ON-SITE WASTEWATER INSPECTION REPORT
Permit Number: OSP151304 PID Number: 017-101-63 ❑✓ New ❑ Upgrade
Spinell Homes Inc
ress
14092 Raptors Knoll Cir.
5
-
DESCRIPTION
Block
Knoll
Range
10
From
Septic
Tank
Absorption
Field
Lift Station
Holding
Tank
Sewer
Line
Well
127.1
150.8
100+
100+
85.3
Surface Water
200+
200+
N/A
__N/A
Lot Line
28.3
21.9
N/A
N/A
NA
Foundation
46.3
66.1
NIA
N/A
Curtain Drain
50+
50+
NIA
N/A
Remarks
BSORPTION FIELD
0 Deep Trench ❑ Shallow Trench ❑ Sed ❑ Mound
❑ Other
it Rating Total depth from original grade
- 1.2 GPD/SF 13 Ft
pth to pipe invert from original grade - Gravel depth beneath pipe
5 Ft. 8ft.
added above original grade.. Gravel length _
2.4 Ft. 40 Ft.
ivel width Beds: Number of Lines Distance between lines
2.5 Ft. N/A N/A Ft.
at absorption area Number of trenches Dist. between trenches
640 Fr 1 N/Art
T.E.P. ❑
Anchorage Tank I 1,500Gal-
Material Number of compartments
Steel 2
LIFT STATION
on level at I IPump off level at IHigh water alarm at
make and model
by 'I
PIPE MATERIAL House to tank IdI IIIIU
Installer 3034 drainfield 3034
Pomraining Excavation Drainfield 3034 Co/MT 3034
inspector Pannone Engineering Services BENCH MARK (Assumed elevation) 100ft
Inspection a Location and description -
dates: f 2/5/2016 2 2/5/2016
T4 2/5/2016 a'". - First Floor Finish Floor
COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL Engineer's Stamp
Approval:
Approved tvv,,-�����'--'f
InencM'rnn Denny 1_1_19 Ann
Date
Date,gI () - I (..M
FIE
1 \
k5\
II ��
RESERVE DRAIN FIELD (P)
BASED ON CAT 3 SYSTEM
MIN 7.91-F x 2.5'W x 8.0'ED x 13.0'TD�
Ipi
+25%
SEPTIC AREA (P)
BY OTHERS (NIC) - -
RESERVE DRAIN FIEL
-35LF x_2.5'W x 8.0'ED x 11
NEW DRAIN FIELD
40LF x 25W x 8.0'ED x 13.0 TD
C2
TH-1'
/ (PES) NEW 1500g SEP M
N
DC \s
f5% SLOPE & DRAINAGE -
Mt ct Qi�COEASEMENT-\ -
T2 Tl
T -11
(ANDERSON 2013) +5% -
O� op -T10' UNDERGROUND R.O.W.
\\ _eA skAC V C /\ •h
LO NEW
5
HOUSE
TH-12
/ (ANDERSON 2013 WELL (E)
60X10 RETENTION BASIN \
" SEE NOTE
`y
WELL (E) 3
" NOTE: ya/
RETENTION BASIN IS REQUIRED BY PLAT.
THE BASIN WILL BE NO MORE THAN 2 FEET.
DEEP. THIS LOT IS TYPIFIED BY DRY -
'Z WOODLAND VEGETATION, WITH SOIL THAT
_ PERCOLATES FASTER THAN 5 MINUTES PER %
INCH. IT IS NOT LIKELY THAT THIS RETENTION
BASIN WILL EVER CONTAIN WATER. -
PAMONE ENG SVC, LLC
P.O. BOX 100217 ANCHORAGE, AK 99510
PHONE (907) 272-8218 FAX (907) 272-8211
TH
TEST HOLE
LF
LINEAR FEET
SF
-SQUARE FEET
BR
BEDROOM
(P)
PROPOSED -
(E)
EXISTING
CO
CLEAN OUT NO.
MT
MONITOR TUBE NO
TYP
TYPICAL
M1
NOTES:
RECORD
DRAWING
DRAWN BY:
NJC
PLAN
RAPTOR'S KNOLL, LOT 6
RAPTOR PROPERTIES LLC
RAPTOR'S KNOLL CIRCLE
ANCHORAGE, AK 99516
C D
WELL WE48.4 .58.4
F A \ 11 Date
C�s�`e�+ 0/2016
S/2
1.=50'
P.I.D. NO
017-101-63
••. •Steven RPannone
,P '. CE 8749 .<4:
OSP151304
Sheet
2 OF
I
A
B
FC
3.8
17.8
- T1
47.5
53.1
T2
56.4-
62.2
DC-
62.5
- 68.4
C1
67.2
76.2
M1
67.3
76.4
C2
104.2
110.6
M2
104.1
1.10.5
C D
WELL WE48.4 .58.4
F A \ 11 Date
C�s�`e�+ 0/2016
S/2
1.=50'
P.I.D. NO
017-101-63
••. •Steven RPannone
,P '. CE 8749 .<4:
OSP151304
Sheet
2 OF
I
SPECIAL PROVISIONS TO SPECIFICATIONS
s5
5
40.0
PRIMARY SEPTIC SYSTEM
SF
w
m
BR -
m
(P)
Q o
O
o
Jo
z
MT
FILTER FABRIC
F
MIN LENGTH: 39.1 LF
zQ
a
mQ
TOTAL AREA: 640 SF
z
RESERVE SEPTIC SYSTEM
w
z
/[�,ToDRAIN PIPE-
SOIL RATING: 6.0 GPD/SF
LEGEND
ini
SYS. TYPE: DEEP TRENCH 8.0'ED
W WATER LINE/
MIN LENGTH: 7.9 LF
ORAIN ROCK 6" ABOVE PIPE INV
USE: -
o -
DEEP BURIAL
1,500g SEPTIC
TANK NEW
DESIGN PARAMETERS
TEST HOLE
40.0
PRIMARY SEPTIC SYSTEM
SF
NO. BEDROOM: 5 (750 gpd)
BR -
TANK SIZE: 1500g
(P)
PERC RATE: 4.5 MPI
(E)
SOIL RATING: 1.2 GPD/SF
CO
AREA ROD: 625 SF
MT
SYS. TYPE: DEEP TRENCH 8.0'ED
TYP
MIN LENGTH: 39.1 LF
- -
- USED: - -
40LFx2.5'Wx8.0' E.D., 13.0' TD -
TOTAL AREA: 640 SF
DESIGN PARAMETERS
RESERVE SEPTIC SYSTEM
NO. BEDROOM: 5 (750 gpd)
TANK SIZE: 2,000g WITH 2 AX 20 PODS
PERC RATE: 4.5 MPI
SOIL RATING: 6.0 GPD/SF
LEGEND
AREA ROD: 125 SF
SYS. TYPE: DEEP TRENCH 8.0'ED
W WATER LINE/
MIN LENGTH: 7.9 LF
WELL RADIUS
USE: -
SS NEW SEPTIC
8LF MINx2.5'Wx8.0' E.D., 13.0' TO
- -
TOTAL AREA: 5-.�;_ sX
NOTES:
PANNON Pr
PANG SVC, C, LLC
RECORD DRAWING
P.O. BOX 100217
ANCHORAGE, AK 99510
PHONE (907) 272-8218
FAX (907) 272-8211
DRAWN BY:
NJC
RAPTOR'S KNOLL, LOT 6
RAPTOR PROPERTIES LLC
RAPTOR'S KNOLL CIRCLE
DESIGN DETAILS ANCHORAGE, AK 99516
86.9 -4.5
78.9-7
6.0
-19.0 1900
72.9
NO GROUND WATER
ENCOUNTERED
ABBREVIATIONS
TH
TEST HOLE
LF
- LINEAR FEET
SF
SQUARE FEET
BR -
BEDROOM
(P)
PROPOSED
(E)
EXISTING
CO
CLEAN-OUT NO.
