HomeMy WebLinkAboutRAPTORS KNOLL LT 1Raptors Knoll
Lot I
#017-101-58
Municipality of Anchorage
Community Development Department Page 1 of 2
On-Site Water and Wastewater Program
4700 Elmore St. • P.O. Box 196650 Anchorage,AK 99519-6650• http://www.muni.org/onsite•(907)343-7904
ON-SITE WASTEWATER INSPECTION REPORT
Permit Number: OSP181036 PID Number: 017-101-58 ❑✓ New ❑ Upgrade
Name:
RAPTOR PROPERTIES LLC ABSORPTION FIELD
Address 0 Deep Trench ❑ Shallow Trench 0 Bed 0 Mound
RAPTORS KNOLL CIRCLE ❑ Other
Phone Number of Bedrooms Soil Rating Total depth from original grade
3 0.6 GPD/SF 12.5 Ft.
LEGAL DESCRIPTION Depth to pipe invert from original grade Gravel depth beneath pipe
Subdivision Block Lot 2.0 Ft. 10.0Ft.
RAPTORS KNOLL 1 Fill added above original grade Gravel length
Township Range Section
2.0 Ft. 40 Ft.
Gravel width Beds:Number of Lines Distance between lines
SEPARATION DISTANCES 2.5Ft. N/A N/A Ft.
To Septic AbsorptionHolding Sewer Total absorption area Number of trenches Dist.between trenches
From Tank Field Lift Station Tank Line 800 Ft2 Ft.
Well 119.1 123.3 N/A N/A 74.1
TANK O Septic ❑S.T.E.P. ❑Holding 0 Other
Manufacturer Capacity
Surface water 100+ 100+ N/A N/A GREER 1000Ga1.
Material Number of compartments
Lot Line 21.9 10.8 N/A N/A PLASTIC 2
NA -
Foundation 59.5 68.3 N/A N/A LIFT STATION
Manufacturer Capacity
Curtain Drain 50+ 50+ N/A N/A Gal.
I
Pump on level at Pump off level at High water alarm at
Remarks
in. in. in.
Pump make and model Electrical Inspections performed by
PIPE MATERIAL House to tank 3034 Tank to 3034
Installer drainfield
POMRAINGING EXCAVATION Drainfield 3034 CO/MT 3034
Inspector PANNONE ENGINEERING SERVICES BENCH MARK (Assumed elevation) 84.0ft
Inspection iv Location and description
dates: 1 10/18/18 2,., 10/19/18
Td 10/19/18 4'" 12/6/18
NW BOTTOM HOUSE TRIM
COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL Engineer's Stamp
�t
Conditional Approval: Date ��P,�(.OF A(,Qs��l+
St ,.. ;I5annorae kr
r0} :* 814 ,Approved '� . 6WS Date 41/18 �k� 2C +i'CC4 tt a�A.,�
holt Tim �c k 1 uilA
Inspection Report_1-1-12.doc V
* SITE NOTES:
1. DRIVEWAY LOCATION SHOWN IS FROM DEVELOPER'S PLOT PLAN. PES DID NOT DESIGN DRIVEWAY AND IS NOT
RESPONSIBLE FOR IT'S LOCATION. THE DRIVEWAY WILL BE CONSTRUCTED ABOVE ORIGINAL GRADE AND WILL NOT
CREATE ANY CUT SLOPES ON THE LOT, ABOVE OR BELOW THE SEPTIC SYSTEM.
2. RETENTION BASIN IS REQUIRED BY PLAT. THE BASIN WILL BE NO MORE THAN 2 FEET DEEP. THIS LOT IS TYPIFIED BY
DRY WOODLAND VEGETATION, WITH WELL PERCOLATING SOIL. IT IS NOT LIKELY THAT THIS RETENTION BASIN WILL EVER
CONTAIN WATER.
3. ANY SLOPE WITHIN 50' OF THE DRAINFIELD WILL BE AT 4:1 OR FLATTER.
DESIGN PARAME ERS -„ INSTALLED BRAIN FIELD
PRIMARY SEPTIC SYSTEM \I s.\ W 4OLF x 2.5'W x 10.0'ED x 12.5'TD'
NO. BEDROOM: 3 (450 gpd) 4 `"I-W \ INSTALLED CLEAN OUT AND / amt,
TANK SIZE: 1000 MONITOR TUBE AT EACH END
PERC RATE: 17 MPI oz \ \ i -�
SOIL RATING: 0.6 GPD/SF D RESERVE DRAIN FIELD P
AREA RQD: 1000 SF I o J .ES •co T.-10LF x 2.5'W x 10.0'ED x 12.5'TD
SYS. TYPE: DEEP TRENCH 10.0'ED w 0' BASED ON CAT III
MIN LENGTH: 37.5 LF \ o ��_ 1
1 11-1-2
1.
USED: m ANDERSON INSTALLED 1000q SEPTIC TANK =
40 LFx2.5'Wx10.O' E.D., 12.5' TD o \ �` W/ FOUNDATION CLEAN OUT BEFOR§
TOTAL AREA: 800 SF \ T, r t AND DCO AFTER
� � F , , , Jj.
