HomeMy WebLinkAboutUS SURVEY 3200 LT 2U55 #3200 Lot 2 #090-041-04 Municipality of Anchorage Community Development Department Page 1 of 3 On-Site Water and Wastewater Program 4700 Elmore St. • P.O. Box 196650 Anchorage, AK 99519-6650 • http://www.muni.org/onsite • (907) 343-7904 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSPXXXXXX PID Number: 090-041-04 ❑ New ❑ Upgrade Name: Marilyn Lybarger ABSORPTION FIELD ❑ Deep Trench ❑✓ Shallow Trench ❑ Bed -❑ Mound Address 177 Comfort Ln. Indian, AK 99540 ❑ Other Phone Number of Bedrooms - Soil Rating Total depth from original grade - 4 - 0.8GPD/SF - 4Ft. LEGAL DESCRIPTION - - Depth to pipe invert from original grade - - 2 Ft. Gravel depth beneath pipe - 2Ft. Subdivision Block Lot US Survey #3200 - - 2 Fill added above original grade 0 Ft Gravel length - - 53 (2) Ft. Township Range Section - Gravel width 5Ft Beds: Number of Lines N/A Distance between lines N/A Ft SEPARATION DISTANCES - To Septic Absorption Lift Station Holding Sewer Total absorption area Number of trenches Dist. between trenches From Tank Field Tank Line -)5 1S'F 2 10.1 Ft. Well 107.8 108.2 N/A N/A 91.9 TANK I] Septic ❑ S.T.E.P. ❑ Holding ❑ Other Manufacturer Existing Capacity I 1,5000al. Surface Water 123.5 103.9 N/A N/A Material Number of compartments Lot Line 80.1 11.5 N/A N/A Steel 2 NA Foundation 10.3 38.0 N/A N/A LIFT STATION Manufacturer Capacity - Curtain Drain 50+ 50+ N/A N/A Gal. RemarksThis record drawing is based of the 4/27/2016 - Pump on level at - in. Pump off level at in-1 High water alarm at in, survey as-built. This record drawing is also for the purpose of documenting the currently undocumented - Pump make and model Electrical Inspections performed by system. Drain field covered with 2" of insulation. ISJSWIM PIPE MATERIAL House to tank Tankto Installer ' drainfield v'r MIMN - Drainfeld CO/MT- Inspector l/�N `LN� BENCH MARK (Assumed elevation) 'POOR Inspection „ - 1 Location and description - - - dates: : O� rn _ Man door threshold by garage - 3rd COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL Engineer's Stamp Conditional Approval: Date •��everi '•l5annorae f/ ` 81? Approv k,w�_ Date Inspection Report _1-1-12.doc inn' s1 OFFSET CAM LOT 2 M M 07 A B Ti 13.4 43.9 T2 13.8 41.0 C1 93.4 90.5 M1 92.0 89.5 C2 100.9 94.0 M2 100.8 93.5 C3 54.4- 40.0 - C4 - 68.4 49.6 inn' s1 OFFSET CAM LOT 2 M M 07 fl �, TRUE NORTH SCALE 1"= 50' 1,500 GAL STEEL SEPTICII TANK (E) WELL E 11.5 c7 1 110.4 c2 w (AIV D%E c4 M2 \ 11 2 EACH SHALLOW TRENC 53'L x 5'W x 2'ED x 4'TD NOTES: RECORD- DRAWING OF EXISTING UNDOCUMENTED DRAWN I NJC SITE PLAN PANNONE ENG SVC, LLC P.O. BOX 102954 ANCHORAGE, AK 99510 PHONE (907) 272-8218 FAX (907) 272-8211 US SURVEY #3200, LOT 2 MARILYN LYBARGER 177 COMFORT LN. INDIAN, AK 99540 7/6/2016 Scale 1"=50' P.I.D. NO X90-041-04 PERMIT NO. OSPXXXXXX Sheet 2 OF 4BR SFD 1 WELL E B 108.2 - DRIVEWAY fl �, TRUE NORTH SCALE 1"= 50' 1,500 GAL STEEL SEPTICII TANK (E) WELL E 11.5 c7 1 110.4 c2 w (AIV D%E c4 M2 \ 11 2 EACH SHALLOW TRENC 53'L x 5'W x 2'ED x 4'TD NOTES: RECORD- DRAWING OF EXISTING UNDOCUMENTED DRAWN I NJC SITE PLAN PANNONE ENG SVC, LLC P.O. BOX 102954 ANCHORAGE, AK 99510 PHONE (907) 272-8218 FAX (907) 272-8211 US SURVEY #3200, LOT 2 MARILYN LYBARGER 177 COMFORT LN. INDIAN, AK 99540 7/6/2016 Scale 1"=50' P.I.D. NO X90-041-04 PERMIT NO. OSPXXXXXX Sheet 2 OF DESIGN PARAMETERS PRIMARY SEPTIC SYSTEM NO. BEDROOM: 4(600 gpd) TANK SIZE: 