Loading...
HomeMy WebLinkAboutRABBIT CREEK VIEW & HEIGHTS BLK 5H LT 1ARabbit Creek View &Heights Block 5H Lot 1 A #020-551-36 Inspection Re ort 1- - .d Municipality of Anchorage Community Development Department Page 1 of 5 On -Site Water and Wastewater Program 4700 Elmore St. • P.O. Box 196650 Anchorage, AK 99519-6650 • http://www.muni.org/onsite • (907) 343-7904 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP141264 PID Number: 020-551-36 ❑ New ❑✓ Upgrade Name: Mark Schimscheimer ABSORPTION FIELD ❑ Deep Trench ❑✓ Shallow Trench ❑ Bed ❑✓ Mound Address 16751 Carl Street ❑ Other Phone Number of Bedrooms Soil Rating Total depth from original grade 3 4 GPD/SF +3.5 Ft. LEGAL. DESCRIPTION Depth to pipe invert from original grade +4:0 Ft. Gravel depth beneath pipe - 0.5 Ft. Subdivision Block Lot Rabbit Creek View & Heights 511 1 A Fill added above original grade 6.5 Ft. Gravel length 25 Ft. Township Range Section Gravel width 5Ft. Beds: Number of Lines N/A Distance between lines N/A Ft. SEPARATION DISTANCES TO Septic Absorption Holding Sewer Total absorption area Number of trenches Dist. between trenches From Tank Field Lift Station - Tank Line -- 125 Ft= 1 N/A Ft. Well 104.6 119.7 117.0 N/A 75.8 TANK ❑ Septic El S.T.E.P. ❑ Holding ❑ Other Manufacturer Anchorage Tank IOrenco Capacity 1,5000al, Surface Water 100+ 100+ 100+ N/A Material Steel Number of compartments 2 Lot Line 8.8 17.6 13.9 N/A NA Foundation 31.0 46.1 42.6 N/A LIFT STATION Manufacturer Orenco Capacity 250 Gal. Curtain Drain N/A N/A N/A N/A Pump on level at Pump off level at High water alarm at Remarks 43 in. 40 in. 45 in. Pump make and model P2005 Electrical Inspections performed by A.C. Electric -Norman Halilic PIPE MATERIAL Housetotank 3034 drainfeld Tank to 3034 Installer _ Homeowner / A+ Home Services Draintield 3034 CO/MT 3034 Inspector Pannone Engineering Services BENCH MARK (Assumed elevation) 100ft Inspection fs 6/3/2015 6/5/2015 Location and description dates: 2 Garage F.F. P 6/8/2015 4'" 6/9/2015 COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL Engineer's Stamp At Conditional Approval Date ql� • • Qki,�j, /�g�Q'(� :� �i ��••��e'veti •f�. •�anriorae•,r� . E 8149 ,r it Approved J. Date 7 / Inspection Re ort 1- - .d DRIVEWAY NOTE: IN THE EVENT THAT THE DRIVEWAY EFFECTS THE PLACEMENT OF THE - - RESERVE DRAIN FIELD AT ANY TIME _ IN THE FUTURE THE DRIVEWAY SHALL LOT VACANT BE REMOVED AND RELOCATED TO A ��_ NO WELLS OR SEPTICS -6 LOCATION THAT ALLOWS PLACEMENT OF THE RESERVE FIELD. TH-3 (PES 2015)'- TH—,2 8 - (PES 2015) - - (PES 2014) LIMIT OF FILL ' SE i 10' UTILITY EASEMENT TH M2 ' 1 \ LOT VACANT ` (TED MOORE 2007) NO WELLS OR SEPTICS i / r1 , -� _6 / � � \ 1 c LS2 t \ — DRIVEWAY 6.\ LS1 \ - \ LOT 2A PRELIMINARY SEE NOTE _'� 8.8 \\ / SEPTIC DESIGN - mi — SEE DESIGN CRITERIA M' T' , / FOR LOT 1 A PRIMARY (NEW)/RESERVE DRAIN FIELD (P) 104.6 25.OLF x 5'W x 0.5'ED x +3.5'TD .yly - 45LF x 20'W INFILTRATION AREA B A NEW 15008 S.T. E. P. TANK NEW WITH AX 20 POD & AUX PUMP VAULT 38R L _ HOUSE LOT VACANT / NO WELLS OR SEPTICSZF \ I I /p , PRELIMINARY W� L 3 -r LOCATION FOR LOT 2 L A WELL (P) \ `ZBYRON DRIVE NOTES: PANNONE ENG SVC, LLC of A � 7Date /15 - RECORD DRAWING �,....,Lq lt� 7/15/2015 P.O. BOX 100217 ANCHORAGE, AK 99510 S PHONE (907) 272-8218 FAX (907) 272-8211 ig�`P �y++ Sccle .... .. I P.I.D. NO RABBIT CREEK VIEW & HEIGHTS, BLOCK 5H, LOT 1A 020-551-36 MARK SCHIMSCHEIMER I S'tev'e'n'R. 'an'none j PERMIT No. I PF.•. CE 814 �� j OSP141264 16751 CARL STREET PLAN ANCHORAGE, AK 99516 + Sheet��1��� 2 OF 5 A B FC - -&0 - T1 32.9 37.6 LSI 40.0 43nD- LS2 43.0 45.0 mi - 48.4 48.3 M2 69.7 64.50 NOTES: PANNONE ENG SVC, LLC of A � 7Date /15 - RECORD DRAWING �,....,Lq lt� 7/15/2015 P.O. BOX 100217 ANCHORAGE, AK 99510 S PHONE (907) 272-8218 FAX (907) 272-8211 ig�`P �y++ Sccle .... .. I P.I.D. NO RABBIT CREEK VIEW & HEIGHTS, BLOCK 5H, LOT 1A 020-551-36 MARK SCHIMSCHEIMER I S'tev'e'n'R. 'an'none j PERMIT No. I PF.•. CE 814 �� j OSP141264 16751 CARL STREET PLAN ANCHORAGE, AK 99516 + Sheet��1��� 2 OF 5 SPECIAL PROVISIONS TO SPECIFICATIONS 1. ALL CONSTRUCTION SHALL BE INSTALLED AS SPECIFIED IN THE MOST CURRENT EDITION OF THE MUNICIPALITY OF ANCHORAGE STANDARD SPECIFICATIONS (MASS) FOR COMPONENT PARTS AND MATERIALS USED IN CONSTRUCTION OF ON-SITE WASTEWATER DISPOSAL SYSTEMS AND ATTACHED SPECIAL PROVISIONS. 2. SCOPE OF WORK: INSTALL NEW 1500g S.T.E.P. TANK WITH AX20 POD, SOIL ABSORPTION -SYSTEM, AND WELL. 3. GROUNDWATER WAS MONITORED AT 1.5 FEET BELOW EXISTING GRADE AS EVIDENCED BY THE SOIL TEST HOLE. IF AN APPARENT WATER TABLE IS OBSERVED IN ANY OF THE EXCAVATIONS LESS THAN 1.5 FEET BELOW EXISTING GRADE NOTIFY THE ENGINEER IMMEDIATELY. 2 RIGID INSULATION FILTER FABRIC I.25" 0 PERF PIPE W/ I/8' HOLES DRILLED 18" O.C. / DRAIN ROCK 6' ABOVE PIPE INV 6" TS- (TYP) ROCKv -_: 2 SAND � 3 97.6 j:I TH-1 p OR 10.0'-12.5MoA TYPE II FILL' 94E — -1 S -1.J 8.5-11 6/12/14 ML ' MCA TYPE II FILL TO BE PLACED IN 12 -INCH LIFTS COMPACTED TO 807. DESIGN PARAMETERS PRIMARY SEPTIC SYSTEM N0. BEDROOM: 3 (450 gpd) TANK SIZE: 1500g S.T.E.P. W/ AX20 POD & AUX PUMP VAULT PERC RATE: 6-15 MPI SOIL RATING: 4 GPD/SF AREA ROD: 112.5 SF SYS. TYPE: WIDE TRENCH 0.5'ED MIN LENGTH: 22.5 LF -USE: 25 LF X 5.0' WIDE, 0.5' E.D., +3.5 TD TOTAL AREA: 150.0 SF DESIGN PARAMETERS ERS - IN-SITU INTERFACE NO. BEDROOM: 3 (450 gpd) PERC RATE: 60-90 MPI SOIL RATING: 0.5 GPD/SF AREA ROD: 900 SF USE: 45 LF X 20.0' WIDE TOTAL AREA: 900 SF LEGEND W WATER LINE/ WELL RADIUS SS NEW SEPTIC CU COPPER DIP DUCTILE IRON PIPE TH SECTION` o„'-" ° 85.' FC - FOUNDATION. CLEAN OUT T# TANK CLEAN OUT NO. C# CLEAN OUT NO. M# MONITOR TUBE NO. R. 1. RIGID INSULATION 2 2" RIGID