\
DESIGN PARAMETERS
RESERVE SEPTIC SYSTEM i tai n ` -J I 4
NO. BEDROOM: 3 (450 gpd) 1 \
Vi%TANK SIZE: 1500 ADVANTEX __ ci DRIVEWAYBR \ \ o1N/ AX20 POD -Ni --~ \ USF •
PERC RATE: 17 MPI w�M ` 1i �`E A B
SOIL RATING: 4 GPD/SF \ \
AREA ROD: 150 SF z FC 3.5 51.6SYS. TYPE: DEEP TRENCH 10.0'ED v fid' \ � Ti 62.1 95.1
MIN LENGTH: 5.6 LF . ` T2 63.2 99.2
O • I RETENTION BASIN SEE NOTE 2.
\ • MT 60.8 98.1
USE: Y
10 LFx2.5'Wx10.0' E.D., 12.5' TD \ \ L .
\ WEA-y` DCO 66.5 101.6
TOTAL AREA: 200 SF o Cl 69.6 97.6
/J_ \ M1 70.7 98.5
__,7c%. \ ` ! 10' UTILITY EASEMENT C2 105.0 138.8 s'/ N
M2 1424.6 1 138.0
z
o'- F- --
> D
<0 0 0
a aa zzQ ,,,Zo .2 m
z3 ) T< O ~
1.0 U 0 $u i o1 FILTER FABRIC 2.
- _ OC.FC. _ _, c, Z a
79.0 u 2 DRAIN ROCK 6"ABOVE PIPE INV 0 6
// 4o ORA!N PIPE F.C.78.0
- O.C.76.0
t R+ -1.0
�'• i• is i• i i �•
74.4 74.2 CONNECT �T.'.11:$��,:e-•,• .��••t♦`Y•� ��•�
To mom 'v`j`[�',X``.tiX�:� iX.�, �-��i. -2.0
1000 g SEPTIC TANK ' •4.•4.•_I •~10.0•DRAIN ROCK•�,�•a,a, at c 4
OF DRAIN .Y. . {X, .
FIELD +0110a04.. ..4.,1..i•11, 00A,
PROFILE •rir,_.r�.r,Y� 0 -:�X x*-�!Y.,!z.4T e<
SCALE:NTS *4,i.,i1i.1i,4,4"41 y4r��'P'1 I CM
7401 i o�Y{•-NZ", *y;v."VT ,' 4"foe+,• '. X Y; 7;,sc DRY:5/15/13
• -15.0
CM 1
---1 -18.5
DATE PERFORMED:
NOTES: �����.\` Dote
RECORD DRAWING PANNONE ENG SVC, LLC qF AL. ,k 12/17/2018
P.O. BOX 100217 ANCHORAGE, AK 99510 S
PHONE (907) 272-8218 FAX (907) 272-8211 %ri" .:' '•�-yr1 ScaIe
••• ... .. ••• .... / P.I.D. NO
DRAWN: ACP RAPTOR'S KNOLL, LOT 1 -101-58
RAPTOR PROPERTIES LLC StevenFR. Pennome PERMIT NO
RAPTOR'S KNOLL CIRCLE �n•. C- 8149 i// 0SP181036
II PLAN ANCHORAGE, AK 99516 1kt`"PF�!'R •.•.0Na�c ~ Sheet
`���\zi�� 2 OF 2
•
ncc co:t3
„;?;xSC.i t C,0S.k
;kl, Ill Lit/A ... wAvoi viftiFL .; s
. 0....,....‘;
,.;:.j ' .‘4•a:X:a1,01t+A:tt446.40-,V.WAYOMI9CMCIOMOXIM-Pr.XIMMI0.VA .14..SGb.AEMI2tXrwxliMrl y.
P.O.Bar.670269.Chhuglak,Jc J. u6? rlil V.-2? $
•
Ci'r•L'i: i:.);- L•',^>:: Spinel#Home.>
x
LEGAL DESC?i3r T iri.',? ;{apti.x(s Knri i.-t:t?. Soto ri-stt 1. .42
.,
DATE: 7-9-.o e
PE'':(ili P;LjM I:R: osP1a1t13'.'; DA 07`SSti+_: MS/29/1 Depth� ' F,"am To '
TA IDF 'TIFIC�,TiON NUM Eli. ('',"101 ZC=iO - ---
•
i5 well icicati_'d ct approved permit!Oi.4+tiCt!l: Yi �;o_ - i.. ..-.._. E-....___.._ Casing �t ___ _-_-..__.,..-.._ ___.-..-.-_
Method c Dftii:>? aSr rotary ! jtiilf f?tow: `_. ...___.__< ___� _ _ - -_
Depth, s Weil: :; i 4 ' 64 Silty Sand&GI-aye;
Casing Type: Ste,e! '__W?.,2rtirk.^.ess .2501 incP!es 64 i
`.. 81 ...., -iiia yard&Grave _ __.l _._
_
Diameter: 6 rin .
inches, der , : c.: fee>_
S ___ 81 104, Hardpan
Staii flat}f Lev'_,. _-..._._._..-------..._.____Y._Q" ---- '• 104 'tiner type 200' 4.5" PVC 110 :.lav i `rava!W411:
-
Racoven 'tte. i.5 :/ vpr i oh i { ..._ Silty Sand& 4ra,ei Damp, ____ — I _ _
_i'i';hQ =ii Te,i'; t {i: 3.49 1555
.i.lj,nrSilt S. &Cra's'Pl 1t,1 Ci::t.'!R et
Type:Y'.' Si if'i2n OpeningyType:1 �'�^r,:,$:i!) li !)I !hole. ' .;:.._.ASS 167 ___ _—_................
r---,
r e',<,�v t .. t? c- u a :i
I..—: Screened S'tx"!rtii'.£:t Stopped
167 Bearo •
<
Gen GrayF � P ,fTrati.7c SE.r1e S':4 Ci ..