1,500g SOIL RATING: 0.8..GPD/SF AREA ROD: 750 SF SYS. TYPE: SHALLOW TRENCH 5'W x 2'ED (RF=0.7) LENGTH: 106 LF x 5/0.7 =757 SF USE: 2 EACH 53LFx5'Wx2' E.D., 4.0' TO TOTAL AREA: 757 SF NOTES: RECORD DRAWING OF EXISTING UNDOCUMENTED SYSTEM I NJC SITE PLAN PROFILE ABBREVIATIONS 2" R.I. TEST HOLE WELL RADIUS (P) PROPOSED - FILTER FABRIC EXISTING NEW SEPTIC Co CLEAN OUT NO.. 4" 0 DRAIN PIPE MONITOR TUBE NO. , TYP - DRAIN ROCK 6" ABOVE PIPE INV GEORGE PUTNAM TH#1 3/22/1994 2.0 OR - -I.o 1 it �InE=Tr�YE EL. as a-. yl EL. esa - SM DRAIN ROCK -4.0 EL 8L9 El 8]8 � SM -s.0 SM -10 elx NO GROUND WATER MONITORED - SECTION z 0Q 7 0 m 0 0 z 0 ow w w IC o L` wPIPE z wK 6" 3 EL. lal;- E INVI "PIPE ---I 96 9I: -1EL 1,500 GAL o EL 9e.z EL a9.9 wase t, TANK (E) E<. aza DRAIN ROCK 53.0 OF EACH DESIGN PARAMETERS PRIMARY SEPTIC SYSTEM NO. BEDROOM: 4(600 gpd) TANK SIZE: 1,500g SOIL RATING: 0.8..GPD/SF AREA ROD: 750 SF SYS. TYPE: SHALLOW TRENCH 5'W x 2'ED (RF=0.7) LENGTH: 106 LF x 5/0.7 =757 SF USE: 2 EACH 53LFx5'Wx2' E.D., 4.0' TO TOTAL AREA: 757 SF NOTES: RECORD DRAWING OF EXISTING UNDOCUMENTED SYSTEM I NJC SITE PLAN PROFILE ABBREVIATIONS WATER LINE / - TH TEST HOLE WELL RADIUS (P) PROPOSED - (E) EXISTING NEW SEPTIC Co CLEAN OUT NO.. MT MONITOR TUBE NO. , TYP TYPICAL PANNONE ENG SVC, LLC P.O. BOX 102954 ANCHORAGE, AK 99510 PHONE (907) 272-8218 FAX (907) 272-8211 US SURVEY #3200, LOT 2 MARILYN LYBARGER 177 COMFORT LN. INDIAN. AK 99540 Date 7/13/2016 Scale 1"=50' P.I.D. NO -690=041-04 PERMIT NO, OSPXXXXXX Sheet 3 O 3 Mtmicipalfty of Anchorage Department of Health and Human. Services 825 " L" Street 44 Rick Mystrom, P.O. Box 196650 Anchorage, Alaska 99519-6650 Mayor 343-4744 May 18, 1995 Marilyn R. Lybarger HC 52 Box 8802 Indian, Alaska 99540 Subject: US Survey 3200 Lot 2 Permit #SW940132, PID #090-041-04 The subject permit, issued May 18, 1994 by this office for a single family well and/or on-site wastewater system, has expired as of May 18, 1995. A new permit must be obtained from this office for a well and/or on-site wastewater system NOT installed by the expiration date. If you have drilled the well, a well log must be sent to this office for documentation of the installation and to close the permit. If a licensed Professional Engineer has inspected the installation of the on-site wastewater system, the original as -built inspection report must be sent to this office for review, approval and documentation. All inspection reports must be submitted within 30 days of construction completion. When applying for a new permit, the fees are: $320.00 for an on-site wastewater permit; $120.00 for a well permit and $440.00 for a combined on-site wastewater and well permit. If you have any questions, please call this office at 343-4744. cerely, am Cross, P.E. rogram Manager On-site Services enc: Copy of Permit cc: Lantech MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND HUMAN SERVICES P.O. BOX 196650, 825 "L" STREET, ROOM 502 ANCHORAGE, ALASKA 99519-6650 ON-SITE WELL AND WASTEWATER DISPOSAL SYSTEM PERMIT PERMIT NUMBER:SW940132 DESIGN ENGINEER:LANTECH OWNER NAME:LYBARGER MARILYN R OWNER ADDRESS:HC 52 BOX 8802 INDIAN, AK 99540 PARCEL ID:09004104 LEGAL DESCRIPTION: US SURVEY 3200 LT LOT SIZE: 98175 (SQ. FT.) NUMBER OF BEDROOMS: 5 THIS PERMIT: 5 2 THIS PERMIT IS FOR THE CONTRUCTION OF: DISPOSAL FIELD /SEPTIC TANK / WELL SYSTEM ALL CONSTRUCTION MUST BE IN ACCORDANCE WITH: PAGE 1 OF 1 DATE ISSUED: 5/18/94 EXPIRATION DATE: 5/18/95 1. THE ATTACHED APPROVED DESIGN. 