HomeMy WebLinkAboutSOUTH HILLS BLK 1 LT 5ASouth Hills Block 1 Lot 5A #017-063-55 Municipality of Anchorage Community Development Department Page 1 of 3 On -Site Water & Wastewater Program 4700 Elmore St. • P.O. Box 196650 Anchorage, AK 99519-6650 • http:llwww.muni.org/onsite • (907)343-7904 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP161223 PID Number: 017-063-55 ❑ New 0 Upgrade Name: LORI & RICHARD SCHANCHE ABSORPTION FIELD ❑ Deep Trench ❑ Shallow Trench ■ Bed ❑ Mound Address: 7201 OLD HILLSIDE WAY *ANCHORAGE, AK ❑ Other Phone: No. of Bedrooms: Soil Rating: Total Depth frvm original gentle: 830-6147 3 0.7 GPD/Sq, Ft. Ft. LEGAL DESCRIPTION Dept to pipe Invert from capital Same: Gravel depth beneath pipe: SEE DWG. R. 0.5 Ft Subdivision: Block: Lot: Fill added above orgtalgmae: Gravel length: SOUTH HILLS 1 5A SEE DWG. 43 R. Ft. Owns Ip: - aege: -Section: - Grevelwdth 3ads Number of lines: Distance between lines: 15 FL 3 5 Ft. SEPARATION DISTANCES Total absoryuon area: 645 umberof trencn�: Dist baNrean trenches: To Septc Absorption Lift Holding Publir/Private From Tank Field Station Tank sewer Lines SpFt. . Well 100'+ 100'+ _ 25'+ TANK N Septic ❑ S.T.E.P. ❑Holding ❑ Other Manufacturer. capacity: Surface Water 100'+ 100'+ - ANCHORAGE TANK 1000 Gal. Lot Line 5'+ 10'+ - - N/A Malarial: Numberaruomparlmeats: STEEL 2 Foundation 5'+ 10'+ _ _ LIFT STATION Curtain Drain NONE KNOWN Manaractarer. c r: Gal. Remarks: OLD TANK WAS DECOMMISSIONED PER UPC 'Pump orf level at: J-Pu!.!P!.� ravel ac Ngh water alarm at *LIMITED TO THE REMOVAL OF CONTAMINATED MATERIAL, ADDED Pump Make &Martel Electrical Inspections perfohned by. MOA APPROVED SAND FILTER SO BOTTOM (TOP OF SAND) OF NEW BED IS 0.1 FEET HIGHER THAN THE TOP OF SAND IN ORIGINAL BED. PIPE MATERIAL DRAINFIELD IS 35'+ FROM SLOPES>25% (WR#OSV161091) House to tank D3034 Tank to D3034 drainTeld Installer WILCO EXCAVACTION, LLC Drainfield D3034 CO/MT D3034 Inspector GEG, Ltd. BENCH MARK (Assumed elevation) 100.00 Ft. Inspection Dates: 1St 8/11/2016 2nd 8/12/2016 Locatlon and Description: 3rd 8/12/2016 4th 8/15/2016 BOTTOM OF BACKDOOR THRESHOLD ENGINEER'S L Community Development Department Approval \\\\\ ���4, �F Conditional approval: Date: �y • ■. ..... .. .......... 0 .. . ...... .. ............ ........ 0 �I• �';* Game s 6j= ; 21 • �� CE_777 Approved: ww Date: •4+ /'hOFESSt�P:•� 11,\1\\\\\• E BE #L11 AECC884 Ina,umion Report_L1-12.Eoc PERMIT NUMBER: OSP161223 A I B DB1 12.6 23.6 DB2 12.6 24.4 ST1 60.2I 70.2 ST2 66.8 77.8 083I Os.2 SOA DB4 70.4 81.3 C01 93.7 1107.51 CO2 95.2 1109.0 CO3 101.0 113.0 C04 102.4113.3 COS 123.8 143.4 COO 127.7 146.3 C07 130.3 147.8 MT1 93.3 107.6 MT2 104.2 115.6 MT3 123.4 143.1 MT4 1132.1 148.4 RECORD DRAWING PARCEL ID NUMBER: 017-063-55 SOUTH HILLS: BLOCKI,LOT3 i n O�Q DBL3! NEW 1000 GALLON SEPTIC TANK / B / EXISTING3 / BEDROOM HOUSE \LOT6 I 100' WEI I RANI SHED PER CONVERSATIONS WITH THE HOMEOWNER(LORI SCHANSCHE) ON 8/3/2016 THERE IS NO WATER OR SEWER \ SERVICE TO THE GARAGE GARNESS ENGINEERING GROUP, Ltd PREPARED FOR: LORI & RICHARD SCHANCHE PROJECT/LEGAL DESCRIPTION: SOUTH HILLS; BLOCK 1, LOT 5A TYPE OF WORK: RECORD DRAWING PHONE NUMBER: PAGE NUMBER: 830-6147 2 OF 3 DRAWN BY: L.K.B. DATE: 8/23/2016 9 H ... .. .0 ff A. SS S i CE -795 f�OFESS� Pi♦♦ Alpine Drilling & Enterprises Well Log Permit Number: #SW Date of Issue: Parcel Identification Number: Date Started: 7-19-16 Date Completed: 7-19-16 Is well located at approved permit location? x Yes ❑ No Legal Description: South Hills Block m1 Lot 5A Richard Schanche & Lori Eddie Property Owner Name & Address: 7201 Old Hillside Way Anchorage, Alaska 99516 Borehole Data: Depth (ft) Method of Drilling x air rota Type,Soil Thickness & Water Strata From To r5 El cable tool existing well bedrock Casing type: steel 0 112 11 Wall Thickness:, 025 inches 112 166 Diameter: 6 inches Depth: ? feet Liner Type:_ Diameter: _ inches Depth: _ feet WATER QUALITY TESTING ��S _—Af5-c')-- C011100rrtL Ar8e111C _� Z. 7 above feet Static water level (from ground level): 61 feet Pumping level: 160 feet after 2 hours pumping 7 gpm Recovery Rate: 7 gpm Method of Testing: air li Well Intake Opening Type: ❑ Open End x Open Hole ❑ Screened Start _ feet Stopped _ feet ❑Perforations Start _feet Stopped _feet Grout Volume: Pump: Intake Depth_ feet Pump size _ hp Brand Name Well Disinfected Upon Completion? x Yes ❑ No Method of Disinfection: chlorine tablets Comments: Welt Driller: Alpine Driling & Enterprises PO Box 110496 Anchorage AK 99511 50' 50' N w O {p 2 LJV JZ D z C] no � I f— 6'££ 9'lZ Z as J d Q LO N `n 4 M�l Op n O � ,r) J M -- O' 3.=(� f I.! I� CJ oo N W W a x OD J O Z m �7x d Z 0 W E� E� Q $ Z � �Dto W � J a Z y W g I a N az QQ m U o • i C z W z � �j FI v a w w 0 U v� ow C) a o a > Z wJ w m C) ^ m'^ pi A a U uw m 3 n� Ana W a C I I I I O N LO U U EN Z N O O a o 3 w � I 50' 50' 101 O O N A v N N U t r TUB Oy.Oi'C � T F N i W y 7 0 V 00a�� V Oc� 00>.a E, 00 .r4, p E a 2 r w p 0'00 P m p +, C 4.T P Gy"'��l+ 0. "0.— >W q m N C ..�. 0 Tp LC Grt Ny 00N ,00�0 .a 0 °[•...> OO'O0 fA »a C a O d p O'p L 04 .a M ..s M �., 0 0 W V r4 O 0 'o O� TE0 N WQ.0Co,=000 VA''� Wd VwU rr! CmC ado Ly or, Gv c0. 0 0 Q.0 V C _...0 .0 N. 5 O V V R`O qr�!a, w R?J) £6 b0£ 3„lZ,9Z.tbS — — — �w o� N O I ' O {p 2 LJV JZ D W C] no � I f— 6'££ 9'lZ Z as d Q LO N `n 4 M�l Op n O � ,r) J M -- O' 3.=(� f I.! I� CJ oo N W o a x OD O x �7x 101 O O N A v N N U t r TUB Oy.Oi'C � T F N i W y 7 0 V 00a�� V Oc� 00>.a E, 00 .r4, p E a 2 r w p 0'00 P m p +, C 4.T P Gy"'��l+ 0. "0.— >W q m N C ..�. 0 Tp LC Grt Ny 00N ,00�0 .a 0 °[•...> OO'O0 fA »a C a O d p O'p L 04 .a M ..s M �., 0 0 W V r4 O 0 'o O� TE0 N WQ.0Co,=000 VA''� Wd VwU rr! CmC ado Ly or, Gv c0. 0 0 Q.0 V C _...0 .0 N. 5 O V V R`O qr�!a, w R?J) £6 b0£ 3„lZ,9Z.tbS — — — �w o� I I I } I J Z W O N I WWWQ I I I .tbM3N210 l3nbap I N O I ' © XQ I {p 2 JZ I � W W U � I f— 6'££ 9'lZ Z 1 n O Vl NSS p W a x OD x �7x E� E� z $ o � �Dto y I N O • i C � �j FI v c 0 �] pi A V d � C � O O N LO U EN N O O a o 3 I I I } I J Z W O N I WWWQ I I I .tbM3N210 l3nbap I 30' S - } C] C p] 0 C 0 L C C I V) Z � O � w C C � S L W V7 L L� L OC Z I O F O C J _ O L (n L W L CC C 30' 1 1 � � I� N O I ' © XQ I {p 2 JZ I � W I o� � r I f— 6'££ 9'lZ f w xN) Qaznc -q o I na I ac 30' S - } C] C p] 0 C 0 L C C I V) Z � O � w C C � S L W V7 L L� L OC Z I O F O C J _ O L (n L W L CC C 30' 1 1 � � I� On -Site Wastewater Disposal System Permit MUNICIPALITY OF ANCHORAGE Development Services Department On -Site Water & Wastewater Program 4700 Elmore Road, PO Box 196650 Anchorage, AK 99519-6650 Telephone: (907) 343-7904 Permit Number: OSP161223 Tax Code Number: 01706355000 Work Type: Septic Upgrade Permit Effective Dates: August 06, 2016 to August 06, 2017 Design Engineer: GARNESS ENGINEERING GROUP LTD Subdivision: SOUTH HILLS e p<u till( -III Site Legal Address: SOUTH HILLS BILK 1 LT 5A G:2939 Owner/Address: SCHANCHE RICHARD T & LORI EDDIE 7201 OLD HILLSIDE WAYANCHORAGE AK 995163742 Site Mailing Address: 7201 OLD HILLSIDE WAY, Anchorage Lot Size in Sq Ft: 93823 Total Bedrooms: 3 This permit is for the construction of: Y Disposal Field Y Septic Tank N Holding Tank N Privy N Private Well N Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80). 3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either: A. Open and Close on the same day. B. Covered, sealed, and heated to prevent freezing. Received By: % '�u h_- ``" Issued By: J ✓'J'a Date: ri r Date: �6 nCl( Municipality of Anchorage Development Services Division On -Site Water and Wastewater Program **** VARIANCE/WAIVER REVIEW **** Waiver#: OSV161091 COSA#: _ Permit#: OSP161223 PID#: 017-063-55 Legal Description: South Hills B1 L5A Engineer: Garness Engineering Group Applicant: Lori Schanche Your request for a waiver of the required 50 feet horizontal separation from the absorption field to the excessive slope has been approved. The approved separation distance is 35.0 feet. This waiver approval applies to the proposed absorption field only. Any future upgrade to the on-site wastewater disposal system will require all separation distances be met or another approval from this department. ❑ The affected adjacent property owner(s) have been given a 7 day notice regarding this waiver. ❑ Notarized letter(s) of nonobjection have been received from the owner(s) of the affected adjacent property. ® Adjacent properties are not affected by this waiver. ..............................................................................