HomeMy WebLinkAboutMOUNTAIN VALLEY ESTATES #1 BLK 5 LT 9Mountain
Valley Est. #1
Block 5
Lot 9
#050 - 661 - 12
MUNICIPALITY OF ANCHORAGE
On -Site Water & Wastewater Program
PO Box 196650 4700 Elmore Road
Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997
http://www.muni.org/onsite
On -Site Wastewater Disposal System Permit
Permit Number: OSP211416
Work Type: Septic Renewal
Effective Date:
Expiration Date:
Tax Code Number: 05066112000
Site Legal Address: MOUNTAIN VALLEY ESTATES #1 BILK 5 LT 9 G:0758
Site Mailing Address: 3750 BIRDSONG DR, Eagle River
Owner: HAYNES CLAUDINE &
Design Engineer: FORGE ENGINEERING
This permit is for the construction of:
Q Disposal Field Q Septic Tank ❑ Holding Tank ❑ Privy
9/27/2021
9/27/2022
Lot Size in Sq Ft: 78465
Total Bedrooms: 3
❑ Private Well ❑ Water Storage
All construction shall be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80)
3. The wastewater code requires inspections during the installation. The engineer shall notify the Development
Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
shall be either:
a. Opened and Closed on the same day, or
b. Covered, sealed, and heated to prevent freezing
i. Special Provisions:
1. The Engineer isrequired to do an additional percolation test prior to construction of theseptic field. Please
submit stamped andsigned results with the As -built Inspection Report. If the results require a design
change, constructionof the system will stop pending On -Site review and approval.
2. The cover per the design is to be in place prior to Inspection Report approval.
727,3 C hang e. I o co- atn -to allow 57-o v q,rotVr'� S l ocv,
Veronica Pope
2021.09.27
Received By:*'kl� 15:38:11 -08'00'
Issued By:
Date:
Date: 27 Z
MUHMPA UY 7 OF HCHOR �\ G
Community Development Department Phone: 907-343-7904
Development Services Division Fax: 907-343-7997
On -Site Water & Wastewater Program
ON-SITE SEWER/WELL PERMIT APPLICATION
Parcel I.D. 050-661-12
Property owner(s) Claudine Haynes & Carolyn Hackett Day phone 232-0128
Mailing address 205 E. Dimond Blvd., #275 Anchorage, AK 99515
Site address 3750 Birdsong Drive Eagle River, AK
Legal description (Sub'd., Block & Lot) Mountain Valley Estates #1, Block 5, Lot 9
Legal description (Township, Range & Section)
Lot Size 78,465 Sq. Ft. Number of Bedrooms Three (3)
APPLICATION IS FOR:
APPLICATION IS AN:
TYPE OF DWELLING:
(® all that apply)
Absorption Field
®
Initial ❑
Single Family (SF) ❑X
Septic Tank
❑X
Upgrade ❑X
(w/wo AD U)
Holding Tank
❑
Renewal FX]Duplex
(D) ❑
Privy
❑
Multiple Dwellings ❑
(SF and/or D)
Private Well
❑
Water Storage
❑
THIS APPLICATION
INCLUDES A VARIANCE / WAIVER REQUEST FOR:
Distance:
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
(5lgnature of property owner or authorized agent)
Permit/Rush Fees: 1 / q.6- Waiver Fees:
Date of Payment:
Receipt Number:
Permit No. 0--/p 2 I y h
Permit App_':- : :'-.,'c
Date of Payment:
Receipt Number:
Waiver No.
C o -�Z
ENGIN E E R I NG
PO BOX 240773
ANCHORAGE, AK 99524
522-7773 677-7766 (FAX)
August 12, 2021
MOA Development Services Dept, On -Site Water & Wastewater Program
4700 Elmore Rd
Anchorage, AK 99507
Subject: Mountain Valley Estates 41, Block 5, Lot 9 — 3750 Birdsong Drive
Septic Permit Change Order
Dear On -Site Services Engineer:
We originally submitted an application for a trench extension to upgrade the existing system to a
3 -bedroom septic, but found groundwater at a shallower depth than anticipated. We are now
proposing a whole new trench in a new location with a 1'250 -gallon lift station.
The ground surface on the lot is at or greater than 25% in the area of the proposed absorption
trench. Attached is a slope cross section showing the worst-case effluent travel for steep slope
encroachment justification. Slopes greater than 46% are found within 100' of the absorption
trenches, but no daylighting of effluent is probable. The underlying soils in the area absorb water
at rates between 4 and 5 minutes per inch. No migration of effluent is expected other than
downward. The proposed design meets all MOA steep slope requirements as stated in AMC
15.65.210.13.4. Ground surface contours are shown on the site plan indicating the grade and
direction of flow. Storm water drainage will not affect this septic system. The trench will be
constructed parallel to the slope as much as possible.