INSULATION Z DV DIVERTER VALVE FS FLOW SPLITTER - po FILTER FABRIC o OG ORIGINAL GRADE FG FINISH GRADE - DRAIN ROCK V ABOVE PIPE INV - - g 1.25" P PERF PIPE W/ g a 1/8" HOLES DRILLED 18" O.C. � ¢O O 2 ¢ O 2'$AND O� J IDO 7 1 10.0' MOA TYPE II FILL` L967 i00 AX20 PO - 9"0.3 1500 g S.T.E.P. TANK I 45A TRENCH SEE DESIGN PROFILE ABBREVIATIONS DESIGN PARAMETERS PRIMARY SEPTIC SYSTEM N0. BEDROOM: 3 (450 gpd) TANK SIZE: 1500g S.T.E.P. W/ AX20 POD & AUX PUMP VAULT PERC RATE: 6-15 MPI SOIL RATING: 4 GPD/SF AREA ROD: 112.5 SF SYS. TYPE: WIDE TRENCH 0.5'ED MIN LENGTH: 22.5 LF -USE: 25 LF X 5.0' WIDE, 0.5' E.D., +3.5 TD TOTAL AREA: 150.0 SF DESIGN PARAMETERS ERS - IN-SITU INTERFACE NO. BEDROOM: 3 (450 gpd) PERC RATE: 60-90 MPI SOIL RATING: 0.5 GPD/SF AREA ROD: 900 SF USE: 45 LF X 20.0' WIDE TOTAL AREA: 900 SF LEGEND W WATER LINE/ WELL RADIUS SS NEW SEPTIC CU COPPER DIP DUCTILE IRON PIPE TH TEST HOLE FC - FOUNDATION. CLEAN OUT T# TANK CLEAN OUT NO. C# CLEAN OUT NO. M# MONITOR TUBE NO. R. 1. RIGID INSULATION DCO DOUBLE CLEAN OUT.. DV DIVERTER VALVE FS FLOW SPLITTER - REG BELOW FINISH GRADE OG ORIGINAL GRADE FG FINISH GRADE TS&V TOPSOIL AND VEGETATE NOTES: PANNONE ENG SVC, LLCof A `�� Date RECORD DRAWING L sl� P.O. BOX 100217 ANCHORAGE, AK 99510 J : 7/15/2015 'C�•9 PHONE (907) 272-8218 FAX (907) 272-8211 Cj�P' f9�) Scale *:49TH NITS ...... . • .. .... I P.I.D. NO RABBIT CREEK VIEW & HEIGHTS, BLOCK 5H, LOT IA 020-551-36 MARK SCHIMSCHEIMER Steven R. Pa none' PERMIT NO. 19F. E 849 •�� 16751 CARL STREET �s����r OSP141264 DESIGN DETAILS ANCHORAGE, AK 99516 +`il�F0�70 ES5'DNp�� sheet 3 OF 5 READING SOILS LOG - PERCOLATION TEST TEST HOLE 1 / SLOPE /� SITE PLAN OR ORGANICS TH-2 1 -\ (PES 2015) ,. 2 TH-1 3 (PES 2014) 4 10' UTILITY EASEMEN 5 ML BLUISH SILT TH i.._._ ED MOORE 2007) M 2 6 X TH .. I X11 LS2 6. B Al ��M�M� T1 9 10 M A11 B i SILK SAND NEW 1 12 SM WITH SOME .313R GRAVEL 13 BOH WAS GROUND WATER SLOPE 14 ENCOUNTERED? N 15 IF YES, AT WHAT TH DEPTH? -DRY' - X 16 17 DEPTH TO WATER AFTER MONITORING? - 18 DATE: DATE PERFORMED: 612115 PEROLATION RATE ' (min/inch) PERC HOLE DIAMETER 6 inches TEST RUN BETWEEN 11 FT AND 12 FT COMMENTS: Test hole excavated by A+ HOME SERVICES. Pere test was not possible due to depth of soil stratum. *SEE SIEVE ANALYSIS. PERFORMED BY: Steven R. Pannone, P.E. I CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDLINES IN EFFECT ON THE DATE OF THIS TEST. NOTES: PANNONE ENG SVC, LLC P.O. BOX 102954 ANCHORAGE, AK 99510 = oF.a \�� rc .Cq l�+ S Date 7/15/2015 RECORD DRAWING Scale PHONE (907) 272-8218 FAX (907) 272-8211 *�49 TH y*+II NTS .... ....... / P.I.D. NO RABBIT CREEK VIEW & HEIGHTS, BLOCK 5H, LOT 1A / 020-551-36 MARK SCHIMSCHEIMER P tev'eCERB 4annope'/ PERMIT NO. 16751 CARL STREET ANCHORAGE, AK 99516 i ,� IIlk . 1� PROFESSION`, SOILS LOG Sheet 4 OF 5 READING DATE CLOCK TIME NET TIME WATER LEVEL NET DROP READING 1 6!4/14 SEE NOTE 2 3 4 5 6. READING SOILS LOG - PERCOLATION. TEST TEST HOLE 3 WATER LEVEL NET DROP READING 1 SLOPE l SITE PLAN OR ORGANICS TH-2 1 ..(PES 2015), 2 TH-1� \ 3 (PES 2014)-� 3 L_ 4 10' UTILITY EASEMEN 5 ML BLUISH SILT TH M2 ED MOORE 2007) 6 X TH LS2 -- — .. 6 LS1 � � 6 M1 MT1�M�M"�� A y SILTY SAND 8 /�N 11 SM WITH SOME GRAVEL NEW � 12 BOH - 38R 1 13 WAS GROUND WATER SLOPE 14 ENCOUNTERED? N 15 IF YES, AT WHAT TH DEPTH? -DRY' - X 16 17 DEPTH TO WATER AFTER MONITORING? 16 _ DATE: DATE PERFORMED: 6!2115 PEROLATION RATE (min/inch) PERC HOLE DIAMETER 6 inches TEST RUN BETWEEN 11 FT AND 12 FT COMMENTS: Test hole excavated by A+ HOME SERVICES. Pere test was not possible due to depth of soil stratum. "SEE SIEVE ANALYSIS. PERFORMED BY: Steven R. Pannone, P.E. I CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDLINES IN EFFECT ON THE DATE OF THIS TEST. NOTES: ANN N EN SVLLC CK �.O ���� �\\ QF Q�gSI'� Date 7/15/2015 RECORD DRAWING BOX 102954 ANC ANCHORAGE, 99510 = �y�y Scale PHONE (907) 272-8218 FAX (907) 272-8211 %6j�P NTS �.... ... ... L. ... P.LD. -NO RABBIT CREEK VIEW & HEIGHTS, BLOCK 5H, LOT 1A 020-551-36 MARK SCHIMSCHEIMER 16751 CARL STREET / Steven R. Pannone / /�P ;� CE tag er/ +��lFAE� PERMIT N0. OSP141264 SOILS LOG ANCHORAGE, AK 99516 It\�OTs"� Sheet 5OF5 READING DATE CLOCK TIME NET TIME WATER LEVEL NET DROP READING 1 614!14 SEE NOTE z 3 4 5 6 Certificate of Installation Advantex Septic System Location: Land Use Permit Number R14-2432 SJ MFR Carl Street Anchorage, Alaska 99516 - Rabbit Creek View & Heights, Block 5H, Lot lA 167171=. Mark Schimscheimer, PE 6131 Austria Drive Anchorage, Alaska 99516 (907)830-7322 Engineer: Pannone Engineering Services (PES), LLC BOX 100217 Anchorage, Alaska 99510 (907)272-8218 Permitted by: Development Services Division, Municipality of Anchorage: Permit Number OSP141264 Installation Contractor: A Plus Home Services 7501 E 140th Avenue Anchorage, AK 99516-3851 (907)345-1890 Electrician: A.C. Electric, License Number: (Nermin Halilic) 4719EeAve #3 Anchorage, Alaska 99508 (907) 980-220-�7 5 - The above signatures certify that the above information is true and correct and that the svatem was installed and nnerates ac intended ner the discinline, of the asaiuned sionatory Alpine Drilling & Enterprises Well Log Permit Number: #SW 141264 Date of Issue: 8-29-14 Parcel Identification Number: 02055136000 Date Started: 9-24-14 Date Completed: 9-24-14 Is well located at approved permit location? x Yes ❑ No Legal Description: Rabbit Creek View & Heightsv Block 5 H Lot 1A Property Owner Name & Address: Durrant Bianca & William Michael J �ni ] vyy5 r- <ie) wl P r PO Box 93 Hope, Alaska 99605 Borehole Data: Depth (ft) Method of Drilling x air rotary ❑ cable too] Soil Type, Thickness & Water Strata From To Casing type: steel Stick-up 0 2 Wall Thickness: .250 inches Gravel fill silt silt 2 5 5 1/ Diameter: 6 inches Depth: 83 feet Liner Type: -- Diameter: inches Depth: feet gravelly silt 11 35 Casing stickup above ground: 2 feet Static water level (from ground level): 2 feet silt 35 41 gravelly silt 41 76 Pumping level: 80 feet after clay 76 81 2 hours pumping 12 gpm Recovery Rate: 12 gpm silty water sand & gravel 81 83 Method of Testing: air lift Well Intake Opening Type: x Open End ❑ Open Hole ❑ Screened Start feet Stopped feet ❑ Perforations Start feet Stopped feet Grout Type: bentonite granules Volume: 1 Depth: Start 0 feet Stopped ? feet Pump: Intake Depth feet Pump size hp Brand Name Well Disinfected Upon Completion? x Yes ❑ No Method of Disinfection: chlorine tablets Camments: Well Driller: Alpine Drilling & Enterprises PO Box 110496 Anchorage AK 99511 Development Services Department Building Safety Division On -Site Water & Wastewater Program 4700 Elmore Road P.O. Box 196650 Mark Begich Anchorage, AK 99507 Mayor wmE.muri.org/onsife (907)343-7904 Pump Installation Log Well Drilling Permit Number: SW 141264 Date of issue: 8129114 Parcel Identification Number:o2055136000 A FIE? Legal Description Block 5H, Lot 1A Rabbit Creek View & Heights Property Owner Name & Address: Bianca & William Durrant/Mark Schimsheimer P.O. Box 93 Hope, AK 99605 Pump Installation Date: 5/26/2015 Pump Intake Depth Below Top of Well Casing: 75 feet Pump Manufacturer's Name: Goulds Pump Model: 10SB05 Pump Size 1/2 hp Pitless Adapter Burial Depth: N/A feet Pitless Adapter Manufacturer's Name: N/A Pitless Adapter Installer: N/A Well Disinfected Upon Completion? ❑✓ Yes ❑ No Method of Disinfection: Comments: Please save for your engineer. Pump Installer Name: Aarow Pump & Well Service, LLC This is needed for your COSA. P.O. Box 110496 Anchorage, AK 99511-0496 Attention: The pump installer shall provide a pump installation log to the DSD within 30 days of pump installation. MUNICIPALITY OF ANCHORAGE Community Development Department Phone: 907-343-7904 On -Site Water & Wastewater Program Fax: 907-343-7997 Septic System Owner -installer Agreement A real estate property owner (Owner) may install their own septic system. The department may issue an approval for a homeowner to perform work on a conventional (not AWWTS) on-site wastewater disposal system to serve that individual's owner -occupied, single-family or duplex home if the homeowner satisfies and agrees to the following requirements. ` The property owner and excavation equipment operator may perform work on no more than one owner installed project in a 12 -month period As owner of (legal description) R C' V OW 84k a --fv Gad 1,4 1 agree the following items are true and accurate. 1. My (!�perience installing septic ,cul fsG�E� ', 2. The name of the operator is. 1 i2_ da�icj t 7,rCIr�'L 3. There will not be compensation for installation services rendered. 4. 1 will be actively involved with the septic system installation at all times. 5. The name of the inspecting engineer ism/ ,vis+ , j7Ji/G2®,erir 6. 1 agree to discuss the following items with the inspecting engineer: a. Permit design criteria and specifications. b. Inspection requirements set forth in AMC 15.65.150. c. 2 -hour minimum advance notice given to the On-site Water & Wastewater Program for all required municipal inspections. 7. 1 agree any changes I make to the items listed above will require anew approval before performing work. 8. 1 agree to have the project -speck On-site Wastewater Disposal System Permit available at the construction site for the duration of all related work. Owner's printe Owner's signa Septic System Owner d name:i�'ar!% ture: Date: Z3 Install reement Feb20 On -Site Water & Wastewater System Permit MUNICIPALITY OF ANCHORAGE Development Services Department On -Site Water & Wastewater Program 4700 Elmore Road, PO Box 196650 Anchorage, AK 99519-6650 Telephone: (907) 343-7904 Permit Number: OSP141264 Tax Code Number: 02055136000 Work Type: WellSeptic Initial Permit Effective Dates: August 29, 2014 to August 29, 2015 Design Engineer: PANNONE ENGINEERING SERVICE Subdivision: RABBIT CREEK VIEW & HEIGHTS Site Legal Address: RABBIT CREEK VIEW & HEIGHTS BILK 5H LT 1A G:3340 Owner/Address: DURRANT BIANCA & WILLIAM MICHAEL PO BOX 93 HOPE AK 996050093 Site Mailing Address: 8001 Byron DR, Anchorage This permit is for the construction of: Y Disposal Field Y Septic Tank N Holding Tank Lot Size in Sq Ft: 19824 Total Bedrooms: 3 N Privy Y Private Well N Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80). 3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either: A. Open and Close on the same day. B. Covered, sealed, and heated to prevent freezing. Received Issued By: fC Municipality of Anchorage P.O. Box 196650 • 4700 Elmore Road Anchorage, Alaska 99519-6650 a (907) 343-7904 • Fax (907) 343-7997 hftp://www.muni.org/Onsite Development Services Division On -Site Water and Wastewater Program Ment �o y r' n Department **** VARIANCEIWAIVER REVIEW **** Waiver#: OSP141367 COSA#: _ Permit#: OSP141264 PID#: 020-551-36 Legal Description: Rabbit Creek View & Heights. Block 5H, Lot 1A Engineer: PES Applicant: Mark Schimscheimer Your request for a waiver to allow the installation of Engineered Receiving Soil as described and regulated by the proposed (as of 8/29/14) version of AMC 15.65 is approved. ............................................................................... Waiver is Granted: X Waiver is not Granted: Date: P l l y Approved Name of Reviewer MUNICIPALITY OF Property owner(s) Mark Schimscheimer Day phone Mailing address 6131 Austria Drive, Anchorage, AK 99516 Community