November 11, 2009
W.O.06754
Mr. Ross Noffsinger, P.E
Municipality of Anchorage
Dept. of Development Services
PO Box 196650
Anchorage, Alaska 99519-6650
RE: Preliminary Plat - End of the Road (S-11592)
Soils Investigation Report for On Site Septic Systems
Dear Mr. Noffsinger,
The following report is being submitted for your review and approval in accordance with AMC
21.15.110 and AMC 15.65.180. This project is located in the southeast corner of Section 6, T12N,
R3W. (Reference plat numbers 97-113 and 99-133). This subdivision consists of a 45.7 acre tract
which is being subdivided into 5 lots and two small tracts (see Appendix'A,' Figure 1). The lots range
in size from 3.5 to 11.5 acres with the average lot size being about 9 acres.
Of the five lots being created by this plat, two of the lots have existing homes with approved septic
systems and wells (see Appendix 'C'). As such, test pits were dug on only three of the five lots (Lots
1, 3, & 4). No testing was conducted on the two small Tracts (Tract A and B), since they cannot be
developed. Test pits were dug to a minimum depth of 16.5 feet, or to 2' below the water table (where
water was encountered) using a track mounted Hitachi backhoe. Soils were visually classified, and a
four inch perforated monitoring tube was placed in each test pit.
The soils consisted primarily of slightly silty sands to slightly silty sandy gravels which were overlaid
by a foot of organic sands/silts and root material. No bedrock was encountered in any of the holes.
Detailed soils information for each lot can be found on the Soils Log in Appendix 'B'.
Percolation tests were performed on each lot in accordance with MOA guidelines. The soils on each
lot percolated at rates around 1 minute per inch. For those lots which percolated faster than 1 minute
per inch, a sand filter will be required; however, the existing material will most likely meet M.O.A.
gradation requirements for sand filters.
Small seeps of water were initially encountered on lots 3 and 4. Both of these seeps stopped flowing
within a short time of being exposed. After monitoring over several years (through the spring,
summer and fall), groundwater was present only on Lot 1. The water level after monitoring for Lot 1
was 13.0 feet below the surface.
Dimond Center Tower, 5" Floor • 800 East Dimond Blvd. Suite 3-550 • Anchorage, Ak. 99515
Ph (907) 344-1385 • Fax (907) 344-1383 • Email: admin@dhialaska.com
SERVING ALASKA SINCE 1985
Based on the percolation rates, AMC Title 15.65.180.B.1 (Subdivision Standards), Table 2, requires
all lots have a minimum of 10,000 square feet. Figure I (Appendix'A') shows the location of the
reserve area for each lot.
In summary, there is adequate area on each of the lots for an on site septic system, the required
reserve areas, a domestic well, house and driveway. This subdivision as proposed meets all the
requirements as established by AMC 15.65.180 and AMC 21.15.110.
Enclosure
cc: Ghislaine Cremo
acldh
754se"creportr
Ve truly yours,
tory Engineers
Dee High, P. .
Principal
*.:49
••as•••••••••u••••. .
T
'p • DEE HIGH. gyp„•, .; i
.'meg^ • CE - 5807
W.O.# 06754
DHI CONSULTING ENGINEERS
800 E. DIMOND BLVD. SUITE 3-545 A
ANCHORAGE, ALASKA 99515
SOILS LOG -PERCOLATION TEST AV
i
TEST HOLE LOG LOT 1 i .
rn : DEE HICyK(� I; g�
ROGER CREMO 9 19 9''• p�/
PERFORMED FOR: DATE PERFORMED: �2006'(1�/`er•••, LV •8••,•\�C�'�
LEGAL DESCRIPTION: LOT 1 END OF THE ROAD SUBDIVISION �4% PrOfesS%
T.H. LOT 1 Date: it F
IFN THIS DATA IS PROVIDED TO MEET THE REQUIREMENTS FOR
j7, 912" ORGANIC MAT SUBDIVIDING THE PROPERTY. THIS TEST HOLE DATA MAY NOT
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
18" ORGANIC SILT
SLIGHTLY SILTY SANDY GRAVEL
F-1
p
OCCASIONAL ROCK TO 5"
a / WAS GROUND WATER S
a'. 0 SEEP 0 10.5' ENCOUNTERED ? YES L
IF YES, AT WHAT 0
DEPTH ? 10.5' P
E
DEPTH OF WATER
AFTER MONITORING ? 13.0' DATE: 10-16-09
BE USED FOR THE DESIGN OF AN ON-SITE SEPTIC SYSTEM
WITHOUT THE WRITTEN CONSENT OF THE ENGINEER.
