HomeMy WebLinkAboutDALE BRIGGS BLK 1 LT 6 N100'Dale Briggs Block 1 Lot 6 NIOO' #050-181-01 Municipality of Anchorage On -Site Water and Wastewater Program • (907) 343-7904 Page 1 of 3 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP161070 PID Number: 050-181-01 Dwelling: ❑ Single Family (SF) ❑■ Duplex (D) ❑ Multiple (SF and/or D) Project: ❑C New ❑ Upgrade Name: Gar & Katherine Henning ABSORPTION FIELD ❑ Deep Trench A Shallow Trench ❑ Bed ❑ Mound Address P.O. Box 770597 Eagle River, AK 99557 ❑ Other Phone Number of Bedrooms Soil Rating Total depth from original grade Six (6) 1.2 GPD/SF 6.8-7 Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade 2.8-3 Ft. Gravel depth beneath pipe 4.0 Ft. Subdivision Block Lot Dale Briggs 1 6 N100' Fill added above original grade 1.5-2 Ft. Gravel length 80 Ft. Township Range Section Gravel width 5 Ft. Beds: Number of Lines Distance between lines Ft. SEPARATION DISTANCES To Septic Absorption Lift Station Holding Sewer Total absorption area Number of trenches Dist. between trenches From Tank Field Tank Line 800 Fe 2 >10 Ft. Well NA NA NA NA >25' TANK ❑p Septic ❑ S.T.E.P. ❑ Holding ❑ Other Manufacturer Anchorage Tank Capacity 1 2,000 Gal. surface water >100' >100' NA NA Material Steel Number of compartments 2 Lot Line >5' 10' NA NA NA Foundation >5' >10' NA NA LIFT STATION Manufacturer Capacity Gal. Curtain Drain No ne Noted Pump on level at Pump off level at High water alarm at Remarks in. in. in. Pump make and model Electrical Inspections performed by PIPE MATERIAL House to tank D3034 Tank to drainfield D3034 Installer Royce Martin Drainfield D3034 CO/MT D3034 Inspector MEA BENCH MARK (Assumed elevation) 100.0 ft Inspection 15' 11/20/16 nd 11/20/16 Location and description dates: 2 t Front Deck NE Corner 3rd 4 COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL ��i�' :tOF Conditional Approval: Date „W61).•°�• '•rte 00 v 49 TH O e..... .......111���ttt. ..:.io 00 �MICHAEL E. ANDERSON : 0 �0 J •. CE - 4381 .' �`�.AVr Ap Date '� �- `,������ ♦���� Inspection Report_9-1-12.doc 0 0 < 0 00 m na G 0 G (n 0 0 0 0 C/) (D 0 _0 0-0, (D Cl: --i fines 0 C (D < 9-0 < (D 1� I WE I I 0 -a CD n 3 Z c 3 cr CD .i W, LVOR At 3 0 CD 0 ;u m 0 < 0 -CD M 0 > m - 0 z a cn SD M ?�> < 0 Vim= = 0 > (D (n 0 =7 0 tome 0) > CD M -!-4 (.0 C) 4p MI 7403�1 KANTISHNA DRIVE --------------- N 00*03'00"E 100.00' -n o n cn u) CO < --4 0) N cn P. - ---- — --- 0-) tV P I- w -r? co 00 1\) 0 --4 O> 4 C)1,;- --4 p1 Cn W N) 03 . X1 m 0 (n I 0 00 Ul, m M=. U) N) 0) C� 7z, 0 coo 0 0 0 > > < 9:1 0 (po 0 m 0 ) fOUO M < CD r- a Z :0) 0 X C3) 0 :3 (D (a > (D 3 (A > (D m rr 0 -0 -a CP 5, Z)x (D o -P 3 0 S 00*01'00"W 100.00 Lot 4 -a CD n 3 Z c 3 cr CD .i W, LVOR At 3 0 CD 0 ;u m 0 < 0 -CD M 0 > m - 0 z a cn SD M ?�> < 0 Vim= = 0 > (D (n 0 =7 0 tome 0) > CD M -!-4 (.0 C) 4p MI 7403�1 Municipality of Anchorage Page 3 of 3 DEVEOPMENT SERVICES DEPARTMENT 4700 Elmore Road Anchorage, AK. 99519-6655 - 343-7904 On -Site Wastewater Disposal System or Well Inspection Report Permit Number: OSP161070 PID No. 050-181-01 93.7 93.5 U 98.3 UU � Finished OG 2" Insulation 2,000 Gallon Septic Tank 14.3 P94.15 C14 N LOU 98.1 96.5 Finished Grade Original Grade Geotextile Fabric i� 89.71 40' (Trench Length) 82.5 Groundwater @ 85.5' NORTH TRENCH 5/15/13 U �U 98.0 96.5 Finished Grade Original Grade Geotextile Fabric ---------- 89.7 Drainfield Rock 89.71 40' (Trench Length) 82.5 Groundwater @ 85.5' NORTH TRENCH 5/15/13 U �U 98.0 96.5 Finished Grade Original Grade Geotextile Fabric 89.51 40' (Trench Length) 82.5 Groundwater @ 85.5' 5/15/13 SOUTH TRENCH PROFILE AS -BUILT - No Scale 93.7 93.5 49Th `9 1.1t .1.:::..