( Waiver is Granted: X Waiver is not Granted: Date: Approved by: l Name of Re ' wer ....................................................... ..................... **** VARIANCE/WAIVER REVIEW **** 1 MUNICIPALITY OF ANCHORAGP.i[ *"S►l Community Development Department Phone: 907-q43--7,904 Development Services Fax: 9�i3y.X On -Site Water & Wastewater Program Mayor Dan Sullivan On -Site SewerfWell Permit Application �a ,qUG ' G16 017-063-5� For ASingle Family Dwelling 1 I(��j5 Parcel I.D. 01 6 �6 Property owner(s) LORI SCHANCHE Day phone 8�bf4$ t Mailing address 7201 OLD HILLSIDE WAY *ANCHORAGE, AK 99516 Site address 7201 OLD HILLSIDE WAY *ANCHORAGE, AK 99516 Legal description (Sub'd, Block & Lot ) SOUTH HILLS; BLOCK 1, LOT ZW 5i} Legal description (Township, Section & Range) Lot Size Sq.Ft. Number of Bedrooms 3 APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DEWELLING: ( mal l that apply) Initial ❑ Single Family (SF) Absorption Field Upgrade ® (w/wo ADU) Septic Tank ® Renewal Duplex (D) E]❑ Holding Tank ❑ Multiple Dwellings ❑ Privy ❑ (SF and/or D) Private Well ❑ Water Storage ❑ THIS APPLICATION INCLUDES A VARIANCE/ WAIVER REQUEST FOR: DRAINFIELD TO SLOPE >25% Distance: 35' I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal codes. GARNESS ENGINEERING GROUP, Ltd. (Signature of property owner or authorized agent) Permit/Rush Fees: Date of Payment: Receipt Number: L�97a f Permit No. Date of Payment: y,�/l6 Receipt Number: 203631 Waiver No. (Rev. 01/11) GARNESS ENGINEERING GROUP, Ltd CIVIL & ENVIRONMENTAL ENGINEERS August 4, 2016 Municipality of Anchorage Development Service Department On -Site Water & Wastewater Program 4700 Elmore Road Anchorage, AK 99507 Ref: Proposed Septic System Upgrade for South Hills; Block 1, Lot 5A To whom it may concern: The existing 3 bedroom house is served by a private well and septic system. The drainfield is in a state of failure and needs to be upgrade. We are proposing to install a new 1000 gallon septic tank and bed type drainfield. We are proposing to excavate out all contaminated material and rebuild the existing bed at an elevation of 0.1 feet higher than the bottom of the existing system. The drainfield is designed around Theodore F. Moore, P.E. 1990 testholes #8, #11, and #12. Comments regarding the design are summarized as follows: 1. SOILS: See the attached 1990 soil logs by Theodore F. Moore, P.E. which show the soil classifications, groundwater monitoring, and the percolation test results. 2. DRAINFIELD DESIGN: See attached design drawing for drainfield specifications. 3. SURFACE WATERS: There are no surface water concerns. 4. TOPOGRAPHY: See the attached design drawing. 5. WAIVER: We are requesting that your department issue a waiver from the required separation distance of 50 feet for drainfield to slopes greater than 25% down to 35 feet. Justification for granting this waiver are as follows: • The existing drainfield is approximately 35 feet from slopes greater than 25%. No daylighting was observed on 8/3/2016. • As can be seen on the attached profile drawing, a 25% slope line drawn 2 feet above the top of rock does not daylight until 37 feet. • The area between the drainfield and the slopes is highly vegetated. We are unaware of any adverse impacts this installation would have on adjacent wells or septic systems. If you have any qU tions, please contact us at 337-6179. Thank you for your assistance. P. E.. M.S. 3701 East Tudor Road, Suite 101 `Anchorage, Alaska 99507-1259 Phone: (907) 337-6179 ` Fax: (907) 338-3246' Website: www.garnessengineering.com I / I APPROXIMATE / LOCATION OF STREAM PER MOA GIS MAPPING / 0 II SOUTH HILLS; BLOCK 1, LOT 7 I 100'WELL RADIUS " I SOUTH HILLS; \ BLOCK 1, LOT6 i / � I , I I I I \\\�I I I SOUTH HILLS; BLOCK 2, LOT CSEPTIC ARE \ / SOUTH HILLS; j BLOCKI,LOT3 GARNESS ENGINEERING GROUP, Ltd CIVIL & ENVIRONMENTAL ENGINEERS 3701 E. TUDOR ROAD. SUITE 101 ' ANCHORAGE. AK 99507 `PHONE (907) 337-5179' FAX N07) 335-3246' WEBSITE: www aamessenolneenmaom PREPARED FOR: LORISCHANCHE )JECT/LEGAL DESCRIPTION: SOUTH HILLS; BLOCK 1, LOT 5A E OF WORK: SITE PLAN PHONE NUMBER: PAGE NUMBER: 830-6147 1 OF 3 DRAWN BY: D.J.G. DATE: 8/5/2016 r I I I I I I I I I I I I I I I I I I I 1"= 100' DESIGN CRITERIA: NUMBER OF BEDROOMS:3 GALLONS PER DAY (GPD): 450 PERCOLATION RATES: '<1 MI W INCH PROPOSED APPLICATION RATE: 0.7 MINIMUM DRAINFIELD SQ.FT.: 643 'PER THEODORE F. MOORE T.H.48 AND#11 DRAINFIELD DESIGN: MAXIMUM DEPTH: LIMITED TO REMOVAL OF CONTAMINATED MATERIAL WIDTH: 15 FEET LENGTH: 43 FEET M.O.A. APPROVED SAND FILTER: "AS NEEDED EFFECTIVE: 0.5 ACTUAL SQPT.: 645 FT' 'AS NEEDED TO REBUILD THE PROPOSED DRAINFIELD AT AN ELEVATION OF 0.1 FEET HIGHER THAN THE EXISTING BED ��PO 5 (3<51 vbj , ` EXISTING CLEAN(( O�O (NEW) DOUBLE CLEANOUTS GEG, Ltd. HAS A 8 PAGE SPECIFICATION LETTER THAT PERTAINS TO THIS DESIGN. TO OBTAIN A COPY OF THE LETTER CONTACT GEG. BY PROCEEDING FORWARD WITH THIS INSTALLATION, THE ENGINEER, WELL DRILLER, _ CONTRACTOR AND PROPERTY OWNER AGREE _% THAT THEY HAVE READ THESE \ SPECIFICATIONS AND AGREE TO ACCEPT THE TERMS AND CONDITIONS OUTLINED. NOTE: THE CONTRACTOR SHALL HAVE ALL WELL RADII FLAGGED BY A REGISTERED EXISTING 3 LAND SURVEYOR PRIOR TO DRIVE CONSTRUCTION. PROPOSED 1000 GALLON SEPTIC TANK; INSTALL DOUBLE CLEANOUTS BEFORE AND AFTER THE SEPTIC TANK (NEN(() DOUBLE CLEANOUTS EXISTING SEPTIC TANK TO BE DECOMMISSIONED PER UPC SOUTH HILLS; BLOCK 1, LOT 6 pAr 43 FEET �/ 5: 'r X15 FEET APPROXIMATE LOCATION OF 1880 T.H.912 BY THEODORE F. MOORE, P.E. APPROXIMATE LOCATION OF 1980 T.H.98 BY THEODORE F. MOORE, P.E. APPROXIMATE LOCATION OF 1990 T.H.#11 BY THEODORE F. MOORE, P.E. SOUTH HILLS; BLOCK 1, LOT 3 DRAINFIELD 20 i 10 PER CONVERSATIONS WITH THE > HOMEONMER(LORI SCHANSCHE) ON �- — 8/3/2016 THERE IS NO WATER OR SEWER 10%/ \ SERVICE TO THE GARAGE z Y \\ I v GARNESS ENGINEERING GROUP, Ltd CIVIL & ENVIRONMENTAL ENGINEERS 3701 ETUDOR ROAD. SUITE 1C1' ANCHORAGE AK99567' PHONE ((9 911 337 6179 'FAX (907) 3383246WEBSITE w,,M mas,erOlnuGr,Q,cm PREPARED FOR: LORISCHANCHE PROJECT/LEGAL DESCRIPTION: SOUTH HILLS; BLOCK 1, LOT 5A TYPE OF WORK: SEPTIC SYSTEM DESIGN UPGRADE PHONE NUMBER: PAGE NUMBER: 830-6147 2 OF 3 DRAWN BY: D.J.G. L 8/3/2016 I LICENSE LICENSE P%FESS 0 GARAGE EXISTING 3 DRIVE BEDROOM HOUSE1,. 'WELL RADIUS SHED \ SERVICE TO THE GARAGE z Y \\ I v GARNESS ENGINEERING GROUP, Ltd CIVIL & ENVIRONMENTAL ENGINEERS 3701 ETUDOR ROAD. SUITE 1C1' ANCHORAGE AK99567' PHONE ((9 911 337 6179 'FAX (907) 3383246WEBSITE w,,M mas,erOlnuGr,Q,cm PREPARED FOR: LORISCHANCHE PROJECT/LEGAL DESCRIPTION: SOUTH HILLS; BLOCK 1, LOT 5A TYPE OF WORK: SEPTIC SYSTEM DESIGN UPGRADE PHONE NUMBER: PAGE NUMBER: 830-6147 2 OF 3 DRAWN BY: D.J.G. L 8/3/2016 I LICENSE LICENSE P%FESS 0 Municipality of Anchorage Page I of . 3 DEPARTMENT OF HEALTH AND HUMAN SERVICES ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, Alaska 99519-6650 • Telephone: 343-4744 On-Site Wastewater Disposal System and/or Well Inspection Report Permit Number: 9 100 PID Number: 01706'3 (1 Name: CECIL WELLS Wastewater System: ® New D Upgrade Address: _ 7201 R11-1506WA ANCA. ABSORPTION FIELD Phone: 3 '45 _ 819 y No. of Bedrooms: D Deep Trench D Shallow Trench X Bed D Mound D Other LEGAL DESCRIPTION Soil Rating: 0-7 Total Depth from original grade: 3.61 — S1 GPD/Sq. Ft. Lot:Block: Subdivision: Depth to pipe Ibottom from original grade: Y2 Gravel depth beneath pipe 5 1 SOUTH MILLS 1 — 2 Ft. 0.5' Ft. Township: 12 N Range: 3 W Section: zS Fill added above original grade: 2 Gravel length: '43 x IS Ft. Ft. WELL: EXIST. D New D Upgrade Gravel depth: Number oflines: 3 Distance between lines: Ft. -S Ft. Classification (Private, A,B,C): Total Depth: Cased To: Total absorption area: Pipe material: 4" PERF F-31 O Ft. I Ft. 44S So. Ft. N"NON PERF PVC D -303 Driller: Date Drilled: Static Water Level: Installer: Date stalled: Ft. CARL 5 EXCAVATING S! o 4- 17 I Yield: Pump Set at: Casing Height Above Ground: TANK E X I $'T 7 N (� GPM Ft. Ft. SEPARATION DISTANCES VSeptic D Holding D S.T.E.P. To Septic Absorption Lift Holding P861 a/Private Manufacturer: Capacity in gallons: From Tank Field Station Tank Sewer Lines 1000 Well SC', 138r ,—. —• loo Material: STEL Number of Compartments: 1 urfa e WatLot >foo' >loo' -- — > loo' LIFT STATION N. A. Size in gallons: Manufacturer: Line S9 23, p Foundationli r r 95 _ O "Pump on" level at: "Pump off' level at: High water alarm at: Curtain Pump Make & Model .Electrical Inspections performed by: I Drain BENCH MARK Remarks'?eASSORP'Tiotsi FIELD 1S LOCATE> LOCATE Location and Description: N Lo-r fi IUSOMeNr ON /c,e 714PE oL B SEM6NT DOOR TFfE E X IS NG Ic TA'NI• WAS NoRTN SIDE OF ov5Ei Assumed Elevation: INS C E Y EAA P TECH ELC 100.00 ENGINEER'S SEAL ON 101S31.90 N D PFOUNP o CSC- /N (Too D CGNDITIO � % Inspections performed by: FLATTOP Ti5cd. Svcs. Dates: 1st E111./91 0Co: '. 0 * ; 4 2nd s I qI 0.600.040 ..... . ... Department of Health and Humans approval %THEODORc F. 1.toORE o M � •,• Services ���rIIV- /'/!T V114e,•.......`.���Reviewed by: c.