MT
MONITOR TUBE NO.
TYP
TYPICAL
OF AL �sl Date Z
�.......q 1� �
���,• �.9++ Scale
*• % NTS
Steven 'f *�Pannon e•
ice•. CE 8149 .•<e:
OSP151304
Sheet
3 OF
08/07/2014 07:07 907-345-0202 ALPINE DRILLING PAGE 02/02
Alpine Drilling & Enterprises
Well Log
Permit Number. #SW 141500 Date of Issue: 11-12-14 Parcel Identification Number: 01710155000
Date Started: 11-17-14 Date Completed: 11-18-14 Is well located at approved permit location? a ices ❑ No
Legal Description: Timber Trail Lot 6
Property Owner Name & Address: Raptor Properties LLC
5725 Yukon Charlie Loop
Anchorage, AK 99502
Method of Drilling x air rotary ❑ cable tool
Borehole Data: Depth (ft)
Soil Type, Tbiekness & Water Strata
From
To
Casing type:steel
.—
Stick up
Gravelly silt
0
2
2
12
Wall Thiclmess:.250 inches
Diameter: 6 inches Depth: 204 feet
Liner Type:
Gravelly cobbly silt
12
40
Diameter: _ inches Depth: — feet
sandy silt
40
59
Casing stickup above ground: 2 feet
cobbly silty gravel
silt
gravelly cobbly silt
59
66
77
66
17
160
Static water level (from ground level): 145 feet
Pumping level:feet after
2 hours pumping 15+ gpm
Recovery Rate: 15+ gpm
cobbly gravel
160
165
Method of Testing: Atli
sandy silt
165
171
well Intake Opening Type:
gravelly silt
silty water sand &gravel
171
199
199
204
x Open End ❑ Open Hole
❑ Screened Start _ feet Stopped— feet
perforations Start feet Stopped—feet
Grout Type: bentonite eranules Volume: 2 bes
D S feet Sto ed ? et
Pump- Intake Depth _ feet
WATER QUALITY TESTING
pump size _ hp Brand Name
Well Disinfected Upon Completion? x Yes ❑ No
cworm - pteq
Coillooff L
Method of Disinfection: chlorine tablets
Nitrates I.3 o
Arsenic: _ N a
mgII-
ug&
Comments:
s
Well Driller: Alpine Drilling & Enterprises
PO Box 110496
Anchorage AK 99511
'tom
v BILL 8. COLEDOC CO dba
O
- ULLIVAN WATER WELLS
P.O. Box 670269, Chugiak, AK 99567 688-2759
www.sullivanwaterwells.eern
Pump Installation Loj
Well Drilling Permit Number: SW OSP151304 Date of Issue 9-1&15
Parcel Identification Number: 01710163000
Legal Description
Raptors Knoll Lot 6
Pump Installation Date: 2-24-16
Pump Intake Depth Below Top of Well Casing: 190
Pump manufacturer's Name: Grundfos
Pump Model: 10SQE15-330
Pump Size: 1.5
Pitless Adapter Burial Depth: 10
Pitless Adapter installer: Pomraning Excavation
Disinfected Upon Completion? ® yes Q no
Method of Disinfection: Chlorine So PPM -
Comments: Pitless Manufacturer: Martinson
Pump Installers Name: Sullivan Water Wells
Property Owner Name & Address
Spineli Homes 1900 W. Northern Lights Blvd #200
Anchorage, AK 99517
feet
hp
feet
Attention: The pump installer shall provide a pump installation log to the DSD within 30 days of pump installation.
Permit Number:
Tax Code Number:
On -Site Wastewater Disposal System Permit
MUNICIPALITY OF ANCHORAGE
Development Services Department
On -Site Water & Wastewater Program
4700 Elmore Road, PO Box 196650
Anchorage, AK 99519-6650
Telephone: (907) 343-7904
OSP151304
01710163000
Work Type: Septic Initial
Permit Effective Dates: September 16, 2015 to September 15, 2016
Design Engineer: PANNONE ENGINEERING SERVICE
Subdivision: RAPTORS KNOLL
Site Legal Address: RAPTORS KNOLL LT 6 G:3037
Owner/Address: RAPTOR PROPERTIES LLC
5725 YUKON CHARLIE LOOP ANCHORAGE AK 995020000
Site Mailing Address: Lot Size in Sq Ft: 51421
Total Bedrooms: 5
This permit is for the construction of:
Y Disposal Field Y Septic Tank N Holding Tank N Privy N Private Well N Water Storage
All construction must be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater
Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80).
3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services
Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either:
A. Open and Close on the same day.
B. Covered ,s ae„ledd _and heated to prevent freezing.
Special Provisions:
1. Prior to Inspection Report approval, the Pump Install Log and water samples are to be
submitted for review.
2. A MOA Encroachment Permit is required for the well located in the Slope and Drainage
Easement prior to Inspection Report approval.
3. A letter of non -objection from Chugach Electric Association for the well in the 10' easement
required prior to Inspection Report approval.
Received
Issued By
MUNICIPALITY OF ANCHORAGE
Community Development Department Phone: 907-343-7904
Development Services Division Fax: 907-343-7997
On -Site Water & Wastewater Program
ON-SITE SEWER/WELL PERK 1T APPLICATION
Parcel I.D. 017-101-63
Property owner(s) Raptor Properties LLC Day phone
Mailing address 5725 Yukon Charlie Loop, Anchorage, AK 99502
Site address Raptors Knoll Circle
Legal description (Sub'd., Block & Lot) Raptor's Knoll, Lot 6
Legal description (Township, Range & Section)
Lot Size 51,421
Sq. Ft.
Number of Bedrooms 5
Waiver Fees:
APPLICATION IS FOR:
APPLICATION IS AN:
TYPE OF DWELLING:
Receipt Number:
(M all that apply)
Waiver No.