Wells on this and adjacent lots are shown. The new system will be a minimum of 100' from all
wells and surface water, and more than 5' away from the septic tank.
Please refer to the attached test hole log and plan and profile sheets for the septic design. If this
design is followed, there will be no adverse impacts to adjacent properties.
Sincerely,
Michael E. Anderson, PE
a
MOUNTAIN VALLEY ESTATES SUB #1, BLOCK 5 LOT 9
71
I / EXISTING WEIL I I \
I ,
\ LOT 8
ALTERNATE SITE: CAT I I SYSTEM I I '
15' LONG x 5'\WIDE X 0.5' E�FECTIVE �� LIMITS OF FILL I I 1
DEPTH ABSORPTION'TREN � H, APP \ I
�TE 6.6
\ 76'LONG x5' WIDE x 0.5� s ( l
\ \ \1 EFFECTIVE DEPTH
\ \ \ 1ABSOgPTIO I TRENCH LOT 9-/
EXCXVATMATERIAL F�OM E)ISTING T 2
I TRENH & REBUILD w/ MOP SAND r /
LOT\ 14 I , ( I I i l� 1 0 MT \ ` I EXISTING TANK
\TO'RE�MAIN IC ... I� // %
/ SERVICE.
1 1 NOTE: DO, NOT
1 ' I EXCEED 3' TOTAL 1 I 2-BDRM"HOME
1 I I DEPTH FROM 1 ` j/ / IIEXISTING INDOOR
I HIGHEST ;ORIGINAL I ( I i' GRI<JDER PUMP
I (
GRADE w/ TRENCH I A�
I II } } I GARAGE Irv/
I I I BATYROOMI
EXISTING WELL��
I LI
OT 13
I I I I r LQ'r
i WELL 416
V- EX��NIERING \I t OTE:i
NO SURFACE WATER WITHIN 100' OF THE PROPOSED SEPTIC LEGEND
SYSTEM.
CO - CLEANOUT
ALL WELLS ON SURROUNDING LOTS WITH IMPACTS TO THIS 2CO - DOUBLE CLEANOUT
PROPERTY ARE SHOWN. NO CONFLICTS WITH WELLS OR SEPTIC FCO - FOUNDATION CLEANOUT
SYSTEMS. FS - FLOW SPLITTER VALVE
0 50 100 MH - MANHOLE
FEET MT - MONITORING TUBE
SV - SEPTIC VENT
1 "=50' TH - TEST HOLE
MOUNTAIN VALLEY ESTATES SUB #1, BLOCK 5 LOT 9
DESIGN FACTORS:
450 GPD PEAK FLOW
PERK RATE: 4.8 MIN/IN
APPLICATION RATE: 1.2 GPD/SF
SYSTEM REQUIREMENTS:
SHALLOW TRENCH SYSTEM
NEW 1,250 GALLON STEP TANK
450 GPD / 1.2 GPD/SF /5' WIDE * 1.0 RED. FACTOR = 75 LF TRENCH REQUIRED (75 LF SPECIFIED)
BOTTOM OF TRENCH: 3.0' BELOW GRADE @ HIGHEST POINT
FLOW LINE ELEVATION: 2'6" BELOW GRADE @ HIGHEST POINT
TOP OF TRENCH: 6" ABOVE GRADE @ HIGHEST POINT
2:1
1
APPLY JUTE MESH OR
EQUIVALENT & VEGETATE FILL
SLOPE FOR STABILIZATION
�! ir0.1 51
2" INSULATION
2'
1.25" PVC w/30 - is" HOLES
SPACED EVENLY (HOLES DOWN)
DRAINFIELD ROCK
TYPICAL TRENCH SECTION
(NO SCALE)
NOTES:
1. GRADE AREA OVER TRENCH TO DRAIN AWAY
2. PROVIDE 3' OF COVER OVER TRENCHES AND 4' OVER SEPTIC TANK, OR 2'
WITH 2" OF INSULATION
3. CHECK GROUNDWATER AT TIME OF CONSTRUCTION. IF LEVEL IS HIGHER
THAN PREVIOUSLY OBSERVED, CALL ENGINEER IMMEDIATELY
> AGE
E N G 1 N E E R I N G
49th •�°.�
MICHAEL E. ANDERSON f a
No. CE -4381 2 0
; *-4ep:embe, 14,' 0?1.1%�-
0 pROFES51Cto-
/ 'w
RA
z
W
d = w M
�
., rn, a Z
�� l d e v
�
r O:
_.
:
_.... ...... ..
._.. ._...___-._..._
�. .:Eb
ire
00
L
�^ Cp
U
0
m
_
w
- w
tCD
_
U
o
_
W
LO
��2.. _.
- Ln
VJ
W
f—
- -
C)
M
LijN
—
Q
W
II
CD
W
o1
C9
U)
-----
N
Jz
o
-
Q
oaLO
z,
a .0 w
cr
IL
z
«
L
75w
r
w
I
0
i
O LCA O.