- ss89 .,•.' and approved Date:pa'pro,, A ��° ray z-uis wall MUAzc Flattop Technical Services Permit,No. 9f Od 7,5 14530 Echo Street Page 2 of 3 Anchorage, Alaska 99516 Municipality of Anchorage DEPARTMENT OF HEALTH AND HUMAN SERVICES ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, Alaska 99519-6650 • Telephone: 343-4744 On -Site Wastewater Disposal System and/or Well Inspection Report Legal Description: LOT s, 9LK I SouTN 4ILLS 61D PID No.: 0170631/ 72-013 A (2/91) MOA 25 Flattop Technical Services Permit No. 21007,C 14530 Echo Street Page 3 of 3 Anchorage, Alaska 99516 Municipality of Anchorage DEPARTMENT OF HEALTH AND HUMAN SERVICES ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, Alaska 99519-6650 • Telephone: 343-4744 On -Site Wastewater Disposal System and/or Well Inspection Report Legal Description: LOT ate, BLk 1 SOUTH HILLS S/D PID No.: O 17 d 6 3 I [-V w M kvv I) M V H ZD tw PAGE 1 OF MUNICIPALITY OF ANCHORAGE � pm DEPARTMENT OF HEALTH.AND HUMAN SERVICES-�j�-�� P.O. BOX 196650, 825 "L" STREET, ROOM 502 ANCHORAGE, ALASKA 99519-6650 MODO-e. ON-SITE WASTEWATER DISPOSAL SYSTEM (UPGRADE) PERMIT PERMIT NUMBER:SW910075 DESIGN ENGINEER:FLATTOP TECHNICAL SERVICES OWNER NAME:WELLS CECIL K & DOLORIS OWNER ADDRESS:PO BOX 2030048' ANCHORAGE, AK 99520 PARCEL ID:01706311 LEGAL DESCRIPTION: SOUTH HILLS BLK 1 LT 5 SEC. 26, T12N, R3W, SM LOT SIZE: 45000 (SQ. FT.) NUMBER OF BEDROOMS: 3 THIS PERMIT: 3 THIS PERMIT IS FOR THE CONTRUCTION OF: DISPOSAL FIELD SYSTEM ALL CONSTRUCTION MUST BE IN ACCORDANCE WITH: DATE ISSUED: 4/30/91 EXPIRATION DATE: 4/30/92 1. THE ATTACHED APPROVED DESIGN. 2. ALL REQUIREMENTS SPECIFIED IN ANCHORAGE MUNICIPAL CODE CHAPTERS 15.55 AND 15.65 AND THE STATE OF ALASKA WASTEWATER DISPOSAL REGULATIONS (18AAC72) AND DRINKING WATER REGULATIONS (18AAC80). 3. THE FOLLOWING SPECIAL PROVISIONS. SPECIAL PROVISIONS: �r%�dde/�LGO`sY "/ Yl" 4'1d'1eu11k as GCOS.G M'4u as pdssi ale r�3 RECEIVED BY: moRtwollmI DATE: ._ l i i2 DATE: � 1 11' -A Flattop 1'echnical Services 14530 Echo Street, Anchorage, AK 99516 Phone(907)345-1355 Lot 5, Block 1, South Hills S/D 7201 Hillside Way Wastewater disposal system Upgrade Design Narrative The proposed soil absorption bed is will serve a three bedroom residence which means that the system must be designed to absorb 450 gallons of water per day. As shown on the soil logs for test holes #8 & 11 in the vicinity of the planned soil absorption bed, the proposed absorption stratum is a slightly silty sandy gravel. Because the measured perc rate of this stratum is faster than 1 minute per inch, the proposed design includes a 2 foot thick sand filter as required by code. The wastewater ordinance specifies that filter sand shall have a design application rate of 0.7 gpd / sq. ft., so the required basal area is 450 / 0.7 = 643 square feet. This can be achieved by a 15 foot wide by 43 foot long soil absorption bed as designed. Due to unfavorable soil conditions encountered in test holes dug on Lot 5, the proposed soil absorption bed will be constructed on Lot 4, as shown on the site plan. Use of this site will allow construction of a gravity system in optimal soils. A copy of the easement which has been recorded to enable this configuration is enclosed. As indicated on the site plan, the closest portion of the soil absorption bed will be approximately 40 feet away from a natural break in slope, beyond which the terrain drops off at 60% towards Rabbit Creek Road. Since this is less than the 50 foot separation specified in the wastewater ordinance, a waiver of this provision to 40 feet is requested. The proposed construction site is on a gently sloping natural bench, and it would not be feasible to move further away from the natural break in slope. Due to the gentle slopes in the vicinity of the proposed construction site, there is no basis for concern that construction as proposed will create a situation where effluent will daylight through the side of the steeper slope. The proposed construction will not impact any existing wells or septic systems on this or adjoining lots. It will utilize a potential site for a wastewater disposal system on Lot 4, however both lots have the same owner, and the owner is aware that that any future development of wastewater disposal facilities for a separate residence on Lot 4 will entail the designation of both an original and a replacement site on the lot separate from this planned construction site. The soils logs for test holes #6, 9, & 10 indicate that there is sufficient room remaining on Lot 4, should the owner wish to develop it separately at some future time. In that situation, a well could be situated near the lot frontage on Hillside Way. Despite the fact that the existing 1000 gallon, single compartment septic tank is 20 years old, an inspection in the fall of 1990 revealed that it is still in remarkably good condition. Thus, the project does not call for the replacement of the existing tank. At such time as the tank does require replacement, a new 2 compartment 1000 gallon tank will have to be located outside the 100 foot radius from the well on Lot 5. Aside from the abovedescribed information, the proposed construction is not expected to have any impact on reserved space / surface and subsurface or on drainage. z to V K m nj m � V, m� W i 6 x ni o O ,'p Cn om M O W�� O c m ��y ro rt C CJi C1 ro A m AV .°•-+• . ••.gyp fie;' na: :�� �`• ONO to a K a r m V, m� W i S x ni o rn " -► LA "� I O ,'p Cn om M O W�� O c m ��y ro rt C CJi C1 ro A m AV .°•-+• . ••.gyp fie;' na: :�� �`• ONO to r - 0 o a m V, m� W i S � m i to r .D LA OU Z C w O ,'p Cn om M O W�� O c m ��y ro rt C CJi C1 ro A m AV .°•-+• . ••.gyp fie;' na: :�� �`• ONO r- Q0 00 0 N m V, m� W O ,'p Cn om M O W�� O c m ��y ro rt C CJi C1 ro A m AV .°•-+• . ••.gyp fie;' na: :�� �`• ONO 0 k 43� C.O. 2.5' IS 5 4"PERF PIPE F-810� O 'v EXISTING 1H0 FVNG MONITORTUg65 Is, SEPTI(c TANK O 5' GLEAM OUT-, 4"NoN PER; 2.5'° D-3o3Y M.T. �FNSrAtit• A 1.1MITS OF C I.RANour. 75, FRU" TAA(h) A excAvArldN PLAN VIEW SCALE : I" = 10' M.C.o. UNCLASSIFlET.D oRIGINAt io7, FILL 6ROvt4b 3 21MINIMVM FILTER FABRIC 20 INSULATION o��.�� oma•♦w �fie• Q (2�'S6WEA GR Vel, .S' D£PTII OF SAND FILTER - EXcAvA7/oN CANDISTuRBED r CrRAv��, SECTION A - A Flattop Technical Services SCALE : ! ` = S � 14530 Echo Street Anchorage, Alaska 99516 I�'y pAv e...y.................. �.. E�;1 ey7NEOD0['c F. MOOPE CE - 3539 •" AV PLAN AND CROSS - SECTION SOIL ABSORPTION BED SERVING LOT S SOUTH HILLS SSD SCALr-: AS SHOWN DATE : 14/91 DIM BY: Flattop Technical Services 14530 Echo Street, Anchorage, AK 99516 Phone (907) 345-1355 Lot 5, Block 1, South Hills S/D 7201 Hillside Way Wastewater disposal system Upgrade Specifications 1.0 General: 1.1 The scope of the project includes abandonment of the existing seepage pit and construction of a new 15' wide by 43 foot long soil absorption bed connected up to the existing septic tank. 1.2 Construction shall be as depicted on the approved site plan and design drawings. Minor deviations from these drawings may be allowed or required by the engineer conducting the inspections. All construction procedures and material specifications shall conform with Municipal and State requirements. 1.3 All separation distances shall be in conformance with Municipal requirements, unless specifically waived. 1.4 The contractor shall be responsible to obtain any necessary utility locates, and to work around any buried utilities. 2.0 Septic Tank: 2.1 The existing septic tank may be retained in service provided it's structural integrity still is good at the time of connection to the new soil absorption bed. The required separation distance from the well is 50 feet for the existing tank, however any replacement tank will have to be 100 feet from the well. 2.2 Pipe connections to the tank shall be equipped with waterproof mechanical couplings. The waste line between the tank and the soil absorption system shall have a minimum slope of 1/8" per foot. 3.0 Soil absorption system: 3.1 The soil absorption system shall be constructed by excavating the surface soils in the designated bed area to a depth of 5 feet below original ground level on the uphill side of the bed. The bottom of the bed excavation shall be level. 3.2 A 2 foot thick layer of approved filter sand shall be placed in the excavation. The filter sand shall comply with Municipal specifications. 3.3 A total of 12 inches of sewer gravel shall be placed on top of the sand with the 4" diameter perforated pipes buried level in the sewer gravel in the configuration shown, such that the bottom of the pipes is no less than 6 inches above the top of the sand. The sewer gravel shall be 0.5" - 2.5" screened gravel, with less than 3% passing the #200 sieve. 3.4 Monitor tubes and cleanout pipes shall be of 4" diameter and installed in the locations shown on the design drawings. The portion of the monitor tube extending through the sewer gravel shall be perforated. 3.5 Approved filter fabric shall be placed over the entire top surface of the sewer gravel. A minimum of 2 feet of soil cover is to be placed over the filter fabric. If the soil cover thickness is less than 3 feet, two inches of rigid, burial type insulation is to be placed over the entire top surface of the gravel, in addition to the filter fabric. 3.6 The top surface of the cover material shall be raised a minimum of 6 inches higher than the surrounding terrain to allow for subsequent settlement, and shall be graded to smooth contours. Fill slopes shall be no steeper than 3:1. 