HomeMy WebLinkAboutMOUNTAIN PARK ESTATES BLK 5 LT 4BOnsite File Mountain Park Estates Block 5 Lot 4B #017-061-42 (Rev 05/02/18) Municipality of Anchorage On-Site Water and Wastewater Section • (907) 343-7904 Page of ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP201065 PID Number: 017-061-42 Dwelling: ® Single Family (SF) ❑ with ADU ❑ Duplex (D) ❑ Two Single Family Project: ❑ New ® Upgrade Name TRAVIS & STEFANIE CUSTARD ABSORPTION FIELD - EXISTING ❑ Deep Trench ❑ Wide Trench ❑ Bed ❑ Mound Site Address 13201 RIDGEVIEW DRIVE, ANCHORAGE ❑ Other Phone71f Bedrooms Soil Rating Total depth from original grade 773 GPD/SF Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade Ft. Gravel depth beneath pipe Ft. Subdivision Block Lot Fill added above original grade Ft. Gravel length Ft. MOUNTAIN PARK EST. 5 4B Township Range Section Gravel width Ft. Beds: Number of Lines Distance between lines Ft. SEPARATION DISTANCES ToSeptic Absorption Lift Station Holding Sewer Total absorption area Number of trenches Dist. between trenches From Tank Field Tank Line Ft' Ft. Well 100'+ __ 25'+ ITANK ® Septic ❑ S.T.E.P. ❑ Holding ❑ Other Manufacturer GREER Capacity 1000 Gal. Surface Water 100'+ -- Material HDPE Number of compartments 2 Lot Line 10'+ -- NA Foundation 10'+ -- LIFT STATION Manufacturer Capacity Gal. Remarks Alarm location Electrical installed by PIPE MATERIAL House to tank 3034 drainfield Tank to Installer A+3034 Drainfield CO/MT 3034 Inspector FWC BENCH MARK (Assumed elevation) 100 ft Inspection Vt 4/20/20 nd 4/20/20 Location and description 3`d 12/21/2020 4" DOOR SILL ON-SITE WATER AND WASTEWATER SECTION APPROVALOF _ A 'N Conditional Approval: Date ...,• ••'�� ���Q•,••'• TH • Curtis Huffman �� Septic System Approved - //// %� �F��•,• CE 128991 Date �� �iS� ��.24 •.•�ti�' ��F • . •t z/2 t /200 • ��� .� pROF ESSiONQAP.. F, W Note: this approval does not include well permit requirements. �� (Rev 05/02/18) 4/17/2020 MUNICIPALITY OF ANCHORAGE Development Services Department `s Phone: 907-343-7904 On -Site Water & Wastewater Section Fax: 907-343-7997 ON-SITE SEPTIC/WELL PERMIT APPLICATION Parcel I.D. 017-061-42 Property owner(s) TRAVIS & STEFANIE CUSTARD Day phone 9073176481 Mailing address IS021 RIDGEVIEW DRIVE, ANCHORAGE, AK 99516 Site ad13 "l tW2'1 RIDGEVIEW DRIVE, ANCHORAGE, AK 99516 Legal description (Sub'd., Block & Lot) MOUNTAIN PARK EST. 135, 1_413 Legal description (Township, Range & Section) Lot Size 19,440 Sq. Ft. Number of Bedrooms 3 APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: (® all that apply) Absorption Field ❑ Initial ❑ Single Family (SF) 0 Septic Tank Upgrade 0 (w/wo ADU) Duplex (D) ❑ Holding Tank ❑ Renewal El Multiple Dwellings ❑ Privy ❑ (SF and/or D) Private Well ❑ Water Storage ❑ THIS APPLICATION INCLUDES A WAIVER REQUEST FOR: Distance: I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes. .-- (Signature of property owner or authorized agent) l ULeLl) A -j / Permit/Rush Fees: .4Q5.4Q57/�/& F - -�6 Waiver Fees: Date of Payment: � /1VZ Q Date of Payment: Receipt Number: 61':H20 Receipt Number: Permit No. o 5f°%/(11,05 Waiver No. GADevelopment Services\Building Safety\On Site Water and Wastewater\Forms\Client FormsTermit Application.doc 13030 Sues Way, Anchorage, AK 99516 907-350 -9566 / firstwaterAK@gmail.com April 16, 2020 Municipalities of Anchorage On-Site Water & Wastewater Program 4700 Elmore Road Anchorage, AK 99507 RE: SEPTIC TANK UPGRADE PERMIT LEGAL: MOUNTAIN PARK ESTATES BLOCK 5, LOT 4B The owner has requested that we obtain a septic permit to upgrade the existing collapsed septic tank (concrete lid) on the above referenced lot. Due to the collapse and public health / safety, we request an expedited review. We propose to install a 1000-gallon HDPE tank to serve the existing 3-bedroom residence. The lot and area are served by private wells. The design will not impact any of the neighboring properties. Please contact us if you have any questions. Sincerely, Curtis Huffman, P.E. Municipality of Anchorage On-site Water and Wastewater REVIEWED FOR CODE COMPLIANCE OSP201065, Rebecca Carroll, 04/17/20 Municipality of Anchorage On-site Water and Wastewater REVIEWED FOR CODE COMPLIANCE OSP201065, Rebecca Carroll, 04/17/20 Municipality of Anchorage Page DEPARTMENT OF HEALTH AND HUMAN SERVICES ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 · Anchorage, Alaska 99519-6650 · Telephone: 343-4744 On-Site Wastewater Disposal System and/or Well Inspection Report Permit Number: ~'cw ?'7 ~16"7 PIDNumber: Name: ~1,1<~1 ~ ~ ~A y Wastewater System: ~ New ~ Upgrade Address: ~ ~/ ~,~ v,~ ~c ABSORPTION FIELD No. of Bedrooms: Phone: ~ ~. ~ ~ A( ~ ~ Deep Trench ~ Shallow Trench ~ Bed ~ Mound ~ Other LEGAL DESCRIPTION Sol, Rating: Total Depth from original grade: Lot: Block: Subdiv~ion: Depth to pipe bottom from origina~ grade: Gravel depth beneath pipe Township: I Range: I Section: Fill added above original grade: Gravel length: I I WELL: ~ D New ~ Upgrade Gravelwidth: Number of lines: Distance between lines: Classification (Private, A,B,C): Total Depth: Cased To: Total absorption area: Pipe material: ~ Driller: Date Drilled: Static Water Level: Installer: ~ ~o~ Date installed: Yield: GPM I Pump Set at: Ft. ] Casing Height Above Ground:Ft. TANK ~x SEPARATION DISTANCES = s,~tic ~ Ho~Uing ~ S.T.E.P. TO Septic Absorption Lift Holding Public/PrivateManufacturer: Capacityin galrons: From Tank Field Station Tank Sewer Lines ~ ~ Material: Number of Compa~ments: Sudace Water > ~OO > ~ - - - LIFT STATION Lot Size in gallons: I Manufacturer: Foundation J [, ~jO t . -- "Pump on" level at: "Pump off" level at: High water alarm at: Cu~ain Pump Make & Model Electrical inspections pedormed by: Drain ..... Remarks: A6~o~F~o~ ~ ~ ~,~/~ BENCH MARK Location and Description: I Assumed Elevation: ENGINEER'S SEAL Inspections pedormed by: /-(a~ ~& %¢c Dates: 1st 7/z z/~ 7 ~ ..... .4 , ,, ' ....... ' Department of Health and Human Services approval '~'~ , 72-013 (Rev. 9/91) MOA 25 PERMIT NO: SW970167 NEW 18'X36' SOIL ABS. BED PID NO: 01706142 DBL. C.O, "BULL RUN" DI' VALVE xx ORIGINAL SEPTIC SYST. PAGE 2 OF 2 SWING TIES: ~ FROM: "A .... B .... C .... D" ~ TO: S.T.C.O. "X" 17.