_z , O LO ..�.
—
_LO CD
z
DEPTH
(feet)
1 -
SOILS LOG AND PERCOLATION TEST
LEGAL DESCRIPTION: MOUNTAIN VALLEY ESTATES #I, BLOCK 5, LOT 9
PERFORMED FOR: .JOHN STEWART
DATE: 7/7/21 PROJECT No.:
PARCELID#: 050-661-12 TECHNICIAN: J. MILLETTE
TEST HOLE 1
RE60-
2 ..r
3
4 SILTY GRAVEL W SAND
5 GM
6
7
8 j
10
11
12
13
14
15
16
17
1&
1
COMMENTS:
SLOPE
WAS GROUND WATER ENCOUNTERED2 YES
IF YES @ WHAT DEPTH? 9.5' L
DEPTH OF WATER AFTER MONITORING: 9.5 0
DATE OF MONITORING: 7/15/21 P
E
SITE PLAN
SEE SITE PLAN
GROSS TIME NET TIME DEPTH TO NET DROP
DATE READING WATER
(MINUTES) (MINUTES) (INCHES) (INCHES)
TEST HOLE PRESOAKED PRIOR TO TESTING:
PERCOLATION RATE: (MIN/INCH) PERC. HOLE DIA. (INCHES)
TEST RUN BETWEEN: FT. and FT.
DEPTH
(feet)
1-
2-
3-
4-
5-
6-
7
8
9
10
11
12
13
14
15
16
17
18
19
20
SOILS LOG AND PERCOLATION TEST
E N G I N E E R I N G
LEGAL DESCRIPTION: MOUNTAIN VALLEY ESTATES #I, BLOCK 5, LOT 9
PERFORMED FOR: JOHN STEWART
DATE: 7/7/21 PROJECT No.:
PARCELID#: 050-661-12 TECHNICIAN: J. MILLETTE
TEST HOLE 2
•C
SILTY GRAVEL W SAND
GM
SLOPE
3 .' 6- : a I WAS GROUND WATER ENCOUNTERED? YES
COMMENTS:
SITE PLAN
SEE SITE PLAN
IF YES tJ WHAT DEPTH?
9.5
DEPTH OF WATER AFTER MONITORING:
9.5'
L
0
DATE OF MONITORING:
7/15/21
P
GROSS TIME NET TIME DEPTH TO NET DROP
DATE READING (MINUTES) (MINUTES) WATER (INCHES)
(INCHES)
TEST HOLE PRESOAKED PRIOR TO TESTING:
PERCOLATION RATE: (MIN/INCH) PERC. HOLE DIA. (INCHES)
TEST RUN BETWEEN: FT. and FT.
MUNICIPALITY OF ANCHORAGE
On -Site Water & Wastewater Program
PO Box 196650 4700 Elmore Road
Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997
http://www.muni.org/onsite
On -Site Wastewater Disposal System Permit
Permit Number: OSP201321
Work Type: Septic Renewal
Effective Date:
Expiration Date:
Tax Code Number: 05066112000
Site Legal Address: MOUNTAIN VALLEY ESTATES #1 BLK 5 LT 9 G:0758
Site Mailing Address: 3748 BIRDSONG DR, APT, Eagle River
Owner: HAYNES CLAUDINE &
Design Engineer: FORGE ENGINEERING
This permit is for the construction of:
Q Disposal Field Septic Tank Holding Tank Privy
l»enr
oIs,
llepartment
8/25/2020
8/25/2021
Lot Size in Sq Ft: 78465
Total Bedrooms: 3
Private Well Water Storage
All construction shall be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80)
3. The wastewater code requires inspections during the installation. The engineer shall notify the Development
Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
shall be either:
a. Opened and Closed on the same day, or
b. Covered, sealed, and heated to prevent freezing
Special Provisions:
CO#1 moved the grinder pump outside the well radius.
Received By: Date:
Issued By: Date g2.6Z0
8/26/20
Community Development Department Phone: 907-343-7904
Development Services Division Fax: 907-343-7997
On -Site Water & Wastewater Program
ON-SITE SEWER/WELL PERMIT APPLICATION
Parcel I.D. 050-661-12
Property owner(s) Claudine Haynes & Carolyn Hackett Day phone 232-0128
Mailinq address 205 E. Dimond Blvd., #275 Anchorage, AK 99515
Site address 3750 Birdsong Drive Eagle River, AK
Legal description (Sub'd., Block & Lot) Mountain Valley Estates #1, Block 5, Lot 9
Legal description (Township, Range & Section)
Lot Size 78,465 Sq. Ft. Number of Bedrooms Three (3)
APPLICATION IS FOR:
APPLICATION IS AN:
TYPE OF DWELLING:
(® all that apply)
Absorption Field
❑X
Initial ❑
Single Family (SF)
❑X
(w/wo ADU)
Septic Tank
ElUpgrade
FR
Duplex
❑
(D)
Holding Tank
ElRenewal
❑X
Multiple Dwellings
❑
Privy
❑
(SF and/or D)
Private Well
❑
Water Storage
❑
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
Distance:
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit/Rush Fees: 4 10 8. q 5
Date of Payment: a! 181.2 0.2, 0
Receipt Number: 09 2 I % )�N
Permit No. 0,5P201 3 2 1
Permit App_:- : . -..:c
Waiver Fees:
Date of Payment:
Receipt Number:
Waiver No.