5.0 Inspections: 5.1 A total of 5 engineering inspections will be required during the course of the project: (1) initial stakeout with the contractor to establish the location of the system and to discuss the plans, specifications and construction procedures, (2) after the native material has been excavated to expose the infiltrative surface to ensure that it is level and at the right elevation, and conforms with the soil test information, (3) after the sand filter material has been placed, (4) after the sewer gravel is in place and the distribution pipes have been laid and connected up to the septic tank, but prior to placement of insulation or filter fabric, and (5) after final backfill and grading is complete. 5.2 The installer shall coordinate the timing of the inspections with the engineer sufficiently far in advance to ensure the availability of the engineer. BLANKET EASEMENT Cecil K. Wells and Doloris Wells are the owners, in fee simple, as tenants in the entirety of Lot 5, Block 1, South Hills Subdivision, Anchorage, Alaska and Lot 4, Block 1, South Hills Subdivision, Anchorage, Alaska, Third Judicial District, Anchorage Recording District, as a consequence of Warranty Deeds recorded in Book 462, Pages 869 and Book 136, Pages 0771-0772. Cecil K. and Doloris Wells hereby convey to Cecil and Doloris Wells for Ten Dollars ($10) in good and sufficient consideration for a blanket easement upon Lot 41, Block 1, South Hills Subdivision, for the benefit of Lot 51 Block 1, to construct and maintain upon Lot 4, Block 1, such septic system or systems as may be required by Lot 5, Block 1, including but not limited to absorption beds, leach fields, piping, and any other requirement which may be imposed by the Municipality of Anchorage as a requirement for condition of replacement of the existing septic system on Lot 5, Block 1. DATED this cr—/ day of &zj L , 1991. ii _ CEC LK. WELL Cec r K. Well Doloris Wells STATE OF ALASKA ) ) ss: THIRD JUDICIAL DISTRICT ) dividually and Attorney -in -Fact for The foregoi inns rument was acknowledged before me this _ day of , 1991, by Cecil K. ,•r Municipality of Anchorage DEPARTMENT OF HEALTH 8, HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG — PERCOLATION TEST T.�- #I PERFORMED FOR: C. E C I L W I L L S DATE PERF 6RMEN LEGAL DESCRIPTION:$1 SUVTI� N1LL5 Township, Range, Section: 5��;: (o T DESCRIPTION: -- L SLOPE SITE PLAT s rya rf� Yd,h AV PV* * a..................::� . THEODORE P. A,AOORE;� _ 1 • 3rrgV --a•—vti-r� 1 t" 1 2 ML SILT j Did`/ 3 SLIGHTLI SANDY 4 SLIGNTL`( GRAVELLY 5- 00 BoULDERS a 6- 7- ML SILT 8- 9- 10-- 910 WAS GROUND WATER ML SLIG14TLy ENCOUNTERED? NO 11 6RAVE-LL11 SILT S B. H. IF YES, AT WHAT L 12 P P DEPTH? ry,A • N?kl E 13 Depth to Water After Monitoring? DRY Dale: 11111 0 14- 15- 16- 17 4151617 18 19 20 COMMENTS Reading Date Gross Net Depth to Net Time Time Water Drop PERCOLATION RATE (minutes/inch) PERC HOLE DIAMETER TEST RUN BETWEEN FT AND FT ��l23/9c PERFORMED BY: CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: 72-008 (Rev. 4/85) - Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG — PERCOLATION TEST `T.N• #2 .ri- `4,jI lik wk AV A4' t? , T 14 fee 64:0"As 15*%THEODORU F. MOORE : 19 PERFORMED FOR: CECIL WELLSyy,�'� rr••'� D GATE PERF66MED7� LEGAL DESCRIPTION: L 9 B SOUTM WILLS Township, Range, Section: p�1 SLOPE SITE PLAN 1 2 3 4 5 6 7 8 9 10 11 12 13 14• 15• 16- 17 - 6•17• 18• 19- 20 - (FEET) 4.-92 PT ML WAS GROUND WATER ENCOUNTERED? NO S IF YES, AT WHATA�t L DEPTH? N -A . O P E Depth to Water Alter Monitoring? Dale: Reading Date Gross Net Depth to Net Time Time Water Drop I I PERCOLATION RATE (minutes/inch) PERC HOLE DIAMETER TEST RUN BETWEEN FT AND FT COMMENTS No MoAtkr TZ4,6e Ill .Cjatiea PERFORMED BY: _nvCn. 5�ti4f'I - r� ;� CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: _ 11 / /72. / 94 72-008 (Rev. 4/85) L Munlclpalily of Anchorage t DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG — PERCOLATION TEST -r. H • *3 ;n Bl`ruoNE,fH'S,s,E4�4); v� `A. „ • s C2 • �r el .� PERFORMED FOR: CECIL WELLS DATE PERFORMED: �._.••4i�+. (vlz4 LEGAL DESCRIPTION: L 5 81 SOUTH HILLS Township, Range, Section: SEC 2 6, T 12 N' g 3 W DEPTH SLOPE SITE PI GN (FEET) VT 1 2H GM SILTY GRAVEL 3 TRfINSITION IN6 TO 1 4 ML GRAVELLY SILT 5 6 420 SEE PS 7 B. H, 8 9 10 11 12 13 14 15 16 17 18 19- 20 -[ COMMENTS Per°C l-e.rf 7r a: e.cF of T° !i. #3 WAS GROUND WATER YES ENCOUNTERED? IF YES, AT WHAT / DEPTH? 6 °S Depth to Water After r Monitoring? 6 xS Date: I I f /go Reading Date Gross Time Net Time (t„) Depth t Water t,N, Net Drop .rte Re50 K l0 25 11:05 2SIP2 rr K20 l: 27 23 3/ 11.32 5 21 V''/ f H o II'.33 23 %Z I1: 38 5 21 s/ 1 'Y -fHao 11,38:30 23 ?/ 11:43:30 S 21 7/s 2 t9 o Il'.gY 23 s/ II,�f9 i 21 S' 2 a PERCOLATION RATE 2' �O (minutes/inch) PERC HOLE DIAMETER Or TEST RUN BETWEEN _2 �Z - FT AND 3 FT PERFORMED BY: FL ATT O P TEC14 SU S I 0..erC_ 0- CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: - II i O 72-008 (Rev. 4/85) Municipality of Anchorage DEPARTMENT OF HEALTH a HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG — PERCOLATION TEST ° .Illy_ �.eec• _ <'.\`a.� PERFORMED FOR: CECIL WELLS DATE PERFORMED:_ LEGAL DESCRIPTION: L5' 81 SOUTH HILLS Township, Range, Section: SEC 26, T 12 N, R 3W DEPTH SLOPE SITF PI GN (FEET) I I I I I I t 2 3- 4- T. 0. 4T.N. # 5- 6 7 8- 9- 10- 11 91011 12 13- 14- 15- 16- 17 314151617 81920 18- 19- 20 PT ML SILT B. N. WAS GROUND WATER ENCOUNTERED? IF YES, AT WHAT DEPTH? Depth to Water After Monitoring? Dale: Reading Date Gross Net Depth to Net Time Time Water Drop PERCOLATION RATE (minutes/inch) PERC HOLE DIAMETER f TEST RUN BETWEEN FT AND FT COMMENTS MCI Yh&A4&/' stye Indrittec-'( PERFORMED BY: —FLATTOP TEc N QVC s I K�'iK_ CER1-IFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: 90 72-008 (Rev. 4/85) Municipality of Anchorage ^r �l °; �5:. .`..: a ; Afere a e,,.eeee.eeeee ee?: DEPARTMENT OF HEALTH 8 HUMAN SERVICES or 825 825 "L" Street, Anchorage, Alaska 99502-0650 . °+ e SOILS LOG —PERCOLATION TEST S), ,.ti°,Taaoc 1'i V /. .• � / y PERFORMED FOR: CEC IL WELLS DATE PERFORMED: i9� i g2�� (U/AV LEGAL DESCRIPTION: L 5 B I SOUTH HILL S Township, Range, Section: SEC 2 6 `j-12 N, R 3 1 W DEPTH SLOPE SITE PLAN It (FEET) 1 PT 2 ML SANDY SILT H SE N Cl 4-{ I GM SILT`I 6RAVE-L 5 6 Hi o SEF PS 7 T.♦r#S B.N. 8 9 10 11 12 13 14 15 16 17 18 19 20 I (o S. E. of T.H.# S WAS GROUND WATER ENCOUNTERED? ES IF YES, AT WHAT DEPTH? �o Depth to Water Aller le Monitoring? 6 6 Date: II/f/70 Reading Date Gross Time 1 Net Time Depth to\ Water I ff) Net Drop PReSoAk 10/2sho I : l0 27 Y8 1:30:30 22 1/ + W, 0 t:31: 30 23 -s/ #1� 1 I'4(: 3o /0 22 I s o t 1'•YZ 23 s # :52 l0 22 158 t42 o 1:53 22 3/ 203 10 22 y � s/ JPERCOLATION RATE 6-2 (minutes/inch) PERC HOLE DIAMETER - „ `` TEST RUN BETWEEN �_ FT AND 3 /2 FT COMMENTS �u.rnq Tt'G( o4 iaq �a/ T H } PERFORMED BY: _.FLATTOP TECN S/CS�/ � r^,'� I .1.� "'—�+� CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: 11 / /7,/9 0 72-008 (Rev. 4/85) dip ow +w Munlclpallty of Anchorageo *�;•49T11 A••5 ®� DEPARTMENT OF HEALTH & HUMAN SERVICES �••••••••••••••••• •••.:..•t 825 "L" Street, Anchorage, Alaska 99502-0650 0 /'0900,0;600 i a .. ;............ SOILS LOG — PERCOLATION TEST ¢e . THEODORE F. MOORE ; et T LI W 44-f CE -3589 Pp~10/2,4/10 ld PERFORMED FOR: CECIL WEL S _ DATE PERFORMED•SSIC7)a' Q,O� LEGAL DESCRIPTION: L r Pi I 5OUTN WILLS Township, Range, Section: SEC DEPTH PE sit PLAN PLAN FT (FEET) 1 r • SM SILTY, COARSE SAND 2- 3 3 GM SILTY GRAVEL WITH SOME SAND 4 ML 5 Gw CLEAN SANW1 6 GRAVEL a 7- 8 8 H 9 GM SILTY SANDY 10 GRAVEL WAS GROUND WATER ENCOUNTERED? Nil 11 S IF YES, AT WHAT L DEPTH? KA. . O 12 B.µ. P E 13 T 09 Depth to Water Alter 1l Monitoring? DRY Date: 11/1190 14- 15- 16- 17 4151617 18 19 20 COMMENTS �WEr.t. Reading Date Gross Net Depth to Net Time Time Water Drop PERCOLATION RATE (minutes/inch) PERC HOLE DIAMETER TEST RUN BETWEEN FT AND FT PERFORMED BY: FLA'iTOP TEC N. SVCS 1 '�,-0 �-t-k CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: _I it 90 72-008 (Rev. 4/85) 0MEN 0NIX M�lII!�' ME MMIND 010M No MIN INNINI■ �WEr.t. Reading Date Gross Net Depth to Net Time Time Water Drop PERCOLATION RATE (minutes/inch) PERC HOLE DIAMETER TEST RUN BETWEEN FT AND FT PERFORMED BY: FLA'iTOP TEC N. SVCS 1 '�,-0 �-t-k CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: _I it 90 72-008 (Rev. 4/85) tir Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG — PERCOLATION TEST 7. R. i�7 got •U. .... ..•. I:... :i: THEUOUI2E F.r�MOORE;' 3589� ' ql� 4 PERFORMED FOR: LEC I L WELL S DATE PERFORMED:"A LEGAL DESCRIPTION: L,5- P I SOVTH WILLS Township, Range, Section: SEC DEPTH PE SI� PLAN (FEET) 1 1 1 Pr Mt_ TIGHT BROWN SILT 3 1n 4 5 6 GM SILTY G RAKE L BROWN / DAMP 7 f ML TIGHT BROWN SILT 8 He 9 GM SILTY GRAVEL 10 13 Row WAS GROUND WATER S. ENCOUNTERED? 1 11 RAMP S IF YES, AT WHATL 12 DEPTH? 12 r �O i1 PO GP SANDY GRAVEL E $ 13 GRAY Depth to Water Alter 7.N.#! 