`.............................' f ``i MICHAEL E. ANDERSON ;•)Tj, ---------- �/— 89.5 Drainfield Rock 89.51 40' (Trench Length) 82.5 Groundwater @ 85.5' 5/15/13 SOUTH TRENCH PROFILE AS -BUILT - No Scale 93.7 93.5 49Th `9 1.1t .1.:::..`.............................' f ``i MICHAEL E. ANDERSON ;•)Tj, MUNICIPALITY OF ANCHORAGE DEVELOPMENT SERVICES DEPARTMENT 4700 BRAGAW STREET ANCHORAGE, AK 99519-6650 DEPTH (feet) 1- 2- 3- 4- 5 6 7 8 9 10- 11 12- 13- 14- 15- 16- 17 18. 19. SOILS LOG - PERCOLATION TEST LEGAL DESCRIPTION: LOT 6, BLOCK I, DALE BRIGGS SUBDIVISION PERFORMED FOR: GAR HENNING DATE: 1012712012 PROJECT No.: PARCEL ID#- TECHNICIAN: A. HARALA TEST HOLE 2 a SILTY GRAVEL WITH SAND 4 GM a a SLOPE N 11 OQ SITE PLAN SEE SITE PLAN i WAS GROUND WATER ENCOUNTERED? its IF YES @ WHAT DEPTH? 1 S DEPTH OF WATER AFTER MONITORING: I I' O 2% d DATE OF MONITORING: 5/15/13 P E n BOH @ 14' DATE READING GROSS TIME (MINUTES) NET TIME (MINUTES) DEPTH To WATER (INCHES) NET DROP (INCHES) TEST HOLE PRESOAKED PRIOR TO TESTING: 10/27 1 3:13/3:23 10 .25"/8.50" 6.25" 2 3:24/3:34 10 .38"/8.50" 6.12" 3 3:35/3:45 10 .25"/8.5o,, 6.25" 4 3:47/3:57 10 2.50"/8.57 6.07" 5 3:58/4:08 10 2.38"/8.50" 6.12" 6 4:10/4:20 10 2.38°/8.50° 6.12" PERCOLATION RATE: 1.6 (MIN/INCH) PERC. HOLE DIA. 6�� (INCHES) TEST RUN BETWEEN: 3.5 FT. and 4.5 FT. COMMENTS: TEST HOLE PRE SOAKED PRIOR TO TEST. TEST PERFORMED BY ANDERSON ENGINEERING. I, MICHAEL E. ANDERSON CERTIFY THAT THIS WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS DATE: 7/25/17 On -Site Wastewater Disposal System Permit MUNICIPALITY OF ANCHORAGE Development Services Department On -Site Water & Wastewater Program 4700 Elmore Road, PO Box 196650 Anchorage, AK 99519-6650 Telephone: (907) 343-7904 Permit Number: OSP161070 Tax Code Number: 05018101000 Work Type: Septic Renewal Permit Effective Dates: April 21, 2016 to April 21, 2017 Design Engineer: ANDERSON ENGINEERING Subdivision: DALE BRIGGS Site Legal Address: DALE BRIGGS BLK 1 LT 6 N100' G:0152 Owner/Address: HENNING GAR M & CATHERINE J PO BOX 770597 EAGLE RIVER AK 995770597 Site Mailing Address: Lot Size in Sq Ft: 19600 Total Bedrooms: 6 This permit is for the construction of: Y Disposal Field Y Septic Tank N Holding Tank N Privy N Private Well N Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80). 3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either: A. Open and Close on the same day. B. Covered, sealed, and heated to prevent freezing. Received Issued By , L By: Date: Date: UNICIPALITY OF ANCHORA �° _ Community Development Department " Ph : 907-343-7904 Development Services Division 07-343-799 On -Site Water & Wastewater Program *11 ON-SITE SEWERMIELL PERMIT APPLICATION Parcell.D. DSS—/8l-O/D-ao Property owner(s)r• Mailing address �p �fb0k o` s i -1-) 0 S97 t�(� ve' ,fes Day phone 7y5 -(. C- /q gIY77 Site address ('leaf- zmk Legal description (Sub'd., Block & Lot) J3 zes $ ( L [ A(tJOd Legal description (Township, Range & Section) Lot Size (j&.QQ Sq. Ft. Number of Bedrooms �o APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: (® all that apply) Absorption Field Initial ❑ Single Family (SF) ❑ Septic Tank �]c Upgrade ❑ (w/wo ADU) Holding Tank ❑ Renewal Duplex (D) .s Privy ❑ Multiple Dwellings ❑ (SF and/or D) Private Well ❑ Water Storage ❑ THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR: Distance: I certify t1l tthe above information is correct. I further certify that this is in accordance with owner or authorized Permit/Rush Fees: C �I 0 1 -60,f C':!V,. Waiver Fees: Date of Payment: Receipt Number: Permit No. 0 J � 1070 Permit App_9-1-12.doo Date of Payment: Receipt Number: Waiver No. ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, AK 99524 522-7773 677-7766 FAX MEMORANDUM DATE: April 20, 2016 TO: Jay Crewdson FROM: Mike Anderson, P.E. SUBJECT: N100', Lot 6, Block 1, Dale Briggs Subdivision Septic System Permit No. OSP151069 The septic system design for the subject lot was originally designed and permitted in June of 2015. The permit is now up for renewal. No development has been completed on this or surrounding lots since the original permit was issued to my knowledge. Conditions in the area remain the same as described in the original design and permit application. On -Site Wastewater Disposal System Permit MUNICIPALITY OF ANCHORAGE Development Services Department On -Site Water & Wastewater Program 4700 Elmore Road, PO Box 196650 Anchorage, AK 99519-6650 Telephone: (907) 343-7904 Permit Number: OSP151069 Tax Code Number: 05018101000 Work Type: Septic Initial Permit Effective Dates: June 04, 2015 to June 03, 2016 Design Engineer: ANDERSON ENGINEERING Subdivision: DALE BRIGGS Site Legal Address: DALE BRIGGS BLK 1 LT 6 N100' G:0152 Owner/Address: HENNING GAR M & CATHERINE J PO BOX 770597 EAGLE RIVER AK 995770597 Site Mailing Address: Lot Size in Sq Ft: 19600 Total Bedrooms: 6 This permit is for the construction of: Y Disposal Field Y Septic Tank N Holding Tank N Privy N Private Well N Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80). 3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either: A. Open and Close on the same day. B. Covered, sealed, and heated to prevent freezing. Received Issued By Municipality of Anchorage Development Services Division Onsite Water and Wastewater Program went IS, 1� P J v H N N epartment **** VARIANCE/WAIVER REVIEW **** Waiver#: OSV161015 COSA#: _ Permit#: OSPIS1069 PID#: 050-18"1 Legal Description: Dale Brings, Block 1, Lot 6 N100' Engineer: Anderson Engineering Applicant: Gar & Catherine Henning Your request for a waiver of the required 10 feet horizontal separation from the _absorption field to the property line has been approved. The approved separation distance is'6 feet. This waiverapproval applies to the proposed absorption field only. Any future upgrade to the on-site wastewater disposal system will require all separation distances be met or another approval from this department. The affected adjacent property owner(s) have been given a 7 day notice regarding this waiver. ❑ Notarized letter(s) of non -objection have been received from the owner(s) of the affected adjacent property. 0 Adjacent properties are not affected by this waiver. 'man ... MEN .... Nam .... owes .... an ... won...won, Waiver is Granted: X Waiver is not Granted: Date: Approved by' Reviewer ............................. a ... .'