Loading...
HomeMy WebLinkAboutTIMBERLUX #1 BLK D LT 4TI*mberlux #1 Block D Lot 4 #018-271-18 nspecion epo Municipality of Anchorage MAN 12 2014 On -Site Water and Wastewater Program • (907) 343-7904 Page 1 of 3 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP131464 PID Number: 018-271-18 Dwelling: 0 Single Family (SF) ❑ Duplex (D) ❑ Multiple (SF and/or D) Project: ❑ New 0 Upgrade Name: SCOTT POWELL ABSORPTION FIELD ❑ Deep Trench ❑ Shallow Trench K Bed ❑ Mound Address 15320 CURVELL DR., ANCHORAGE, AK ❑ Other Phone Number of Bedrooms Soil Rating Total depth from original grade 4 0.7 GPD/SF 3.2 Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade .5 Ft. Gravel depth beneath pipe 0.5 Ft. Subdivision Block Lot TI MBERLUX # 1 D 4 Fill added above original grade 2-2.5 Ft. Gravel length 58 Ft. Township Range Section Gravel width 15 F] Beds: Number of Lines 3 Distance between lines 5 Ft. SEPARATION DISTANCES To Septic Absorption Holding Sewer Total absorption area Number of trenches Dist. between trenches From Tank Field Lift Station Tank. Line 870 Ft= NA I NA Ft. Well >100' >100' NA >25' TANK ❑ Septic ❑ S.T.E.P. ❑ Holding ❑ Other Manufacturer Capacity Gal. Surface Water >100' >100' NA Material Number of compartments Lot Line >10' >5' NA NA Foundation >10' >5' NA LIFT STATION Manufacturer ANCHORAGE TANK Capacity 500 Gal. Curtain Drain >50' >50' NA Remarks EXISTING DRAIN FIELD ABANDONED Pump on level at 25 in. Pump off level atHigh 44 in. water alarm at 22.5 in. PER UPC REQUIREMENTS. BAFFLES REPLACED EXISTING CONCRETE TANK. Pump make and model ORENCO Electrical Inspections performed by MOA PIPE MATERIAL House to tank 3034 Tank to SCH40 drainfield Installer A+ HOME SERVICES Draintield SCH40 CO/MTF810 Inspector LARS SPURKLAND BENCH MARK (Assumed elevation) 100 it Inspeection to 2/5/14 2/7/14 Loscription cation and de ction 3'd 2/10/14 2�d a BOTTOM SIDING SW HOUSE CORNER COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL En q&%S" At Conditional Approval: /fs d e_r Date OF X i:1 �• y i3bC- vie '0 101,:: UKLADF..°� H�i Approved Date Vo A nspecion epo TH SWING TIES A 8 ST. C.O. C 165' 66.0' S T. C.O. D 10.5' 64.5' DBL. C.O. E 15.0' 61.0' L.S. M.H. F 44.0' 38.0' DF. MT. G 116.5' 35.0' DF. MT. H 142.5' 67.0' Eur.=101.8' H2O IIEY.=9d4' gam aEV.=9a9' CURV RABBIT CREEK ROAD 25 0 25 50 n 100 125 150 SCALE.• I' = 100 FT. Monitor 2' Insulation —Slit Barrier NTI SCALE NOT£.• THIS IS NOT A SURVEYED PUT. WELL A• SEPTIC LOCATIONS TAKEN FROM ON-SITE WATER AND WASTE WATER DEPARTMENT DOCUMENTATKIN. ALL LOCATIONS SHOWN ARE APPROXIMATE. r0 ELEKAXW N TS Eur.=.ax' Filter Sand 5006 STEP TANK 0 SPURKLAND U. BENCH MARK BOTTOM SIDING SW HOUSE CORNER -W441j;: S V` * ASSUMED ELEVATION 100' SPURKLAND ENGINEERINGRECORD DRAWINGS 203 W 15TH. AVENUE TIMBERLUX #1 BM D LOT 5 ANCH. AK. 99501 JIM BOWS DATE: MARCH 5, 2014 (907) 279-3916 6240 E. 111 AVE., ANCHORAGE, AK 99516 SHEET: 1/1 GRID.3136 PERMIT #17SP131464 P1B # 018-271-18 TIMBERLUX#IBBL44SB, BWG On -Site Wastewater Disposal System Permit MUNICIPALITY OF ANCHORAGE Development Services Department On -Site Water & Wastewater Program 4700 Elmore Road, PO Box 196650 Anchorage, AK 99519-6650 Telephone: (907) 343-7904 Permit Number: OSP131464 Tax Code Number: 01827118000 Work Type: Septic Permit Effective Dates: December 18, 2013 to December 18, 2014 Design Engineer: SPURKLAND ENGINEERING Subdivision: TIMBERLUX #1 Site Legal Address: TIMBERLUX #1 BLK D LT 4 G:3136 Owner/Address: POWELL SCOTT E & CATHALEEN M 13001 FLORAL LANE ANCHORAGE AK 995163140 Site Mailing Address: 15320 CURVELL DR, Anchorage This permit is for the construction of: N Disposal Field Y Septic Tank N Holding Tank Lot Size in Sq Ft: 54973 Total Bedrooms: 4 N Privy N Private Well N Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80). 3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either: A. Open and Close on the same day. B. Covered, sealed, and heated to prevent freezing. Received MUNICIPALITY OF ANCHORAGE Community Development Department Phone: 907 -343 - Development Services Division Fax: 907-343-7997 On -Site Water & Wastewater Program ON-SITE SEWER/WELL PERMIT APPLICATION Parcel I.D. 018-271-18 Property owner(s) SCOTT POWELL Mailing address 15320 CURVELL DR., ANCHORAGE, AK 99516 Site address SAME Day phone 575-7911 Legal description (Sub'd., Block & Lot) TIMBERLUX #1 BLOCK D LOT 4 Legal description (Township, Range & Section) Lot Size Sq. Ft. Number of Bedrooms 4 APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: IS all that apply) Absorption Field ® Initial ❑ Single Family (SF) El Septic Tank El Upgrade El (w/wo ADU) HoldingTank ❑ Renewal nn Duplex (D) ❑ ° g - Multiple Dwellings ❑ Privy El (V agd/or D) Private Well ❑ t6 Water Storage ElL)CC 2013 THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR: Distance: I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes. of property owner or authorized agent) Permit/Rush Fees: Waiver Fees: Date of Payment: /Z� 7�"3 Date of Payment: Receipt Number: / 5�ry ,owos� Receipt Number: Permit No. 65 P Ib 14�`( Waiver No. permit App_9-1-12.doc Environmental Consulting and Design SEPTIC SYSTEM DESIGN TIMBERLUX #1 BLOCK D LOT 4 Municipality of Anchorage December 16, 2013 Development Services Department On Site Water and Wastewater Program 4700 Elmore Road Anchorage, Alaska 99519 Subject: Septic System Installation Permit Renewal 15320 Curvell Dr. Ladies and Gentlemen: I am writing to request a renewal of the septic system installation permit for the above referenced property. The original permit application was submitted by Flattop Technical Services and issued on August 13, 2009, permit # SW090149. A site inspection was conducted on December 12th, 2013. Both test holes groiund water monitors tubes were located. Ground water was observed at a depth of 7.5 feet in TH#1 and 9.5 feet in TH#2. The design as approved does not require any modifications. If you have any questions or concerns, please contact me at 279-3916. Sincerely, ar purkland, P.E. Civil Engineer 203 West 150h Avenue Suite 203, Anchorage, AK 99501, Phone: (907) 279-3916 Fag: (866) 354-1597, Lspurkland@gci.net MUNICIPALITY OF ANCHORAGE Development Services Department On -Site Water 6 Wastewater Program 4700 South Bragaw Street P.O. Box 196650, Anchorage, AK 99519-6650 (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT Upgrade Date Issued: Aug 13, 2009 Expiration Date: Aug 13, 2010 Permit Number: SWO90149 Parcel ID: 018-271-18 Legal Description: TIMBERLUX #1 BLK D LT 4 Design Engineer: 0019 FLATTOP TECHNICAL SERVICES Site Address: 015320 CURVELL DR Owner Name: SCOTT POWELL Lot Size: 0 SO. FT. Owner Address: POB 233252 Total Bedrooms: 0 Permit Bedrooms: 4 ANCHORAGE. AK 99523-0000 This permit is for the construction of: ❑-1 Disposal Field ❑✓ Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations (18AAC80 ). 