4.0 SATURATED Monitoring? Date: 14- 15- 16- 17 4151617 81920 18- 19- 20 IM Net Time Depth to Water 0Mal ��11�■ mZ►����Man. ME �E°i\\WOMEN MINMIM 'mma MEno ���\\e�� MENEM WELL \ Reading Date Gross Time Net Time Depth to Water Net Drop U PERCOLATION RATE (minutes/inch) PERC HOLE DIAMETER TEST RUN BETWEEN FT AND FT COMMENTS TH.47 ON 2S% SLOPE • No IST IKSTALcEb Soil Aof ScclActbl- '�+�� ronl�luL�ton of on- Sr�c ,Burl ctbso rho., syff« PERFORMED BY: _FLATTOP TECH SVS , -mac-. CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: /f /1./ iG 72-008 (Rev. 4/85) Munlcipallty of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG — PERCOLATION TEST T.N.#8 THEODORE F. M00RE ;� , 'a. CE - 3589 PERFORMED FOR: CECIL WE L S DATE PERFORMED: LEGAL DESCRIPTION:_L Y - P� I SOUTH WILL S Township, Range, Section: SEC 2Y,',''j"(2 DEPTH nT PE sitPLANPLAN (FEET) r_ I , SKE7 RDD ISH SAMDY zL LOAM `Y 3 GF/GM SLIGHTL`( SILTY 4 13 ROwN GRAVEL 5 MANY C088LES g AND BovLDt-RS 7 8 9 SM/ML GRgY SILTY SAND 10 WAS GROUND WATER �=■�i■����� ENCOUNTERED? NO 11 $. Fi • S 011140 IF YES, AT WHAT L O 12 T$ DEPTH? P E 13 Depth to Water Aller p Monitoring? � Dale:fl / 1-2-40 14 15 16 17 18 19 20 UPERCOLATION RATE (minutes/inch) PERC HOLE DIAMETER 8 TEST RUN BETWEEN 9. a FT AND yFT COMMENTS-M•T. INSTA LLED PERK -TEST - CovcD NOT KEEP HOLE FULL PERFORMED BY: FLATTOP TECH, SVCS �.�-rJL /�r-fi-en,�_ CERIIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: f 1 12--190 72-008 (Rev. 4/85) N �=■�i■����� 1.400 011140 MWO WE ■�G/I ►�■■■■■ ■■/�����■■■■ �M■II �I■/■■\\■■■ ■■,.■■ ■■1 MINE .■ UPERCOLATION RATE (minutes/inch) PERC HOLE DIAMETER 8 TEST RUN BETWEEN 9. a FT AND yFT COMMENTS-M•T. INSTA LLED PERK -TEST - CovcD NOT KEEP HOLE FULL PERFORMED BY: FLATTOP TECH, SVCS �.�-rJL /�r-fi-en,�_ CERIIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: f 1 12--190 72-008 (Rev. 4/85) �=■�i■����� UPERCOLATION RATE (minutes/inch) PERC HOLE DIAMETER 8 TEST RUN BETWEEN 9. a FT AND yFT COMMENTS-M•T. INSTA LLED PERK -TEST - CovcD NOT KEEP HOLE FULL PERFORMED BY: FLATTOP TECH, SVCS �.�-rJL /�r-fi-en,�_ CERIIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: f 1 12--190 72-008 (Rev. 4/85) Munlclpallty of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG — PERCOLATION TEST TH. #9 dip jW THEODORE r. MOORE CE -3589 .•` ��' a 64 PERFORMED FOR: CECIL WFL DATE PERFORMED: LEGAL DESCRIPTION: L N _$ I SOOT H W) LL S Township, Range, Section: SEC 26; Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG — PERCOLATION TEST T. 4. #/o dw -%w 6000, -40 w•.....I-ay •�' 4,N �Tkn,14�iTIII •�.f..'...II.I.I....��..1.11IY .�..... .. ..T...1:: :THEODORE F, MOORE;1� � ®'n •„ CE -3589 II1Z/90 PERFORMED FOR:—fL�* I L WELL -4� DATE PERFORME LEGAL DESCRIPTION: L DEPTH (FEET) FT 1 2 3 4 5 6 7 T-Wo/o 8 9- 10- 11 1011 12 13- 14- 15- 16- 17 314151617 18 19 20 COMMENTS GP ML M Wur��wiwi• 111111'1`�6� WAS GROUND WATER ENCOUNTERED? Nt0 S IF YES, AT WHAT t L DEPTH? N.f} , O P E Depth to Water Alter Monitoring? Dale; M/FLL \ Reading Date Gross Time Net Time Depth to Water Net Drop PERCOLATION RATE (minutes/inch) PERC HOLE DIAMETER TEST RUN BETWEEN FT AND FT PERFORMEDBY: _FLATTOP aCq St/ I �.-..f. 7hol„c CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: _ iI 72-008 (Rev. 4/85) - Municipality of Anchorage c%4 9 Tli DEPARTMENT OF HEALTH & HUMAN SERVICES 0•••••• •••••••••....•.5..• 825 11" Street, Anchorage, Alaska 99502-0650 SOILS LOG — PERCOLATION TEST „ • THEOVORL F, MOORE i l l 4 -� N �.y' ., CE - 3589 nJ� PERFORMED FOR: _ CECIL IL WELL DATE PERFORMED:, LEGAL DESCRIPTION: L y $ I SOUTH HILLS Township, Range, Section: SEC Zip,f"(' DEPTH PE Slip PLAN (FEET) PT 1 2 6P/6M SLIGHTLY SILTY / GRAVEL 3 n GP I P SANDY GRAVEL L� y 5 SLIGHTLY SILTY s � SW GRAVELLY SAND 7 CLEAN 8 He WiSM SLIGHTLY SILTY s GRAVEL CNCREASIK(6LY DAMP 10 WAS GROUND WATER WITH DEPTH ENCOUNTERED? NO 11 S IF YES, AT WHAT pp L P 12 T #II DEPTH? �(,✓//i vf� 13 Depth to Water After pry Monitoring? y Date: 10/12-/90 14- 15- 16- 17 4151617 81920 18- 19- 20 PERK TEST S'N W. O F T.N.# it I■►I■■■■li■■ Date Gross Net Time T me(Moo) Depth to Water Net Drop J 12" PRE90A u/2 9d 3:33 2 1 %y 3-)37 DRY + H o 3:38 28 .e - OWN 3: r(l: 25 23 318 3i r ■���■■■ 22 % I Y man 3:yz"Es 23 ■ tk2 3: 43: SS I 2z Y8 +q'30 3:4y: 257 23 S�8 ■■■��AA■■■ems sl 3 3:ys:2S t 22 Ya I `v v 3:y6'.2s I ■�iG 111014 ONE NNE �i■■��■■E ON k--wwELL \ Reading Date Gross Net Time T me(Moo) Depth to Water Net Drop J 12" PRE90A u/2 9d 3:33 2 1 %y 3-)37 DRY + H o 3:38 28 .e - START 3: r(l: 25 23 318 3i r 3:y2 2S 1 22 % I Y +H o 3:yz"Es 23 tk2 3: 43: SS I 2z Y8 +q'30 3:4y: 257 23 S�8 sl 3 3:ys:2S t 22 Ya I `v v 3:y6'.2s I z( I'/8 JPERCOLATION RATE 0, 9_ (minutes/intc,Ih)PERC HOLE DIAMETER TEST RUN BETWEEN 3.5- FT AND y. o FT COMMENTS . t10Al J!�-6 e iT dr{u((PK PERFORMED BY: FLATTOP TECH SVCS_ CERTIFY l -HAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: 72-008 (Rev. 4/85) �xQ. .............�,�'�� yr Municipality of Anchorage4CTii ��' DEPARTMENT OF HEALTH & HUMAN SERVICES ®o* oo ............$so#.::. 825 "L" Street, Anchorage, Alaska 99502-0650 002 :.... .......' ...�.� : SOILS LOG — PERCOLATION TEST µ THEODORE F, MOORE ; T. A r2 •., CE - 3589 PERFORMED FOR: CECIL IL WFL -S DATE PERFORMED: LEGAL DESCRIPTION: L DEPTH (FEET) PT - 1 2 3- 4- 5- 6 456 7 8 9 T.N.+IIZ 10- 11 12 13- 14- 15- 16- 17 314151617 18 19 20 GM GP/( 1200 WAS GROUND WATER ENCOUNTERED? NO S IF YES, AT WHATL N.A.A O DEPTH? P E Depth to Water After Monitoring? Dale: WELL Reading Date Gross Net Depth to Net - Time Time Water Drop PERCOLATION RATE (minutes/inch) PERC HOLE DIAMETER TEST RUN BETWEEN FT AND FT COMMENTS -.NO MONITOR ?U E TE.[i hole duq y4. Cpsr�/rrn �pn7�rynu[I(Y O� /►t Crfl/Y.Lf n Cvu n C>< n N. # d' e n PERFORMED BY: FLATTOP T i u s'V SI -� CERT IFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: l(11"'190 72-008 (Rev. 4/85) BLANKET EASEMENT Cecil K. Wells and Doloris Wells are the owners, in fee simple, as tenants in the entirety of Lot 5, Block 1, South Hills Subdivision, Anchorage, Alaska and Lot 4, Block 1, South Hills Subdivision, Anchorage, Alaska, Third Judicial District, Anchorage Recording District, as a consequence of Warranty Deeds recorded in Book 462, Pages 869 and Book 136, Pages 0771-0772. Cecil K. and Doloris Wells hereby convey to Cecil and Doloris Wells for Ten Dollars ($10) in good and sufficient consideration for a blanket easement upon Lot 4, Block 1, South Hills Subdivision, for the benefit of Lot 5, Block 1, to construct and maintain upon Lot 4, Block 1, such septic system or systems as may be required by Lot 5, Block 1, including but not limited to absorption beds, leach fields, piping, and any other requirement which may be imposed by the Municipality of Anchorage as a requirement for condition of replacement of the existing septic system on Lot 5, Block 1. DATED this �� day of . pz/� , 1991. RECEIVED APR S 1991 CEC L K. W LL , individually and Ceci K. Well s Attorney -in -Fact for Municipality of Anchorage Doloris Wells Dept. Health & Human Services STATE OF ALASKA ) ss: THIRD JUDICIAL DISTRICT ) /1 The foregoi g in, rument was acknowledged before me this ` \ day of 1991, by Cecil K. Wells, individually and as attrin-fac on Wells. 7/h commission expires: BLANKET EASEMENT Page 2 22P.2 f of Doloris 0 j we'll A b Vzl/ � C—a 7 � b 2b b A b Vzl/ r G y� ti } T�v CIVII. & ENVIRONMENTAL ENGINEERING • ENERGY CONSERVATION & ANALYSIS THEODORE F. MOORE, P.E. June 11, 1991 PH: (907) 345-1355 John Smith M.O.A. DHHS P.O. Box 19-6650 Anchorage, AK 99519 Dear Mr. Smith: 14530 ECHO ST. ANCHORAGE, ALASKA 99516 RECEIVED JUN 12 1991 Piun c pwi,iy of Anchorage Dopt. Health & Human Services Per your request, enclosed is a revised as -built profile drawing for L5, B 1, South Hills S/D showing the additional elevation information you requested. I know you take it as your duty to enforce the letter of the ordinance, but please bear with me while I make a couple of comments. Admittedly, the ordinance specifies that a profile drawing showing certain specified pieces of information is to be part of the final inspection report, but in my opinion some of the specific required pieces of information are irrelevant, and other important pieces of information are omitted. For example, giving the invert elevations of the beginnings and ends of the distribution pipes doesn't help determine whether there are high or low points in the middle of the pipes which could prevent even distribution of effluent. In my inspections I take it upon myself to try to ensure that the excavator has kept the entire distribution pipe system level within small tolerances, and I feel providing that assurance is more relevant than providing the elevations of a couple of arbitrarily chosen pipe ends. I have a conceptual difficulty with drawing profiles of non-linear systems. It would be helpful to me if you could provide us engineers with an example of how a typical profile should be drawn to represent a normal bed type soil absorption system having 3 or 4 parallel distribution pipes. What sort of horizontal and vertical scales do you have in mind? Why does neither the