$' 23' DBL. C.O. "E" 22' 28' VALVE "F" 24' 29' DBL. C.O. "G" 33' 36' ~ - - ~C M.T. "H" 46' $4' ,, - ' ,, C.O. "1" 54' 65' ' ' , C.O. "J" 75' 74' " M.T. "K" '~7oo' '" THEODORE F. MOORE EX4'STING ', CE - 3589 ~OUSE3~DRM ~, ',,,, ' LOT 4B BLOCK 5 ~ ',, ~N. C.O. ~ ORIGINAL _LON CONCRETE WELLS SEPTIC TANK DBL. PLAN VIEW SCALE: 1" -- 30' FINAL GRADE ELEV. 92.3' ORIG. GND. ELEV. 90.3' FABRIC T.H. ~ M.T. DRY 5/19/97 ELEV. 77.4' INV. 81.9 ALL PIPES BOT. GVL ELEV. 81.4 SAND ELEV. 79.6' CROSS SECTION NOT TO SCALE 89.5' EXISTING 1000 GALLON CONCRETE SEPTIC TANK L.4B, BLK. 5, MTN. PK. EST. #1 SEPTIC SYSTEM UPGRADE AS-BUILT INSP. REPORT FLATTOP TECHNICAL SERVICES 14530 ECHO STREET ANCHORAGE, ALASKA 99516 SCALE: AS NOTED DRAWN BY TFM AUGUST, 1997 PAGE 1 OF 1 MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH A_ND HUN3UN SERVICES P.O. BOX 196650, 825 "L" STREET, ROOM 502 A_NCHORAGE, ALASKA 99519-6650 ON-SITE WASTEWATER DISPOSAL SYSTEM (UPGRADE) PERMIT PERMIT NUMBER:SW970167 DESIGN ENGINEER:FLATTOP TECHNICAL SERVICES OWNER NAME:FORTUNY MIKEL & RENE OWNER ADDRESS:13201 RIDGEVIEW DR ANCHORAGE, ALASKA 99516 PARCEL ID:01706142 DATE ISSUED: 7/02/97 EXPIRATION DATE: 7/02/98 LEGAL DESCRIPTION: MOUNTAIN PARK ESTATES BLK 5 LT LOT SIZE: 19440 (SQ. FT.) NUMBER OF BEDROOMS: 3 THIS PERMIT: 3 4B THIS PERMIT IS FOR THE CONSTRUCTION OF: DISPOSAL FIELD /SEPTIC T/MNK SYSTEM ALL CONSTRUCTION MUST BE IN ACCORDANCE WITH: 1. THE ATTACHED APPROVED DESIGN. 2. ALL REQUIREMENTS SPECIFIED IN ANCHORAGE MUNICIPAL CODE CHAPTERS 15.55 AND 15.65 AND THE STATE OF ALASKA WASTEWATER DISPOSAL REGULATIONS (18AAC72) AND DRINKING WATER REGULATIONS (18AAC80). 3. THE ENGINEER MUST NOTIFY DHHS AT LEAST 2 HOURS PRIOR TO EACH INSPECTION. PROVIDE NOTIFICATION BY CALLING 343-4744 ( 24 HOURS } (NOT REQUIRED FOR WELL ONLY PERMIT) 4. FROM OCTOBER 15 TO APRIL 15 A SUBSURFACE SOIL ABSORPTION SYSTEM UNDER CONSTRUCTION DURING FREEZING WEATHER MUST BE EITHER: A. OPENED AND CLOSED ON THE SAME DAY B. COVERED, SEALED AND HEATED TO PREVENT FREEZING 5. THE FOLLOWING SPECIAL PROVISIONS. SPECIAL PROVISIONS: RECEIVED BY: ~ ~ DATE: 7 ~Z3/'~ 7 DATE: 7-2 - TECHNICAL CIV1L & ENVIRONMENTAL ENGINEERING ~, ENERGY CONSERVATION & ANALYSIS THEODORE F. MOORE, P.E. PH: (907) 345-1355 June 3, 1997 14530 ECHO ST. ANCHORAGE, ALASKA 99516 M.O.A. DHHS P.O. Box 19-6650 Anchorage, AK 99519 Dear Sirs: The purpose of this letter is to provide the required design narrative in support of our application for a permit to construct wastewater disposal facilities on Lot 4B, Block 5, Mountain Park Estates, located at 13201 Ridgeview Drive. Soils logs, perc test results, a site plan, design drawings and specifications are enclosed for your review. This application is essentially for a renewal of permit # 910277 which was never constructed at that time, however a sand filter has been added in an attempt to enhance the longevity of the previously approved soil absorption bed. A lot line waiver was issued in 1991 allowing the new system to be within 2 feet of the north lot line, and presumably that waiver is still valid. The proposed system will be constructed in the vicinity of test hole # 2. As can be seen from the soil log, the native material between 9' and 15.5' is a slightly silty sand with a measured perc rate of less than 1 minute per inch. Using the soil application rate of 0.7 gpd/sq, ft. specified in the wastewater ordinance for filter sand, this 3 bedroom residence requires a total absorption area of(3 x 150)/0.7 = 643 square feet. The proposed 20' x 33' bed design has a total absorption area of 660 square feet. The topography of the lot slopes down towards the north at approximately 3%. The location of the bed will encompass test hole #2, however that should not create any problem with settling since the test hole was backfilled with sandy material which has had over 5 years to stabilize. The proposed project will have no significant impact on present or future water supply and wastewater disposal systems serving adjacent properties, nor will it have any significant impact on reserved space-surface and subsurface, or on drainage. Please give me a call at 345-1355 if you have any questions on this submittal. Sincerely, Ted Moore, P.E. ~ I ! o SEPTIC o BLOCK 8 ~ ., ~ j/~' J SEPTIC '-. ~ .~- '~ ,' SYSTEM '' '~ . ~- ~' ~ O¢*~ ~ , ~ WELL~ ~ T.H. , \ / PROPOSED _,,__d\__ ~ "-. F ....... _~ / 20'X33' ~-''''' ~ HOUSE SOIL ABS. BED ~-' , .~ ', './ '. '. / \--. - 4B , '/ , ..~ , 7-, -. ,/ ~ BLOCK 5 , X"%, ~ SEPTIC TANK SEPTIC' SYST. EXIST. WELLS. LOT 4A .HOUSE SEPTIC SYSTEM o LOT 4B, BLK. 5, MTN. PARK EST. WELL AND SEPTIC SYSTEM SITE PLAN FLATTOP TECHNICAL SERVICES 1 INCH = 50 FEET 14530 ECHO STREET DRAWN BY TFM ANCHORAGE, ALASKA 99516 REV. MAY, 1997 NOTE: THIS IS NOT A SURVEYED PLAT. ALL LOCATIONS SHOWN ARE APPROXIMATE. PLAN VIEW SCALE: 1" = 10' - 0" 33 "A" I--~C.O. ~M.T. 4" F~810 PERF. !~ ~-C 0 M.T, ~  4" D-3034 L FROM 1000 GAL. SEPTIC TANK "A" MONITOR TUBE-- UNCLASSIFIED BACKFILL MOUND 12" ABOVE ORIGINAL GRADE ~ROVED FILTER 3 FILTER FABRIC · 1/2" - 2 1/2" SEWER GVL. · F-810 PERF DIST. PIPE SECTION "A - A" SCALE: 1" = 5' - 0" LOT 4B, BLK. 5, MTN. PARK ESTATES SEPTIC SYSTEM UPGRADE PLAN AND CROSS-SECTION FLATTOP TECHNICAL SERVICES 14530 ECItO STREET ANCHORAGE, AK, 99516 SCALE: AS SHOWN DRAWN BY: TFM REV. JUNE, 1997 Flattop Technical Services 14530 Echo Street, Anchorage, AK 99516 Phone (907) 345-1355 Lot 4B, Block 5, Mountain Park Estates S/D 13201 Ridgeview Drive Wastewater disposal system installation Specifications 1.0 General: 1.1 The scope of the project consists of installation of a 1000 gallon septic tank which discharges into a 20"wide x 33"long soil absorption bed. 1.2 Construction shall be as depicted on the approved site plan and design drawings. Minor deviations from these drawings may be allowed or required by the engineer conducting the inspections. All construction procedures and material specifications shall conform with Municipal and State requirements. Ail separation distances shall be in conformance with Municipal requirements, unless specifically waived. 1.3 The contractor shall be responsible to obtain any necessary utility locates, and to work around any buried utilities. 1.4 The contractor shall provide adequate cover material and rough grading over all system components to ensure that proper drainage is achieved after settlement and that there are no residual depressions. Insofar as possible the contractor shall minimize damage to trees and existing lawn areas. 1.5 Unless specifically agreed otherwise, the homeowner shall be responsible for finish grading after the soil is compacted, as well as placement of topsoil and reseeding all areas disturbed by the construction. 