HomeMy WebLinkAboutCROSS VIEW ESTATES BLK 1 LT 31Cross View
Estates
Block 1
Lot 31
#015-221-62
Permit Number:
Tax Code Number:
Work Type:
On-Site Water & Wastewater System Permit
OSP141106
01522162000
WellSeptic
MUNICIPALITY OF ANCHORAGE
Development Services Department
On-Site Water & Wastewater Program
4700 Elmore Road, PO Box 196650
Anchorage, AK 99519-6650
Telephone: (907) 343-7904
Initial
Permit Effective Dates: May 15, 2014 to May 15, 2015
Design Engineer: ANDERSON ENGINEERING
Subdivision: CROSS VIEW ESTATES
Site LegalAddress: CROSS VIEW ESTATES BLK 1 LT 31 G:2737
Owner/Address: HARDING HOMES OF ALASKA INC
5771 HERITAGE DRIVE ANCHORAGE AK 995160000
Site Mailing Address: 12090 LOWER HERITAGE CIR, Anchorage
Lot Size in Sq Ft: 40229
Total Bedrooms: 5
This permit is for the construction of:
Y Disposal Field Y Septic Tank N Holding Tank N Privy Y Private Well N Water Storage
All construction must be in accordance with: 1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater
Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80).
3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services
Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either:
A. Open and Close on the same day.
B. Covered, sealed, and heated to prevent freezing.
Date:
Municipality of Anchorage
P.O. Box 196650 · 4700 Elmore Road
Anchorage, Alaska 99519-6650 · (907} 343-7904 · Fax (907) 343-7997
http:llwww.muni.or.qlOn$ite
Development Services Division
On-Site Water and Wastewater Program
Department
**** VARIANCE/WAIVER REVIEW ****
WaiverS: OSP141122 COSA#: Permit#: OSPt41t06
PID#: 015-221-62
Legal Description: Cross View Estates Block 1 Lot 3t
Engineer: Anderson En.qineerin,q
Applicant: Harding Homes
Your request for a waiver of the required 50 feet horizontal separation from the absorption field
to the excessive slope has been approved. The approved separation distance is 18.0 feet.
This waiver approval applies to the proposed absorption field only. Any future upgrade to the
on-site wastewater disposal system will require all separation distances be met or another
approval from this department.
[] The affected adjacent property owner(s) have been given a 7 day notice regarding this
waiver.
[] Notarized letter(s) of nonobjection have been received from the owner(s) of the affected
adjacent property.
[] Adjacent properties are not affected by this waiver.
Waiver is Granted: X Waiver is not Granted:
Date: ~'~,~/.~ Approved by: Name of Revi. c~r ~
Rec#: 063006 Amount: $215.00 Date Paid: $/13/14
**** VARIANCE/WAIVER REVIEW ****
MUNICIPALITY OF ANCHORAG
Community Development Department Phone: 907-343-7904
Development Services Division Fax: 907-343-7997
On-Site Water & Wastewater Program
ON-SITE SEWER/WELL PERMIT APPLICATION
Parcel I.D. 015-221-62
Property owner(s) Harding Homes of Alaska, Inc.
Mailing address 5771 Heritage Drive Anchorage, AK 99516
Day phone 350-1860
Site address 12090 Lower Heritage Circle Anchorage, AK 99516
Legal description (Sub'd., Block & Lot) Cross View Estates, Block 1, Lot 31
Legal description (Township, Range & Section)
LotSize 40,229 Sq. Ft. Number of Bedrooms Five (5)
APPLICATION IS FOR:
([~ all that apply)
Absorption Field []
Septic Tank []
Holding Tank []
Privy []
Private Well []
Water Storage []
APPLICATION IS AN:
Initial []
Upgrade []
Renewal []
TYPE OF DWELLING:
Single Family (SF) []
(w/wo ADU)
Duplex (D) []
Multiple Dwellings []
(SF and/or D)
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
Dis tance:
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
(Signature of property owner or authorized agent)
PermiFRush Fees:
Date of Payment:
Receipt N umber:
Permit No.
Waiver Fees:
Date of Payment:
Receipt Number:
Waiver No.