260 i 292 Bedrock Gray w/Qua;tGroat Type: B2 i7tlt: Volume.: 3n i;
Depth:from
___.._ ...._........ f2 feet a 340Bedrock Gray 2.�iafti
r
Well Lisinfecteo upon Cor< :etian• ve!, i no _. _. .....Method of oof Disinfection•' Chlorine SC PPM
Ccr,IhsG i ts: •
h.
J.`-.!:-3. 5 2 GPM(left curs'-rit'•,slightly
ightl`I above bedrock ...
i.kflo'w this water to enter vp7.d1 .r a.c dol y to'."daatr r ' :_.._.._..._._._.._.__._._._. ...__.....----
•
cemir.g from bedrock below) ...._......._.._.,..._.
i
•
_-.._._...-.-_.-WATER QUALITY-TESTING" !
at
e ..
Col/100ml-
-----
i
Arsenic.. .... _ _.._ . ..... - •
1'., FC'ay'':3.i:i)b.:`; i.: _iYo •-'a'..:'s•;'. / .._:FS!?< '.^ s:'.•7;iS'. sv �i .
e�;_.i _ viLei 1:�;, :.:� .r:..
_ > % -c^,� -,�x,i•c.:its
pili .;r .. .,,:;107.irr Kli.till:V.': :1.i!t. 1 ,'tt!�." . ..friii:' av7 '3 ?F -,..Citi ^i ,. '��^rs?�.... -.R..�. .:_ .
--...................-
c3 0,.•
I...._...:_i,_..,_..i.r.:.i.3hi...,W
...A...,,,....R w...,...ELLs,..,
P.O. Box 67025.9.Chucii,. •:,Alf.99567 663-2759
1411.,VW.S tin Iva nwate rweits.co m
Pump Instalbtion Log
i
_ ,...„,
Well grilling Perrnit Number:SW OSP1g1035 Date of Issue 3/29118
Parcel ldentification 1,Zumber: 01710158000
li Legal Description 1 Property Owner Name& Address
I Raptors Knoli Lot 1 I 5pinell Homes •
1 ,
11; .
11 Pump Installation Date: 7-13-19
.11
1 1 Pump Intake Depth Below Top of Well Casing: 310
,1 Pump manufac-turer's Name: c&w feet :
;
ill
/ Pump Model: 4F07G10301
ei
4! Pump
12 Size: 1 hp •
ii
Pitless Adapter Burial Depth: 10 feet
{! 1
1! Pitiess Adapter Installer: Pomraning Excavation
I!
il Disinfected Upon Completion? Z. yes Fl no
fi
1j Method of Disinfe.ction: Chlorine 50 PPM li
gi
li
11 11 11
Comments: Pitless Manufacturer:Martinson
,f
11 1!
it
if
11
) Pump Installers Name: Sullivan Water Wells
11
il
?if
4ktw,m.oariaaso.rcewxovv...e.w.rxvnr,eeoyrar.*.+eovsaesedga.a:edwr,.nsstv.zsowee,...r.ao...m.Iwv:....Z..dr.ass-aon.Mascwve.C.S.PII.Aae.,TM•.w.w.wnInz4nerozrfca,%e.••15r.rv.an,arAeu.uanVnwaxdliowzsasr--v,vanr.xnaa,wmsztsnrssmnno•avm•oq
Attention:The pump installer shall provide a pump instzsliation log to the DSD within 30 days of pump installation.
PLAT NO. 2014-128
RAPTORS KNOLL SUBDIVISION
LOT 1
44,317 S.F.
S 89°58'11"E 320.06'
19....---,
s i •
143.3'
* ;�
Q' Naa
SEPTIC SYSTEM . p.
M
°
® 2130
-z I rn
C.)
b laIb t
m
GRpY4 OR' c kr .1114 I`' co
I
o c TO Iwrn
Y C3 ILL/I- 0
30' i C) i as 0 r
VI 0 I 16-:;.?, 0
ce 0 Io
O o ?.5 0 20.6 t o O
0
5 z I Z
I I
I !
10' UNDERGROUND WELL
CEA ROW ESMT.
I
i (2014-043192-0)
I f
1 „ =30'
I 10' T. & E. ESMT. 10' UTILITY ESMT.
(79-217) O
S 89°58'11"E 319.95'
0
M
E. 142ND AVENUE
AS - B U I L T I HEREBY CERTIFY THAT I HAVE SURVEYED THE
PROPERTY DEPICTED ABOVE AND THAT NO
GASTALDI LAND ENCROACHMENTS EXIST EXCEPT AS INDICATED. O®® �F14Rah
SURVEY ING. LLC IT iS THE RESPONSIBILITY OF THE OWNER TO e®�� °,...° AC
JEFF A. GASTALDI. R.L.S. DETERMINE THE EXISTENCE OF ANY EASEMENTS, 4�P ...
°° •°°•4_ .�5�®.