1.6 Prior to the start of construction, the property owner shall arrange for a surveyor to locate the northeast corner of the lot and to stake the lot lines in both directions at 25' and 50' from this corner. 2.0 Septic Tank: 2.1 The new 1000 gallon, 2 compartment septic tank shall be Municipally approved and shall be set level on undisturbed soil. Each compartment shall be equipped with a watertight manhole cover and a 4" cleanout. If the tank is buried less than 4 feet, it shall be insulated with 2 inches of approved burial type, rigid insulation. The existing septic tank shall be properly abandoned. 2.3 Ail pipe connections to the tank shall be equipped with waterproof mechanical couplings. The waste line from the residence to the septic tank shall have a minimum slope of 1/4'" per foot, and the waste line between the tank and the soil absorption system shall have a minimum slope of 1/8" per foot. A cleanout shall be installed within 5 feet of the building foundation, and a double cleanout shall be installed within 5 feet downstream of the septic tank. A second double cleanout shall be installed near the midpoint of the waste line between the septic tank and the soil absorption bed. 3.0 Soil absorption system: 3.1 The soil absorption system shall be constructed by excavating the surface fill and silt from the entire 20' wide x 33 foot long bed area down to expose a fine sand stratum at a depth of approximately 9.5 feet below ground level in the vicinity of test hole #2. 3.2 The bottom of the excavation shall be level. Any compacted or smeared surfaces shall be raked to allow proper infiltration. A total of 2 feet of filter sand shall be placed in the bottom of the excavation. Sand serving as filter material shall have less than 4% passing the #100 sieve and shall comply with Municipal filter sand specifications. "D.O.T. Road Sand" as manufactured by CPP meets these specifications. 3.3 A total of 1.0 feet of approved sewer gravel shall be placed in the bottom of the excavation with the perforated distribution pipes laid level such that the pipe inverts are no less than 0.5 feet above the bottom of the sewer gravel. Sewer gravel shall be 0.5" - 2.5" washedand screened gravel (as supplied by Anchorage Sand and Gravel), with less than 3% passing the #200 sieve. 3.4 Monitor tubes and cleanout pipes shall be of 4" diameter and installed in the locations shown on the design drawings. The portion of the monitor tube extending through the sewer gravel shall be perforated. 3.5 Approved filter fabric shall be placed over the entire top surface of the sewer gravel. A minimum of 2 feet of soil cover is to be placed over the filter fabric. 3.6 The top surface of the cover material shall be raised a minimum of 12 inches higher than the surrounding terrain to allow for subsequent settlement, and shall be graded to smooth contours. Fill slopes shall be no steeper than 3:1. 3.7 Unless specifically agreed otherwise the homeowner shall be responsible for arranging to have the site finish graded after the backfill material has stabilized, and for placement of adequate topsoil and seed to promote rapid revegetation of all areas disturbed by the construction. 4.0 Inspections: 4.1 A total of 5 engineering inspections will be required during the course of the project: (1) initial stakeout with the contractor to establish the location of the system and to discuss the plans, specifications and construction procedures, (2) after the native material has been excavated to expose the infiltrative surface to ensure that it is level and at the right elevation, and conforms with the soil test information, (3) after the sand filter material has been placed, (4) after the sewer gravel is in place and the distribution pipes have been laid and connected up to the septic tank, but prior to placement of insulation or filter fabric, and (5) after rough backfill and grading is complete. The septic tank requires one inspection after it is set level and the piping connected, but prior to backfill. This inspection may be incorporated with any of the above inspections. 4.2 The installer shall coordinate the timing of the inspections with the engineer sufficiently far in advance to ensure the availability of the engineer. PERPO.MED POR: MIK£ LEGAL DESCRIPTION:,~OT 1 2 '3 4 5 6 7 8 9 10- 11 12 13- 14 15 16 17 18 19 20 COMMENTS FILL p'l- 5P/ M ~lattO~) Technlcal ser-~,ice-s 14530 Echo Street Anchorage, A/as~,a 9951 $ Municipality ot Anch'~Y~ge DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L' Street, Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST FORTUNY qB B5 Township, Range, Section: LOAM SILT WAS GROUND WATER ENCOUNTERED? ~sT Reading Date Gross Net Depth to Net Time Time Water Drop +~o I~', ~ 2~ ~ 12'.51 S IF YES, AT WHAT L DEPTH;' i'~ 'A 0 · p E Deplh to Water AFter . I,.~ 'g.~',L. Montlorin b~¥ Dale: ~ PERCOLATION RATE "~ [ (minutes/inch) PERC HOLE DIAMETER TEST RUN BETWEEN JO FT AND IO'~'~ FT PERFORMEDeV: FL/Il'TOP T~Cl-/ 5l/('r, , //'~~ CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STA:rE AND MUNICIPAL GUIDELINES IN EFFEC'r ON THIS DATE. DATE: 72-006 (Rev. 4/85) Municipality of A chora e Departmellt of Health and Human Services Tom Fink, 825 "L" Street Mayor P.O. Box 196650 Anchorage, Alaska 99519-6650 343-4744 September 12, 1991 Ted Moore, P. E. Flattop Technical Services 14530 Echo Street Anchorage, Alaska 99516 Subject: Waiver Re¢[uest for Lot 4B Block 5 Mountain Park Estates S/D Waiver Re¢~est #WR910041, PID #017-061-42, SW910277 Dear Mr. Moore: Your request for waiver of the required 10 foot separation between a septic system and a lot line has been approved. waived distance is 2 feet to north property line abutting Crestview Drive. The · This approval applies to the existing septic system lot line separation only. Any future upgrade to the septic system will require all separations be met or another approval from this department. Sincerely[. Daniel N. Bolles On-si~e Services Concur: ~hn Smit~ ~~anag~r' On-site Services DNB.ljm Tom Fink, Mayor unici ality Anchorage Department of Health and Human Services 825 "L" Street P.O. Box 196650 Anchorage, Alaska 99519-6650 343-4744 September 10, 1992 Mikel Fortuny 13201 Ridgeview Drive Anchorage, Alaska 99516 Subject: Lot 4 Block 5 Mountain Park Estates Subdivision Permit #SW910277, PID #017-061-42 The subject permit, issued September 10, 1991 by this office for a single family well and/or on-site wastewater system, has expired as of September 