date 9/2012005 En ineers Comments: In conducting an adequacy test, I attempt to provide a thorough, conscientious g . · . . .*~ ? / en ineerin aaa s s of the s stem in accordance w~th MOA DSD Guldehnes & Regulations. The g g Y . Y ,. . r orted results describe the erformance of the system under the conditions encountered at the time of the test~ and separatton &staaces measured to readily ldentffiable features. The operational hfe of all wells and septic systems depend on the local soil condition, ground water levels that may fluctuate nn the ear aad the water us eofthefam y bmng served by the system These cond]ttons are du g y , ag . . ~ outside the control of the evaluator of this system. All systems eventually fall and satisfactory test results ~ do not uarantee fi~ture performance of the system, nor do they guarantee that there are no hidden defects_~r.~__~. ~ g . or encroachments PES can therefore not provide any wammty for future perforrnaace nor give any ~~eq-3. I~n tn estimate of how long the system will conttnue to meet the operational reqmremaats of the ADEC or MOADSD The contentofthisrepor[is for thesolebaaefitofthe owner listed ahove Any reliaace upon or use of this report by any other person or party ,s not authorized nor wall ,, confer any legal right whatsoever. 6. DSD SIGNATURE Approved for Disapproved. x Conditional approval for Monitor water level in lower trench thru 15 Oct 05. bedrooms· 2 bedrooms, with the following stipulations: Relocate trench if any liquid appears. Money to placed in escrow in the amount of $5,000.00. Money in escrow shall not be released until this office has given final approval. The work shall AddifionalGomments be comoleted no later than 15 Jun 06. Attachments: HAA Checklist Septic System Advisory Well Flow Advisory Expiration Date: (Rev. X Maintenance Agreements Supplemental Engineer's Report Other Original Certificate Date: Reissue Date: Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewatar Program 4700 South Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (907) 343-7904 HEALTH AUTHORITY APPROVAL CHECKLIST Legal Description: A. WELL DATA Well type P Date completed 3/611986 Total depth 142 ft Date of test Static water level Well production WATER SAMPLE RESULTS: Coliform 0 colonies/100 mi Date of sample: 513012005 B. SEPTIC/HOLDING TANK DATA Tank Type/Material Steel Lot 8A Block 7H Rabbit Creek HeiRhtS If A, B, or C provide PWSID # __ Sanitary seal Y_ Cased to 140 ft FROM WELL LOG 31611986 0 ff 9.6 g.p.m Parcel i.D.: 020-'114-27 Well Log _Y. Wires properly protected _Y Casing height (above ground) 48 in. AT INSPECTION 512812005 0 ff 7.6+ g.p.m Nitrate 2.37 mg/I Other bacteria 0 colonies/100 mi Collected by: Laura Pannone Arsenic NIA mg/I Date installed 8/22/2005 Tank size 1000 Cleanouts Y Foundation cleanout Y Date of pumping Pumper New C. ABSORPTION FIELD DATA Date installed 8122/2005 Soil rating (g.p.d./ft't or ft2/bdrm) 250 Length 75125 ff Width 515 ft Effective absorption area 500 f~ gal Number of Compartments 2_ Depression over tank N High water alarm NIA Total depth 1.511.5 ft Date of adequacy test 812212008 Results (Pass/Fail) Pass Fluid depth in absorption field before test new in Water added Elapsed Time: 0 min Final fluid depth 0/0 in Any rejuvenation treatment (past 12 mo.) (Y/N & type) No (Rev. 11/99) Monitoring tube Y/Y Depression over field NIN For _3 bedrooms ~ gal. New depthnew in. Absorption rate >= 450+ gp.d. If yes, give date System type 5-wide trench Gravel below pipe 0.510.8 ft D. LIFT STATION Date installed "Pump on" level at __ Datum Size in gallons in"Pump off' level at Cycles tested E. SEPARATION DISTANCES SEPARATION DISTANCES FROM WELL ON LOT TO: Septic tank/lift station on lot 100 Absorption field on lot 154 Public sewer main 100+ Sewer/septic service line 50+ in Manhole/Access High water alarm level at __ in Meets alarm & circuit requirements? On adjacent lots 100+ On adjacent lots 100+ Public sewer manhole/cleanout Holding tank 100+ SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Building foundation 20+ Water main 100+ Drainage 100+ 100+ Absorption field 6 Surface water 100+ Property line 25+ Water service line $0+ Wells on adjacent lots 100 SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Water main 100+ Driveway, parkingA, ehicle storage 40+ Property line 10 Water Service line 50+ Curtain drain 40+ F. COMMENTS New field installed 8/22/05. Building foundation 80 Surface water 100+ Wells on adjacent lots 100+ G. ENGINEER'S CERTIFICATION i certify that I have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA HAA guidelines in effect on this date. Engineer's Printed Name Steven R. Pannone, P.E. Date 8128105 HAA Fee $ Date of Payment Receipt Number (Rev. 1'1/99) I1 ). Waiver Fee $ Date of Payment Receipt Number 9~ SURVEY CERllFICAllON ~ LOT SURVEY :SURVEY 'FYPE PLOT PLANS & LOT' SURVEYS F RObert Prepared by Johns, & Assoc, Profession(il Land Surveyors Dote Surve~d: '7 2 0 0 ~ Drown by: i~ELT Checked by Dote Orewn: '/--~'*05 [~rd: 3340 [w'°' 25-214 Lot SA, Block 7H P.a. bb~lt Creek Heights SYMBOLS · SET REOAR ~--~ ~ DRAiNAOE ~ ASPNALT o FOUND REBAR O o O WOOD FENCE ~ CONCRETE ~0~ ASSUN~ED ELEV, ~Y~g(-. X METAL FENCE F/~'~F/rJ} ~OOb DECK NOTE: ONLY THOSE [MPRO¥'EMENTS ABOVE GROUND AND ~Sl8LZ WiLL BE SHOWN, FENCES, WELLS~ SEPIDC CLEANOUTS, SIDEWALKS, DR!~WAYS, ETC., .ARE SHOWN IN THEIR APPROXIMATE LOCATION, ONLY, SNOW MA,\' PREVENT SOME IMPROVEMENTS FROM BEINO SEEN AND LOCATED. ALL DISTANCES ARE ~ECORD UNLESS OTHERWISE NOTED. Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program 4700 Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 www. ci.anchorage.ak.us (907) 343-7904 Waiver Review Worksheet WR#: 050058 PID#: 020-571-09 HA#: 050318 Permit~: Date Received: 7-28-05 Legal Description: Rabbit Creek Heiqhts Block 7H Lot 8A Engineer: Pannone EnRineerinR P.O.Box 102954 Anch. Ak. 999510 Applicant: Michael Kunkle Waiver Requested: 5 feet separation distance alJsorpfion field to property line. Criteria: Geology Points: A. Water Table B. Soil Sorption C. Permeability D. Water Table Gradient E. Horizontal Separation Total: Waiver is Granted: ~ Waiver is not Granted: List Conditions or Reasons for above: F---/I~ of Reviewer Rec#: ?/~'$;CAmount: $. / '~,~ Date Paid: ?12812005 Municipality of Anchorage ILO. Box 196(350 ' Anchoragc, Alaska 99519-6650 , Telephone (907) ~3/~-8~3()1 · rax (907) Mayor Mark Begich Bt~g S~e~ I~xSsion 7/28/2005 Pannone Engineering P.O. Box 102954 Anch. Ak. 99510 Subject: Dear Steve Parmone: Waiver Request for Rabbit Creek Heights Block 7H Lot 8A Waiver Request #WR050058 ~t~5IoI~ 1~ 8020-571-09 /~-~'-~ ~i~3 ~5. jge ~---~ Your request for a waiver of the required 10 feet horizontal separation from the absorption field to property line has been approved. The approved separation distance is 5.0 feet. This waiver approval applies to the existing absorption field to property line separation only. Any future upgrade to the on-site wastewater disposal system will require all separation distances be met or another approval from this department. If there are any further concerns or questions regarding this waiver, please call our office at 343-7904. Sincerely, Jeffrey W. Poet Engineering Technician On-Site Water & Wastewater Program Community, Security, Prosperity MUNICIPALITY OF ANCHORAGE Department of Health & Human Services DIVISION OF ENVIRONMENTAL SERVICES 343-4744 CERTIFICATE OF INSPECTION FOR HEALTH AUTHORITY APPROVAL OF ON-SITE SEWER AND WATER FACILITY FOR SINGLE FAMILY DWELLING Parcel I.D # ,(-'%.