Development Department Development Services Division Legal description (Township, Range & Section) On -Site Water & Wastewater Program Lot Size 19,824 Sq. Ft. Number of Bedrooms 3 ANCHOR ACS UI 0016 Phone: 907-343-7904 Fax: 907-343-7997 ON-SITE SEWER/WELL PERMIT APPLICATION Parcell.D. 020-551-36 Property owner(s) Mark Schimscheimer Day phone Mailing address 6131 Austria Drive, Anchorage, AK 99516 Site address Carl Street Legal description (Sub'd., Block & Lot) Rabbit Creek View and Heights, Block 5H, Lot 1A Legal description (Township, Range & Section) Lot Size 19,824 Sq. Ft. Number of Bedrooms 3 APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: IN all that apply) Absorption Field Q Initial 0 Single Family (SF) Q (w/wo ADU) Septic Tank Q Upgrade ❑ (D) ❑ Holding Tank ❑ Renewal F-1Duplex Privy El Multiple Dwellings (SFand/or D) ❑ 1- x Private Well ❑X Water Storage ❑ JUL .1 8 2014 THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR: Engineered Receiving Soil Distance: I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes.. (Signature of property owner or authorized agent) Permit/Rush Fees:`f Date of Payment: Receipt Number: F�G Permit No. 9PLYJ;26d Permit App_ _- : . !-'.-c, Waiver Fees:/5' Date of Payment: 194: "'/y Receipt Number: ®C35�q it Waiver No. /`-fie/3 et7l Pannone Engineering Services Lac Steven R. Pannone, Principal Registered Professional Engineer E-mail: steve@aanengak.com August 6, 2014 Municipality of Anchorage Development Services Department On -Site Water & Wastewater Program 4700 Elmore Rd. P. 0. Box 196650 Anchorage, Alaska 99519 Subject: Rabbit Creek View & Heights, Block 5H, Lot 1A Well and Septic System Permit Request Ladies and Gentlemen: I am writing to request a permit to install a well and septic system be issued for this property. The proposed systems will serve proposed three bedroom (3) bedroom house. Currently the lot is undeveloped. The proposed system will utilize a 1500g S.T.E.P. tank with an AX20 Pod and Auxiliary Pump Vault. The surrounding lots are undeveloped. There are no wells or septics on surrounding lots within 200 feet of this system. Soils. One test hole was performed by Ted Moore in May of 2007 and one test hole was performed by Pannone Engineering Services in June of 2014, and groundwater was monitored for seven days. Ground water was observed at one foot (1.5') below the ground surface after the seven day monitoring period. It is my opinion, based on the results of the percolation tests and overall soils appearance; an application rate of 4 gallons/day/square feet should be used for a CAT III wastewater system utilizing ERS. See waiver Request. Per homeowner, I request that we be allowed to do additional test holes at time of construction as a condition of the permit. Soil Absorption System Design. a. See Sheet 2 of the design package. 2. Surface Water: There is no surface water within 100 feet of the proposed septic tank and drain field. The proposed drain field upgrade will maintain at least 100 feet from all surface water and drainage ditches. 3. Ground Water and Potable Aquifer: Well logs found for the surrounding lots all indicate wells with solid casings over 100 feet in depth through a variety of soils layers that bare water at depths of no less than 50 feet, with all static water levels over the top of the well casing at the surface. This indicates an aquifer that is deeper than any near enough the surface that they may be affected by a septic drain Mailing: P.O. Box 100217, Anchorage, AK 99510-0217 Physical: 332 East Manor, Anchorage, AK 99501 Telephone: (907) 272-8218 FAX: (907) 272-8211 Page 2 of 3 field. Additionally the aquifer at the depths is pressurized sufficiently not to allow contamination if perforated, as indicated by artesian wells on the surrounding lots. Any tank new or future located in this area and buried deep enough to have 4 feet of cover will perforate or has already perforated the same ML layer in question. There is likely existing earthwork in the area for roads, drainage ways, etc, that have already done so as well. It is highly unlikely that this drainfield will contaminate any aquifer that has potable water. 4. Topography: The existing topography slopes from the south to the north at approximately 10% in the area of the proposed drain field. There are no steep slopes in the vicinity of the drain field. S. Waiver Request for use of Engineered Receiving Soil (ERS). I am requesting a waiver to the 1992 Code to use the proposed Code Update Section of Engineered Receiving Soils (ERS). Below I will detail my request justifying the use of ERS: a. One test hole was excavated by PES in 2014. The soils logs are attached. Ground water was monitored. b. This design proposes to use two types of ERS. The base soils that will act as an interface between the existing soils and the soil absorption system (SAS) will be MoA Type II or Type IIA, which has a specified gradation per MASS. This interface will be approximately thirteen feet in depth and will be compacted to approximately 80 percent to allow free flow of the effluent through it into the native soil using MoA Waste Water Code application rates. The infiltration area of the interface between the ERS and the in-situ soil was based on the 60- 90 minute per inch percolation rate of the in-situ receiving soil. A two foot thick filter sand layer will be placed over the MoA Type II material to act as an interface between the SAS and ERS. c. The SAS is sized assuming a percolation rate of the ERS soil, assumed 6-15 MPI, which gives an application rate of 4 GPDSF. d. The system will protrude above the ground surface. The cover of the system will produce a mound, which will have at a minimum, three to one side slopes and six inches of organically rich soil to promote the growth of vegetation. 