10, 1992. A new permit must be obtained from this office for a well and/or on-site wastewater system NOT installed by the expiration date. If you have drilled the well, a well log must be sent to this office for documentation of the installation and to close the permit. If a licensed Professional Engineer has inspected the installation of the on-site wastewater system, the original as-built inspection report must be sent to this office for review, approval and documentation. All inspection reports must be submitted within 30 days of construction completion. When applying for a new permit, the fees are: $200.00 for an on-site wastewater permit; $75.00 for a well permit and $275.00 for a combined on-site wastewater and well permit. If you have any questions, please call this office at 343-4744. Sincerel~ Program Manager On-site Services enc: Copy of Permit PAGE 1 OF 1 MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND HUMAN SERVICES P.O. BOX 196650, 825 "L" STREET, ROOM 502 ANCHORAGE, ALASKA 99519-6650 ON-SITE WASTEWATER DISPOSAL SYSTEM (UPGRADE) PERMIT PERMIT NUMBER:SW910277 DESIGN ENGINEER:FLATTOP TECHNICAL SERVICES OWNER NAME:FORTUNY MIKEL OWNER ADDRESS:13201 RIDGEVIEW DR ANCHORAGE, AK 99516 DATE ISSUED: 9/10/91 EXPIRATION DATE: 9/10/92 PARCEL ID:01706142 LEGAL DESCRIPTION: MT PARK ESTATES BLK 5 LT 4~ SEC 26, T12N, R3W, SM LOT SIZE: 19440 (SQ. FT.) NUMBER OF BEDROOMS: 3 THIS PERMIT: 3 THIS PERMIT IS FOR THE CONTRUCTION OF: DISPOSAL FIELD SYSTEM ALL CONSTRUCTION MUST BE IN ACCORDANCE WITH: 1. THE ATTACHED APPROVED DESIGN. 2. ALL REQUIREMENTS SPECIFIED IN ANCHORAGE MUNICIPAL CODE CHAPTERS 15.55 AND 15.65 AND THE STATE OF ALASKA WASTEWATER DISPOSAL REGULATIONS (18AAC72) AND DRINKING WATER REGULATIONS (18AACS0). 3. THE FOLLOWING SPECIAL PROVISIONS. SPECIAL PROVISIONS: SEPARATION TO NORTH PROPERTY LINE ALONG CRESTVIEW DR. IS WAIVED TO 2', FROM THE ABSORPTION BED. RECEIVED BY: ~ ~//~'~- DATE: ISSUED BY: __ _ DATE: CIV1L & ENVIRONMENTAL ENGINEERING · ENERGY CONSERVATION & ANALYSIS 14530 ECHO ST. THEODORE F. MOORE, P.E. August 29, 1991 PH: (907) 345-1355 ANCHORAGE, ALASKA 99516 M.O.A. DHHS P.O. Box 19-6650 Anchorage, AK 99519 Dear Sirs: The purpose of this letter is to provide the required design narrative in support of our application for a permit to construct wastewater disposal facilities on Lot 4B, Block 5, Mountain Park Estates 4/1 S/D, located at 13201 Ridgeview Drive. Soils logs, perc test results, a soil sample, a site plan, design drawings and specifications are enclosed for your review. The existing soil absorption system is surcharged, and in need of replacement. The proposed system will be constructed in the vicinity of test hole # 2. As can be seen from the soil log, the native material between 9' and 15.5' is slightly silty sand with a measured perc rate of less than 1 minute per inch. The enclosed sample of material taken form the perc hole demonstrates that it is equivalent to "filter sand" as described in the ordinance. Using the soil application rate of 0.7 gpd/sq, ft. for filter sand, this 3 bedroom residence requires a total absorption area of (3 x 150)/0.7 = 643 square feet. The proposed 20' by 33' bed design has a total absorption area of 660 square feet. The location of the proposed bed will encompass test hole #2, however this should not create any problem with settling because the test hole only goes 6 feet deeper than the bed bottom and was backfilled with sandy material. The topography of the lot in the vicinity of the proposed soil absorption bed slopes towards the north at approximately 3%. The proposed project will have no impact on present or futm'e water supply and wastewater disposal systems serving adjacent properties, nor will it have any impact on reserved space/surface and substu'face, or on drainage. Please give me a call at 345-1355 if you have any questions on this submittal. Sincerely, Ted Moore, P.E. IS~ PT IC. LOT lut 13LoC~ ~ ~IELL ON ~ LoT ur~ Co~N~ LOT 13 EXIST, 3 Rou.sE D -.to $ ¥ LoT ~ BLK ~ ~L P~opE~T¥ Co~NE~ \ FI&ii6~ T~chi~ic&l Se~rvlc~s 14530 Echo Street Anchorage, Alaska 99516 -SITE PLAN SCALE; I% 30~ DATE: c~[Ctl b~'~ DY: ~ N, OT~: "THI% IS NoT A 5uRV~~/Ei PLAT. ALL LoCA'T~ON $ ARS' APP~n¥ t 1,4 ATE, 0~'/'TvB~ ¢" ?Ef~F PtPe" ~/ ~' ~ l.S / O-3o3H ~- ~ MoN~TO~ ~-- ." ,- .'" ," -" -" /' /" ~' / /' /" / ~.,' ~' / ~ / z . .-' W' '. .... " .' '" 2.5 ' ~F~o~ moo ~Ac A 20r ViEW TOTA~ DEPT~ ,C e.o. ~.T, "~ ~..~ ........ .,..,...:...~ ~~L~ m ~ ~jH~ooo~ ~:. ~oo~/ ~ Pl~top n~c~l Se~ zces $~.,. CE-3589 , ~ . Tec~ .. v' ~ ~ ,.....,... ~,~ _ ~4530 Echo Street ~. P~t~X ~ ' Anchorage, Alaska 99B~ ~ T L ~tB~ SS, MT. PARK EST. ~'1 SOIL ABSORPTION BEb PLAN ANb CRoss-$ECT~Oh Flattop Technical Services 14530 Echo Street, Anchorage, AK 99516 Phone (907) 345-1355 Lot 4B, Block 5, Mountain Park Estates #1 13201 Ridgeview Drive Wastewater disposal system installation Specifications 1.0 General: 1.1 -The scope of the project consists of verifying the integrity of an existing septic tank and installing a new 20' wide x 33' long soil absorption bed. 1.2 Construction shall be as depicted on the approved site plan and design drawings. Minor deviations from these drawings may be allowed or required by the engineer conducting the inspections. All construction procedures and material specifications shall conform with Municipal and State requirements. 1.3 All separation distances shall be in conformance with Municipal requirements, unless specifically waived. 1.4 The contractor shall be responsible to obtain any necessary utility locates, and to work around any buffed utilities. 1.5 Prior to the start of construction, the property owner shall re'range for a surveyor to locate the northeast corner of the lot and to stake the lot lines in both directions at 25' and 50' from this comer. 2.0 Septic Tank: 2.1 The existing septic tank may be retained in service only if it's structural integrity has been verified, and if it has functional cleanout pipes with airtight caps, allowing pumping access to each compartment. 2.2 If after the contractor exposes the existing tank, it is found to not be in satisfactory condition, the tank shall be properly abandoned and replaced with a new 1000 gallon Municipally approved tank with a minimum of two compartments. The new tank shall be set level on undisturbed soil. Each compartment shall be equipped with a watertight manhole cover and a 4" cleanout. If the tank is buried less than 4 feet, it shall be insulated with 2 inches of approved burial type, rigid insulation. 