2000 E. DOWLING RD., SUITE 8 COVENANTS OR RESTRICTIONS WHICH DO NOT '�' Cr 49TH i\ °
ANCHORAGE, ALASKA 99507 APPEAR ON THE RECORDED SUBDIVISION PLAT. s
PHONE 248-5454 UNDER NO CIRCUMSTANCES SHOULD ANY DATA
GRID DATE HEREON BE USED FOR CONSTRUCTION OR FOR I. Jeffery A. Gastaldi : o A
ESTABLISHING BOUNDARY OR FENCE LINES. O.��^ o(3�I�Pe/elm�
SW3037 10/31/2018 s
ANCHORAGE RECORDING DISTRICT, ALASKA a® a •......°•
F.B. JOB NO. , p"Orass,onot l.°�44
NOTE : NO CORNERS SET THIS DATE „gill.
N IS II**
18-03 RAPTOR1
""T� MUNICIPALITY OF ANCHORAGE
aON�--�. Oa \7\l n •
� ' On-Site Water&Wastewater Program
lispilis,,+I ' r,a„�\ PO Box 196650 4700 Elmore Road
14e. t1Anchorage,Alaska 99519-6650 Phone:(907)343-7904 Fax:(907)343-7997 ,�"' httpa/www.muni.org/onsite 11 g�
iii
On-Site Water & Wastewater System Permit
Permit Number: OSP181036 Effective Date: 3/29/2018
Work Type: WellSeptic Renewal Expiration Date: 3/29/2019
Tax Code Number: 01710158000
Site Legal Address: RAPTORS KNOLL LT 1 G:3037
Site Mailing Address: 14175 RAPTORS KNOLL CIR, Anchorage
Owner: SPINELL HOMES INC Lot Size in Sq Ft: 44317
Design Engineer: PANNONE ENGINEERING SERVICES Total Bedrooms: fY 3
This permit is for the construction of:
0 Disposal Field Q Septic Tank 0 Holding Tank 0 Privy II Private Well 0 Water Storage
All construction shall be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80)
3. The wastewater code requires inspections during the installation. The engineer shall notify the Development
Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
shall be either:
a. Opened and Closed on the same day, or
b. Covered, sealed, and heated to prevent freezing
Special Provisions:
PRIOR TO INSPECTION REPORT APPROVAL: Property improvements (driveway, landscaping, etc) shall be
verified to not have any 25% or greater slopes within 50 feet down gradient of the drainfield, and that the finish
grades provide positive drainage away from the drainfield, i.e.; no ponding at or near the drainfield.
C O- 1 3//Mg Des( chanq� 1-0 3 G IWA,5.
Received By. ei ' /, ,/ai./L.-.,.�►.t i.Ii.//_/ .4 Date: -6/30/./g
/ I Date: 3�G/ r°
Issued By: ,) . / A.
r
MUNICIPALITY OF ANCHORAGE
Community Development Department ^" Phone: 907-343-7904
Development Services Division Fax: 907-343-7997
On-Site Water & Wastewater Program
ON-SITE SEWER/WELL PERMIT APPLICATION
Parcel I.D. 017-101-58
Property owner(s) Spinel) Homes INC Day phone
Mailing address 1900 Northern Lights Blvd Anchorage, AK 99517
Site address 14175 Raptors Knoll Circle
Legal description (Sub'd., Block & Lot) Raptors Knoll Lot 1
Legal description (Township, Range & Section)
Lot Size 44,317 Sq. Ft. Number of Bedrooms/ 3
APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING:
(®all that apply)
Absorption Field ❑x Initial ❑ Single Family (SF) ❑X
(w/wo ADU)
Septic Tank ❑X Upgrade ❑
Duplex (D) ❑
Holding Tank ❑ Renewal 0 Multiple Dwellings ❑
Privy ❑ (SF and/or D)
Private Well x❑
Water Storage ❑
THIS APPLICATION INCLUDES A VARIANCE /WAIVER REQUEST FOR:
Distance:
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit/Rush Fees: � Waiver Fees:
Date of Payment: - Date of Payment:
Receipt Number: 01' s Receipt Number:
Permit No. CJ'PITI 031, Waiver No.
Permit App_:-'• ::..,:c:
On-Site Water & Wastewater System Permit
,lrf nt ..S‘MUNICIPALITY OF ANCHORAGE
�., Development Services Department
t.
On-Site Water& Wastewater Program
4700 Elmore Road, PO Box 196650 l)(1)a r t m(m t
Anchorage, AK 99519-6650
Telephone: (907) 343-7904
Permit Number: OSP151367
Tax Code Number: 01710158000
Work Type: WellSeptic Initial
Permit Effective Dates: November 18, 2015 to November 17, 2016
Design Engineer: PANNONE ENGINEERING SERVICE
Subdivision: RAPTORS KNOLL
Site Legal Address: RAPTORS KNOLL LT 1 G:3037
Owner/Address: RAPTOR PROPERTIES LLC
5725 YUKON CHARLIE LOOP ANCHORAGE AK 995020000
Site Mailing Address: 14175 RAPTORS KNOLL CIR. Anchorage Lot Size in Sq Ft: 44317
Total Bedrooms: 4
This permit is for the construction of:
Y Disposal Field Y Septic Tank N Holding Tank N Privy Y Private Well N Water Storage
All construction must be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater
Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80).
3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services
Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours).