~ ~) -- ~ ~ L\ - ~.~'-~ HAA# GENERAL INFORMATION (Must be completed prior to submittal) (a) Legal Description (include lot, block, subdivision, section, township, range) Lot 8; Bloc~ 7; Rabbit Cre~H~ights Subdivision; Location (address or directions) 7921 Susan Circle (b) Property owner H.U.D. I11-032015-703 Mailing Address · Telephone: (home) Business (c) Lending Institution Mailing Address Telephone (d) Real Estate Company and Agent Address 640 W¢~t 36th Avenue Telephone 563-3333 (e) Mail the HAA to the following address: (or check here,(~ if hold for pick up.) List contact person and day phone number below: ASSOCIATED BROKERS ATTN: Sandy Hjolmstad Sure One Anchorage. Ak. 99503 S & S ENGINEERING 17034 Eagle River Loop Road Eagle R~ver, Alaska ~257Z 2. TYPE OF RESIDENCE Single-Family E~X Number of bedrooms 3. WATER SUPPLY Individual Well ~3~ Community [] Public [] Note: If community well system, must have written confirmation from the State Department of Environmental Conservation attesting to ih legality and status. 4. SEWAGE DISPOSAL On-site.lO( Public F1 Community [] Holding Tank [] Note: If community well system, must have written confirmation from the State Department of Environmental Conservation attesting to the legality and status. 72-025(Rev. 7/88} Page 1 of 2 ~ Io ~ O6ed 'HJot~ s,~aeu!t~ue leUO!SSelo~d eql u! suo!ss!uJo Jo s~o~e ~ot alq!suodsaJ lou s! @SeJoqouv lo/~l!led piu nJN eql 'penss! s! eleoil!lJeo ~ aJoj@q elep ez,~ieue Jo suoRoedsu! lonpuoo lou op SHHC] lo see,~OldCU=! 'sluetue~inb@J elels pub I~epel u!8l.leo Aisle,s ol Jap Jo u! suo!~nl!lsu! 8uipuel J!eql pu~ secuoq ~o sJes~qo~nd o~ ,iselJnoo ~ se s!ql seop SHHC] eq± 'e~selV ~o a~IS eq~ u! peJe),s!t~e~ ~eeu!l~ue leuo!sseloJd luepuedepu! ue,~q a^oqe ~ qd~lSe~ed u! ue^i8 suo?,~lueseJde~ eq~ uodn ,~lUO pes~q pe~o!lp@o le^mddv/9,poqlnv qlleeH sanss! (SHHQ) seo!^~@S uecu nH pue qll~eH Jo lUeLUlJedeQ eS~oqouv lo,~liledp!un~ aqJ. leAoJddv I~UO!l!puoo ,to SLuJe.I. leuog!puoo -- p@AoJddesfQ ~X~ peAoJddv T~AOhldd'~ SHHO '9 ~OlAR 2 7 1991 MUNICIPALITY OF ANCHORAGE (MOA) Health Authority Approval (HAA) CHECKLIST - FEBRUARY 1984 343-4744 Legal Description: Am WELL DATA Well Classification lo_c.K' If A, B, C, D.E.C. Approved (Y/N) ~_ Well Log Present (Y/N) Total Depth /L/2 Cased to Static Water Leve"~"FIo~,,~, ~ocr '-kP Casing Height Above Ground Electrical Wiring in Conduit (Y/N) SEPARATION DISTANCES FROM WELL: To Septic/Holding Tank on Lot / 04 To Nearest Edge of Absorptior~ Field on Lot To Nearest Public Sewer Line To Nearest Sewer Service Line on Lot Water Sample Collected by ~ Date Completed ~ - //-'/0' Depth of Grouting Yield Pump Set At Sanitary Seal on Casing (Y/N) H Depression Around Wellhead (Y/N) hJ ; On Adjoining Lots { 0 '~ ; On Adjoining Lots To Nearest Public Sewer Cleanout/Manhole Water Sample Test Results Corn ments'7~ '~1~/~ ~L,,&~_...