SLOPE SITF PI AN
B.O.H.
PEAo1N0
DALE aR033 191E
NET 1wE
mm
MET Haar
POMMM
PRESOAK
9/19/96 -
6:15
12'
12'
PRESOAK
9/19/06
6:12
12'
12'
1
9/19/06
6:07
6'
6'
1.92
2
9/19/06
6:21
6'
6'
1.06
3
9/19/06
6:23
6'
6'
1.06
4
9/19/06
6:27
6'
6'
1.05
PERCOLATION RATE: 1.08 (MINUTES/INCH.) PERCHOLE DIAMETER: 6"
TEST RUN BETWEEN: 3.5 FT. AND 4.0 FT.
PERFORMED BY: DEE HIGH 1 CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH
ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: 10-19-2009 754THL6D
W.O.# 06754
DHI CONSULTING ENGINEERS 41--
•
800 E. DIMOND BLVD. SUITE 3-545 AVQ` .
ANCHORAGE, ALASKA 99515 � "'
SOILS LOG—PERCOLATION TEST
TEST HOLE LOG LOT 3 wo "'
PERFORMED FOR: ROGER CREMO • CE 5807
DATE
DATE PERFORMED: 9-19-2006 �`�P�e••�•••••••
LEGAL DESCRIPTION: LOT 3 END OF THE ROAD SUBDIVISION A,'PrOfesSlof°�'o�
T.H. LOT 3 Dater
_ 6" ORGANICS THIS DATA IS PROVIDED TO MEET THE REQUIREMENTS FOR
SUBDIVIDING THE PROPERTY. THIS TEST HOLE DATA MAY NOT
1 BE USED FOR THE DESIGN OF AN ON-SITE SEPTIC SYSTEM
12" REDDISH ORGANIC SILTS WITHOUT THE WRITTEN CONSENT OF THE ENGINEER
2
3
4
5
/
6
/
/
7
SLIGHTLY SILTY SANDY GRAVEL
8
/
F-1/NFS
SMALL SEEP 0 16.5'
/
9
10
11
/
/
12
D %
13
14
15
D/
/
16
B.O.H.
17
SLOPE SiTF vi AN
WAS GROUND WATER S
ENCOUNTERED ? YES L
IF YES, AT WHAT O
DEPTH ? 16.5' P
DEPTH OF WATER E
AFTER MONITORING ? NONE DATE 10-1s-09
18
19
PERCOLATION RATE: 0.94 (MINUTES/INCH.) PERCHOLE DIAMETER: 6-
20 TEST RUN BETWEEN: 4.0
FT. AND 4.5 FT.
COMMENTS, SEEP STOPPED AFTER A FEW MINUTES.
PERFORMED BY: I CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH
ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: 10-21-2009 754THL4D
W.O.# 06754
DHI CONSULTING ENGINEERS
800 E. DIMOND BLVD. SUITE 3-545
ANCHORAGE, ALASKA 99515 Ar
SOILS LOG—PERCOLATION TEST Ar
TEST HOLE LOG LOT 4 iq
m DEE HIGH i
PERFORMED FOR: ROGER CREMO ♦#� �'. CE 5807
DATE PERFORMED: 9/19/06 ��fe .'., .•'( i
LEGAL DESCRIPTION: LOT 4 END OF THE ROAD SUBDIVISION ��; )'_ofessjoo
T.H. LOT 4 Date:
16" ORGANICS THIS DATA IS PROVIKQ�DD TO MEET THE REQUIREMENTS F6R
SUBDIVIDING THE PROPERTY. THIS TEST HOLE DATA MAY NOT
16" RED ORGANIC SILTS BE USED FOR THE DESIGN OF AN ON-SITE SEPTIC SYSTEM
WITHOUT THE WRITTEN CONSENT OF THE ENGINEER.
