HomeMy WebLinkAboutTHE LANDINGS BLK 2 LT 5The Landings Block 2 Lot 5 #020-061-03 Municipality of Anchorage Community Development Department Page 1 of 4 On-Site Water & Wastewater Program 4700 Elmore St. a P.O. Box 196650 Anchorage, AK 99519-6650 a hftp://www.muni.org/onsite •(907)343-7904 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP161217 PID Number: 020-061-03 ❑ New NUpgrade Name: BURNS HOLDING, LLC. ABSORPTION FIELD ■ Deep Trench ❑ Shallow Trench ❑ Bed ❑ Mound Address: 16240 OLD SEWARD HIGHWAY ❑ Other Phone: No. of Bedroom$: sou Rating: TOW Depth from anginal grace: 632-5535 5 4.0 01allil 10 (MAX.) n LEGAL DESCRIPTION Depth to pipe invert hard original gonna: crawl depth benealh rape: 3.0 (MAX) Pe 7 Ft. Subdivision: Block: Lot: Fill addedebow original grade: Grawlluoh: THE LANDINGS 2 5 SEE DWG. 20 own Ip: anger a Ion: _ Gmvelwidin sari Numbmofanee: o6lencebeMeen lines: 2.5 DISTANCES Total absorptionarea: 280 Numbarofhanches: 1 Dist between trenches: - To Septic Absorption Lift Holding Publlc/Pmrdte Fmm Tank Field Station Tank Sewer Linea SQR. FI Well *75'+ *75'+ *75'+ - 25'+ TANK ❑ Septic ■ S.T.E.P. ❑Holding ❑Other Manufemurec Capectly: Surface Water 100'+ 100'+ 1001+ - ANCHORAGE TANK 2500 Gal. Lot Line 5'+ 10'+ 5'+ - N/A Materiel: Numberofcord'unwnle: STEEL 2 LIFT STATION Foundation 5'+ 10'+ 51+ - ManaWdorac ORENCO 24" PUMP VAULT capecirr: —70 Ga. Curtain Drain - *25'+ - - Remarks: PER CONTRACTOR, OLD TANK AND CRIB WERE °Pumpwovelat°Pump 32 oW level at 22 Iighwateralarmac 36 DECOMMISSIONED PER UPC. *WR#OSV161088 **FOUNDATION Pump Make a Menet Eleatual Inspections periomwtl by: DRAIN SEPARATION DISTANCE VERBALLY APPROVED PER 20-OSI-HFF MOA CONVERSATIONS WITH DEB WOKENFUSS DURING CONSTRUCTION PIPE MATERIAL House to tank D3034 Tankto D2665drainfield D3034 Installer ARM SERVICES Drainfield D3034 CO/MT D3034 Inspector GEG, Ltd. BENCH MARK (Assumed elevation) 99'05 Ft Inspection ocetian and Denaaheon: Dates: 1st R/AY201R 2nd R/11/2n1_ 3rd 8!11/2016 4th TOP OF TANK MANHOLE (MH2) ENGINEE SSEAL Community Development Department Approval ''�04 •.••"` '•# Conditional approval: Date: : 0 �...... ..............00 6.cA^°,.. ..A.. • IGa ass 17-I Approved: �'t/VL Date pyo pp.�.1.'.... LICENSE'11, ;;`S; #AECC884 Inspection nepo t 1-1-12.doc PERMIT NUMBER: RECORD DRAWING I N G PARCEL ID NUMBER: OSP161217 020-061-03 I I PER CONVERSATIONS WITH THE HOMEONWER THERE IS A FOUNDATION DRAIN ON THE SOUTHWEST PERIMETER OF THE HOUSE; TO BE CONSERVATIVE, WE HAVE ASSUMED IT GOE AROUND THE PERIMETER OF THE ENTIRE H E; IT SHOULD ALSO BE NOTED THAT THERE WAS NO WATER OBSERVED FLOWING OUT OF THE OUTLET PIPE DURING THE T.H. EXCAVATION OR / INSTALLATION OF THE SEPTIC SYSTEM. /i. ROUTE OF SEWER LINE FROM FCO TO DOUBLE CLEANOUTS IS ASSUMEI IT IS UNKOWN IF THERE ARE MULTIPLE SEWER DBL1 LINES THAT EXIT THE HOUSE. THE CONTRACTOR TIED INTO THE EXISTING SEWER LINE AT THE TANK AND DOUBLE CLEANOUTS WERE INSTALLED. �D/Ug O i N NEW 2500 GALLON STEP TANK - NEW AX -20 PODS NEW 24" ORENCO PUMP VAUL GARNESS ENGINEERING GROUP, Ltd PREPARED FOR: BURNS HOLDING, LLC. I PHONE NUMBER: 632-5535 PAGE NUMBER: 2 of 4 PROJECTILEGAL DESCRIPTION: DRAWN BY: THE LANDINGS; BLOCK 2, LOT 5 L.K.B./D.J.G. TYPE OF WORK: DATE: �, AS -BUILT 8/16/2016 0 LICENSE RII #AECC884 A N SCALE: 1� 1"=40' rt PERMIT NUMBER: PARCEL ID NUMBER: OSP161217 AS -BUILT DRAWING 020-061-03 ELEVATION OG EXISTING GRADE - 98.46-98.86 ELEVATM AT TOP OF TANK = ELEVATION OF INVERT = 9195 DISCHARGE PUMP ELEVATION AT TOP DF MANHOLE - 99.05 ADVANTEX AX20 POD ANCHORAGE TANK 2,500 GALLON S. T. E.P. TANK GARNESS ENGINEERING GROUP, Ltd CIVIL & ENVIRONMENTAL ENGINEERS PREPARED FOR: BURNS HOLDING; LLC. LEGAL DESCRIPTION: THE LANDINGS; BLOCK 2, LOT 5 TYPE OF WORK: AS -BUILT DRAWING PHONE NUMBER: IPAGE NUMBER: ( 907) 632-5535 1 4 OF 4 D.J.G. DATE: 8/15/2016 i� On -Site Wastewater Disposal System Permit MUNICIPALITY OF ANCHORAGE Development Services Department On -Site Water & Wastewater Program 4700 Elmore Road, PO Box 196650 Anchorage, AK 99519-6650 Telephone: (907) 343-7904 Permit Number: OSP161217 Tax Code Number: 02006103000 Work Type: Septic Upgrade Permit Effective Dates: August 04, 2016 to August 04, 2017 Design Engineer: GARNESS ENGINEERING GROUP LTD Subdivision: THE LANDINGS Site Legal Address: THE LANDINGS BLK 2 LT 5 G:3235 Owner/Address: BURNS HOLDINGS LLC PO BOX 778 STERLING AK 996720000 Site Mailing Address: 16240 OLD SEWARD HWY, Anchorage This permit is for the construction of: Y Disposal Field Y Septic Tank N Holding Tank N Privy Lot Size in Sq Ft: Total Bedrooms: IMrtmcnt 65210 5 N Private Well N Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80). 3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either: A. Open and Close on the same day. B. Covered, sealed, and heated to prevent freezing. 00yBV,,610'l • /eco/A L4VAW,'nq iv 5%7ow �ou��Yaftbn Received Issued By: Ixzz Dntra J� Municipality ®f Anchorage ss Development Services Division On -Site Water and Wastewater Program **** VARIANCE/WAIVER REVIEW **** Waiver#: OSV161088 COSA#: Permit#:OSP161217 PID#: 020-061-03 Legal Description: The Landings B2 L5 e, approve, b Engineer: Garness Engineering Group / 1 ZJ shortgatlbn �f0.1✓I. 13maJ Applicant: Don and Lynn Burns Your request for a waiver of the required 50 feet horizontal separation from the absorption field to the excessive slope has been approved. The approved separation distance is 35.0 feet. In addition; the tank, pump vault and drainfield are approved to be 75' from the well. See the engineers letter for mitigating factors. This waiver approval applies to the proposed absorption field only. Any future upgrade to the on-site wastewater disposal system will require all separation distances be met or another approval from this department. ❑ The affected adjacent property owner(s) have been given a 7 day notice regarding this waiver. ❑ Notarized letter(s) of nonobjection have been received from the owner(s) of the affected adjacent property. ® Adjacent properties are not affected by this waiver. ............................................................................... Waiver is Granted: X Waiver is not Granted: Date: g /� Approved by: Name of ReviewjefX ........................................................... .................. **** VARIANCEIWAIVER REVIEW **** ukS'h MUNICIPALITY OF ANCHORAGE Community Development Department Phone: 907-343-7904 Development Services Fax: 907- 343-7997 On -Site Water & Wastewater Program Mayor Dan Sullivan On -Site Sewer/Well Permit Application For A Single Family Dwelling Parcel I.D. 020-061 -03 Property owner(s) DON & LYNN BURNS Day phone 632-5535 Mailing address 16240 OLD SEWARD HIGHWAY *ANCHORAGE, AK 99516 Site address 16240 OLD SEWARD HIGHWAY *ANCHORAGE, AK 99516 Legal description (Sub'd, Block & Lot ) THE LANDINGS; BLOCK 2, LOT 5 Legal description (Township, Section & Range) Lot Size ❑ APPLICATION IS FOR: ( ,all that apply) ❑ Absorption Field Septic Tank Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage ❑ Sq. Ft. Number of Bedrooms 5 APPLICATION IS AN: Initial ❑ Upgrade Renewal ❑ TYPE OF DEWELLING: Single Family (SF) (w/wo ADU) Duplex (D) ❑ Multiple Dwellings ❑ (SF and/or D) THIS APPLICATION INCLUDES A VARIANCE/ WAIVER REQUEST FOR: STEP TANK, PUMP VAULT, & DRAINFIELD TO WELL; 7_5' 75' 79- DRAINFIELD TO SLOPES >25% Distance: ��� 35' I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal codes. GARNESS ENGINEERING GROUP, Ltd. (Signature of property owner or authorized agent) Permit/Rush Fees:1�54 5 f76/9'. Za Ef�ZoWaiver Fees: k'/lZe' Date of Payment: F -/'-16 Date of Payment: 8`1-16 Receipt Number: aq5_? Receipt Number: o9S64 Z'V Permit No. 0 Z�� Waiver No. (���(6`(,-0�r=f (Rev. 01/11) - 5Ko ` Nuan ce GARNESS ENGINEERING GROUP, Ltd ......... " CIVIL & ENVIRONMENTAL ENGINEERS _. August 2, 2016 (Revised) Municipality of Anchorage Development Service Department On -Site Water & Wastewater Program 4700 Elmore Road Anchorage, AK 99507 Ref: Proposed Septic System Upgrade for The Landings; Block 2, Lot 5 To whom it may concern: The existing 5 bedroom house is served by a private well and septic system. The Grainfield is in a state of failure and needs to be upgraded. We are proposing to install a new 2500 gallon STEP tank, a 24" Orenco pump vault, two (2) AX -20 pods, and a deep trench type drainfield. One testhole was excavated on the property and the drainfield is designed around the 30 foot radius of this testhole. Comments regarding the design are summarized as follows: 1. SOILS: See the attached 2016 soil log which shows the soil classifications, groundwater monitoring, and the percolation test results. 2. DRAINFIELD DESIGN: See attached design drawing for drainfield specifications. 3. SURFACE WATERS: There are no surface water concerns. 4. TOPOGRAPHY & SLOPE WAIVER: As can be seen on the attached design and profile drawing, the drainfield is approximately 35 feet away from slopes >25%. We are requesting that your department issue a variance from the required separation distance of 50 feet to 35 feet. Justifications for granting this waiver are as follows: • We will be using CAT III advanced treatment system, so the effluent quality will be much greater than that of conventional treatment. • With the use of advanced treatment, the system will be remotely monitored and have a maintenance agreement. If the system were to become surcharged the service provider would be notified and corrective action taken. • The existing drainfield is approximately 5 feet from slopes >25% and no daylighting was observed by GEG during our site visit on 7/21/2016 and 6/16/2016. • The existing slopes are vegetated. • See the attached waiver drawing (page 4 of 4) which indicates that at a 25% 3701 East Tudor Road, Suite 101 "Anchorage, Alaska 99507-1259 Phone: (907) 337-6179 * Fax: (907) 338-3246 * Website: www.garnessengineering.com Page 2 of 2 slope, 2.5 feet above the invert of the lateral, daylighting would not occur within 50 feet. 5. SEPTIC SYSTEM COMPONENTS TO WELL WAIVER: As can be seen on the attached design drawing, the proposed STEP tank, pump vault, and drainfield are approximately 75 feet away from the well. We are requesting that your department issue a variance from the required separation distance of 100 feet to 75 feet. Justifications for granting these waivers are as follows: • Anchorage Tank places a specialized coating (Chemthane 4200) on their Advantex tanks to prevent rusting, this tank will have this coating on it. • We will be using CAT III advanced treatment system, the effluent quality will be much greater than that of conventional treatment. • With the use of Advanced Treatment, the system will be remotely monitored and have a maintenance agreement. If the system were to become surcharged the service provider would be notified