2. ALL REQUIREMENTS SPECIFIED IN ANCHORAGE MUNICIPAL CODE CHAPTERS 15.55 AND 15.65 AND THE STATE OF ALASKA WASTEWATER DISPOSAL REGULATIONS (18AAC72) AND DRINKING WATER REGULATIONS (18AAC80). 3. THE ENGINEER MUST NOTIFY DHHS AT LEAST 2 HOURS PRIOR TO EACH INSPECTION. PROVIDE NOTIFICATION BY CALLING 343-4744 OR 343-4681 AFTER BUSINESS HOURS 4. FROM OCTOBER 15 TO APRIL 15 A SUBSURFACE SOIL ABSORPTION SYSTEM UNDER CONSTRUCTION DURING FREEZING WEATHER MUST BE EITHER: A. OPENED AND CLOSED ON THE SAME DAY B. COVERED, SEALED AND HEATED TO PREVENT FREEZING 5. THE FOLLOWING SPECIAL PROVISIONS. SPECIAL PROVISIONS: THIS SYSTEM MUST BE INSTALLED IN ACCORDANCE WITH THE REVISED DESIGN SUBMITTED_9Qi 5/10/94. RECEIVE ISSUED DATE: ` J DATE: / / RECEIVED Permit No. MAY 121994 Pageof W.O. 94L1118 Municipality of AnchoraWnicipality of Anchorage 4/8/94 DEPARTMENT OF HEALTH AND ftV"th,L ftTIr"?i,a�VIces Date ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 Anchorage, AK 99519-6650• Tel: 343-4744 On—Site Wastewater Disposal System/Well Inspection Report Legal Description: LOT 2 U.S.S. SURVEY 3200 PID No. SITE NARRATIVE LOT 2 U.S.S. Survey 3200 is bordered by TRACT B-1 (undeveloped) to the north, U.S.S. 1868 (undeveloped) to the south, LOT 1 U.S.S. Survey 3200 (residential) to the east, and LOT 3 U.S.S. Survey 3200 (residential) to the west. The lot topography is general characterized by sloping in a south easterly direction with a drainage stream flowing through the property and exiting on the south west side. Lot 1 has a well house located approximately 35' from the property line. Lot 3 appears to have no conflicting on—site services or topographical features. The site parameters considered for the development of this lot are identified on the Site Plan. The client's proposed lot development is a 1200 square foot addition increasing their total number of bedrooms to five (5). The existing well and unrecorded septic system are inadequate and will be abandoned and removed. Two test pits were dug on 3/22-23/94. A perched water table was encountered in test pit #2 ®8.0'. Monitoring tubes were placed in each test pit and rechecked on 3/25 & 4/2. Test pit no. 1 generally consisted of SANDY SILT with GRAVEL (SM) to approx. 4' below the existing ground surface underlain by SANDY GRAVEL with SILT to approximately 8'. Fractured rock with sand and silt was encountered to the end of the test pit, approx. 10'. On 4/2/94 1" of water was recorded in the monitering tube, approx. 10' below the existing ground surface. This test pit had a percolation rate of 7 minutes per inch between 4' and 5' below the existing ground surface. The second test pit generally consisted of SILT with SAND and GRAVEL (ML) to approx. 8.5' below the existing ground surface with a percolation rote of 45 minutes per inch between 4.2' and 4.7' below the existing ground surface. The percolation test hole was saturated overnight and the test was run on 3/23/94. The obsorbtion field size is based on 15 min/inch. Replacement field size is based on 45 per inch. The monitering tubes were checked on 5-6-94 and no water was observed. ■ LAND & CONSTRUCDDN SUR4£vORS-PLANNERS-ENGINEERS 440 WEST 9ENSCN BLVD. Y 103 ANCHORAGE, ALASKA 99503 (907) 562-5291 EBL COMP Fie I.... Permit No. Pageof Municipality of Anchorage W.0, 941_1118 DEPARTMENT OF HEALTH AND HUMAN SERVICES Date ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, AK 99519-6650• Tel: 343-4744 On—Site Wastewater Disposal System/Well Inspection Report Legal Description: LOT 2 U.S.S. SURVEY 3200 PID No. en C- 01 01 SITE PLAN RECEIVED MAY 12 1994 OT Z NEIGHBORS L WELL HOUSE Municipality of Anq* Rl OMO' ept. Health & Human S USS 3200 / / / EXISTING WELL INSTALL GREASE TRAP 1OD' RADUIS IN KITCHEN WASTE TO BE ABANDONED LINE. \ 1 PROPOSED WELL / / 1/ 100' RADUIS /1 e G HOUSE / I / / IAITI DDD/ME E PROPOSED WELL LOCATION \ l; \\\ i SGRA ( ROAD \ _ EXISTG //iNSrn��TRod/ // \ 7S 9'p01, E SYSTEM / srFvFk USS A 8680P�D II \ \ \ DRAINAGE UNOEVE STREAM — \ DRAINAGE STREAM / \100' RADUIS / LEGEND: SET FIND \ 5/8"RB W/CAPD 5/8" RB ® 3.25" AL.MON. MONUMENT & HUB & TACK O \ OVERHANG- ® — _ — ' • CLEANOUTS WOOD DECKS- CONCRETE- 0 MONITOR TUBES ASPHALT- = SEE CROSS GRAVEL- [ SECTION DETAIL SEPTIC STANDPIPES- QS (��� CONTOUR INTERVAL: 2 WATER WELL- APPRX. TEST PIT 1 LAND & CONSTRUCTION SURVEY S-PLANNERS-ENGINEERS/� — LOCA110N 4 NEST BENSON BLVD. A 103 SCALE. 1 — 50 DRAINAGE ANCHORAGE, N.ASKA , 99503 (907) 562-5291 rage, arvice s CD o Lo n � )) O O M 100'+ CONTRACTOR '0 €TELD VERIFY DISTANCE `CA 1 �9 ASSUME 0.0' ELEV _ AT STATION i*ODS � \ W 4 P�� OFq�gsa® y*'••gTH •�•�® >i ?Y �GREG6IGVM. PUTN AMS is ••� CE 7892 � • o® dere �•••••••••�®\� �� °'�rofesslo�o♦� TE ,`®®®cas♦ EBE CCNP 11 1080.ONG Permit No. Pageof Municipality of Anchorage W.O. 941_1118 DEPARTMENT OF HEALTH AND HUMAN SERVICES Date 5/10/94 ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 • Anchorage, AK 99519-6650• Tel: 343-4744 On—Site Wastewater Disposal System/Well Inspection Report Legal Description: LOT 2 U.S.S. SURVEY 3200 PID No. MANIFOLD PIPE INSTA> -m4v. .'C MONITOR TUBE — PERFORATED IN `-R $l3on�PIST1W 0.Ylord 5' WIDE SWALLOW TRENCH FINISH GRADE SOND SOLID PIPE MANIFOLD 4" PERFORTATED PIPE PERF PIPE 24" MIN, PIPE PERF DOWN HOLES DOWN LAID LEVEL SEPTIC . ___ I ilkllY7i CLEANOUT: AT MONITORING 2 BEGINNING OF TRENCHES TUBE- CAPPED AND AT EACH END 10' PERFORATED IN SEWER ROCK, SOLID ABOVE. 3/4" TO 1.5' SEWER ROCK 66.5' PLAN VIEW NTS 3/4" - 1.5" SEWER ROCK PROFILE (TYP) MONITOR TUBE - CAPPED. PERFORATED IN SEWER ROCK, SOLID ABOVE. BACKFILL 2" INSULATION 6" GRAVEL I 4" PERFORATED PIPE LAID LEVEL WITH HOLES DOWN AND I CAPPED ON END. SIDEWALL OF TRENCH 3/4" - 1_5" SEWER ROCK 5.0' B' WATER TABLE IMPERMF_ABLE 2" BLUE LAYER �- BOARD INSULATION END CAP 24' ASSUMPTIONS: RECEIVED 1. FIVE (5) BEDROOMS 2. ACCEPTING SOIL RATING: MAY 12 1994 190 SO. FT./BDRM 3. NO GROUND WATER AS OF 5-6-94 Municipality of N<t�:n.: REQUIRMENTS: Dept. Health R Humil." S� 1. 1500 GALLON SEPTIC TANK 2. ABOSORPTION BED TOTAL AREA: 950± SO. FT. 3. PLACE BOTTOM OF ABSORPTION BED AT 4.0' BELOW EXISTING GROUND SURFACE, INSTALL 2" BLUE FOAM BOARD INSULATION AND USE 24" MIN. OF NATIVE SOIL BACKFILL. 4. WASTE LINE FROM KITCHEN INTO GREASE TRAP IS OPTIONAL. TYP. CROSS SECTION NTS _ANO & CCNSTRUCVON SURVEYORS-RUNNERS-ENCNEERS 440 WEST BENSON BLVD. R 103 ANCHORAGE. ALASKA 99503 (907) 562-5291 'o -M6 A I2ry11 Hw n E9E CPAP Eia_ IC80.OXC MONITOR TUBE — PERFORATED IN IUTS - CAPPED ROCK. SOLID ABOVE. FINISH GRADE SOND PIPE PERF PIPE 24" MIN, HOLES DOWN 1500 GAL SEPTIC ___ TANK Rnon 3/4" - 1.5" SEWER ROCK PROFILE (TYP) MONITOR TUBE - CAPPED. PERFORATED IN SEWER ROCK, SOLID ABOVE. BACKFILL 2" INSULATION 6" GRAVEL I 4" PERFORATED PIPE LAID LEVEL WITH HOLES DOWN AND I CAPPED ON END. SIDEWALL OF TRENCH 3/4" - 1_5" SEWER ROCK 5.0' B' WATER TABLE IMPERMF_ABLE 2" BLUE LAYER �- BOARD INSULATION END CAP 24' ASSUMPTIONS: RECEIVED 1. FIVE (5) BEDROOMS 2. ACCEPTING SOIL RATING: MAY 12 1994 190 SO. FT./BDRM 3. NO GROUND WATER AS OF 5-6-94 Municipality of N<t�:n.: REQUIRMENTS: Dept. Health R Humil." S� 1. 