3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. Received By: Date: 61241 /'C"'9 Municipality of Anchorage 1.1 Development Services Department Building Safety Division On -Site Water and Wastewater Program ` 4700 Elmore Road P.O. Box 196650 Anchorage, Alaska 99507 www.muni.org/onsite (907)343-7904 ON-SITE SEWERNVELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. _ 01 & — 2 71 _ iF Property owner(s)�-off Poc,,. p Day phone 2'rY-1997 Mailing address P•o. ea,i 23 2S Zip Code9952 ? Site address /S3 20 ('ac r 4.N D ., { Zip Code Legal description (Sub'd., Block & Lot) 1.4,1 y ls'/k `p� TS/ux # / Legal description (Township, Range & Section) Lot Size Sq. Ft. Number of Bedrooms '7/ THIS APPLICATION IS FOR (0 all that apply): THIS APPLICATION Is AN: Absorption Field ® Initial E3Septic Tank ® Upgrade 12 Holding Tank ❑ Renewal El ❑ Private Well ❑ Water Storage ❑ I certify that the above information is correct. I further certify that this application is being made for a Single Family Dwelling and is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit/Rush Fees: S?,o Waiver Fees: Date of Payment: S - / O — O Ci Date of Payment: Receipt Number: _O 0 S_ cl q Ci Receipt Number. (Rev. 11/05) CML 6 ENVIRONMENTAL ENGINEERING • ENERGY CONSERVATION & ANALYSIS TED MOORE, P.E. 14530 ECHO CANYON ROAD PHJFAX: (907)345-1355 ANCHORAGE, AK 99516 E -Mail: tgmoore@gcl.net August 10, 2009 M.O.A. DSD P.O. Box 19-6650 Anchorage, AK 99519 Dear Sirs: The purpose of this letter is to provide a design narrative in support of our application to upgrade the wastewater disposal system serving the 4 -bedroom residence on Lot 4, Block "D", Timberlux S/D, Unit # 1, located at 15320 Curvcll Drive. Soils logs, perc test results, a site plan, design drawings and specifications are enclosed for your review. As can be seen from the soils log for test hole 42, the native soil between 1.25 and 9.5 feet below ground level is sandy gravel with a measured percolation rate of less than one minute per inch. Although no groundwater was observed at the time the test hole was dug or during the ensuing week, relatively shallow seasonal groundwater tables have been documented in the general area. According we propose to construct a shallow bed -type absorption system with a two -foot thick sand filter to position the bottom of the sewer gravel at a depth of 0.75 feet below original ground level. Using a soil application rate of 0.7 gpd/sq. ft. as specified in the wastewater ordinance for filter sand, the required absorption area for a 4 -bedroom residence is (4 x 150Y0.7 = 858 square feet. The proposed 15' wide by 58' long soil absorption bed has a basal area of 870 square feet. The topography of the lot is almost level, with about a 2% slope downwards towards the WNW. In order to construct the system parallel to existing contours of the land and avoid conflict with an existing shed, the south end of the absorption bed will extend into a platted 20 -foot wide "screening and fencing easement". I discussed this configuration with Laura in the Municipal R.O.W. section and was informed that such an easement is not a concern of theirs, so no R.O.W. easement would be required. I also discussed this with Jeff Poet in your office and he concurred that there should not be any objection to having a portion of the absorption bed extend into this easement. According to Municipal records, the existing 1250 -gallon, single compartment, concrete septic tank was installed in 1970 at a distance of approximately 90 feet from the well on the same lot. At that time the required separation distance from a private well was 50 feet, so no waiver was or should be required for continued use of the tank. A Municipal waiver was issued in 1992 allowing the more recent well on Lot 3 to be approved at a distance of 85 feet from this septic tank. Since concrete tanks do not necessarily deteriorate rapidly with age, the property owner would prefer to utilize this septic tank in conjunction with a new 500 -gallon lits station located outside the 100 -foot protective radii of all wells. We propose to do so, providing an inspection of the tank conducted at the time of bed construction reveals that the tank is still in sound condition, does not leak and has a functional outlet baffle. If the existing septic tank is found to be no longer in acceptable condition, it will be properly abandoned and replaced with a new 1500 -gallon STEP tank located more than 100 feet from all wells. The proposed system will have no significant impact on present or future water supply and wastewater disposal systems serving adjacent properties, nor will it have any significant impact on reserved space - surface and subsurface, or on drainage. Please give me a call at 345-1355 if you have any questions on this submittal. Sincerely, rev l3?o-...c, Ted Moore, P.E. LOT 3 �\ CURVELLDRIVE — — — v - --�' LOT 4, BLOCK "D" TIMBERLUX #1 1 - , R = 100, WELL V , ` C 1 1 1 `♦ 1 1 •♦ 1 1 , 1 1 . 1 1 1,4-BDRMI !HOUSE R=100' INSPECT Or ABANDON EXISTING CONCRETE TANK •i INSTALL 500 -GAL. , LIFT STATION or 1500 -GALLON STEP TANK CONSTRUCT 15' WIDE x 58' LONG SOIL ABS. BED m` W. 0.8 GVL b 2.0 ISF SAND �— T.H_T.H. #2 r --------------- 20 SCREENING AND FENCING ESMT_ ----------- RABBR CREEK ROAD FA �. 9IH # ...................... 4 i THEODORE F. MOORE I_ CE -3589 1 L40fe ' N ♦' I ` I HOUSE 1 I I I , I � I I ' WELL I , I , I , LOT 5 I , I ' I . ,r ' SEPTIC AREA ° i 1.25" DIA. SCHED. 40 PVC w 3/16" HOLES IN BOTTOM SPACED 2' O.C. -'--------------------- --------------- I LOT 4, BLOCK "D", TIMBERLUX SID, ADD'N #1 SEPTIC SYSTEM UPGRADE SITE PLAN FLATTOP TECI INICAL SERVICES 1 INCH= 50 FEET 14530 ECI10 CANYON ROAD DRAWN BY TFM 1 ANCI IORAGE, ALASKA' WELD I W I f(un, i ek I I I ci CURVELLDRIVE — — — v - --�' LOT 4, BLOCK "D" TIMBERLUX #1 1 - , R = 100, WELL V , ` C 1 1 1 `♦ 1 1 •♦ 1 1 , 1 1 . 1 1 1,4-BDRMI !HOUSE R=100' INSPECT Or ABANDON EXISTING CONCRETE TANK •i INSTALL 500 -GAL. , LIFT STATION or 1500 -GALLON STEP TANK CONSTRUCT 15' WIDE x 58' LONG SOIL ABS. BED m` W. 0.8 GVL b 2.0 ISF SAND �— T.H_T.H. #2 r --------------- 20 SCREENING AND FENCING ESMT_ ----------- RABBR CREEK ROAD FA �. 9IH # ...................... 4 i THEODORE F. MOORE I_ CE -3589 1 L40fe ' N ♦' I ` I HOUSE 1 I I I , I � I I ' WELL I , I , I , LOT 5 I , I ' I . ,r ' SEPTIC AREA ° i 1.25" DIA. SCHED. 40 PVC w 3/16" HOLES IN BOTTOM SPACED 2' O.C. -'--------------------- --------------- I LOT 4, BLOCK "D", TIMBERLUX SID, ADD'N #1 SEPTIC SYSTEM UPGRADE SITE PLAN FLATTOP TECI INICAL SERVICES 1 INCH= 50 FEET 14530 ECI10 CANYON ROAD DRAWN BY TFM 1 ANCI IORAGE, ALASKA' AUGUST, 2005 NOTE: THIS IS NOT A SURVEYED PLAT. ARE 2.5 5 15 5 2.5 1.25" DIA. SCHED. 40 PVC ..A. w 3116" HOLES IN BOTTOMS 58 SPACED 2.0' ON CENTER ....... .................. ... .....5 . . . .. O M.T.1 .................. . , . , .......... _.. „ ............ O M. T.!. 4' D-3034 FROM NEW FDN. C.O.OR EXISTING "A" Llw- SEPTIC TANK NEW 1500 -GALLON STEP TANK (OR 500 GALLON LIFT TANK (d existing concrete tank found to be in good shape) 1.25" DIA. HDPE OR SCHED. 