..... a ... . -.:....... a....................� MUNICIPALITY OF Community Development Department Development Services Division On -Site Water & Wastewater Program Phone: 907-343-7904 Fax: 907-343-7997 ON-SITE SEWER/WELL PERMIT APPLICATION Parcel I. D. 050-181-01 Property owner(s) Gar & Catherine Henning Day phone Mailing address P.O. Box 770597 Eagle River, AK 99557 Site address 17013 Kantishna Drive Eagle River, AK 99557 Legal description (Sub'd., Block & Lot) Dale Briggs, Block 1, Lot 6 N100' Legal description (Township, Range & Section) Lot Size 19,600 Sq. Ft. Number of Bedrooms Six (6) APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: (0 all that apply) Absorption Field 0 Initial 0 Single Family (SF) El (w/wo ADU) Septic Tank 0 Upgrade ❑ Duplex (D) 0 Holding Tank ❑ Renewal ❑ Multiple Dwellings ❑ Privy ❑ (SF and/or D) Private Well ❑ Water Storage ❑ THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR: Lot Line Distances'6.-S I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit/Rush Fees: 5�1— Date of Payment: 4f Al1/S Receipt Number: 6,2Li559 IS Permit No. 4W 16-1 D (04) Permit App_9-1-12.doc Waiver Fees: 021 Date of Payment: L/ /L Receipt Number: a'5-"% 44 Waiver No. 65V 151015 ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, AK 99524 522-7773 677-7766 FAX April 4, 2015 Municipality of Anchorage Development Services Department On -Site Water and Wastewater Program 4700 South Bragaw Street Anchorage, AK 99519-6650 Subject: N100' Lot 16, Block 1, Dale Briggs Subdivision Septic System Design and Permit Application Impacts to Adjacent Properties Dear Onsite Services Engineer The owner of the North 100' of Lot 6, Block 1, Dale Briggs Subdivision intends to construct a new six -bedroom duplex on the lot. We are therefore requesting a permit be issued for the construction of a new septic system to accommodate the structure. The attached Site Plan and backup documentation identify the location and configuration of the proposed septic system along with the alternate site. Also identified on the plans are the existing wells on surrounding lots. The area is served by the AWWU water system and a new water service will be constructed to this lot No conflicts exist between the proposed septic system and wells on adjacent lots. Drainage arrows are shown on the site plan showing the grade and direction of flow on the lot. The drainage pattern will not be changed as a result of this project. A test hole was placed on the lot in the area of the absorption trench and alternate site. The log indicates silty gravel with sand (GM) and some silt in the zone specified for the absorption trench. The percolation rate of the soil was determined to be 1.7 minutes per inch. Groundwater was found during the placement of the test hole at 11' below the surface and remained at that level during the monitoring period which included May 15, 2013. An application rate of 1.2 gallons per day per square foot was used in the design of the absorption system. We are proposing to place a new 2,000 -gallon septic tank and 2 - 40' long by 5' wide by 4' effective depth absorption trenches to treat and dispose of the effluent generated in the duplex. The elevation of the distribution line in the absorption trench will be 3' below the surface and