2.3 All pipe connections to the tank shall be equipped with waterproof mechanical couplings. The waste line from the residence to the septic tank shall have a minimum slope of 1/4"' per foot, and the waste line between the tank and the soil absorption system shall have a minimum slope of 1/8" per foot. A cleanout shall be installed within 5 feet of the building foundation, and a double cleanout shall be installed within 5 feet downstream of the septic tank. A second set of double cleanouts shall be installed midway on the line between the tank and the new soil absorption bed. 3.0 Soil absorption system: 3.1 The soil absorption system shall be constructed by excavating the surface fill and silt from the entire bed area down to a expose a fine sand stratum at a depth of approximately 9.5 feet below ground level in the vicinity of test hole #2. 3.2 The bottom of the excavation shall be level. Any sand used for leveling shall comply with Municipal specifications. 3.3 A total of 1.0 feet of approved sewer gravel shall be placed in the bottom of the excavation with the perforated distribution pipes laid level such that the pipe inverts are no less than 6 inches above the bottom of the sewer gravel. Sewer gravel shall be 0.5" - 2.5" screened gravel, with less thm~ 3% passing the #200 sieve. 3.4 Monitor tubes and cleanout pipes shall be of 4" diameter and installed in the locations shown on the design drawings. The portion of the monitor tube extending through the sewer gravel shall be perforated. 3.5 Approved filter fabric shall be placed over the entire top surface of the sewer gravel before backfill. The top surface of the cover materiai shall be raised a minimum of 12 inches higher than the surrounding terrain to allow for subsequent settlement, and shall be graded to smooth contours. The top 4 inches of cover material shall be topsoil. Fill slopes shall be no steeper than 3:1. The owner shall be responsible for reseeding the disturbed areas. 4.0 Inspections: 4.1 A total of 4 engineering inspections will be required during the course of the project: (1) initial stakeout with the contractor to establish the location of the system and to discuss the plans, specifications and construction procedures, (2) after the native material has been excavated to expose the infiltrative surface to ensure that it is level and at the fight elevation, and conforms with the soil test information, (3) after the sewer gravel is in place and the distribution pipes have been laid and connected up to the septic tank, but prior to placement of insulation or filter fabric, and (4) after final backfill and grading is complete. The existing septic tank requires one inspection, and if a new tank is installed a second inspection is required after it is set level and the piping connected, but prior to backfill. These inspections may be incorporated with any of the above inspections. 5.2 The installer shall coordinate the timing of the inspections with the engineer sufficiently far in advance to ensure the availability of the engineer. ~tt6~ TecI~nlcaI ..... 14530 Echo SIreet Anchorc~ge, .AIgo..a 99515 Municipality o! Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST FERFORMEOPOR= MIK£ LEGAL O ESCRIPTION',].Or 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15. 16- 17 18 19 20 COMMENTS ..pRELiPI(N/~f~',f ~£/~C. PERFORMED BY: _~'/-A"TTOP T~C~ FORTUN"J DATE PERFORMED:~ Township, Range. Section: S~¢ .2~, TI2N, /~, ~v' SLOPE SITE FILL., ~R~VELL"J SILT NL SiLT SoME COBBLES No $~4 5~LTY SANb I:'OCK'~-I'S oF' sp/SM HATE~ ~,AL I~ECOPI~ CLEANE~ WlTtt WASGROUNDWATER ENCOUNTERED? INCRE~ S~NG bEPTN s IF YES, AT WHAT L O DEPTH? ~,~, p E Depth 10 Water After $ 6 5. G.L,, Monitorino? PIP'.."{ Oa~e: Reading Date Gross Net Depth to Net Time Time Water Drop PERCOLATION RATE ~ TEST RUN BETWEEN ,~,,~' 'T, fl. t~2 (minutes/inch) PERC HOLE DIAMETER FT AND C~ FT ~'1/'(' ~, I ,_~_.-~..~/~"~ CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STA:rE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE, DATE: .,, 72-008 (Rev, 4/85) - ~ft6~ Technical sefVlcSs 14530 Echo Anchorage, Municipality o! Anch~Y,~ge DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Ataska 99502-0650 SOILS LOG ~ PERCOLATION TEST PERFORMED FOR: LEGAL DESCRIPTION:!OT I FiLL J IKE FO TUN¥ p-~ SILT sP/S 6 7 8 9 10 11 12, 13- 14 15 16 17 18 19 20- COMMENTS RE, ST OF 5' DATE PERFORMED: Township, Range, Section; .5~C .2~,, T 12 r.I, LOAM SLOPE SITE WAS GROUND WATER ENCOUNTERED? IF YES, AT WHAT DEPTH? Depth Io Waler Alter Monitoring? -T,tl.~t r Reading Time Not Time Depth to Water 2~ Net Drop PERCOLATION RATE ~ / TEST RUN BETWEEN . JO (minutes/inchl PERC HOLE DIAMETER FT AND ID.~'-~ FT PERFORMED BY: F'~/~'I'TO p T~ C J-/ .~'V'(' _~ '--f"~"~' -/~"~'~-- CERTIFY T'AT THIS TEST WAS PERFORMED iN ACCORDANCE WITH ALL STA:DE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: ,~ // 2..~ j'__~. / 72-008 (Rev, 4/8,5) PERFORMED FO.: MIK£ LEGAL DESCRIPTION:J. oT 2 '3 4 Ntt 5 6 7 8 9 10 11 12 13 14 15 16 17, 18- t9- 20 COMMENTS ~Ftl0~5 Technlcc! Se~ic~s 14530 Echo Street Anchorc~ge, A . lg,~..~ 9951G ~u~l~lpalil~ gl ~EPA~TMENT OF HEALTH & HUMAN SEaVIGE8 8a5 "k" 8Jreet, Anohorage' Alaska 99502-0650 SOILS LOG ~ PERCOLATION TEST FORT(.,,Ny qB. Township, Range, Section: SLOPE SILT 5P / Sa 5LI~TL~{ 51L7~ F~NE 5Aqb WAS GROUND WATER ENCOUNTERED? S IF YES, ATWHAT L DEPTH? 0 p E Depth Io Water Aller Monitoring? Dale: Flooding Date Gross Net Depth to Net Time Time Water Drop PERCOLATION RATE TEST RUN BETWEEN -- (m,nutes/inch) PERC HOLE DIAMETER __ FT AND ~FT PERFORMED BY: F'ZATTOP T~C{4 5'V¢ ~ ~ I ~.~'"~ /~'~:'~-""~t,. CERTIFY THAT THIS TEST WAS PERFORMED iN ACCORDANCE WITH ALL STA~E AND MUNiCiFAL GUiDELiNES iN EFFECT ON ~ HiS DATE, DATE: 72-008 (Rev. 4/85) Tom Fink, Mayor unicipality of Anchorage Department of Health and Human Services 825 "L" Street P.O, Box 196650 Anchorage, Alaska 99519-6650 343-4744 September 12, 1991 Ted Moore, P. E. Flattop Technical Services 14530 Echo Street · Anchorage, Alaska 99516 Subject: Waiver Request for Lot 4B Block 5 Mountain Park Estates S/D Waiver Request ~WR910041, PID ~017-061-42, SW910277 Dear Mr. Moore: Your request for waiver of the required 10 foot separation between a septic system and a lot line has been- approved.~.~he~-~ ~ waived distance is 2 feet to north property line abutting .