Absorption Field
❑x
Initial ❑X
Single Family (SF)
1z
(w/wo ADU)
Septic Tank
❑x
Upgrade ❑
Duplex (D)
❑
Holding Tank
❑
Renewal ❑
Multiple Dwellings
❑
Privy
❑
(SF and/or D)
Private Well
❑
Water Storage
❑
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
Distance:
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
Permit App_-'-:. :'-.Ic;
Permit/Rush Fees:
Waiver Fees:
Date of Payment: /5
Date of Payment:
Receipt Number:
Receipt Number:
Permit No. 015plo
Waiver No.
Permit App_-'-:. :'-.Ic;
Pannone Engineering Services, LLC
Steven R. Pannone, Principal
Registered Professional Engineer
E-mail: steve0panengak.com
August 31, 2015
Subject: Raptor's Knoll, Lot 6
Septic System Upgrade Permit Request
Design. Narrative
This is a design narrative for a permit to install a septic system to be issued for this property. The proposed
systems will serve an proposed five bedroom (5) bedroom house. Currently the lot is undeveloped. This
lot is served by a private well that was installed before the subdivision was completed. The surrounding
developed lots are served by private wells. There are no wells within 100' of the proposed septic system.
1. Soils. Two test holes were performed on this lot by Michael E. Anderson in February of 2013, and
groundwater was monitored for at least seven days. Ground water not was observed to a depth of 19'
below the surface in the test hole monitor tube in May of 2013. Bedrock was not encountered in the
test hole. Based on the results of the percolation tests and overall soils appearance; an application rate
of 1.2 gallons/day/square feet was used for a conventional wastewater system in the area of the test
hole.
2. Soil Absorption System Design.
a. See Sheet 1 of the design package.
3. Surface Water: There is no surface water within 100 feet of the proposed septic tank and drain field.
The proposed drain field upgrade will maintain at least 100 feet from all surface water and drainage
ditches.
4. Topography: The existing topography generally slopes from the east to the west in the area
surrounding the septic system at approximately 10%. There are no steep slopes within 50' of the proposed
drain field. The proposed drain field will maintain 50' separation all steep slopes.
S. Drawing Markings: The Drawings are marked "For MoA Review Only". When written notification that
the review is complete and that there are no further comments is received from MoA On -Site Department,
the note will be removed and "Issued for Construction" drawings will be issued.
The proposed installation will not affect the future development of this or the surrounding lots.
Mailing: P.O. Box 100217, Anchorage, AK 99510-0217
Physical: 332 East Manor, Anchorage, AK 99501
Telephone: (907) 272-8218 FAX: (907) 272-8211
SEPTIC AREA (P)
BY OTHERS (NIC)
i\
`
RESERVE DRAIN FI
I
35LF x 25W x 8.0'ED x 1
5
PRIMARY DRAIN FIELD (P) \
�M -
4OLF x 25W x 8.0'ED x 13.0'TD
WITH MONITOR TUBE AND f 5%
CLEAN OUT AT EACH END
- - RESERVE DRAIN FIELD (P) TH-1
_ ,,M�-�M
-
4OLF x 2.5'`W/ x-8.0'ED x 13.0'TD (PES)
//
J oNz
1y.
JJJIII
SLOPE & DRAINAGE
EASEMENT
TH- 1 1
• (ANDERSON 2013)
ZZ
1500g SEPTIC TANK (P) kQ/NN
I INSTALL FOUNDATION CLEAN OUT
10' UNDERGR UND R.O.W.
AND DOUBLE CLEAN OUT
\\
g _
vwi M +5%M 5
BR 102.4 w
/l<L
05%HOUSE
DRQ f
N
o TH-12
/ (ANDERSON 2013)
WELL E
60XIO RETENTION BASIN \
/ SEE NOTE -
g
1 < _
II �G
�
7i
WELL (E)
��
� �' w Aw
ABBREVIATIONS
-
LF
LF
TEST HOLE
LINEAR FEET
/ 1 \
SF
SQUARE FEET * NOTE:
BR
(P)
BEDROOM RETENTION BASIN IS REQUIRED BY PLAT. -
PROPOSEDTHE BASIN WILL BE NO MORE THAN 2 FEET
\
(E)
DEEP. THIS LOT IS TYPIFIED BY DRY
EXISTING - �G WOODLAND VEGETATION, WITH SOIL THAT
CO
CLEAN OUT NO. PERCOLATES FASTER THAN 5 MINUTES PER
MT
MONITOR TUBE NO. INCH. IT IS NOT LIKELY THAT THIS RETENTION
TYP
TYPICAL BASIN WILL EVER CONTAIN WATER.
-
"°TES:PANNONE
ENG SVC, LLC
P.O. BOX 100217 ANCHORAGE, AK 99510
--'`OF At\��i
'�� " • " • qS 1)
D01/11/16t
CHANGE ORDER
Scole
PHONE (907) 272-8218 FAX (907) 272-8211
j * .49 *�l�
�....... . .... ....
P.I.D. NO
RAPTOR'S KNOLL, LOT 6St
••� /
017-101-63
�°
RAPTOR PROPERTIES LLC
even -p Pa Pannone
P CE 8149 c /
RAPTOR'S KNOLL CIRCLE
F •`./
�� �,r�•. . ��-r
OSP151304
PLAN
ANCHORAGE, AK 995160�
Oi s"V`
Sh1 etOF 3
SOILS LOG - PERCOLATION TEST
SLOPE \
TH
�I
ON 2013)
12 '"
TEST HOLE 1
GRAY SILTY - -
WATER
LEVEL
READING
SM
GRAVEL WITH
GRAYSILTY
1
SILTY SAND
GM!
GRAVEL WITH
WAS GROUND WATER
14
SM
SILTY SAND
2
2.227"
IF YES, AT WHAT
(FILL)
3
DEPTH? -DRY
16
--
---
a
1519
ORGANICS/
4
2.315"
OR/OL
ORGANIC SILTS
1520
5
6.293"
--
---
6
1530
10.5 MIN
SILTY GRAVEL
2.308"
4.540"
SM
WITH SILTY SAN
s
7
a
9
10
SOILS LOG - PERCOLATION TEST
SLOPE \
TH
�I
ON 2013)
12 '"
-
GRAY SILTY - -
WATER
LEVEL
READING
SM
GRAVEL WITH
13
1457
SILTY SAND
6.293"
---
WAS GROUND WATER
14
1507
ENCOUNTERED? N
15
2.227"
IF YES, AT WHAT
3
1508
DEPTH? -DRY
16
--
---
a
1519
DEPTH TO WATER AFTER
17
2.315"
MONITORING? -DRY
18
1520
DATE:- 12/2115
19
BOH
DATE PERFORMED: 12/11/15
GO
SITE PLAN \
\1 ,
\ TH-1
(PES)\
I
1- \
I
10
SLOPE
TH
X
READING DATE
CLOCK
TIME
NETTIME
WATER
LEVEL
READING
NET DROP
Q(MPI)
1 11DEC15
1457
--
6.293"
---
---
2
1507
10 MIN
8.520"
2.227"
4.490"
3
1508
---
6.293"
--
---
a
1519
10.5 MIN
8.608"
2.315"
A.505"
5
1520
---
6.293"
--
---
6
1530
10.5 MIN
8.601"
2.308"
4.540"
PEROLATION RATE 4.5 (min/inch) PERC HOLE DIAMETER 6 inches
TEST RUN BETWEEN 6 FT AND 7 FT
COMMENTS: Test hole excavated by POMRANING EXCVATION. Prec hole was presoaked.