1500 GALLON SEPTIC TANK 2. ABOSORPTION BED TOTAL AREA: 950± SO. FT. 3. PLACE BOTTOM OF ABSORPTION BED AT 4.0' BELOW EXISTING GROUND SURFACE, INSTALL 2" BLUE FOAM BOARD INSULATION AND USE 24" MIN. OF NATIVE SOIL BACKFILL. 4. WASTE LINE FROM KITCHEN INTO GREASE TRAP IS OPTIONAL. TYP. CROSS SECTION NTS _ANO & CCNSTRUCVON SURVEYORS-RUNNERS-ENCNEERS 440 WEST BENSON BLVD. R 103 ANCHORAGE. ALASKA 99503 (907) 562-5291 'o -M6 A I2ry11 Hw n E9E CPAP Eia_ IC80.OXC RECEIVED Permit No. Pageof MAY 12 1994 W.O. 931_1118 Municipality of Anqiorage unrgi 1' ¢ DEPARTMENT OF HEALTH AD.��m�RCES Date ENVIRONMENTAL SERVICES DIVISION erwces P.O. Box 196650 Anchorage, AK 99519-66500 Tel: 343-4744 On—Site Wastewater Disposal System/Well Inspection Report Legal Description: LOT 2 U.S.S. SURVEY 3200 PID No. NOTES: 1 ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH ON-SITE WASTEWATER TREATMENT AND DISPOSAL REGULATIONS OF THE EPA DESIGN MANUAL. 2 INSTALL NEW 1500 GAL SEPTIC TANK AS SHOWN ON THE DRAWINGS. RECORD INLET AND OUTLET ELEVATIONS OF THE TANK. TANK SHALL BE PLACED ON UNDISTURBED NATIVE SOIL. PLACE OUTSIDE PROTECTIVE WELL RADIUS. 3 ANY DEVIATION FROM THE DESIGN MUST BE AUTHORIZED BY THE ENGINEER PRIOR TO ITS INCORPORATION INTO THE SYSTEM. 4 CONTRACTOR TO LOCATE ALL UNDERGROUND UTILITIES, PROPERTY LINES, EXISTING WELLS, WATER WAYS, SURFACE AND SUBSURFACE DRAINAGE FACILITIES, LAKES, PONDS, AND OTHER FACILITIES REQUIRING SEPARATION DISTANCES FROM THE PROPOSED SEPTIC SYSTEM. NOTIFY THE ENGINEER OF ANY OBSERVED CONFLICTS PRIOR TO CONSTRUCTION. 5 NOTIFY THE ENGINEER 24 HOURS PRIOR TO COMMENCING WITH CONSTRUCTION. A MINIMUM OF TWO INSPECTIONS ARE REQUIRED. THE FIRST INSPECTION SHALL BE OF THE SUBGRADE, PRIOR TO PLACING SAND FILETER. THE SECOND INSPECTION SHALL BE AFTER THE PLACEMENT OF GRAVEL, DISTRIBUTION PIPING, STANDPIPES, TANK, AND OTHER COMPONENTS AS SPECIFIED. 6 CONTRACTOR SHALL DELIVER TO THE ENGINEER A SET OF RED -LINED, AS -BUILT DRAWINGS SHOWING ALL DATA AS SPECIFIED IN THE ON-SITE WASTEWATER TREATMENT AND DISPOSAL REGULATIONS WITHIN 30 DAYS OF THE FINAL INSPECTION. INVERTS AND SWING TIE LOCATES SHALL BE TO THE NEAREST TENTH OF A FOOT. THESE AS-BUILTS SHALL BE USED TO DOUBLE-CHECK THE ENGINEER'S INFORMATION PRIOR TO SUBMITTAL TO DHHS. 7 STAKE ALIGNMENT OF SYSTEM WITH MARKERS SHOWING THE PROTECTIVE DISTANCES FROM WELLS AND OTHER BODIES OF WATER PRIOR TO BEGINNING INSTALLATION. g A SOILS LOG MUST BE PROVIDED OF THE TRENCH WALLS AND BED OF SUBSURFACE DISPOSAL FIELD IF THE SOILS DIFFER FROM CONDITIONS UPON WHICH THE PERMIT WAS BASED. 9 ALL EXCAVATION DEPTHS ARE ADVISORY. THEY ARE TO BE VERIFIED AND MAY BE MODIFIED BY THE ENGINEER. 10 SLOPE ALL FILL MATERIAL TO DRAIN AT 2% MIN. SLOPE, AND 3:1 MAX SLOPE, AND IN SUCH A MANNER THAT PONDING AT OR NEAR THE DRAIN FIELD DOES NOT OCCUR. THE FILL SHALL BE LEFT AT 6" HIGHER THAN SHOWN TO ALLOW FOR SETTLEMENT. SEED SURFACE AFTER COMPLETING INSTALLATION. 11 ALL PIPE SHALL BE PVC CONFORMING TO ASTM D3034 OR ENGINEER -APPROVED EQUAL. .♦e®®®®`, 12 MATERIAL USED AS FILL SHALL BE CLEAN AND FREE OF ORGANICS, F:OFA:�4 TRASH AND CONSTRUCTION DEBRIS. ®,`P•• ON 13 RECORD THE FINISH GROUND ELEVATION OVER TOP OF BED. / * :/4 �7.