the total depth will be 7'. A minimum of 3' of fill or 2" of insulation and 2' of fill will be placed over the absorption trench and 4' over the septic tank. The ground surface on the lot in the area of the septic system slopes to the north at N100' Lot 6, Block 1, Dale Briggs Subdivision April 4, 2015 Page Two shallow grades. The new trenches will be constructed parallel with the contours of the slope as much as possible in conformance with Municipal requirements. The new septic system will be constructed a minimum of 100' from all wells and any surface water and 10' the proposed and existing water services in the area. If the system is constructed in accordance with our design the following statements apply: The system, if constructed as designed, will have no adverse impact on the wells in the area or those to be constructed in the future. 2. The system, if constructed as designed, will have no adverse impact on existing septic systems in the area or those to be constructed in the future. 3. The system, if constructed as designed, will have no adverse impact on reserve space, either surface or subsurface, on any lots located in the area. 4. The system, if constructed as designed, will have no adverse impact on drainage patterns in the area. The current drainage pattern will be maintained. Sincerely, Michael E. Anderson, P.E. Attachments MICHAEL E. ANDERSON April 6, 2015 Municipality of Anchorage Development Services Department On -Site Water and Wastewater Program P.O. Box 196650 Anchorage, AK 99519-6650 Subject: North 100' Lot 6, Block 1, Dale Briggs Subdivision Separation Distance Waiver Absorption Trench to Lot Line Dear On Site Services Engineer: The subject lot is only 100' in depth allowing very little area for an on site septic system. The lot and the surrounding area are served by the AWWU water system however and no conflicts will result from placement of the absorption trench at 6.3' from the north property line. Soils in this area percolate at rates less than 5 minutes per inch and little or no migration of effluent is expected. We therefore request a waiver be issued allowing the absorption trench system to be constructed 6.3' from the north property line. Sincerely, Michael E. Anderson, P.E. .' 49th MICHAEL C ANDERSON No. CE -4381 I I 4: • I i � � � N i c� %Ito411 o'� N x o a `, .����r sY�Vl� , •��� 11 rE'n¢o �� MLLyy�•�. is e�•.N C 'r 11♦6• •.. D c y I ,00.00 M.00,LG40 s U MM I m�� E °o a '� 03------------------------------- - o O Wz ¢ w w 3Q ` W X� O I a ti p p0 (� oma® o %0zaw H ¢ ¢ Of -1 x o 0 C) 0O N2 li w i �' U/ ,. > I O� N 0 > V M ✓; p Jo vi f/I wN O II > N o O a iu w o o t0 w ' 1 J L7 O 3��. x o � oo p °J' w 03 w J Q 0'4b o C Z K m 0 ¢ly w m I O 65 >> �> W 0 Lj Z , .— D 0 a/m¢ d mN I O O`V a w o .� 3 E toz coma�ioo Q� c ami w o' ^ v Ow. a)—011 00 °gym ~ r m w I I U' O p> O Z ¢3 o v Z Ztn `Darn W H J� IUi 3: C) N L, I 1N31Y35tl3 N31tlM ,5 ,00.00L 3„00,£0.00 N N NORTH 100', LOT 6, BLOCK 1 DALE BRIGGS SUBDIVISION DESIGN FACTORS: SYSTEM REQUIREMENTS Six Bedroom Duplex 5' Wide Trench System Perc. Rate: 1-5 Min./Inch 2,000 Gallon Septic Tank Application Rate: 12 GPD/SF 4' Drainfield Rock 6 Bedrooms ` 150 GPD/Bedroom = 900 SF Absor tion Area 900 SF/1.2 GPD/SF/5 SF (Width) `.5 (Red. Factor 750 LF Trench Length THEREFORE: Construct 2-40' Long x 5' Wide x 4' Effective Depth Absorption Trenches. Flow Line Elevation in Trenches to be 3' Below Original Ground Surface. Total Depth to be 7' Below Existing Ground, Provide 3' Cover Over Absorption Trench and 4' Cover Over Septic Tank. Place Flow Splitter to Insure Even Flow to Each Trench. 