and corrective action taken. • The existing drainfield has an existing encroachment to the well and recent water samples (6/16/16) indicate no apparent adverse impact on the aquifer (nitrates ND). • The house is between the well and the proposed septic system components (well is in the house). We are unaware of any adverse impacts this installation and waivers would have on adjacent wells or septic systems. If you have any questions, please contact us at 337- 6179. Thank you for your assistance. Sincerely, P. E., M. S. 3701 East Tudor Road, Suite 101 *Anchorage, Alaska 99507-1259 Phone: (907) 337-6179 * Fax: (907) 338-3246 * Website: www. garnessengineering.com GARNESS ENGINEERING GROUP, Ltd CIVIL & ENVIRONMENTAL ENGINEERS August 9, 2016 Municipality of Anchorage Development Service Department On -Site Water & Wastewater Program 4700 Elmore Road Anchorage, AK 99507 Ref: Proposed Septic System Upgrade for The Landings; Block 2, Lot 5 To whom it may concern: Per conversations with the homeowner, there is a foundation drain located on the southern portion of the house. The line outlets to the southern portion of the lot onto the steep slopes. We are requesting that your department waive the required separation distance of 50 feet from drainfield to foundation drain to 25 feet. It should be noted that no water was coming out of the outlet pipe during our inspection on 8/8/2016. Justifications for granting these waivers are as follows: We will be using CAT III advanced treatment. The effluent quality will be much greater than that of conventional treatment. The soil percolation rate was 2.5 min/inch. Given the percolation rate, it is likely that the effluent will travel vertically. Rather than horizontal to the north. There was no water running out of the foundation drain outlet pipe during our site visit. We are unaware of any adverse impacts this waivers would have on adjacent wells or septic systems./If you have any questions, please contact us at 337-6179. Thank you for your assist e. P.E., M.S. 3701 East Tudor Road, Suite 101 *Anchorage, Alaska 99507-1259 Phone: (907) 337-6179 * Fax: (907) 338.3246 * Website: www.garnessengineering.com DESIGN CRITERIA: NUMBER OF BEDROOMS: 5 GALLONS PER DAY (GPD): 750 PERCOLATION RATEIS: 2.5 minlinch PROPOSED APPLICATION RATE: *4 MINIMUM DRAINFIELD SQ.FT.: 188 FEET' 'CAT III SYSTEM DRAINFIELD DESIGN: MAXIMUM DEPTH: 10 FEET MAX WIDTH: 2.5 FEET LENGTH: 20 FEET M.O.A. APPROVED SAND FILTER: NIA EFFECTIVE: 7 FEET REDUCTION FACTOR: NIA ACTUAL SOFT.: 280 FEET' SHALL HAVE THE EAST LOT LINES, AND ALL WELL RADII 7LAGGED BY A REGISTEREC LAND SURVEYOR PRIOR TO 50% LOCATION OF CUI TO SLOPES >25% WE ARE PROPOSING TO REBUILD THE PROPOSED DRAINFIELD IF IT WERE TO FAIL. NO ALTERNATE SITE IS SHOWN. vc GEG, Ltd. HAS A 8 PAGE SPECIFICATION LETTER THAT PERTAINS TO THIS DESIGN. TO OBTAIN A COPY OF THE LETTER CONTACT G DEG. BY PROCEEDING FORWARD WITH THIS INSTALLATION, THE ENGINEER, WELL DRILLER J� CONTRACTOR AND PROPERTY OWNER AGREE e THAT THEY HAVE READ THESE • : O/7 SPECIFICATIONS AND AGREE TO ACCEPTTHEDRVEWAY 5 TERMS AND CONDITIONS OUTLINED. a JPX t 00 FOOT RADIUS EXISTING 5 BEDROOM HOME IPO p) PAD AX`20,TDS CQ�, STALL DOUBLE CLEANOUTS PROPOSED 2500 GALLON STEP TANK T APPROXIMATE LOCATION OF EXISTING SEEPAGEPIT TO BE DECOMMISSIONED PER UPC EXISTING SEPTIC TANK TO BE COMMISSIONED ° PER UPC 5 15%CO I°150/(o ox Ir50° APPROXIMATE LOCATION OF TRANSITION FROM 1.25' PRESSURIZED THE LANDINGS, UNE INTO 4" BLOCK2,LOTS GRAVITY FEED LINE APPROXIMATE LOCATION - CUTTOSLOPES >25Ma — PROP�dSED HN7 ORAIf1FIELD � —I - 3S WAIVER REQUEST SEP�dC- AF,2E GARNESS ENGINEERING GROUP, Ltd CIVIL & ENVIRONMENTAL ENGINEERS 3701 E TUDOR ROAD. SUITE 101 ANCHORAGE, AK99507'PHONE (907) 3376179- FM(907)330.3246'WEBSITE_vn>w_galnaSsx.W..... aom PREPARED FOR: PHONENUMBER: PAGE NUMBER : DON & LYNN BURNS 632-5535 2 OF 4 PROJECT/LEGAL DESCRIPTION: DRAWN BY: THE LANDINGS, BLOCK 2, LOT 5 PNB/DJG TYPE OF WORK : DATE: � SEPTIC SYSTEM DESIGN UPGRADE REVISED 8/2/16 'fPOFESS\ �� AX20 - Mode lb GARNESS ENGINEERING GROUP, Ltd CIVIL & ENVIRONMENTAL ENGINEERS 3701E TUDOR ROAD. SUITE 1C1' ANCHORAGE, AK 99507' PHONE (967) 3376179' FAX (907) 33832J6 `WEBSITE .gzrnessengmeanng,ccm PREPARED FOR: PHONE NUMBER: PAGE NUMBER: DON AND LYNN BURNS 632-5535 3 OF 4 PROJECTILEGAL DESCRIPTION: DRAWN BY: THE LANDINGS, BLOCK 2, LOT 5 PNB TYPE OF WORK: DATE: � ADVANTEX DETAIL 7/28/2016 0 LICENSE #AECC884 ?ROFESS10N:i GARNESS ENGINEERING GROUP, Lid. CIVIL & ENVIRONMENTAL ENGINEERS 3701 E TUDOR ROAD. SU I TE 101'ANCHORAGE, A N 93507` PHONE TM713375179' FM(907)3333246'YDEBSITEwmv.9emvsenBlneamgrom SOIL LOG - PERCOLATION TEST LEGAL DESCRIPTION: THE LANDINGS; BLOCK2, LOTS PERFORMED FOR: DON & LYNN BURNS DATE: 7/21/2016 ULH (feet 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 TEST HOLE #1 DATE ORGANICS/LOAM SOIL CLASSIFICATIONS 7/21/2016 GW _- ORG GP ML GM CL GC OL 3 MH ': �'• : SP CH SM ,' ON Sc 6" GW DEPTH TO GROUNDWATER DATE DRY 7/21/2016 DRY 7/2212016 DRY 7/28/2016 2 - 13.18 SITE DATE READING CLOCK NET TIME TIME (MINUTES) WATER LEVEL READING NET DROP (INCHES) 7/23/2016 1 - - 6r' " 2 - 13.18 Orr 61r 3 6" 4 - 14.48 Orr 6" 5 61, 6 - 14.95 Orr 6rr 7 6rr 8 - 15.05 Or' 6" PERCOLATION RATE 2.5 (MIN./INCH) PERC. HOLE DIA. TEST RUN BETWEEN 6 FT. AND 7 FT. A FOUR HOUR PRESOAK VVAS PERFORMED: E YES ❑ NO 6 (INCHES) SOILS LOGGED BY: DAVID GARNESS PERCOLATION TEST PERFORMED BY: LANDON BRUCE COMMENTS: PERCOLATION READINGS ARE WITHIN 1/16 OF INCH. PERFORMED BY GEG, Ltd. I, JEFFREY A. GARNESS, CERTIFY THAT THIS WAS PERFO��EDI ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE: ' �2�' fL Municipality of Anchorage Page f of DEPARTMENT OF HE=ALTH AND HUMAN SERVICES ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, Alaska 99519-6650 • Telephone: 343-4744 On -Site Wastewater Disposal System and/or Well Inspection Report Permit Number: 970y/e7 — PID Number: _O20067t03 Name: - Wastewater System: ❑ New N Upgrade Address:/ fJ L ? yo a(a 'e�va� lam_ ABSORPTION FIELD Phone: � No. of Bedrooms: ^596 el, ,S'2 2 _ ❑Deep Tren ❑Shallow Trench ❑Bed ❑ Mo d ❑Other LEGAL DESCRIPTION Soil Rating: Total Depth m original grade: Lot: Block: Subdivision: Depth to pipe bottom from original gratle: vel depth beneath pipe Jr- he l and/n Ft. Township: Range: Section: Fill added above original gra Gravel the Ft. Ft. WELL: g:xtsr ❑ New ❑ Upgrade Gravel witlth: Number of lines: stance between lines: Ft. Ft. Classification (Private, A,B,C): Total Depth: Cased To: Total orption area: Pipe material: Ft. Ft. _ Driller: Date Drilled: Static Water Level: Ft. Installer: Cart :r Enca� a Nrn Date Installed: 7/ / / 9e _ Yield: Pump Set at: Casing Height Above Ground: TANK GPM I=__ Fl. SEPARATION DISTANCES W Septic ❑ Holding ❑ S.T.E.P. To Septic Absorption Lift Holding Public/Private Manufacturer: Capacity in gallons: From Tank Field Station Tank Sewer Lines 4,)GI ,�,, elk �21Q Well ' 66 /wee%re Material: �r Slee I Number of Compartments: 2 Surface_ Water 100 ' s STATION N•i}, Lot °I0, _ Size in gallons: _LIFT ___ Manufacturer. Line Foundation _ "Pump on" level at: "Pump off ' level at: High water alarm at: I� Curtain Pump Make &ModelT Electrical Inspections performed by: Drain Remarks: _�+ntr )nr%t((cd 4:Cf.-- BENCH MARK Location and Description: rU ✓4r� jo e-,wlt. war vtr Con e re Ae f res h0(elCR 6L /v}9 ranI-oa t21g/97 Ql(aci/n AnIrIOI.r GCca _ Elevation: /Assumed -Jv lie dl' _ Lem [.tee/(. ��� / Oa . 0 Ft ENGINEER'S SEAL Inspections performed by: _le1-1ve Tpc/Svc Dates: 1st 2nd ✓, Department of Health and Htaman Services approval Reviewed and approved by: Al/. Date:$ 72-013 (Rev. 9/91) MOA 25 LU I S FLOCK PERMIT NO: 970410 PAGE 2 OF 2 \ PID NO: 02006103 EXISTING WELL i rn SWING TIES: HOUSE FROM: COR. "A" COR. "B" „B h £ S TO: FDN. C.O. "C" 8.5' 24' "A" S.T. C.O. "D" 14' 31' TBM- S.T. C.O. "E" 22' 39' NEW 1250 GALLON o "D" -- -" _ SEPTIC TANK p "E" _SHED DOUBLE C.O.— EXISTING ------ 12' X 12' LOG CRIB PLAN VIEW SEEPAGE PIT SCALE: 1" _= 30' GROUND ELEV. 98.9' FROM �– _ �_ L_U_ HOUSE F:19NV. INV. / 1250 GALLON 94.3' SEPTIC TANK 4.1' PROFILE VIEW SCALE: 1" = 5' mon r oi"/ MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND HUMAN SERVICES P.O. BOX 196650, 825 "L" STREET, ROOM 502 ANCHORAGE, ALASKA 99519-6650 PAGE 1 OF 1 ON-SITE WASTEWATER DISPOSAL SYSTEM (UPGRADE) PERMIT PERMIT NUMBER:SW970410 DESIGN ENGINEER:FLATTOP TECHNICAL SERVICES OWNER NAME:JARRELL JAMES C OWNER ADDRESS:16240 OLD SEWARD HWY ANCHORAGE, ALASKA 99516 PARCEL ID:02006103 LEGAL DESCRIPTION: THE LANDINGS BLK 2 LT 5 LOT SIZE: 65210 (SQ. FT.) NUMBER OF 13EDROOMS: 3 THIS PERMIT: 3 THIS PERMIT IS FOR THE CONSTRUCTION OF: SEPTIC TANK SYSTEM ALL CONSTRUCTION MUST BE IN ACCORDANCE WITH: DATE ISSUED:12/05/97 EXPIRATION DATE:12/05/98 1. THE ATTACHED APPROVED DESIGN. 2. ALL REQUIREMENTS SPECIFIED IN ANCHORAGE MUNICIPAL CODE CHAPTERS 15.55 AND 15.65 AND THE STATE OF ALASKA WASTEWATER DISPOSAL REGULATIONS (18AAC72) AND DRINKING WATER REGULATIONS (18AAC80). 3. THE ENGINEER MUST NOTIFY DHHS AT LEAST 2 HOURS PRIOR TO EACH INSPECTION. PROVIDE; NOTIFICATION BY CALLING 343-4744 ( 24 HOURS ) . (NOT REQUIRED FOR WELL ONLY PERMIT) 4. FROM OCTOBER 15 TO APRIL 15 A SUBSURFACE SOIL ABSORPTION SYSTEM UNDER CONSTRUCTION DURING FREEZING WEATHER MUST BE EITHER: A. OPENED AND CLOSED ON THE SAME DAY B. COVERED, SEALED AND HEATED TO PREVENT FREEZING 5. THE FOLLOWING SPECIAL PROVISIONS. SPECIAL PROVISIONS: RECEIVED BY ISSUED BY: fDATE: Ay - DATE: l -,� -- rrLcu run Ht:I.VHU IME HEUUEST OF: WHEN RECORDED RETURN TO: Name TrrpnsAla Address 400 N City, State, Zlp 'THIS SPACE PROVIDED FOR RECORDER'S USE: SPECIAL POWER OF ATTORNEY KNOW ALL MEN BY THESE PRESENTS, that Jam24 C. Jarrell,_ ties made, constituted and appointed, and by these presents does make, constitute and appoint .Juseephine Utic his/her true lawful attorney-in-fact for and in his/her place and steed and for his/her use and benefit concerning: Lot IS, Block 2, THE LANDINGS according to the officlal Plat thereof, filed under Plat No, 09.37, records of the Anchorage Recording District, Third Judicial District, State of Alaska. lasting until fe'S 2-? / 5' 8 , so as to ask, demand, sue for, recover, collect and receive all such sums of money, debts,- % dues, accounts, legacies, bequests, interests dividends, annuities, and demands whatsoever, as are now or shall hereafter become due, owing, payable or belonging to him/her, and to have use and take all lawful ways and means in his/her name, or otherwise, for the recovery thereof, by attachments, arrest, distress or otherwise, and to compromise and agree for the some, and to make, sign, seal and deliver acquittances, or other sufficient discharges for the some; far him/her and in his/her name, to bargain, contract, agree for, purchase, receive and take