ordinance nor the newly implemented DHHS "as -built" form call for the elevation of the bottom of the sewer gravel to be shown on the profile, and also the bottom of the sand filter when applicable? It would seem to me that these are more important bits of data than those you requested I provide. Also, on the first sheet of the new DHHS as -built form, why is the gravel length, but not the gravel width deemed important enough to record? There are numerous other data reporting requirements which I do not understand, both apparent omissions and other data which I feel is superfluous. Of course, from my perspective I would prefer that the Department solicit comments from the affected engineers before adopting new reporting sheets, as I would think we might be able to offer some constructive suggestions. Thanks for hearing me out. Sincerely, Ted Moore, P.E. Flattop Technical Services Permlt No. 9 (00 -t r 14530 Echo Street Page 3 of 3 Anchorage, Alaska 99516 Municipality of Anchorage DEPARTMENT OF HEALTH AND HUMAN SERVICES ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, Alaska 99519-6650 0 Telephone: 343-4744 On -Site Wastewater Disposal System and/or Well Inspection Report Legal Description: LOT BLk 1 SOvTN H ILLS St/D PID No.: D 1-706311 i ELEVATIO BASEt4EAT DOOR ii1RESHoLp SVRFac6 of 9b -TAN KpovgLE C.o> INdART =9S.T1 ` 141 W END- _ - oG 4Eo E: 8N0 I F=(NA A6:04Pr° 1701) ' ovER r3Ev =93 r i r FILL --� INSVLA T_ ON SEI"ER 6RAvEc 4 a 8 ID D15TRIgvTront plpEE. iNV eed o P Oil Pa. 38 ENGINEER'S SEAL PIPE'S hf►fD L.EvEL, rte, 0raq` 4�'N of A4 BaTrorl OP SAnrD 670 M ��• •• •• f * �97M _ _--- (3aftu/» of Taff. 41- If ti 7. = c9 1,& • � ?? /ya GR&OND wAMIT _r-prou;v rB?Ep : THEODORE �. FAOORE; CE -3589 c; l/' y ro�ess►oc �►6"11-4 t9i 72-013 A (2/91) MOA 25 GAAe-HD- I GREATER ANCHORAGE AREA BOROV 1H _ J HEALTH DEPARTMENT J 327 EAGLE ST. ANCHORAGE, ALASKA 99501 279-2511 INSPECTION REPORT ON SITE SEWAGE DISPOSAL SYSTEM MAILING PHONE NAME � � /G /:�'/-�-/ ADDRESS O� - �= LOCATION tri' � C� / ��' T LEGAL DESCRIPTION Z L7% SEPTIC TANK: I�%r NUMBER OF DISTANCE FROM WELL MATERIAL S'i �'-=- COMPARTMENTS LIQUID �- LIQUID CAPACITY X0 4:�'�2 GALLONS. INSIDE LENGTH INSIDE WIDTH `� DEPTH SEEPAGE SYSTEM: SEEPAGE PIT: NUMBER OF PITS -OUTSIDE DIAMETER - OR WIDTH `�- LENGTH DEPTH 14- LINING MATERIAL - ` ZXIOX;> • DISTANCE FROM WELV� 2 ` BUILDING FOUNDATION NEAREST LOT LINE f20 . TOTAL EFFECTIVE ABSORPTION AREA (WALL AREA) TILE DRAIN FIELD: DISTANCE FROM W FOUNDATION_ NUMBER OF LINES / !� DISTANCE BETWEEN LINES_ ABSORPTIOREA SQ. FT. LENGTH OF EA DEPTH: TOP OF TILE TO FINISH G SQ. FT. TOTAL LENGTH NEAREST LOT LINE , OF LINES - IN. TOTAL INES DEPTH OF FILTER MATERIAL BENEATH IN.-TOTAL EFFECTIVE IN. ABOVE TILE WELL: DISTANCE FROM WATER DEPTH , BUILDING FOUNDATION. �� SAMPLE �� NEAREST NEAREST J� SEPTIC r� SEEPAGES / �� OTHER �. LOT LINE L SEWER LINE TANK lti SYSTEM.' CESSPOOL , SOURCES_ DISTANCES: DIAGRAM OF SYSTEM f DATE ;7 APPROVE t HEALTH AUTHORITY 333 3AAB-HD-2GREATEFL�..- ANCHORAGE AREA 1s...,,R0UGH Case No. 1 HEALTH DEPARTMENT 327 Eagle St. Anchorage, Alaska 99501 279.2511 ! , j' '' a ,Vv SEWAGE DISPOSAL SYSTEM - APPLICATION & PERMIT �� �� fir/ — NAME OF APPLICANT � � LL � MAILING ADDRESS �©X PHONE NO.,� RESIDENCE ADDRESS LOCATION OF INSTALLATION � � , LEGAL DESCRIPTION /-e7 L �cK d�✓6 �� �' r'd 'i�iLL APPLICATION TO INSTALL: SEPTIC TANK "� , SEEPAGE PIT ✓ TO SERVE THE FOLLOWING FACILITY 65:11L'f6LE FINANCED THROUGH THROUGH PERCOLATION TEST RESULTS , DRAIN FIELD , OTHER TO BE INSTALLED BY ANTICIPATED DATE OF COMPLETION BELOW TO BE FILLED OUT BY HEALTH DEPARTMENT THIS IS TO SERVE AS b�/� LL 5' PERMIT TO INSTALL A AS DESCRIBED BELOW. SIZE OF UNIT TO BE SERVED SEPTIC TANK SIZE(20 ' TYPE DISTANCES: . X12 4-�F610&E I/`,'R /riiA) (G6 / i49M L"_Lta- Health Authority SEEPAG AREA DIAGRAM OF SYSTEM TYPE I certify that I am familiar with the requirements of Greater Anchorage Area Borough Ordinance No. 28-68 and that the above described system is in accordance with said code. DATE a 6 j APPLICANTS SIGNATURE E �`� \� E Municipality of Anchorage �a , On -Site Water & Wastewater Program (907) 343-7904 e 4k' Certificate of On—Site Systems . oto ot,3g�� Approval Parcel I.D. _04Z-96344— Expiration Date: 1. GENERAL INFORMATION Complete legal description SOUTH HILLS; BLOCK 1, LOT',5)� Location (site address) 7201 OLD HILLSIDE WAY -ANCHORAGE, AK 99516 Current Property owner(s) LORI SCHANCHE Day phone 907-830-6147 Mailing address 7201 OLD HILLSIDE WAY *ANCHORAGE, AK 99516 Real Estate Agent NIA Day phone - 2. TYPE OF DWELLING: ® Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 3 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Individual Well Individual On-site Individual Water Storage ❑ Individual Holding tank ❑ Community Class Well ❑ Community On-site ❑ Public Water System ❑ Public Sewer ❑ Waiver/Variance request for. NIA Distance:= NJ Received by: Date: COSA to be released to the engineer, unless otherwise requested by the engineer. COSAFee$ A(46T -I(pllo r Lfo40 Date of Payment gla(011� (*, Receipt Number COSA# OSCIb(3$� Waiver Fee $ Date of Paymenl Receipt Number Waiver # If more than I septic system is on the lot: COSA Checklist # _of_ Structure served by this system Certificate of On -Site Systems Approval Checklist 155 - Legal Description: SOUTH HILLS; BLOCK 1, LOT 5A Parcel ID. 017 -063 -yr *WELL WAS DEEPENED BY ALPINE DRILLING & ENTERPRISES ON 7/16/2016 "*PER ALPINE DRILLING & ENTERPRISES -SEE ATTACHED DRILLING LOG A. WELL DATA ***ASSUMED BASED UPON SURROUNDING WELL LOGS Well type PRIVATE If A, B, or C provide PWSID# N/A Date completed 1971(?) & 2016 Sanitary seal (Y/N) YES Total depth , **166 ft. Cased to ***40+ ft. FROM WELL LOG Date of test Static water level�� ft. NO Well production — 9 -p.m -WATER SAMPLE RESULTS: Well Log (Y/N) *NO Wires properly protected (Y/N) YES Casing height (above ground) 12+ in. AT INSPECTION 7/19/2016 **61 ft **7 g.p.m. Coliform *0 colonies/100 ml. Nitrate ND mg./L. Collected by: GEG, Ltd. Arsenic: 12.9 ug JL. Date of sample: 8/1/2016 & *6112/2016 *AAROW PUMP & WELL SERVICE B. SEPTICIHOLDINGTANK DATA *DOUBLE CLEANOUTS Tank Type/Material SEPTIC/STEEL Date installed 6111-15/2016 Tank size 1000 gal.. Number of Compartments 2 Cleanouts (Y/N) YES Foundation cleanout (YIN) Depression over tank (YIN) NO High water alarm (Y/N) N/A Date of pumping NEW Pumper C. ABSORPTION FIELD DATA *BELOW FINAL GRADE Date installed 6/11-15/2016 Soil rating kp.dr or fe/bdrm) 0_7 System type BED Lengtfi 43 ft. Width 15 ft. Gravel below pipe 0.5 ft, Total depth *3:96 ft. Eff. absorption area 645 fe Monitoring tube YES Depression over field NO Date ofaa_gequacy test NEW Results (Pass/Fall) For 3 bedrooms Fluid depth in absorption field before test= in. Water added=gal. New depth in. Elapsed Time: = min. Final fluid depth _ in. Absorption rate >= 450+ g.p.d. Any rejuvenation treatment (past 12 mo.) (Y/N & type) N/A If yes, give date D. LIFT STATION Date installed Size in gallons Manhole/Access "Pump on" level at in. "Pump off' level at wa er alarm level at Cycles tested - Meets alarm & circuit requirements? E. SEPARATION DISTANCES SEPARATION DISTANCES FROM WELL ON LOT TO: Septic tank/lift station on lot 1001+ On adjacent lots 1001+ Absorption field on lot 1001+ On adjacent lots 1001+ Public sewer main 76+ Public sewer manhole/cleanout 1001+ Sewer /septic service line 25'+ Holding tank 751+ Animal containment areas 50'+ Manuretanimal excrete storage areas 1001+ SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Building foundation 5'+ Property line 5'+ Absorption field 5'+ Water main 101+ Water service line 10+ Surface water Wells on adjacent lots 1001+ SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Property line 10'+ Building foundation 10'+ Water main 10'+ Water service line 10'+ Surface water 100'+ Driveway, parking/vehicle storage 10'+ Curtain drain NONE KNOWN Wells on adjacent lots 1004 F. COMMENTS DRAINFIELD IS 36+ FROM SLOPES GREATER THAN 25% (WR#OSV161091) G. ENGINEER'S CERTIFICATION I certify that t have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. Engineer's Printed Name JEFFREY A. GARNESS Date 15 du t (Rev. 10/12/12) XALUUUU4 Municipality of Anchorage s , Development Services Department Building Safety Division On -Site Water and Wastewater Program 4700 Elmore Street P.O. Box 196650 Anchorage, AK 99519-6650 www.muni.org/onsite (907)343-7904 Arsenic Advisory Certificate of On -Site Systems Approval # OSC161387 A Certificate of On -Site Systems Approval inspection and test of potable water was recently conducted on the well water supply on Block 1, Lot 5A of South Hills Subdivision. This inspection revealed an arsenic concentration of 12.9 micrograms per liter (ug/L) for the property's well water sample. The Environmental Protection Agency (EPA) has established a maximum contaminant level (MCL) of 10.0 ug/L for public drinking water systems. While private wells are not subject to this regulation, EPA standards are based on existing health information and can therefore be used to gauge the relative quality of water from private wells. Information on arsenic is available from the On -Site Water and Wastewater Program website (www.muni.or onsite) or at 343-7904. This advisory must be attached to all copies of the subject Certificate of On - Site Systems Approval. CD00 o LOT 6 N -i $41'40'16"E 302.88 (R&M) rn m ,0£ OS __ _--_---- 21 6 33.9 107.8 m m I w < < mCf) 0 0 mq m m \J r r I rte., O O �� on " D ➢ < io O o ® GSF O O x o �JJJ O O m N C/) C/) m = < O ' (n 0A 0 O GRAVEL DR IVEWgy C/)I a plD w O C51 pN m " N D A D p m m 2KJ cS m Ir W DO < C8 cg m � I� J,a jI C m m m m z� m 4{ / O C� o 0 o m �n m � I ,0£ S41'26'21"E 304.93 R&M) ,OS LOT 3 N ON N mZ. y Q D' ' �I J A m Om O �y m� m� Z o mo nNN a •• ReZ f �J D- J A N Z _ A -'o zo o Zy0 m s y OOP m z N m o p ••N K }� t• S14 y R v m < 2 / GAY •�i�' V O m • • •� N z 0 /i•r i •��� OFO 's o N / • to 'F .y 0 • : Z Z I W 02 •/ �• 0 to • 1 N •? • ot1 � rn •`wr��r��� titi 2y 4 0 3 aha Fit O O OY n �n y 0��^:�m O m Uw W O O 0 w F,_ 0 7 y Y:r 64 v 5 O O h 3� n m 9 '0Off, G.