Test run for at least one hour. Last 3 readings reported
PERFORMED BY: J.R.LAWENDOWSKI. I CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE
WITH ALL STATE AND MUNICIPAL GUIDLINES IN EFFECT ON THE DATE OF THIS TEST.
NOTES:
PANNONE `ENG SVC, LLC
P.O. BOX 102954 ANCHORAGE, AK 99510
PHONE (907) 272-8218 FAX (907) 272-8211
���� 1\
_ of a� ���
'��•' "•qS 1�
%6j�p �y1�
*; �I
..... ....
........ .. . ..
/ P teve CER. �Onno:-e�
I �f. �/
�)
1�lFgFOp""'NP��
il�`,oFEsslo_�,
Date
01/08/16
CHANGE ORDER
Scale
NTS
RAPTOR'S KNOLL, LOT 2
RAPTOR PROPERTIES LLC
RAPTOR'S KNOLL CIRCLE
ANCHORAGE, AK 99516
P.LD. NO
-101-63
PERMIT NO.
OSP151304
SOILS LOG
meet
2 OF 3
CO --�7 1
SPECIAL PROVISIONS TO SPECIFICATIONS
1. ALL CONSTRUCTION SHALL BE INSTALLED AS SPECIFIED IN THE MOST CURRENT EDITION OF THE MUNICIPALITY OF
ANCHORAGE STANDARD SPECIFICATIONS (MASS) FOR COMPONENT PARTS AND MATERIALS USED IN CONSTRUCTION OF
ON–SITE WASTEWATER DISPOSAL SYSTEMS AND AND IN ACCORDANCE WITH AMC 15.65.
2. SCOPE OF WORK: INSTALL NEW 1 SOOg SEPTIC TANK, AND SOIL ABSORPTION SYSTEM.
GROUNDWATER WAS NOT ENCOUNTERED TO A DEPTH OF 19 FEET BELOW EXISTING GRADE AS EVIDENCED BY THE SOIL
TEST HOLE. IF AN APPARENT WATER TABLE IS OBSERVED IN ANY OF THE EXCAVATIONS LESS THAN 19 FEET BELOW
EXISTING GRADE NOTIFY THE ENGINEER IMMEDIATELY. - -
THE CONTRACTOR SHALL HAVE ANY LOT LINE ANT) WELL RADIUS SHOWN ON THE PLAN WITHIN 30 FEET OF THE
PROPOSED SYSTEM STAKED BY A REGISTERED LAND SURVEYOR BEFORE STARTING THE WORK.
THE CONTRACTOR IS RESPONSIBLE FOR ALL R.O.W. AND OTHER REQUIRED PERMITS, OTHER THAN THE ATTACHED.
THE CONTRACTOR SHALL CALL FOR LOCATING OF ALL BURIED UTILITIES. --
17. THE CONTRACTOR SHALL PROVIDE 24 HOUR NOTICE TO THE ENGINEER PRIOR TO START OF WORK. ALL SURVEYING
AND LOCATES SHALL BE IN PLACE PRIOR TO NOTIFYING THE ENGINEER.
I8. THE CONTRACTOR SHALL NOTIFY THE ENGINEER OF ANY DISCREPANCY BETWEEN THE APPROVED DRAWINGS AND SITE
CONDITIONS/LIMITATIONS POTENTIALLY CAUSING THE NEED TO MODIFY THE DESIGN.
I9. AT THE COMPLETION OF THE WORK, THE CONTRACTOR SHALL SUBMIT RED–LINE AS–BUILT DRAWINGS TO THE
ENGINEER. THE RED–LINES SHALL INCLUDE PIPE LENGTHS, ORIGINAL GROUND ELEVATIONS, PIPE ELEVATIONS, AND
TANK ELEVATIONS.
I10. THE CONTRACTOR SHALL SIGN THE FOLLOWING:
I CERTIFY THAT ALL WORK WAS PERFORMED IN ACCORDANCE WITH THE APPEND PERMIT, AND ANY AND ALL CHANGE
ORDERS, AND THAT THE AS–BUILT REDLINES ARE TRUE AND ACCURATE REPRESENTATION OF THE PROJECT AS
CONSTRUCTED.
CONTRACTOR:
BY: TITLE:
DATE:
DESIGN PARAMETERS
PRIMARY/RESERVE SEPTIC SYSTEM
NO. BEDROOM: 5 (750 gpd)
TANK SIZE: 15OOg
PERC RATE: 4.5 MPI
SOIL RATING: 1.2 GPD/SF
AREA ROD: 625 SF
SYS. TYPE: DEEP TRENCH 8.0'ED
MIN LENGTH: 39.1 LF
USE:
40LFx2.5'Wx8.0' E.D., 13.0' TD
TOTAL AREA: 640 SF
LEGEND
W WATER LINE/
WELL RADIUS
SS — NEW SEPTIC
ABBREVIATIONS
TH
TEST HOLE
LF
-LINEAR FEET
SF
SQUARE FEET
BR
BEDROOM
(P)
PROPOSED
(E)
. EXISTING
CO
CLEAN OUT N0.
MT
MONITOR TUBE NO.
TYP
TYPICAL
NOTES: PANNONE ENG SVC, LLC -� QF. A� `k1 U011/09/16
CHANGE ORDER P.O. BOX 102954 ANCHORAGE, AK 99510 r .qS 11
PHONE (907) 272-8218 FAX (907) 272-8211 A-C� �y+� Scale
NTS
...... .. . .. .. I P.I.D. NO
RAPTOR'S KNOLL, LOT 6 -1a -s3
RAPTOR PROPERTIES LLC �/ Steven 'R. Pannone PERMIT N0.
P.•, CE 8149 .'c�j OSP151304
RAPTOR'S KNOLL CIRCLE ci_r
SOILS LOG ANCHORAGE, AK 99516
Sheet
(,iIDPROFESSOFE IONA�
���3 OF 3
Municipality of Anchorage
Development Services Department
Building Safety Division
On -Site Water and Wastewater Program
4700 Elmore Road
P.O. Box 196650 Anchorage, AK 99507
/ www.ci.anchoraoe.ak.us
(907) 343-7904
Soils Log - Percolation Test
Performed For: Ray Hickel Date Perfc
Legal Description: Timber Trail Subdivision, Lot 6 Township, Range, Section:
Slope
TT—F—
Uepm
(Feet)
1-
�L
2-
3-
4-
5-
6-
-
3-4-
5-6-
9-
10-
11-
9 10-11-
I
1
15-
16-
17-
18-
19-'
5-16-
17-18-19-
WAS GROUND WATER jI
ENCOUNTERED?