~ B. SEPTIC/HOLDING TANK DATA Date Installed ~-,/~- ~Size ! ~ ~-I No. of Compartments Standpipes (Y/N) c[ Air-tight Caps (Y/N) cl. Depression over Tank (Y/N) ,ti Pumping/Maintenance Contact on File (Y/N). Holding Tank High-Water Alarm (Y/N) ~//~ SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK: To Water-Supply Well To Property Line To Water Main/Service Line ,¥ To Stream, Pond, Lake or Major Drainage Course Comments .:~,~ p"~ c.. I~0 ,~ ¢)~0/ ~)~ Foundation Cleanout (Y/N) Date Last Pumped ~, - ~' J~,)/iA ;for Temporary Holding Tank Permit (Y/N) To Building Foundation To Disposal Field / O0 't 72-026 {Rev 7/88) Front Page 1 of 2 C. ABSORPTION FIELD DATA Soils Rating in Absorption Strata Date Installed ! - ~- ~:)~ Width of Field / C) '/- /' 0 Square Feet of Absortion Area ~ ~5~ ~) ~ravel ~//~ ~,, Type of System Design Length of Field Depth of Field Bed Thickness Statndpipes Present Depression over Field (Y/N) ~ Date of Last Adequacy Test '-~ ~ 2 % - ~) Results of Last Adequacy Test ,~¢~+l:<.,Yr,4c._~e¢,~ - ~ SEPARATION DISTANCE FROM ABSORPTION FIELD: To Water-Supply Well TO Building Founfation Lot To Water Main/Service Line To Stream, Pond, Lake, or Major Drainage Course To Driveway, Parking Area, or Vehicle Storage Area To Property Line ~ © / To Existing or Abandoned System on ; On Adjoining Lots ..~O ~"f TO Cutback (if present) ~ ~ D. LIFT STATION Date Installed Size in Gallons "Pump On" Level at High Water Alarm Level at Tested for Meets MOA Electrical Codes Comments Dimensions Manhole/Access (Y/N) "Pump Off" Level at Vent (Y/N) Pumping Cycles during Adequacy Test, **Check Permitted Bedroom Rating Against HAA Request** I certify that I have checked, verified, or conformed to all MOA and HAA guidelines in effect on inspection. Signed Company Date MOA No. 5 & 5 ENG~N~ER~'NG t 7034 Eagle River Loop Road No. 204 of this Receipt NO. ~ ~'~' Date of Payment Amount: $ ~, -'1 r~'~ 72-026 (Rev. 7/88) Back Receipt No. Waiver Fee: $ Date of Payment Page 2 of 2 OMUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION DIVISION OF ENVIRONMENTAL HEALTH CERTIFICATE OF INSPECTION FOR HEALTH AUTHORITY APPROVAL OF ON-SITE SEWER AND WATER FACILITY 264-4720 Application Date GENERAL INFORMATION (a) Legal Description (include lot, block, subdivision, section, township, range) I-~:7~' :Y ~z~ <~. '? Location (address or directions) (b) Applicant Name ~'~d)~/ Z /~(~Z¢ Telephone: Home. ~ r~ ~ ZT~ Business Applicant Address (c) Applicant is (check one): Lending Institution ~; Owner/builder~; Buyer D; Other ~ (explain); (d) Lending Institution Address Telephone (e) Real Estate Company and Agent d~[, ;/%~ .I Address Telephone (f) Mail the HAA to the following address: TYPE OF RESIDENCE Single-Family~ Multi-Family [] Number of Bedrooms Other WATER SUPPLY Individual Well~, Community [] Public [] ~- Note: If community well system, must have written confirmation from the State Department of Environmental Conservation attesting to the legality and status. SEWAGE DISPOSAL Onsite~,: Public [] Community [] Holding Tank [] Note: If corn mueity well system, must have written confirmation from the State Department of Environmental Conservation attesting to the legality and status. Page 1 of 2 72-025 (11/84) ENGINEERING FIRM PROVIDI INSPECTIONS, TESTS, FILE SEARCH, D~ AND INFORMATION As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation of this Health Authority Approval shows that the on-site water supply and/or wastewater disposal system is safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is in compliance with all Municipal and State codes, ordinances, and regulations in effect on the date of this inspection. , Name of Firm Telephone . Address /',';¢'¢~' ,tv// ..~_~,.,49 ~--~,//"~"'~ ~ [ / 6. DHEP APPROVAL Approy~d for ~"-~'~-~-~-:~//bedrooms by (..