40 PVC PLAN VIEW SCALE 1" = 10' MONITOR TUBE 3 2.5 5 ORIGINAL GROUND _/ 2.8 I 2 .11 y,0' ISF FILTER SAND - NATIVE GRAVEL 15 CROSS-SECTION "A -All SCALE: 1" = 5' 15' -WIDE x 58' LONG SOIL ABS. BED w. 0.8' WASHED GRAVEL 8 2.0' ISF SAND UNDER DISTRIBUTION PIPES AV AV 49 m � it ........................ j p : THEOOORE F. IIOORE i ., CE -3589 �A 1 ere ••.••• ��� , \ qb',E?ofe ss 10 SOIL COVER RIGID INSULATION 5 , 2.5 FILTER FABRIC 0.8' WASHED SEWER GRAVEL 1.25" DIA. SCHED. 40 PVC w 3116" DIA. HOLES @ 2.0' LOT 4, BLOCK "D", TIMBERLUX S/D # 1 SEPTIC SYSTEM UPGRADE _ PLAN AND CROSS-SECTION FLATTOP TECHNICAL SERVICESSCALD: AS SI [OWN 14510 ECI10 CANYON ROAD DRAWN BY: TFM ANCI IORAGE, AK, 99516 AUGUST. 2009 FLATTOP TECHNICAL SERVICES 14530 ECHO CANYON ROAD ANCHORAGE, ALASKA 99516 TEST HOLE # 2 SOILS LOG - PERCOLATION TEST LEGAL DESCRIPTION: _Lot 4,, Block •Di_Thmbedux SID DATE PERFORMED: _July 28, 2009 PERFORMED FOR: _-Scott Powell_ DEPT (feet: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 17 18 19 VES PL SM Reddish sandy Wm GP Clean, slightly silty sandy gravel Dry GP/GM Somewhat silty sandy gravel Dry, thin lenses of SM SM Bmwn/Blue sand w. roots 8 sticks B.H. SLOPE 1% Depth to Groundwater Date _No Groundwater- 7128/09 _Monitor tube dry, 8/6/09- -- -----_�-1-_� QuoOF ®� A Lip �• N1111111 "y AOTHL�#A ��. 1/1/1 • • 111111111�1C`1.11•/1/1�/1'(Z 1�M .}1/%"4ir'}1: •.1111 �1rrt ®it�1 �. HEODORE F. LIOCRE: SITE PLAN Date _ Reading Clock Time N (m 7/27_ 5-gallonpresoak- .----#2 _ _11:34:20 __ 1135:20 _ - _ - _ _11:36:20 11:36:40- - _— _2nd 5-gallogs6ak-_ -11:40 - -- - - -- - #1 _ #2 11:41 _1 1;42 -- -- --#3 — -11:43 — - -11:43:30 - ---__-- i LOT 4 BLOCK -W T ABERLUX H T.H: #1 Ne Time inutes) 7 .. 1. 0.33 2% Percometer Net Drop Reading (inches) -- - --- _-_2E 21 3/8 —46/8- 5/8_18 --- 1 3518 -_163!4 _ = dry =. --21.1/4 31/4- -31/4- 83/8_ 83/8_ 27/8 63/4 --dry PERCOLATION RATE «1— (minutesMch) PERC HOLE DIAMETER 8 TEST RUN BETWEEN_2.25-FT AND _2.75_-, FT COMMENTS: PERFORMED BY FLATTOP TECHNICAL SERVICES. I _TAy,P eoplj� CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: 6 /!O / 09 FLATTOP TECHNICAL SERVICES 14530 ECHO CANYON ROAD ANCHORAGE, ALASKA 99516 TEST HOLE # 1 SOILS LOG - PERCOLATION TEST LEGAL DESCRIPTION: —Lot 4, Block'D',TlmbedUx SID DATE PERFORMED: __July 28,.2009 - PERFORMED FOR: -.__Scott Powell _ DEPTH PL (feet) Net Drop (mches) 1 - SM Reddish sandy loam 2- GP Clean sandy gravel 3 - SM Silty fine sand 4- Damp, w. streaks 5- -6- 6- GP Sandy gravel Dry 7- e - SM Brown/Blue silty sand 9 Damp, cohesive, w. old sticks 10" GP/GM Somewhat silty Depth to Groundwater 11 + B.H. Gravel —No Gri _Monitc 12 --- 13- 14 3-14 = 15- 16 -i I 17 18 j I i 20-1 I SITE PLAN LOT 413LOCK'V TIYBERLUX H 1% T.H: Date NmN 48 54 T.N. i #2 I 2% Date Reading Clock Time Net Time (minutes) Percometer Reading Net Drop (mches) PERCOLATION RATE (minuteslmch) PERC HOLE DIAMETER - TEST RUN BETWEEN FT AND FT COMMENTS: -._-No percolation. test conducted because even better soils encountered in test hole #2. PERFORMED BY FLATTOP TECHNICAL SERVICES. I_ J� %%Sp.a„L CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: B //O /09 e'fattop 7ecfinicalSemj= 14530 rF.cho Canyon 4jpa4 Anchorage, AX 99S16 Thone (907) 345-1355 Lot 4, Block "D", Timberlux S/D, Addition #1 15320 Curvell Drive Wastewater disposal system Specifications 1.0 General: 1.1 The scope of the project consists of inspecting an existing concrete septic tank and installing either a 500 -gallon lift station or a new 1500 -gallon STEP tank that pumps effluent up into a new 15 - foot wide by 58 -foot long soil absorption bed with 0.5 feet of washed sewer gravel and 2.0 feet of ISF filter sand under the distribution pipes. 1.2 Construction shall be as depicted on the approved site plan and design drawings. Minor deviations from these drawings may be allowed or required by the engineer conducting the inspections. All construction procedures and material specifications shall conform to Municipal and State requirements. All separation distances shall be in conformance with Municipal requirements, unless specifically waived. Prior to the start of construction the contractor shall arrangefor a land surveyor to place survey laths to delineate the 100 -foot well radii for the Lot 4 and Lot 3 wells in the vicinity of the existing septic tank and proposed STEP tank. The surveyor should also place survey laths at the southeast corner of the lot and at 50' and 100' divtances from that corner along the south and east lot lines. 1.3 The contractor shall be responsible to obtain any necessary utility locates, and to work around any buried utilities. 1.4 Unless agreed otherwise, the contractor shall be responsible for any tree clearing and grubbing necessary to complete the project. 1.5 The contractor shall provide adequate cover material and rough grading over all system components to ensure that proper drainage is achieved after settlement and that there are no residual depressions. Insofar as possible the contractor shall minimize damage to trees and existing lawn areas. 1.6 Unless specifically agreed otherwise, the homeowner shall be responsible for finish grading after the soil is compacted, and seeding all areas disturbed by the construction. 2.0 Tanks: 2.1 The existing concrete septic tank shall be exposed to allow the engineer to inspect its condition and to check for possible leakage around seams and to verify the condition of its outlet baffle. If the tank is found to be in unsatisfactory condition it shall be properly abandoned per code by pumping and backfilling with soil. The existing log crib seepage pit shall be properly abandoned per code. 2.2 If the existing tank is found to be in good condition with a functional outlet baffle, the contractor shall install a new 500 -gallon, Municipally approved lift station outside the 100 -foot radius around the well. if the existing septic tank is not in good condition it shall be properly abandoned and replaced with anew Municipally approved 1500 -gallon STEP tank located outside the 100 -foot radius around all wells. All tanks that are buried less than 4 feet shall be insulated with 2 inches of approved burial type, rigid insulation. 2.3 All pipe connections to the tanks shall be equipped with waterproof mechanical couplings. The waste line from the residence to the septic tank shall have a minimum slope of 1/4"' per foot. A foundation cleanout shall be installed within 4 feet of the building foundation, or a double cleanout installed upstream of the septic tank. 2.4 The lift station shall be installed either in the separate 500 -gallon tank or in the second compartment of the STEP tank. The lift station package shall be an "Orenco' system as supplied by Anchorage Tank. 2.5 The contractor shall be responsible to obtain the necessary Municipal electric permit and inspection, and shall provide a copy of the electrical inspector's report to the engineer overseeing the construction of the wastewater disposal system. 