IF YES, AT WHAT DEPTH? L
0
Depth to Water After P
Monitoring? (\€f.�c E
Date:
r 49?H :7`
".. •.•MICHAEI. E. A14DERSOPJ 2�
c+ ,
;rte•. CE -4381 :sem
��,�qF• �BlltiV ,.���•
Feb
Site Plan
Reading
Date
Gross Time
Net Time
Depth to Water
Net Drop
1-2
2/15/2013
�Z'`0 lI�I O�
( 0 fi lR i
�J.3&1 lA-
`t"•(g `r
3.4
13'�o9�i�i9
u
y,4�f�li.iz
3.�`�•`
5-6
.0(
7-6
9-10
iz.`SI I al
PI
11-12
PERCOLATION RATE (minutes mh) PERC HOLE DIAMETER e5 "
TEST RUN BETWEEN y.a FTAND�%T FT
.COMMENTS Perc Cavity was presoaked
PERFORMED BY: A. Harala I N!WJ a� CERTIFY THAT THIS TEST WAS
PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: f l)-1) • fY
Municipality of Anchorage
Development Services Department
Building Safety Division
y�r On -Site Water and Wastewater Program
4700 Elmore Road
P.O. Bax 196550 Anchorage, AK 99507
www.ci.anchoraoe.ak.us _
(907) 343-7904
Soils Log - Percolation Test
Performed For: Ray Hickel
Legal Description: Timber Trail Subdivision, Lot 6
r6r
CL�
10-
11-
l- 11 yGr
1
15- W
16- 1MVfit
17- i4ivy
18-
19 4 jrt-4
Date
Township, Range, Section:
non
WAS GROUND WATER
ENCOUNTERED?
S
IF YES, AT WHAT DEPTH? L
Depth to Water After P
Monitoring? Fv f4 c'e E
Date:
Reading
Date
Gross Time
Net Time
Depthto Water
Net Drop
1-2
2/15/2013
(3:�y�{�J'''%/
IO t i
5�g.-,"
�3.IV'
s -s
13'�I�lt3�S5"
`�
✓�,b3(r3.��
Z,a�-.,
7-8
it
tt
�e�'Ivtn
%ico
9-10
9-10
11-12 1ILO
14�31
PERCOLATION RATE A, (minoteshmh) PERC HOLE DIAMETER g's
TEST RUN BETWEEN 9-.'-i FT AND5;,9 FT
COMMENTS Perc Cavity was presoaked
PERFORMED BY: A. Harala I �iL� Z C�RTIFY THAT THIS TEST WAS
PERFORMED IN ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: fv -+ 7-J y'
L___.
MUNICIPALITY OF ANCHORAGE
Development Services Department M ; Phone: 907-343-7904
On -Site Water & Wastewater Section Fax: 907-343-7997
Parcel I.D.
017-101-63
Certificate of On -Site Systems Approval
1. GENERAL INFORMATION
Complete legal description
14092 RAPTORS KNOLL CIR, ANCH AK
Location (site address)
Expiration Date:. JU&I
RAPTORS KNOLL LT 6
Current property owner(s) SCOTT LINDSTROM
Mailing address SAME
Real estate agent
2. TYPE OF DWELLING:
F Single Family (w/wo ADU)
❑ Duplex
❑ Multiple Dwellings (Single Family and/or Duplex)
3. NUMBER OF BEDROOMS: 5
Day phone
Day phone
4. TYPE OF WATER SUPPLY:
TYPE OF WASTEWATER DISPOSAL:
Private Well[7
Private Septic
0
Water Storage
❑
Holding Tank
❑
Community Well
❑
Community
❑
Public Water System
❑
Public Sewer
❑
Waiver request for: Distance:
Received by: Date:
COSA to be released to the engineer, unless otherwise requested by the engineer.
COSA Fee $ J� 5� Waiver Fee $
Date of Payment `, [-2 Date of Payment
Receipt Number 03127- 16 Receipt Number
COSA A D AL2 I l l y'_� Waiver #
5. STATEMENT OF INSPECTION BY ENGINEER
As certified by my seal affixed hereto and as of the validation date shown below, i verify that my investigation, based
on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the
on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of
bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the
Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater
disposal system is (are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in
effect at the time of installation, I acknowledge that On -Site staff may visit the site to verify the information submitted.
Name of Firm MIKE N ANDERSON, P.E. Phone 727-8864
Address 4661 NATRONA AVE ANCH AK
Engineer's Printed Name MIKE N ANDERSON, P.E. Date 3-29-21
By: Original Certificate Date: y .
/�6'.'7 I
The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the
representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is
not responsible for errors or omissions in the professional engineer's work.
7. ATTACHMENTS:
COSA Checklist X Nitrate Advisory
Septic System Advisory Arsenic Advisory
Well Flow Advisory Other
COSA Checklist Olue sheet
•,
�
a... t' n
IRS <i '
, • �-��� O•��Y fir('
6. DSD SIGNATURE
}~ 4 �T�l ;
..:...
5
.:. ..........�r
`
�.
V/ System #1 Approved for
bedrooms • •, • • • . ........... .
! MICHAEL N. ANDfA,`,—N 0`—
System #2 Approved for
bedrooms �,� : •• C>_ 946 J
riA ♦ • e.
Disapproved
Conditional approval for
bedrooms, with the following stipu{-�,�,,�
lull(((((((((
'PV
v ON,g1TE �
=� WP�E. ,t PjER z
J 0GlK
cfi
By: Original Certificate Date: y .
/�6'.'7 I
The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the
representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is
not responsible for errors or omissions in the professional engineer's work.
7. ATTACHMENTS:
COSA Checklist X Nitrate Advisory
Septic System Advisory Arsenic Advisory
Well Flow Advisory Other
COSA Checklist Olue sheet
COSA Checklist
Legal Description: RAPTORS KNOLL LT 6
If more than 7 septic system on lot: COSA Checklist # of
A. WELL DATA
H Well log is filed with Onsite (or attached)
Date drilled 11/18/14
Total depth 204 ft
Cased to 204 ft
IN Sanitary seal is functioning correctly
M Wires are properly protected
Casing height (above ground) 18+ in.
Date of flow test for COSA 3/25/21
Static water level at beginning of test 145 ft.