�Sn 0 Sy w SA W O e v • F+� > 0P.<O �nYSUN • E 7 N D a I N 7aC =�1 'm1 W` p' m ay O �y0o yW o� 0go K m 0 7 N N �0 7D w P. w • 1~.� or OR. �� w m W .., 7 m y Q�cn a, w N m m Z �' Y O'. o0 m ,00..wa o [� d w o 0 = N 0 L I I I I � x I I r I I� � � O f�*1 n U � m � ID/l Z A - O � Z JJ Z A O �.y yD ti� N V m Z Z m A � A � z m m O Z v m � C N ti C m m o z m L MUNICIPALITY OF ANCHORAGE • DEPARTMENT OF HEALTH & HUMAN SERVICES Division of Environmental Services On -Site Services Section P.O. Box 196650 Anchorage, Alaska 99519-6650 343-4744 CERTIFICATE OF HEALTH AUTHORITY APPROVAL FOR A SINGLE FAMILY DWELLING Parcell.D.# 1. GENERAL INFORMATION HAA# 0RsSS0_23-' Complete legal description Lor S 131-k � SOv" O f"S Location (site address or directions) 72 o I I4iLLr iDE wA`l Property owner NFLEN FA NSTROM Day phone 561-2023 Mailing address Bok 110218 1 A NCII 41< "S'' Lending agency Day phone -ZS Mailing address Agent Pa F Crtrr , Realk'v Cen E -el' Day phone 3 � Yy-O5�7 Address ft AAcAoCa � 99So'7 Unless otherwise requested, HAA will be held for pickup. 2. NUMBER OF BEDROOMS: 3 3. TYPE OF WATER SUPPLY: Individual well /— Community well Public water NOTE: If community well system, provide written confirmation from State ADEC attest- ing to the legality and status of system. 4. TYPE OF WASTEWATER DISPOSAL: Individual on-site Holding tank Community on-site Public sewer NOTE: If community wastewater system, provide written confirmation from State ADEC attesting to the legality and status of system. 72-025 (Rev. 1/91) Front MOA N21 t 9 vow Ao"9 MA AOU) -el •i{aom s jaaw6ua jeuolsseloid eql ul suolsslwo ao slam aol alglsuodsaa lou s! e6ejogouy to AlllediolunlN oql •panssl sl aleoipliao a aaolaq elep azAleue io suolloodsui lonpuoo lou oP SHHd jo saaAoldw3 •sluawa.ilnba.i alels pue lejapal uieveo A4slles of iapio ul suoilnlllsul 5uipual dell pue sawog to s iesegojnd of Aselanoo a se slgl saop SHHO aql •eilsely to alelS all ui paaalsl6aa aaaulbua leuoissaload luapuedepul ue iq anoge g gdei6eaed ul uanl6 suo!jejuasaidai all uodn Aluo paseq saleollllaaO lenoaddy Allaoglny glleaH sanssi (SHHd) saolnaaS uewnH pue glleaH to luawlredao a6eaogouy to Al!!edlolunyq aql - NUI.LI1VJ suoilelndlls 6ulnnollol eql gl!m 'swooapaq •swooapaq sluawwoO Ieuolllppv aol lenoidde leuoll!Puoo •pano.iddesla aol panoaddy 3kinIVNJIS SHHd '9 eAnleu6ls s,aaaul6u3 1.5 0PD-:3 0�5 ssaippv SS�auogd 5-)/15 N:)71dOLlh/1 walk;oaweN -uoiloadsui sill jo alep eql uo loolle ul suoileInbai pue 'seoueulp.io 'sopoo alelS pue ledioiunw lie ql!m eouelidwoo ui si walsAs lesodsip jelemalsem ao/pue Alddne aalenn ails-uo aqj 'uolloadsui pue uolle6iisanul Aw woal pue sail; 96eaogouy to Al!ledlolunlN aql woal paulelgo uoilewaolui oql uo paseq jegj /(luanaaglanl I •ulaaaq paleolpul ainlonalslo adAl pue swooapaq to jagwnu aqj aol alenbape pue leuollounl 'ales sl walsAs lesodslp aaleMalsem ao/pue Alddns aalum ails-uo all jell smogs uolleolldde lenojddy Allaoglny glleaH slgl to u01le5llsanu! Aw legj A!laan ! 'rnolaq umogs alep uo!lepllen all to se pue olaaaq paxllle leas Aw /(q pallpoo sy 833NION3 AS NO11O3dSNl dO LN3W31t/lS 'S WATER WELL ADVISORY HEALTH AUTHORITY APPROVAL NO. C -5 During a recent Health Authority Approval on-site inspection and test of the ppable water supply well on Lot Block I of 6el-1- N .I -V Subdivision, the well's productivity was determined to be gallons gallons per minute. The minimum well productivity required by this department (AMC 15.55) is 150 gallons per day per bedroom. On this basis, the minimum well flow requirement for a _ bedroom residence isO,,' gallons per minute. Although the subject well currently meets the minimum well production requirements, all parties concerned are advised that the production capacity of the well may fluctuate and that water conservation measures may be required during periods of low production capacity. Measures which can be taken to minimize the impact of a low production well are: 1. Installation of a storage tank (300 to 500 gallon) to serve as a reserve source during times of maximum water usage. 2. Restriction of noncritical water uses such as, washing cars, lawn and garden watering, etc. 3. Installation of water saving devices on faucets, showers and toilets. 4. Conservative use of laundry facilities and dishwashers. This advisory must be attached to all copies of the subject Health Authority Approval. Municipality of Anchorage O Department of Health and Human Services 16 HEALTH AUTHORITY APPROVAL CHECKLIST Legal Description: LOT 5 ELIC I SOUTH HILLS Parcel I.D. OI i 0631 I A. Well Data Well type PRIVATE If A, B, or C, attach ADEC letter. ADEC water system number Log present (Y/N) Total depth Sanitary seal (Y/N) Date of test Static water level Well flow Pump levell Date completed PRE 1970 Driller VNK Cased to 112 i Casing height 22'r FROM WELL LOG SEPARATION DISTANCES FROM WELL TO: Wires properly protected (Y/N) i/ /r olo m 2 Nitrate < 0- / M1 1Y m n one reg a,, fed( Date of sample: 9! I 91 93 AT INSPECTION FLATTOP TECF SVCS l /0+% 9 3 / rT1 — y rT1 o 3.p.m. O.E 9.p -m. n m I 2 (D �y e Septic/holding tank on lot SO (LEGAL w ; On adjacent lots >100' Absorption field on lot 138 ; On adjacent lots > /00 Public sewer main N.A. Public sewer manhole/cleanout- Sewer service line 60 Petroleum tank NONE OBSERVED WATER SAMPLE RESULTS: Coliform O co ( /r olo m 2 Nitrate < 0- / M1 1Y Other bacteria n one reg a,, fed( Date of sample: 9! I 91 93 Collected by: FLATTOP TECF SVCS B. SEPTIC/HOLDING TANK DATA Date installed 9/70 Tank size 1000 GAL Compartments Cleanouts (Y/N) Y Foundation cleanout (Y/N) tl Depression (Y/N) High water alarm (Y/N) N A • Alarm tested (Y/N) WA. Date of pumping 917/93 Pumper NORTHLAND SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK TO: Well(s) on lot 80 f On adjacent lots > /00 Foundation I t To property line 59 Absorption field 85 Water main/service line r Surface water/drainage > /00 72-026(3/93)'Front CONTINUED ON BACK PAGE C. LIFT STATION Date installed Size in gallons Vent(Y/N) High water alarm level "Pump on" level at Meets MOA electrical codes (Y/N) SEPARATION DISTANCE FROM LIFT STATION TO: Well on lot D. ABSORPTION FIELD DATA On adjacent lots Manufacturer Manhole/Access (Y/N) "Pump off" Level at Cycles tested Surface water Date installed 5/11 Soil rating (GPD/Ft') 0.7 System type BED Length y3 Width 15 Gravel thickness 0.5 Total depth 3.5 '– 5 Total absorption area 649 FJ Cleanout present (Y/N) Y Depression over field (Y/N) N Date of adequacy test 9/1019-S Results (pass/fail) ro sr for 3 Bedrooms Water level in absorption field before test 0 After test Peroxide treatment (past 12 months) (Y/N) NouE 0owrt o F If yes, give date SEPARATION DISTANCE FROM ABSORPTION FIELD TO: Well on lot- �3$ On adjacent lots -;:o loo To building foundation erty line To existing or abandoned system on lot 90` On adjacent lots 1�—' ton I Cutbank > /00 Water main/service line 120 Surface water > 100 Curtain drain NONE 0S 5C- RV n E. ENGINEER'S CERTIFICATION Driveway, parking/vehicle storage area $5 1 certify that l have checked, verified, or conformed to all MOA and HAA guidelines in effect on the date of this inspection. VN YL q t Al�� ✓�{!.