2.6 The lift station shall be equipped with a watertight, insulated manhole riser and cover extending a minimum of 6" above final grade with positive surface drainage away from the manhole. The contractor shall be responsible for determining the necessary length of the manhole riser. 2.7 The on, off, and alarm floats shall be set at the elevations specified by the lift station supplier, and their proper operations shall be verified by the contractor. 2.8 The discharge line from the lift station to the soil absorption system shall be 1.25" dia. Sched 40 PVC or IIDPE. 3.0 Soil absorption system: 3.1 The soil absorption bed shall be constructed by excavating a 15 -foot wide by 58 -foot long excavation to a depth of 2.8 feet below ground level on the uphill side of the bed. 3.2 The bottom of the excavation shall be level. Any compacted or smeared surfaces shall be raked to allow proper infiltration. 3.3 A total of 2.0 feet of ISF filter sand (with less than 2% passing the #100 sieve and 1% passing the #200 sieve) shall be placed in the excavation and compacted by foot to create a level surface at the level of the original ground at the location of the test hole monitor tube. 3.4 Next, a total of 0.8 feet of washed sewer gravel shall be placed on top of the sand with the perforated distribution pipes laid level such that the pipe inverts are no less than 0.5 feet above the bottom of the sewer gravel. 3.4 The distribution pipes shall be 1.25" diameter schedule 40 PVC with 3/16" holes drilled in the bottoms at 2.0' spacing. Monitor tubes shall be of 4" diameter and installed in the locations shown on the design drawings. The portion of the monitor tube extending through the sewer gravel shall be perforated. 3.5 Approved filter fabric shall be placed over the entire top surface of the sewer gravel. Two inches of rigid, burial type insulation is to be placed over the entire top surface of the gravel, in addition to the filter fabric. 3.6 Two feet of soil cover material shall be placed above the top of the insulation, of which the top six inches is to be topsoil. Fill slopes shall be no steeper than 3:1. 3.7 Unless specifically agreed otherwise the homeowner shall be responsible for arranging to have the site finish graded after the backfill material has stabilized, and for placement of adequate seed to promote rapid revegetation. 4.0 Inspections: 4.1 A total of 5 engineering inspections will be required during the course of the project: (1) initial stakeout with the contractor to establish the location of the system and to discuss the plans, specifications and construction procedures, (2) after the native material has been excavated to expose the infiltrative surface to ensure that it is level and at the right elevation, and conforms with the soil test information, (3) after the compacted sand filter material has been placed, (4) after the sewer gravel is in place and the distribution pipes have been laid and connected up to the STEP tank, but prior to placement of insulation or filter fabric, and (5) after rough backfill and grading is complete. The septic tank and STEP tank installation inspection shall be in conjunction with one of the other listed inspections. 4.2 The installer shall coordinate the timing of the inspections with the engineer sufficiently far in advance to ensure the availability of the engineer. GREAtcR r� ANCHORAGE AREA BORL,JGH Department of Environmental Quality 3330 C Street Anchorage, Alaska 99503 r. INSPECTION REPORT ON-SITE SEWAGE DISPOSAL SYSTEM /�_ .. /2 qpiiiiiii i i _ . 0LS!H I // - % / I C?trft--C-�� ✓J . / 12fAy . 11 -CV . LEGAL DESCRIPTION SEPTIC TANK:,, DISTANCE -1,a�" / NUMBER OF q FROM WELL _L— MANUFACTURER__QA-d51MATERIAL COMPARTMENTS INSIDE LENGTH INSIDE WIDTH LIQUID DEPTH LIQUID CAPACITY 2-5:_7J GALLONS. SEEPAGET:�%A2C� I / O h NUMBER OF PITS --L—. DIAMETER —OR WIDTH L, LENGTHS DEPTH /f ;E7 LINING MATERIAL /tiP�PJ'� CRIB SIZE: DIAMETER _DEPTH_DlSTANCE FROM: WELL. TOTAL EFFECTIVE S BUILDING FOUNDATION_, NEAREST LOT LINE . ABSORPTION AREA (WALL AREA) SQ. FT. ADDITIONAL ABSORPTION WELL: Ir TYPE v CONSTRUCTION BUILDING NEAREST FOUNDATION LOT LINE CESSPOOL , OTHER SOURCES APPROVED DISAPPROVED DISTANCES: INSTALLED BY: 50" —" PIPE MATERIAL: LOT SLOPE: _ REMARKS: DEPTH NEAREST SEPTIC SEWER LINE , TANKS, REMA DISTANCE FROM: SEEPAGE SYSTEM lig DIAGVtAM OF SYSTEM DATE �t,V 15,0 APPROVED .• • •-�x� A.A.B. yam No. EQ -031 0 GREATER A CHORAGAREA BOROUGH DEPARTMENT OF ENVIRONMENTAL QUALITY 3330"C"STREET ANCHORAGE, ALASKA 99503 TELEPHONE 274-4581 �o' OPM PERMIT NO. / 3° SEWAGE DISPOSAL SYSTEM APPLICATION AND PERMIT LEGAL DESCRIPTION INSTALLATION OF: SEPTIC TANK SEEPAGE PIT TYPE AND SIZE OF FACILITY TO BE SERVED FINANCED THROUGH BOIL TEST RESULTS COMPLETION DATE ANTICIPATED TO BE INSTALLED BY OTHER NOTE, THIS PERMIT IS NOT VALID WITHOUT SOIL TEST FINAL INSPECTION: 24 HOUR NOTICE REQUIRED. BACKFILLING OF ANY SYSTEM WITHOUT FINAL INSPECTION BY THE DEPARTMENT OF ENVIRONMENTAL QUALITY AUTHORITY WILL BE SUBJECT TO PROSECUTION. SEPTIC TANK SIZE TYPE MINIMUM DISTANCES, REQUIREMENTS FOUNDATION TO SEPTIC TANK �f SEiFAGG-AMeT SIZE ��GLI FOUNDATION TO SEEPAGE PIT f/0 „ DRAIN FIELD -%%L "cj'—t^ SEPTIC TANK TO SLSP*6==FWALL /' SEPTIC TANK4[EPAZih TS` `7 , DRRIN-FTELD' TO NEAREST LOT LINE. WELL TO SEPTIC TANK /-SEEPAGS-PiT DRA -FIELD ALSO CONSIDER AREA WELLS. WAFSR-MAIN-M?EPTtCTAWK SEEPAGE PIT DRAIN FIELD SEPTIC TANK, 06 I SEEPAGE PIT 0O /DRAIN FIELD 1661 00/ TO RIVER, LAKE, STREAM. CAST IRON INTO AND OUT OF SEPTIC TANK AND INTO CRIB CROSSING GAP OF EXCAVATION 5 FEET INTO UNDISTURBED SOIL. 4 INCH DIAMETER CAST IRON SIPHON PIPES ON SEPTIC TANK AND SEEPAGE PIT FITTED WITH AIRTIGHT REMOVABLE CAPS. GRAVEL BACKFILL CONFORM TO BOROUGH REGULATIONS REGARDING INSTALLATION. INSTA✓LL-ATION. ` /ll!7/G/�-tom /�Fi�✓,Uli%O C"I, G.A.A.B. OR LICENSED DESIGNER - 1 CERTIFY THAT 1 AM FAMILIAR WITH THE REQUIREMENTS OF GREATER ANCHORAGE, DESCRIBED SYSTEM IS IN ACCORDANCE WITH SAID CODE. DATE 8 f /D/7 APPLICANT'S SIGNATURE 14 FORM NO. EQ -019 TYPE DIAGRAM OF SYSTEM �' ' ?b' i�nR "77_5 NAME OF APPLICANT MAILING ADDRESS .545 PHONE INSTALLATION LOCATION LEGAL DESCRIPTION INSTALLATION OF: SEPTIC TANK SEEPAGE PIT TYPE AND SIZE OF FACILITY TO BE SERVED FINANCED THROUGH BOIL TEST RESULTS COMPLETION DATE ANTICIPATED TO BE INSTALLED BY OTHER NOTE, THIS PERMIT IS NOT VALID WITHOUT SOIL TEST FINAL INSPECTION: 24 HOUR NOTICE REQUIRED. BACKFILLING OF ANY SYSTEM WITHOUT FINAL INSPECTION BY THE DEPARTMENT OF ENVIRONMENTAL QUALITY AUTHORITY WILL BE SUBJECT TO PROSECUTION. SEPTIC TANK SIZE TYPE MINIMUM DISTANCES, REQUIREMENTS FOUNDATION TO SEPTIC TANK �f SEiFAGG-AMeT SIZE ��GLI FOUNDATION TO SEEPAGE PIT f/0 „ DRAIN FIELD -%%L "cj'—t^ SEPTIC TANK TO SLSP*6==FWALL /' SEPTIC TANK4[EPAZih TS` `7 , DRRIN-FTELD' TO NEAREST LOT LINE. WELL TO SEPTIC TANK /-SEEPAGS-PiT DRA -FIELD ALSO CONSIDER AREA WELLS. WAFSR-MAIN-M?EPTtCTAWK SEEPAGE PIT DRAIN FIELD SEPTIC TANK, 06 I SEEPAGE PIT 0O /DRAIN FIELD 