HomeMy WebLinkAboutT15N R1W SEC 18 LT 40T15N RIW Sec 18 Lot 40 #051-171-21 Municipality of Anchorage On -Site Water and Wastewater Program • (907) 343-7904 Page of ON-SITE WASTEWATER INSPECTION REPORT Permit Number: SW090171 PID Number: 051-171-21 Dwelling: ® Single Family (SF) ❑ Duplex (D) ❑ Multiple (SF and/or D) Project: ® New ❑ Upgrade Name: RACHAEL POPE ABSORPTION FIELD ® Deep Trench ❑ Shallow Trench ❑ Bed ❑ Mound Address 19450 Joy Ave., Chugiak, AK 99567 ❑ Other Phone Number of Bedrooms Soil Rating Total depth from original grade 4 0.45 GPD/SF 10.5 Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade 2.0 Ft. Gravel depth beneath pipe 8.5 Ft. Subdivision Block Lot 40 Fill added above original grade Varies See Dwg Ft.1 JGravel length 80 Ft. Township Range Section 15N 1 W 18 Gravel width 2 Ft. Beds: Number of LinesDistance -- between lines -- Ft. SEPARATION DISTANCES To Septic Absorption Lift Station Holding Sewer Total absorption area Number of trenches I Dist. between trenches From Tank Field Tank Line 1360 Fly 2 17 Ft. Well 100+ 100'+ 100'+ NA NA TANK ® Septic ® S.T.E.P. ❑ Holding ❑ Other Manufacturer NEW Cap acity 1500 Gal. Surface Water 100'+ 100'+ 100'+ NA Material Anchorage Tank Number of compartments 2 Lot Line 5'+ 10'+ 5'+ NA NA Foundation 5'+ 10'+ 5'+ NA LIFT STATION Manufacturer Anchorage Tank / Orenco Capacity 1500 Gal. Curtain Drain NA *50'+ NA NA Remarks *None known. Field / Tank insulated Pump on level at 44 in. Pump off level at 42 in. High water alarm at 48 in. Tank designed for 12' burial. Pump make and model Franklin 2445040117 — 1/2HP Electrical Inspections performed by See Owner Letter PIPE MATERIAL House totank 3034 nfi id 3034 Installer Owner Install dra Drainfield 3034 CO/MT 3034 Inspector ARCTERRA BENCHMARK (Assumed elevation) 100 ft Inspection 1" 7/30/2009 Location and description 2"d7/3012009 3" 7/30/2009 a" Garage Floor COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL �! �^ OF Al Conditional Approval: Date / *�4 TH f a KE u ti 7 t ti r Approved T f --�, Date � ' r P�rr:�ssto1�'O' -� eels Slam Inspection Report_9-1-12.doc AS—BUILT SYSTEM DETAILS/SITE PLAN Permit SWO90171 T15N R1W SEC 18 LOT 40 PID# 051-171-21 `D o U 333' "'co o 28.5' m M O 12 s. 8,O• N of O n' CO C 333 1500—GAL CO 6 STEP 401 CO Mr ESER� a N y o TH09-2 g s TH09-1 SCALE, 1' _ g — A—C=14' y 99.00 99.3 106. B—C=44' o !®NITDR TUB N A—D=17' o cDur FINAL GRADE 106,4 106.2 ;: B—D=42' c a ER rAM6 / °A vAx¢s A—E=34' ay 1500 GAL B—E=25' yN STEP 104,2 104,2 T o A—F=22' v w TANK SEWER ROCK 89.13 89.13 95,70 TRENCH 1 95,70Li E 4D• FINAL GRADE Tum 106.0 SCALE, NTS 106.3 106.3 J°orn ru.iEA ■AM6 / n°uATm� vAa¢s m 104.0 104,0 I SEWER ROCK 95.50 TRENCH 2 m \(L95,_5_0'\ � OF \ 40' SCALEi NTS MI / ��. • 1 PREPARED FOR. RACHAEL POPE y4, �RC Ey``C� 0 19450 JOY AVE. :C c ,^ * : `t TH ^) * � CHUGIAK, AK 99567 p m t S FIELDBOOKS cauruim: rx n p IB .�yAr / 9WNDAFt1: ABC atANN' VQGAVF � \ UMWG: ABC CHEam: KMD A3 A93UO.h ABC DATE: 00 �'...��.. E\`�=� DM nVE; ax0: 000 v��R�'ONS ZT1G�p�l ° ACAD nv:: 00 ,a9 No.: 00 ryfR TILTING ,a,561 AK. 99577 VVIR/A. Elogk i Mayor Oevelopment Services 0epartment Building ! fi S.# tXvision ♦O 1 - • � Permit Number: #SW_ Date of Issue: _ Date Started: i-0 t Date Completed: Legal Description: Property Owner Name &c Address: i i> Parcel ldeatificatioumber: Is well located at approved permit location? © Yes ❑ No b -f 40 Borehole Data: Depth (ft) Soil Type, Thickness & Water Strata From To Method of Drill'mg Q air rotary ❑ cable tool (rasing type: -Wall Thickness:.inches Diameter 4 inches Depth: feet Liner Type: Diameter: _ inches Depth: _ feot Casing stickup above ground: feet _..- s .tl�f-ta✓cX Static nivel from { ground level},feat Pumping level.—feet ai%r hours pumping -7 gpm Recovery Rate: _. gp Method of Testing: ns� f vi A lelAll Well Intake Opening Type: Open land ❑ Opm Hole Screened Start _ feet Stopped _ feet ,Perforations start 4- _feet Stopped Sin feet GroutType: _ Volume: _ Depth: Start feet Sto feet Pump: Intake Depth:_„_ feet Pump size .^ hp Brand Name Well Disiafected Upon Completion? (2 Yes 0 No Method of Disinfection: yr„a„t Comments. Well Driller: WATER011 RYTESTING Coliform 001/100ML, Nnreies MA AtseMc ug/L Attention: The well driller shall provide a well log to DSD within 30 days of completion. ....... _ .... Development Services Department Building Safety Division On -Site Water & Wastewater Program *A& 4700 Elmore RoodP.O. Box 196650 MarcBegfch Ancorage, AK 99507 Mayes WWW M=i.GM&Rsite (907)343-7904 Pump Installation Log Well Drilling Permit Number: SW-0—ib/ % 1 Date of Issue: Parcel Identification Number: 051- Legal Description Property Owner Name & Address: Ti 55J 2 i W SE_C. 18 t -:-r 4 D kaxj w fopR lzi4-S'O aUn Ave. CK,u ct_z Ar- 99S -(o-7 Pump Installation Date: ot0 Pump Intake Depth Below Top of Well Casing: feet Pump Manufacturer's Name: Pump Model: E53�:-S ti i3 1 D— Pump Size hp II Pitless Adapter Burial Depth: feet !I Pitless Adapter Manufacturer's Name: vtr Lo)' L+ Pitless Adapter Installer- � � PdPA-- Well Disinfected Upon Completion?M Yes ❑ No , Method of Disinfection: � y� cS�S eo W cc-A� x%.44 Comments: U,)C er �� [✓� 2Af o Pump Installer Name: C� p e�- Attention: The pump installer shall provide a pump