( 4 G too.aol? y. �.' Signature �, � �41 L "A " 4 O Y a ': F4�YA 1100.1... -- Engineer's Name l heAJove- T. �A'J.'90(I 9y� Date s2/J yLer» e r 1,S� 1993 THEODOR6 F. a:500RE ,•� ` . y =i' " "e CE-3� 'II9 t u �J l'o 4�V pyo •;�' �'{yi�' HAA Fee $ b .w Waiver Fee $ Date of Payment '73 Date of Payment Receipt Number�7 l% % � Receipt Number- 72-026 (3/93)` Back FLATTOP TECHNICAL SERVICES 14530 Echo St., Anchorage, AK 99516 Ph. (907) 345-1355 WCk-t, YIEI-b ADEQUACY TEST DATA SHEET Legal Description: �,ot5`, 6/0c k 11, SawFh S/D Street Address: 7201 14111stale tcv,r, V WELL LEVEL FLUID Client Name: /-felet, F-Arr Test Date: -9 /to /93 Tested By: C1irr„/ H2O METER NET. CAL WELL LEVEL FLUID Initial Conditions: Float #1 in set " b.t.o. " pipe w. " fluid Float #2 in set " b.t.o. " pipe w. " fluid Float #3 in set " b.t.o. " pipe w. ".fluid Float #4 in set b.t.o. " pipe w. " fluid Water added through: 10 :15, U : 30 666, 79 _-__ 7 ACTION TAKEN TIME H2O METER NET. CAL WELL LEVEL FLUID LEVEL S f -a r t 10:63 291 6'07 0_S6 10:67 10 :10 G Z9 G K9ey _ – 71/ pu"r off 10 :15, U : 30 666, 79 _-__ 7 1 oS 96 Re s! -art pumg ofi to: 4s- 1 o : Sl 667— 70& _ 79 0 161 -22 91 10 -57 - pt e sfurf 11 , 15 11 :3o 70 to/ 0 9V 89 Pure o 11 : 37 732 123 ZY _ 10-5 6 hr1 12:zy 75-J lay 99 H : 30 7 / 2Gy 96 Measured Well Yield = 2'3j! 7o 9a/ ; 0 --!TVP n Adequate for 3 Bdrms 360 � �n Unit Absorption Capacity = Average Absorption Rate = Surge Capacity = Adequate for Bdrms a MUNICIPALITY OF ANCHORAGE L��A a DEPARTMENT OF HEALTH & HUMAN SERVICES pie �j T Division of Environmental Services On -Site Services Section P.O. Box 196650 Anchorage, Alaska 99519-6650 343-4744 CERTIFICATE OF HEALTH AUTHORITY APPROVAL FOR A SINGLE FAMILY DWELLING Parcel I.D. # D 1-7 C63 // 1. GENERAL INFORMATION HAA# V\ P�q\(1Q\n Complete legal description L-o'f 5 6/0cl-c 2 Scccfh *11r S/p Location (site address or directions) 7 20/ Hrlls"oPe 6l ey 4f- Yi9LZ_ Property owner Ceti k. Cyell Day phone 3`1S- &(9 y Mailing address P.O. 60 21 203Do y An_ chon�y e hf< 99SZ0 Lending agency Cr M Day phone 562- 2r8( Mailing address -T"dol- Rd. Anchccoye Ak 99S0-3 Agent Address Day phone Unless otherwise requested, HAA will be held for pickup. 2. NUMBER OF BEDROOMS: 3 3. TYPE OF WATER SUPPLY: Individual well Community well Public water NOTE: If community well system, provide written confirmation from State ADEC attest- ing to the legality and status of system. 4. TYPE OF WASTEWATER DISPOSAL: Individual on-site Holding tank Community on-site Public sewer NOTE: If community wastewater system, provide written confirmation from State ADEC attesting to the legality and status of system. 72-025 (Rev. 1/91) Front MOA #21 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation of this Health Authority Approval application shows that the on-site water supply and/or wastewater disposal system is safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is in compliance with all Municipal and State codes, ordinances, and regulations in effect on the date of this inspection. Name of Firm Servrc..r Phone 3YS- S3— Address l y.S 3 0 EchO AOc horotc -e Ak 99S/6 Engineer's signature ���r� �^� Date G /3/9/ 6. DHHS SIGNATURE Approved for 15 bedrooms. Disapproved. Conditional approval for Additional Comments A4� fit •"� , .w •� lT�•°°w°o•°a••e••°•••se s. e• •� AA'.) °. THEODORE K. ;�AOORE • ai • c C� y n "p -A `V+1/V•n CF. - 3 J••�` ifJ sYN yl Gt'j a /'rolass'sas;'}� bedrooms, with the following stipulations: By JG n-� Date The Municipality of Anchorage Department of Health and Human Services (DHHS) issues Health Authority Approval Certificates based only upon the representations given in paragraph 5 above by an independent professional engineer registered in the State of Alaska. The DHHS does this as a courtesy to purchasers of homes and their lending institutions in order to satisfy certain federal and state requirements. Employees of DHHS do not conduct inspections or analyze data before a certificate is issued. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 72-025(Rev.1/91) Back MOA#21 Municipality of Anchorage Department of Health & Human Services HEALTH AUTHORITY APPROVAL CHECKLIST Legal Description: Ls, Bi 5DuT14 HILLS Parcel I.D. 4017 06'3 A. WELL DATA Well type PRIVAT E If A, B, or C, attach ADEC letter. ADEC water system number N•A Log present (Y/N) N Date completed PRE 1970 Driller UNK Total depth 112' PER 175 NAA Cased to 112 Casing height 22 11 Sanitary seal (Y/N) Y Wires properly protected (Y/N) FROM WELL LOG AT INSPECTION Z O Date of sample: 530/ 91 Collected by: FLATToP 11 �R! o i Date of test c o Q Static water level APPRoK yo u rn w O �{S .-r Well flow 9.p.m. . g.p.m.i Pump level IJNKNownl Z ? LLJ U =� W SEPARATION DISTANCES FROM WELL TO: 3' Septic/holding tank on lot SOr CEGA� AT TIME adjacent lots 7/Oo of On ad j w iNSTAL44T''Oki Absorption field on lot 118t ; On adjacent lots >y0O Public sewer main -7/00( Public sewer manhole/cleanout -7 Public sewer service line > j01) / Petroleum tank NONE OBSERVED WATER SAMPLE RESULTS: Coliform D Nitrate Nr D 4 !i Other bacteria O Date of sample: 530/ 91 Collected by: FLATToP TECH Svcs B. SEPTIC/HOLDING TANK DATA Date installed 9 1-70 Tank size 1000 GAL Compartments NoT Req. AT TIME Cleanouts (Y/N) Y Foundation cleanout (Y/N) OF MSTALIATIO Depression (Y/N) High water alarm (Y/N) N.A. Alarm tested (Y/N) N. A Date of pumping 10 23%9D , .5' /16191 b y )90/0 SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK TO: Well(s)onlot RO On adjacent lots >100 Foundation I To property line 59 t Absorption field 8S Water main/service line r Surface water/drainage i /00 n 72-026 (Rev- 3/91) Front MOA 21 CONTINUED ON BACK PAGE C. LIFT STATION (ll g Date installed Size in gallons Vent(Y/N) High water alarm level "Pump on" level at Manufacturer Manhole/Access (Y/N) "Pump off" level at Cycles tested Meets MOA electrical codes (Y/N) SEPARATION DISTANCE FROM LIFT STATION TO: Well on lot On adjacent lots Surface water D. ABSORPTION FIELD DATA Date installed 51/6 4, 17/ 4/ Soil rating 0.7 (SPD 6:7 System type BED Length 3 Width IS Gravel thickness I Total depth Total absorption area (O 144 G Cleanouts present (Y/N) Y Depression over field (Y/N) N Date of adequacy test NA. NEw SYSTEM Results (pass/fail) N.A. for 3 bedrooms Peroxide treatment (past 12 months) (Y/N) N.A • If yes, give date N• A - SEPARATION DISTANCE FROM ABSORPTION FIELD TO: Well on lot 13 S On adjacent lots 7 Aoo / Property line 2.3 / To building foundation 95 To existing or abandoned system on lot ti 90 On adjacent lots- /oo Cutbank ';;'/00 Water main/service line = 120 ` Surface water _- 7/00 Driveway, parking/vehicle storage area 815' Curtain drain NO 146 oBSER VE b E. ENGINEER'S CERTIFICATION I certify that I have checked, verified, or conformed to all MOA and HAA guidelines in effect 0 the date of this inspection. O t4 Signature ,. TH 0 ° 3� ids ee eYeeeeeeeYeq eee YYYe°Y YEA Engineer's Name T%eo,_e of i=. )`ic_os re Y 00e 00 OY• Ye°e0 Date TQ A e 3, lQ 9/ .THEODORE E. MOORE;° CE -3589 ,+' ,'-' IV �, yy..ee YY v ��4� �••faoa ee°° (� �� HAA Fee $ Date of Payment Receipt Number 72-026 (Rev. 3/91) Back MOA 21 Waiver Fee: $ Date of Payment Receipt Number hiR lgtit04Abf ALFA p4a B� gb'hJiyLn JAnun44 � � GREATER ANCHORAGE AREA BOROUGH Department of Environmental Quality 3330 "C" Street, Anchorage, Alaska 99503 274-4561 Date Received --7Z—/— 7.5 - Time of Inspection O© /�,/�%, Date of Inspection REQUEST FOR APPROVAL OF INDIVIDUAL SEWER & 14ATER FACILITIES FOR 1. Approval requested by: Mailing Address: / mune: 2. Property Owner:,� eD d Phone: .2 7 -. — d ` Mailing Address: T" U• /d/�T)b 'V- /ff% -- i 9 50 � 3. Legal Descr 4. Location: 5. Type of facility to be inspected 6. Well Data A. TypeAl C. Construction 7. Sewage Disposal System: No. of bedrooms B. Depth D. Bacterial Analysis .6"It A. Installed -10-7— 11'9% B. Installer C. Septic Tank: 1. Size/000 2. Manufacturer e ' i D. Seepage Pit: 1. Absorption Area (, )( (, x y 2. Material E. Disposal Field: Total length of lines 8`. Distances: A. Well to: Septic tank G5 1 , Absorption area o Sewer Lines , Nearest lot line ZO'-N n Other contamination B. Foundation to septic tank *9a`✓ ~ 3` , Absorption area w t1O- i C. Absorption area to nearest lot line EQ -034 (1/74) Page 1 of two pages Page 2 of two pages-'Rc,.,,st for Approval of Individual`",er & Water Facilities A Legal -Description Comments Approved 10 — Disapproved Date q /0 7,5 ���"'���"" AprAoval,Valid for one year from date signed Greater Anchorage Area Borough, Department of Environmental Quality DIAGRAM OF SYSTEM I certify that the information contained in this request for approval to be a true ano accurate representation of the subject sewer and water facilities and these facilities are operating satisfactorily. SIGNED Date EQ -034 (1/74) GREATER ANCHORAGE AREA BOROUGH._. Department of Environmental Quality 3330 C St., Anchorage, Alaska 99503 - 274-4561 REQUEST FOR APPROVAL OF INDIVIDUAL SEWER & WATER FACILITIES 1. Type of Inspection: C14RO 2. Property Owner: (f-emc--«- «- Mai -1 ing Address: �C) Zof, 4-199-7, 419SOq Day Phone. 277^ZGO'7 3. Name of Buyer: �JIA VA FHA -DaL-0fL1 % CONY --' LJ E 4 -Ls Mailing Address: Day Phone //�� 4. Name of Lending Institution: NAT'IO,VAL 6ANiL dFALA%KA Mailing Address: Head Office, Anchorage Phone 5. Name of Realtor or Agent: 1U/ A Mailing Address: Phone 6. Legal Description: ,'O -r is- , Z L K_ i , � . H I LL S ;�06 Location: MiLc- 3'/LI 2AGNkT CREEK '2,0A3�, 7. Type of Facility to be inspected :�E-SIDE U LE No. Bdrms. 3 8. Water Supply Type of Supply: Public Utility Individual If Individual, number of dwellings presently served If Individual, depth of well 11-2, 9. Sewage Disposal System Type of System: Public Utility If Individual, date of installation EQ -037 (1/74) 19 Individual (on-site)