1661 00/ TO RIVER, LAKE, STREAM. CAST IRON INTO AND OUT OF SEPTIC TANK AND INTO CRIB CROSSING GAP OF EXCAVATION 5 FEET INTO UNDISTURBED SOIL. 4 INCH DIAMETER CAST IRON SIPHON PIPES ON SEPTIC TANK AND SEEPAGE PIT FITTED WITH AIRTIGHT REMOVABLE CAPS. GRAVEL BACKFILL CONFORM TO BOROUGH REGULATIONS REGARDING INSTALLATION. INSTA✓LL-ATION. ` /ll!7/G/�-tom /�Fi�✓,Uli%O C"I, G.A.A.B. OR LICENSED DESIGNER - 1 CERTIFY THAT 1 AM FAMILIAR WITH THE REQUIREMENTS OF GREATER ANCHORAGE, DESCRIBED SYSTEM IS IN ACCORDANCE WITH SAID CODE. DATE 8 f /D/7 APPLICANT'S SIGNATURE 14 FORM NO. EQ -019 TYPE DIAGRAM OF SYSTEM GAAB-HDI �' G�FATER ANCHORAGE AREA BOROUGH HEALTH DEPARTMENT / 327 EAGLE ST. ANCHORAGE, ALASKA 99501 279-2511 INSPECTION REPORT ON-SITE SEWAGE DISPOSAL SYSTEM MAILINGNAME �� �J `I��f Lam` ADDRESS // U� S�—PHONEE 7a 3a LOCATION P1/1SL'I! .LEGAL DESCRIPTION 107-'// 151t� 1/�%l/SC'���%�X SEPTIC TANK: �`� / `��L+xG'�-ry NUMBER OF pnvr'1 DISTANCE FROM WELL ^ MATERIAL 111---Cl4 G/, COMPARTME TS / aSv 5v&-17t� LIQUID LIQUID CAPACITY GALLONS. INSIDE LENGTH INSIDE WIDTH DEPTH SEEPAGE SYSTEM: SEEPAGE PIT: NUMBER OF PITS / OUTSIDE DIAMETER OR WIDTH , LENGTH 2, DEPTH LINING MATERIAL IBJ �TS . DISTANCE FROM WELL <, / , BUILDING FOUNDATION 1c' / NEAREST LOT LINE ' TOTAL EFFECTIVE ABSORPTION AREA (WALL AREA) v c 9 SO. FT. TILE DRAIN FIELD: TOTAL LENGTH DISTANCE FROM WELL , FO , NEAREST LOT LINE . OF LINES , NUMBER O LINES STANCE BETWEEN LINES TRENCH WI IN. TOTAL EFFECTIVE ABSORPTION ARE SO. FT. LENGTH OF EACH LINE DEPTH: TOP OF TILE TO FINISH GRADE DEPTH OF FILTER MATERIAL BENEATH TILE IN. ABOVE TILE WELL;"/T% " `i7 C'/«� 'i DISTANCE FROM / WATER TYPE DEPTH ,BUILDING FOUNDATION. I f- SAMPLE NEAREST NEAREST SEPTIC C / SEEPAGE / OTHER LOT LINE f'�'" • SEWER LINE rd� ,TANK •� , SYSTEM �f , CESSPOOL - , SOURCES_ DIAGRAM OF SYSTEM DISTANCES: ; � I � I I i 1 DATE �1 GAAB-}(D•2 GREATEN ANCHORAGE AREA("1OROUGH IIEALTII DEPARTMENT 327 Eagle St. Anchorage, Alaska 99501 279-2511 SEWAGE DISPOSAL SYSTEM - APPLICATION & PERMIT � W_ NAME OF APPLICANi��o 1426— hAILING ADDRESSZ10 /SPHONt7 %S3S RESIDENCE ADDRESS LOCATION OF INSTALLATION fI/-SLitT CERf LEGAL DESCRIPTIO APPLICATION TO INSTALL: SEPTIC TO SERVE THE FOLLOWING FACILITY FINANCED THROUGH_/ -7o/L P#,TEST RESULTS SEEPAGE PIT_ , DRAIN FIELD , OTHER TO BE INSTALLED BY ANTICIPATED DATE OF COMPLETION -2 y 11Z- /V/C774r,&— BELOW TO BE FILLED OUT BY HEALTH DEPARTMENT THIS IS TO SERVE AS ". (_Izzzo—�_ -, PERMIT TO INSTALL A 5:571r -702r, ;%ys AS DESCRIBED BELOW. SIZE OFUNTO BE SERVED — J �C21f• //r 16 SEPTIC TANK SIZE TYPE OCA(J . SEEPAGE AREA VC/LTYPE DIAGRAM OF SYSTEM DISTANCES: �Qi11/`�1�(/Yj� �V&V o JSCJ�r1c /f1/�� = Sa! '74 t s HEALTH AVTHORITY OR LICENSED DESIGNER I certify that I am familiar with the requirements of Greater Anchorage Area Borough above described sys em is in accordance with DATE O said code. APPLICANTS SIGNATU (ante No. 28-68 and that the ?' OO/4 ?trT n GREATER ANCHORASE AREA. P.OROUG1-^1 • HEALTH DEPARTMENT CASE A 327 EAGLE STREET ANCHORAGE, ALASKA 99501 Performed For ,r rre, i�rnrrrp Date Performed — c Legal Description: Lo y nlock�_Subdivision (; mak A This Fort,- Re-orts a: Soils LOP ,/ Percolation Fest Depth Feet Soil Charatteristies Location Sketch t1e. betfom he le: sedimenfs represPnf av: Gncten f 4op soil f ho f has becy% buried Gy cllat101 depcslls. 1 a5siyrted t 1 a vn l u e, el a 7S"—'/bckm Sim;lar }v fh't C1 M{-. ,qll shalt. had #-ela4i,:03 Sharp boundries. Fq f inier4c4 a tt 1 there was Ah Pt}rernely high mcisfure. tcnleni almest to be Ccnsidareb o, wt,ter f-a61e. SCme tuct4Pr wes leauiny }he sedimenf6 ai fhis IOcu 1,'011 eu f t h,Y was 0-f c' minor amcUn'f`, Sf Was Ground Plater Encountered?jUn � o A� re arl(s� If Yes, At What Depth Proposed Installatjon; Seepage Pi Depth Of Inlet u..c ne Test Performed By: Pprre r Data Certified By: Date I / {--Z�19 1 N ,10'� N GREATER ANCHORAGE AREA BOROUGH Department of Environmental Quality 3330 "C" Street, Anchorage, Alaska 99503 274-4561 Date Received September 13, 1976 Time of Inspection k:30 p.m. Date of Inspection 9-14-76 Tuesday REQUEST FOR APPROVAL OF Pratt INDIVIDUAL SEWER & WATER FACILITIES FOR Con v. 1. Approval requested by: Alaska National Bank ,p�(..Y1c_- Mailing Address: Pouch 7010 Phone: 277-5511 x 31 2. Property Owner: Jerry D. Crowe & Frankie C. Phone: non -working Mailing Address: Curvell Drive 3. Legal Description: Lot 4 Block D Timberlux Subdivision 4. Location: Rabbit Creek to Longbow Drive, left on Curvell Drive 5. Type of facility to be inspected Single Family No. of bedrooms 3 6. Well Data: Individual A. Type B. Depth C. Construction D. Bacterial Analysis 7. Sewage Disposal System: On-site system, upgraded 1976 A. Installed B. Installer C. Septic Tank: 1. Size 2. Manufacturer D. Seepage Pit: 1. Absorption Area 2. Material E. Disposal Field: Total length of lines 8. Distances: A. Well to: Septic tank , Absorption area Sewer Lines Nearest lot line Other contamination B. Foundation to septic tank Absorption area C. Absorption area to nearest lot line EQ -034 (1/74) Page 1 of two pages Page 2 of two pages - Req At for Approval of Individual S�';r & Water Facilities Legal Description Comments Approved Lot 4 Block D TimberlAx Subdivision N1 Disapproved Date Approval,Valid for one year from date signed Greater Anchorage Area Borough, Department of Environmental Quality DIAGRAM OF SYSTEM I certify that the information contained in this request for approval to be a true and accurate representation of the subject sewer and water facilities and these facilities are operating satisfactorily. SIGNED EQ -034 (1/74) Date n 'GREATER ANCHORAGE ARIA BOROUGH Department of Environmental Quality Y' cr r� 3330 "C" St., Anchorage, Alaska 99503 - 274-4561 OF INDIVIDUALS SEWER &FORPWATERLFACILITIES R E C EIL/E:�� 1. Type of Inspection:• CMRO VA FHA =V xx 2. Property Owner: CROWE, Jerry D. and Frankie C. Location: Rabbit Creeek Road to Longbow Drive . Left Mailing Address: Unknown (Curvell Drive) Day Phone Disconnected 3. Name of Buyer: BAILEY, BERT R. and BONNIE J. Mailing Address: 4325 MacAlister Drive Day Phone 344-6810 4. Name of Lending Institution: Alaska National Bank Mailing Address: Pouch 7-010 Phone 277-5511 Ext. 31 5. Name of,Realtor or Agent: Eugene W. Bates Tast Realty Mailing Address: 3050 Lake Shore Drive Phone 274-5676 6. Legal Description: Lot 4, Block "D", Timberlux S/D Add. O1 Location: Rabbit Creeek Road to Longbow Drive . Left on Curvell Drive. 7. .Type of Facility to be inspected: Single family No. Bdrms. 3 8. Water Supply Type of Supply: Public Utility Individual xx If Individual, number of dwellings presently served Unknown If.Individual, depth of well Unknown . 