installation log to the DSD within 30 days of pump installation. July 27, 2016 Municipality of Anchorage Community Development Department On -Site Services PO Box 196650 Anchorage, AK 99519 RE: 19450 Joy Avenue Septic Lift Station Electrical Installation Dear On -Site Services, The septic system at my home situated at 19450 Joy Avenue, Chugiak was installed during the summer of 2010. The licensed electrician I hired to wire the lift station provided me with a letter certifying the installation met code at the time the work was performed, but I am unable to locate the letter. This letter explains how the lift station electrical was performed. I am providing this letter to submit to the Municipality of Anchorage for approval of my septic system. I personally installed the rough -in electrical from the lift station to the house. I dug a 2' trench and ran the exterior rated 12-3 wire through underground conduit from the lift station junction box to the exterior of the house. I hired a licensed and bonded electrician to perform the connections. He wired the lift station components and installed an exterior junction box and alarm, which he affixed to the exterior of the home. He installed a separate alarm inside the home as well. The pump and alarms are wired on two separate circuits. Photos of the installation are attached. The electrical wiring is installed in accordance with the applicable codes and requirements. It has been functioning properly since it was brought online when I moved into the home in April 2011. The septic system was tested this summer and operates correctly. Please do not hesitate to contact me if you have any questions. Sincerely, Rachael Pope �/ 19450 Joy Avenue Chugiak AK, 99567 907-863-1953 MUNICIPALITY OF ANCHORAGE Development Services Department On -Site Water 6 Wastewater Program 4700 South Bragaw Street P.O. Box 196650, Anchorage, AK 99519-6650 (907) 343-7904 ONSITE WASTEWATER DISPOSAL SYSTEM / WATER SUPPLY PERMIT Initial Permit Number: SWO90171 Date Issued: Sep 02, 2009 Expiration Date: Sep 02, 2010 Parcel ID: 051-171-21 Legal Description: T1 5N R1 W SEC 18 LT 40 Design Engineer: 0070 ARC TERRA ENGINEERING & SU Site Address: NHN JOY AVE Owner Name: JONATHAN & RACHAEL POPE Lot Size: 108900 SO. FT. Owner Address: 16938 PARK PLACE #1 Total Bedrooms: 4 Permit Bedrooms: 4 EAGLE RIVER. A 99577 - This permit is for the construction of: ❑✓ Disposal Field Q Septic Tank ❑ Holding Tank ❑ Privy Private Well ❑ Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specked in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72 ) and Drinking Water Regulations ( 18AAC80 ). 3, The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by tailing (907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must be either: A. Open and closed on the same day. B. Covered, sealed, and heated to prevent freezing. Received Issued By. Date: 3 G Date: — Q C Municipality of Anchorage -�1 Development Services Department Building Safety Division On -Site Water and Wastewater Program 4700 Bragaw Street P.O. Box 196650 Anchorage, Alaska 99519-6650 www.muni.org/onsite (907)343-7904 ON-SITE SEWER/WELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING Parcel I.D. 0,S/ — /7/ —.2/ Property 4' phone Mailing address Ile ?.;S ZwLk'Y'1a-ec FaalAe,"Zip Code 995-77 Site address _A/SV 41? AVe. IA iLgL4.k-, Zip Code Legal description (Sub'd., Block & Lot) Legal description (Township, Range & Section) Lot Size /40,9. 90 Sq. Ft. THIS APPLICATION IS FOR (® all that apply): Absorption Field Septic Tank Holding Tank ❑ Privy ❑ Private Well Water Storage ❑ 7-15 AJ RIYJ Sec_ IS,/ 1,o �i0 e Number of Bedrooms THIS APPLICATION IS AN: Initial V Upgrade ❑ Renewal ❑ certify that the above information is correct. I further certify that this application is being made for a Single Family Dwelling and is in accordance with applicable Municipal Codes. of property owner or authorized agent) Permit/RushFees: $-7;0• " Waiver Fees: Date of Payment: 2 Lj% Date of Payment: Receipt Number: 57:3 !i( Receipt Number. (Rev. 11105) August 7, 2009 ARC 1. ERRA CONSULTING, INC 212 E. 51° Ave, Anchorage, AK. 99503 Office (907) 868-3791, Fax (907) 868-3793 Municipality of Anchorage Development Services Department On -Site Water & Wastewater Program P.O. Box 196650 Anchorage, AK 99519-6650 Subject: New Well & Septic Permit - 715N R1W SEC18 LOT 40 Gentlemen: The owner has requested we proceed forward to obtain well and septic permits on the subject lot. Previous work performed by other engineers is attached for your review and consideration. As shown on the attached as -built survey by Mark Seward, the house has already been started along with a recently drilled well and installed septic tank (which will be removed). The owners have spoken with Development Services Department staff with regards to these issues. On July 30, 2009 we performed percolation tests and water monitoring on the existing testholes. The results of these tests are attached for your review. Also, previous work performed by other engineers is attached for your review and consideration. The owners have attempted and are attempting to acquire original documents, including the well log. If required, additional soil investigation will be done prior