PO BOX 240773
ANCHORAGE, AK 99524
522-7773 677-7766 (FAX)
August 14, 2020
MOA Development Services Department
On-Site Water & Wastewater Program
4700 Elmore Road
Anchorage, AK 99507
Subject: Mountain Valley Estates #1, Block 5, Lot 9 – NHN S. Birchwood Loop
Septic System Design – Permit Renewal – Permit No. OSP191259
Dear On-Site Services Engineer:
The Septic system upgrade permit for this lot was issued on July 8, 2019. It has now expired. All
aspects of the original design remain as submitted and approved. No revisions to the surrounding
lots have occurred. We request the permit be renewed for the upgrade of the septic system on the
lot to serve a three-bedroom home.
Please refer to the attached test hole log and plan and profile sheets for the septic design. If this
design is followed, there will be no adverse impacts to adjacent properties.
Sincerely,
Michael E. Anderson, PE
8/14/20
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP201321, Deb Wockenfuss, 08/25/20
MUNICIPALITY OF ANCHORAGE
On -Site Water & Wastewater Program
PO Box 196650 4700 Elmore Road
Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997
http://www.muni.org/onsits
On -Site Wastewater Disposal System Permit
Permit Number: OSP191259
Work Type: Septic Upgrade
Tax Code Number: 05066112000
Effective Date
Expiration Date:
Site Legal Address: MOUNTAIN VALLEY ESTATES #1 BLK 5 LT 9 G:0758
Site Mailing Address: 3748 BIRDSONG DR, APT, Eagle River
Owner: HAYNES CLAUDINE &
Design Engineer: FORGE ENGINEERING
This permit is for the construction of:
0 Disposal Field ❑ Septic Tank ❑ Holding Tank ❑ Privy
`�--r.a
r..
c.
1)e pa rtrneat
7/8/2019
7/7/2020
Lot Size in Sq Ft: 78465
Total Bedrooms: 3
❑ Private Well ❑ Water Storage
All construction shall be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80)
3. The wastewater code requires inspections during the installation. The engineer shall notify the Development
Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
shall be either:
a. Opened and Closed on the same day, or
b. Covered, sealed, and heated to prevent freezing
Received By: r1lJ Date: Lq L
Issued By: Date: % %
MUNICIPALITY OF ANCHORAGE
Community Development Department Phone: 907-343-7904
Development Services Division Fax: 907-343-7997
On -Site Water & Wastewater Program
ON-SITE SEWER/WELL PERMIT APPLICATION
Parcel I.D. 050-661-12
Property owner(s) Claudine Haynes & Carolyn Hackett Day phone 232-0128
Mailing address 205 E. Dimond Blvd., #275 Anchorage, AK 99515
Site address 3750 Birdsong Drive Eagle River, AK
Legal description (Sub'd., Block & Lot) Mountain Valley Estates #1, Block 5, Lot 9
Legal description (Township, Range & Section)
Lot Size 78,465 Sq. Ft. Number of Bedrooms Three (3)
APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING:
(® all that apply)
Absorption Field ❑X Initial
❑ Single Family (SF) ❑X
(w/wo ADU)
Septic Tank ElUpgrade
NDuplex ❑
(D)
Holding Tank F-1Renewal
❑
Multiple Dwellings ❑
Privy ❑
(SF and/or D)
Private Well ❑
Water Storage ❑
THIS APPLICATION INCLUDES A VARIANCE /
WAIVER REQUEST FOR:
Distance:
I certify that the above information is correct. I further
certify that this is in accordance with
applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit/Rush Fees: t'5gsoo
Waiver Fees:
Date of Payment: (0/2,501 Ll
Date of Payment:
Receipt Number: 5 LQ �t�/
Receipt Number:
p
Permit No. 0S IOI l I o� S�
Waiver No.
Am
Permit App_'-'-:- .. -,:crID 14 VL
PO BOX 240773
ANCHORAGE, AK 99524
522-7773 677-7766 (FAX)
June 25, 2019
MOA Development Services Dept, On-Site Water & Wastewater Program
4700 Elmore Rd
Anchorage, AK 99507
Subject: Mountain Valley Estates #1, Block 5, Lot 9 – NHN S. Birchwood Loop
Septic System Design
Dear On-Site Services Engineer:
The owner of the above lot intends to upgrade the current home on the lot to three bedrooms. We
are submitting this permit application for the extension of the existing absorption trench to
accommodate three bedrooms. The existing septic tank, placed in 2016 is sufficiently sized for
the upgrade. The attached site plan identifies the location of the home and existing well, septic
location and alternate site. No conflicts exist between this proposed system and any other well or
septic system on this lot or adjacent lots.