6. In-situ Soil Percolation Test Waiver: I request a waiver to the requirement to perform a percolation test on the SM layer that will be used as receiving soil under the ERS. A sieve analysis was performed on this layer to confirm the soil classification. The soil was described by sieve to be Gravelly Silty Sand. The application rate for this type of soil per 18 AAC 72.035(6) Table B is 275 square feet per bedroom (0.54 gpd/sf) for a conventional system, and we are using a much more conservative application rate of 0.5 gpd/sf for a CAT III system. 7. Drawing Markings: The Drawings are marked "For MoA Review Only'. When written notification that the review is complete and that there are no further comments is received from MoA On -Site Department, the note will be removed and "Issued for Construction" drawings will be issued. Mailing: P.O. Box 100217, Anchorage, AK 99510-0217 Physical: 332 East Manor Ave, Anchorage, AK 99501 Telephone: (907) 272-8218 FAX: (907) 272-8211 Page 3 of 3 The proposed installation will not affect the future development of the surrounding or existing lots. There are no surrounding wells within 100 feet of the proposed septic location. If you have any questions or concerns, please contact me at 272-8218. Sincerely, Steven R. Pannone, P.E. Owner/Civil Engineer Mailing: P.O. Box 100217, Anchorage, AK 99510-0217 Physical: 332 East Manor Ave, Anchorage, AK 99501 Telephone: (907) 272-8218 FAX: (907) 272-8211 I- NOTE. ADDITIONAL TEST HOLES SHALL BE PERFORMED 20' AND - 40' DOWNHILL OF PROPOSED _----_- F --- SYSTEM BEFORE INSTALLATION OF SEPTIC SYSTEM. r I I DRIVEWAY NOTE _I N THE EVENT THAT THE DRIVEWAY - EFFECTS THE PLACEMENT OF THE LOT VACANT -- RESERVE DRAIN FIELD AT ANY TIME NO WELLS OR SEPTICS ` IN THE FUTURE THE DRIVEWAY SHALL BE REMOVED AND RELOCATED TO A LOCATION THAT ALLOWS PLACEMEN- /— TH-1 a� OF THE RESERVE FIELD- - / (PES 2014; _ LIP.IIT OF FILL 1C'UTIJTY EAScibIEfJT\ TI -,i LOT'VACAN7 (T -ED MOORE 2007] x;� � NO WELLS OR S- LOT 2A PRELIMINARY SEPTIC DESIGN SEE DESIGN CRITERIA -- FOR LOT IA PRIMARY RESERVE DRAIN FIELD (P) J.CLF x x 2 5ED x +—'.3 � TD %� Orc 1 ` 4.2 4 --LF x 20'A INFILTRATION AREA A, 1 \ 1w0g T E.P- T^NK (P) L , � WITH AX 20 POD & AUX PIMP VAULT � BR I DO NOT PGCE ..;.�u PCL DIRECT_Y OVER TANK HC,US - (P) 77 i LOT VACANT / X NO WELLS OR SEPTICS \,\ � PRELIMINARY bJELL 3 s per- LOCATION FOR LOT 2A I I - �— WELL (Pl `L S' BYRON DRIVE W d2�wW'( W —AA M y 1, � 1 NOTES: PANNONE ENG SVC, LLC _--'OF A/ Ott "ate 4 FOR coNsrRucnoN P.O. BOX 100217 ANCHORAGE, AK 99510 C� qS l) PHONE (907) 272-8218 FAX (907) 272-8211 �PID.NO RABBIT CREEK VIEW & HEIGHTS, BLOCK 5H, LOT 1A 'i ..�....f oTo—sal-3s Steven R. annorae PERMIT N0. MARK SCHIMSCHEIMER I /�F CE 8149�r OSPi 41264 NSN CCARL STREET �. PLP.N ANCHORAGE, AK 99516(1><k MESS � — sa��OF 4 SPECIAL PROVISIONS TO SPECIFICATIONS 1. ALL CONSTRUCTION SHALL BE INSTALLED AS SPECIFIED IN THE MOST CURRENT EDITION OF THE MUNICIPALITY OF ANCHORAGE STANDARD SPECIFICATIONS (MASS) FOR COMPONENT PARTS AND MATERIALS USED IN CONSTRUCTION OF ON-SITE WASTEWATER DISPOSAL SYSTEMS AND ATTACHED SPECIAL PROVISIONS 2, SCOPE OF WORK: INSTALL NEW 15009 SEP_ TANK WITH AX20 POD, SOIL ABSORPTION SYSTEM, AND WELL. 3. GROUNDWATER WAS MONITORED AT 1_1 FEET BELOW EXISTING GRADE AS EVIDENCED BY THE SO[,- TEST HOLE. IF AN APPARENT WATER TABLE IS OBSERVED IN ANY OF THE EXCAVATIONS LESS THAN 1.5 FEET BELOW EXISTING GRADE NOT17YTHE ENGINEERIMMEDIATELY. 2' RIGID INNLATiON A FILTER FABRIC 25' o PERF PIPE W/ HOLES DRILLEC 18" 0.C. �DRAIN.ROCK o" ABOVE PIPE INV 2 SAND I - 0' Moa ttPE II FILL` Ala, TYPE II FILL TO BE PLACED IN 12 -INCH LIFTS CCVPACTED TO 83% 1500 i S T.E.P. TANK PROFILE DESIGN PARAMETERS PRIMARY SEPTIC SYSTEM NQ BECROOKA 3 (430 gpdj TANK SIZE. 13OOg SLE.P. Ail AX20 POD & AUX PUMP VAULT PERC R=SE. 5-15 MPI SOIL RATING. 4 GPD/SF ,',RE-' ROD. 1 12.5 SF SYS. TYPE. WIDE TRENCH A.J'ED MIN LENGTH. 22.5 LF USE 25 LF X 5.0' WIDE, 0.5' E.D., +3.5' TD TOTAL AREA: 130.0 SF TRENCH SEE DESIGN DESIGN P,ARAE/1ETERS ERS - IN-SITU INTERFACE NO BEDROOM: 3 (450 ']Pd' PERC RATES SC -90 MPI SOIL RATING: O.o GPD/SF AREA ROD: 900 SF ISE 45 LF X 200' WIDE TOTAL AREA: 00C SF LEGA-ND W WATER LINE/ WELL RADIUS SS NEW SEPTIC CM/ cM -11 0 ABBREVIA. C,NS 6"TS&v (TMP) CU COPPER DIP DUCTILE IRON PIPE TH TEST HOLE FC FOUNDATION CLEAN OUT SECTION TANK C. EA,N OUT N0. -LEAN OUT n10- Mri — 2RIGID INSULATION F I RIGID INSULATION DCO DOUBLE CLEAN OUT FILTER FABRIC PkERTER VALVE FS FLOW SPLITTER - —DRAIN ROCK 6 'BOVE PIPE INV - OG ORIGINAL GRADE FG FINISH GRADE rt 21 a PERF PIPE v/ o TOPSOIL AND VEGETATE t i s" HOLES DRILLED 18" O.C. NH* �r z0 40 jw r OZ 60 51ND n0 II----I—I I'jr� Mp4 TYPL ll FIL` 1500 i S T.E.P. TANK PROFILE DESIGN PARAMETERS PRIMARY SEPTIC SYSTEM NQ BECROOKA 3 (430 gpdj TANK SIZE. 13OOg SLE.P. Ail AX20 POD & AUX PUMP VAULT PERC R=SE. 5-15 MPI SOIL RATING. 4 GPD/SF ,',RE-' ROD. 1 12.5 SF SYS. TYPE. WIDE TRENCH A.J'ED MIN LENGTH. 22.5 LF USE 25 LF X 5.0' WIDE, 0.5' E.D., +3.5' TD TOTAL AREA: 130.0 SF TRENCH SEE DESIGN DESIGN P,ARAE/1ETERS ERS - IN-SITU INTERFACE NO BEDROOM: 3 (450 ']Pd' PERC RATES SC -90 MPI SOIL RATING: O.o GPD/SF AREA ROD: 900 SF ISE 45 LF X 200' WIDE TOTAL AREA: 00C SF LEGA-ND W WATER LINE/ WELL RADIUS SS NEW SEPTIC CM/ cM -11 0 ABBREVIA. C,NS 6"TS&v (TMP) CU COPPER DIP DUCTILE IRON PIPE TH TEST HOLE FC FOUNDATION CLEAN OUT T; TANK C. EA,N OUT N0. -LEAN OUT n10- Mri LI'C IITOR TJBE NO. F I RIGID INSULATION DCO DOUBLE CLEAN OUT PkERTER VALVE FS FLOW SPLITTER BFG BELOW FINISH GRADE OG ORIGINAL GRADE FG FINISH GRADE TS&V TOPSOIL AND VEGETATE Noyes: PAMONE ENG SVC, LLC _ �'OF A ��lCate FOR coNsrRucnoN .... Cq lit 8/26/1 4 P.O. BOX 100217 ANCHORAGE, AK 99510 S PHONE (907) 272-8218 FAX (907) 272-8211 i�g`P �Z*0 scale N IS %* P.Lo- No RABBIT CREEK VIEW &HEIGHTS, BLOCK 5H, LOT 1A.ozo-aal-ss Steven R� annone MARK SCHIMSCHEIMER / / PE 1T INo. DO CE 8149 .'