lands, tenements, hereditaments, and accept the seisin and possession of all lands, and all deeds, and other assurances in the law therefor; and to lease, let, demise, bargain, sell, remise, release, convey, mortgage and hypothecate lands, tenements and hereditaments, upon such terms and conditions and under such covenants as he/she shall think fit; to assign and transfer any note or mortgage; to dedicate any street, avenue, alloy, place, way or park for public uses. ALSO to bargain and agree for, buy, sell, mortgage, hypothecate, and in any and every way and manner deal In and with goods, wares and merchandise, choses in action and other property, in possession or In action, and to release mortgages on lands or chattels, and to make, do and transact all and every kind of business of what nature and kind whatsoever. AND also for hlim/har and in his/her name, and as his/her act and deed, to sign, see], execute, deliver and acknowledge such deeds, leases and assignments of leases, covenants, Indentures, agreements, mortgages, hypothecations, bottomries, charter parties, bills of lading, bills, bonds, notes, receipts, evidences of debt, releases and satisfactions of mortgage, judgment and other debts, and such other instruments in writing, of whatsoever kind or nature, as may be necessary or proper in the premises. GIVING AND GRANTING unto his/Iter said attorney full power and authority to do and perform all and every act and thing whatsoever requisite and necessary to be done in and about the premises as fully to all Intents and purposes as he/she might or could do if personally present; and by signing hereunder confirming the above. I CERTIFY that James C. Jervell __ before ma and sign the foregoing document ft thereln on day of rrt STATE DF DICIAL DISTRICT �Q.tiGj U.I P/L CDU. l'7 Jamas (:. roll did appear for the stated purposes and reasons set forth Notaiilc 0V My commission exoires a i 0 R lrC" l -'Rol1 xT o, t�?�'„ l���i � f� �'; r4 r Department of Health and i-lumara Services 825 " L' Street Rick Mystrem' Mayor P.O. Box 196650 Anchorage. Alaska 99519-6650 343-4744 December 8, 1997 Ted Moore, P.E. Flattop Technical Services 14530 Echo Street Anchorage, Alaska 99516 Subject: Waiver Request for Lot 5 Block 2 The Landings Subdivision Waiver Request #WR970074, PID 11020-061-03, SW970410 Dear Mr. Moore: Your request for waiver(s) of the required 100 foot horizontal separation of an on-site wastewater disposal system to a private well has been approved. The approved separation distance(s) are a private well to the new septic tank of 65 feet; and, private well to the existing seepage pit of 88 feet. This waiver approval applies to the existing on-site wastewater disposal system to well separation only. Any future upgrade to either will require all separation distances be met or another approval from this department. If there are any further concerns or questions regarding this waiver, please call our office at 343-4744. Sincerely, r Daniel J. Roth Civil Engineer On-site Services Program ljin: #6 MUNICIPALITY OF ANCHORAGE Department of Health and Human Services On-site Services Section Waiver Review Worksheet WR# _j R970074_ PID# 020-061-03 _ HA# Permit # _ Date Received: November 12, 1997 Legal Description: Lot 5 Block 2 The Lands _ Engineer: Ted Moore,—P.E_, 1'iahtop Technical Services 14530 Echo Street, Anchorage, Alaska 99516 Applicant: Jim Jarrell=-- -- Waiver Requested: Private we:Ll to new septic tank of 65 feet., private well to existing seepage pit of 88 feet Criteria 1. Geology: Points: A. Water Table B. Soil Sorption C. Permeability D. Water Table Gradient E. Horizontal Separation TOTAL, • -- 2. Special Conditions: — 3. Other: - ----------- Waiver is Granted: _� Waiver is NOT Granted: List Conditions or Reasons for above: �'EE 1977-i9(M5.0__ Date: 4-97 __ By: j9l,�/V — Name of Reviewer Rec #: 03296/4678 Amount: $ 920.00 Date Paid: November 12. 1997 OOJ I➢A wf}lvET2 lfEqu Esr W tors o3 ouc ?_ i//E L71/v7iIvGS Su 6D. WANF56 /?f=quE5r Ivt4lwoER wR970074 VRIVF-R Rfgt4F5T FOM 0,V -LOT Iv Etl, ro 5EPTIC 'rgvk or (,�F-FEEr ✓)NVO 88 FEET 'r0 :M!P4612 PIT, 5 APTIC H/f roR Y— rHC- Su®f-Ecr SrEPr/c Sy'SrEm L. &jr CON:r7Wk[7W0 IN JunuL. of /972. T</F w W$f NOT IN PLACE Arros r/M6 OF CONJTRu[T)ON OF iME WNfTL°tvATfle SYSTEM, Th I�AJT)WYPraR SY1rEM IN LOC/%rev Oauwko1nnp/ENr )znom r/KI- I -P -LL /N RL<EJ1 ON A V,+nY/nub x/ Opp OF r- lO 010, rhCE XOIL. f TME 0.. /¢fT'EG.gTE/e frXrE /1 (ONf)'liU CrKO Iry A-4-4 W/rH XO, F S/tr. rl4/f ree& or- Sol,- OFL=14 r2S %$%2Y II76M wMf r'E <vA rEIQ 7-l2ElgrMB/vr CPLr 1+//r/ES. rNF: 1..6LL /N t?"Efrjow -W/T-f PRILL,80 WITHO"r spNP_F/r OR ✓C penmIT. 1`; <f pLLE064-P TO lgl*vB PEIFN PIML.FJ 1-v 1%72, r'ICN CRIA GvNf R�llu /Rd/✓ TD I?E loo ' .4r rI-rlf rli r. /A/t.n ,i0' freers )LCE sSDr/c iAule. THE I1641, r//rJ 0401E P* OVA[? 6t) T -O 8E A'r L EA -f r 1.i FL`IK r Pe, Al, tWORL' /3 NO 6. 6LL t OGS AIOwA-/& rgLIE Ror RR F_ wY-LL Le61 NEARpy/ ro ve USED rOR TME' Pu/?9o>EJ of ;F/Lf/.f u.A-l-o R15a-Lr5r. THE t Fi o am rFCF f 0"7W(wbsr 1IGE or- r/re 04.0 T gv,MV N/oHL-AY /FwNSA? r -o ENc, p60R06k fT/FRrt&6 /Fr rl-<F NOft7'MIERlr Lor A7- ¢0' Af'W 1.04/.-1a6 'ro";," 7-0 rfcE fu BJ -PCT" LOT Ar 80 PEE); rff/.f /NL/eENTING QHF!'F( OF OF OBDROC.0 IfOUW& PIP oc F_ t✓PLL Y61w4,vpf T7 -CN_ t.6irrF_WR-rigK Jijra- ON Trac JLtp,rCr ALONG Nlrf.t T/2F_ rq Jf Fr4-CE Y 1LOO/NL PRO. TSTE 1-I54L 7'-I'eE W01'TEt rr;rr-... /-+AI153 F0/? A- FFYV URI DL {i: ('0NG7T/ON TMcs t„FLL rl-1,+7NO PACrEIZIA k[x/fTf ALPP NO N/rtP/}7-61 ARE OErI--C rM0<f.- NO WELL L 06 S lIV TME f%RE,% IPEPORT 1¢Nr t<.)MCR FNCUuv7-&,?,9,0 IST 74/,E SO/ COS/)'TET /e I,OfWlfor-k INT-e)?rnL-1 /v FI9c7-/P NMA l4P,PORrCV ry FxIJr P/et0/e TO 05PRoc&, Lc.v 7'Rde 5 of A. D. C. -C.-5oD. /�aiNrs JMfiTFR THO — 9R z 80'-!�'CKIB nerrH ,', 70'wares Thalf�E5— 30 )e 7+ -so S,7 SOL SORD ria N rr (70)i 5fi( 70/6 �170)� r 3.51 ,, z P�nk��•v � �. � r�' 70) 70 * 6,V/ tv,9rER TffvcE 6oViruvr Af.lq"e fovs5/rvRrivF_ 0 2 9 HOI?I ZONr&L. .SEVRRg 7'ronJ 6ti _ "— x�_,6�I L6 ar _ !r 6 RIWO 7-a rA /6. Z CO,v(Gulia,v 6(z#N7- b.)9)v€,p PARK l[ti®w•sl>; ,& ANcimonAco, AAIr.A onA a4146m'Ei71 b SIX INCH WAT.-R WELL DRILLED AND CASED OUT TO THE DEPTH OF 330 Teat. DRILLED AT THE TE OF 978.00 PER FOOT. PROPERT,Y,OWNER LOCATION OF WELL Ron. lb4heA 344•-8778 Lt. j Qtk. sub. DRILLER BeAn to GLcuh o._ RampaAt DAtittnq, Ookk4. WELL LOG: 0---_.?�1 SA.l,ty. rAnat rr�,th 3.0%-ldltct 23---•4�i/dnnn._ .Sofro/lnA. GaArlrAp 45----781 —Sdt4p qf7.aaeL, 4006 78----60' CAeen.+.tonQ_ A drh.okev,_.-dAde�ntL 760-••2751 A 4e,' a& na 275-••3061 •Serlimen �t 2ack-.-- — P=e. To-taL wate�t 4 ta:td in, ctu, i y 4houtd 4how to at d ear tet of- 4u�ace. A.t ,the )tate of 7.6 ca)4 pelt loot. Pump. 4houtd be- .ia4-taUe.d ,to 70 deet. Tata- coot of- )Mt LUaq: Chw4e, on,ty, la/t 220 Teet of- D)a U bi9-: $3960.00 COST INCLUDES ALL LABOR AND MATERIAL FOR COMPLETION OF SAID DRILLING. WRITE CHECK PAYABLE TO RAMPART DRILLING WORKS FOR THE SUM OF ,c3Q60 0n THANK YOU VERY MUCH. IE CLAUS OF RAMPART DRILLING WORKS DATE gubk 2ltd, 78 (1 SERVICE CHARGE 0P 1Y.% PER MONTH WILL E3E ASSESSED ON PAST DUE ACCOUNTS. 14,7� —A, KT -It- LUC 120, f3ly E� �� t clJolloll Ak 0ff%1 �d C'AvTt-k �AnrJ�I,vGS 5'v/gip. )-a a) -)w 33 - G) p `r c i jgy vi- (,)lA i b t ,i G l A/ - /)i4)A.)) ') klPI A7-- CA3)-e(I 4/ R ' `r I I 6, RA) , MUNICIPALITY OF ANCHORAGE DEPT. OF HEALTH & ENVIRONMENTAL P OTECTION OCT 2 7 1931 RECEIVED 0 N T m o N U) m _m w J O CD CD C) o v C 9 (p Ndz A ZN� 0 a1 F=5® R" �. > m� 3 m 0 —v�3: G0 70 0 I 7 0 m N a C) 0 � d O a O V L F," CIVIL & ENVIRONMENTAL ENGINEERING • ENERGY CON: ERVATION & ANALYSIS THEODORE P. MOORE, P.E. 14530 ECHO ST. PH: (907) 345.1355 November 12, 1997 ANCHORAGE, ALASKA 99516 M.O.A. DHHS P.O. Box 19-6650 Anchorage, AK 99519 Dear Sirs: The purpose of this letter.is to provide the required design narrative in support of our application for a permit to replace the existing septic tank serving the residence on Lot 5, Block 2, The Landings S/D. In order to do so, we will also need a waiver allowing the new tank to be located within 65 feet of the private well serving the lot and allowing the existing seepage pit to remain in its present location which we calculate to be as close as 88 feet from the well. A site plan, construction specifications, water sample test results, and copies of relevant documents from DHHS files are enclosed for your review. The proposed replacement tank will be located southeast of the present tank in the approximate location shown on the site plan. The topography of the lot in the area of the septic tank and existing seepage pit is a bench which slopes towards the southwest at approximately 5-10%, with steeper slopes above and below. The proposed project will have no significant impact on present or future water supply and wastewater disposal systems serving adjacent properties, nor will it have any significant impact on reserved space -surface and subsurface, or on drainage. I was unable to locate a driller's log for the well serving this lot, however according to other documents on file at the Health Department it was probably drilled in the summer of 1972. A notation on the inspection report for the sewage disposal system indicates that the well depth is 145 feet, however during a recent adequacy test I measured the pump intake to be 154 feet below the top of the casing. On November 7, 1997 the static water level stood at 24.5' below the top of the casing, which equates to approximately 23 feet below ground level. A flow test that we conducted on October 28, 1997 showed the yield of the well to be 2.0 gpm. Water samples collected on that date were satisfactory, showing 0 coliform or other bacteria per 100 ml., and non-detectable nitrates. I was also unable to locate well logs for either of the adjacent lots on the west side of the Old Seward Highway, but the well serving Lot 4 (drilled where the ground is approximately 30 feet higher) is reported to have a depth of 186 feet. According to the owner of Lot 6, that well is also approximately 160 feet deep. A log for the well on Lot 7, Block 1, of The Landings (located several hundred feet away across the Old Seward Highway) is enclosed. The depth of this well is reported to be 51 feet, so data from it may not be particularly relevant to the lot under discussion. According to the as -built inspection report, the wastewater disposal system serving Lot 5 was sized for 3 bedrooms and was installed in June of 1972. The system consists of a 1000 gallon steel septic tank which discharges into a 12' x 12' x 6' deep log crib seepage pit. The required separation distances at the time of installation were 50 feet from the septic tank to the well and 100 feet from the seepage pit to the well. A HAA form prepared in 1987 reported the