The ground surface on the lot is at or greater than 25% in the area of the proposed absorption
trenches. The trench is designed to comply with all requirements of the steep slope provision of
the ordinance in that the distribution line if 4.5’ below the surface and natural vegetation down
slope will not be disturbed. Slopes greater than 46% are found within 100’ of the absorption
trenches, but no daylighting of effluent is probable. The Underlying soils in the area absorb
water at rates between 4 and 5 minutes per inch. No migration of effluent is expected other than
downward. Ground surface contours are shown on the site plan indicating the grade and
direction of flow. Storm water drainage will not affect this septic system. The extension to the
existing trench will be constructed parallel to the slope as much as possible.
Wells on this and adjacent lots are shown. The new system will be a minimum of 100’ from all
wells and surface water, and more than 5’ away from the septic tank.
Please refer to the attached test hole log and plan and profile sheets for the septic design. If this
design is followed, there will be no adverse impacts to adjacent properties.
Sincerely,
Michael E. Anderson, PE
6/25/19
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP191259, Rebecca Carroll, 07/08/19
Ort- ' e� er Wastewater
MOUNTAIN VALLEY ESTATES #1, BLOCK 5�FbR9DECOMPLIAN
OSP201321, Deb Mckenfuss, 0812
I C O�II
I I / LOT 8 \
\ 11 \ EX STING WELL
TRI I I
EXTEND EX',STING EN�H 13' \ I I I ►
LONG x 5' WIbE x 4' FFECT�VE \ I J
I D PTH. !RrMOV EXISTNG
CLEACLIT A D CONECT O \ ► 1 I I
PIS\BUTI!D\LINE\co
I I I I
1 �T• / OT -/
TH
I XIS ING 2 'LO G 5'IDE
I 1 ATERNATE ITE ) %4' E FEC IVE EP H x
I LOT, 14 I ' I I I I r ►. I ABS R 1 N/RE CH I I►
E INTI G/��,250 ALL0N /
S PTI TANK /
-BDRMIHOME � 1 L � � \ . ":':••:••• � � � � I
A I A ION I
w/GR E PTP
1FC0 I I
I I I ) I1 G�ARAG� �v/ E
BEbR00 A.Drl _ /: , ►I I
EX IN W�LL \ / \ \ 1 ► I
I ►,� n I \ � I• I
I
LOT , , ► J �� ,� I
P
L h 10
I I I I( I Q
I XITI WELL
��
I
CHGINCFPIHG I IJOTE.
OF gpe�0® NO SURFACE WATER WITHIN 100' OF THE PROPOSED SEPTIC
.CE..........._C Q� A SYSTEM.
`�• 49th •••';' �a ALL WELLS ON SURROUNDING LOTS WITH IMPACTS TO THIS
... .n.....a
.C•� PROPERTY ARE SHOWN. NO CONFLICTS WITH WELLS OR SEPTIC
SYSTEMS.
T'; h11CHAEL E. ANDERSON 49m
NO. CE -4381 ; _•® 0 50 100
A r�F'• . er25120 •,.••`<�:p® FEET
1"-50'
LEGEND
CO - CLEANOUT
2CO - DOUBLE CLEANOUT
FCO - FOUNDATION CLEANO
FS - FLOW SPLITTERVALVE
MH - MANHOLE
MT - MONITORING TUBE
SV - SEPTIC VENT
TH - TEST HOLE
MOUNTAIN VALLEY ESTATES #1, BLOCK 5, LOT 9
DESIGN FACTORS: SYSTEM REQUIREMENTS:
450 GPD PEAK FLOW
PERK RATE: 4.8 MIN/IN
APPLICATION RATE: 1.2 GPD/SF
5' WIDE TRENCH SYSTEM
EXISTING 1,250-GALLON SEPTIC TANK
EXISTING 25' LONG TRENCH
TYPICAL TRENCH SECTION
(NO SCALE)
4" PERFORATED PVC (HOLES DOWN)
DRAINFIELD ROCK
5'
6"
6"
4'
4'
NOTES:
1. GRADE AREA OVER TRENCH TO DRAIN AWAY
2. PROVIDE 3' OF COVER OVER TRENCHES AND 4' OVER SEPTIC TANK, OR 2'
WITH 2" OF INSULATION
3. CHECK GROUNDWATER AT TIME OF CONSTRUCTION. IF LEVEL IS HIGHER
THAN PREVIOUSLY OBSERVED, CALL ENGINEER IMMEDIATELY
BOTTOM OF TRENCH: 8.5' BELOW GRADE
FLOW LINE ELEVATION: 4.5' BELOW GRADE
TOP OF TRENCH: 0.5' ABOVE GRADE
450 GPD / 1.2 GPD/SF /5' WIDE * .5 RED. FACTOR = 37.5 LF TRENCH REQUIRED (38 LF SPECIFIED)
6/25/19
EXTEND EXISTING TRENCH 13' FOR A TOTAL LENGTH OF 38'.