Permit App_g-1-12.doc
ANDERSON ENGINEERING
P,O, BOX 240773 :
ANCHORAGE; A~99524
522:7773 6777766 (FAX)
May 1, 2014
Municipality of Anchorage
Development Services Department
On-Site Water and Wastewater Program
4700 Elmore Road
Anchorage, AK 99519-6650
Subject:
Lot 31, Block 1, Cross View Estates Subdivision
Septic System Design and Permit Application
Impacts to Adjacent Properties
Dear Onsite Services Engineer:
The owner of Lot 31, Block 1, Cross View Estates Subdivision intends to construct a
new five-bedroom home on the lot. We are therefore requesting a permit be issued for
the construction of a new well and septic system to accommodate the home. The
attached Site Plan and backup documentation identify the location and configuration of
the proposed well and septic system along with the alternate site. Also identified on the
plans are the existing wells in the area and septic systems on surrounding lots. No
conflicts exist between the proposed septic system and well or septic systems and wells
on adjacent lots. Drainage arrows and ground surface contours are shown on the site
plan showing the grade and direction of flow on the lot. The drainage pattern will not be
changed as a result of this project.
The test hole placed on the lot in the area of the absorption trench and alternate site
indicate silty sand with gravel (SM). The percolation rate of the soil at the test hole was
determined to be 4.4 minutes per inch. No groundwater was found during the
placement of the test hole and none was noted during the monitoring period. An
application rate of 1.2 gallons per day per square foot was used in the design of the
absorption system. We are proposing to place a new 1,500-gallon septic tank and an
oversized 60' long by 3' wide by 6' effective depth absorption trench to treat and
dispose of the effluent generated in the house. The elevation of the distribution line in
the absorption trench will be 3' below the surface and the total depth will be 9'. A
minimum of 3' of fill or 2" of insulation and 2' of fill will be placed over the absorption
trench and 4' over the septic tank.
The ground surface on the lot in the area of the septic system slopes to the west at a
shallow grade with some cross sloping from the east. The new trench will be
Lot 31, Block 1, Cross Point Estates Subdivision
May 1, 2014
Page Two
constructed parallel with the contours of the slope as much as possible in conformance
with Municipal requirements. The new septic system will be constructed a minimum of
100' from all wells and any surface water and 10' the proposed and existing water
services in the area.
If the system is constructed in accordance with our design the following statements
apply:
The system, if constructed as designed, will have no adverse impact on the wells
in the area or those to be constructed in the future.
The system, if constructed as designed, will have no adverse impact on existing
septic systems in the area or those to be constructed in the future.
The system, if constructed as designed, will have no adverse impact on reserve
space, either surface or subsurface, on any lots located in the area.
The system, if constructed as designed, will have no adverse impact on drainage
patterns in the area. The current drainage pattern will be maintained.
Sincerely,
Michael E. Anderson, P.E.
Attachments
LOT 24. BLOCK
Vocont
CROSS VIEW ESTATES
LOT 10, BLOCK 2
//
LOT 27, BLOCK 1
Vocont
/
/
/ '~
\
CROSS VIEW ESTATES
LOT B, BLOCK 2
\
\
LO,~ 30, BLOCK I
// Vacant
AREA MAP
ANDERSON~ SCALE 1' = tOO'
No, 6E-4381
CROSS
PLAT NO. 2006-171
VIEW ESTATES SUBDIVISION
LOT 31, BLOCK 1
40,229 S.F.
LOT 50, BLOCK
VACANT
Septic To
HERITAGE HEIGHTS DRIVE
SITE PLAN
SCALE 1' = 50'
LEGEND:
C0 - Cleonout
SV - Septic Vent
FCO - Foundo[ion Cleanout
TH - Test Hole
MT - Monitor Tube
LOT 31, BLOCK 1, CROSS VIEW ESTATES
DESIGN FACTORS: SYSTEM REQUIREMENTS:
Five Bedroom Home DeepTrench System
Perc. Rate: 4.4 Min./Inch 1,500 Gallon Septic Tank
Application Rate: 1.2 GPD/SF 6' Drainfield Rock
5 Bedrooms X 150 GPD/1.2 GPD/SF (Application Rate) = 625 SF Absorption Area
625 SF/12 SF/LF = 52.08 LF Trench Length
THEREFORE: Construct a 60' Long x 3' Wide x 6' Effective Depth Absorption Trench at the
Location Shown. Flow Line Elevation in Trench to be 3' Below Original Ground Surface. Total Depth
to be 9' Below Existing Ground. Provide 4' Cover Over Septic Tank and 3' Cover Over Absorption
Trench. Maintain 100' Separation from Wells in the Area.