- Crestview Drive. This approval applies to the existing septic system lot line separation only. Any future upgrade to the septic system will require all separations be met or another approval from this department. Sincerely9 . , Daniel N. Bolles On-site Services Concur: On-site Services DNB.ljm 'OP 'TECHNICAL CIVIL & ENVIRONMENTAL ENGINEERING · ENERGY CONSERVATION & ANALYSIS THEODORE F. MOORE, P.E. 14530 ECHO ST. PH: (907) 345-1355 September 10, 1991 ANCHORAGE, ALASKA 99516 Dan Bolles M.O.A. DHHS P.O. Box 19-6650 Anchorage, AK 99519 Dear Mr. Bolles: As we discussed this A.M., in submitting our application dated 8/29/91 for a sewer upgrade permit for Lot 4B, Block 5, Mountain Park Estates #1, we neglected to request a waiver allowing the proposed soil absorption bed to be within 2' of the north property line abutting Crestview Drive. By means of this waiver request, we wish to correct that oversight. The proposed design was selected to optimize the proximity of the system to the best soils which were encountered in test hole#2, while staying away from the 100 foot radius from the private well serving the lot. This forces the proposed bed to be within approximately 5 feet of the lot line, and the waiver to 2 feet is to compensate for possible survey errors. Since the requested waiver is for the distance to a lot line abutting a dedicated right of way, granting the waiver will have no impact on any existing or possible future wells or wastewater disposal systems. It will also have no impact on any possible future expansion of Crestview Drive. Please give me a call if you have any questions on this waiver request. cc: Mikel Fortuny Sincerely, Ted Moore, P.E. J~UNI(~IPAI.ITY OF ANCHORAGE [NVII~{)NI~tNTAL SERVICES ,~ ~'~ ~ '~ 1991 RECEIVED  MUNICIPALITY OF ANCHORAGE · DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTION ENVIRONMENTAL ENGINEERING DIVISION 825 L Street- Anchorage, Alaska 99501 Telephone 264-4720 ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT NAME PHONE I ~JNEW MAI LING ADDRESS LEGAL DESCRIPTION ] Wall Absorption araa Dwalling PERMIT NO, DISTANCE TO: ~ Z Manufacturer Material No, of compartments ~ ~ Liq. capacity in gallons IF HOME.DE: Inside length Width Liquid depth ~ ~ DISTANCE TO: Well Dwelling PERMIT NO. =_~O Z ~ Manufacturer Material Liquid capacity in gallons Q Wall Foundation " Nearest lot line . PERMIT NO~ ~ Z ~ NO. of lines Length of each line ~ Total length of li~es ~ Trench width ~ Distance between liGes ~ Top of tile to finish grade ~ Material beneath tile Q~ ~- ~ ~~,~u:~s Total effective absorption~ area Length Width Depth PERMIT NO. ~ ~ Type of crib Crib diameter Crib depth Total effective absorption area Well Building foundation Nearest lot line ~ DISTANCE TO: ~ Class Depth Driller Distance to lot line PERMIT NO. ~ DISTANCE TO: , Building foundation Sewer line '~ Septic tank Absorption area(s) OTHER PIPE MATERI~LS SOIL TEST RATING INSTALLER t~ APPROVED ~ DATE LEGAL CONSTRUCTION TEST L~B ~ "One Test is worth a Thousand Opinions" 2204 Cleveland Anchorage, Alaska 99503 277-0231 Performed for Don Delk Legal Description: Lot 4B Block This Fomn reports: SOILS TEST yes Date Performed 10/17/79 Subdivision Mt. Park Estates PERCOLATION TEST Depth Feet 6" Soil Characteristics Topsoil & Reddish Silt Fine Brown Sand (SP) 16' Bottom of Test Hole Was Ground Water Encountered No If YES, What depth? Reading Date Gross TJ~ne Net TLme Depth to H20 I Net Drainage Percolation Rate Minute Proposed Installation: SEEPAGE PIT DRAIN WIELD Depth of Inlet Depth to Bottom of Pit or Trench CO'~4ENTS: 150 square feet drainage area required per bedroom. Test Performed by ~/ y.~ Data Certified Bv: Construction Test Lab D['Pau~ Date : October IQ; 1979 Municipality of Anchorage Development Services Department Building Safety*Division On-Site Water & Wastewater Program c~. ~' ~.. 4700 Brag~ .w.. Street P.O. Box 196650 Anchorage, AK 99519-6650 www.muni.org/onsite (907) 343-7904 OF ON-SITE SYSTEHS APPROVAL SINGLE FAMILY DWELLING OERTIFICATE FOR A Parcel I.D. 017-061-42 1. GENERAL INFORMATION Expiration Date: Complete legal description Location (site address) Current Property owner(s) Mailing address Lending agency Mailing address Real Estate Agent Mailing address MOUNTAIN PARK ESTATES S/D; BLOCK 5, LOT 4B 15201 RIDGEVIEW DRIVE * ANCHORAGE, AK * 99516 RENE FORTUNY Day phone P.O. BOX 112846 * ANCHORAGE, AK * 99511 360-7323 Day phone Day phone UnleSs otherwiSelrequested, COSA will be held by DSD for pickup. 2. NUMBER OF BEDROOMS: 5 31 TyPE oFWATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Individual Well · Individual On-site · Individual Water Storage [] Individual Holding tank [] Community Class Well [] Community On-site [] Public Water System [] Public Sewer [] The Municipality of Anchorage Development Services Department (DSD) Issues Certificates of On-Site Systems Approval (COSA) based only upon the representations given in paragraph 4 by an independent professional civil engineer registered in the State of Alaska. Certificates of On-Site Systems Approval are required for the transfer of title (except between spouses) for properties served by a single-family on-site wastewater disposal and/or water supply system. DSD also issues COSAs upon request to homeowners. Certificates of On-Site Systems Approval are valid for 90 days from the date of issue for properties served by a private or Class C well and may be reissued with new water samples. (Certificates may be reissued for a period of up to one year with valid water samples.) Certificates are valid for one year for properties served by Class A or B wells or a public water system. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 4. STATEMENT OF INSPECTION BY ENGINEER ~ o~ ~,e vo,,da,,on da,~ o,,,,v,,, below, 1 verify *~' '" ' As certified by rny seal a,~:xed he,mo and .... ~ "~': -': ^'~ ~" .... investigation, based on procedures outlined in the Certificate of On-Site Systems Approval Guidelines for this application, shows.that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the inforrnation obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm GARNESS ENGINEERING GROUP, Ltd. Phone 557-6179 Address 5701 E. TUDOR ROAD. SUITE 101 * ANCHORAGE, AK 99507 Engineer's Printed Name JEFFREY A. GARNESS, P.E. Date Engineer's Comments: In conducting this evaluation, GEG, LtD. attempted to provide a thorough, conscientious engineering arralysis of the system in accordance with ADEC and MOA DSD Guidelines & Regulations. The reported results described the performance of the system under the conditions encountered at the time of the test, and separation distances measured to readily identifiable features. The operational life of all wells and septic systems depend on the local soils condition, groundwater levels that may fluctuate during the year, and the water usage of the family being served by the system. These conditions are outside the control of the evaluator of the system. Satisfactory test results do not guarantee future performance of the system, nor do they guarantee that there are no hidden defects or encroachments. GEG, LTD. can therefore not provide any warranty or future estimate of how long the system will continue to meet the operational requirements of the ADEC or MOA DSD. The content of this report is for the sole benefit of the owner listed above. Any reliance upon or use of this report by any other person or party is not authorized, nor will it confer any legal right whatsoever. DSD SIGNATURE /[~'~'/Approved for Disapproved. bedrooms. Conditional approval for ', PR . 0,,.. OGRAM .._. bedrooms, with the following stipulations: -~'~.°.. . .° Z~."~' 72gj))))) ) Attachments: COSA Checklist L.~ Septic System Advisory Well Flow Advisory Arsenic Advisory Maintenance Agreements Supplemental Engineer's Report Other Original Certificate Date: Municipality of Anchorage Development Services Department Building Safety Division On-Site Water & Wastewater Program 4700 Bragaw Street P.O. Box 196650 Anchorage, AK 99519-6650 www. muni.org/onsite (907) 343-7904 CERTIFICATE OF ON-SITE SYSTEMS APPROVAL 'CHECKLIST Legal Description: MOUNTAIN PARK ESTATES S/D; BLOCK 5, LOT 4B Parcel ID: (~1 '7" ~:)~ l"/"//2.~ A. WELL DATA *PER (;EG INSPECTION! Well type PRIVATE Date completed 1969? Total depth '169+ ft. If A, B, or C provide PWSID# N/A Sanitary seal (Y/N)YES Cased i .ft. Well Log (Y/N) Wires properly protected (Y/N) Casing height (above ground) NO YES 12+ in. FROM WELL LOG Date of test Static water level Well production g.p.m. WATER SAMPLE RESULTS: Coliform ~ colonies/lO0 mi. Arsenic: N~ ug./L. Nitrate mg./L. Date of sample: 9/22/2010 AT INSPECTION 9/23/2010 169 3.1 g.p.m. Other bacteria ~ colonies/100 mi. Collected by: GE(:; Ltd. B. SEPTIC/HOLDING TANK DATA Tank Type/Material SEPTIC/CONCRETE Date installed Tank size 1000+ gal. Number of Compartments UNKNOWN Cleanouts (Y/N) Foundation' Cleanout (Y/N) YES Date of pumping 9/17/2010 C. ABSORPTION FIELD DATA ~*BELOW EXISTING GRADEI 1.0/24/1.979 ~ 150 FT2/BDRM Date installed 7/'22-2.3/1997 Soil rating (g.p.d./ft2or ft'/bdrm) 0.7 GPD/FT2 System type 20 3 Length 36 .ft. Width 18 ft. Gravel below pipe 19697 YES Depression over tank (Y/N) NO High water alarm (Y/N) N/A Pumper. A+ HOME SERVICES 1991 TRENCH TRENCH 1997 BED BED 8 0.5 · 11.6 320 Total depth ~ ft. Eft. absorption area 648 ft2 Monitoring tube YES Date of adequacy test 9/23/2010 Results (Pass/Fail) PASS Fluid depth in absorption field before test ~ 0 in. Water added 450 gal. Elapsed Time: - min. Final fluid depth 0 in. Any rejuvenation treatment (past 12 mo.) (Y/N & type) NONE NOTE: PREVIOUSLY DOCUMENTED CRIB AND TRENCH CONNECTED AS Absorption rate >= KNOWN If yes, give date Depression over field NO For 3 bedrooms New depth 0 in. 450+ g.p.d. D. LIFT STATION Date installed "Pump on" level at in. E. SEPARATION DISTANCES SEPARATION DISTANCES FROM WELL ON LOT TO: Size in gallons Manhole/Access ~ J "Pump off" leve_~..a~. High water alarm level at Cycles tested Meets alarm & circuit requirements? 100'+ Septic tank/lift station on lot AbSorption field on lot 100'+ Public sewer main N/A Sewer/septic service line 25'+ Animal containment areas 50'+ On adjacent lots 100'+ On adjacent lots 100'+ Public sewer manhole/cleanout Holding tank N/A Manure/animal excrete storage areas N/A 100'+ SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Building foundation 5'+ Property line 5'+ Water main N/A Water service line, 10'+ Wells on adjacent lots 100'+ Absorption field Surface water. 5'+ 100'+ SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO: Property line *2'+ Building foundation 10'+ Water service line 10'+ Surface water 100'+ Curtain drain NONE KNOWN Wells on adjacent lots. 100'+ Water main N/A Driveway, parking/vehicle storage 1'+ COMMENTS *PER EXISTING WAIVER #WR910041. G. ENGINEER'S CERTIFICATION I certify that I have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. Engineer's Printed Name JEFFREY A. GARNESS Date Cj/~'q/iliP COSA Fee $  Date of Payment (Rev. 11/05) Waiver Fee $~'~3-~ Date of Payment Receipt Number '¢ Robert E ,Johns, Jr. & Assoc. ~ ~ ANCHORAGe, ~A~A 99504 m,~ ~, ~ ~ ' Scale: Rec. Lot S,F, Rec, Plot ~Je"No. FOUNDA~ON AS-BUILT ~ ~ ~ ~.~ ~. ~ ~ ~ ~ Dote Su~eyed: Drown b~ Checked ~"" ~' ~ ~~ Mountain Park Estates D ~OT ~u~ ~R~ ~E $~B~S ~ R~L ~C~RE A~BUILT O FOIJND REBAR ~--e~ WOOD ~NCE ~ OONCRE~ ~ P~T ~ . . . AS-BUILT . . , LOT ~R~, . - TOPOGRAPHY ~ ~eUlgT ,.. .o coR.~s sIT ~ ~R~ ~-~[T ~o C~ ~ . ~ ASSUMED E~V._~ X X METAL FENQ~ ~ ..... WOOD ,DECK,, PLOT P~S a LOT ~R~ NO~: IT IS ~E RESPONSIBILITY OF ~E BUILDER OR OWNER, PRIOR TO ONLY THOSE IMPROVEMEN~ ABO~ GROUND AND VISIBLE WILL CONS~UCTION, TO VERI~ PROPOSED BUILDING GRADE RELATIVE SHOWN. FENCES, ~LLS, SEP~C CLEANOU~, SIDEWALKS, T0 FINISHED GRADE AND UTJLI~ CONNECTIONS AND TO DETERMINE ETC., ARE SHOWN IN THEIR APPROXIMATE LOCA~ON, ONLY. SNOW ~E EXIS~NOE OF ANY EASEMENTS, CO~AN~ OR RES~IC~ONS MAY PREVENT SOME IMPRO~MENTS FROM BEING SEEN AND LOCA~D. WHICH DO NOT A,PPEAR ON THE RECORDED SUBDIVISION PLAT. ALL DISTANQES ARE R~OORD UNLESS OTHERWISE NOTED. UNDER NO CIROUMSTANCES SHOULD AN AS-BUILT BE USED F~R OONS~UCTION OR FOR ESTABUSHING BOUNDARY OR FENCE LINES. ~E SUR~YOR T~ES R~O~SI~LITY FOR THE INITIAL TRANSAC~ON ONLY AND ASSUMES FINANCIAL LIASILI~ ONLY FOR THE OOST OF THE SURLY. LIS~D DISTANCES PREVAIL O~R SO.ENG. R~RODUC~ON MAY CAUSE ERRORS IN SCALE. Municipality of Anchorage Development Services Department Building Safety Division On-Site Water and Wastewater Program 4700 Elmore Street P.O. Box 196650 Anchorage, AK 99519-6650 www.muni.org/onsite (907) 343-7904 Nitrate Advisory Certificate of On-Site Systems Approval # 101240 A Certificate of On-Site Systems Approval inspection and test of potable water was recently conducted on the well water supply on Block 5, Lot 4B of Mountain Park Estates subdivision. This inspection revealed a nitrate concentration of 7.66 milligrams per liter (mg/L) was reported for the