9. Sewage Disposal -System Type.of System:. Public Utility Individual (on-site) Ix If Individual, date of installation Unknown ®r. GREATER ANCHORAGE AREA BOROUGH Department of Environmental Quality J3330 Street, Anchorage, Alaska 99503 274-4561 • Yt Date Received May 28, 1976 \ Time of Inspection Date of Inspection REQUEST FOR APPROVAL OF INDIVIDUAL SEWER & WATER FACILITIES FOR Conv. 1. Approval requested by: Peoples Bank and Trust Mailing Address: 644 West 8th Avenue 3:00 p.m. 6-1-76 Tuesday Les Buchholz Phone: 279-7511 2. Property Owner: Jerry Crowe Phone: 505-988-6560 3. 4 Mailing Address: Post Office Box 2348, Santa Fe, New Mexico Legal Description: Lot 4 Block D Timberlux Subdivision Location: Rabbit Creek Road 5. Type of facility to be inspected Single Family 6. Well Data: A. Type Individual C. Construction B. Depth 87501 No. of bedrooms 5 D. Bacterial Analysis 7. Sewage Disposal System: On—site system A. Installed 1970 B. Installer C. Septic Tank: 1. Size D. Seepage Pit: 1. Absorption Area E. Disposal Field: Total length of lines 8. Distances: 2. Manufacturer 2. Material A. Well to: Septic tank , Absorption area Sewer Lines Nearest lot line Other contamination B. Foundation to septic tank Absorption area C. Absorption area to nearest lot line EQ -034 (1/74) Page 1 of two pages s Page 2 of two pages - Re ^st for Approval of Individual '"ler & Water Facilities 'Legal Description Lot 4 Block D Timberlux Subdivision Comments Approved Disapproved Date Approval,Valid for one year from date sj[g ed Greater Anchorage Area Borough, Department of Environmental Quality DIAGRAM OF SYSTEM '/ C��rluq I certify that the information contained in this request for approval to be a true and accurate representation of the subject sewer and water facilities and these facilities are operating satisfactorily. SIGNED EQ -034 (1/74) Date •- ���� MUNICIPALITY OF ANCHOPAO-c ^ DEPT. OF HEP.LhI .. l CQ�ri,CI JI'I" ENVOONMENTAL P:C%CTION oit- GREATER MAY 23.0x1976 v, ANCHORAGE AREA BOROUGHpECEIU_.EQ Department of Environmental Quality _ 3330 "C" St., Anchorage, Alaska 99503 --244-45-61 REQUEST FOR APPROVAL OF INDIVIDUAL SEWER & WATER FACILITIES 1. Type of Inspection: CMRO VA FHA CONV t/ 2. Property Owner: Jorra O fe' PO..6a3Nd' 8�so/ Mailing Address:—,la22n Of-, d&_4w L�G' z� o Day Phone .5'0r- 4,566 3. Name of Buyer: WA fer F d- 112 A r Dnin'for tl, Mailing Address: e,7la?G 6rrr// ' ket. Day Phone .3 i7-/9h'L 4. Name of Lending Institution: _P0r.nlo's gn-nlf C1 Tru_-) Mailing Address: 6 -w &c ',rA Ove- _Phone o? 7 j- 7T11 5. Name of Realtor or Agent: -)rrl, fi ss rr 0brtNin Mailing Address: �� L-. Firtl_t Fr/� h-ojtc, Phone _2j-2-r-71 Cl'Q.0 707'05"Pr &rj,37')L r%w 3'V-a9/'O 6. Legal Description: 11 / / b,1-AL�! S',. 64 Location: 0f� t1�C�G�IcE eatt_L' trail, )4twn cn nn ° rc. w /n fti /?Ytmt•c�lItc J--j 7. Type of Facility to be inspected: S1iduNo. Bdrms. 8. Water Supply Type of Supply: Public Utility Individual If Individual, number of dwellings presently served _ If Individual, depth of well T 9. Sewage Disposal System Type.of System: Public Utility Individual (on-site) v If Individual, date of installation 19740 EQ -037 (1/74) I June 2, 1975 4.1 Totem Realty I Barb Bliss '515 bast Fireweed Lane Anchorage, Alaska 99503 Subjecti Lot 4 Block D Timberlux subdivision Dear He. Bliss: The seepage pit at the time of inspection was within four (4) toot of the ground surface. N, new absorpiton area is requested before an approval can be granted by this department. The septic tank must be pumped for =aintenaace purposes. The well is approved construction. A new absorption tronch consisting the following specifications, Depth 9.5 feet Gravel depth 4.5 feet Length S$U"t A permit is required from this office. A copy of this letter at the time pf permit applicatica would bo helpful. if you have any further ". astions, please contact this office at 27G-2221, extension 285. sincerely, Los V. Buchhola Sanitarian, LaZ/ljh Municipality of Anchorag MAR • / J 1 On -Site Water and Wastewater Program --'`t (907)343-7904 -reek `dam Certificate of On -Site Systems Approval P / Parcel I.D. 018-271-18 Expiration Date: (0 —�cO 1. GENERAL INFORMATION Complete legal description Timberlux #1; Block D, Lot 4 Location (site address) 15320 Curvell drive *Anchorage 99516 Current Property owner(s) Lorna Findley Day phone 303-818-0717 Mailing address Real Estate Agent 2. TYPE OF DWELLING: ® Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: A J 4. TYPE OF WATER SUPPLY: Individual Well 19 Individual Water Storage ❑ Community Class Well ❑ Public Water System ❑ Waiver/Variance request for: NIA Received by: COSA to be relea Day phone TYPE OF WASTEWATER DISPOSAL Individual 19 Holding Tank ❑ Community ❑ Public Sewer ❑ the e�eer, unless otherwise requested by the engineer. COSA Fee $ 4yto l Date of Payment 212,r 114, Receipt Number ilri,, - COSA# 65oi 162 to Date: Waiver Fee $ Date of Payment Receipt Number Waiver # 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm Garness Engineering Group, Ltd. (GEG) Phone (907) 337-6179 Address 3701 E. Tudor Road, Suite 101, Anchorage AK 99507-1259 Engineer's Printed Name Jeffrey A. Garness Date ,?dr e /16 In conducting this evaluation, GEG provided an engineering evaluation of the well and/or septic system in accordance with the guidelines and regulations established by the Municipality of Anchorage and industry practices. The reported results describe the condition of the systems on the date/s of the evaluation. Separation distances were measured to readily identifiable features. Hidden defects or encroachments may exist that were not identified during the evaluation. The operational life of all wells and septic systems depend on a variety of variables including, but not limited to, soil conditions, groundwater levels (that may fluctuate during the year), quality of construction (materials and workmanship), and the water usage of the family utilizing the system/s. These conditions can vary, and are outside the control of GEG. Satisfactory test results do not guarantee future performance of the system/s; therefore, GEG makes no warranty (express or implied) regarding the future performance of the well or septic system. GEG makes no representation whether an alternative well or septic system can be installed on the property in the event either of the current systems fail. The content of this report is for the sole benefit of the person1party who retained GEG. Reliance upon the information provided in this report by any other person or party, including but not limited to subsequent property purchasers, is not authorized. In short, GEG disavows any legal duty to anyone other than the person/party who paid for this report. 