actual distances to be 65' and 100' respectively. According to my field measurements, coupled with an estimate of the underground configurations of the components, it appears that the actual distances from the well to the closest portions of the existing septic tank and seepage pit are 60 and 88' respectively. Thus, a waiver is also needed in order to obtain HAA approval of the seepage pit. On October 28, 1997 I conducted an adequacy test of the wastewater disposal system. Since the house had been vacant for a month prior to the test, I arranged for a water delivery to pre-soak the seepage pit. The initial fluid depth in the seepage pit was 8.5 inches, and the addition of 2100 gallons of trucked water caused the fluid depth to rise another 40.375 inches. I then was able to measure the absorption rate by adding another 690 gallons of water from the well over the course of several hours. These measurements demonstrated that the seepage pit is still able to absorb water at a more than adequate rate for a 3 -bedroom residence. The existing septic tank has a cleanout only on the second compartment and there is a significant obstruction in the outlet line from the tank. Since the tank is now over 25 years old, it seemed futile to try to repair these deficiencies; hence this permit application. In the absence of a relevant well log, it is necessary to make some assumptions regarding the underlying soil conditions. With the static water level in the well approximately 23 feet below ground surface, this could be construed as the depth to groundwater. On the other hand, the fact that the well was drilled to a depth of over 154 feet indicates that the aquifer being tapped by the well is at least 154 feet below ground level and must be confined by overlying strata of impermeable material. The fact that both the well and the septic system have been in place for over 25 years, and the water samples still show 0 coliform or other bacteria and non-detectable nitrates, is pretty good evidence that the proximity of the septic tank and seepage pit to the well will not lead to contamination of the well. Replacing an old, rusted out septic tank with a new tank located further from the well can only make the present situation better. There are no wells downhill of this septic system, as the lot abuts Potter Marsh. The following is a breakdown of how waiver analysis points could be assigned using DEC's 1985 "Separation Distance Waiver Guidelines for SCRO". Category Points Distance to water table - 13' (or 144', if bottom of casing used) 1.55 (or 7.23) Soil Sorption (assume clay and sand equal) 4.5 Permeability (assume pert rate > 50 min./inch) Water table gradient (assume +10%) Horizontal separation (65' to tank, 88' to seepage pit) 1.6 (or 2.52 to pit) Total points 16.65 Based on this point assignment it appears that the requested waiver can be safely granted without concern as to contamination of the well from these septic system components. Please give me a call at 345-1355 if you have any questions on this submittal. Sincerely, 1;eA 212 Ted Moore, P.E. HOUSE WELL- \ SEPTIC \ \ SYSTEM \ O \\ LOT 4 BLOCK 2 �A6 y \ iC \ y EXISTING _..--_--_---- -74\ WELL \ R 100 500/0 J \ /0% 60j/ U p% INSTALL NEW HOUSE SOA p 1250 GALLON SEPTIC TANK ABANDON --- EXISTING__i/ o� 10% 1000 1000 GAL. ° SEPTIC TANK SHED MOVE EXIST. GREENHOUSE/ /50% / EXISTING X LO _ LOG CRIB SEEPAGE PIT 49 ........................ i, THEODORE F. MOORE i ,�• '.� CE - 3589 1 SfP� •�'•... N•••• lG�I ° GAR. SEPTIC SYSTEM / HOUSE , WELL LOT 6 BLOCK 2 Flattop Technical Services 14530 Echo Street, Anchorage, AK 99516 Phone (907) 345.1355 Lot 5, Block 2, The Landings S/D 16240 Old Seward Highway Wastewater disposal system installation Specifications 1.0 General: 1.1 The scope of the project consists of abandoning an existing 1000 gallon steel septic tank and installing a new 1250 gallon septic tank and cleanouts. 1.2 Construction shall be as depicted on the approved site plan and design drawings. Minor deviations from these drawings may be allowed or required by the engineer conducting the inspections All construction procedures and material specifications shall conform to Municipal and State requirements. All separation distances shall be in conformance with Municipal requirements, unless specifically waived. 1.3 The contractor shall be responsible to obtain any necessary utility locates, and to work around any buried utilities. 1.4 The contractor shall provide adequate cover material and rough grading over all system components to ensure that proper drainage is achieved after settlement and that there are no residual depressions. Insofar as possible the contractor shall minimize damage to trees and existing lawn areas. 1.5 Unless specifically agreed otherwise, the homeowner shall be responsible for finish grading after the soil is compacted, as well as placement of topsoil and reseeding all areas disturbed by the construction. 2.0 Septic Tank: 2.1 The existing septic tank must be properly abandoned by thoroughly pumping, removing the top and backfilling with soil. Note: The elevation of the tank is too low to pump front the parking area, and the access drive down to the tank is very steep and narrow. The neighbor to the south has indicated a willingness to allow a pumper track to come down his driveway to pump the tank, however sanding of that drive may be necessary. 2.2 The new 1250 gallon, 2 compartment septic tank shall be Municipally approved and shall be set level on undisturbed soil. Each compartment shall be equipped with a watertight manhole cover and a 4" cleanout. If the tank is buried less than 4 feet, it shall be insulated with 2 inches of approved burial type, rigid insulation. In order to install the neap tank in the location shown, it will be necessary to rnove a dilapidated greenhouse. Care should betaken to minimize damage to the greenhouse while skidding it out of'the way. 2.3 All pipe connections to the tank shall be equipped with waterproof mechanical couplings. The waste line from the residence to the septic tank shall have a minimum slope of 1/4"' per foot, and the waste line between the tank and the soil absorption system shall have a minimum slope of 1/8" per foot. The contractor is responsible for ensuring that the entire waste line between the tank and the seepage pit is clear and functional. A cleanout shall be installed within 5 feet of the building, and a double cleanout shall be installed within 5 feet downstream of the septic tank. 3.0 Inspections: 3.1 A total of 3 engineering inspections will be required during the course of the project: (1) initial stakeout with the contractor to establish the location of the system and to discuss the plans, specifications and construction procedures, (2) after the tank has been set level and the piping connected, but prior to backfill, and (3) after rough backfill and grading is complete. 3.2 The installer shall coordinate the timing of the inspections with the engineer sufficiently far in advance to ensure the availability of the engineer. A� ggkj'�1 'T&E Environmental Services Inc. /_`=-�Y , c;-^�c�uoi-r�nr�c��n�frons��ivf�f��orsi CT&L' Ref.# 976639001 Client Name Flattop Technical Srv. Project Name/# L 5, Blk 2, The Landings S/D Client Sample ID L 5, Blk 2, The Landings S/D Matrix Drinking Water Ordered By PWSID 0 Parameter Results Client PO# Printed Date/Time 11/03/97 12:33 Collected Date/Time 10/28/97 14:10 Received Date/Time 10/28/97 15:20 Technical Director: Stephen C. Ede — Released By� AUowabte Prep PDL Units Method Limits Date Analysis Date Init Nitrate -N 0.100 U 0.100 mg/L EPA 300.0 10 max 10/29/97 GCP Total Coliform 0.00 col/100ml. SM18 92228 10/28/97 TMW C'r&E Environmental Services Inc. AL Laboratory Division Drinking Water Analysis Report for Total Coliform Bacteria 200 W. Potter Drive Anchorage, AK 9951 B-1605 RE.-IDhNSTRUCTIONSO:VREVERSE SIDE BEFORE COLLECTf.NGSAMPLE 907) 562-2343 Fax: 19071561.5301 MUST BE COMPLETED BY NATER SUPPLIER ❑ PUBLIC NATER SYSTEM I.D. A I% PRIVATE WATER SYSTEM � Send Rrsu//l�rr t4 Send Invoice -- xn`er 5vsum.�.lnwlomv\ym \rna.l•,•.. unu. umD�� \ILIiOy' AW(dl f nL c A-4c� ❑ Send Raulrs ❑ Send lnvoicr�—mss .\ILimY AYYfM �—_a SAMPLE DATE: l L Ci I E2. L9= Month Day Year SAMPLE TYPE: pY Routine ❑ Treated Nater ❑ Repeat Sample (for routine sample WUntreated Nater with lab ref. no. _) ❑ Special Purpose Time Collected SAMPLE LOCATION Collected By 40110(07 _ �:._P , r Pl,e Pnnl Comments: TO BE COMPLETED BY LABORATORY ina osis shows this Water SAMPLE to be: Satisfactory ❑ Unsatisfactory ❑ Sample.over 30 hours old, results may be unreliable ❑ Sample.too long in transit; sample should not be o� er -IS hours old at examination to indicate reliable results. Please send new sample via special delivery mail. Date Received Time Received Analysis Be? nn Analytical Method: :Method: A -, fembrane Filter ❑ X1."10 -MUG • Number of colonies/ 100 ml. LaabbReL:•o. Result* �Anniyst Sent to .A.D.E.C. :inch Fbls Jun LJ Foxed Date: _®_ Time:._ Client notified of unsatisfactory results: ❑ ___ ❑ Phoned Spoke with Fixed Due: _ --- Time: _ BACTERIOLOGICAL NATER ANALYSIS RECORD .NI.N(O-?ICG Result: Total Coliform & Coli Membrane Filter: Direct Count Colonies/100 ml Verification: LTB __-_ —_ BGS — COLIFIRM„_ r.vrc'-n,Y.vYm.,YYsrYa,Y-f fllr - Inhrr IIYDIOIY Fecal Coliform Confirmation -- Final dlembreine Filter Results _ e Colif m/100 ml ,{' . Date LCA 9/G� Time �� hrs Reported By _4 ' T %1 SE3S Membor of the SGS Group (Soci6t6 G6n6rale de Surveillance) n I Nnlc MARYI Alin MICHIGAN. MISSOURI. NEW JERSEY. OH10. WEST VIRGINIA w.e.oI GR'"` ER ANCHORAGE AREA BORO441 01.,RTMENT OF ENVIRONMENTAL DUAL(. TUEIOR ROAD ANCHORAGE, ALASKA 99507 279. BION REPORT ON.aie ecw Arel,ft ..-_. c� NAME./1 MAILING/%rADDRESB�.L:rL-LL.II`i'/ ♦ -_ .75�j_ ..�?�_..z�.rL/L• PHo�E�U_L IOCAtIJN�� .—_LEGAL DESCNIPIION SEPTIC TANK: DISTANCE FRO, 1V E116�/// I. i!'14�C.MAIERIAI NUMBER Or L IG UIOCAPACItYCOMPARIMCNIS_-l�____ _,TH 3.7�C:F. ___L44 --_GAItJNS. INSIDE IEN;IIH __INSIDE WIDTH _ — LIQUID SEEPAGE SYSTEM SEEP : i�>�•: /'.,c' — _ DEPTH r_=- \GE PIT; "S'%`/' '!!^�'/!✓/' ri+izsz NUMBER OF PIIS_ /__—_OUISIDE DI i pM[ICR__, F.-! _OR WIDTH ' '��-�✓..ii... � LENGTH LINING DEPTH l NEAREST Lot IINF.a n DISTANCE FROM WEIIG}%dL' /7.f" dA.�. BUILDING fOUNDAIION.r7!'; TILE DRAIN FIELD: TOTAL `FFECr14 ABSORPTION FREA (W LH AREAL--�T•�� )r DISTANCE FROM WHI WNpmrplj�f 10'AL LENGTH _ NEARESI�1aE_�_—_ OF LINES _ NUMBER OF LINES �.