�L,1�7O LAND k CONSMUCi SURVEYMt PLMNMS-ENQNEERS 440 WEST BENSON BLVD. $ 103 ANCHORAGE, ALASKA 99503 (907) 562-5291 ESE CMP rne. IDSD.DWG • ae PERFORMED FOR LEGAL ®'POgE IiJ�ERr °SEB. •��+ RECEIVED ,�: ?s� Municipality of Anchorage /�Y DEPARTMENT OF HEALTH & HUMAN SERVICES, 2 1994 r' 825 "L" Street, Anchorage, AlaskanD 9MOOrOFWY Of Anchora ''�? °SEC R' SOILS LOG — PERCOLAWN IYW & Human Se 'c r'°° CE 7892 aP.r' DATE PFRFOR14ED: 2 V.S,S SotJey 32-v° Township, Range, Section: (FEET) I D. pkv iL SQ" I J wf� rowed '�rr�a.2 rirgbn'� c S W" Y C-K-ztje I w;'wx s',4 (sm W; [4.1, G Af () �vST Q r'r' COMMENTS SLOPE bit t FLAN WAS GROUND WATER I ENCOUNTERED? NO S IF YES, AT WHAT L DEPTH? O 20 P E Depth to Water After p MonitodngT Date: n PERCOLATION RATE 7 (minutes/inch) PERC HOLE DIAMETER 8 TEST RUN BETWEEN )' FT AND 5 FT PERFORMED BY: CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: 72-008 (Rev. 4/85) +� Municipality of Anchorage �y DEPARTMENT OF HEALTH & HUMAN SERVICES �•� ' • •' T 825 "L" Street, Anchorage, Alaska 99502-0650 Pt' co • M. PUT?4AM e �? SOILS LOG — PERCOLATION TESTS CE > 78s2 PERFORMED FOR: DATE PERFORP4ED: �� �h •Ri LEGAL DESCRIPTION: LoA 2 0. 3.5. Suroev g2DO Township, Range, Section: DEPTH SLOPE SITE PLAN (FEET) INTI—I 3- 6- II 6 C�L> 7 9 r� 11 12 13 14 15 16 17 18 19 20 >z^� 4 511 �I '2�[tro Jt¢ WAS GROUND WATER ENCOUNTERED? des S T WHAT (orf- L J P E r ae f ; Date: % qy IF YES, A DEPTH? Depth to Wale Monitoring? PERCOLATION RATE �- (minutes/inch) PERC HOLE DIAMETER TESTRUNBETWEENJ=-FT AND �� FT COMMENTS Ilona-6J`Fn rl W%I!-G,' °P- 0.,F , AI,� -)Y-IC-r,C" �j , I PERFORMED BY: 1 CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: 72-008 (Rev. 4/85) II MAMpAMIT 3)M11j17CD 'U0M7'&KQ 1201 Ramona St. 99515 ANCHORAGE* ALASSSA ,344-7714 wclsl -11 S aLc--� (0gL)-oj4\-01A SIX INCH WATER WELL DRILLED ----------OUT TO THE DEPTH OF 205 feet. DRILLED AT THE RATE OF 524.0) PER FOOT. Steel casing seated out to 4J ft. PROPERTY OWNER ''1r• Tom Lybarger 653-7726 'afl�l-Y - DRILLER Bernie Claus of Rampart Drilling Works. WELL LOG: 0 - 17' Coarse gravel & small boulders. 30$ silty material. 17 - 29' CingLomerate. A broken weathered fractured rock material. 29 - 40' Bedrock. A fairly soft sedimentary rock. Casing driven to 40 ft. 40 - 205' Bedrock. A very hard sedimentary rock. 1/2 gpm water yield showing by 65 ft. From thin fissures & cracks in the bedrock. By 165 ft a total of 2 gpm was showing out of granular type rock. From 173 to 176 ft. an additional 2 gpm was showing coming out of a porous type rock. At this depth, 4 gpm was produced at short duration pumping (30 minutes) then the production dropped down to about 3 gpm. By 205 ft., (196-199) production increased to a total of steady 8 gpm. (Two hours of pumping.) During short term pumping (30 minutes) gpm indicated a steady ten. A 1/2 horse submersible pump should be installed at the 160 ft. level. But a 3/4 horse pump, if used, should be installed at about 180 ft. 25 ft. off bottom. The water has been pump almost crystal clear, but will pump a slight amount of silt in the first two hours, on installation of sub pump. Water recovery is back up to within 35 ft. of surface. No mob or demob cost. This Well paid for in full with 30 ft. no charge. COST INCLUDES ALL LABOR AND MATERIAL FOR COMPLETION OF SAID DRILLING. This Water Well guaranteed & certified by Rampart Drilling. WRITE CHECK PAYABLE TO RAMPART DRILLING WORKS FOR THE SUM OF ---------- THANK YOU VERY MUCH. BERNIE CLAUS OF RAMPART DRILLING WORKS DATE June 17, 199h SERVICE CHARGE 0 F lyn% PER MONTH WILL BE ASSESSED ON PAST DUE ACCOUNTS. 