~pproved.~ /~ Disapproved Terms of Conditional Approval Conditional CAUTION The Muncipality of Anchorage Department of Health and Environmental Protection (DHEP) issues Health Authority Approval certificates based solely upon the representations given in paragraph 5 above by an independent professiona~ engineer registered in the State of Alaska. The DHEP does this as a courtesy to purchasers of homes and their lending institutions in order to satisfy certain federal and state requirements. Employees of DHEP do not conduct inspections or analyze data before a certificate is issued. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. Page 2 of 2 72-025 (11/84) MUNICIPALITY OF ANCHORAGE (MOA'~ HEALTH AUTHORITY APPROVAL (HAA) CHECKLIST- FEBRUARY 1984 MUNICIPALITY OF ANCHORAGE DEPT. OF HEALTH & ENVIRONMENTAL PROTECTION 264-4720 Le?l Description: WELL DATA Well Classification '7~/~*? K'"/f~/~'"' If A, B, C, D.E.C. Approved (Y/N) Well Log Present(~_N) Date Completed --~-~- ~G YiCd Total Depth /¢~ _ C~-to--/~. Depth of~routing W~- ~ Stabc Water Lev~q ~,~ ~~At _ ~// Casing Height Above Ground ~ ~ Sdnitary'$eal on Casing~N) _ Electrical Wiring in Conduit~N) Depression Around Wellhead (Y~ Separation Distances from Well: To Septic/Holding Tank on Lot /~"Y To Nearest Edge of Absorption Field on Lot To Nearest Public Sewer Line Cleanout/Manhole Water Sample Collected by Water Sample Test Results ; On Adjoining Lots ; On Adjoining Lots To Nearest Public Sewer To Nearest Sewer Service Line on Lot /¢' ¢J/~/ ;Date ~.~- 7~--0'~ Comments B. SEPTIC/HOLDING TANK DATA Date Installed 5 '-/~ ' '¢5//¢ Size /~'¢'¢ ~"¢'~ No. of Compartments ~ Standpipes ~N) Air-tight Caps~,l) Foundation Cleanout Y~) Depression over Tank (Y/~h Date Last Pumped /f///¢/ Pumping/Maintenance Contract on File (Y/N) ,4//~ ; for ,~/A Holding Tank High-Water Alarm (Y/N) /J//~ Temporary Holding Tank Permit (Y/N) '4//h Separation Distances from Septic/Holding Tank: To Water-Supply Well To Property Line To Water Main/Service Line Course /o~ / -/~ To Building Foundation To Disposal Field To Stream, Pond, Lake, or Major Drainage Comments Page 1 of 2 72-026(11/84) C. ABSORPTION FIELD DATA Soils Rating in Absorption Strata Date Installed /" 'Y ~ ~ Width of Field ,/~2 / /7> Square Feet of Absorption Area Depression over Field (Y~ Results of Last Adequacy Test Separation Distance from Absorption Field: To Water-Supply Well To Building Foundation /~/~'~ ~ Lot ,,~//~ To Water Main/Service Line /'//,'~ To Stream/Pond/Lake/or Major Drainage Course To Driveway, Parking Area, or Vehicle Storage Area Type of System Design ,Z---- Length of Field .~/ / '~ Depth of Field ,.~ ¢_5'; Gravel Bed Thickness ~" Standpipes Present ~) Date of Last Adequacy Test /'/'/-~ To Property Line / 0 To Existing or Abandoned System on / ; On Adjoining Lots /d-~' 7 To Cutbank (if present) LIFT STATION SiT in G_.al, l,°.ns , , ~ "Pump On Level at High Water Alarm Level at Tested for Electrical Codes (Y/N) Comments Dimensions Manhole/Access (Y/N) "Pump Off" Level at Vent (Y/N) .uring Adequacy Test. Meets MOA ** Check Permitted Bedroom Rating Against HAA Request SignedlCertifythat I~v~chec/~ed,,~e~._ed,orconformedtoall MOAand HAAguidelinesineffectonthedateofthisinspection. ~c~_----~, ~e_~d,~ Date Company /z~ ~-~, ~' MOA No. Receipt NO. %~ ~C'i ~ Date of Payment ~ ~' Page 2 of 2 ALASKA ENVIRONMENTAL CONTROL SERVI~I~, INC. 1200 West 33rd Aven~, Suite B ANCHORAGE, ALASKA 99503 (907) 561-5040 JOB SHEET NO CALCULATED 8Y OF DATE /~ 30 DATE