6. DSD SIGNATURE 0 System #1 Approved for bedrooms System #2 Approved for bedrooms �Y OF,11V Disapproved �O 5p ., Conditional approval for bedrooms, with the following stip doSON-SITE ��'•, CVATER AND r": Original Certificate Date: - —_?, 2 ^ I The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. ATTACHMENTS: COSA Checklist Septic System Advisory Well Flow Advisory COSA Nue sheet 9-1-12.doc Nitrate Advisory Arsenic Advisory Other N more than 1 septic system is on the lot: COSA Checklist # _of Structure served by this system Certificate of On -Site Systems Approval Checklist Legal Description: A. WELL DATA TIMBERLUX #1; BLOCK D, LOI 4 Parcel ID: 018-271-18 *ASSUMED PER YEAR BUILT HOUSE AND ORIGINAL SEPTIC INSTALLATION DATE **PER GEG INSPECTION ***ASSUMED PER SURROUNDING WELL LOGS - SEE ATTACHED Well type PRIVATE If A, B, or C provide PWSID# N/A Well Log (Y/N) NO Date completed *1970 Sanitary seal (YIN) YES Wires properly protected (Y/N) All Y� Total depth **45+ ft. Cased to ***40+ ft. Casing height (above ground) 12+ in. FROM WELL LOG AT INSPECTION Date of test 2/19/16 00 Static water level_ L ft. 31.1 ft, N Well production g.p.m. 2.2+ 9;p,m, WATER SAMPLE RESULTS: Coliform 0 colonies/100 mi. Nitrate 0.612 mg./L. Collected by: GEG. Ltd. Arsenic: JI D ug./L. Date of sample: 2/18/16 B. SEPTIC/HOLDING TANK DATA *DOUBLE CLEANOUTS BEFORE TANK TankType/Material SEPTIC/CONCRETE Date installed 5/20/70 Tank size 1250 gal Number of Compartments 1 Cleanouts (YIN) YES Foundation cleanout (Y/N) *NO Depression over tank (Y/N) NO Hi h water alarm (Y/N) YES Date of pumping a- 1 (O Pumper MC.CLY)OJ( C. ABSORPTION FIELD DATA eELow exrsnNc cRAOE Date installed - 2/5/14 Soil rating (g.p.d./Worq/bdo 0_7 System type BED Length' 58 ft. Width 15 ft. Gravel below pipe 0.5 g, Total depth --ti-41—ft. Eff. absorption area8�0 fe Monitoring tube YES Depression Qver field . NO Date of adequacy test 2/19/16 Results (PaSS/Fail) PASS Fo.r- ` bedrooms Fluid depth In absorption field before test E in. Watef added 501 gal. New depth E in. Elapsed Time: E min. Final fluid depth E in. Absorption rate >= 4+450+ g,p.d_ Any reluvenation treatment (past 12 mo.) (Y/N & type) NONE If yes, give date - PER 2014 INSPECTION REPORT BY LARS SPURKLAND, P.E. 2" INSULATION OVER DRAINFIELD. 3�0- *PER 2014 INSPECTION REPORTs s o D. LIFT STATION THERE IS AN INTERIOR ALARM INSIDE ^ fie+ G F•G, TdSP°L�iO Date installed 2/5/14 Size in gallons 500 . Manhole/Access (Y/N) YES "Pump on" level at 75 in. "Pump off" level at 78 in. High water alarm level at 71 Datum TOP OF MANHOLE Cycles tested 3 Meets alarm & circuit requirements? *YES E.. SEPARATION DISTANCES SEPARATION DISTANCES FROM WELL ON LOT TO: Septic tank/lift station on lot *50'+/100'+ On adjacent lots 100'+ Absorption field on lot 100'+ On adjacent lots 100'+ Public sewer main 75'+ Public sewer manhole/cleanout 100'+ Sewer /septic service line 25'+ Holding tank 75'+ Animal containment areas 50'+ Manure/animal excrete storage areas 100'+ SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Building foundation 5'+ Property line 5'+ Absorption :9 Water main 25'+ Water service line 10'+ Surface water 100'+ Wells on adjacent lots 100'+ SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Property line 10'+ Building foundation 10'+ Water main 10'+. Water service line 10'+ Surface water 100'+ Driveway, parking/vehicle storage 10'+ Curtain drain NONE KNOWN Wells on adjacent lots 100'+ F. COMMENTS *50'+ TO 1970 SEPTIC TANK 100'+ TO 2014 LIFT STATION G. ENGINEER'S CERTIFICATION I certify that I have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSH guidelines in effect on this date. Engineer's Printed Name JEFFREY A. GARNESS Date 3) 1 I'l lb (Rev. 11/05) t GARNESS ENGINEERING GROUP Ltdn - oe . l CIVIL&ENVIRONMENTAL ENGINEERS �::�� _-- �.----- _ March 22, 2016 Municipality of Anchorage Development Service Department On -Site Water & Wastewater Program 4700 Elmore Road Anchorage, AK 99507 Ref: Timberlux #1; Block D, Lot 4 - Request COSA Approval for 4 Bedrooms To whom it may concern: I am writing this letter in regards to 15320 Curvell Drive Anchorage, AK (Timberlux #1; Block D, Lot 4). Per the request of the agent, the system was originally inspected and tested for 3 bedrooms. The home was confirmed by Anchorage Live to be a 3 bedroom house. However, per MOA records, an appraisal of the home, and your staff the home is actually 4 bedrooms. We are requesting your department issue the COSA as a 4 bedroom approval to reflect the actual sizing of the septic system and house. Per MOA records, the septic system is sized for 4 bedrooms. During our inspection/test, five -hundred and one (501) gallons of water was introduced into the system over a period of 210 minutes, causing no rise in the monitoring tube. Based upon this data, it is apparent that if an additional ninety-nine (99) gallons of water were introduced the system would have been capable of absorbing it. This would have resulted in a 4 bedroom passed test. It should be noted that elevation shots were taken and the monitoring tube was shown to be at an elevation of 101.7. Per the 2014 inspection report the bottom of the system elevation was 101.8. In short, the MT goes slightly below the bottom of the effective and still remained dry throughout the test. We understand that your department only considers these requests on a case-by-case basis and is not something that your department will typically allow. If you have any quos ions please call me at 337-6179. E.. M. S. 3701 East Tudor Road, Suite 101 * Anchorage, Alaska 99507-1259 Phone: (907) 337-6179 * Fax: (907) 338.3246 * Website: www.garnessengineering.com GuY� it '• ,o , m N t`n N -3- M O Sca /e: l'r= 30' �i� 8/63 R /90.00 48° N j W/Dayl;yh�smf� J '"'36�TIL t VEWT3 SEPn�t+�K� 6/° w Ch.O HH ,a V 34 f 1 W O 20' Sc✓een h9 Fenc (Piq F- 10 10 `,Ute 4O "p187,72 NO CORNERS SET THIS DATE EASEMENTS OF RECORD, OTHER THAN THOSE SHOWN ON THE RECORDED PLAT ARE NOf SHOWN HEREON. DOW L �ta r 0 I hereby certify that I have performed a Mortgagee's inspection of the following described propertrv: �-o f4 /C" k 72 lb ev/u X .sub AGI H /VO l ' Anchorage Recording Precinct, Alaska, and that the improvements situated thereon are within the property lines and do not overlap or encroach on the property lying adjacent thereto, that no improvements on property lying adjacent thereto encroach on the premises in question and that there are no roadways, transmission lines or other visible easements on said property except as indicated hereon. Dated at Anchorae, Alaska this day of _ ✓a n . _,s U6 FRED WALATKA & ASSOCIATES (907) 248.7666 Engineers and Surveyors c 0 MUNICIPALITY OF ANCHORAGE jai DEPARTMENT OF HEALTH li HUMAN SERVICES IkMa Division of Environmental Services On -Site Services Section P.O. Box 196650 •Anchorage,Alaska 99519-6650 _ .... - 343-4744 CERTIFICATE OF HEALTH AUTHORITY, t. APPROVAL FOR A SINGLE FAMILY DWELLING fl Parcel I.D. # 0 I'S ^ 1-71 1 Y . _ - HAA ri 4i Q°1ifl �d l Lo it 1 GENERAL INFORMATION --- v _ •?.. .. -- Complete legal description Lot 4; Btock D: 7cm6entuz •Subdiv.isicn 01 • 15320 Cu2vett D2ive Location (site address or directions, "-Anchotag¢. 'AK 1• . \BQJLt b Bonnie Baeteu " Pr9pe_rtyowner Day phone - 349 2685 +. Mailing address T5320 CunveLt Drive Anehonaae.' AK 99516 - 'kLending gency _ Day phone Mailmgaddress -- - • • Agent Day phone .:Address r I' V`. v. .v,rsTl StM M, -i�,F ?' r4 , :. a w /. .! a _ r r 'a^ rf4t.' . '! ♦ . ', r r v'..' :. � , ; ,_:,n.