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP191259, Rebecca Carroll, 07/08/19
LEGAL DESCRIPTION:
PERFORMED FOR:
DATE:
PARCEL ID#:Professional Engineers Stamp:
SOILS LOG - PERCOLATION TEST
TECHNICIAN:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
DEPTH
(feet)
PROJECT No.:
TEST HOLE 1
SLOPE
SLOPE
SITE PLAN
DATE READING GROSS TIME
(minutes)
NET TIME
(minutes)
DEPTH to
WATER NET DROP
TEST HOLE PRESOAKED PRIOR TO TESTING:
PERC. HOLE DIA. (INCHES)PERCOLATION RATE: (MIN/INCH)
TEST RUN BETWEEN: FT. and FT.
COMMENTS:
TEST PERFORMED BY ANDERSON ENGINEERING. I, MICHAEL E. ANDERSON CERTIFY THAT
THIS WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS
DATE:
(inches)(inches)
OB/OG 2%2%
Mountain Valley Estates #1, Block 5, Lot 9
Mike McGough
5/16/16
W. Roberts
Silty Gravel
with Sand
BOH @ 16'
Development Services Department
4700 Bragaw Street Anchorage, AK 99519-6650
Municipality of Anchorage
DATE OF MONITORING:
WAS GROUND WATER ENCOUNTERED?
DEPTH OF WATER AFTER MONITORING:
IF YES @ WHAT DEPTH?
Yes
14'
5/23/16
5/16
11:13
10:43
10:42
10:12
3
4
2
1
30
30
6.38"
0.75"
7.13"
7.00"
0.75"
4.8
4.0 5.0
6"
Test Hole Pre Soaked Prior to Test.
6/6/2016
11:15
11:45
5
6 30
0.75"
7.00"
GM
See Site Plan
6.25"
6.25"
14'
6-26-19
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP191259, Rebecca Carroll, 07/08/19
Permit Number:
Tax Code Number:
Work Type:
On-Site Water & Wastewater System Permit
OSP161151
05066112000
WellSeptic
MUNICIPALITY OF ANCHORAGE
Development Services Departm.ent
On-Site Water & Wastewater Program
4700 EImore Road, PO Box 196650
Anchorage, AK 99519-6650
Telephone: (907) 343-7904
Initial
Permit Effective Dates: June 27, 2016 to June 27, 2017
Design Engineer: ANDERSON ENGINEERING
Subdivision: MOUNTAIN VALLEY ESTATES #1
Site Legal Address: MOUNTAIN VALLEY ESTATES #1 BLK 5 LT 9 G:0758
Owner/Address: NAUMANN ANNE C & TERRY R
718 W 1490 NORTH CIR WASHINGTON UT 847800000
ml'tlnent
Site Mailing Address: 3750 BIRDSONG DR, Eagle River
Lot Size in Sq Ft: 78465
Total Bedrooms: 2
This permit is for the construction of:
Y Disposal Field Y Septic Tank N Holding Tank N .Privy Y Private Well N Water Storage
All construction must be in accordance with: 1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater
Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80).
3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services
Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either:
A. Open and Close on the same day.
B. Covered, sealed, and heated to prevent freezing.
Date: _
Municipality of Anchorage
_Development Services Division
On -Site Water and Wastewater Program
�i�enr
�o
i
Deparrmeut
* * * * VARIANCE/WAIVER REVIEW * * * *
Waiver#: OSV161065 COSA#: _ Permit#: OSP161151
PID#: 050-661-12
Legal Description: Mountain Valley Estates #1 Block 5 Lot 9
Engineer: Anderson Engineering
Applicant: Terry and Anne Naumann
The following waiver requests are approved.
1. Zero (0) feet between the drainfield and a 25% or greater slope.
This waiver approval applies to the proposed drainfield only. Any future upgrade to the on-site
wastewater disposal system will require all separation distances be met or another approval from
this department.
❑ The affected adjacent property owner(s) have been given a 7 day notice regarding this waiver.
❑ Notarized letter(s) of non -objection have been received from the owner(s) of the affected
adjacent property.
X Adjacent properties are not affected by this waiver.
...............................................................................