� DISTANCE IIIWEEN ""FS ---TRENCH _.TRENCH WIDT IN. ICTAL EFFECTIVE ABSORPTIO AN� Sp FI LENGTH OF EACH DEPTH, TOP OF TILE 10 FINISH GRADE wEll; 1 (Ol LIN. DISTANCES ' /Nr�.. Uf✓' JaVr >•<'Fi r7�iAv(, 4 /9VNasW<.Y. i O �•�f A'�i✓•'/'Afy+� l:fi <.r✓� OF FRTER MATERIAL BE 1118 "('1 _ -_. IBI. ABOVE TILE._ DEPTH_ ffgi DISTANCE FROM WATE _,BUILDING FOUNDATION,= wAIER NEARS - SEWER LINE L E SI'PTIC SEEPAGE NEAREST 1ANR_ I _ _-_ SYLUA_ CESSPOOL "� OTHER _'- , ------ RCES. DIAGRAM OF SYSTEM DATE_-- ��' _—_-. AI ROVEO-�—_':�. G.A.A.E. Wed 1. Log �Ir ��� M ""CRv UT ti(�1,� — 4ck,al fr For, ............................. ... Location......�oT.. / Lk / i;4E G�l� 1'606 " SG�Ih ' ................................................................... Date completed ..........- ......— q I .................................................................................. Depthof well......... S/...'........................................................................... I............. Sizeof casing .......... ,/ ................................................................. :...... ........................... Distanceto water ....... 3.�..................................................................................... Distance to water while pumping....... i..Q .........................................at rate of ............ .3.4.1,?. ....................... gallons per hour. < (9PA( F orm ion from to _ SicT� S"e_611.,41/-e-1 I-48 40 418 _ 151 _ 0,441C ........................... I ......... Driller DEL' t DRILLING COMPANY SRA BOX 394 0 AI.CHORAGE, ALASKA 99507 FLATTOP TECHNICAL SERVICES 14530 ECHO ST. ANCHORAGE, ALASKA 99516 TEST HOLE # 1 SOILS? -OG -- PERCOLATION TEST LEGAL DESCRIPTION:_ Lot 4, Block 2 The Landa Ps SA? _ DATE PERFORMED: September 8. 1995 PERFORMED FOR: Galen Hansen DEPTHSLOPE (foot)Pt 1r, SM Reddish sandy loam COMMENTS: GP/GM Somewhat silty sand), gravel lenses of clean sandy ;ravel damp in areas of high -r silt content sidewalls stable B.H. Depth to Groundwater I Data 4. r rY s........ru••......YaK ....r...........•...0 •.rye THEODORE P. MOORE ,• "+ CF. - 3539 •" d ., 4 SITE PLAN 4 0 ° o HOUSE 60%/ TSH, #2 10%� T.H. #1 70% ..._........... ......................___.............. SEE SLOPE ARROWS [kine Reading Clock Time - Net Time (minutes) Percometer Reading Not Oro p (inches) 9, 3 12" Presoak - _ Add water and start 3:23:30 23 3/8 . _:•3 5 21 3/8 2 ..__ Add water 3:29 231/2 _ 02 Add water 3:34 _ 3:35 57— TFST�— 23 %/16 3 _ 3:40 21 1/4 Add water 3:40:30 23 1/2 _- #4 3:45:30 5 213/8 11E110CLATION RATE 3 (minutos/Inch) PERC HOLE DIAMETER 6.'-'-- 8" TEST RUN BETWEEN 6.75, FTAND 7.25 FT PERFORMED BY FLATTOP TECH NICALSERVICES. I -��'�� CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPAL GO,, )EI.INES IN EFFECT ON THIS DATE. DATE: 917-019's- AAiYAM 70, 01,10 , of Crolw'ul M IxA ,Yow Curry. IDK]) p 7001 for .k. Or,,. 11,1 n, 177•6{l S) ('�. O Ancbn9q AI •.N ]]$01 VAif l VII L, It�0A0 onion" ce pont N v Vornt a Drilling & Ehternr aes Or IIIIN rmtt b, OCAtlOo Of ML Ppur ro-ol,l• ,It"op 71, If, or IC. A.G.L. b. I - b.-hroulf, CvN lripw got Aloek IA INct fallen Ao.. tyvntMl/ 71-7 1. n 1141.1 �- Anch The Landi s 1 I e/S �w -Ion It. 01 Soon, rM o1roct1w Afro-, Awd InialKuoni - � C 4 1 t Ct1a•1 Mtn,..M Ano of Wit LoeSo1O, -- r 1, ML lK fmt Nlw 'lot*togl•IIM ivv -io• hllr+ 1. HAL Ptrtef If of") Nrpc• Il.ml Ian 62 Top -eosin t• _ 11 1 E 7 ; ay ai ] tv.ct ay b �,nhhl S. litwo Uok []"for' ❑Onion ❑M - u-All�till(::vYr87.aL..11 110 - ❑lrtirl ❑hr«--. p_ tI I } _ I 7 - b.-hroulf, CvN lripw got Aloek IA INct fallen Ao.. tyvntMl/ 71-7 1. n 1141.1 �- Anch The Landi s 1 I e/S �w -Ion It. 01 Soon, rM o1roct1w Afro-, Awd InialKuoni - � r S 4 1 Anchorage 99502 Ct1a•1 Mtn,..M Ano of Wit LoeSo1O, -- 1, ML lK fmt Nlw 'lot*togl•IIM ivv -io• hllr+ 1. HAL Ptrtef If of") Nrpc• Il.ml Ian 62 Top -eosin t• _ 11 1 E - b.-hroulf, CvN lripw got Aloek IA INct fallen Ao.. tyvntMl/ 71-7 1. n 1141.1 �- Anch The Landi s 1 I e/S �w -Ion It. 01 Soon, rM o1roct1w Afro-, Awd InialKuoni - - ). OAn to at VIIU Tim Buckley -.. I mot r..II SRA 4005 B op - Anchorage 99502 Ct1a•1 Mtn,..M Ano of Wit LoeSo1O, -- 1, ML lK fmt Nlw 'lot*togl•IIM ivv -io• hllr+ 1. HAL Ptrtef If of") Nrpc• Il.ml Ian 62 Top -eosin t• _ NN of _Nt•r41 �_ ay ai ] tv.ct ay b �,nhhl S. litwo Uok []"for' ❑Onion ❑M - u-All�till(::vYr87.aL..11 110 - ❑lrtirl ❑hr«--. p_ silt -56 otNri� �.1n 41 1 _ ] 57 -S. Y1t1 [7 PMrttts ❑Mlle tIM11 ❑IrMtry.: �1vn1 2.. ❑Irfllotlon ❑AaMorld-❑ta.wnld . ❑Tait wli ❑OlNrl �e -58- 59 Sod & =� rdnan & grnvBl }{i[i� 6 S. cA7IKf ❑7nrwlN �wi1N drillod It _6-I.. to -6j-ft. Proof, wl/ht y L-Jwvft, L IIAISA Df MLI Tnet-o= nnswnd _ u...Nn 611 Cliff „`_�l•rqut - Nl Pdtw.n �� It. tM Sl to info t e -•�-�__..����, S.: SIAM MRA LI]tLI_— �'—pAla... �Mlwr IoM fvrpn tai o/ rlwNnr`V,If otOkO . Ca8 - ., A 101 NPI Of I `AIJtl 10. "Fr" CIVIL Nlgf ION It. after �,1,•,• Mt. fwlr,l, Id.o, i _ ^Il. 'ft.,�� Arl, rW fool [NVIAONMkN A rpt �.�,_,_• Il U1, L, I"•uul IL wic Mw COnfA It IOMI - In AMID•« Ili E]Illlrn Af'aa tank Dian /wd• ---Dr r r --- WtIMCI WII Srwt"I ❑ro. E] of MtlHitlI --❑Ma t.+t �❑OtN,t d K"pi kit wpllr) ",=-- —� --- -�---- 1111th of Orol PIH le <rw<I tY1... Troo, Prt loco -❑Aoe tlrwainp ❑7•t ❑Othn ��-----��_ 11, AANAALI IS, Work ALL CWRAC70A,S C141111CAT104: - ?hit von vat dnil.d under w funNicliM end uric neon 11 trwo to IN NSo of wI o,,owl•dAe rood Nl ph Vernt_o Dp,li n & aLLernrlaes n 4i •1. if tN. e,n vTlTii tT-`� Md..... 99507 S!,(1],_p1_ �YtAhorage Liln,d: too, _4 T9 ud moo. uury Iar,. Co. WR Boer ilnrleet,an: Witt • Stile DOCS, 114K • Orilla, MARY blta t J V•' a nr 1. �M-W DRILLING, INC, i fix() DRILLING L00 1: �ryf'��lPl1 Ron Monhor D Well Owner Ron =Uso o! Well an. � - 1 Location (address of: Township, Range, Section, If known; or distance main road Lot J !;lock 2 LrrulJnp;n SubdJ.vielon Size of casing_V Depth of }lole-250 _feet - Cased to -250---feet —_ Static water levelI. (above) (below) lend. surface. Finish of well (check one) open end (XX . - Screen ( ); Perforated - Describe screen or perforatlb.._ _ Well pumping test at --gallons per (hoot); (minute) for—! --hours wltl�l�Oz —,.ft. of drawdown from static level - Date of completio„ •lune 171977 WELL L00 Dopth In feet from ground surface Give details of formations penetrated, site of material, color and haolnrs a 0 200 WEITi_NG WELL .._ .. _._.7'0�� 22—To 250 Bodrock 'wntor se.t a in n ordic frnetures —TO-- _ �_ j � i /I%Z)t U ri••G <O� rJ'A C•Tc'R.: /�f,CYI C 1�/�)t/1n• G C'p��lAti f ;; 1 1 r DA�� ar3;tF .a MAY- JoFar_ j'J J'l �tAfi�c li= lr_• L. �, 3S t. 17ieAl TnP D 14 4' E oL Jar �,�1L , f�ri/� G7;J+•),t•'+• i y p 6,kA l f- r. 4 C I AI i 110 - A erk 3�a P, %�ZY� - Ai1Gci J7 GFI?m, MUMCIOAIItY OF ANgIpRAOE DEVt. C,F 11' OlI S etwVRON,dENLAE V:OtICTION ! OCT 2 7 1981 RECEIVED f GAA8 HDI OR TER ANCHORAGE AREA 130ROV -1 DL_.ARTMENT OF ENVIRONMENTAL. QUALI, 3500 TUDOR ROAD ANCHORAGE:, ALASKA 99507 279.8686 _ INSPECTION REPORT ON-SITE SEWAGE DISPOSAL SYSTEM .. MAILING NAME —ADDRESS/ -L PHONE�L�'L� LOCATION���-%?. ___LEGAL DESCRIPTION / '�— - 1 / SEPTIC TANK: U DISTANCE FROM WELL !'.�'�'��1-'W %" MATERIAL -�7L'r — NUMBER OF �/, � -- — _� ,Ll�� __COMPARTMENTS.-� LIQUID LIQUID CAPACITY Z.�L-BGG' _GALLONS. INSIDE LENGTH �___INSIDE WIDTH `-- _DEPTH ''--- SEEPAGE SYSTEM ------- SEEPAGE PIT: NUMBER OF PITS— . -_OUTSIDE DIAMETER _OR WIDTH_ _/�� -, LENGTH /-�., DEPTH , LINING MATERIAL LL- %" K'Zz✓�; - /�,�� _. DISTANCE FROM WEL Z�,�%�_Vic'%i/_=�'G'✓i%, BUILDING F°OUNDATION•-Z i NEAREST I.OT LINE e=��— — TOTAL EFFECTIVE ABSORPTION AREA (WALT AREA) / --SQ. FT. TILE DRAIN FIELD: DISTANCE FROM WELL - NUMBER OF LINES_ ABSORPTION AREA DISTANCE BETWEEN LINES SQ. FT. LENGTH OF EACH LIN -------.�,_ TOTAL LENGTH NEAREST LOT'ET E OF LINES __TRENCH WIDT __ IN. TOTAL EFFECTIVE DEPTH: TOP OF TILE TO FINISH GRADE DEPTH OF FILTER MATERIAL BENEATH TILE IN. ABOVE TILE-- WELL: or/�/�» T — 1j� E DISTANCE FROM _ WATER — DEPTH_ _BUILDING EOUNDATION.___ 4` _SAMPLE "-., NEAREST LOT LINE DISTANCES: h / /�/3/•PSI/ c tc7��✓ rive �adG' _ NEAREST SEPTIC SEEPAGE SEWER LINE_ Lam_, TANK_ , SYSTEM____ DIAGRAM OF SYSTEM OTHER CESSPOOL_ SOURCES -- -- DATE i�-.-_ APPROVED. G.A.A.B. IJ 0 DATE i�-.-_ APPROVED. G.A.A.B. GREA T ER ANCHORAGE AREA Boh jUGH DEPARTMENT OF ENVIRONMENTAL. QUALITY PERMIT NO. 3500 TUDOR ROAD POUCH 6.6SO ANCHORAGE. ALASKA 88502 �/ /JJ _ TELEPHONE 278-8686 /V�le, L--nv�5' / SEWAGE DISPOSAL SYSTEM - APPLICATION AND PERMIT NAME OF APPLICANT - •/ /F��/r��'TITVNIIS�H .S /CIG �)�_ MAILING ADDRESS 1,)i/�/S���j/A�����` PHONE 3'�y "3//U INSTALLATION LOCATION /1// f3,7— C>r/IFLk LEGAL DESCRIPTION %AN016i - S - O al o INSTALLATION OF: SEPTIC TANK ``� SEEPAGE PIT— T DRAIN FIELD , OTHER —, TYPE AND SIZE OF FACILITY TO BE SERVED s_LCCLf±-/E L3 SOIL FINANCED THROUGH p— TO BE INSTALLED BY `� SOIL TEST RESULTS _ l e%0161d-- NOTE. THIS PERMIT IS NOT VALID WITHOUT SOIL TEST COMPLETION DATE ANTICIPATED FINAL INSPECTION: 24 HOUR NOTICE REQUIRED. BACKFILLING OF ANY SYSTEM WITHOUT FINAL INSPECTION BY THE HEALTH DEPARTMENT AUTHORITY WILL BE SUBJECT TO PROSECUTION. SEPTIC TANK SIZE 1000 TYPE S e41 SEEPAGE AREA SIZE TYPE MINIMUM DISTANCES, REQUIREMENTS FOUNDATION TO SEPTIC TANK FOUNDATION TO SEEPAGE PIT —.C20 DRAIN FIELD _ -- SEPTIC TANK TO SEEPAGE PIT WALL / '3 I SEPTIC TANK `✓ —. SEEPAGE PIT. DRAIN FIELD , TO NEAREST LOT LINE. WELL. TO SEPTIC TANK J SEEPAGE PIT __✓_�O DRAIN FIELD ALSO CONSIDER AREA WELLS, WATER MAIN TO SEPTIC TANK — 0 SEEPAGE PIT _ �U DRAIN FIELD_ SEPTIC TANK,SEEPAGE PIT/.L DRAIN FIELD TO RIVER, LAKE. STREAM. CAST IRON INTO AND OUT OF SEPTIC TANK AND INTO CRIB CROSSING GAP OF EXCAVATION 5 FEET INTO UNDISTURBED SOIL. 4 INCH DIAMETER CAST IRON SIPHON PIPES ON SEPTIC TANK AND SEEPAGE PIT FITTED WITH AIRTIGHT REMOVABLE CAPS. GRAVEL BACKFILL CONFORM TO BOROUGH REGULATIONS REGARDING INSTALLATION. HEALTH AUTHORITY OR LICENSED DESIGNE DIAGRAM OF SYSTEM I CERTIFY THAT I AM FAMILIAR WITH THE REQUIREMENTS OF GREATER ANCHORAGE AREA BOROUGH ORDINANCE NO. 2868 AND THAT THE ABOVE DESCRIBED %� SY'SSTEM MISS IN ACCORDANCE WITH SAID CODE. BE _ DATE .��J2S, APPLICANT'S SIGNATURE ATER ANCHORAGE AREA BOROL DEPARTMENT OF ENVIRONMENTAL QUALITY CASE # 3500 TUDOR ROAD ANCHORAGE, ALASKA 99502 Performed For -Deny,L' C'_ L _ Date Performed lD 2� Lecaa'I .Oescrir.tion: 1_ot 6 Block 2 Subdivision 1.gvld,1nQs This Form Renorts Soils Log v Percolation Test Depth Feet Soil Characteristics 2 _ - - 1 I I 3 — �> e— n 5 6 — r 7 — 1 In Was Ground Water Encountered?_AD_ If yes, At what Depth? Reading Date Gross Time Net Time Depth to H2O I Net Drop rercoiation nate Minute Proposed Instillation: Seepage Pit_1C Drain Field Deoth of Inlet Depth To Bottom Of Pit Or Trenc COMMENTS: sr.S ".