4. From October 15 to April 15. a subsurface soil absorption system under construction during freezing weather must either:
A. Open and Close on the same day.
B. Covered, sealed, and heated to prevent freezing.
Special Provisions: PRIOR TO INSPECTION REPORT APPROVAL: Property improvements
(driveway, landscaping, etc) shall be verified to not have any 25% or greater slopes within 50 feet
down gradient of the drainfield, and that the finish grades provide positive drainage away from the
drainfield, i.e.; no ponding at or near the drainfield.
Arl4-
t
ip
Received By: / Date: 1 1 f - 0 S
Issued By: / Date: 1( d S
MUNICIPALITY OF ANCHORAGE
:kms
Community Development Department 46 of Phone: 907-- o ,•!4
Development Services Division Fax: to = - •®7.-,
On-Site Water &Wastewater Program ti RUSH!
ON-SITE SEWER/WELL PERMIT APPLICATION E Nov 0 6 Zu15
12- 3
017-101-58 '1 O
Parcel I.D. << ��
Property owner(s) Raptor Properties LLC Day phone a6 8 °�
Mailing address 5725 Yukon Charlie Loop, Anchorage, AK 99502
Site address Raptors Knoll Circle
Legal description (Sub'd., Block & Lot) Raptors Knoll, Lot 1
Legal description (Township, Range & Section)
Lot Size 44,3174 Sq. Ft. Number of Bedrooms 4
APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING:
(®all that apply)
Absorption Field ❑X Initial ❑X Single Family (SF) ❑x
(w/wo ADU)
Septic Tank ❑X Upgrade ❑ Duplex (D) ❑
Holding Tank ❑ Renewal ❑ Multiple Dwellings ❑
Privy ❑ (SF and/or d)
Private Well
Water Storage ❑
THIS APPLICATION INCLUDES A VARIANCE /WAIVER REQUEST FOR:
Distance:
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
(Signature of property owner or authorized agent)
Ia5t1.4°
_
Permit/Rush Fees:JM/t a Si Waiver Fees:
Date of Payment: /l /1///S Date of Payment:
Receipt Number: tOV Receipt Number:
Permit No. OSPI S 13V.- Waiver No.
Permit App_j-:• ::...c
co
Pannone Engineering Services ac
Steven R. Pannone, Principal
Registered Professional Engineer
E-mail:steveCa)panengak.com
July 31, 2018
Subject: Raptor's Knoll, Lot 1
Septic System Install Permit Request
Design Narrative
This is a design narrative for a permit to install a septic system to be issued for this property. The proposed
systems will serve a proposed three bedroom (3) bedroom house. Currently the lot is undeveloped. The
well on this lot has been drilled per the original permit, but moved downhill to accommodate the recently
permitted drain field on the adjoining lot. This lot and the surrounding lots are served by private wells.
Required separation distances to wells will be maintained.
1. Soils. One test hole was performed on this lot by Michael E. Anderson in February of 2013, and
groundwater was monitored for at least seven days. Ground water was not observed to a depth of
18.5' below the surface in the test hole monitor tube after the 7 day monitoring period. Bedrock was
not encountered in the test hole. Based on the results of the percolation tests and overall soils
appearance; an application rate of 0.6 gallons/day/square feet was used for a conventional
wastewater system in the area of the test hole. Due to the drain field that was permitted in the well
radius of the permitted well on this lot, the proposed well was relocated and drilled west of the
original proposed location, making it necessary to move the drain-field partially out of the test hole
radius. Existing soils reports from the surrounding lots are attached to demonstrate the continuity of
soils in the area, per 15.65.210.0 `Exception'.
2. Soil Absorption System Design.
a. See Sheet 1 of the design package.
3. Surface Water:There is no surface water within 100 feet of the proposed septic tank and drain field.
The proposed drain field upgrade will maintain at least 100 feet from all surface water and drainage
ditches.
4. Topography: The existing topography generally slopes from the east to the west in the area
surrounding the septic system at approximately 20%, flattening out to about 10% below the system. There
are no steep slopes within 50' of the proposed drain field. The proposed drain field will maintain 50'
separation all steep slopes.
5. Drawing Markings:The Drawings are marked "For MoA Review Only". When written notification that
the review is complete and that there are no further comments is received from MoA On-Site Department,
the note will be removed and "Issued for Construction" drawings will be issued.
The proposed installation will not affect the future development of this or the surrounding lots
Mailing: P.O. Box 100217, Anchorage, AK 99510-0217
Physical: 332 East Manor, Anchorage, AK 99501
Telephone: (907) 272-8218 FAX: (907) 272-8211
* SITE NOTES: CO I
1. DRIVEWAY LOCATION SHOWN IS FROM DEVELOPER'S PLOT PLAN. PES DID NOT DESIGN DRIVEWAY AND IS NOT
RESPONSIBLE FOR IT'S LOCATION. THE DRIVEWAY WILL BE CONSTRUCTED ABOVE ORIGINAL GRADE AND WILL NOT
CREATE ANY CUT SLOPES ON THE LOT, ABOVE OR BELOW THE SEPTIC SYSTEM.
2. RETENTION BASIN IS REQUIRED BY PLAT. THE BASIN WILL BE NO MORE THAN 2 FEET DEEP. THIS LOT IS TYPIFIED BY
DRY WOODLAND VEGETATION, WITH WELL PERCOLATING SOIL. IT IS NOT LIKELY THAT THIS RETENTION BASIN WILL EVER
CONTAIN WATER.