� / OSP141264 BYRON DRIVE CARL STREET �) s � r DESIGN DETAILS ANCHORAGE, AK 9951E ��Ii�FROFESsaNP` Sheet 2 of 4 4JIM SLIDE SF-- -) F ECOF 6" f OVER THIS CONNEC TG PR01 SHEEP, PRGTECT!0In— EXTEND TO BRIDGE EXCAVATION ADVANTEX DESIGN ADVANTEX � a" ADVANTEX AXE' POD LOCATE BESIDE TANK TANK BEDDING DETAIL PASSIVE AIR LE„NouT 3.6 NATI'dE MATERIAL MGA. TYEE II GRAVEL (NFS) B E D TER K W/ SEDER ROCK i `, =_5-1300 SEP. TANK `—LIMITS OF=XCAdATION i--2' TYP_ SECTION BUOYANCY CALCULATION SEIGHT CALCUL -'TIONS Puoant ForceFo,ce Weight of Nater Displaced .Plx(5. 4)xIO +7 61,:62.4 PCF = 15.039 // Up COUNTER %EIGHT '-some �at r C& surto e - all soil saturated 4 Burne angle of repose - C Degree Assume bedd-ao does al add to force down Assume ank c -s no weight Weight of 1,10A type I ill"oPCF - 62.4 PCF)=72.6 get f2'x5.3x IC -6.28)x%26 PCF = 7,240 0 Dawn weight of Native Soil !120 PCF - 62.4 PCF)=57.6 -of (3.6 x5.3'IC-11 31 )sZ6 NCF = 10,309 E Dawn Total Weight on Tank = 17,379 OKI NOTES: ��� ���\� Date PANNONE ENG SVC, LLC OF A / FOR COPNSTRUCTION .Lq `l) 8/26 14 P.O. BOX 100217 ANCHORAGE, AK 99510 scale PHONE (907) 272-8218 FAX (907) 272-8211 �g y NTS RABBIT CREEK VIENI & HEIGHTS, BLOCK 5H, LOT 1A_ MARK SCHIMSCHEIMER Steven R_ Ponnone / PERMIT NO. -P, CE 8149 .'�% OSP14126-4 BYRON DRIVE/ CARL STREET SITE SECTION ANCHORAGE, AK 99510 11 Sheet sheet 3 OF 4 TEST HOLE 1 OR ORGANICS 1 6/12/2014 0 2 -77 6/4/2014 3 CLOCK 4 READING DATE 5 ML BLUISH SILT 6 — READING 7 6/4114 SEE NOTE 8 2 9 I SILTY SAND SM WITH SOME 10 GRAVEL 11 5 BOH 6 12 13 — i 14 15 16 17 18 DATE PERFORMED: 6/4/14 SOILS LOG - PERCOLATION TEST SLOPE X TH WAS GROUND WATER ENCOUNTERED? Y IF YES, AT WHAT DEPTH? -2.0' DEPTH TO WATER AFTER MONITORING? -1.5'- DATE: 6/12/14 TH MOORE 2007) ' SITE PLAN ---- TH-1 (PES 2014) \, / \ 10' UTILITY EASEM JCF � \ C 3BP SLOPE TH X PEROLATION RATE ` (min/inch) PERC HOLE DIAMETER 6 inches TEST RUN BETWEEN 9 FT AND 10 FT COMMENTS: Test hole excavated by A+ HOME SERVICES. Perc test was not possible due to depth of soil stratum and presence of groundwater. See soils sieve analysis. PERFORMED BY: Steven R. Pannone, P.E. I CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDLINES IN EFFECT ON THE DATE OF THIS TEST. NOTES: ���� \\V Dote PANNOoNE4 ENG SVGE,C, 9slsLo �e oF. gCgsL�� 8/26/14 FOR CONSTRUCTtON PHONE (907) 272-8218 FAX (907) 272-8211j g�P '�y�j� scnlr *: gg RABBIT CREEK VIEW & HEIGHTS, BLOCK 5H, LOT 1,k- - 32o-541-36 MSteven RPan - , _ ARK SCHIMSCHEIMER � PERMIT No. OSP141264 EYRON DRIVE/ CARL STREET SOILS LOG ANCHORAGE, AK 99516 ��1��pROFESSDNp�� Sheett 4OF 4 CLOCK WATER READING DATE TIME ,NETTIME LEVEL NET DROP READING 1 6/4114 SEE NOTE 2 s 4 5 6 PEROLATION RATE ` (min/inch) PERC HOLE DIAMETER 6 inches TEST RUN BETWEEN 9 FT AND 10 FT COMMENTS: Test hole excavated by A+ HOME SERVICES. Perc test was not possible due to depth of soil stratum and presence of groundwater. See soils sieve analysis. PERFORMED BY: Steven R. Pannone, P.E. I CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDLINES IN EFFECT ON THE DATE OF THIS TEST. NOTES: ���� \\V Dote PANNOoNE4 ENG SVGE,C, 9slsLo �e oF. gCgsL�� 8/26/14 FOR CONSTRUCTtON PHONE (907) 272-8218 FAX (907) 272-8211j g�P '�y�j� scnlr *: gg RABBIT CREEK VIEW & HEIGHTS, BLOCK 5H, LOT 1,k- - 32o-541-36 MSteven RPan - , _ ARK SCHIMSCHEIMER � PERMIT No. OSP141264 EYRON DRIVE/ CARL STREET SOILS LOG ANCHORAGE, AK 99516 ��1��pROFESSDNp�� Sheett 4OF 4 w -1. 1-- -1 VJ .... J111L 11VIIYLl I III VNU1IL I LIQ 1-1/2 3/4 3/8 #4 #10 #20 #40 #100 1200 100 90 80 70 s w 60 3 w 50 z w v w 40 a 30 20 10 , 0 100 10 1 0.1 0.01 0.001 GRAIN SIZE IN MILLIMETERS GRAVEL SAND COBBLES SILT or CLAY NMA rlfe NMR Ulm rilE SYMBOL SAMPLE SOURCE DEPTH (feet) CLASSIFICATION — — — — Gravelly Silty Sand (SM) Crowther Associates Particle Size Distribution Plate Geotechnical Engineering Services Lot 1A Block 5H Rabbit Creek View Subdivision Anchorage, Alaska Job No, 040.002 Pannone UA B5H Rabbit Creetk View Date June 2014 ADVANCED WASTEWATER TREATMENT SYSTEM MAINTENANCE AND REPAIR AGREEMENT BETWEEN MUNICIPALITY OF ANCHORAGE AND THIS MAINTENANCE AND REPAIR AGREEMENT made and entered into as of this �.S Day of of 20/y by and between herein the "OWNER," and the Municipality of Anchorage, herein the "MUNICIPALITY." In consideration of the mutual covenants contained herein, the parties to this Maintenance and Repair Agreement agree as follows: 1. Advanced Wastewater Treatment Systems. Municipality grants permission to Owner to utilize and operate an Advanced Wastewater Treatment System (AWWTS), described as located at (legal description). 2. Definitions. Alteration. Any change to the design or function of an A W WTS that includes the installation or removal of any parts, components or pieces not included in the original construction permit and design. Certificate of On -Site Systems Approval (COSA). An approval by the Municipality of existing water and wastewater disposal systems given at the time of property sale and title transfer in accordance with Anchorage Municipal Code (hereinafter, "AMC') 15.65. These approvals certify that the systems are adequate for the homes that they support and meet the codes that were in place at the time of system construction. Damage. Any man-made or natural change in a system that would inhibit the system from performing as designed. Maintenance and Repair. The scheduled and as needed replacement of existing parts, components and pieces of an AWWTS that were included in the original design which would allow the AWWTS to continue to perform as designed. Permit. An On -Site Wastewater Disposal Permit as required by AMC 15.65 to construct and operate an AWWTS. 