Loading...
HomeMy WebLinkAboutCROSS VIEW ESTATES BLK 2 LT 16Cross View Estates Block 2 Lot 16 #015-221-78 Municipality of Anchorage Community Development Department Page 1 of 3 On -Site Water and Wastewater Program 4700 Elmore St. • P.O. Box 196650 Anchorage, AK 99519-6650 • http://www.muni.org/onsite • (907) 343-7904 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP141444 PID Number: 015-221-78 ❑✓ New ❑ Upgrade Name: Colony Builders, Inc. ABSORPTION FIELD ❑✓ Deep Trench ❑ Shallow Trench ❑ Bed ❑ Mound Address 9420 Vanguard Drive Anchorage, AK 99516 ❑ Other Phone Number of Bedrooms Soil Rating Total depth from original grade 6 .45 GPD/SF 12.3 Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade 4.3 Ft. Gravel depth beneath pipe 8•0Ft. Subdivision Block Lot Cross View Estates 2 16 Fill added above original grade 1-2 Ft. Gravel length 126 Ft. Township Range Section Gravel width 3Ft. Beds: Number of Lines Distance between lines Ft. SEPARATION DISTANCES To Septic Absorption Lift Station Holding Sewer Total absorption area Number of trenches Dist. between trenches From Tank Field Tank Line 2,016 Fe Two >1617t. Well >100' >100' >100' >7 >25' TANK 0 Septic ❑ S.T.E.P. ❑ Holding ❑ Other Manufacturer Anchorage Tank Capacity 2,000Gal. Surface Water >100' >100' N/A N/A Material Number of compartments Lot Line >5' >10' N/A N/A Steel Two NA Foundation >5' >10' N/A N/A LIFT STATION Manufacturer Capacity Curtain Drain None Noted Gal. Remarks Pump on level at in. Pump off level at in. High water alarm at in. Pump make and model Electrical Inspections performed by Installer PIPE MATERIAL House to tank D3034Tank to D3034 drainfield Red Dog Excavating Drainfield F810 CO/MT D3034 Inspector A. Harala BENCH MARK (Assumed elevation) 100.0ft Inspection 15' 11/14/ od 1 11/15/ Location and description dates: 2 3`° 6/29/ 4'° ISS', Bottom Step Back Deck. COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL 4xi�F 4mitimp 14 Conditional Approval: DateAV ®� . i 4 9 TH M. -'��'® �••• •.•e• .••• ••.• • •••••• ••® D..•. . ..... .... .••o•� e..�/ �� -.MICHAEL E. ANDERSON : 4 CE - 4381; _`�Ar � Approved pp >?t %d- Date 6130 J5 1®pRWSOFE0O '®' Ctase d w CSS inspection Keport_i-i-il.aoc 1 On-Site Water & Wastewater System Permit OSP141444 01522178000 WellSeptic MUNICIPALITY OF ANCHORAGE Development Services Department On-Site Water & Wastewater Program 4700 Elmore Road, PO Box 196650 Anchorage, AK 99519-6650 Telephone: (907) 343-7904 Permit Number: Tax Code Number: Work Type: Permit Effective Dates: October 20, 2014 to Design Engineer: ANDERSON ENGINEERING Subdivision: CROSS VIEW ESTATES Initial October 20, 2015 Site Legal Address: CROSS VIEW ESTATES BLK 2 LT 16 G:2737 Owner/Address: COLONY BUILDERS INC 9420 VANGUARD DR ANCHORAGE AK 995070000 Site Mailing Address: 5544 HERITAGE HEIGHTS DR, Anchorage Lot Size in Sq Ft: 53835 Total Bedrooms: 6 This permit is for the construction of: Y Disposal Field Y SepticTank N Holding Tank N Privy Y Private Well N Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Ddnking Water Regulations (18AAC80). 3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either: A. Open and Close on the same day. B. Covered, sealed, and heated to prevent freezing. UB ITTA MUNICIPALITY OF ANCH R/ ( [ Community Development Department Phone: Development Services Division On-Site Water & Wastewater Program ON-SITE SEWER/WELL PERMIT APPLICATION Pamel I.D. 015-221-78 Property owner(s) Colony Builders Mailing address 9420 Vanguard Drive Anchorage, AK 99507 Day phone Site address NHN Heritage Heights Drive Anchorage, AK 99516 Legal description (Sub'd., Block & Lot) Cross View Estates, Block 2, Lot 15 Legal description (Township, Range & Section) LotSize 53,835 Sq. Ft. Number of Bedrooms Six(6) APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: ([~;~ all that apply) Absorption Field [] Initial [] Single Family (SF) [] (w/we ADU) Septic Tank [] Upgrade [] Duplex (D) [] Holding Tank [] Renewal [] Multiple Dwellings [] Privy [] (SF and/or D) Private Well [] Water Storage [] THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR: Dis tance: I cer[ify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit/Rush Fees: ~(o~" ,~15"' -~ ~'l'~VVaiver Fees: Date of Payment: ~~0 ~/~ Date of Payment: Receipt Number: 0 ~ ~ Receipt Number: Permit No. ~1~ I~y ? Waiver .o. Permit App_9-1-12.doc October 21 2014 Municipality of Anchorage Development Services Department On-Site Water and Wastewater Program 4700 Elmore Road Anchorage, AK 99519-6650 Su~e~: Lot 16, Block 2, Cross View Estates Subdivision Septic System Design and Permit Application Impacts to Adjacent Properties Dear Onsite Services Engineer: The owner of Lot 16, Block 2, Cross View Estates Subdivision intends to construct, a new six-bedroom home on the lot. We are therefore requesting a permit be issued for the construction of a new well and septic system to accommodate the home. The attached Site Plan and backup documentation identify the location and configuration of the proposed well and septic system along with the alternate site. Also identified on the plans are the existing wells in the area and septic systems on surrounding lots. No conflicts exist between the proposed septic system and well or septic systems and wells on adjacent lots. Drainage arrows and ground surface contours are shown on the site plan showing the grade and direction of flow on the lot. The drainage pattern will not be changed as a result of this project. The test holes placed on the lot in the area of the absorption trenches and alternate site indicate silty sand with gravel (SM/ML). The percolation rate of the soil at the test holes was determined to be 31-60 minutes per inch. No groundwater was found during the placement of the test hole and none was noted dudng the monitoring period. An application rate of .45 gallons per day per square foot was used in the design of the absorption system. We are proposing to place a new 2,000-gallon septic tank and 2- 63' long by 3' wide by 8' effective depth absorption trenches to treat and dispose of the effluent generated in the house. The elevation of the distribution line in the absorption trench will be 3' below the surface and the total depth will be 11'. A flow splitter valve will be placed to insure even flow to each trench. A minimum of 3' of fill or 2" of insulation and 2' of fill will be placed over the absorption trench and 4' over the septic tank. The ground 'surface on the lot in the area of the septic system slopes to the southeast at a shallow grade with some cross sloping from the east. The new trenches will be Lot 16, Block 2, Cross Point Estates Subdivision October 2, 2014 Page Two constructed parallel with the contours of the slope as much as possible in conformance with Municipal requirements. The new septic system will be constructed a minimum of 100' from all wells and any surface water and 10' the proposed and existing water services in the area. If the system is constructed in accordance with our design the following statements apply: The system, if constructed as designed, will have no adverse impact on the wells in the area or those to be constructed in the future. The system, if constructed as designed, will have no adverse impact on existing septic systems in the area or those to be constructed in the future. The