Natural
Backfill
~©
Geotextile
Fabric
4" Perforated
PVC (Holes Down)
Drainfield Rock
TYPICAL DEEP TRENCH SECTION
NOSCA'E) ..........
NOTE' Grade Area Over Trench to Drain Away . ~
' , , ~ . m
Minimum 6 Separation From Bedrock. ~.,..~ ........ ..,,...¢ ......... ¢,.,..~..~,,~
Minimum 4 Separation From Groundwater. ~ ~
Minimum 100 Separation From Wells in the Area. ,~ MICHAELE. ANDERSON
Minimum 100' Separation From Sudace Water or Streams ~¢-~
· ~.,...-. ..~
&700
DEPTH
(~)
1
2
3
4
5
6
7
8
9
11
20.
MUNICIPALITY OF ANCHORAGE
DEVELOPMENT SERVICES DEPART~IENT
BRAGAW STREET ANCHORAGE, AK 99519-6650
SOILS LOG ~ PERCOLATION TEST
LEGAL DESCRIPTION: LOT 51, BLOCK I, CROSS VIEW ESTATES SUB.
PERFORMED FOR: HARDING HOr"IES
DATE: h/2L/201& PROJECT No.:
PARCEL ID#: TECHNICIAN:
I TEST.OLE^ I
OB/OG
SILTY SAND
WITH GRAVEL
LOOSE
DRY
W. ROBERTS
WAS GROUND WATER ENCOUNTERI~D? .__
DEPTH OF WATER AFTER MONITORING:
BOH @
SLOPE
NO
SITE PLAN
SEE SITE PLAN
5% j
DATE OF MONITORING: 5/I/IA
DEPTH TO
DATE READING GROSS TIME NET Tilde WATER NET DROF
(PIINUTES) (MINUTES) (INCHES) (INCHES)
TEST HOLE PRESOAKED PRIOR TO TESTING:
4/24 1 11:03/]1:13 10 4.00"/1.75" 2.25"
2 11:14/11:24 10 3.75"/1.50" 2.25"
3 11:25/11:35 10 4.00"/1.75" 2.25"
4 11:36/11:46 10 4.00"/1.75" 2.25"
5 11:47/11:57 10 3.75"/1.50" 2.25"
6 i1:58/12:08 10 4.00"/1.75" 2.25"
PERCOLATION RATE: 4.4 (MmnNCH) PERC. HOLE DIA. 6" .(INCHES)
TEST RUN BETWEEN: 7 FT. and 8 FT.
COMMENTS: TEST HOLE PRE SOAKED PRIOR TO TEST.
TEST PERFORMED BY ANDERSON ENGINEERING. I, MICHAEL E. ANDERSON CERTIFY THAT
THiS WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS
DATE: h/28/I/4
May 13, 2014
Municipality of Anchorage
Development Services Department
On-Site Water and Wastewater Program
4700 South Bragaw Street
Anchorage, AK 99519-6650
Su~e~:
Lot 31, Block 1, Cross View Estates Subdivision
Absorption Trench to Slope Waiver
Dear Onsite Services Engineer:
The north end of the alternate absorption trench proposed for Lot 31, Block 1, Cross
View Estates Subdivision is located 18' from the edge of the shallow 1.5' deep dry
drainage ditch along Lower Heritage Circle. The backslope of the ditch is greater than
25%. We are therefore applying for a waiver allowing placement of the absorption
trench at this location.
Subsurface soils in the area of the absorption trench are porous sandy gravel with silt.
No migration of effluent is expected toward the slope. We therefore recommend a
waiver be issued allowing placement of the alternate absorption trench within 18' of the
slope greater than 25%.
Sincerely,
Michael E. Anderson, P.E.