3. ANY SLOPE WITHIN 50' OF THE DRAINFIELD WILL BE AT 4:1 OR FLATTER.
o Z WELL (E)
•IP
i
w
a I
o \.
\41-----....W-R���j _
\.,....,.. I p
-
J DRAIN FIELD (P,A1 ��
° o10• LF x 2.5'W x 10.0'ED x 12.5 TD
v ac WITH CO AND MT AT EACH END r I
0 *ENSURE DRIVEWAY IS GRADED / SEPTIC AREA (E)
o D'0 PREVENT RUNOFF FROM BEING RESERVE DRAIN FIELD (P)
Y TRAPPED OVER DRAIN FIELD. 1OLF x 2.5'W x 10.0'ED x 12.5'TD
o
cn ix BASED ON CAT III
C w
z 10
a b �SE/Nwf ` M-M_M\ z
iit.
41
1
• 1 aftimm,„„,„„...
r 10008 SEPTIC TANK (P) n.
WITH DOUBLE CLEAN OUT w
a
. it N 11 OVAND FOUNDATION CLEAN OUT w c.)
3 BR d
APPROXIMATE LOCATION OFI-IJJ
RETENTION BASIN. SEE NOTE 2. HOUSE(P) LOT 1 3o• v
ct
>o
I NEW WELL _,
. 1 _ Zi • -JW
/MSM--170 o
•
/� - - c
/1 10' UTILITY EASEMENT
\ 142ND AVENUE
N \
12 /
w I
WELL (E)
NOTES: �.......Nu, Dote
CHANGE ORDER PANNONE ENG SVC, LLC �— OF AL l Dote 018
P.O. BOX 100217 ANCHORAGE, A99510 '��••''••.1044
PHONE (907) 272-8218 FAX (907) 272-8211 //*0).• * ��� •�y+�i Scale 50
\ \ * /, P.I.D. NO
RAPTOR'S KNOLL, LOT 1 ar. `!., 017-101-58
RAPTOR PROPERTIES LLC Steven '1annorae P PERMIT NO.
0 fes•. CE 8149 ,• Al
, OSPxxxxxx
RAPTOR'S KNOLL CIRCLE �t mss'•• •\
PLAN ANCHORAGE, AK 99516 4�l���oFESS1gNP`� Sheet
2
'k\X -��
SPECIAL PROVISIONS TO SPECIFICATIONS GOA(
1. ALL CONSTRUCTION SHALL BE INSTALLED AS SPECIFIED IN THE MOST CURRENT EDITION OF THE MUNICIPALITY OF
ANCHORAGE STANDARD SPECIFICATIONS (MASS) FOR COMPONENT PARTS AND MATERIALS USED IN CONSTRUCTION OF
ON—SITE WASTEWATER DISPOSAL SYSTEMS AND AND IN ACCORDANCE WITH AMC 15.65.
2. SCOPE OF WORK: INSTALL NEW 1000g SEPTIC TANK, AND SOIL ABSORPTION SYSTEM.
3. GROUNDWATER WAS NOT ENCOUNTERED TO A DEPTH OF 18.5 FEET BELOW EXISTING GRADE AS EVIDENCED BY THE SOIL
TEST HOLE. IF AN APPARENT WATER TABLE IS OBSERVED IN ANY OF THE EXCAVATIONS LESS THAN 18.5 FEET BELOW
EXISTING GRADE NOTIFY THE ENGINEER IMMEDIATLY.
APPROXIMATE FINISHED GRADE
BY OTHERS
PROVIDE FILL TO CREATE A
MINIMUM OF 3.0'OF COVER
OR INSTALL RIGID INSULATION
FILTER FABRIC
4"0 DRAIN PIPE
DRIVEWAY DRAIN ROCK 6"ABOVE PIPE INV HOUSE
BY OTHERS BY OTHERS
TH-2
(ANDERSON 2013)
2.5 OG -1.0
OL -2.0
DRAIN ROCK 7; 10'0 cv
LEGEND
W- WATER LINE/
WELL RADIUS
6.0 -15.0 SS NEW SEPTIC
GM
-18.5
ABBREVIATIONS
CU COPPER
DIP DUCTILE IRON PIPE
TH TEST HOLE
DESIGN PARAMETERS DESIGN PARAMETERS FC FOUNDATION CLEAN OUT
T# TANK CLEAN OUT NO.
PRIMARY SEPTIC SYSTEM RESERVE SEPTIC SYSTEM
NO. BEDROOM: 3 (450 gpd) NO. BEDROOM: 3 (450 gpd) C# CLEAN OUT NO.
TANK SIZE: 1000 TANK SIZE: 1500 ADVANTEX M# MONITOR TUBE NO.