Comments
B. TANK DATA
Age oftank(s) 2016 years
Tank type/material
Measured operating fluid level in septic tank 48„
H Standpipes/foundation cleanout per record drawing
Date of pumping "steel/septic, pump 3/25/21
D. ABSORPTION FIELD DATA
Which system tested (date installed) 2/5/16
M ALL standpipes present per record drawing
Total measured depth from grade 15.5 ft (max)
Measured depth to pipe invert from grade 7.5 ft (min)
❑ N/A —pressurized field
❑� Monitor tubes go to bottom of effective. If not, state
depth into effective
Parcel ID: 017-101-63
Structure served by this system _
Well production at time of test 5.5+ gpm
Water storage tank volume 0 gallons
Well disinfected for coliform test? ❑ Yes H No
X Coliform bacteria is Negative
Nitrate 2.2 mg/L ❑ Nitrate less than MRL (ND)
Arsenic ug/L N Arsenic less than MRL (ND)
Collected by MNA
Date of Sample 3/25/21
C. LIFT STATION
❑ Required maintenance completed
Age of lift station _ years
Lift station material
Comments:
Adequacy test date 3/25/21
Results Q✓ Pass For 5 bedrooms
Fluid depth prior to test 65 in
Water added 800 gal
New depth 70 in
Elapsed time 1440 min
H Code -required soil cover over field Final fluid depth 65 in
❑ System presoaked Absorption rate 750+ gpd
(Required if vacant for greater than 30 days prior to Any rejuvenation treatment (past 12 months)
date of test)
Gallons introduced 0 gallons If yes, enter date
Com ments/Deficiencies:
COSA Checklist yellow sheet
E. SEPARATION DISTANCES
From Private Well on Lot to: (Please enter distances if less than required or if community well)
Septic Tank/Lift Station on Lot > 100' Community Sewer Manhole/Cleanout > 100'
✓❑ Yes if No _ ft Q Yes if No _ ft
Neighboring Tank > 100' 0 Yes if No _ ft Private Sewer/Septic Line > 25' ❑� Yes if No _ ft
Absorption Field on Lot > 100' EJ Yes if No_ ft Holding Tank > 100' El Yes if No ft
Neighboring Absorption Fields > 100' Animal Containment > 50' Q Yes if No ft
[v Yes if No _ ft
Manure/Animal Excreta Storage > 100'
Community Sewer Main > 75' Yes f No _ ft ❑✓ Yes if No _ ft
From Septic/Holding Tank on Lot to: (Please enter distances if less than required)
Building Foundations > 10' Q✓ Yes if No _ ft Surface Water > 100' ❑✓ Yes if No ft
Property Line > 5'
Q
Yes
if No _ ft
Absorption Field > 5'
Q
Yes
if No ft
Water Main > 10'✓Q
✓❑
Yes
if No ft
Water Service Line > 10'
Q
Yes
if No ft
Wells on Adjacent Lots:
Private Wells > 100'
Community Wells > 200'
2✓ Yes if No _ ft
❑✓ Yes if No _ ft
If septic tank is under driveway comment below
From Absorption Field on Lot to: (Please enter distances if less than required)
Building Foundation > 10' Q✓ Yes if No_ ft If absorption field is under driveway comment below
Property Line > 10'
Water Main > 10'
Water Service Line > 10'
Surface Water > 100'
F. ENGINEER'S COMMENTS
0
Yes
if No _ ft
✓❑
Yes
if No ft
❑
Yes
if No ft
✓❑
Yes
if No ft
G. ENGINEER'S CERTIFICATION
Wells on Adjacent Lots:
Private Wells > 100'
Community Wells > 200'
/ certify that 1 have determined through field inspections and review
of Municipal records that the above systems are in conformance with
MOA COSA guidelines in effect on this date.
COSA Checklist yellow sheet
❑✓ Yes if No ft
❑� Yes if No ft
Parcel I.D. 017-101-63
1
Municipality of Anc
On -Site Water and Wastewater
(907)343-7904
Certificate of On -Site Systems
GENERAL INFORMATION
Complete legal description Raptors Knoll, Lot 6
Location (site address) 14092 Raptors Knoll Cir.
Spinell Homes Inc
01-1z1 1 01 (to
I ��+s
V111ift.
JUL 21 2016
Expiration Date: 1 ' rlB 1
Current Property owner(s)Day phone
Mailing address
Real Estate Agent
A
1900 W Northern Lights Blvd. 200 Anchorage, AK 99517
Day phone
2. TYPE OF DWELLING:
Il Single Family (w/wo ADU)
❑ Duplex
❑ Multiple Dwellings (Single Family and/or Duplex)
3. NUMBER OF BEDROOMS:
5
4. TYPE OF WATER SUPPLY:
TYPE OF WASTEWATER DISPOSAL:
Individual Well
it
Individual
El
Individual Water Storage
❑
Holding Tank
❑
Community Class Well
❑
Community
❑
Public Water System
❑
Public Sewer
❑
Waiver/Variance request
Received by: Date:
CCSA to bp, eased to the engineer, unless otherwise requested by the engineer. _
COSA Feb' $ 6q.10 Waiver Fee $
Date of Payment '�-f aal �� Date of Payment
Receipt Number C �S3J�� Receipt Number
COSA # O' GJ%��n f1 Waiver #
5. STATEMENT OF INSPECTION BY ENGINEERa
As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined
in the Certificate of On S' S�{s"tegfy Approval Guidelines for this application, shows that the on-site water supply and/or wastewater
disposal system is are �` "
p y ( ) '1{unctio I and adequate for the number of bedrooms and type of structure indicated herein. I further verify that
based on the information o ained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply
and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at
the time of installation.
In conducting an adequacy test I attem - provide a thorough, conscientious engineering analysis of the system in accord ' h MoA Co'
guidelines and regulatioggsThe,.re Its describe the performance of the system under the conditions encountered a test,
and separation distances srri'red"to readily identifable features. The operational life of all wells and septic systems depe" I'
condition, ground water levels that may fluctuate during the year, and the water usage of the family being -served by the system. Th fy` . �.*.
are outside the control of the evaluator of this system. All systems eventually fail and satisfactory test results do not guarantee"fu
performance of the system, nor do they guarantee that there are no hidden defects or encroachments. Therefore we cannot provide any warran ._1,
for future performance, nor can we estimate remaining life of the system. The content of this report is for the sole benefit of the owner listed
above.
Name of Firm Pannone Engineering Services LLC
Address P.O. Box 100217, Anchorage Ak. 99510
Engineer's Printed Name Steven R Pannone"
6. DSD SIGNATURE
_) System #1 Approved for bedrooms
System #2 Approved for bedrooms
Disapproved
Phone (907) 272-8218
Date 7/21/2016
_z
�P��ALgS,�q��
*: qg 'rH * /
E -819°n ��
Conditional approval for bedrooms, with the following stipulations:
Original Certificate Date:T-I d -i(0—
The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA)-based only
upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality
of Anchorage is not responsible for errors or omissions in the professional engineer's work.
7. ATTACHMENTS:
COSA Checklist X
Septic System Advisory
Well Flow Advisory
COSA blue sheet ° :.t c
Nitrate Advisory
Arsenic Advisory
Other
If more.than 1 septic system is on the lot:
COSA Checklist # + of
Structure served by this system i
Certificate of On -Site Systems Approval Checklist
Legal Description Raptors Knoll, Lot 6 parcel ID: 017-101-63
A. WELL DATA
Well type Private If A, B, or C provide PWSID #
Well Log (Y/N) Y
Date completed 11/18/2014 Sanitary seal (Y/N) Y
Wires properly protected (Y/N). Y
Total depth 204 ft. Cased to 204 ft.
Casing height (above ground) .18} in.
FROM WELL LOG
AT INSPECTION
Date of test 11/1812014
New
Static water level 145 ft
New ft
Well production 15+ g.p.m.
New 9 -
p.m -WATER SAMPLE RESULTS:
Coliform Neg eolonies1100 mL Nitrate 1.30' mg/L
Arsenic ND ug/L Date of sample: 6/29/2016
Collected by: PES
B. SEPTICIHOLDING TANK DATA
Tank Type/Materiaf Septic/Steel
Date installed 2/5/2016
Tank size 1,500 gal. Number of Compartments 2
Cleanouts (Y/N) Y
Foundation;cleanout (YIN) Y Depression over tank (YIN) N
High water alarm (YIN) N
Date of pumping NeW Pumper N/A
C. ABSORPTION MELD DATA
2/5/2016 z z 1.2 GPD/SF Deep Trench
Date installed Soil rating (g.p.d./ft or ft /bdrm) System type
Length 40 ft. Width 2.5 ft. Gravel below pipe.8 ft.
Total depth 1 ��-fl. c Eff. absorption area 640 ff2 Monitoring tube Y Depression over field N
Date ofadequacy4test-,_New Results(Pass/Fail) PASS For S bedrooms
Fluid depth in absorption field before test New in. Water added -New
gal. New depth NeW in.
Elapsed Time: New min. Final fluid depth New in. Absorption rate >= 750+ g;p,d.
Any rejuvenation treatment (past 12 mo.) (Y/N & type) NO if yes, give date
111
D. LIFT STATIQU
Date installed Size in gallons_
"Pump on" level at in: "Pump off' level at
_Datum Cycles tested
Manhole/Access (YIN)
in. High water alarm level at
Meets alarm.& circuit requirements?
E. SEPARAfbNDISTANCES r
WELL ON LOT TO:
Septic tank/lift station on lot 100+ On adjacent lots 1004-
Absorption
00+Absorption field on lot 100+ On adjacent lots 100+
Public sewer main 75+ Public sewer manhole/cleanout 1004-
Sewer
00+Sewer /septic service line 25+ Holding tank 100+
Animal containment areas 50+ Manure/animal excrete storage areas 100+
SEPTIC/HOLDING TANK ON LOT TO:
Building foundation 5+ Property line 5+ Absorption field 5+
Water main 10+ Water service line 10+ Surface water 100+
Wells on adjacent lots 100+
ABSORPTION FIELD ON LOT TO:
Property line 10+
Building foundation 10+ Water main
Water Service line 10+ ` = Surface water 100+ Driveway, parking/vehicle storage �}
Curtain drain 50+ Wells on adjacent lots 100+
F. COMMENTS
G. ENGINEER'S CERTIFICATION
1 certify that i have determined through field inspections and
review of Municipal records that the above systems are in
conformance with MOA COSA guidelines in effect on this date.
Engineer's Printed Name, Steven Peinnone
Date , 7/21/2016
COSAcanary sheet 2.6-15.doc
A 2016-030446-0
S
K Recording District 301 Anchorage
A 07/28/2016 83:10 PM Page 1 of 4
II IMINIBIIIINIINNIIIlNINlININNIIIINNNIIIIIINIIII�I(IIIINIIIlII�! IN
1203-34A
Grid 3037
EN16019
017-101-63-000
ENCROACHMENT PERMIT
This permit is between Chugach Electric Association, Inc., an Alaska non-profit electric cooperative,
(herein "Chugach', whose address is P. O. Box 196300, Anchorage, Alaska 99519 and Spinell
Homes, Inc., (herein "Permittee"), whose address is 1900 W. Northern Lights Boulevard, Suite 200,
Anchorage, Alaska 99517.
I. Easement. Chugach is the grantee or user of an easement for the construction and
maintenance of electrical facilities, as follows:
Described in that certain written instrument recorded on the 20 day of June 1957, at Book
E2, Page 319, on file in the office of the District Recorder, Anchorage Recording District,
Seward Meridian, Alaska,
Described in that certain written instrument recorded on the 23'a day of October 2014, at
Serial Number 2014-043192-0, on file in the office of the District Recorder, Anchorage
Recording District, Seward Meridian, Alaska,
(herein "Easement") which pertains to the following described real property:
The Easterly Ten Feet (E'ly 10') of Lot Six (6), Raptors Knoll Subdivision, according to
Plat Number 2014-128, filed on the 15th day of December 2014, on file in the office of the
District Recorder, Anchorage Recording District, Seward Meridian, Alaska.
Permittee acknowledges the validity of the Easement. Permittee wan -ants and represents that
Permittee is the owner of the fee simple interest in the land subject to the Easement and the
following described real property to which the Easement is adjacent:
Lot Six (6), Raptors Knoll Subdivision, according to Plat Number 2014-128, filed on the
15'i day of December 2014, on file in the office of the District Recorder, Anchorage
Recording District, Seward Meridian, Alaska,
(herein "Parcel').
Encroachment Permit - Page I of 4
2. Encroachment. Permittee has constructed or purchased the following improvements
on or within the real property subject to said Easement:
A well that encroaches approximately Six Feet into the northern side of said Easement
for a distance of approximately One Foot (1'),
(herein "Encroachment").
3. Permit Chugach hereby authorizes Permittee to continue the existence of the
Encroachment in its existing location subject to the covenants set forth in this permit.
4. Indemnification. Permittee shall indemnify and hold Chugach harmless from any
claims for personal injury, property damage or other loss arising in anyway from the continuation of
the Encroachment.
5. No Expansion or Increase. Permittee shall not in any way expand or increase the
extent to which the Encroachment occupies any of the real property encumbered by the Easement
without the prior written consent of Chugach. Chugach has no obligation to provide such consent.
6. No Interest in Real Estate Acquired. Permittee hereby acknowledges that the
Encroachment and any additions thereto, even if in violation of this permit, has not and shall not in
the future give rise to any interest or estate in the real property subject to the Easement or any other
real property. Without in any way limiting the foregoing, Permittee acknowledges that the
Encroachment is not adverse to any interest of Chugach and its continuation is entirely with the
permission of Chugach forpuiposes of the common law doctrine of adverse possession. Thispermit
creates no interest in the real property subject to the easement.