� u_i„ /,. Test Performed By Data Certified By: Date: MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION DIVISION OF ENVIRONMENTAL HEALTH CERTIFICATE OF INSPECTION FOR HEALTH AUTHORITY APPROVAL OF ON-SITE SEWER AND WATER FACILITY 264-4720 Application Date July 6,1987 "1. GENERAL INFORMATION (a) Legal Description (include lot, block, subdivision, section, township, range) Lot 5, Block 2 The Landings, Location (address or directions) 16240 Old Seward Hi4hwa (b) Applicant Name James Jarrel _ Telephone: Home 274-0136 Business 276-6301 Applicant Address 1801 Nor ne St Anrhnrane;_tiacka 9Ybllj (c) Applicant is (check one): Lending Institution ❑ ; Owner/builder ❑ ; Buyer 5; Other ❑ (explain); (d) Lending Institution Telephone Address (e) Real Estate Company and Agent — Address Telephone (f) Mail the HAA to the following address: Hold for pickup. Please call Bruce Patterson @ DatumiEngineers 563-3142 2. TYPE OF RESIDENCE rr� Single -Family n Multi -Family ❑ Other — -- " NumberofBedrooms listed as three on previous applications. the House could be classified as a four bedroom house. 4th bedroom would be very small. Adequacy based on`four bedrooms, 3. WATER SUPPLY COOP)Individual Well Community ❑ Public ❑ Note: If community well system, must have written confirmation from the State Department of Environmental Conservation attesting to the legality and status. 4. SEWAGE DISPOSAL Onsite RX Public ❑ Community ❑ Holding Tank ❑ Note: If community well system, must have written confirmation from the Stale Department of Environmental Conservation attesting to the legality and status. Page 1 of 2 72-025 It v84) 5. ENGINEERING FIRM PROVIDING INSPECTIONS, TESTS, FILE: SEARCH, DATA AND INFORMATION A As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation of this Health Authority Approval shows that the on-site water supply and/or wastewater disposal system is safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is in compliance with all Municipal and State codes, ordinances, and regulations in effect on the date of this inspection. Name of Firm Datum Engineering & Surveying Telephone 563-3142 Address 4500 Business Park Blvd. Anchorage, Alaska 99503 Date July 6, 1987 0 Drum D. Patterum CE 5034 DHEP APPROVAL Approved for bedroom— Approved __X— Disapproved — Conditional _- Terms of Conditional Approval I \ � rhe0 CAUTION Date Engineer's Seal The Muncipality of Anchorage Department of Health and Environmental Protection (DHEP) issues Health Authority Approval certificates based solely upon the representations given in paragraph 5 above by an independent professional engineer registered in the State of Alaska. The DHEP does this as a courtesy to purchasers of homes and their lending institutions in order to satisfy certain federal and state requirements. Employees of DHEP do not conduct inspections or analyze data before a certificate is issued. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. Page 2 of 2 72-025 (11/84) C MUNICIPALITY OF ANCHORAGE (MO.+/ MUNICIPALITY OF ANCHOVGLTH AUTHORITY APPROVAL (HAA) [NVIRONMENTAL SERVICES DI L CHECKLIST - FEBRUARY 1984 264-4720 A. WELL DATA J U L- 91997 RECEIVED Legal Description: Lot 5, Block 2, The. Landings Well Classification Ind i Vi dual Wel 1_ If A, B, C, D.E.C. Approved (Y/N) -- Well Log Present (Y/N) — N Date Completed — 1972_ Yield ;i 2g.p11>_during adeauaCy Total Depth 145feet— Cased to —unknown Depth of Grouting _UnknowY est. Static Water Level _ unknQW1L Pump Set At llnknowtl Casing Height Above Ground —_2 fPPt Sanitary Seal on Casing (Y/N) —yes Electrical Wiring in Conduit (Y/N) —NQS— Depression Around Wellhead (Y/N) no Separation Distances from Well: To Septic/Holding Tank on Lot _ On Adjoining Lots —J0.0_' p1 US To Nearest Edge of Absorption Field on Lot 100' _ ; On Adjoining Lots �t nnj�S To Nearest Public Sewer Line None nearby_ To Nearest Public Sewer Cleanout/Manhole _ None np xby _ To Nearest Sewer Service Line on Lot Water Sample Collected by -BDP of Da n_Znga4ee(^i_r4g_ ; Dateit 1y Water Sample Test Results Zero S i i farm Ni tratps - Not deter tacLta 0 1 Comments B. SEPTIC/MOLDING TANK DATA X11 S4K alp !_'CCi A"' C.. al 15nq 7 r 1 o 7"r�J�L l ! ! Q Date Installed ___1972-- Size _1.OD0—ga lNo. of Compartments -- 1 not seen could Standpipes (Y/N) yes — Air -tight Caps (Y/N) _y(11; Foundation Cleanout (Y/N) be—Uffder—deck Depression over Tank (Y/N) n0 Date Last Pumped Pumping/Maintenance Contract on File (Y/N) ne ;for Holding Tank High -Water Alarm (Y/N) n/a Temporary Holding Tank Permit (Y/N) N/A r' ITSeparation Distances from Septic/Holding Tank: �HjI'6p T Water -Supply Well — 65 To Building Foundation _12 ° dy 45' plus ' 1�'�yf !j o Property Line To Disposal Field 30 ap>I)rOk. -0��iw"� ��11 U To Water Main/Service Line �sprviGefrpm wpl l 70'�1p MX_ To Stream, Pond, Lake, or Major Drainage �P Course fiver 1(10 feet — �� Comments Page 1 of 2 72-026(11/84) C. ABSORPTION FIELD DATA Soils Rating in Absorption Strata 85 (f rom Fi 1 e) Type of System Design 1 ng rrih Date Installed 1972 Length of Field 12' ( from f i l e) Width of Field 12' (frpm file) Depth of Field F' ( from fila) Gravel Bed Thickness unknown 15" useable Square Feet of Absorption Area Unknown Standpipes Present (Y/N) Depression over Field (Y/N) no Date of Last Adequacy Test .iul.y 2, 1987 Results of Last Adequacy Test System adequate for a three bedroom house Separation Distance from Absorption Field: To Water -Supply Well I00' To Property Line To Building Foundation 3,5 to 40 feat To Existing or Abandoned System on Lot no others on lot ;OnAdjoining Lots none within 50 ' To Water Main/Service Line 100 ' To Cutbank (if present) none close To Stream/Pond/Lake/or Major Drainage Course nnna visible nVpr 100' To Driveway, Parking Area, or Vehicle Storage Area Comments bottom of field is only six feet below ground surface field is now M< for 4 --bedroom, but is nearing en�i of capar_ity to suport 4 bedrooms ( 8 people ) , The surge capacity of the seepage D. LIFT STATION pit is limited due to the shallow depth of gravel. bottom of gravel is less than 15 below septic tank outlet. Date Installed Size in Gallons "Pump On" Level at High Water Alarm Level at Tested for Electrical Codes (Y/N) Comments Dimensions Manhole/Access (Y/N) Pump Off' Level at ** Check Permitted Bedroom Rating Against HAA Request ** Vent(Y/N) Pumping Cycles during Adequacy Test, Meets MOA I certify th have the erifi d, or conformed to all MOA and HAA guidelines in effect on the date of this inspection. Signed 0 vuY�. Date -�- 87 Company l -A f MOA No. Receipt No. -2- Date of Payment�— ff /r4" rJ 7 Amount: $ �(� ✓ d 1� � f � -. C Q F' Bruto V. ?u7icron Page 2 of 2 r " Cr C[ 934 72-026 (11/84) O� A]OFESS10;�f,'� Engineer's Seal CHEMICAL & GEOLOGICAL LABORATORIES OF ALASKA, INC. TELEPHONE (907) 5622343 5633 B Street Anchorage, Alaska 99518 ^^ Drinking Water Analysis Report for Total Coliform Bacteria TO BE COMPLETED BY WATER SUPPLIERII TO BE COMPLETED BY LABORATORY El PUBLIC WATER SYSTEM I.D.N �� A I ' h U I Water SAMPLE to be: A PRIVATE WATER SYST y y ^._. _ Name �� � �� hor1�N . _ S'CI'j >1 I.L ik- 5 l C A—L. �J7t! Mai' g A dress �nn ' State Zip Code til SAMPLE DATE: Fo-- I Lv_1_�J Em Mo. Day Year SAMPLE TYPE: ❑ Routine ❑ Check Sample (for routine sample with lab ref. no. ) ❑ Treated Water XSpecial Purpose CI Untreated Water SAMPLE Time Collected NO. LOCATIO 31 / I C�ect'd` By 2 3 4 5 na ysis s ows 1 s Satisfactory CI Unsatisfactory ❑ Sample too long in transit; sample should not be over 30 hours old at examination to Indicate reliable results. Please send new sample via special delivery mail. G "1 Date Received r / J Time Received �L Analytical Method: Membrane Filter ` No. of colonies/100 ml. Lab Ref. No. Result" Analyst /L 1 10 � I ETI L E l� m LJJ J L� BACTERIOLOGICAL WATER ANALYSIS RECORD READ INSTRUCTIONS Membrane Filter: Direct Count 0 Coilform/100ml BEFORE Verification: LTB BGB COLLECTING SAMPLE Final Membrane t Results _ ollform/100ml Reported By Date_'" Time: 122 (2 a.m. p.m. TNTC = Too Numberous To Count OB = Other Bacteria I CHEMICAL & GEOLOGICAL LABORATORIES o£ALASKA, INC 5633 .STREET m� A� , c a3 ,� T e#92-0040440 Ar mR q 2 mt> n m:i :v m m It: <mi,m.zm;1 : & >:;«:e «»m 4 > \. n «,. a Am«G . ± mea Wirut,a:>ytaIV] am9,Rm>? Urdu plo. e« u m:, ». :Mhji,z kr wawa««;« ,nm 'Llpnc m r a am m + uim m ;U: mm:A+ m+mmm mmt:m: +m uwc TOT±�UItjkil u&«A; :� Ami ml�:AmaEm 1 r 1 m , m m6zlGril(um a ;« b:j s a m Remarks Above Wloo G mss ; U�-L,e +cam + #a CIMESIMPIAGAL & GEOLOGICAL LABORATORIES OF ALASK4,INC .��m,BSTREET ANCHORAGE, ALASKA 99518TELEPHONE cm, &FEDERALT e,92-0 _m n mrA 6 m t am; m:& W ,± mm :G+, I,A, :« xe By ,UUC> m, , cum m« mWs /:'oou qE,�a H ».x. 0060 j wave«vA�n»ce4mwENG IF,s axrucc; riUMILEDIV&A 7m + :wm 4:QQQ w Wvim, faramotor «ms +nems Result/Um, &r<+ No. :mz o m!«aa a< +!i «Prom mgm ELI « @ ::«w 7a �m �lxmq: w- — � ---------- Put , i +ciw twitcut.t[orishbove lus No:+um a+M,kvillamAmn Nip m mow. act" cmr«a fIC))EPARTME' 2V - 825 _5 MUNICIPALITY OF ANCHORAGE. OF HEALTH AND FNVIRONMEN PROTECTION L Street, Anchorage, AlasKa 99501 279-2511, ext. 224 or 225' Lute Received: June 8, 1977 I , 41- Time _./����,1/Y1, r2: `.Pimc _._. #3: Time Date _ ._1>?_ 77_. nirnl Date ._.. — Date Ins1a _ � �St�11_...-- InsP -- l:usp - REQUEST FOR APPROVAL OF :INDIVIDUAL SEWER AND WATER .F ACIIJ_TIMS 1. Lending Institution Request:.: Alaska Pacific Bank %'Sue Benson Mailing Address: Post Office Box 420 99510 Phone; 276-3P.L0/40 2. Property Owner_: _Dennis/Jean Biastrpck Phone: 344-9110 - - -- - afte:e Mailing Address 3. Legal Description: Lot 5 ng Block 2 The Landis Subdivision ------ FJi S , 4: Single Family Residence: Number (-)F Bedroom,:Q�) - Multiple Family Residence: ( ) Number of Bedrooms: _ A x 5. Well System: individual Well Coim unil:.y/Public System ( Ahv 7S' Permit ik _ .-. Depth of. We � �u-- Well Log ori [File J� Constr.uct.i.on_,..�2- - - 13aclrr.ra] Analysis -- 6. Sewage: Disposal System: On --site Systcm ( X){ Public Uti.li/y ( )/ Permit. $ Installed 19:72-_..._--- lnstal.lor - �)�/di/ Lqc, Ee Septic Tank Size. —��, Manufacturer `r� 5 Absorption Ar (.a �� Soils Ra.i e Material i 7. Distances: Well to Septic Tank -��- - to 'Absorption Area to Sewer Line ©� r 1 �N^ea c st Lot .line [absorption Area to Nearest Lot. Line------C:� DeparLmenc Worksheet: _ MUNICIPALITY OF ANCHORAGE v -iii.. •.! DEPARTML'NT OF HEALTH AND ENVIRONMENTAL- PROTECTION - 825 L Street, Anchorage, Alaska 99501 2.'79--2511, ext. 224, 225 REOUEST FOR APPROVAL. OF +,� k INDIVIDUAL SEWER and WATER FACILITIES I V t �E 1. Type of Inspection: VA ----__FHA_ _CONV_ xx Dennis & Jean Biastrock 2. Property Owner:—______._____— - _ Mailing Address:___. unknown 3. Name of Buyer: _—_— Richard and Dorris Enter ,----_-- --._-- Mailing Address 6517 E. 31st Ave. 4. NamAlaska Pacific Banke of Lending Institution:_-_ --- —__ Day Phone 344 9110 after 6/2/77 276-2131 or 333-8626 Day Phone:_ - Mailing Address: -__P'0_ Box 1120 Anchorage 9951.Chone:_-276 3110 ext. 40 5. Name of Realtor or Agent Mailing Add 6. Legal Description Location: none Ph L5 B2 Landings SD Anchorage Old Seward Hwy, approximately 9 miles SE of Anchorage 7. Type of Facility to be Inspected 8. Water Supply Type of Supply: SE M Public Utility --.