PERC RATE: 17 MPI W/ AX20 POD R.I. RIGID INSULATION
SOIL RATING: 0.6 GPD/SF PERC RATE: 17 MPI DCO DOUBLE CLEAN OUT
AREA RQD: 750 SF SOIL RATING: 4 GPD/SF DV DIVERTER VALVE
SYS. TYPE: DEEP TRENCH 10.0'ED AREA RQD: 112.5 SF FS FLOW SPLITTER
MIN LENGTH: 37.5 LF SYS. TYPE: DEEP TRENCH 10.0'ED BFG BELOW FINISH GRADE
MIN LENGTH: 5.6 LF OG ORIGINAL GRADE
USE: FG FINISH GRADE
40 LFx2.5'Wx10.0' E.D., 12.5' TD USE: FF FINISH FLOOR
TOTAL AREA: 1,000 SF 10 LFx2.5'Wx 10.0' E.D., 12.5' TD TS&V TOPSOIL AND VEGETATE
TOTAL AREA: 200 SF NIC NOT IN CONTRACT
NOTES: ��� \\ Dote
PANNONE ENG SVC, LLC - OF A���l
CHANGE ORDER P.O. BOX 100217 ANCHORAGE, 6/27/2018
99510 ?�� qs ll
PHONE (907) 272-8218 FAX (907) A.272-8211 4, ••... Scale
j*' 4 .twv. �..I�j P.I. TS
4titRAPTOR'S KNOLL, LOT 1 017-101-58
RAPTOR PROPERTIES LLC r Steven R. Pannone / PERMIT NO.
RAPTOR'S KNOLL CIRCLE Mas . CE 8149 \�/ osPxxxxxx
DESIGN DETAILS ANCHORAGE, AK 99516 <<iirr. ••o�sso•• Sheet2 2
•\\x,
COPY or; ;,-,„,,I s(,tbd . -P le
,,,,,,,,,,
Municipality of Anchorage �RsoF � Sd0�
Development Services Department NO Cse ,: '•;1
• Building Safety Division o* : 49TH Ofp
. /1 c.-Ak...e On-Site Water and Wastewater Program 0 6
4700 Elmore Road 0/r`` _, r P.O. _
V
•M CHAEL E. ANDERSON, ' : a'
��► . .Box 196650 Anchorage,AK 99507
www.ci.anchoraoe.ak.ug �,•. S
(907)343 7904 �A iii,!. G -4 8i ••• N���
Soils Log - Percolation Test ,6I�d� veO '
Performed For: Ray Hickel Date Performed: Feb 8,2013
Legal Description: Timber Trail Subdivision, Lot 1 Township,Range,Section:
Slope Site Plan
4,11/
Depth
1:1
(Feet) 0 &
1- 10�- l ryt1�
2-r
o � It
4-
6.0
,.._.:44
K IVO
6- �� � ;rL
7-
8-
WAS GROUND WATER
9- ENCOUNTERED?
S
10- • IF YES,AT WHAT DEPTH? L
-
Depth to Water After
0
11- Monitoring? Cw„4„r P E
12- Date: -I>-i S
13-
14- Reading Date Gross Time Net Time Depth to Water Net Drop
15-c_ _ s 1 2/14/2013 I' 1 /..'/..' J,Ej "
7
16- 17 .a 2 10121 ;C, MI6 I,2c ' 1 ,(y °1
18- 4 (o;L d .30 Vat 1 , (1," 11 �� h
19:- —ft?,S" 5 I C' 91 '' - 0 `%7. ....-,,-
20- 6 If ;Z s 3 o I,,I rf s K.,&) (, ,,1"
PERCOLATION RATE (7 (minutes/inch) PERC HOLE DIAMETER -I'd
TEST RUN BETWEEN 4--„c FT AND f..:(::, FT
COMMENTS Pero Cavity was presoaked
PERFORMED BY: A. Harala 1114E/�V, ,I) Ca .,.<Q...-.-e RTIFY THAT THIS TEST WAS
PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: iii (7-/)e
.V
141.3
•
of
• �^ Municipality of Anchorage
/ On-Site Water and Wastewater Program
—/ (907)343-7904
SA ETV
Certificate of On-Site Systems Approval
Parcel I.D. 017-101-58 Expiration Date: it\ 1`I .a 0
1. GENERAL INFORMATION
Complete legal description RAPTOR KNOLL L1
Location (site address) 14175 RAPTORS KNOLL CIR.
Current Property owner(s) SPINELL HOMES INC. Day phone
Mailing address 1900 W. NORTHERN LIGHTS BLVD
Real Estate Agent Day phone
2. TYPE OF DWELLING:
Single Family(w/wo ADU)
❑ Duplex
El Multiple Dwellings(Single Family and/or Duplex)
3. NUMBER OF BEDROOMS: 3
4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL:
Individual Well Q Individual
Individual Water Storage ❑ Holding Tank ❑
Community Class Well ❑ Community ❑
Public Water System ❑ Public Sewer ❑
WaiverNariance request for: Distance:
Received by: Date: /7--//9,
COSA to be released engineer,unless otherwise requested by the engineer.
COSA Fee $ 6.(1.0 Waiver Fee $
Date of Payment 14/0 Date of Payment
Receipt Number l)r-1(40:J .7 Receipt Number
COSA# 0Ca/403y Waiver#
5. STATEMENT OF INSPECTION BY ENGINEER
As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation,based on procedures outlined
in the Certificate of On-Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater
disposal system is(are)safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that
based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply
and/or wastewater disposal system is(are)in compliance with all applicable Municipal and State codes,ordinances,and regulations in effect at
the time of installation.