3. Term. The term of this Maintenance and Repair Agreement shall begin on the date of approval by the Municipality to operate the installed system or issuance of a COSA, and shall continue while the AWWTS is in use or is operational or until the property is sold or title is transferred by the owner and a new COSA is issued to the new owner or transferee of the property. 4. Alterations, Installation and Removal of Additional Equipment. Prior to performing any alterations to an AWWTS, the owner agrees to obtain an On-site Wastewater Disposal Permit from the Municipality in accordance with AMC 15.65. 5. Maintenance and Repairs. A. Throughout the term of this Maintenance and Repair Agreement, the Owner shall maintain their AWWTS in a satisfactory condition capable of producing treated septic effluent in accordance with the equipment's approval for operation in the Municipality. The owner shall enter into a service alzreement with an AWWTS service and maintenance provider approved by the municipality and the manufacturer of the AWWTS for the entire term of the AWWTS. In addition, it shall be the responsibility of the Owner during the term of this Maintenance and Repair Agreement, and any renewals thereof, at the owner's sole expense, to pay for any and all: (1) repair(s), (2) maintenance, (3) adjustment(s), (4) replacement costs, and (5) inspection costs. B. Owner agrees to comply with all applicable ordinance, laws, regulations, rules and orders for the AWWTS. C. Upon request by the Municipality, the owner agrees to provide the Municipality a written schedule of routine maintenance and repairs which have been performed on the system. When a record of maintenance is documented and maintained by the system vendor, the owner agrees to allow the Municipality access to this information. D. Owner acknowledges that the fine for failing to maintain and repair an AWWTS may be assessed in accordance with AMC 14.60 for improper discharge. F. Owner agrees that only maintenance and repair personnel approved by the Municipality will inspect and make any necessary maintenance, repairs or permitted alterations to the system. F. Owner agrees to grant the Municipality reasonable access to test and inspect the AWWTS upon 24 hours written notice. G. Owner agrees that any sale or transfer of title of the property will not occur without a new Certificate of On -Site Systems Approval. H. Owner agrees that the AW WTS installation and maintenance requirements as provided by the AWWTS vendor/installer and approved by the Municipality are the governing guidelines for the construction, maintenance and repair of the Owner's AW WTS. 6. Nonwaiver.. The failure of either party at any time to enforce a provision of this Maintenance and Repair Agreement shall in no way constitute a waiver of the provisions, nor in any way affect the validity of the Maintenance and Repair Agreement or any part hereof, or the right of such party thereafter to enforce each and every provision hereof. 7. Amendment. A. This Maintenance and Repair Agreement shall only be amended, modified or changed by a writing, executed by authorized representatives of the parties, with the same formality that this Maintenance and Repair Agreement was executed with, and such writing shall be attached to this Maintenance and Repair Agreement as an amendment. B. For the purposes of any amendment modification or change to the terms and conditions of this agreement, the only authorized representatives of the parties are: a. Owner: 5r ,zt% ,� '� 5 t /'/ C /ll C. b. Municipality: Director, Community Development or designated authority C. Any attempt to amend, modify, or change this contract by either an unauthorized representative or unauthorized means shall be void. I 8. Jurisdiction: Choice of Law. Any civil action arising from this Maintenance and Repair Agreement shall be brought in the Superior Court for the Third Judicial District of the State of Alaska at Anchorage. The laws of the State of Alaska shall govern the rights and obligations of the parties under this Maintenance and Repair Agreement. 9. Severabilitv. Any provisions of this Maintenance and Repair Agreement decreed invalid by a court of competent jurisdiction shall not invalidate the remaining provisions of the Maintenance and Repair Agreement. STATE OF ALASKA THIRD JUDICIAL DISTRICT The foreg, 20( Ll, by My Commission expires: MUNICIPALITY: Date: r" l (- ss. d ed before me this day of , Date: name) Title: • 'rt Municipality of Anchorage 9 On -Site Water and Wastewater Program (907) 343-7904 Certificate of On -Site Systems Approval Parcel I.D. 620-551-36 Expiration Date: 1. GENERAL INFORMATION Complete legal description RAbbit Creek View & Heights, Block 5H, Lot 1A Location (site address) 16751 Carl St. Current Property owner(s) Mark Schlmscheimer Day phone Mailing address 6131 Austria Dr. Anchorage, AK 99516 Real Estate Agent Day phone 2. TYPE OF DWELLING: i] Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF 3 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Individual Well 1XI Individual Z Individual Water Storage ❑ Holding Tank ❑ Community Class Well ❑ Community . ❑ Public Water System ❑ Public Sewer 1771 WaiverNariance Received by:Date: 4COSA to be released to t e ngineer, unless