2MSLOPE SITE PLAN
3 a
4
5
6
7
8
9
Fli
0
10
4-
11
12 r Z.
13 /.
14
15
16
17
18
19
20
SANDY GRAVEL
TRANSITION TO
SLIGHTLY SILTY SANDY GRAVEL
W/ DEPTH F—i/NFS
OCCASIONAL ROCK TO 6"
WAS GROUND WATER S
® 10.5' ENCOUNTERED ? YES L
IF YES, AT WHAT 0
DEPTH ? 10.5' E
DEPTH OF WATER E
AFTER MONITORING ? NONE DATE: 10-19-2009
SILTY SAND
I KolmI
PERCOLATION RATE: 1.06 (MINUTES/INCH.) PERCHOLE DIAMETER: 6"
TEST RUN BETWEEN: 4.0 FT. AND 4.5 FT.
COMMENTS- SEEP STOPPED AFTER A FEW MINUTES.
PERFORMED BY: DEE HIGH I CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH
ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: 10-21-2009 754THL5D
CHUGACH STAT_ PARK VICINITY MAP 1"=1 MILE
\ _ -----
DRAINAGE—_HANNEL •'/ \ I sl I x I x I JI I 2
-,..-.,aeo EXIST. SEPTIC,i� - '4TL`�is'�.`� 1
CHANNELS � - a J
/ '\--•�''1,,,,, LOT 1 PRO -sem... �.;.:.i EX i LL j I I S 1
�• i e
Y / PROPOSED ELL
LOT 2 N
HOUSE sEXI
LOT 2A >Ae /"SITE�' f
-I- 10 11 I t: e
DRAINAGE
�CHANNELS _j
L"° —1 INc H uSe � ISO,( — - NOTES:
p -1'115
._._� r
_.
I I - 'i \., -...................... 1. LOTS 2A & 2 HAVE EXISTING WELLS AND
l _ 10,000 S.F-"L•••'" 1 -'! SEPTIC SYSTEMS WHICH HAVE BEEN
- - - - - - - - PROPOSED APPROVED BY M.O.A. ON-SfTE SERVICES
` - -- - - -" - HOUSE SftE / x
-
EAT. SE . - �M � . - > <-r4�_ \ - 2. TRACTS A k 8 CANNOT BE DEVELOPED
SYSTEMS -'ovr /.. / T 3 - AS RESIDENTIAL HOME SITES.
a'sipp ,e• _ - ''' / 10,000 S.1( - 3. LOT 1, 3 k 4 MEET THE REQUIREMENTS
A.M.C. 21.15, 21.55 AND 21.65.
G7�dd�OD� WOOG C3D WE P
/ Qa®�a _
LOT 3\,m, LOT 4 R� 1� 10000 S.F. -
LOT $
o ,LOT 2 \ \ / 1� ,r PROP SE-
Z 3db�G3 WELL, Ho_u�PE j
_ y WELL, S1iN
LEGEND
SYMBOL
DESCRPTION..
SUBDIVISION BOUNDARY
- -
INTERIOR PROPERTY UNE
DRAINAGE CHANNEL
TEST HOLE k NUMBER
�{ '•.Y^...i;:;i:.�
PROPOSED SEPTIC AREA
PROPOSED WELL WITH 100'
PROTECTIVE WELL RADIUS.
4. i
g>R�e7e1 •., vrvi lY
n12. FIGURE 1
Dffi CONSULTING ENGINEERS
am . 11011111111m KAMM
LOT - T leph « ("TA" -Ism rm tompu-,aea
LOT 6 see sm e�5e • u&(9 a ses
200 0 200 400 END OF THE ROAD
Ii i i I I I I
QQOgp QD° LOT 5 ON-SITE SEPTIC MAP
Distances are shown in feet. f8 m wio 2143 ax,cr
I" - 200'. °� 11 05 7540081E i
w 06754 1
D H I CONSULTING ENGINEERS
Civil Engineering • Surveying • planning
Mr. Dan Roth
' Municipality of Anchorage
Building Safety Division
Development Services Department - On -Site Supervisor
' P.O. Box 196650
Anchorage, Alaska 99519-6650
RE: Preliminary Plat - End of the Road
Domestic Water Availability
Dear Mr. Roth,
October 5, 2006
W.O.: 06754
811592 JUN 1 69W
The proposed subdivision consists of 5 lots ranging from 3.6 acres to 13.3 acres; and one tract that is 2.9 acres.