--Individual xx If Individual, number of dwellings presently served If Individual, depth of well 9. Sewage Disposal System 3 Type of System: Public ------ Individual (on-site)_ xx_ If Individual, date of installation probably 1972 ���-- �rGO---- C 5/27/77? Iv`l Sue Benson v 1 • 01 Alaska Pacific Bank �1 276 3110 �ic�-, _��tc �✓r� 2 72-003131761 06 122oa1 Rev 073 - K - �'tA DEPARTMENT OF HEALTH AND -SOCIAL'S,-_ 1.0cc -- On fop DIVISION OF PUBLIC HEALTH 'rES Lab Na —_ _ ❑ of Well ` ❑ Other,__—�--- INDIVIDUAL AND SEMI-PUBLIC --- PURPOSEOFE%AMINA'HON: Illness Sorpected? - BACTERIOLOG I CAL WATER - — ANALYSIS - OFFICE �nTE Repairs to SysteniP. C1 Yes ❑ No S,gndlure UG 1220 I b1.7 6ACTERIOLOGICAL WATER ANALYSIS RECORD Flnalyss shows the Water SAMPLE to be - _ INDIVIDUAL�LI PUBLIC ❑ CHLORINE RESIDUAL PPM_— READ INSTRUCTIONS Ume Received_ (e2 //-! Time Rece,ved_ No. - LXQrsloctory I REPORT RESULTS TO ❑ Unsatis(aclory - _ pEj Questionablel + ❑ Sample iota long in-lmnvl, sainpli; shoald no16e over 48 - _ - - - - - - - -hours old or exnntinotion to indiccue reliable resells. Please ADDRESS —_ send new sample `--_—ZIP ❑ Battle broken m Iragsit, please sent -new sample CIiY.�-` CODE ADDRESS oFsouece J r l -lel ��/C_� SANITARIAN'SREMARKS - COMPLETE THIS SECTION ONLY IF WATER IS AN INDIVIDUAL SUPPIyY -iTIE_ CO-I'LE`C-T CL D ' DATE COLLECTED COLLECTED BY !- .— -�- - SempleCollecteJFrom I'i.�Ritchen Top ❑Bathroom Tap ❑ BosemeN�TUP- ❑ Other IU,li Well — 0 -Dog ❑ Driven ❑ Drilled ❑ Bored - - SOURCE: - - ❑ Spring ❑ Cismnt ❑ Other___ —. Dug Well or Cistern Construction: - WaII ❑ Wood ❑ Concrete ❑ Metol ❑ Tile Bark or - Top E7 Wood ❑ Concrele ❑ Mewl ❑ Open Top ❑ Co,,,, LOCATION - '❑ In Basemen, ❑ Basemen, CHlss, ❑ Under Housn `.- ❑ In Yard ❑ Olhcr Bul Ihn, Sewer - _ Septic DISTANCE TO:or Oger Dn,,e,ge Pnc-- .Feet. Tank Feet. isle seepo" Coss" Field---Feet. -PIt —:Feel Pool_"__Feel. Nivy____Feel. Other Possible - SourcesofContamination_ -_ - — .MATERIAL: Building Sewer" ❑ Cost Iran ❑ Wood ❑ Tile ❑ Fibre ❑ Asbestos CemeN -- ❑ Plastic Joint Material GENERAL: Does Water Become Muddy or Discolored? ❑ Yes [] No When? --- _ Dlgale, of Well Well Casing L Mnterlal_ —Diameter_ DPpII, _ Length of Water Depth I � Drop pipe - Fort"' Bollom tFeel. Offset in In Utility PUMP LOCATION ❑ }n Well ❑ 8aseme,n ❑ In Basement ❑ Room - - 1.0cc -- On fop ❑ of Well ` ❑ Other,__—�--- --- PURPOSEOFE%AMINA'HON: Illness Sorpected? - E) Yes ❑ No - New Soormpf Supply? ❑ Yes ❑ No Repairs to SysteniP. C1 Yes ❑ No S,gndlure UG 1220 I b1.7 6ACTERIOLOGICAL WATER ANALYSIS RECORD - Rev1913 READ INSTRUCTIONS Ume Received_ (e2 //-! Time Rece,ved_ No. - ONi- REVERSE SIDE BEFORE COLLECTING` SAMPLE Lactose Broth 10" 10cc Iarc lora IDci 1.0rc 1.0cc -- 24 Homs 4811o1111 --- Brilliant Greets�- 24 Hours 48 Hoots - -. — - EMB__ --- Lactose Broth, 24 E®.— 48 his .—_---Gram's stain_—__ t C.IJo.m Density_ _--- IMost probuble No. per 100ccl MP Resuhs Reported by�� Date_ o n. This ono ly's -nch oles Collor, Ong a rusuis lobe: t - Present________ & M. gr:HOL([ AfG Jl S GREATER ANCHORAGE AREA BOROUGH Department of Environmental Quality q 3 S AAl k 99503 274 4561 #,ao,,,,01 3 30 C treet, nchorage, as a JA I� [ 2 Approval requeste Mailing Address: Date Received�02 Time of Inspection Date of Inspection REQUEST FOR APPROVAL OF INDIVIDUAL SEWER & WATER FACILITIES _ FOR Property Owner:,�J Phone: Mailing Address: 3. Legal Description: 4. Location: evl _ _Q — (moi✓ ^ ; ✓J 5. Type of facility to be inspected No. of bedrooms 6. Well Data: A. Type C. Construction 7. Sewage Disposal System:.��!�� B. Depth 5' 0--��— D. Bacteria] Analysis J��j/✓/yrz 1� A. Installed _Z W- — B. Installer r �j C. Septic Tank: 1. Size ^'zF 2. Manufacturer (ri D. Seepage Pit: 1. Absorption Area)//'�/'0kz4,-%2' 2. Material E. Disposal Field: Total length of lines 8. Distances: A. Well to: Septic tank U'_, Absorption area O,& Sewer Lines '^�_�" i Nearest lot line �0 _, Other contamination B. Foundation to septic tank / Absorption area C. Absorption area to nearest lot line's' EQ -034 (1/74) Page 1 of two pages Page ?. of two pages - Requeat for Approval of Individual Se.,vLr & Water Facilities Loyal Description Comments Approved,1_ /�__ Disapproved Date Approval Valid for one year from date signed Greater Anchorage Area Borough, Department of Environmental Quality DIAGRAM OF SYSTEM I certify that the information contained in this request for approval to be a true ana accurate representation of the subject sewer and water facilities and these facilities are operating satisfactorily. SIGNED EQ -034 (1/74) Date TATE OF LASKA 06-1 220 a DEPAI LENT OF S HEALTH AND Lab. No. AND SOCIAL SEI, ACES DIVISION OF PUBLIC HEALTH oAT — BACTERIOLOGICAL WATER ANALYSIS - OFFICE — -- - Records in this office indicate this WATER SUPPLY to be of: PUBLIC ❑ SEMI-PUBLIC ❑ INDIVIDUAL©- OTHER_ D Satisfactory D Questionable D Unsatisfactory Sanitary Status. H EPORT RESULTS l'O - locc 10cc ' 10cc 10cc Looe O.lec i Analysis shows this Water SAMPLE to be:. NAME- 48 hours Brilliant Green - ❑-Smisfactory D Questionable D Unsatisfactory. - _ 40 hours ADDRESS ----- - - If. an "Unsatisfactory" or "Questionable". status. is indicated above - ZIP you should take immediate action as recommended below. —CODE =--- 1. Notify consumers Water is polluted. Boil -or chemically CITY treat this water asoutlinedin the enclosed leaflet ADDRESS . "Drink It Pure." - - 0FSOURCE 2. increase chlorination sufficiently to meet recommended residual standards. SAMPLE COLLECTED BY -- Determine source of contamination and take action necessary to maintain - a safe water supply at all times. - - %__ Pie DATE COLLECTED -- • TIME COLLECTED Sample Collected From p Kitchon Tap D Bathroom Tap D Basement Tap 3. Check chlorination and other mechanical equipment. Make certain it is D functioning properly. �Other(List)-- � a 4. is not obtained, please Yager checking equipment disinfecting or I�— advisor wire this office for emergency assistance or advisory services. Well D Dug D Driven p Drilled D Bored 5. This is a so, face water source and subject to pollution by man and animals. SOURCE: D Spring ❑Cistern D Other - An approved Water supply source should be developed. Dug Well or Cistern Construction: ❑Brick or _� 0. Im in your' ❑dug wall pdriveh well ❑drilled well ❑cistern Walls— ❑Wood ❑Concrete DMetal ❑Tile Concrete - - - Top— D Wood ❑Concrete D Metal D Open Top __ 7. Relocate your well to a safe location in relationship to your sewage disposal LOCATION: p In Basement - p Basement Offset D Under House system. D see enclosure D In Yard pother_ 8. Sample too lungintransit; sample should not be over 48 hours old at - Building Sewer Septic Feet Tank —Fort examination to indicate reliable results, please send new sample. DISTANCE TO: or Other Drainage Pipe Tile SeePaga Cess- - Poal Feet Privy. Feet lease send new le. p Bottle Broken in transit, p sem p Field ---Feet. Pit Feet. Other Possible 9: Contact your nearest. ❑ Local Health Department or ❑Alaska Sources of Contamination Asbestos Fibre ❑Cement ,-- Division of Public Health, sanitation office for bulletins, consultation and MATERIAL: Building Sower- DIrron D Wood DTile p assistance. D Plastic Joint Material —Type --- SANITARIAN'S REMARKS- - GENERAL: Does Water Become Muddy or Discolored? DYes ON. - - - When? Diameter of WeII Depth Feet -- Wall teriel ng —Diameter_—Depth Material - - --- Length of Water B — Drop Pipe From Bottotto m ----Feet. ---- PUMP LOCATION: D In Well D Offset In p In Basement D In Utility Basement Room - D On ToD Other - Of Wall PURPOSEOFEXAMINATION: Illness Suspected? Dyes DNo Now Source of Supply? D Yes ONO Repairs to System? D Yes ONO Signature 06-1220 (b) BACTERIOLOGICAL WATER ANALYSIS RECORD READ INSTRUCTIONS. - Date Received ` r' ��� - TimeReceived n^;Lab. No. ON REVERSE SIDE BEFORE_ COLLECTING SAMPLE Lactose Broth loco locc 10cc ' 10cc 10cc Looe O.lec 24 hours 48 hours Brilliant Green - 24 hours 40 hours —Lactose Broth, 24 hrs. 48 hrs. - Gram's stain —Coliform Density (Most probable No. per 100cc.) - —MF results _ —Detergent Test - - -Reported by— - , • : .�.. - Date ' -'-- This analysis Indicates Coliform Organisms to be: Absent 1 2 9 4 5. 6 GREATER FhICHORAGE ARi. BOROUGH Department of Environ•;!,ntal Quality 3330 "C" St., Anchorage, AI a s k a 99503 -•274 REQUEST FOR APPfiOVAL OF INDIVIDUAL SE'rIER � 'WATER FACILITIES Type of Inspection: CMIRO Property Owner: Mailing Address Name of Buyer: ---_ —^ Mailing Address: Name of Lending Institution: Mailing Address: _��• Name of Realtor or Agent: Mailing Address: VA FHA CONV Legal Description: Location: _ Day Phone w �x o Phone a Ci — Phone _- Bdrms.�a_ 7. Type of Facility to be inspected: _No. 3. Water Supply Type of Supp1Y: Public Utility Individual If Individual, number of d!,,El1ings presently served If Individual, depth of v;o11 9. Sewage Disposal System Type of System: Public Utility ^__ Individual (on-site) If IndiVidual, date of installation Municipality of Anchorage On -Site Water & Wastewater Program (907)343-7904 RUSH! AUG 16 2016 CERTIFICATE OF ON-SITE SYSTEMS APPROVAL Parcel I.D. 020-061-03 Expiration Date: I 1 —' -N l�2 1. GENERAL INFORMATION Complete legal description THE LANDINGS; SLOCK2, LOT5 Location (site address) 16240 OLD SEWARDHIGHWAY -ANCHORAGEAK99516 Current Property owner(s) BURNS HOLDING, LLC. Day phone Mailing address 16240 OLD SEWARDHIGHWAY `ANCHORAGEAK99516 632-5535 Real Estate Agent . BONNIE MEHNER Day phone 223-0005 2. TYPE OF DWELLING: 0 Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 5 4. TYPE OF WATER SUPPLY: Waiver Fee $ TYPE OF WASTEWATER DISPOSAL: Individual Well Receipt Number_ 66=6 Individual On-site COSA # QY,[&130 Individual Water Storage ❑ Individual Holding tank ❑ Community Class Well ❑ Community On-site ❑ Public Water System ❑ Public Sewer ❑ WaiverNariance request for. N/A Distance: Received by: Date: B I G COSA to be released to the engineer. unless otherwise requested by the engineer. COSA Fee $ f! /' 4B-7 Waiver Fee $ Date of Payment ghw& Date of Payment Receipt Number_ 66=6 Receipt Number COSA # QY,[&130 Waiver # 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, i verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and(or wastewater disposal system Is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm GARNESS ENGINEERING GROUP, Ltd. Phone 337-6179 Address 3701 E. TUDOR ROAD, SUITE 101 R ANCHORAGE, AK, 99507 Engineer's Printed Name JEFFREY A. GARNESS, P.E. Date 0/)64 Engineers Comments: to conducting this evaluation, GEGprovidedan engineering evaluation of the vmAaaArsep6csystemin accmdarme vAM9 guidelkes and regulations established by the Municipality o/Anchorage andiMushyromcdces. The mpodedresuffs desmibe the contlgion of the systerNs