7/0 (�\O t Ce (11; ;'0RUV1 Municipality of ranchorUL z I 201 On -Site Water and Wastewater Progr(907)343-7904 f r Ac 5� Certificate of On -Site Systems Approval Parcel f:D. 090-041-04 - Expiration Date: l 1. GENERAL INFORMATION Complete legal description US Survey #3200, Lot 2. Location (site address) 177 Comfort Lane Current Property owner(s) Marilyn R Lybarger Day phone Mailing address Real Estate Agent 552 W Tam Oshanter Drive. Pheonix, AZ 85023 2. TYPE OF DWELLING: x1 Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 4 Day phone 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Individual Well 0 Individual 0 Individual Water Storage ❑ Holding Tank ❑ Community Class Well ❑ Community ❑ Public Water System ❑ Public Sewer ❑ WaiverNariance request Received by: Date: -711 Y l d10 ( (0 COSA to be released to the engineer, unless otherwise requested by the engineer, - COSA Fee $ Waiver Fee $ Date of Payment 1 AL1 ifo Date of Payment Receipt Number u tRl�1 Receipt Number COSA# Waiver# 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown b€low, kverify that my4n4eStibatlon, Used on procedures outlined in the Certificate of Onsite Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. In conducting an adequacy test, I attempt to provide a thorough, conscientious engineering analysis of the system in accordance with MOA COSA guidelines and regulations. The reported results describe the performance of the system under the conditions encountered I the time of the test, and separation distances measured to readily identifiable features. The operational life of all wells and septic systems depend ,nn 1F1E•local oil'; condition, ground water levels that may fluctuate during the year, and the water usage of the family being served by the syst* 4m. ese yoriditions are outside the control of the evaluator of this system. All systems eventually fail and satisfactory test results do At gbarahiee future_, performance of the system, nor do they guarantee that there are no hidden defects or encroachments. Therefore we cannot$rovide any warranty for future performance, nor can we estimate remaining life of the system. The content of this report is for the sole benefit of the owner listed above. Name of Firm Pannone Engineering Services LLC Address P.O. Box 100217, Anchorage Ak. 99510 Engineer's Printed Name Steven R Pannone 6. DSD SIGNATURE System #1 Approved for `1 bedrooms System #2 Approved for bedrooms Disapproved Phone (907) 272-8218 Date 7/11/2016 S}even R. ririorie CE -8149 i Conditional approval for bedrooms, with the following stipulations: By: 1` Original Certificate Date: / 7� [ -C The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 7. ATTACHMENTS: COSA Checklist X Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other COSA blue sheet f c If more than 1 septic system is on the lot: COSA Checklist # -L_of +_ Structure served by this system Certificate. of Ori=Site Systems Approval Check itt Legal Description: US Survey #3200, Lot 2.parceLlDc 090-041-04 A. WELL DATA Well type Private If A, B, or Cprovide PWSID # Well Log (YM) Y Date completed 6/17/94 Sanitary seal/N Y - (Y ) _ Wires properly protected (YIN) Total depth 205 ft. Cased