7. Modification of Utility Facilities. If the electric utility facilities located within the
Easement are upgraded, added to, replaced or reconstructed, Permittee shall pay that portion of
Chugach's total costs for such modification which is reasonably attributable to accommodating or
preserving the Encroachment. If such payment is not made within thirty (30) days ofwritten demand
for same, Chugach may terminate this permit in accordance with paragraph 9, below.
8. Covenants Running with the Land. The obligations of the Permittee arising from this
permit shall be covenants running with the land which shall burden the Parcel and the Permittee's
interest in the land subject to the Easement and shall benefit the Easement.
9. Termination. Chugach may terminate this permit after the giving of thirty (30) days
written notice of such termination if
a. The Encroachment is enlarged, increased or extended within the real property
affected by the Easement.
Encroachment Permit - Page 2 of 4
Page2 of 4
20]6-030446-0
b. The Encroachment is damaged by any means to an extent ofmore than thirty percent
(30%) of its replacement cost at the time of destruction.
c. Permittee fails to make the payment described in paragraph 7, above.
10. Term. This permit shall, if not sooner terminated by Chugach, expire forty (40) years
from the date hereof.
11. Entire Agreement. This written permit constitutes the entire agreement between the
parties with respect to the subject matter hereof and supersedes all other prior or contemporaneous
agreements, oral or written, between the parties. No modifications, amendments, deletions, additions
or alterations of the permit shall be effective unless in writing anc sipgd by all of the parties hereto.
CHUGACH ELECTRIC ASSOCIATION, INC.
13y: 1i� M W
Shelly Schmitt, S or Manager
Distribution Engineering
Date: 14,
Andre C. Spinelli, Authorized Agent
Spinell Homes, Inc.
Date: 7' Z7— 1
Encroachment Permit - Page 3 of 4
Page 3 of 4
2016-030446-0
STATE OF ALASKA )
) ss:
THIRD JUDICIAL DISTRICT )
The foregoing instrument was acknowledged before me this 27+l� day of
2016, by A,dre C'. &'ife//f'
(P ME(S) OF PERSON(S) SIGNING DOCUMENT)
NCT,ARY�N = ��• +�
PUBLIC/
�,qJe ary P c m and for the State of Alaska
7LPF'pVP`' My Commission expires: 0/-p
STATE OF ALASKA )
) as:
THIRD JUDICIAL DISTRICT )
The fore oing instrument was acknowledged before me this 2y day of
,2016,by LAA f- 5'c,4mj7j
Senior Manager, Distribution Engineering of Chugach Electric Association, Inc.,
an Alaska corporation, on behalf of the corporation.
AFTER RECORDING RETURN TO:
Chugach Electric Association, Ine.
P.O. Box 196300
Anchorage, Alaska 99519-6300
Attn: Land Services Department
p
NotaryPubli n and for the State of Alaska
My commission expires: 0/-o /-2d r 8
Encroachment Permit - Page 4 of 4
Pape 4 of 4
20'16-030446-0
RAPTORS KNOLL SUBDIVISION
CiHUCp/G�rI7 LOT 6
POW MIG AIASKA� RRURE MAP: 1203-34A
Chugach Electric Association, Ina GRID: 3037
EN16019
PLAT NO. 2014-28
RAPTORS KNOLL SUBDIVISION
LOT 6
51,421 S.F.
GASTALDI LAND
SURVEYING, LLC
JEFF A. GASTALDI, R.LS.
2000 E. DOWUNG RD., SUITE 8
ANCHORAGE, ALASKA 99507
PHONE 248-5454 '
GRID
SW303Y
15-05
DATE
3/11/2016
JOB NO.
I HEREBY CERTIFY THAT I HAVE SURVEYED THE
PROPERTY DEPICTED ABOVE AND THAT NO
ENCROACHMENTS EXIST EXCEPT AS INDICATED.
TT IS THE RESPONSIBILITY OF THE OWNER TO
DETERMINE THE EXISTENCE OF ANY EASEMENTS,
COVENANTS OR RESTRICTIONS WHICH DO NOT
APPEAR ON THE RECORDED SUBDIVISION PLAT.
UNDER NO CIRCUMSTANCES SHOULD ANY DATA
HEREON BE USED FOR CONSTRUCTION OR FOR
ESTABLISHING BOUNDARY OR FENCE LINES.
ANCHORAGE RECORDING DISTRICT, ALASKA
NOTE: 'NO CORNERS SET THIS DATE
,**t\MV,♦
OF"'aL
sAir
� o
49TH ;
�t
Jeffery A. Gostoldl ;
LS -6091 : 1`
•`� rOfeselonall'e
1 "=40'
Ecklund, Timothy J
From: Luis <luis@spinellhomes.com>
Sent: Wednesday, August 10, 2016 2:10 PM
To: Ecklund, Timothy J
Subject: Fwd: Lot 6 Raptors Knoll
Sent from my iPhone
Begin forwarded message:
From: "Kohlhase, Kent E." <KohlhaseKE@ci.anchorage.ak.us>
Date: August 10, 2016 at 1:29:00 PM AKDT
To:'Andre Spinelli' <andre@spinellhomes.com>
Cc: Mike Anderson <andengr@gci.net>, Ray <srhickel@gci.net>, "'Jeff Gastaldi (igastaldi@Rci.net)"'
<igastaldi@gci.net>, "scopepne.ron@gmail.com" <scopepne.ron@gmail.com>, Lauren Spinelli
<lauren@spinellhomes.com>, "Luis Garcia" <luis@spinellhomes.com>, "Frost, Jack L."
<FrostJL@ci.anchorage.ak.us>, "Snelson, John W." <SnelsonJW@ci.anchorage.ak.us>, "McGee, Lynn M."
<McGeeLM@ci.anchorage.ak.us>, "Stuller, Gretchen J." <StullerGJ@ci.anchorage.ak.us>
Subject: RE: Lot 6 Raptors Knoll
Andre,
ROW will issue the encroachment permit for this well.
I don't have the permit number for the home construction, but if all permit requirements have been
met, you should be able to get a CCO, if not a full CO. Please work with the permit counter to get your
CCO.
Let me know if you have any questions.
Thanks-
Kent
hanks-
Kent
Kent Kohlhase, P. E.
Project Management & Engineering
Municipality of Anchorage
(907) 343-8159
From: Andre Spinelli Imailto:andre@spinellhomes.coml
Sent: Tuesday, August 9, 2016 4:07 PM
To: Kohlhase, Kent E. <KohlhaseKE@ci.anchorage.ak.us>
Cc: Mike Anderson <andengr@Rci.net>; Ray <srhickel@gci.net>;'Jeff Gastaldi (jgastaldi@gci.net)'
<Igastaldi@gci.net>; scopepne.ron@Rmail.com; Lauren Spinelli <lauren@spinellhomes.com>; Luis
Garcia <luis@spinellhomes.com>