This property is zoned R10SL, which encourages large lots and low density development. This property is abutted
on the South and East by Chugach State Park. No further development can take place in those directions and there
can be no development on the 2.9 acre tract.
Two of the five proposed lots already have wells (Lot 2A, Block 5 and Lot 1). They produce about 30 gpm and
6 gpm respectively. The proposed development will require three additional wells.
Water availability in this area has been excellent. The static water level ranges from 27' to 162' below the surface.
Flow rates are reported to range from 3gpm to 50gpm. Well depths are ranging from 60' to 427'. Most of the wells
are finding water in the bedrock aquifer. We expect that lots on this subdivision will encounter bedrock between
30' to 100' below the surface. To date, all bedrock wells have produced adequate supplies of water.
The geology in this area of the watershed consists of glacial till over weathered, fractured bedrock. The existing
bedrock aquifer has not shown any signs of being depleted and the addition of three more wells will not over stress
the aquifer.
Due to the make up of the aquifer, the large distance between the individual wells and low density development,
this development will not impact the existing wells in adjacent subdivisions.
We would appreciate your approval of the preliminary plat.
Attachmem:.
=Roger Cremo
754waterreport.wpd
truly yours,
�"sulting Engineers
Dee High, P
Principal
Legal Description
Hillside North Home Tract
Static Water Level
42 feet
Depth of Well
66 feet
Production Rate
6 gpm
Hillside North #1 Lott
150 feet
410 feet
5 gpm
Hillside North #1 Lot2
162 feet
200 feet
8 gpm
Hillside North #5 BIk3 Lot4
95 feet
205 feet
4 gpm
Hillside North #5 BIk3 Lot5
73 feet
120 feet
6 gpm
Hillside North #7 BIM Lott
27 feet
365 feet
4 gpm
Hillside North #7 BIk4 Lot3
45 feet
107 feet
5.4 gpm
Hillside North #7 BIk4 Lot4
88 feet
427 feet
3 gpm
Hillside North #7 BIk5 Lot2
47 feet
245 feet
30 gpm
Hillside North #7 BIk5 Lot3
50 feet
340 feet
3 gpm
Hillside North #8 BIk4 Lot6
42 feet
61 feet
50 gpm
Hillside North #8 BIk5 Lot4
55 feet
60 feet
12 gpm
Taiga Lot2
119 feet
220 feet
5 gpm
Taiga Lot6
60 feet
190 feet?
8 gpm
Legal Description
Hillside North Home Tract
Static Water Level
42 feet
Depth of Well
66 feet
Production Rate
6 gpm
Hillside North #1 Lott
150 feet
410 feet
5 gpm
Hillside North #1 Lot2
162 feet
200 feet
8 gpm
Hillside North #5 BIk3 Low
95 feet
205 feet
4 gpm
Hillside North #5 BIk3 Lot5
73 feet
120 feet
6 gpm
Hillside North #7 BIk4 Lott
27 feet
365 feet
4 gpm
Hillside North #7 BIk4 Lot3
45 feet
107 feet
5.4 gpm
Hillside North #7 BIk4 Lot4
88 feet
427 feet
3 gpm
Hillside North #7 BIk5 Lot2
47 feet
245 feet
30 gpm
Hillside North #7 BIk5 Lot3
50 feet
340 feet
3 gpm
Hillside North #8 BIk4 Loth
42 feet
61 feet
50 gpm
Hillside North #8 BIk5 Lot4
55 feet
60 feet
12 gpm
Taiga Lot2
119 feet
220 feet
5 gpm
Taiga Lot6
60 feet
190 feet?
8 gpm
Average Total
94.5
243.5
26.5