to 40 ft. Casing height (above ground) FROM WELL LOG AT INSPECTION Date of test 6/17/94 4/20/16 Static water level 35 ft 33 W611 production 8 g.p.m. 7.9+ 9 P m- WATER SAMPLE RESULTS: Coliform Ne9 colonies/100 mL Nitrate -0.110 mg/L Arsenic NU ug/L Date of sample: 6/24/16 Collected by: PES B. SEPTIC/HOLDING TANK DATA TankType/Material Septic/Steel Unknown installed Tank size 1500 gal Number of Compartments 2 Cleanouts (Y/N) Y Foundation cleanout (YM) Y Depression over tank (Y/N) N High water alarm( (Y/N) N Dateofpumping t V ��) Pumper 7 -f �ii�i (S�A �J C. ABSORPTION FIELD DATA Unkng" z 0:8 g.p.d/sf Date installed Soil rating (g:p.d./ft2 or ft /bdrm) System type Shallow Trench Length 53 3.7 ft. Width id�� ft. Gravel below pipe 2 ft Total depth_ ft. , absorption of lea flz Monitoring tube Y— Depression over field .4120/20x1: Y Date of adequa y tot + - %Results (Pass/Fail) For 4_: badrooms Fluid depth in absorption field before test 0/ Q in. Water added:687 gal. New depth 0 0 in. Elapsed Time;, 90 min: Final fluid depth 0 ,O in. Absorption rate >= 600+ g.p.d. Any rejuvenation treatment (past 12 mo.) (Y/N & type) N If yes, give date D. LIFT STATION Date installed "Pump on" level at_ Datum Size in gallons - Manhole/Access (Y/N) in. "Pump off' level"at in. High water alarm level at in. _ Cycles tested Meets alarm & circuit requirements? E. SEPARATION DISTANCES, WELL ON LOTTO: ' Septic tank/Ilft station on lot 100+ On adjacent lots 1-00+ Absorption field on lot 100+ On adjacent lots 100+ Public sewer main 75+ Public sewer manholelcleanout 100+ Sewer /septic service line 25+ Holding tank "0+ - Animal containment areas 50+ Manure/animal excrete storage areas 100_ -+ SEPTIC/HOLDINGTANK ON LOTTO: Building foundation 5+ Poperty line 5+ Absorption field 5+ - Water main 10+ Water service line 10+ Surface water 100+ Wells on adjacent lots 100+ ABSORPTION FIELD ON LOT TO: Property line 10+ Building foundation 10+ Water main 10+ 10+ 100+ Water Service line Surface water Driveway,,parking/vehiclestorage- Curtain drain 50+ Wells on adjacent lots 1.00+ F. COMMENTS G. ENGINEER'S CERTIFICATION I certify that I have determined through field inspections' and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date,' Engineer's Printed Name Steven Pannone Date 7/1,1 L2016 COSA canary sheet -2-6-1 5.doc o 0 FIND ALUM PIPE UTILITY POLE J79*50'00"" - 330.Op FND BRASS OAP UTILITY POLE +� Lot 2 _ USS 3200 r O N / 2 / � w oON, IN /IN oPq0 / LOG HOUSE I Z Well ''' 0 EATING ME ® RISERT 1100' RADIUS / PORCH ?<4, re25•�y EMENT PAD /VN71�ed1 b \ +02.4' '19,00"W GRAVEL DRIVEWAY I 1337 ®"--R�Rs i \ EXISTING WELL \ -\ 100' RADIUS FND REIRM W/ CAP DRAINAGE STREAM / 100' RADIUS / GRAPHIC SCALE a u sDMMMMMMMO so 120 ( IN FEET ) I hereby certify that I have surveyed the following described property. "LOT 2, USS 3200' Anchorage Recording District, Alaska, and that the improvements situated 'thereon are within the property lines and do not overlap or encroach on the property lying adjacent thereto except as indicated hereon, that no improvements on the property lying adjacent thereto encroach on the premises in question and there are no roadways, transmission lines, or other visible easements on said property except as indicated hereon. 28 Apr 2016 FOR: PARAGON PROPERTIES dfaska06 (907) 242-5287 �r aonsDve[iax su7vcys c7.. {?41'86t SN203 SCALE DATE DRAWN BY Axborlpe, Akye O0.I P0344-D50Ci 1" = 60' 4/27/2016 AMV