Waiver is Granted: X Waiver is not Granted:
Date: Approved by:
................................... .: me of R::l::::................�
MUNICIPALITY OF ANCHORAGE
Community Development Department
Development Services Division
On-Site Water & Wastewater Program
Phone: 907-343-7904
Fax: 907-343-7997
ON-SITE SEWER/WELL PERMIT APPLICATION
Parcel I.D. 050-661-12
Property owner(s) Terry and Anne Naumann
Mailing address 718 West 1490 North Circle
Day phone 694-2141
Site address Washington, UT 84780
Legal description (Sub'd., Block & Lot)
Legal description (Township, Range & Section) Mountain Valley Estates #1, Block 5, Lot 9
Lot Size 78,465 Sq. Ft. Number of Bedrooms Two
APPLICATION IS FOR:
([~ all that apply)
Absorption Field []
Septic Tank []
Holding Tank []
Privy []
Private Well []
Water Storage []
APPLICATION IS AN:
Initial []
Upgrade []
Renewal []
TYPE OF DWELLING:
Single Family (SF) []
(wA~o ADU)
Duplex (D) []
Multiple Dwellings []
(SF and/or D)
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
Slope Waiver - Absorption Trench to Slope Distance: 0'
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit/Rush Fees: ~'7 8 ~ ~
Date of Payment: ~'/~'//~
Re~ipt Number:
Permit No. 0~1~11~
Waiver Fees:
Date of Payment:
Receipt Number:
Waiver No.
Permit App_2- :.
ANDERSONp;o, BoxENGINEERING24077s
ANCHORAGE, AK 99524
522-7773 677~7766 (FAX)
June 6,2016
Municipality of Anchorage
Development Services Department
On-Site Water and Wastewater Program
4700 South Bragaw Street
Anchorage, AK 99519-6650
Subject:
Lot 9, Block 5, Mountain Valley Estates No. 1
Septic System Design and Permit Application
Impacts to Adjacent Properties
Dear Onsite Services Engineer:
The owner of Lot 9, Block 5, Mountain Valley Estates No. 1 intends to construct a new
two-bedroom home on the lot. We are therefore requesting a permit be issued for the
construction of a new well and septic system to accommodate the home. The attached
Site Plan and backup documentation identify the location and configuration of the
proposed well and septic system along with the alternate site. No existing wells are
closer than 100' from the proposed septic system. Drainage arrows and ground surface
contours are shown on the site plan showing the grade and direction of flow on the lot.
No slopes in the area of the proposed septic system exceed 25%. The drainage pattern
will not be changed as a result of this project.
The test hole placed on the tract in the area of the absorption trench and alternate site
indicated silty gravel with sand (GM) material. The percolation rate of the soil was
determined to be 4.8 minutes per inch. Groundwater was found at 14' during the
placement of the test hole and stabilized at that level dudng the monitoring period. An
application rate of 1.2 gallons per day per square foot was used in the design of the
absorption system. We are proposing to place a new 1,000-gallon septic tank and a 25'
long by 5' wide by 4' effective depth absorption trench to dispose of the effluent
generated in the house. The elevation of the distribution line in the absorption trench
will be 4.5' below the surface and the total depth will be 8.5'. A minimum of 3' of fill or
2" of insulation and 2' of fill will be placed over the absorption trench and 4' over the
septic tank.
The ground surface on the lot in the area of the absorption trench slopes from the
southwest to the northeast at grades exceeding 25%. A slope waiver request is
included with this permit application. The new absorption trench will be constructed
Lot 9, Block 5, Mountain Valley Estates No. 1
June 6, 2016
Page Two
parallel with the contours of the slope as much as possible in conformance with
Municipal requirements. The new septic system will be constructed a minimum of 100'
from all wells and any surface water and 10' from the proposed and existing water
services in the area.
If the system is constructed in accordance with our design the following statements
apply:
The system, if constructed as designed, will have no adverse impact on the wells
in the area or those to be constructed in the future.
The system, if constructed as designed, will have no adverse impact on existing
septic systems in the area or those to be constructed in the future.
The system, if constructed as designed, will have no adverse impact on reserve
space, either surface or subsurface, on any lots located in the area.
The system, if constructed as designed, will have no adverse impact on drainage
patterns in the area. The current drainage pattern will be maintained.
Sincerely,
Michael E. Anderson, P.E.
Attachments
LOT 7 LOT 5
T 14
~ LOT 7
LOT 1 3
I
LOT 8
VACANT
MOUNTAIN
PLAT NO. 2006-171
VALLEY ESTATES
LOT 9, BLOCK
78,465 S.F.
SUBDIVISION NO. 1
5
LOT 8
FILL NOTES;
c System.