In conducting an adequacy test,I attempt to provide a thorough,conscientious engineering analysis of the system in accordance with MoA COSA
guidelines and regulations.The reported results describe the performance of the system under the conditions encountered at the time of the test,
and separation distances measured to readily identifiable features. The operational life of all wells and septic systems depend on the local soil
condition,ground water levels that may fluctuate during the year,and the water usage of the family being served by the system.These conditions
are outside the control of the evaluator of this system. All systems eventually fail and satisfactory test results do not guarantee future
performance of the system,nor do they guarantee that there are no hidden defects or encroachments.Therefore we cannot provide any warranty
for future performance, nor can we estimate remaining life of the system.The content of this report is for the sole benefit of the owner listed
above.
Name of Firm Pannone Engineering Services LLC Phone (907) 745-8200
Address P.O. Box 1807 Palmer, AK 99645
Engineer's Printed Name Steven R Pannone .4a , Date `e/24
*' ,'• ,\ y*ft
6. DSD SIGNATURE "' �i ""'
.1 ter
System#1 Approved for 3 bedrooms �j SIeveri 1t. Pannone• le
`ti#� . CE-8149
System #2 Approved for bedrooms
titkDisapproved er�OFESSI� '+
Conditional approval for bedrooms, with the following stipulations:
ON-SITE �,
WATER AND `
PrI WASTEWATER oz
r PROGRAM '
Z ' QGP\l\cs-
By: e.0.0 CQL ) et. Ti>M Ecklurt3 Original Certificate Date: De C 1 9, .20(1S
The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On-Site Systems Approval (COSA)based only
upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality
of Anchorage is not responsible for errors or omissions in the professional engineer's work.
7. ATTACHMENTS:
COSA Checklist X Nitrate Advisory
Septic System Advisory Arsenic Advisory
Well Flow Advisory Other
COSA blue sheet_f .
If more than 1 septic system is on the lot:
COSA Checklist# 1 of 1
Structure served by this system 1
Certificate of On-Site Systems Approval Checklist
Legal Description: Raptors Knoll L1 Parcel ID:017-101-58
A. WELL DATA
Well type Private If A, B, or C provide PWSID# Well Log (Y/N) Y
Date completed 7/9/18 Sanitary seal (Y/N) Y Wires properly protected(Y/N) Y
"+
Total depth 340 ft. Cased to 55 ft. Casing height(above ground) in.
FROM WELL LOG AT INSPECTION
Date of test 7/9/18
Static water level 148 ft. ft.
Well production 4.5 g.p.m. g.p.m.
WATER SAMPLE RESULTS: 4.23
Coliform NEG colonies/100 mL Nitrate v mg/L
Arsenic N/" ug/L Date of sample: 12/10/18 Collected by: PES
NP
B. SEPTIC/HOLDING TANK DATA
Tank Type/Material Septic/Plastic Date installed 10/18/18
Tank size 1000 gal. Number of Compartments 2 Cleanouts(Y/N) Y
Foundation cleanout(Y/N) Y Depression over tank(Y/N) N High water alarm (Y/N) N/A
Date of pumping New Pumper
C. ABSORPTION FIELD DATA
Date installed 10/19/18 Soil rating (g.p.d./ft2 or ft2/bdrm) 0.6 System type Deep trench
Length 40 ft. Width 2.5 ft. Gravel below pipe 10 ft.
Total depth 12.5 ft. Eff. absorption area 800 ft2 Monitoring tube Y Depression over field N
Date of adequacy test New Results(Pass/Fail) For bedrooms
Fluid depth in absorption field before test in. Water added gal. New depth in.
Elapsed Time: min. Final fluid depth in. Absorption rate >= g.p.d.
Any rejuvenation treatment(past 12 mo.)(Y/N&type) If yes, give date
D. LIFT STATION
Date installed Size in gallons Manhole/Access(Y/N)
"Pump on" level at in. "Pump off level at in. High water alarm level at in.
Datum Cycles tested Meets alarm&circuit requirements?
E. SEPARATION DISTANCES
WELL ON LOT TO:
Septic tank/lift station on lot 100+ On adjacent lots 1001+
Absorption field on lot 1 00+ On adjacent lots 1001+
Public sewer main 75'+ Public sewer manhole/cleanout 1001+
Sewer/septic service line 25'+ Holding tank 1001+
Animal containment areas 501+ Manure/animal excrete storage areas 100 +
SEPTIC/HOLDING TANK ON LOT TO:
Building foundation 101+ Property line 101+ Absorption field 101+
Water main 25 + Water service line 25'+ Surface water +
Wells on adjacent lots 1001+
ABSORPTION FIELD ON LOT TO:
Property line 101+ Building foundation 1��+ Water main 101+
Water Service line 25'+ Surface water 1001+ Driveway,parking/vehicle storage 1 0'+
Curtain drain 501+ Wells on adjacent lots 100 +
F. COMMENTS
G. ENGINEER'S CERTIFICATION SOF Acr4,k
;zee • 91-14
I certify that 1 have determined through field inspections and ,,i .
review of Municipal records that the above systems are in O*•49 N 1\ *t�$
conformance with MOA COSA guidelines in effect on this date. 0••• •• 0
Engineer's Printed Name Steven Pannone i••:Seven 12. Parinone• `
•
rh 1, CE-8149 • /
Date `4'lZ/,2 4} 4 ' v• ''
ik1 ;oFEsso 4 l
COSA canary sheet_2-6-15.doc