—,.U JF....I p', 'i Ir ♦: ...,r ,.. .. . 1 , .. % .: r „ � r, l is 'ti 4`Unlesjs. otherwise requested HAA will be held for pickup' �:' t�*i-,`} t ti' °f+ , �; �,: � gt �• u,•, w A luY L:i,l �,, ♦ ♦ r h1• ; \i - r .n a., •7 rf f A Ir r { r �.. 2.*"+' NUMBER OF BEDROOMS t..: i�-3 •.....*.'— . ,. 3 -� . , ,.. , ,rte _. , ,t', �. , . ;;�. �7 i -"•.r rr, r.: . .fi r = :., 4 4/i sT^Ji:>7Q V.vtMr/1•P14 F Y•: i1 �ilT r,bL ), 'j 1 Y r d, y 3. '`„TYPE OF WATER SUPPLY - `f'4 '.L _:.r.,�n�{4:.e..t...cai1'l:asb.k•D4cw.,:af.:.:lv.td'.:31.r ,�._. J.. ~�:f ,t .r �!, t rJ:l. r<�! .y.. r 'L 'h W .mv,�,4h M'-•{'91rw •rn r.r•-xv-v.•r .1.`. - l .. wr ti r Ate:. v t ) Individual well Xxx y n ,Community ell.% Public water. ... _ _ . --.•-- NOTE: If community well system, provide written confirmation from State ADEC attest- .' _ Ing to the legality and status of system. r R s t c 4 .a TYPE;OF WASTEWATER DISPOSAL Individual on siteXXX a 1 4. '�, 3 7 ) g Holding tank-•..�.,-w,•�••-m T., , �., :,. , t-, {v y..; r.� Y Ya\ � �w 4 R• 1 • 1, i M J I1 7 yr e o• , h ` , tf� •�` _ � i !...r m.r ,1 ! .z.: ♦ x.M,1.^!i ...r a' .. a i.2..'�., arlwsi .. ,... 1' ' , r..t1 .f 1„ • < , L i • � Community on-site 117:' ? 1 rCla r pr t �". ,7 J1.1r` � r . i�'Ji v)•.\4 t . Tpn:4 ,} '^' rlµ'J( MT r ♦wn ,{i >'JY`.•1'rC/ ¢C - r' )" _ g1ti)j [`!i3ti Public sewers • 1 � ..r,L A f'• l l..l• 1 7r'.Ma 'S 4r. . i' _.1 �1 .,' V _ . y u. - - - N, 1111 1t NOTE If community wastewatersystemr provide written, confirmet�on from State ADEC , attesting to the legality and status o/system 7 1 r 72-M (F4r.141) Fr MOA m 5. STATEMENT OF INSPECTION BY ENGINEER i . As certified by my seal affixed hereto and as of the validation date shown below, l verify that my investigation of this Health Authority Approval application shows that the on-site water supply and/or wastewater disposal system is safe, functional and adequate for the number of bedrooms -. and type of structure indicated herein. I further verify that based onthe Information obtained from _4 the Municipality of Ancnorage,files and from my investigation and inspection; the"on-site water supply and/or wastewaterr disposal system is in compliance withlall Municipal and State codes, ordinances; and,regulations in effect on the date of this inspection Name ofFlrm- SISENGINEERiNG _ ` --•'Phone''G'�y-- 979 - 17034 Eagle River Loop Rood No. 404 `Address - �Engineersslgnature,• _ Date -Er" r. .+ OR 17 t, i gni l2= enwic vii 17. r, ft ROBERT G COW.W F rVr ti .� l� , DHHS SIGNATURE ftta -Approved bedrooms. n. t rY t w T'>- 7 I 4. t� Ls k •` '� Rt 1. .' ty tva .v4 ♦ wt w +p. Disappro 1. e.i r ^il+t 'Conditional approval for bedrooms 'with, e,Wowmg stipulabons i tT. ii- -AT,i< 2rt fi'r '�.vT i �. .L•_ . e YYi i'.• �.. { 'si% .i ...�u � v _.•f w.a+tin'.., ,.1,,.>.�a4-. T1. .. .. ..i :AY .1' .. �5�+��Y`" �{S_ `,;. ' S - V - 1 moi: rs• .rwG1 iJ J.. ... 1.,..r f,..'�C..f i a..::4_.. ..'♦...... '...-..b. a. .. w._r...'J..ai....J..�-...:..L ..w_ a...,_,. -_.+rn .: a-.�... Giro- ..:Y w,':."•."i A ... :._... ., ._-r .. o,a ,. ... -� __.m.. xi va.•vruz#mrrh v....w..vw cvv.u. r>,•. !.:. �. w ::Additional Comments : ��1t; f .yw V•• •l9 O ,Llf �'.:"!t a i+'21./3t w•'Y l.La •1f ... `Sy"� ,@ se,c i? �r3TacDate"r//ve >�JS .q� .�.t CAUTION :�he•Munici li r!chora e ti .- r, _ _ pe tyi w g Department of Health and Human Services' (DHHS) issues Health Authority `kAjrproval•Ce 'baled only upon the representations given in paragraph 5 above by an independent ,, proteswoirialengin8erregisteredintheStateofAlaska.TheDHHSdoesthisasacourtesytopurchasersofhomes <andthelrlendinginstituttonsinorcJertosatistycertainfederalandstaterequ(remenb EmployeesofDHHSdonot _,conduct lns pections or analyze data before a certificate is issued The Municipality of Anchorage is not ' _..-.. , ... .. responsible for errors or omissions in the professional engineees work t:n-WsOt.aW) e.m ►lwm Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES Environmental Services Division 825"L" Street, Room 502 0 Anchorage, Alaska 995010 (907) 343-4744 /0 `-- Health Authority Approval Checklist r'r 1 Legal Description: "7- It 1144c. 1) T,mlft a to x irl A. WELL DATA Well type r2 , VA 7C Log present (Yo NJ n Parcel I. D.: o / 51 - a -7 0 m If A. B. or C, auach ADEC letter. ADEC water system number Date completed v / q 7 0 Total depth S- a Cased to ti Sanitary seal (91N) Y £ S f P4R hoot f--•..( FROM WELL LOG Ire. U/K Static water level U /K Well production V /K t Casing height (above ground) u 1 �4-- Wires properly protected y/N) %E I AT INSPECTION )�1eI96 g.p.m. g.p.m. d Aer 4 wF WATER SAMPLE RESULTS: Coliform 0 Nitrate 0.1 Other bacteria D Date of sample: I to r/ 9 (.. Collected by: S & S ENGINEERING 17034 Eagle Rive Loop Road Yo. 204 B. SE IOLDING TANK DATA Eagle River, Alaska 99577 Date installed S—/)`° / 7O Tack sire I a ro Number of Compartments I Cieanouts®/N) Y E S Foundation cleanout (Y6 "0 Depression (Y/l1 N o High water alarm (YAW /' O Date of Pumping `>' // r pumper /tit C. A13SORPTION FIELD DXTA S/>0/70 I- 'CR)l3 L Date installed 1 Y 7 6 Soil rating (g. p.d./ft' or f System type 7 c c N av' z at' f r' 1 Length S's ' WigW 3 ' Gravel thickness below pipe y -r ' Total depth 10 '/s. ' 6r* 4 Effective absorption area 4 +r Monitoring Tube present&M Yf JJ Depression over field (YAIS5 N e Date of adequacy test 1 It /61 b Results(Fail) P,+ rS For 3 bedrooms DRY a4 41`0 L ri, S, Fluiddepth in absorptign field before test (in.): H '9" immediately after at 7 gal. water added (in. ): y a"ri.�� 4 -71 j 4 s o f-4 Fluid depth Ae P's " (ins.) Minutes later: a 3 q Absorption rate = 'y CO t a.p.d. Peroxide treatment (past 12 months) (Y/N) ^ r" K new J If yes, give date D. LIFT STATION Date installed Size in gallons Manhole/Access (YM)"Pump on" leve "Pump off' Ic%cl at* _ High water alarm level at* *Datum Cvcles tested E. SEPARATION DISTANCES SEPARATION DISTANCES FROM WELL ON LOT TO: holding talc on lot 9 S ; On adjacent lots /0 J 'r' Absorption field on lot /00 t ; On adjacent lots loo / f Public sewer main N /A Public sewer manhole%leanoul v � A Sewer /septic service line Litt station N 14 SEPARATION DISTANCES FROh SEPfI HOLDING TANK ON LOT TO: i t Building foundation Property line S Absorption field S / Water main/service line Y 0 t Surtax wateddrainage /0 a t Wells on adjacent Tots � S n SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Budding foundation 1't7 t"t" Water maudservice line W 0 + Surface water 10 0 Driveway, p ddng/vehicle storage area *0 ' Ctutain drain Nen £ K ti OW ni Wells on adjacent lots go Property line J n ' -)c -w- %✓ R °la.0070 F. ENGINEER'S CERTIFICATION I certify that I have determined thru field inspections and review ofUunfcipal records in conformance wtt V 0.4 HAA Ruf Ines to effect on this date. Signature -���� Engineer's Name /etlB�R,— C_ l owd✓ .� Date HAA Fee S 0166' 4D c� Waiver Fee S _ Date of Payment Date of Payment Receipt Number % J�L1 �� Receipt Number Rev. 9195 OSS: haawk.doc aotnnr C. COWAN CE•8801 are