to installation. The general slope of this lot is from southeast to northwest at a grade of approximately 0-5% over the proposed septic area. The proposed septic system will serve a 4 -bedroom house. We propose to install a pressurized deep trench. Groundwater was encountered during monitoring at 16.5'. The system has been designed to a maximum depth of 10.5'. T15N Rlw SEC18 LOT 40 August 7, 2009 Page 2 of There is no surface water within 100' of the proposed system and there are no known curtain drains within 50'. We do not expect there to be any adverse effect on adjacent lots by the development of this system. If you have any questions, please contact me at 868-3792/FAX 868-3793. Respectfully submitted, ArcTerra Consulting, Inc. Kenneth M. Duffu s1'.E. Attachments: On -Site Sewer Application Wastewater Absorption System Details/Site Plan Soils Log/Percolation Test Owner/Contractor Specs Soils Log/Percolation Tests (Ronlad Gooden, P.E.) Soils Log/Percolation Tests (S&S Engineering) As -Built Survey (Mark Seward, PIS) Well Log 20441 PTARSIIGAN BLVD • EAGLE RIVER, AK 99577-8736 • PH (907) 868-3791 • FAX (907) 868-3793 WELL & WASTEWATER DISP❑SAL SYSTEM DETAILS/SITE PLA T15N R1W SEC18 LOT 40 NII W. 3 3' OL.#A a sH'r FLAG PR❑PERT LINE WELL RADII & EASEM PRI❑R TO C❑NSTRUCTI❑N NO PUBLIC WELLS WITHIN 200' OF PROPOSED SYSTEM. !O PRIVATE WELLS WITHIN 200' OF PROPOSED SYSTEM EXCEPT AS HOTEL M SEPTIC SYSTEMS WITHIN 200. OF PROPOSED WELL EXCEPT AS HOTEL OF AZ4 1 1 *.49 I 0 KENNETH U.UBFUS•' / �.. CE -7116 ..• �'r ��ssloKa' .�► WN Scaler 1'= 100' DESIGN DETAILS PAGE 1 OF 2 4 BDRM X 150 GPD = 600 GPD 600 GPD/.45 GPD PER SQ. FT. (40 MIN/IN.)= 1,333 SO. FT (1333 / 2 x (8.5' GRAVEL) = 79 FT. TRENCH USE 2 TRENCHES - 40' (L) X 2' (W) X 8.5' (D) Total depth of system Is 10.5' from original grade. Total depth of gravel below distribution pipe Is 8.5' . NOTEST 1. INSTALL 1500 GAL STEP & INSULATE TANK IF (4' COVER. 2. INSULATE TRENCHES WITH 2' HD BURIAL FOAM IF ( 3' OF FILL. MIN. 2' FILL WITH INSULATION, >3' COVER NO INSUL REQ. 3. CONTRACTOR WILL ENSURE MINIMUM 2% SLOPE INTO SEPTIC TANK. 4. CONTRACTOR WILL ENSURE ALL SEPARATIONS TO ADJACENT WELLS, SEPTICS EASEMENTS, PROPERTY LINES, ETC... PREPARED FORT Jon & Rachael Pope 16938 Park Place 81 Eagle River, AK 99577 907-622-8900 FIELD BOOKS .°""D""' BOU STNGHa STAI ASBMT.- DMS OWL RXt ACRD "FILE COMPUTE. DRAW BMW DHEoXEM. KMD DATE 08/07/ MO. NW1155 JOB "" 09-012 WASTEWATER DISPOSAL SYSTEM DETAILS T15N R1W SEC18 LOT 40 OTH09-1 IMT MT x 329.9 PRESSURIZ DISTRIBUTION YSTEM HOLE SPACING DESIGN 1. RESID HEAD = 5' 2. HOLE SI - / .00 GAL. PER HOLE 2 30 PSI 3. 30 GALS (PUMP DELIVERY)/1.00 GALS./HOLE = 30 HOLES 4. 80 LF LATERAL/30 HOLES = 2.6' SPACING PER HOLE 5. ALL HOLES SHALL HAVE CAPS INSTALLED PER MANUFACTURES SPECS. +`� � �� OF ALZ � ^M '.91 u a /* V E JKE-v 'rt - W AKENNETH Y UFFUS CE -7116 AV'� \ '�?OFESSIONI— PREPARED FORT Jon S Rachael Pope 16938 Park Place #1 Eagle Rlver, AK 99577 907-622-8900 FIELD BOOKS souwmr BOUNC STAKM STAKIP AMUIF DMS DMI RE: ACRD iME FILE CouwTm MMAMM: BMW cwocm. KMD DAM 08/07/ am NW1555 "« : 09-012 It Scale, 1'= 30' PAGE 2 OF 2 ro A.\'D Sv AK yp57/'M71A V 4—BR HOUSE Cil W O 0 O N INSTALL S.T. TO BE 1500 • REMOVED o, STEPss 00' WELL 25+/ 7 o_ RADIUS 10' • 5>, 1Y4" PVC TH09-3 17' ESERV MT O O TH09-2 OTH09-1 IMT MT x 329.9 PRESSURIZ DISTRIBUTION YSTEM HOLE SPACING DESIGN 1. RESID HEAD = 5' 2. HOLE SI - / .00 GAL. PER HOLE 2 30 PSI 3. 30 GALS (PUMP DELIVERY)/1.00 GALS./HOLE = 30 HOLES 4. 80 LF LATERAL/30 HOLES = 2.6' SPACING PER HOLE 5. ALL HOLES SHALL HAVE CAPS INSTALLED PER MANUFACTURES SPECS. +`� � �� OF ALZ � ^M '.91 u a /* V E JKE-v 'rt - W AKENNETH Y UFFUS CE -7116 AV'� \ '�?OFESSIONI— PREPARED FORT Jon S Rachael Pope 16938 Park Place #1 Eagle Rlver, AK 99577 907-622-8900 FIELD BOOKS souwmr BOUNC STAKM STAKIP AMUIF DMS DMI RE: ACRD iME FILE CouwTm MMAMM: BMW cwocm. KMD DAM 08/07/ am NW1555 "« : 09-012 It Scale, 1'= 30' PAGE 2 OF 2 ro A.\'D Sv AK yp57/'M71A r �RCTERgq '� ARCTERRA CONSULTING, INC e 212 E. 51" Ave, Anchorage, AK. 99503 Office (907) 868-3791, Fax (907) 868-3793 a �n•N� SOILS PERCOLATION TEST Performed for: Rachael Pope Date Project: T15 N R1 W SFC 18 LOT 40 TEST HOLE # ' TH 09-1 Depth Org / OL CP/SP Gnt/Snl PERC BENCH 7- 8- 14- 15- 16- 17- 18- 19- 20 - SEE ATTACHED S&S SOILS LOG IIOLE PRESOAKED PRIOR TO TEST SEE ATTACHED SITE PLAN FOR IIOLE LOCATION Was Groundwater encountered? — Whatdepth? — Depth to water after monitoring? 16.5' Date? 7/30/09 Reading Date Gross Time Net Time Depth to Water Net Drop 1 7/30/09 1:00 6" _ 2 1:30 30 min 5 4/16" 12/16" 3 1 1:30 1 - 5 4/16" 1 - 4 2:00 30 min 4 8/16" 12/16" 5 2:00 4 8/16" 6 2:30 30 min 3 12/16" 12/16" 7 8 9 10 I 12 • Water Added Percolation Rate 40 (min/in) Perc Hole Diameter 6" Test Run Between 6.5 feet and 7.5 feet 1, Kenneth M. Duffus, certify that this test was performed in accordance with all State and Municipal guidelines in effect on this date. r Q'RCTERRq '� t ARCTERRA i CONSULTINC,, INC 4 a 212 E. 5l' Ave, Anchorage, AK. 99503 It Office (907) 868-3791, Fax (907) 868-3793 SOILS PERCOLATION TEST Performed for: Rachael Pope Date Project: T15 N R1W SEC 18 LOT 40 TEST IIOLE N +T1109-3 IA•pth ....- - -... (Feet) SEE ATTACHED SITE PLAN FOR HOLE LOCATION 0 6- 8- .�I 9- INTEREDIATE 10- PERC TEST BETWEEN TII09-1 & TII09-2 It- 19- HOLE PRESOAKED 20- PRIOR TO TEST NA Whatdepth? NA NA Date? NA Reading •t .d.•. Org/OL _ Depth to Water Net Drop 1 Was Ground water encountered? 2 1 GP/SP - 3 Gni / S1%1 Depth to water after monitoring? 18/16" 3 y*' 'P, PERC BENCH 4 8/16" 0 6- 8- .�I 9- INTEREDIATE 10- PERC TEST BETWEEN TII09-1 & TII09-2 It- 19- HOLE PRESOAKED 20- PRIOR TO TEST NA Whatdepth? NA NA Date? NA Reading Date Gross Time Net Time Depth to Water Net Drop 1 7/30/09 1:00 6" - 2 1:30 30 min 4 8/16" 18/16" 3 1:30 4 8/16" 4 2:00 30 min 3" 18/16" 5 2:00 3" 6 2:30 30 min 18/16" 18/16" 7 8 9 10 Il 12 • Water Added Percolation Rate 20 (min/in) Perchole Diameter 6" Test Run Between 4.5 feet and S_ feet I, Kenneth M. Duffus, certify that this test was performed in accordance with all State and Municipal guidelines in effect on this date. � } � | |�!£! fid 9' lz��z |�!§! !!!( 1--.. � ca | } % ; E5=2 2 R5- I ;; !� ar f1�33y; ; E5=2 2 R5- Municlp31ity of Anchorage Development Services Depallment / Volkling Salcly Dmgm, 1 •� +..� dl Sit" VJatnr end Wnxlewaler Fnq,am I\ 4700 SaAn orapnw SI. ' F.D. Dox 1911050 Anthora9e, AK 99519 6050 i �\".. www.nmd ayrxlnlln (907) 343 791141 Soils Loc Percolation Test Fedmnmd Fana 1AT7iAF Ln11a1 l4anlFlion�L^'�-�+-1��� WOO Fel to �j-�r—y.I.---_�.}: elll) 7ownshi4,Rnn9n.5ectinn• 4 5 V G- 7 - Is. Cn1,11jul —O¢GnUtc,S — Ml.. Colt1I,zSj — 6AI INCH WAS E) WATER Net Drop ENC0tjNCOUNIIREDr Or YES. At YNIAt DEeIIp s �' l apt" 1" W.t.r AM., --777— D — M"MI"r4g7 � LMT" R""nbq D"In Gross Tone �,m 9 PF RCOLATION ru IE TEST RLRI Or T`hT.Ell—r! �-A6'tl N.174n" Net Drop rs�jl of ;5 I u Fr,RC I*IF MAW IF.R rt PLRrORt•trDOY%�e� 7 -- PI, RrORMEDINACCOIIDANCCVII! All $TATE AI`)tdUNICIFr11�O)vrL CERT It Y (I IAT TO 115 TLSr 4VA- 1IIIFrI r C r ON I I IIS OA I E DATE IT is 'iHG I=PLNSIBZLITY"OF mm ON.ER OR BDIIDER • y� PRiCR TC ax;sTRUCPICN.To VERIFY P7^16ID m=Z-C GRADE RELATIVE TO.FIN7,=;;MmE 7.._, VSILITY COmIF7CITCNS. Atm; , DEl'F3L�ipX TRE •E7QSTEm OF ANY EASE?4ST!'S,'WVE: ,�cpjjg�1RIC1'IONS WHICH DO NOT APPEAR ON = REOORDID SRJPDIVISION PLAT. NOTE: ELEVATIONS ARE ASSUPID DATUM. Y o fQ h s abs �o f1' a ' b I HEREBY CERTIFY THAT I HAVE SURVEYED THE FOLLOWING DESCRIBED PR,OPPERTY: AND THAT NO NCRQ4CHME TSE ST t7(LEPi AS INDICATED. IT IS THE RESPONSIOILITY OF THE OWNER TO DETERMINE THS EOSTENCE OF ANY EASEMENTS, COVENANTS, OR RESTRICTIONS WHICH DO NOT APPEAR ON THE RECORDED SUBDI- VISION PLAT. UNDER NO CIRCUMSTANCES SHOULI ANY DATA HEREON BE USED FOR CONSTRUCTION OF FENCE LINES, OR FOR ESTABLISHING BOUND- ARY LINES. �rI rp, a� s bzwmuI h NJl1l.1XIC5 6 Nsl SIIIfVCTl6� SCALE> =yo of '%% DATE• r hP' •.....}}...'9 GRID•✓ it/iST 1 0...,. r..: e....eFBI DrtAWO�f ,51�°r'•�1e,8 �fi: a �RCTERRq ,� ARCTERRA CONSULTING, INC ' •�; ', a 212 E. 510 Ave, Anchorage, AK. 99503 —, N,N� ��Office (907) 868-3791, Fax (907) 868-3793 ON-SITE WASTEWATER DISPOSAL SYSTEM CONSTRUCTION PRACTICES AND MATERIAL SPECIFICATIONS LEGAL DESCRIPTION: T15N R1W SEC18 LOT 40 GENERAL: 1. The scope of this project includes the installation of a septic tank and/or drainfield to serve a single-family residence on the referenced property as delineated on the attached Municipality of Anchorage (MOA) permit and site plan. Construction shall be in accordance with the approved site plan and design drawings; MOA permit with any special provisions or conditions, and all applicable State and Municipal Wastewater Disposal Regulations. 2. ArcTerra Engineering & Surveying, Inc. (ArcTerra) assumes no responsibility of the accuracy of the as -built survey provided by the owner or owner's representative. 3. The owner or contractor is responsible to notify the engineer of any discrepancies noted on the design plans or drawings prior to commencing work. These discrepancies could be, but not limited to, possible encroachments, surface water, varying soils, unplatted easements, types or use of dwellings on or adjacent to property, nearby public wells, etc. 4. The contractor shall be responsible for locating any necessary underground utilities, easements, property lines and surface water. The owner and/or contractor shall ensure, if deemed appropriate, that a registered land surveyor prior to construction flags all setbacks. The contractor shall be responsible for verifying all pertinent separation distances and component layout. 5. Unless specifically agreed otherwise, the property owner shall be responsible for final grading areas subsequently depressed from soil settling. On all leachfield mound systems, the property owner shall be responsible for ensuring a satisfactory vegetation growth over the mounded area. 6. The MOA Development Services Department On -Site Water & Wastewater Program must certify contractors installing wastewater disposal systems. Owners installing their own systems must also receive prior approval from said MOA Department. SEPTIC TANK / IIOLDING TANK/LIFT STATION INSTALLATION: 1. A septic tank is to be constructed by a certified septic tank manufacturer. Construction shall include two 4" cleanouts for pumping access. 2. The septic tank shall be sufficiently bedded with proper material and compacting to prevent damaging, settling or shifting of the tank. 3. All standpipes on the septic tank shall extend a minimum of 12 inches above the final grade. n5N R1W SEC1S LOT40 August 7, 2009 Page 2 of 4 4. Septic tanks installed with less than 4 foot of cover shall be insulated. The contractor will ensure that the fill over the tank does not exceed the burial depth rating. 5. A foundation cleanout shall be installed one to four feet from the building foundation. In the line between the tank and the leachfield there shall be two adjacent cleanouts (unless an effluent pumping system exists within the septic tank). These cleanouts shall be located on undisturbed soil not more than 10 feet from the tank. The second cleanout, in line, shall be to clean toward the septic tank. 6. Final grading over the septic tank shall be such that a positive slope exists away from the septic tank. 7. All H.D.P.E. tanks shall have a vertical length of 4 -inch perforated drainpipe besides the tank extending to the bottom of the tank to above grade to monitor ground water. 8. All tanks shall be anchored when there is not enough adequate soil cover to resist buoyancy forces in high -groundwater areas. 9. All holding tanks and lift stations shall have an audible and visual alarm inside the residence. 10. All lift stations shall be wired in compliance with the Uniform Electrical Code and all MOA guidelines. 11. The contractor shall remove the old tank, or abandon it in compliance with the Uniform Plumbing Code. The contractor is solely responsible for the abandonment procedure. ABSORPTION TRENCII/DRAINFIELD INSTALLATION: 1. Excavate the proposed trench to the dimensions shown on the design. The bottom of the excavation shall be within 2 inches of level. If the sidewalls of the excavaction become smeared, they must be raked or scratched (roughed -up) before gravel (sewer rock) placement. 2. Once the sewer rock is installed, the distribution pipe is installed level with the perforations facing downward. Gravel is then to be placed over the distribution pipe to provide a minimum of 2 inches of cover over the pipe. 3. A silt barrier must be installed between the final gravel layer and the native soil backfill. Ensure the silt barrier covers the entire gravel surface before placing backfill. 4. Monitoring tubes shall be four- (4) inch diameter, installed approximately in the locations shown on the design, and extend a minimum of 12 inches above final grade. The portion of the monitoring tube extending through the gravel shall be perforated from the bottom of the trench to the invert of the distribution pipe. This is equivalent to the effective depth of the gravel as noted on the design. 5. Backfill over the final gravel layer must not be less than twenty-four inches. Insulation must be installed when the backfill depth is less than thirty-six (36) inches. The finish grade over the trench must be mounded to prevent the formation of a depression after settling. 6. All advanced technology waste water disposal systems (Advantex, Biocycle, Intermittent Dosing Sand Filter, etc...) shall be constructed, installed, maintained and monitored per manufacturer's specifications and MOA requirements. 2044117ARMIGAN BLVD • EAGLE RIVER, AK 99577-8736 • PFI (907) 868-3791 • FAX (907) 868-3793 T15N RIW SEC18 LOT40 August 7, 2009 Page 3 of 4 MINIMUM MATERIAL SPECIFICATIONS: 1. A MOA approved septic tank manufacturer must construct any septic tank proposed for installation. 2. The following pipe materials are MOA approved for use in septic system installations: Tyre of Pipe Perforated Solid Cast Iron Yes Yes ASTM D3034 (PVC) Yes Yes ASTM F810 (HDPE) Yes No ASTM D2662 (ABS) Yes Yes 3. Insulation shall be at least 2" thick extruded direct burial polystyrene (Dow Chemical Company Styrofoam HI or equal). 4. Septic tank inlets and outlets shall be fitted with watertight couplings (Caulder, Femco, or equal). 5. A permeable nontoxic silt barrier (Typar 3401, Mirafi 140N, or equal) must be installed between the final leachfield gravel layer and the native soil backfill. 6. All leachfield gravel (sewer rock) shall be 0.5"-2.5" screened gravel with less than 3% passing the #200 sieve. If deemed necessary, a sieve analysis should be performed. 7. When sand is being used as a filter material, its gradation specification must conform to current MOA or ADEC requirements. INSPECTIONS: Typically there will be three (3) inspections required during the installation of the wastewater disposal system. These inspections will occur as follows: 1. The first inspection must be conducted after the excavation of ditches, pits, trenches, or beds and before the installation of any gravel. A septic tank may be set in place, but may not be backfilled before this inspection. 2. The second inspection must be conducted after the placement of the sewer rock, distribution lines, standpipes, and cleanouts, but before the placement of the silt barrier, insulation, or any other backfill. 3. The final inspection is to occur upon final grading of the property. Often there will be more than these 3 inspections required, especially with the installation of multiple trenches, sand filters, pressurized distribution systems, etc. The inspecting engineer is to be contacted at least 24 hours prior to the start of construction. If necessary, a pre -construction meeting will take place on-site. The inspecting engineer will not coordinate, direct or control in any way the contractor's activities. The owner shall contract with the contractor to perform the work outlined in these specifications and attached plans and in accordance with the attached MOA permit. All materials, components, and construction practices shall comply with the MOA's and the State of Alaska's latest ordinances, regulations, or policies regarding wells and septic systems. The failure of the inspecting engineer to notice a material or construction non- compliance does not relieve the contractor of his/her responsibility to correct such deficiency. There will be no contractual arrangement existing between the contractor 20441 PTARMIGAN BLVD • EAGLE RIVER, AK 99577-8736 • PH (907) 868-3791 • FAX (907) 8683793 T15N R1W SECTS LOT 40 August 7, 2009 Page 4 of 4 and ArcTerra. ArcTerra shall be the owner's representative and will inspect the work as stated above to document the contractor's activities. Final acceptance of the contractor's work rests with the owner and the MOA. ArcTerra shall have no liability to the owner or to others for acts or omissions of the contractor or any other persons performing work on this project or the failure of the contractor to carry out the work in accordance with these construction documents. ArcTerra's inspecting engineer will not be responsible for the construction means, methods, and techniques, sequence, procedures or the safety precautions incident to this project. BY PROCEEDING FORWARD WITH THE INSTALLATION OF THE WATER AND/OR WASTEWATER SYSTEM (S), THE PROPERTY OWNER, CONTRACTOR, AND WELL DRILLER ACKNOWLEDGE HAVING READ AND ACCEPTED THESE SPECIFICATIONS. 20441 PPARMIGAN BLVD • EAGLE RIVER, AK 99577-8736 • PH (907) 868-3791 • FAX (907) 868,3793 Z. 7-410 41 41,7 C t4,)f (! / C/ 5ed% Certificate of On -Site Systems Approval Parcel I.D. 051 171 21 1. GENERAL INFORMATION Expiration Date: VlRAtA '2— 0"'7'0.2:z Complete legal description T15N R1 W SEC 18 LOT 40 Location (site address) 19450 JOY Current property owner(s) Mailing address Day phone Ream estate agent Day phone 2. TYPE OF DWELLING: R Single Family (w/ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 4 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Private Well El Private Septic n Water Storage ❑ Holding Tank ❑ Community Well ❑ Community ❑ Public Water System ❑ Public Sewer ❑ Waiver request for: N O N E q _ Distance: Received by: COSA to be released to the engineer, unless otherwise requested by the engineer. Date: COSA Fee $__f5 Waiver Fee $ Date of Payment 2 16 20V Date of Payment Receipt Number 0 (S0 5 (o � Receipt Number COSA # O S C z 11 '71 / Waiver # 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is (are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm C&M ENGINEERING Phone 8545558 Address 20182 TULWAR Engineer's Printed Name CHARLES BALZARINI Date 12/15/21 OF A4.qlow S>�� 6. DSD SIGNATURE % *• 1N • • • • :* ..::: r System #1 Approved for 47( bedrooms r CHARLES G BALZARN1 System #2 Approved for bedrooms ¢ �`��s.. CE -13854 Disapproved ���1F�F�pROfE5S1�N��� Conditional approval for bedrooms, with the following stipulations: `Tlna� i s Co ef� bitld er,M' VI W of - %t.Li �d►ne �e rrr�,'�. ��QrS2 �� ON-SITP By: Original Certificate Date: I2 2G .2d - The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 7. ATTACHMENTS: COSA Checklist X Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other COSA Checklist blue sheet COSA Checklist yellow sheet COSA Checklist Legal Description: Parcel ID: If more than 1 septic system on lot: COSA Checklist # of Structure served by this system A. WELL DATA Well log is filed with Onsite (or attached) Date drilled Total depth ft Cased to ft Sanitary seal is functioning correctly Wires are properly protected Casing height (above ground) in. Date of flow test for COSA Static water level at beginning of test ft. Well production at time of test gpm Water storage tank volume gallons Well disinfected for coliform test? Yes No Coliform bacteria is Negative Nitrate mg/L Nitrate less than MRL (ND) Arsenic ug/L Arsenic less than MRL (ND) Collected by Date of Sample Comments __________________________________________________________________________________ C. LIFT STATION Required maintenance completed Age of lift station years Lift station material Comments: ALL standpipes present per record drawing Total measured depth from grade ft (max) Measured depth to pipe invert from grade ft (min) N/A – pressurized field Monitor tubes go to bottom of effective. If not, state depth into effective Code-required soil cover over field System presoaked (Required if vacant for greater than 30 days prior to date of test) Gallons introduced gallons Adequacy test date Results Pass For bedrooms Fluid depth prior to test in Water added gal New depth in Elapsed time min Final fluid depth in Absorption rate gpd Any rejuvenation treatment (past 12 months) If yes, enter date Comments/Deficiencies: B.TANK DATA Age of tank(s) years Tank type/material6WHHO Measured operating fluid level in septic tank Standpipes/foundation cleanout per record drawing Date of pumping D.ABSORPTION FIELD DATA ______________________ Which system tested (date installed) T15N R1W SEC18 LOT 40 051 171 21 11 1 1.6 8/20/07 - 60 60 1.64 +18 C.Balzarini 12/10/21 22 12/15/21 Pump appears to be set at 42' 12 STEP NA 12 STEEL 12/6/21 Maintenance performed trench 2009 12/10/21 4 10.5 2 600 4 10 2 600 NA NA ✔ COSA Checklist yellow sheet E. SEPARATION DISTANCES From Private Well on Lot to: (Please enter distances if less than required or if community well) Septic Tank/Lift Station on Lot > 100’ Yes if No ft Neighboring Tank > 100’ Yes if No ft Absorption Field on Lot > 100’ Yes if No ft Neighboring Absorption Fields > 100’ Yes if No ft Community Sewer Main > 75’ Yes if No ft Community Sewer Manhole/Cleanout > 100’ Yes if No ft Private Sewer/Septic Line > 25’ Yes if No ft Holding Tank > 100’ Yes if No ft Animal Containment > 50’ Yes if No ft Manure/Animal Excreta Storage > 100’ Yes if No ft From Septic/Holding Tank on Lot to:(Please enter distances if less than required) Building Foundations > 10’ Yes if No ft Property Line > 5’ Yes if No ft Absorption Field > 5’ Yes if No ft Water Main > 10’ Yes if No ft Water Service Line > 10’ Yes if No ft Surface Water > 100’ Yes if No ft Wells on Adjacent Lots: Private Wells > 100’ Yes if No ft Community Wells > 200’ Yes if No ft If septic tank is under driveway comment below From Absorption Field on Lot to: (Please enter distances if less than required) Building Foundation > 10’ Yes if No ft Property Line > 10’ Yes if No ft Water Main > 10’ Yes if No ft Water Service Line > 10’ Yes if No ft Surface Water > 100’ Yes if No ft If absorption field is under driveway comment below Wells on Adjacent Lots: Private Wells > 100’ Yes if No ft Community Wells > 200’ Yes if No ft F. ENGINEER’S COMMENTS G. ENGINEER’S CERTIFICATION I certify that I have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date.12/16/21 ✔✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ MUNICIPALITY OF ANCHORAGE Development Services Department , >} Phone: 907-343-7904 On -Site Water & Wastewater Section Fax: 907-343-7997 Owner fjc�?LEtz_ Lift Station/Pump Vault Maintenance Log Street Address ( qu�0 ,TO Y Septic Tank: -Sludge level inches -Pumping: required yes n -Pumping completed s no Lift station: -Pump basket cleaned Qe no -Effluent filter cleaned a no -Control floats cleaned yeno -Proper float settings confirmed no -Operation satisfactory a no Alarm System: -Dedicated electrical alarm circuit a no -Audible and visual alarm inside dwellin a no -Alarm system operation atisfacto not satisfacto Manhole Riser -Ground water intrusion at riser to tank connection yes ho -Ground water intrusion around pipe penetrationses n -Weep hole functional es no -Manhole lid: Functional a no Insulated , es no Properly Secure a no Other -All manufacturer required inspections and maintenance completed no Comments: Qualified Maintenance Provider: Technician r,4 Company Signature Date of maintenance'/ 1C91d Date )_r/P • Municipality of Anchorage On -Site Water and Wastewater Program" (907)343-7904 CERTIFICATE OF ON-SITE SYSTEMS APPROVAL Parcel I.D. 051-171-21 1. GENERAL INFORMATION Complete legal description T15N RlW SEC18 LOT 40 Expiration Date: -1 ( '31- ( ( Location (site address) 19450 JOY AVENUE CHUGIAK, AK 99567 Current Property owner(s) RACHAELA. POPE Day phone Mailing address Real Estate Agent 2. TYPE OF DWELLING: 19450 JOY AVENUE, CHUGIAK, AK 99567 ® Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) Day phone 3. NUMBER OF BEDROOMS: 4 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Individual Well ® Individual Individual, Water Storage ❑ Holding Tank ❑ Community'Glass —Well ❑ Community ❑ Public Water System ❑ Public Sewer ❑ WaiverNariance request for: Distance: Received by: � �o Date:— /G COSA to be released to the engineer, unless othA i; quested by the engineer. COSA Fee $ 526.Od Waiver Fee $ Date of Payment 8--2-16 / Date of Payment Receipt NumberReceipt Number COSA# Waiver# 6. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm ARCTERRA CONSULTING INC Phone 868-3791 Address 20441 PTARMIGAN BLVD., EAGLE RIVER AK 99577 Engineer's Printed Name KENNETH M. DUFFUS Date 7128116 Engineers Comments: This investigation was completed in compliance with ADEC and MOA regulations. The assessment of the condition of the well and septic applies only to the conditions as of the day tested. The flow and absorption rates may change due to subsurface conditions that may not be observed from the surface, changes inland use, local soil characteristics, groundwater levels that may fluctuate during the year and the water usage of the family being served by the system. The operational life of all well and septic systems are subject to these various and dynamic characteristics and are outside the control of the evaluator of the well and septic system. Therefore, ArcTerra can not give any estimate of how long a - system will function satisfactory for current or future occupants or can ArcTerra guarantee that no unseen OFA \ \ encroachments, deficiencies or discrepancies exist. LAS , 6. DSD SIGNATURE ? KENNETH0 .. FEll4 System #1 Approved for bedrooms. ,,171 a System #2 Approved for bedrooms.PE's 1041 Disapproved. Conditional approval for 1 The Municipality of Anchorage Development Services bedrooms, with the following Original Certificate (DSD) issues Certificates of On -Site Systems Approval (COSA) upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineers work. ATTACHMENTS: COSA Checklist X Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other Cosa b1m sheet -10-1 D-12.dm If more than 1 septic system is on the lot: COSA Checklist # of _ Structure served by this system _ Certificate of On -Site Systems Approval Checklist Legal Description: T15N R1W SEC18 LOT 40 Parcel ID: 051.171.21 A. WELL DATA Well type PRVT If A, B, or C provide PWSID # Date complete/2012007 Sanitary seal (Y/N) Y Total depth 60 ft. Cased to 60A/ pert at 45.50 ft. FROM WELL LOG Date of test 8.20.2007 Static water level 25 ft. Well production 7 g.p.m. WATER SAMPLE RESULTS: Coliform NMp colonies/100 mL Nitrate 2.10 mg/L Arsenic: ND ug/L Date of sample: 616/2016 B. SEPTIC/HOLDING TANK DATA Tank Type/Material SEPTIC / STEEL Tank size 1500 gal. Number of Compartments 2 Foundation cleanout (Y/N) Y Depression over tank (Y/N) N Date of pumping 6/3/2016 Pumper JRs C. ABSORPTION FIELD DATA Well Log (Y/N) Y Wires properly protected (Y/N) Y Casing height (above ground) 24+ in. AT INSPECTION 6/6/2016 ft. 0.85 9 - P.M - Collected by: ARCTERRA Date installed o?D d Cleanouts (Y/N) Y High water alarm (Y/N) Y Date installed 7130/2009 Soil rating (g.p.d.M2 or ft2/bdrm) 0.45 System type DEEP TRENCH Length (2 x 401) 80 ft. Width 2 ft. Gravel below pipe 8.5 ft. Total depth 11* ft. (measured 7012016) Eff. absorption area 1376 ftz Monitoring tube Y Depression over field N Date of adequacy test 6/3/2016 Results (Pass/Fail) PASS For 4 bedrooms Fluid depth in.absorptign field before test 0 /2 in. Water added 600 gal New depth 012 in. Elapsed Time. <5 miii. final fluid depth 012 in. Absorption rate >= 600+ g.p.d. Any rejuvenation treatment (past 12 mo.) (Y/N & type) N If yes, give date D. LIFT STATION Date installed Size in gallons 1500 Manhole/Access (Y/N) Y "Pump on" level at 44 in. "Pump off' level at 42 in. High water alarm level at 48 in. Datum Bottom of Tank Cycles tested 2 Meets alann & circuit requirements? Y E. SEPARATION DISTANCES WELL ON LOT TO: Septic tank/lift station on lot 1001+ Absorption field on lot 1001+ Public sewer main 751+ Sewer /septic service line 251+ Animal containment areas 501+ SEPTIC/HOLDING TANK ON LOT TO: Building foundation 54 Property line 51+ On adjacent lots 1001+ On adjacent lots 1001+ Public sewer manhole/cleanout 1004 Holding tank 100'+ Manure/animal excrete storage areas 1004 Absorption field 54 Water main 104 Water service line 101+ Surface water Wells on adjacent lots 1001+ ABSORPTION FIELD ON LOT TO: Property line 101+ Building foundation 104 Water main 104 Water Service line 101+ Surface water. 1001+ Driveway, parking/vehicle storage 10'+ Curtain drain 50'+(NONE KNowN) Wells on adjacent lots 1001+ F. COMMENTS G. ENGINEER'S CERTIFICATION I certify that I have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. Engineer's Printed Name KENNETH M. DUFFUS Date 7128/2016 COSA canary sheet_2-6-15.doc OF�AL-� 4P1H�l� _`��. P KE\NE M. VE X SSio'4t V Municipality of Anchorage Development Services Department 3 >; Building Safety Division On -Site Water and Wastewater Program 4700 Elmore Street P.O. Box 196650 Anchorage, AK 99519-6650 www.ci.anchorage.ak.us (907)343-7904 Water Well Advisory Certificate of On -Site Systems Approval (COSA) # OSC161333 During a recent COSA on-site inspection and test of the potable water supply well on Block T15N R1W Sec 18, Lot 40 of subdivision, the well's productivity was determined to be 0.95 gallons per minute. The minimum well productivity required by this Department (AMC 15.55) for a 4 -bedroom residence is 0.41 gallons per minute. Although the subject well currently exceeds this minimum requirement, all parties concerned are advised that the production capacity of the well may fluctuate. Restriction of non-critical water uses such as washing cars and watering lawns and gardens may be required. This advisory must be attached to all copies of the subject Certificate of On - Site Systems Approval. r 0 H LOT 29 Aion •q 71 G nIlw znn c�, ANCHORAGE RECORDING DISTRICT, ALASKA AS -BUILT OF: BLM LOT 40 T15N RI W SECI8 SEWARD MERIDIAN SURVEY CERTIFICATION: 1, John L. Schuller, have conducted a physical survey of this property as shown on this drawing and that the improvements situated thereon are within the property lines and no enchroachments exist other that noted. EXCLUSION NOTES: It is the owners responsibility to determine the existence of any easements, covenants, or restrictions which do not appear on the recorded subdivision plat. Under no circumstance should any information on this drawing be used for construction of fences, structures, improvements, or for establishing boundary lines. WORK ORDER NUMBER: DATE SCALE: JE -MAIL - AUG -MAIL AUG 6, 2016 1"=40' 16-047 DRAM IM CHECKED dYj GRID NUMBER: BOOK/PAGE: JLS NW1155 160161 LOT 59 oF _4Z %% 49111 .......... ........ .JOHN L. SCHULLER.- s. LS -10408 '�►: a '' .8.' {e: L6o ' ago ' = FND ALUMINUM MONUMENT = FND RBBAR 0 �5 O PDL NDR Pe• Lia` a �r 1831 Talkeetna Street Anchorage, Alaska 99508 (907) 227-1455 office (907) 274-4992 fax ;A :D