' m.." ~'~. ~ - Te$[ Hole LOT 1 0
~ ~ ~ ~ ~ co - Cleon Ou[
' : 49th ~ ~ · Fsv - Flow Sphtter Volvo
~.,,,,~, ........................ ~ .... 2C0 - Double Cleon Out
'J~"7/~~ ~N°' cE-43m ..<~. ~,''lTE PLAN
'*.-~>~::"~..-., -- _ ___
~4WUFESS~ SCALE 1" = 50'
NOTE:
Ar~s of Excessive Slope ore Shown. No
LOT 9, BLOCK 5, MOUNTAIN VALLEY ESTATES NO. 1
DESIGN FACTORS:
2 Bedroom Home
Perc. Rate: 4.8 Min./Inch
Application Rate: 1.2 GPD/SF (Sand Filter)
SYSTEM REQUIREMENTS:
5' Wide Trench System
1.000 Gallon Septic Tank
4' Effective Depth
2 Bedrooms X 150 GPD/Bedroom = 300 Gallons Per Day(Design Flow)
300 GPD/1.2 GPDISFI5SFILF*.5 (Red. Factor) = 25 LFBed Length
THEREFORE: Construct a new 25' long x 5' wide x 4' effective depth absorption trench at the location
shown on the Site Plan. Distribution pipe to be placed 4.5' below the existing ground surface. Total
depth to be $.5'. Place a minimum of 4' of cover over septic tank or 2" of insulation and 2' of cover.
Insure that all components of the septic sytem are 100' from the well on this and adjacent lots.
6u
4~
/......--G eotextile Fabdc
~ 4" Perforated
PVC (Holes Down)
Drainfield Rock
GM
TYPICAL 5' WIDE TRENCH SECTION
: u u ding Bed to Drain Away. . ~
NOTE Grade Area S rro n
Minimum 6' Separation From Bedrock. ~....~....~...~...~?..~.~....~
Minimum 4' S~paration From Groundwater. ~~
Minimum 100 Separat on From Pr vate Wells in the Area ~'~'~ .............................. ~"~',
. . , . ' ~
Minimum 100 Separation From Sudace Water or Streams. ~
Minimum 10' Separation From Water Se~ice Line. .~;~.
· ~;~..~.:.~* X.~,...."
~ESS~
4700
MUNICIPALITY OF ANCHORAGE
DEVELOPMENT SERVICES DEPARTMENT
BRAGAW STREET ANCHORAGE, AK 99519 6650
11
SOILS LOG - PERCOLATION TEST
LEGAL DESCRIPTION:
PERFORMED FOR:
DATE: 5/10/IO
I'vlOUNTAIN VALLEY ESTATES SI. BLOCK 5, LOT 9
PARCEL ID/*:
MIKE McGOUGH
PROJECT No.:
TECHNICIAN:
DEPTH [ TEST HOLE1 ]
(feet)
0B/0G SLOPE
1
2--
3
4--
5 SILTY GRAVEL
WITH SAND
6--
?
$
9
WAS GROUND WATER ENCOUNTERED? YES
BOH @ 16'
20
W. ROBERTS
SITE PLAN
SEE SITE PLAN
2% -
DATE READING!GR, OSS TINE NET TINE %,~,~-I~RTO NET BRQP
TEST HOLE PRESOAKED PRIOR TO TESTING:
5/16 1 10:12 0.75"
2 10:42 30 7.13" 6.38"
3 10:43 0.75'j
I I 4 11'13 30 7.00 6.25"
I 5 11:15 0.75 ,,
I 6 11 45 30 7.00 6.25
PERCOLATION RATE:4.8 0MiN/INCH)PERC. HOLEDIA. 6" (INCHES
TEST RUN BETWEEN: 4.0 FT. and 5.0 FT.
COMMENTS: TEST HOLE PRE SOAKED PRIOR TO TEST.
TEST PERFORMED BY ANDERSON ENGINEERING. I, MICHAEL E. ANDERSON CERTIFY THAT
THIS WAS PERFORMED 1N ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES 1N EFFECT ON THIS
DATE: 6/6/2016
DERSON ENGINEERING
P.O~ BOX 240773
ANCHORAGE, AK 99524 ~
522-7773 677-7766 (FAX)
June 7, 2016
Municipality of Anchorage
Development Services Department
On-Site Water and Wastewater Program
4700 South Bragaw Street
Anchorage, AK 99519-6650
Su~ect:
Lot 9, Block 5, Mountain Valley Estates Subdivision
Absorption Trench to Slope Waiver
Dear Onsite Services Engineer:
Lot 9, Block 5, Mountain Valley Estates Subdivision has limited area for construction of
a septic system due to the location of the steep slopes on the lot. The primary
absorption trench and the alternate site will be constructed on slopes of approximately
33%. The distribution line in the trenches will be constructed at 4.5' below grade to
provide gravity flow. We are therefore applying for a waiver allowing placement of the
absorption trenches at the location shown.
Soils in the area are very good for the treatment and absorption of septic effluent. The
majority of absorption will be down and migration will be minimal. The imaginary 25%
slope from 2.5' above the distribution line invert will daylight at 39' and 45' respectively
when fill to a depth of 1' to 2' above existing ground is placed. We therefore
recommend a waiver be issued allowing placement of the absorption trench at the
locations shown.
Michael E. Anderson, P.E.