otherwise requested by the engineer. - - COSA Fee $ `29.gD // Waiver Fee $ Date of Payment -11111'5 i�"n,_ Date of Payment Receipt Number Receipt Receipt Number ` COSA # SULCI 5) 3'�0 Waiver # 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. In conducting an adequacy test, I attempt to provide a thorough, conscientious engineering analysis of the system in accordance with MoA COSA guidelinesand regulations. The reported results describe the performance of the system under the conditions encountered at the time of the test, and separation distances measured to readily identifiable features. The operational life of all wells and septic systems depend on the local soil condition, ground water levels that may fluctuate during the year, and the water usage of the family being served by the system. These conditions are outside the control of the evaluator of this system. All systems eventually fail and satisfactory test results do not guarantee future performance of the system, nor do they guarantee that there are no hidden defects or encroachments. Therefore we cannot provide any warranty for future performance, nor can we estimate remaining life of the system. The content of this report is for the sole benefit of the owner listed above. Name of Firm Pannone Engineering Services LLC Phone (907) 272-8218 Address P.O. Box 100217, Anchorage Ak. 99510 Engineer's Printed Name Steven R Pannone 6. DSD SIGNATURE System #1 Approved for bedrooms System #2 Approved for bedrooms Disapproved Date 7/20/2015 Conditional approval for bedrooms, with the following stipulations: By: f G�% r/ Original Certificate Date:' The nic' rage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the epresentations given in paragraph 5 b an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. - - ATTACHMENTS: COSA Checklist X Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other COSH blue sheet f .., c If more than 1 septic system is on the lot: COSA Checklist # 1 of Structure served by this system 1 Certificate of On -Site Systems Approval Checklist Legal Description: Rabbit Creek View & Heights, Block 5H, Lot 1A Parcel ID: 020-551-36 A. WELL DATA Well type Private If A, B, or C provide PWSID # Well Log (YIN) Y Date completed 9/24/2014 Sanitary seal (YIN) Y Wires properly protected (Y/N) Y Total depth 83- ft. Cased to 83 ft. Casing height'(above ground) 18+ in. FROM WELL LOG AT INSPECTION Date of test 9/24/2014 New Static water level 2 ft, New ft.' Well production 12 g.p.m. New g.p.m. WATER SAMPLE RE LILTS: ,�15 Coliform Neg co ora3ales/100 mL Nitrate 0.702 mg/L Arsenic ND ug/L Date of sample: 7/1/2015 Collected by-. PES B. SEPTIC/HOLDING TANK DATA Tank Type/Material Advantex/Steel Date installed 6/9/2015 Tank size 1,500 gal Number of Compartments 2— Cleanouts (Y/N) Y Foundation cleanout (Y/N) Y Depression over tank (Y/N) N High water alarm (Y/N) Y ' Date of pumping New Pumper N/A C. ABSORPTION FIELD DATA Date installed 6/5/2015 Soil ratingi 2 4 GPD/SF Shallow Trench (g.p.d./ft or ft /bdrm) System type Length- 25 ft. Width 5 ft. Gravel below pipe 0.5 ft. Total depth 3 ft. Eff. absorption area 125 W Monitoring tube Y Depression over field N Date of adequacy test New Results (Pass/Fail)- Pass For 3— bedrooms Fluid depthin absorption field before test New in. : Water added New gal. New depth New in. Elapsed Time: New mina Final fluid depth New in. Absorption rate >= 450+ g.p.d. Any rejuvenation treatment (past 12 mo.) (Y/N & type) NO If yes, give date D. LIFT STATION bate installed 7/8/2015 "Pump on" level at 43 in. Datum Bottom of Tank E. SEPARATION DISTANCES WELL ON LOT TO: Size in gallons 250 "Pump off" level at 40 Cycles tested New Septic tank/lift station on lot 100+ Absorption field on lot 100+ Public sewer main 75+ Sewer /septic service line 25+ _ Manhole/Access (Y/N) Y— in. High water alarm level at 45 Meets alarm & circuit requirements? Yes On adjacent lots 100+ On adjacent lots 100+ Public sewer manhole/cleanout 100+ Holding tank 100+ Animal containment areas 50+ Manure/animal excrete storage areas 100+ SEPTIC/HOLDING TANK ON LOT TO: Building foundation 5+ Property line 5+ Absorption field 5+ Water main 10+ Water service line 10+ Surface water 100+ Wells on adjacent lots 100+ ABSORPTION FIELD ON LOT TO: Property line 10+ Building foundation 10+ Water main 10+ Water Service line 101+ Surface water 100+ Driveway, parking/vehicle storage 10+ Curtain drain 50+ Wells on adjacent lots 100+ F. COMMENTS G. ENGINEER'S CERTIFICATION I certify that I have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. Engineer's Printed Name Steven R. Pannone Date 7/20/2015 COSA canary sheet 2-5-15.doc in. LOT 6A 30' N8 79.81' 79.81' 10' Utility Easement Clean Out I (TYp•) Mon Hole -4A, Lid tCom. Vent H W W 0 0.i 00 Q wood De z od dee 0 I 30' LOT 1A BLOCK 5H 0 M 2 Level Wood Frame Residence on Concrete Block Foundation Well S80'1 1 _ BYRON DRIVE NOTE: Distances are measured to the wood trim. I hereby certify that an accurate survey of the following described property: RABBIT CREEK VIEW Sc RABBIT CREEK HEIGHTS SUBDIVISION (2004-91) LOT 1A, BLOCK 5H was made on June 11, 2015 and that the improvements situated thereon are within the property lines and do not overlap or encroach on the property lying adjacent thereto, that no improvements on the property lying adjacent thereto encroach on the premises in question and that there are no roadways, transmission lines or other visible easements on said property except as indicated hereon. Easements other than those shown on the record plat may not appear on this drawing. Anchorage Alaska, this 17th day of June 2015. SCALE : 1 " = 20' 0' 10' 20' 40' LOT 2A 0 M