on the date's of the evaluation. Sepemtfondiluentsweremea mdiomordyidentWabkkaftm.. Hidden dialects orancroachmems may most that were not idenggeddvringtiie evaluation Tha opemiional ffeofall weAs andseplic systems depend on a variety ofvariables including, but not limited to, sdlwnddions, grourr aterlevas(halmayduduafedurmy the year), quality of construction (matedats and wakrnanship), and the vralerusage of fhe famiyuliNing the systeays. These conditions can vary, and are outside fhe corral of GEG. Sab:Nactuy lartresuds do not guarantee Imurepedarmance oifhe sysmads; therefore, GEG makes no warranty (express crimplied) regmdmgthefulum performance of Mend orsepficsysfam. GEG makes no representation whether on agemalive well orsepficsystem can bemstaffedon fielompertym the evert eithwofthe anent systems fail. The canteil of this repod is lorfhe sok beriefAoflhepersoNpady who mlamed GEG. Rehinceupan the iMormationprovided in this repod by any otherpemon orpany, including big rot limdedlosubsMmt pmpedy purcha m is mot authorized. In short, GEG disavows any legal duty to anyone ofherfam Mepenw*artywhopaid forlhis mpwt. 6. DSD SIGNATURE System #1 Approved for � bedrooms. By: AXLlili009 System #2 Approved for bedrooms. ,(OF Afvz',c, Disapproved. "`C 9 Conditional approval for bedrooms, with the following stipulations: 0�,t_S _ Original Certificate Date: 2 —) i--/ r'0 The Municipality or Anchorage Develop,emt Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineerregistered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. �tita:l(f,la,r�� COSA Checklist Septic System Advisory Well Flow Advisory (Rev. 1OMW2) /1C Nitrate Advisory Arsenic Advisory Other If more than 1 septic system is on the lot: COSA Checklist # of_ Structure served by this system Certificate of On -Site Systems Approval Checklist Legal Description: THE LANDINGS; BLOCK 2, LOT Parcel ID: 020-061-03 *PER SURROUNDING WELL LOGS A. WELL DATA `"WELL TEST PERFORMED BYAAROWWELL AND PUMP SERVICE -SEE ATTACHED EMAIL WATER STORAGE TANKS ARE PRESENT Well type PRIVATE If A, B, or C provide PWSID# N/A Well Log (Y/N) NO Date completed 1972(7) Sanitary seal (Y/N) YES Total depth 138+ ft. Cased to *40+ ft. FROM WELL LOG Date of test Static water level 0"'_0 ft. .tt Well production /NO g.p.m. WATER SAMPLE RESULTS: Coliform 0 colonies/100 ml. Arsenic: ND ug./L. Nitrate ND mg./L. Date of sample: 6/16/2016 Wires properly protected (Y/N) YES Casing height (above ground) 12+ in. AT INSPECTION ""8/11/2016 "21.4 ft, ,.1.31 g.p.m. Collected by: GEG, Ltd. B. SEPTIC/HOLDING TANK DATA `SEE NOTE ON PAGE 2/3 OF RECORD DRAWINGS Tank Type/Material STEP/STEEL Tank size 2500 gal. Number of Compartments ? Foundation cleanout (YIN) "YES Depression over tank (Y/N) NO Date of pumping NEW Pumper. C. ABSORPTION FIELD DATA Date installed 8/8-1112016 Cleanouts (Y/N) YES High water alarm (Y/N) YES Date installed 8/8-11/2016 Soil rating :p. d. r ftz/bdrm) 4_0 System type DEEP TRENCH Length 20 ft. Width 2.5 ft. Gravel below pipe 7 ft. Total depth •16.5 ft. Eff. absorption area 280 ft2 Monitoring tube YES Depression over field NO Date of adequacy test NEW Results (Pass/Fail) - For 5 bedrooms Fluid depth in absorption field before test _ in. Water added _ gal. New depth =in. Elapsed Time: = min. Final fluid depth = in. Absorption rate >= 750+ g.p.d. Any rejuvenation treatment (past 12 mo.) (Y/N & type) If yes, give date D. PUMP VAULT "PER MOA ELECTRICAL INSPECTION REPORT Date installed 0/8-11/2016 Size in gallons -70 Manhole/Ac cm (YM) YES "Pump on' level at 32 in. "Pump oft" level at 22 in, High water alar level at 36 in. Datum BOTTOM OF MANHOLE Cycles tested NEW Meets alar $ circuit requirement$? "YES E. SEPARATION DISTANCES SEPARATION DISTANCES FROM WELL ON LOT TO Septic tanknift station on lot Absorption field on lot "75 Public sewer main 75'+ On adjacent lots 100'+ On adjacent lots 100'+ Public sewer manhole/deanout 100'+ Sewer /septic service line Holding tank 76'+ Animal containment areas W+ Manurelanimal excrete storage areas I W+ SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Building foundation g+ Properly line5`* Absorption field 5'+ Water main 104 Water service line 104 Surface water 100'+ Wells on adjacent lots 100'+ SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Property line 16'+ Building foundation 1U'+ Water main 10'+ Water service line 161+ Surface water top'+ Driveway, partdng/vehide storage 1p4 Curtain drain Wells on adjacent lots 100'+ F. COMMENTS "WR#OSV161088"FOUNDATION DRAIN SEPERATION DISTANCE VERBALLY APPROVED BY DEB WOKENFUSS DURING CONSTRUCTION ""WELL IS APPROXIMATELY 21 FEET FROM WHERE THE SEWER SERVICE UNE EXITS THE HOUSE. G. ENGINEER'S CERTIFICATION I certify that I have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines In effect on this date. Engineer's Printed Name JEFFREY A. GARNESS Data 8 1/ b �/6 (Rev. 10(1212) LI RA ADVANCED WASTEWATER TREATMENT SYSTEM MAINTENANCE AND REPAIR AGREEMENT BETWEEN MUNICIPALITY OF ANCHORAGE AND John C. Springsteen & Christine A. Resler THIS MAINTENANCE AND REPAIR AGREEMENT made and entered into as of this John C. Springsteen & Christine A. Resler 8 Day of /a u�,nad- of 2016 , by and between herein the "OWNER," and the Municipality of Anchorage, herein the "MUNICIPALITY." In consideration of the mutual covenants contained herein, the parties to this Maintenance and Repair Agreement agree as follows: 1. Advanced Wastewater Treatment Systems. Municipality grants permission to Owner to utilize and operate an Advanced Wastewater Treatment System (AW WTS), described as A A%1an+eX located at (legal description). Legal: The Landings Lot 5 Block 2 Property Address: 16240 Old Seward Highway 2. Definitions. Alteration. Any change to the design or function of an AWWTS that includes the installation or removal of any parts, components or pieces not included in the original construction permit and design. Certificate of On -Site Systems Approval (COSA). An approval by the Municipality of existing water and wastewater disposal systems given at the time of property sale and title transfer in accordance with Anchorage Municipal Code (hereinafter, "AMC") 15.65. These approvals certify that service and maintenance provider approved by the municipality and the manufacturer of the AWWTS for the entire term of the AWWTS. In addition, it shall be the responsibility of the Owner during the term of this Maintenance and Repair Agreement, and any renewals thereof, at the owner's sole expense, to pay for any and all: (1) repair(s), (2) maintenance, (3) adjustment(s), (4) replacement costs, and (5) inspection costs. B. Owner agrees to comply with all applicable ordinance, laws, regulations, rules and orders for the AWWTS. C. Upon request by the Municipality, the owner agrees to provide the Municipality a written schedule of routine maintenance and repairs which have been performed on the system. When a record of maintenance is documented and maintained by the system vendor, the owner agrees to allow the Municipality access to this information. D. Owner acknowledges that the fine for failing to maintain and repair an AWWTS may be assessed in accordance with AMC 14.60 for improper discharge. E. Owner agrees that only maintenance and repair personnel approved by the Municipality will inspect and make any necessary maintenance, repairs or permitted alterations to the system. F. Owner agrees to grant the Municipality reasonable access to test and inspect the AWWTS upon 24 hours written notice. G. Owner agrees that any sale or transfer of title of the property will not occur without a new Certificate of On -Site Systems Approval. H. Owner agrees that the AWWTS installation and maintenance requirements as provided by the AWWTS vendor/installer and approved by the Municipality are the governing guidelines for the construction, maintenance and repair of the Owner's AWWTS. 6. Nonwaiver. The failure of either party at any time to enforce a provision of this Maintenance and Repair Agreement shall in no way constitute a waiver of the provisions, nor in any way affect the validity of the Maintenance and Repair Agreement or any part hereof, or the right of such party thereafter to enforce each and every provision hereof. 7. Amendment. A. This Maintenance and Repair Agreement shall only be amended, modified or changed by a writing, executed by authorized representatives of the parties, with the same formality that this Maintenance and Repair Agreement was executed with, and such writing shall be attached to this Maintenance and Repair Agreement as an amendment. B. For the purposes of any amendment modification or change to the terms and conditions of this agreement, the only authorized representatives of the parties are: a. Owner: John C. Springsteen & Christine A. Resler b. Municipality: Director, Community Development or designated authority C. Any attempt to amend, modify, or change this contract by either an unauthorized representative or unauthorized means shall be void. 8. Jurisdiction: Choice of Law. Any civil action arising from this Maintenance and Repair Agreement shall be brought in the Superior Court for the Third Judicial District of the State of Alaska at Anchorage. The laws of the State of Alaska shall govern the rights and obligations of the parties under this Maintenance and Repair Agreement. 9. Severability. Any provisions of this Maintenance and Repair Agreement decreed invalid by a court of competent jurisdiction shall not invalidate the remaining provisions of the Maintenance and Repair Agreement. OWNER: By (signature) Date: 2 lk AUG O$ `^ sa��cen 2.1 -.-(Print name) STATE OF ALASKA ) ) ss. THIRD JUDICIAL DISTRICT ) The foregoing instrument was acknowledged before me this 6day of �UcEbt�r ' 2C /LP by E ACACE"di.) � ��� , \\\\\\ N E AND JO iJP'•��s1on w N TA PUBLI FO ALASKA ; �;�F uoTAP, My Commission expires: 7jbtyezo/7- _ ;•mz uP e't sr ..e�06-071' p �,,N OF A"%— MUNICIP r By: tM (signature) Date: (print name) Title: �f ��e J,`C�i✓ psi Jeff Garness From: David Harper <dlharper2@gmail.com> Sent: Friday, August 12, 2016 7:20 AM To: Jeff Garness Subject: 16240 Old Seward Highway Jeff, we visited the above address and performed a bottom hole pump test on the existing well located inside the home on 8-11-16. A valve was placed where the waterline exits the floor coming into the utility room to the storage tanks. The well was ran until it tripped the low water control. Depth at that time was 138 feetTOC. This was performed 4 times over a two hour period and finished with a timed test which put the well production at 1.31 gallons per minute below 120 feet. At that point, water could be heard cascading into the well. The static level at the beginning of the test was21.4 feet from TOC. David L. Harper Aarow Pump & Well Service, LLC