5' TYPICAL 5' WIDE TRENCH SECTION• iviysm (NO SCALE) Jev\7E �•• � NOTE: Grade Area Over Trench to Drain Away. C{i 49th Minimum 6' Separation From Bedrock. 0- ...:. ......t.......P...... Minimum 4' Separation From Groundwater. 0 y� F!-�-s C. Minimum 100' Separation From Private Wells in the Area. 00 : MICHAELE ANDERSON Minimum 100' Separation From Surface Water or Streams No. CE -436, MUNICIPALITY OF ANCHORAGE DEVELOPMENT SERVICES DEPARTMENT 4700 BRAGAW STREET ANCHORAGE, AK 99519-6650 DEP Ell (feet) 1 - 2 3 4 5 6 7 8 9 10- 11 12- 13- 1 1 1 1 1 SOILS LOG - PERCOLATION TEST LEGAL DESCRIPTION: LOT 7 BLOCK I, DALE BRIGGS SUBDIVISION PERFORMED FOR: GAR HENNING DATE: 10/27/2012 PROJECTNo.: PARCEL ID#: TECHNICIAN: A. HARALA OB/OG TEST HOLE 1 a I SILTY GRAVEL d 1 WITH SAND d. GM a � d d d . COMMENTS: BOH @ 13' SLOPE mll MICHAEL E. ANDERSON NO. CE -4381 SITE PLAN SEE SITE PLAN WAS GROUND WATER ENCOUNTERED? YES IF YES @ WHAT DEPTH? F DEPTH OF WATER AFTER MONITORING. I' 2% DATE. OF MONITORING" 5/15/13 HOLE PRE SOAKED PRIOR TO DATE READING GROSS TIME (MINUTES) NET TIME (MINUTES) DEPTH TO WATER (INCHES) NET DROP (INCHES) TEST HOLE PRESOAKED PRIOR TO TESTING: 10/27 1 1:42/1:52 10 .88"714.00" 6.12" 2 1:53/2:03 10 .69"/13.75" 6.06" 3 2:04/2:14 10 7.75^/13.88" 6.13" 4 2:15/2:25 10 7.69"/13.75" 6.07' 5 2:26/2:36 10 .56°/13.63° 6.07' 6 2:37/2:47 10 7.63"/13.63" 6.00" PERCOLATION RATE: 1.7 (MIN/INCH) PERC. HOLE DIA. K (INCHES) TEST RUN BETWEEN: 3_5 FT. and 4_5 FT. TEST PERFORMED BY ANDERSON ENGINEERING. 1, MICHAEL E. ANDERSON CERTIFY THAT THIS WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS DATE: 4/4/2015 Parcel I.D. 050-181-01 0 o� C Municipality of Anchorage On -Site Water and Wastewater Program V6C dA (907) 343-7904 S F E -r Y 3e _17 Certificate of On -Site Systems Approval 1 Expiration Date: -'2_0 -) o C7 Complete legal description Dale Briggs, Block 1, Lot 6 N100' Location (site address) 17022 Monte Road Eagle River, AK 99577 Current Property owner(s) Mailing address Real Estate Agent Day phone 17015 Monte Road Eagle River, AK 99577 2. TYPE OF DWELLING: ❑ Single Family (w/wo ADU) � Duplex 1771 Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: Individual Well El Individual Water Storage F1 Community Class Well 1771 Public Water System ED Day phone r Individual 0 Holding Tank 1771 Community 1-1 . Public Sewer E-71 Waiver/Variance request for: Distance: Received by: Date: 71a�1,7 COSA to be released to the engin6e ,'_r unless otherwise requested by the engineer. COSA Fee $111 - Date of Payment —712,c t f1 Receipt Number 013 COSA# 05C11_11 Waiver Fee $ Date of Payment Receipt Number Waiver # f•�'��-�t�� li�l��il�l� '�7�+r��C�7fii�TCe7�t-���7 As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm Anderson Engineering Address P.O. Box 240773 Anchorage, AK 99524 Phone 522-7773 Engineer's Printed Name Michael E. Anderson, P.E. Date 7/25/2017 OF A4 It a-T- �°° ° 4.9 fi-i 6. DSD SIGNATURE • ... ° � � System #1 Approved for bedrooms ....... ...,. �� VO,4°Ar,Ur:lzsaN..