system, if constructed as designed, will have no adverse impact on reserve space, either surface or subsurface, on any lots located in the area. The system, if constructed as designed, will have no adverse impact on drainage patterns in the area. The current drainage pattern will be maintained. Sincerely, Michael E. Anderson, P.E. Attachments i 49th LOT 17, BLOCK 2 v^cA., / /.; / ..... . /~ AREA MAP CROSS PLAT NO. 2006-171 VI EW ESTATES LOT 16, BLO 53,835 S.F. NOTE: ~ No Arees of Excessive Slope o~r~ Sur¢ace Water are Within 100' of Any Por~ of the New Septic System, BDIVISION 2 STORM DRAII THI CO 2-63' Long x 3' Wide x 8' Effective Absorption 'enches. LEGEND: co - Cleonout SV - Septic Vent FCO - Foundation C[eenout TH - Test Hole tOT - Monitor Tube 2C0 - Double Clean Out FSV - Flow Splitter Valve 20' STORM DRAIN 4~ 69'49'04-"E 196.91' SITE PLAN SCALE 1' = 50' CONTOUR INTERVAL - 2' ~'~/ 49th MICHAEL E. ANDERSON No. C£-4381 LOT 16, BLOCK 2, CROSS VIEW ESTATES SUBDIVISION DESIGN FACTORS: SYSTEM REQUIREMENTS: Six Bedroom Home Deep Trench System Perc. Rate: 30-60 Min,/Inch 2,000 Gallon Septic Tank Application Rate: .45 GPD/SF 8' Drainfield Rock 6 Bedrooms X 150 GPDt.45 GPD/SF (Application Rate) = 2,000 SF Absorption Area 2,000 SF/16 SF/LF = 125 LF Trench Length THEREFORE: Construct 2 - 63' Long x 3' Wide x 8' Effective Depth Absorption Trenches at the Location Shown. Flow Line Elevation in Trenches to be 3' Below Original Ground Surface. Total Depth to be 11' Below Existing Ground. Provide 4' Cover Over Septic Tank and 3' Cover Over Absorption Trench. Maintain 100' Separation from Wells in theAraa. Natural Backfill Geote~Jle Fabdc ('~ 4" Perforated 6" V PVC (Holes Down) Drainfield Rock TYPICAL DEEP TRENCH SECTION SCALE .......... NOTE: Grade Area Over Trench to Drain Away. ~ ~ Minimum 6 Separation From Bedrock. ~........,.,,,,,,.,,,.,,. ........... ~:,.....~ Minimum 4' Separation From Groundwater , . . · ....~.~ Minimum 100 Separabon From Wells in the Area. ~A~ Minimum 100' Separation From Su~ce Water or Streams.-~:%. /:~ Development Services Department Building Safe~ Division P.O. Box 196650 ~chorage, AK 99507 WAS GROUND WATER 2- 3- 4- 13- 14- 17- 20- ENCOUNTERED? IF YES, AT WHAT DEPTH? Depth to Water After ~ Monitoring? Date: Reading Date Gross Time Net Time Depth to Water Net Drop PERCO~TION RATE ~ (minut~nch) _PERC HOLE DIAMETER -~ ~ a PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: Municipality of Anchorage Development Services Department 4700 Elmore Road ~ ~ICHAEL P.O. Box 196650 Anchorage. AK 99507 Soils Log- Percolation Test Pe,ormed For: Date Pe,ormed: LegalDescdption: ~ ~[[~ ~. ~1~/ p~ Township, Range, Se~ion: 1 2- 3- 4- 7- 10- 11- 12- 13- 14- 15- 16- 18- 20- COMMENTS WAS GROUND WATER aiI ENCOUNTERED? IF YES, AT WHAT DEPTH? L Depth to Water After · 0 P Monitoring? l~J ~'~ ~' E Reading Date Gross Time Net Time Depth to Water Net Drop / ;11 / PERCOLATION RATE (mJnute~4nch) PERC HOLE DIAMETER AND ~ FT PERFORMED BY: ~/~ ff~r~f~ CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: Pedormed Far: Municipality of Anchorage Development Services Department Building Safely Division On-Site Water and Wastewater Program 4700 Elmare Road P.O. Box 196650 Anchorage, AK 99507 www.ci.anchoraae.ak.es (907) 343-7904 Soils Log - Percolation Test 7- 8- g- 10- 11- 12- 13- 15- 16- 17- 18- 19- 20- WAS GROUND WATER ENCOUNTERED? IF YES, AT WHAT DEPTH? Monitoring? Reading Date Gross Time Net Time Depth to Water Net Drop PERCOLATION RATE (minum~lnch) PERC HOLE DIAMETER 7 COMMENTS [~,~_- AND ~' FT PERFORMED BY: ~f"2/'? ~'~/~ J CERTIFY THAT THIS TEST WAS PERFORMED iN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: