Loading...
HomeMy WebLinkAboutBURG LT 97B 051 - 172 -55  O Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program, 4700 S. Bragaw St. 'x,.,...,~ P.O. Box 196650 Anchorage, AK 99519-6650 Page of www.ci.anchorage.ak, us (907) 343-7904 ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT Permit Number: OSP101253 PID Number: 051-172-55 Name: Robert & Barbara Hoffman Wastewater System: [] New [] Upgrade Address: PO Box 770309, Eagle River~ AK ~9577 ABSORPTION FIELD Phone: Number of Bedrooms: ~, [] Deep Trench [] ShallowTrench [] Bed [] Mound [] Other: LEGAL DESCRIPTION se, Rating: Total Depth from original grade: Block: Lot: Subdivision: 0.8 GPD/Ft2 ~ Ft, Depth to pipe bottom from original grade: Gravel depth beneath pipe: 97B BURG 4.9 Ft. 1.1 Ft. Township: Range: Section: Fill added above original grade: Gravel Length: 0.8- 1.7 Ft. 1~' Ft. Well: [] New [] Upgrade GraveJwidth: Number of lines: I Distance between lJnes: 5 Ft. 2[ 10 Ft. Classification (Private, A, B, C): Total Depth: Cased to: Total absorption area: Pipe Material: Existing Ft. Ft. 761 Ft2 D3034 Driller: Date Drilled: Static Water Level: Installer: Date Installed: Ft. RPC 6/10/2011 Yield: I Pump Set at: I Casing Height Above Ground: GPM[ Ft.[ Ft. TAN K SEPARATION DISTANCES [] Septic [] Holding [] S.T.E.P. [] Other: · T~ To Septic Absorption LiE Holding ~ublic/Private Manufacturer: Capacity: Tank Field Station Tank Sewer Line Anchorage Tank 1250 GaL Well 100' 100'+ I00'+ NA 25'+ Material: Number of Compartments: Steel 2 Su,faoeW~ter 100'+ 100'+ 100'+ NA ~ / LIFT STATION Lot Line 5~'l' 7~+ 5~'1' NA~ Size: Manufacturer: Gal. Foundation 5~+ 10~+ 5'+ NA ~ "Pump on" level at: "Pump off" level at: in. High water alarm at: in. in. Curtain Drain NA * 509+ NA NA Pump Make & Model Electrical Inspections performed by: Remarks: · None known. Additional pert test performed at north end BENCH MARK of field. Tank insulated. Location and Description: -- Garage Floor Assumed Elevation: 100 Ft. Engineer's Stamp Inspections performed by: ArcTerra Dates: 1sT & 2ND 6/6-6/11/2011 3RD 6/13/2011 Development Se. rvices Department }Approval Reviewed and approved by: ~_~.,..¢'~'/.~,_ ~~ Date: C;~ _/C- / t A3-BUILT 3Y3TEM DETAILS/3ITE PLAN PerMi~ oseioie53 BURG LnT 97B PID~ 05i-i7a-55 LOT 97B / ~ II IEKISTIN 4-BR -- - _ _~L HOUSE ; SCALE, l' = 50' ^-c=~,F' ~~ ' ~~ = : - ~ -:-- ~B-E=68,5' ~ / IS~ c ~ ~-F=73,4' ~ ~ ~ 3H ~ _ L ~B-H=88,1' II II ~ II s~ R~c~ EagLe Rive~, AK 99577 I *~ "~ O0 ~ ~: 10-179 />e~ UL~O, · AK. 99577 ~~ FINAL GRADE 1250 GALx --;~ ~ SEPTIC ~ I~ ~ ~X'l~ TRENCH 1 Performed for: Project: Depth (Feet) 1- 2- 3- 4- 5- 9- 10- 11- 12- 13- 14- 15- 16- 17- 18- 19- 20- Robert Hoffman .~,_.~....... ~.~* .." A-'"..y~ 20441 Pt~ig~ B~vd., Eagle R~wr AK 99577 ~ ~~~. Office (907) 696-6111, Fax (907) 868-3793 ~ ~_ CE 71 SOILS PERCOLATION TEST Date Performed: Burg Lot 97B TEST HOLE # TH 11-1 ORG/OL SEE ATTACHED SITE PLAN FOR HOLE LOCATION SM/GM B.O.H. HOLE PRESOAKED PRIOR TO TESTING Was Ground water encountered? YES Depth to water after monitoring? NA What depth? 13' Date? NA Reading Date Gross Net Depth to Net Time Time Water Drop 1 6/10/11 1:00 6" 2 1:30 30 min 2 15/16" 3 1/16" 3 * 1:31 6" 4 2:01 30min 2 15/16" 3 1/16" 5 * 2:02 - 6" 6 2:32 30 min 3" 3" 7 8 9 10 11 12 · Water Added Percolation Rate 10 (rain/in) Pcrc Hole Diameter 6" Test Run Between 6~ feet and 7 feet I, Kenneth M. Duffus, certify that this test was performed in accordance with all State and Municipal guidelines in effect on this date. Permit Number: Tax Code Number: Work Type: On-Site Wastewater Disposal System Permit OSP101253 05117255000 Septic MUNICIPALITY OF ANCHORAGE Development Services Department On-Site Water & Wastewater Program 4700 Elmore Road, PO Box 196650 Anchorage, AK 99519-6650 Telephone: (907) 343-7904 Upgrade Permit Effective Dates: October 29, 2010 to October 29, 2011 Design Engineer: ARC TERRA CONSULTING INC Subdivision: BURG Site Legal Address: Owner/Address: BURG LT 97B G:1155 HOFFMAN ROBERT M & BARBARA R PO BOX 770309 EAGLE RIVER AK 995770309 Site Mailing Address: 19939 ADRIAN AVE, Chugiak Lot Size in Sq Ft: 50661 Total Bedrooms: 4 This permit is for the construction of: Y Disposal Field Y Septic Tank N Holding Tank N Privy N Private Well N Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80). 3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either: A. Open and Close on the same day. B. Covered, sealed, and heated to prevent freezing. Received Issued By: Date: /~' Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program 4700 Bragaw Street P.O. Box 196650 Anchorage, Alaska 99519-6650 www. muni. org/onsite (907) 343-7904 ON-SITE SEWER/WELL PERMIT APPLICATION FOR A SINGLE FAMILY DWELLING !~1~.~ Parcel I.D. 051-172-55 Property owner(s) ROBERT & BARBARA HOFFMAN Mailing address PO BOX 770309, EAGLE RIVER, AK Site address 19939 ADRIAN AVE, CHUGIAK, AK Day phone .Zip Code 99577 .Zip Code 99567 Legal description (Sub'd., Block & Lot) BURG LOT 97B Legal description (Township, Range & Section) Lot Size 50661 .Sq. Ft. Number of Bedrooms 4 THIS APPLICATION IS FOR ([~ all that apply): Absorption Field [] Septic Tank [] Holding Tank [] Privy [] Private Well [] Water Storage [] THIS APPLICATION IS AN: Initial [] Upgrade [] Renewal [] I certify that the above information is correct. I further certify that this application is being made for a Single Family Dwelling and is in accordance with applicable Municipal Codes. ARCTERRA (Signature of property owner or authorized agent) Permit/Rush Fees: $530.00 Date of Payment: / ~ - Receipt Number: ~ z&'/.~" ' (Rev. 11/05) Waiver Fees: Date of Payment: Receipt Number: ARC~]~RP.A CONSULTING, INC 20441 Ptarmigan Blvd., Eagle River, AK. 99577 Office (907) 868-3791, Fax (907) 868-3793 October 21, 2010 Municipality of Anchorage Development Services Department On-Site Water & Wastewater Program P.O. Box 196650 Anchorage, AK 99519-6650 Subject: Upgrade Sewer Permit - Burg Lot 97B The owner has requested we proceed forward to obtain a septic permit to upgrade the failed leachfield on the subject lot. The general slope of this lot is fiat. On October 14, 2010 a testhole was performed to investigate soils and groundwater. The results of this test are attached for your review. The proposed upgrade will serve the existing 4-bedroom house. We propose to install a 1250- gallon septic tank with two 5'-wide shallow trenches. The existing septic tank will be decommissioned per the UPC. Groundwater was not encountered during excavation, but was measured at 13' during monitoring. The property and adjacent lots are served by private water wells. There is no surface water within 100' of the proposed system and there are no known curtain drains within 50'. We do not expect there to be any adverse effect on adjacent lots by the development of this system. If you have any questions, please contact me at 868-3792/FAX 868-3793. Respectfully submitted, ArcTerra Consulting, Inc. Attachments: On-Site Sewer Application Wastewater Absorption System Details/Site Plan Soils Log/Percolation Test Owner/Contractor Specs 20441 PTARMIGAN BLVD · EAGLE RIVER, AK 99577-8736 ° PH (907) 868-3791 · FAX (907) 868-3793 ~ELL FLAG PR[]PERTY LINES PRIDR TD CBNSTRUCTI~ ZJl 0,''1'''' .4 ~e-~.. K F~G / / S~ =100' D N DETAILS PAGE 1 ~ P /4 BDRM X 150 GPD= 600 GPD/ / / tGO0 GPa/ 0.SGPD PER SO. FT. (~ MIN/IN/)= 750 SQ. FI/ ! \ ~(750 SF / 5' W =' 150 FT X RFXO~SB (~' RACK) = 8~ TRENCH\ ¥SE 2 TRENCHES - 4,q~' (L) X 5' (NV) X ~J]) l~tat depth oF s~tem is ~,5' Fr'om origin~ g~ Z ] NO PUDLIC WELLS WITHIN E~O0' DF ToXCal. depth oF paver beL~)w disi;ribui;ion pipe is ~' , "5 PRIV*TE VELLS WITHIN L:~OO' DF N I~ ~~ pRnPaSED SYSTEM EXCEPT ^S NOTED. 1, INSTALL~L..~AL SEPTIC T.ANK & INSULATE TANK IF~CnVER, NO SEPTIC SYSTEMS WITHIN 20~ DF PRI]PI]SED WELL EXCEPT AS NOTED. 2. INSULATE TREN~ BURIAL '~3' DF FILL. MIN. P' FILL WITH INSULATIDN, )3' CDVER ND INSUL REQ. 3. CDNTRACTDR WILL ENSURE MINIMUM 2× SLDPE INTD SEPTIC TANK, 4. CDNTRACTDR WILL ENSURE ALL SEPARATIDNS TD ADJACENT WELLS, SEPTICS EASEMENTS, PRDPERTY LINES, ETC... PREPARED FOR: RDBERT ~& 3ARBARA HDFFMAN P{] 3DX 770309 EaDLe Rivet-, AK 99577 907-G88-30GG BEll) BOOKS 7116 ' m£cK~. KMD SYAK~ STAKING' ~PO~sstO~D~ ~ JLS WELL 8~ WASTEWATEiR iBISPBSAL SYSTEM DETAILS/SITE PLAN BU~G LET 97B FLAG PROPERTY LINES WELL RADII & EASEMENTS PRIOR TB CBNSTRUCTInN NB PUBLIC WELLS WITHIN 800' DF PROPOSED SYSTEM. ND PRIVATE WELLS WITHIN aO0' DF PROPOSED SYSTEM EXCEPT AS NOTED. ND SEPTIC SYSTEMS WITHIN aO0' DF PROPOSED WELL EXCEPT AS NOTED, Sc(l[e: DESIGN DETAILS PAGE 1 4 BDRM X 150 GPO = 600 GPO 600 GPO/ 0,SGPD PER SQ. FT. (8 MIN/IN.)= 750 SQ. FT (750 SF / 5' W = 150 FT X RF 0,58 (3' ROCK) = 87' TRENCH USE 8 TRENCHES - 44' (L) X 5' (W) X 3' (D) Total depth oF system is 8,5' From original grade, Total depth o~ gravel below distribution pipe is 3' . NDTES: 1. 8. 1'= 100' OF 2 INSTALL 1850 GAL SEPTIC TANK & INSULATE TANK IF <4' COVER. INSULATE TRENCHES WITH 8' HD BURIAL FOAM IF < 3' OF FILL. MIN. 8' FILL WITH INSULATION, >3' COVER NO INSUL REQ. CONTRACTOR WILL ENSURE MINIMUM 8% SLOPE INTO SEPTIC TANK. CONTRACTOR WILL ENSURE ALL SEPARATIONS TD ADJACENT WELLS, SEPTICS EASEMENTS, PROPERTY LINES, ETC.., PREPARED FOR: ROBERT & BARBARA HOFFMAN PO BOX 770309 EcgLe River, AK 99577 907-688-3066 FIELD BOOKS co~pul~: "OONDARY:. BOUNDARy ~i,m STAKING m'~,~: BMW C,ECKEm KMD A..~ILT: JLS DATZ: 10/21/10 Dwc,. RLE: GRID: NWl 155 Ac,m nu~ FILE ~oe No.: 10--179 WASTEWATER DISPBSAL SYSTEM DETAILS :BURG LFIT 97:B 89~7'~1" ~/ ¥ ~ ¥ ~68.~0' FLAT ~1 O~ ~ FLAT / l~ ~ INSTALL ~ ~~ I PER UPC. ~ INSTALL NEW 50.7' FLAG PROPERTY LINES WELL RAI)II & EASEMENTS PRIOR TB CONSTRUCTION Scale: 1"= 30' PAGE 2 DF 2 PREPARED FOR, ROBERT & BARBARA HOFFMAN PB BBX 770309 E6oLe River, AK 99577 907-688-3066 FIELD BOOKS COUPUTEm OR^W: BMW BOLIND.~. BOUNDARY ST~N~ STAKING ~EC~: KMD ~-~LT: JLS D^~ 10/21/10 DW¢,. nLF_: ~D: NWl 155 FILE No.: 10--179 99577 Performed for: CONSULTING, INC 20441 Ptarmigan Blvd., Eagle River AK. 99577 Office (907) 696-6111, Fax (907) 868-3793 SOILS PERCOLATION TEST Robert Hoffman Date Performed: 10/14/2010 Project: Depth Burg Lot 97B ORG/OL TEST HOLE # TH 10-1 SEE ATTACHED SITE PLAN FOR HOLE LOCATION 3- 4- 5- 7- 8- 9- 10- 11- 12- 13- 14- 15- 17- 18- SM/GM B.O.H. Was Ground water encountered? NO Depth to water after monitoring? 13' What depth? NA Date? 10/21/10 Reading Date Gross Net Depth to Net Time Time Water Drop 1 10/15/10 1:00 - 6" 2 1:30 30 min 2 2/16" 3 14/16" 3 * 1:31 - 6" 4 2:01 30 min 2 3/16" 3 13/16" 5 * 2:02 - 6" 6 2:32 30 min 2 3/16" 3 13/16" 7 8 9 10 11 12 · Water Added 19- 20- HOLE PRESOAKED PRIOR TO TESTING Percolation Rate 7.87 Test Run Between (min/in) Perc Hole Diameter 6" feet and 4 feet I, Kenneth M. Duffus, certify that this test was performed in accordance with all State and Municipal guidelines in effect on this date. CONSULTING, INC 212 E. 51st Ave, Anchorage, AK. 99503 Office (907) 868-3791, Fax (907) 868-3793 ON-SITE WASTEWATER DISPOSAL SYSTEM CONSTRUCTION PRACTICES AND MATERIAL SPECIFICATIONS LEGAL DESCRIPTION: BURG LOT 97B GENERAL: 1. The scope of this project includes the installation of a septic tank and/or drainfield to serve a single-family residence on the referenced property as delineated on the attached Municipality of Anchorage (MOA) permit and site plan. Construction shall be in accordance with the approved site plan and design drawings; MOA permit with any special provisions or conditions, and all applicable State and Mtmicipal Wastewater Disposal Regulations. 2. ArcTerra Engineering & Surveying, Inc. (ArcTerra) assumes no responsibility of the accuracy of the as-built survey provided by the owner or owner's representative. 3. The owner or contractor is responsible to notify the engineer of any discrepancies noted on the design plans or drawings prior to commencing work. These discrepancies could be, but not limited to, possible encroachments, surface water, varying soils, unplatted easements, types or use of dwellings on or adjacent to property, nearby public wells, etc. 4. The contractor shall be responsible for locating any necessary underground utilities, easements, property lines and surface water. The owner and/or contractor shall ensure, if deemed appropriate, that a registered land surveyor prior to construction flags all setbacks. The contractor shall be responsible for verifying all pertinent separation distances and component layout. 5. Unless specifically agreed otherwise, the property owner shall be responsible for final grading areas subsequently depressed from soil settling. On all leachfield mound systems, the property owner shall be responsible for ensuring a satisfactory vegetation growth over the mounded area. 6. The MOA Development Services Department On-Site Water & Wastewater Program must certify contractors installing wastewater disposal systems. Owners installing their own systems must also receive prior approval from said MOA Department. SEPTIC TANK/HOLDING TANK/LIFT STATION INSTALLATION: 1. A septic tank is to be constructed by a certified septic tank manufacturer. Construction shall include two 4" cleanouts for pumping access. 2. The septic tank shall be sufficiently bedded with proper material and compacting to prevent damaging, settling or shifting of the tank. 3. All standpipes on the septic tank shall extend a minimum of 12 inches above the final grade. BURG LOT 97B October 21, 2010 Page 2 of 4 4. Septic tanks installed with less than 4 foot of cover shall be insulated. The contractor will ensure that the fill over the tank does not exceed the burial depth rating. 5. A foundation cleanout shall be installed one to four feet from the building foundation. In the line between the tank and the leachfield there shall be two adjacent cleanouts (unless an effluent pumping system exists within the septic tank). These cleanouts shall be located on undisturbed soil not more than 10 feet from the tank. The second cleanout, in line, shall be to clean toward the septic tank. 6. Final grading over the septic tank shall be such that a positive slope exists away from the septic tank. 7. All H.D.P.E. tanks shall have a vertical length of 4-inch perforated drainpipe besides the tank extending to the bottom of the tank to above grade to monitor ground water. 8. All tanks shall be anchored when there is not enough adequate soil cover to resist buoyancy forces in high-groundwater areas. 9. All holding tanks and lift stations shall have an audible and visual alarm inside the residence. 10. All lift stations shall be wired in compliance with the Uniform Electrical Code and all MOA guidelines. 11. The contractor shall remove the old tank, or abandon it in compliance with the Uniform Plumbing Code. The contractor is solely responsible for the abandonment procedure. ABSORPTION TRENCH/DRAINFIELD INSTALLATION: 1. Excavate the proposed trench to the dimensions shown on the design. The bottom of the excavation shall be within 2 inches of level. If the sidewalls of the excavaction become smeared, they must be raked or scratched (roughed-up) before gravel (sewer rock) placement. 2. Once the sewer rock is installed, the distribution pipe is installed level with the perforations facing downward. Gravel is then to be placed over the distribution pipe to provide a minimum of 2 inches of cover over the pipe. 3. A silt barrier must be installed between the final gravel layer and the native soil backfill. Ensure the silt barrier covers the entire gravel surface before placing backfill. 4. Monitoring tubes shall be four- (4) inch diameter, installed approximately in the locations shown on the design, and extend a minimum of 12 inches above final grade. The portion of the monitoring tube extending through the gravel shall be perforated from the bottom of the trench to the invert of the distribution pipe. This is equivalent to the effective depth of the gravel as noted on the design. 5. Backfill over the final gravel layer must not be less than twenty-four inches. Insulation must be installed when the backfill depth is less than thirty-six (36) inches. The finish grade over the trench must be mounded to prevent the formation of a depression after settling. 6. All advanced technology waste water disposal systems (Advantex, Biocycle, Intermittent Dosing Sand Filter, etc...) shall be constructed, installed, maintained and monitored per manufacturer's specifications and MOA requirements. 20441 PTARMIGAN BLVD · EAGLE RIVER, AK 99577-8736 · PH (907) 868-3791 · FAX (907) 868-3793 BURG LOT 97B October 21, 2010 Page 3 of 4 MINIMUM MATERIAL SPECIFICATIONS: 1. A MOA approved septic tank manufacturer must construct any septic tank proposed for installation. 2. The following pipe materials are MOA approved for use in septic system installations: Type of Pipe Perforated Solid Cast Iron Yes Yes ASTM D3034 (PVC) Yes Yes ASTM F810 (HDPE) Yes No ASTM D2662 (ABS) Yes Yes 3. Insulation shall be at least 2' thick extruded direct burial polystyrene (Dow Chemical Company Styrofoam HI or equal). 4. Septic tank inlets and outlets shall be fitted with watertight couplings (Caulder, Fernco, or equal). 5. A permeable nontoxic silt barrier (Typar 3401, Mirafi 140N, or equal) must be installed between the final leachfield gravel layer and the native soil backfill. 6. All leachfield gravel (sewer rock) shall be 0.5'-2.5' screened gravel with less than 3 % passing the #200 sieve. If deemed necessary, a sieve analysis should be performed. 7. When sand is being used as a filter material its gradation specification must conform to current MOA or ADEC requirements. INSPECTIONS: Typically there will be three (3) inspections required during the installation of the wastewater disposal system. These inspections will occur as follows: 1. The first inspection must be conducted after the excavation of ditches, pits, trenches, or beds and before the installation of any gravel. A septic tank may be set in place, but may not be backfilled before this inspection. 2. The second inspection must be conducted after the placement of the sewer rock, distribution lines, standpipes, and cleanouts, but before the placement of the silt barrier, insulation, or any other backfill. 3.The final inspection is to occur upon final grading of the property. Often there will be more than these 3 inspections required, especially with the installation of multiple trenches, sand filters, pressurized distribution systems, etc. The inspecting engineer is to be contacted at least 24 hours prior to the start of construction. If necessary, a pre-construction meeting will take place on-site. The inspecting engineer will not coordinate, direct or control in any way the contractor's activities. The owner shall contract with the contractor to perform the work outlined in these specifications and attached plans and in accordance with the attached MOA permit. All materials, components, and construction practices shah comply with the MOA's and the State of Alaska's latest ordinances, regulations, or policies regarding wells and septic systems. The failure of the inspecting engineer to notice a material or construction non- compliance does not relieve the contractor of his/her responsibility to correct such deficiency. There will be no contractual arrangement existing between the contractor 20441 PTARMIGAN BLVD · EAGLE RIVER, AK 99577-8736 · PH (907) 868-3791 · FAX (907) 868-3793 BURG LOT 97B October 21, 2010 Page 4 of 4 and ArcTerra. ArcTerra shall be the owner's representative and will inspect the work as stated above to document the contractor's activities. Final acceptance of the contractor's work rests with the owner and the MOA. ArcTerra shall have no liability to the owner or to others for acts or omissions of the contractor or any other persons performing work on this project or the failure of the contractor to carry out the work in accordance with these construction documents. ArcTerra's inspecting engineer will not be responsible for the construction means, methods, and techniques, sequence, procedures or the safety precautions incident to this project. BY PROCEEDING FORWARD WITH THE INSTALLATION OF THE WATER AND/OR WASTEWATER SYSTEM (S), THE PROPERTY OWNER, CONTRACTOR, AND WELL DRILLER ACKNOWLEDGE HAVING READ AND ACCEPTED THESE SPECIFICATIONS. 20441 PTARMIGAN BLVD · EAGLE RIVER, AK 99577-8736 · PH (907) 868-3791 ° FAX (907) 868-3793 o~ MUNICIPALITY OF ANCHORAGE O~EC ,o DEPART~ ~NT OF HEALTH & ENVIRONMENTAL PR TION ENVIRONMENTAL ENGINEERING DIVISION 825 L Street- Anchorage, Alaska 99501 Telephone 264-4720 ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT NAME IPHONE MAILING ADDRESS LEGAL DESCRIPTION LOCATION/~ '~ ~ /~Dwelling F~" PERMITNO' OF BEDROOMS ~NO, DISTANCE TO: ~ ,,-, ~ Z Manufacturer Material No. of compartments Liq. capacity~allons Inside leneth ~ Width Liquid dept~ ~ ~ Material Liquid capacity in gallons ~-' DISTANCE TO: Well ~/~ Foundation ~ ~ ~/ Nearestlotlin~+ ~.~/ PERMITNO. ~ Top of tile to finish ~rade Material beneath tile ~ Total effective absomt~ area Length 'Width Depth PERMIT NO, ~ ~ Type of crib Crib diameter /~ Crib depth Total effective absorption area ~ Well Building foundation Nearest lot line ~ DISTANCE TO: ~ ~' L Distance to lot line PERMIT NO. ~ DISTANCE TO: Building foundation Sewer line Septic tank Absorption area(s) PIPE MATERIALS OTHER SOl L TEST RATING INSTALLER REMARKS 3 (Rev. WATER WELL RECORD STATE OF ALASKA DEPARTMENT OF NATURAL RESOURES Division of Geological ~ Geophysical Surveys Drilling Permit No. LOCATION OF WELL (Please complete either ID, lb or lc.) A.D.L. No. I'~. I Borough Subdivision Lot Block I-'~.I I/4 qt rs. Section No. Township N r-1 Range Er-1 Meridian _of_o,_of_ lc. DISTANCE AND DIRECT ON 2. WELL LO~ Feet Below Surfece 4. WEL~ DEPTH: {finel) 5. DATE OF CO~PLETI~ Material Type Top Bottom /~0 ft. 8. CASING: ~ T~eeded ~'Welded diom. in. lo__ft. Depth Sticku~ft. 9. FINISH OF WELL: Ty~e: Dlemetet: ? Slot/Mesh Size: Length: Set between ft. end ft. Backfilling ~revel peck IO. STATIC WATER LEVEL: ~ Above or ~ Below Iond surfoce Dole Equipment used: -. MUNICIPAL/~ II. PUMPING LEVEL below land surface and YIELD DEP[ ~ ANC~o ~~ ft. after hrs. pumping g.p.m. ENvIg~.~,,;..O~ ~,. ~ ~ -'wvl~/~RL' P~OTE~r~"'~ ~ ~. ~ft' after ~hrs' pumping~g.p.m. -"~1~ 12.GROUTING Well Grouted: SEP ~ ,~ ~ ~ Material: ~Nea, Cement 0 Other: Length ~ Drop Pipe capacity g.p.m. . ~ s,~-7~~ ~ C,n,r.,,.~ ~ O,he. 14, REMARKS: 16, WATER WE~L CONTRACTOR'S CERTIFICATION: 15. Woter Temperature ~.o ~ F ~ C This~l ~es dr~led under ~y jurisdictipn end this report is true to the best of my knowledge ~nd belief; Registered Busine~eme . Controct License Number /' Authorized Representative ~ Form OZ-WWR (11/81) Copy Distribution: WHITE-State DGGS~ PINK-Driller, CANARY-Customer MUNICIPALITY OF ANCHORAGE Departmen~f Health and Environment~ 825~ Street, Anchorage, AK. 264-4720 f ~ * * * HANDWRITTEN PERMIT * * * Permit ~. ~ ~.~ WELL AND/OR ON-SITE SEWER PERMIT Appli~: C~*& C~¢' Mailing Address: Loc at '~n/~¢ --~/~--~ ~ / ~ / ~ Phone Number: Legal Description: Type of Soil Absorption System Is: Trench: Drainfield: ~ Maximum Number of Bedrooms: ~ iProtection ~ ' ~ ' Lot Size: Seepage Bed: Holding Tank: Soil Rating(sq.ft/br) The; Required Size of the Soil Absorption System Is: DEPTH S LENGTH _ GRAVEL DEPTH / The length dimension is the length(in feet) of the trench or drainfield. The depth of a trench or pit is the distance between the surface of the ground and the bottom of the excavation(in feet). There is no set width for trenches. The gravel depth is the minimum depth of gravel between the outfall pipe and the bottom of the excavation(in feet). * * REQUIRED SEPTIC(J~ TANK .SIZE = ~5~ GALLONS * * Permit applicant has the responsibility to inform this department during the installation inspections of any wells adjacent to this property and the number of residences that the well will serve. * * * TWO(2) INSPECTIONS ARE REQUIRED * * * Backfilling of any system without final inspection and approval by this department will be subject to prosecution. Minimum distance.between a well and any on-site sewage disposal system is 100 feet for a private well or 150 to 200 feet from a public well depending upon the type of public well. Minimum distance from a private well to a private sewer line is 25 feet and to a community sewer line is 75 feet. Well logs are required and must be returned to this department within 30 days of the well completion. Other requirements may apply. Specifications and construction diagrams are available to insure proper installation. * * * PERMIT EXPIRES DECEMBER 1 9 8 3 * * * Z certify that: (1) I am familiar with the requirements for on-site sewers and wells as set forth by the Municipality of Anchorage. (2) I will install the system in accordance with codes. (3) I understand that the on-site the residence1 is remodeled to Signe~: ~L ~ ~.L))/.~..~i~]) Applicant SWP/024(1/81) sewer system may re,~uire enlargement if include more t.~~~ed~ Issued by: t - Date: -- -- ~ · ~'inl ciI vv/7~/- l'J ORAGED~II[TUNI /A~T~i~A~cH 825 L. Street, Anchorage, Alaska 99501 264-4720 SOILS LOG - PERCOLATION TEST [] SOILS LOG PERCOLATION TEST DATE PERFORMED.~ ~ "'~ ~) / z,c.,) 4 7 8 9 10-- 11 SLOPE SITE PLAN 12 13 14 15 16 ENCOUNTERED? SL O P IF YES, AT WHAT /O / E DEPTH? Reading Date Gross Net Depth to Net Time Time Water Drop 20 PERCOLATION RATE (minutes/inch) 72-OO8 (6/79) , ~ ~II~MUNICIPALITY Of ANCHORAG~ -~ 4' Departmen~ Health and Environment~rotection ~ .~ 825~ Street, Anchorage, AK. ~950]~,~~ _ ~ _~. ~p¢ 264-4720 - * * * HANDWRITTEN PERMIT * * * Permit~ WELL~,1~, ~~'~'%/aRUl\uit ....Q~IT£ ~=,,-~°~'":~ PERMIT Applicant: ~ ~ Mailing Address: Location: Phone Number: Legal Description: ~'~/~_~,~{~.j ._..~/~~"'~--',~ Lot Size: Type of Soil Absorption System Is: Trench: Drainfield: Seepage ~ed/ _ Holding Tank: Maximum NtLmber of Bedrooms: .__~_ y ~~ting(sq.ft/br) The Required Size~'o~/the~'Sc~il/Absorption System DEPTH LENGTH GRAVEL DEPTH Is: WIDTH The length dimension is the length(in feet) of the trench or drainfield. The depth of a trench or pit is the distance between the surface of the ground and the bottom of the excavation(in feet). There is no set width for trenches. The gravel depth is the minimum depth of gravel between the outfall pipe and the bottom of the excavation(in feet). * * REQUIRED SEPTIC(HOLDING) TANK SIZE = GALLONS * * Permit applicant has the responsibility to inform this department during the installation inspections of any wells adjacent to this property and the number of residences that the well will serve. * * * TWO(2) INSPECTIONS ARE REQUIRED * * * Backfilling of any system without final inspection and approval by this department will be subject to prosecution. Minimum distance between a well and any on-site sewage disposal system is 100 feet for a private well or 150 to 200 feet from a public well depending upon the type of public well. Minimum distance from a private well to a private sewer line is 25 feet and to a com~nunity sewer line is 75 feet. Well logs are required and must be returned to this department within 30 days of the well completion. Other requirements may apply. Specifications and construction diagrams are available to insure proper installation. * * * PERMIT EXPIRES DECEMBER 31, 1 9 8 3 * * * I certify that: (1) I am familiar with the requirements for on-site sewers and wells as set forth by the Municipality of Anchorage. (2) I will install the system in accordance with codes. (3) I understand that the on-site sewer system may r~quire enlargemen~ if the ~residence is remodeled to include more~ ~ooms Applicant ' C'" ~_- '~' "~ Date: ~/~/~ SWP/024 (1/81) APPLI NT FILLS OUT UPPER HA .T ONLY Property (~wner ~'~> ~'" ':L (.:_' ', ' i ' ~ ,r~ ~.. ~ 4. ~ ._,. , ,~_~. ,,, Phone :'"~ ' Zip Code '/"'/ Mailing:Address ~ ~ ~' ':~. ~'". , ...... ". ~ ,': .... '/"','.;: /'""/.? /'~L ;" Buyer . ' , /.,/ /.'.':'~ ,/~'%.' .~',L. '"' ' ' -' ' Address .. ."~ . - -.~ ~ ..- '~ .--::(".~,,'-/ 1:- /,,./- ,- .:- /.-': I ) .... Zip Code './~ ''~ ' -~ Phone '" ""' ' :'" -- . '. '-' . ,- : . ~ , . ,--, .~ ,,~: ,'--.: ./' /,2,::- , "/:-//.,'// / .' Address Zip Code Realty Co."& Agent ,~, ,/.;,' ? ,:" Phone Address Zip Code Legal Description '<;;,"' ",~:' '¥': ...... "' '-" '' '-:'-' '.,~::. ~_-~'C~ /~6 ~/~/ Street Location ,>';,'/' .,.:~_/:-/..':/'/ :/' . . '., ,.. ...... Type o~ Residence L~/Single Family No. of Bedrooms ";1 [] Multiple Family [] Other Water Supply [~'l~di~vidual ~ ~ ATTACH WELL LOG. A wetl log is required for all wells drilled since June 1975. [] C~mmunity/ For wells drilled prior to that date, give well depth (attach log if available). [] Public Utility' Sewer Disposal E~.r~lividual Year Individual Installed: .... ~ F~ Pu'blic Utility When Connected to Public Utility: [] "Holding Tank NOTE: THE INSPECTION FEE MUST ACCOMPANY EACH REQUEST BEFORE PROCESSING CAN BE INITIATED. Time Time ' - "- ''~ '~ ~' Time ~ /' Date Date D . Insp~tor Insp~tor Insp~tor~~~ . Insp~t~ _.:~ ~" ~ ~~ ~.~, , "Municipa!itY,,D~t. of OrCHid:th ........ ( ~ APPROVED BEDROOMS . 'CONDiTiONS OF ~entaJ ( ) D~SAPPROVED ( ) CONDITIONAL APPROVAL* DATE ~ BY: ~ Soils Rating Date ~wer Installed Well To Absorption Area Well Log Received Well to Tank Septic T~k Size 72-023 (3/82) Municipality of Anchorage Development Services Department Building SafetyDivision On-Site Water and Wastewater Program 4700 Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 www. munt.org/onSite (907) 343-7904 CERTIFICATE OF ON-SITE SYSTEMS APPROVAL FOR ASINGLE FAMILY DWELLING Pamel I.D. 051_.-1_72-55 GENERAL INFORMATION Complete legal description BURG LOT 97B Location (site address) . 19930 ADRIAN AVE, CI-]UGIAK,...AK.99567 COSA# Expiration Date: Current Property owner(s) ROBERT &.BARBARA HOGAN Mailing address Lending agency Mailing address Day phone PO l~3X 77030~..EAGLE ~R, AK 99567 .. . Day phone m e Real Estate Agent Mailing Address Unless otherwise requested, COSA will be held by DSD for pickup. NUMBER OF BEDROOMS: TYPE OF WATER SUPPLY: Individual Well Individual water Storage Community Class Public Water System .4 Day phone Well D D D TYPE OF WASTEWATER DISPOSAL: Individual On-site I~ Individual Holding Tank I-'] Community On-site r'-I Public SeWer E] The Municipality of Anchorage Development Services Department (DSD) issues Certificates of On-Site Systems Approval (COSA)based only upon the representations given in paragraph 4 by an independent professional civil engineer registered in the State of Alaska. Certificates of On-Site Systems Approval are required for the transfer of title (except between spouses) for properties served by a single-family on-site wastewater disposal and/or water supply system. DSD also issues COSAs upon request to homeowners. Certificates of On-Site Systems Approval are valid for 90 days from the date of issue for properties sewed by a private or Class C well and may be reissued with new water sample results. (Certificates may be reissued for a period of up to one year with valid water samples.) Certificates are valid for one year for properties sewed by Class A or B wells or a public water system. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 4. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On-Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein, I further verify that based on the information obtained from the Municipality of Anchorage files 'and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation, Name of Firm ARCTERRA CONSULTING, INC. Phone 868-3792 Address 20~1 ]~rARMIGAN BLVD., EAGLE RiWv'ER, AK 99577 Engineer's Printed Name KENNETIt M. DUFFUS Date 09112/2011 Engineer's Comments: This investigation was completed in compliance with ADEC and MOA regulations. The assessment of the condition of the well and septic applies only to the conditions as of the day tested. The flow and absorption rates may change due to subsurface conditions that may not be observed from the surface, changes inland use, local soil characteristics, groundwater levels that may fluctuate during the year and the water usage of the family being served by the system. The operational life of all wetl and septic systems are subject to these various and dynamic characteristics and are outside the control of the evaluator of the well and septic system. Therefore, AmTerra can not give any estimate of how long a system will function satisfactory for current or future occupants or can ArcTerra guarantee that no unseen encroachments, deficiencies or discrepancies exist. DSD SIGNATURE ~ Approved for . Z7L Disapproved. Conditional approval for bedrooms. Attachments: COSA Checklist Septic System Advisory Well Flow Advisory Nitrate Advisory X bedrooms, with the following stipulations: E~: WA'fEE AND Arsenic Adviso~ Maintenance Agreements Supplemental Engineers Repo~ Other Original Certificate Date: Municipality of Anchorage Development Services Department Building Safety Division On-Site Water & Wastewater Program 4700 Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 www. munLorg/onsite (907) 343-7904 CERTIFICATE OF ON-SITE SYSTEMS APPROVAL CHECKLIST Legal Description: BURG LOT 97~ A. WELL DATA Pamel ID:.,051_-1_72-55 Date of test Static water level Well production 3-5 WATER SAMPLE RESULTS: Coliform ..bLF,,_G__colonles/100m L Well type ~ If A, B, or C provide PWSID # ,, Date completed ~ Sanitary seal (Y/N) Total depth 350. ft. Cased to 82 FROM WELL LOG 42 ~ g.p.m. Well LOg (Y/N) Y Wires properly protected (Y/N) y Casing height (above ground) __lg..Lin. AT INSPECTION _ 8/30111 31 ff. .., 2.2$ g.p.m. Depression over field N Results (Pass/Fail). For...._ bedrooms Water added, gal, New depth_ _in. g.p.d. Nitrate _ND mg/L Arsenic: 13.1 mgd Date of sample:,~a.~LCollected B. SEPTICJHOLDING TANK DATA Tank Type/Material Se?k/Steel Date installed ~ Tank size ~ gal. Number of Compartments 2 Cleanouts (Y/N) y Foundation cleanout (Y/N) y Depression over tank (Y/N) .bi High wateralarm (Y/N) N Date*of pumping NA-NEWTANK Pumper C. ABSORPTION FIELD DATA · Date installed ~19JZIZIL Soil rating (g.p.d./ft~ or ~/bdrm) 0.8 System type_SHALLOW TRENCH Length 134 ft. Width ~ ff. Gravel below pipe 1.1 ft, Total depth 6 ff. Elf. absorption area Z.O/..ff2 Monitoring tube_Y Date of adequacy test NA-NEW FIELD Fluid depth in absorption field before test __ In. Elapsed Time: min. Final fluid depth in. Absorption rate >= Any rejuvenation treatment (past 12 mo.) (Y/N & type) bT. If yes, give date.- UFT STATION Date installed 'Pump on' level at __in. Datum, Size in gallons 'Pump off' level at __in. Cycles tested E. SEPARATION DISTANCES SEPARATION DISTANCES FROM WELL ON LOT TO: Septic tank/lift station on lot. Absorption field on lot, 100'+ ., Public sewer main,,,?5'+ , Sewer/septic service line 25'+ Animal containment areas 50% Manhole/Access (Y/N) High water alarm level at in. Meets alarm & circuit requirements? On adjacent lots lO0'+ On adjacent lots lO0'+ Public sewer manhole/cleanout 100% Holding tank ,,,,10o'+, Manure/animal excrete storage areas lOO% SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Building foundation $'+ Propertyline 5% Water main to'+ , Water service line 10% , Wells on adjacent lots 't00'+ SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Property line 10'+ Building foundatiqn 10'+ Water Service line lO'+ Surface water 100'+ Curtain drain Sly+ (None Kno~m) COMMENTS Absorption field S'+ Surface water, ,,lO0'+ Water main lO% Driveway, parking/vehicle storage ,, 10'+ Wells on adjacent lots 100'+ G. ENGINEER'S CERTIFICATION I certify that I have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. · Engineer's Pdnted Name KENNETH M, D~$ Date 9/12/2011 COSA Fee $250.00 Date of Payment Receipt Number (Rev, 11/05) Waiver Fee $ Date of Payment Receipt Number Municipality of Anchorage Community Development Department Development Services Division On-Site Water and Wastewater Program 4700 Elmore Street P.O. Box 196650 Anchorage, AK 99519-6650 www.muni.org/onsite (907) 343-7904 Arsenic Advisory Certificate of On-Site Systems Approval # 111344 A Certificate of On-Site Systems Approval inspection and test of potable water was recently conducted on the well water supply on Block , Lot 97B of Burg Subdivision. This inspection revealed an arsenic concentration of 11.1 micrograms per liter (ug/L) for the property's well water sample. The Environmental Protection Agency (EPA) has established a maximum contaminant level (MCL) of 10.0 ug/L for public drinking water systems. While private wells are not subject to this regulation, EPA standards are based on existing health information and can therefore be used to gauge the relative quality of water from private wells. Information on arsenic is available from the On-Site Water and Wastewater Program website (www.muni.org/onsite) or at 343-7904. This advisory must be attached to all copies of the subject Certificate of On- Site Systems Approval. SGS Reft# 1114163001 Client Name ArcTerra Engineering and Surveying Printed Date/Time 09/08/2011 9:48 Project Name/# Burg Lot 97B Collected Date/Time 08/30/2011 13:30 Client Sample 1D Burg Lot 97B Received Date/Time 08/30/2011 14:10 Matrix Drinking Water Technical Director Stephen C. Ede Sample Remarks: Allowable Prep Analysis Parameter Results LOQ Units Method Container ID Limits Date Date Init Metals by ICP/MS Arsenic 11.1 * 5.00 ug/L EP200.8 C (<10) 09/02/11 09/06/11 NRB Waters Department Total Nitrate/Nitrite~N ND 0.100 mg/L SM20 4500NO3-F B (<10) 09/02/11 AYC Microbiology Laboratory E. Coli Negative 1 100mL SM20 9223B A 08/30/11 DLC Total Coliform Negative 1 100mL SM20 9223B A 08/30/11 DLC 97B "' '.' ', v ¥ N.,,89~57'~1" ~W x :,( x 1,,68.,9,0' x ,,~ ........ .. ,. '.4 X X 'X · · · VENTS '1. ('r'~) '~ ,,<, LOT 97B ' .' / I // I. EXlSTiNC .... .i .0 C^NI O/H WELL O/H 15' T&E EASEMENT-- LINE EASEMENT LOT --O/H O/H 5' REMA S89°57'52"E 168.90' LLI ADRIAN AVENUE ANCHORAGE RECORDING DISTRICT ASBUILT OF: BURG SUBDIVISION LOT 97B PLAT 82-466 SURVEY CERTIFICATION: I, John L. Schuller, have conducted a physical survey of this property as shown on this drawing and that the improvements situated thereon are within the property lines and no enchroachments exist other that noted. EXCLUSION NOTES: It is the owners responsibility to determine the existence of any easements, covenants, or restrictions which do not appear on the recorded subdivision plat. Under no circumstance should any information on this drawing be used for construction of fences, structures, improvements, or for establishing boundary lines. WORK ORDER NUMBER: 1 1 -- 025 IDATE: I SCALE: JUNE 15, 2011 I 1"=30' ICHECKED BY~ GRID NUMBER: IDRAWN BY: IE-MAIL: BOOK/PAGE: 110125 I e= FND BRASS CAP MONUMENT ~) = FND 5/8" REBAR 1831 Talkeetna Street Anchorage, Alaska 99508 (907) 227-1455 office (907) 274-4992 fax