� MICHAEL" E, � System #2 Approved for bedrooms ®��zs381 f Disapproved 444 pRQF �,p�- Conditional approval for bedrooms, with the following stipulatlo�i: lr � eN—S _ 7 WATER AND WASTEWATER c PReG �- .7-2_-� Original Certificate Date: The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors'or omissions in the professional engineer's work. 7. ATTACHMENTS: COSA Checklist X Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other COSA blue sheet—E '- .: c If more than Iseptic system ksmn the lot: CDSAChecklist # -of Structure served bythis system D[�|�� Briggs, ��|nC� 1 k� �� W1O[Y Legal OeoorpUnn� ^~ ' ~~''"� ` ^~'`' " ' ' `-~^ ° ' " ' °~ A. WELL DATA - Public Water System Well type IfA,B.orCprovide PWS |D#____ Date completed Sanitary seal H/N\____ Total depth ft. Cased to ft. FROM WELL LOG Date oftest Static water level ft. Well production g -p -nn- VVA[ERSAK4PLE RESULTS: Coliform co|oniee/100 mL Nitrate Arsenic ug/L Data of sample: Well Log HYN)________ Wires properly protected (Y/N)_________ Casing height (above ground) in. AT INSPECTION Collected by: ft. B.SEPTIC/HOLDI0G TANK DATA ���nt'���t��| 11yJD�O1� TankTypa/�oteria| `' r^'`"`' ' Date installed ' ''^-"'^'~ ' " ���� � `� Tank size ' oa| Number ^- C|eanouts(Y7N) ' _--�' _����� . ��` Foundation cleanout (Y/N)Y Depression over tank (Y/N) N_��_ High water elarm(Y/N) Date of pumping Plumper New CODst[Uct'DD Date installed 11/20/17 Soil rating (g.p.dmcor*2 /bdnm) 1.2GPD/SF System type b' Wide � ��z1O � z1 Length� � '" �� Width� ft. G��|��pi�__ft. �5 Tota|depth_`,^�_�� E�AOD �obaorptionarea Monitoring Y,Depression K|,._ Date ofadequacy test New Const. Reou|to(Paoa/Fai|) For6bedrooms Fluid depth inabsorption field before test in. Water added gal. New depth in. Elapsed Time: _______min. Final fluid depth in. Absorption rate >= g.pd. �J Any n�uvenationtreatment (paot12mV.)(Y/N&typm) '= |fyes, give date________ Q. LIFT STATION Date installed "Pump on" level at Datum _ Size ingallons __ in. "Pump off" level at — Cycles tested in E. SEPARATION DISTANCES -PUb|iC Water System WELL ONLOT TO: Manhole/Access (Y/N)_____ High water alarm level at_____ Meets alarm & circuit requirements? Septic tank/lift station onlot Onadjacent lots Absorption field onlot Onadjacent lots Public sewer main Public sewer manhole/cleanout ____ Sewer /septic service line Holding tank Animal containment areas Manure/animal excrete storage areas SEPTIC/HOLDING TANK ONLOT TO: . � Building foundation >51� n Property line >51 / 10 Water main �,'" Water service line >10' Wells unadjacent lots >100' ABSORPTION FIELD ONLOT TO: ' 1M Property line ��'" Building foundation �^1O'_'`..,____ v VVaterServioe|ine>10'_`_,^'Su�ocevvatar �'�°1OO hJOD6�0Ot�� >100'Curtain drain None Noted ` " Wells on adjacent |m�o_`_.~,`, G. ENGINEER'S CERTIFICATION / certify that /have determined through field inspections and review of Municipal moods that the above smh*mo are in conformance with MOA C{>S4guidelines /neffect onthis date. Engineer's Printed Name Date Absorption field >51 Surface water >10O' Water main >10+ DhvaweKpeddng/vehicle storage >1O' 0 S OiTol loo v 100.00' � Y KANTISHNA DRIVE �a p Ct W03'00"E 100.00' aj 6 P p(�♦ tai �Y YAfF p f CD qr 0 Ci x1 ZS . CN' @ 15. .. t. N � , 16.2` 4,0' OD.• z m 0 4,0 CO 0 0 co :e ba;z rn `G C) Q m tt3.4' 5 e Ln I Ci rsi o C) S OiTol loo v 100.00' � Y