property's well water sample. The Environmental Protection Agency (EPA) h~s ~-stablished a mammum contaminant level (MCL) of 10.0 mg/i~ f~-r public drinking water systems. While private wells are not subject to this regulation, EPA standards are based on existing health information and can therefore be used to gauge the relative quality of water from private wells. Please see the attached "Nitrate Fact Sheet" for important information regarding nitrate. This advisory must be attached to all copies of the subject Certificate of On- Site Systems Approval. GARN'ESS ENGINEERING GROUP, Ltd. CONSULTANT,S & GENERAL CONTRACTORS September 27, 2010 Municipality of Anchorage Development Service Department On-Site Water & Wastewater Program 4700 Elmore Road P.O. Box 196650, Anchorage, Ak 99519-6650 (907) 343-7904 Ref: Lot Line Waiver for Mountain Park Estates S/D; Lot 4B, Block 5, To whom it may concern: We request that your department issue a 1-foot lot line waiver from the south property line to the reserve drainfield. I am unaware of any adverse impacts this waiver would have on adjacent wells or septic sy~stems. If you have any questions, please contact us at 337-6179. Thank you for your assistancret /~cerel~, J ( ff~dAS' ~d&e Ga ssJP.E., M.S. Presi~d~n't i k'~ _.J' 3701 E. Tudor Road, Suite 101 * Anchorage, AK 99507-1259 Ph: (907) 337-6179 * Fax: (907) 338-3246 * Website: www.garnessengineering.com Page 1 of 1 Sonja Blewett From: Brian Wille [brian.willel@gmaii.com] Sent: Wednesday, September 29, 2010 5:52 AM To: Sonja Blewett Subject: Re: 13201 ridgeview drive Sorry about this. It is done and good to 42'° No perforations found with. camera. Thanks, On Sep 28, 2010 9:42 PM, "Sonja Blewett" <Sonia~gamessengineering.com> wrote: Hello, I was wondering if you have camera'd the well for 13201 Ridgeview Drive? Thanks a bunch Sonja Blewett Corporate Secretary/Treasurer Garness Engineering Group, Ltd. 3701 E. Tudor Road, Suite 101 Anchorage, AK 99507 Phone: (907) 337-6179 Fax: (907) 338-3246 Brian 9/29/2010 A+ HOME SERVICES , INC. 7501 E. 140th Avenue Anchorage, Alaska 99516 345-1890 , CUSTOMER Mike Fortuny INVOICE # Block Lot DESCRIPTION l%mf~ Septic & ~vitch ti,ldz AMOUNT 8/10 well liue Tank loceted TOTAL Gallons I~ Septic ~ Leach Ama Holding Tank PROBLEM AREA -- CALL FOR MORE INFORMATION NEEDS TO BE DONE AGAIN IN 6 MONTHS Good Shape [] Sludge buildup on bdttom Jim cap missing or [] Cut standpipe to 1,' above ground needs replacing )--- Standpipes 7-.~ Tim~ 'FI Floater on top [] Needs Septictrine APPLI IT FILLS OUT UPPER HA, 3NLY MaillngAddre~ ~ ~ ~-' Buyer ~/'/( C ~ ~ c~.~ ~ ~¢) r '+'~ Type of Resi~nce ~ Single Family ~ Multiple Family No. of Bedrooms ~ Other Water Supply  Individual A~ACH WELL LOG. A w~l Icg is required for all wells drilled since June 1975. Community For wells drilled prier to that date, give well depth (attach Icg if available). ~ Public Utility Sewer Disposal ~ Individual Year Individual Installed: Public Utility When Connected to Public Ut~ity: ~ Holding Tank NOTE: THE INSPECTION FEE MUST ACCOMPANY EACH RE~EST BEFORE ~OOESSING CAN BE INITIATED. Time Time Time Time Date Date Date Date Inspector Inspector Inspector Inspector RECEIVED ('"'"~) APPROVED BEDROOMS *CONDITIONS OF APPROVAL ( ) DISAPPROVED ( ) CONDITIONAL APPROVAL' DATE / (~ '-'~ -- ~ ~ Soils Rating Date Sewer Installed Well To Absorption Area Well Log Received 1 0 ~ ("~' Well to Tank Septic Tank Size / 72-023 September 21, 1982 Charles R. & Regina E. Rosenwinkel SRA Box 376-i~ Anchorage, AK 99507 Subject: Lot 4 B Block 5 Mt. Park Estates ApDroval for t'he individual sewer and wa'ter facil, ities cannot be granted until the following items have been completed: Tile water analysis report needs to be submitted to this office from the Chem Lab, 5633 B Street, for our review. The septic tank pu~npe¢~ with a receipt Sllbmitted to this department. An adequacy test needs to be performed on t'he existing leaching ares.. This test will determine if the system is adequate according 'to National Standards. A listing of private firms performing the test is enclosed. This reporh needs to be submitted to this office for our review. Please notify this Department for a reinspection when the noted discrepancies have been corrected. If there are any further questions, Dlease call this office at 264-4720. Sincerely, ~plgo/p/~ Enclosure Robert C. Pratt Associate Environmental Specialist ALASKA nul orlm nTAL CONTROL Inc. ~nclineerino ,f,- ~nuJ~'onmental Studies ~/~/~ MUNICIPALITY OF ANCHORAGE DF~T ~' ~":~ , ,~, ENVIRoi #,~::~i A~ ~ ,~ L'CrlON SAFECO TITLE COMPLY 3201 C STREET ANCHORAGE AK 99503 t~iT]' ? 1982 RECEIVED SELLER - CHARLES ROSENWINKLE SUBDIVISION-MT. PARK ESTATE BUYER-FORTUNY BLOCK-5 LOT-4B ADEQUACY TEST FOR SEWER SYSTEM THE TYPE OF ABSORPTION SYSTEM IS A TRENCH-CRIB WITH AN AREA OF 320 SQFT. THE SYSTEM IS CAPABLE OF ACCEPTING 450 GALLONS OF WATER PER DAY. THE SURGE CAPACITY OF THE SYSTEM IS 680 GALLONS. BASED UPON THE TEST DATA THE SYSTEM IS ACCEPTABLE FOR A 3 BEDROOM HOME. SEPTIC TANK ADEQUACY THE EXISTING SEPTIC TANK VOLUME OF THIS 3 BEDROOM HOUSE. ~>X:~ ..... ",.'.,. <o I, 1550 IS ADEQUATE FOR 1220 LUesl 25th Auenue · Anchorage, Alaska 99503 · {907) 276-1361 -- ~ ~ DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTIOI~I .... ' //_"~J ~~ml~/~"~"X 82E L Street- Anchorage, A aska 99B01 SEP2:8 1979 ~EQUE~T ~0~ APPROVAL OF INglVlDUAL WATE~ AND 8EWE~ FA01LITIE8 DJR~TION~: 0~mplete ~1t p~ on psg~ 1. In~mpl~t~ r~qu~/~ will not b~ pro~d Pl~8~e ~l owten {10) d~y~ for proae~ing, ' MAI LING ADD~ES8 ' - ~ ' -- ~ / - P~OPE'RTY RESIDENT (If different f~om above) r PHONE 2. BUYER~- ~ ~ · ~ -- MAILING ADDRE88 ' ~ MAI LING ADD~ESS ' . 4. REALTOR/AGENT ~ ~ - ~ PHONE MAILING ADDRESS . . . ___ . __ . __.' LET LOOATION ~ SINGLE FAMILY ~ One ~ Two ~ MULTIPLE FAMILY ~ Thr~e WATER SUPPLY ~ INDIVIDUAL* * T A TACH WELL LOG. A wel log is required for a wells drilled [] COMMUNITY since June t975, For wells drilled prior to that date, § ye well [] PUBLIC UTI LITY depth (attach tog f ava ab e,) 8. SEWAGE DISPOSAL SYSTEM ' ' ' [] INDIVIDUAL/ON-SITE** **If individual/on-site, give installation [] PUBLIC UTI LITY If system is over'two (2) years old an adequacy test is req(Ji~ed by this Department NOTE: THE INSPECTION FEE MUST ACCOMPANY EACH REQUEST BEFORE PROCESSING CAN BE INITIATED, [] Four [] Other, [] Five [] Six 72-010(3/78) 2204 Cleveland Ave. P.o, Box 10-1126 Anchorage,AK. 99511 277- 0231 CONSTkUCTION TE:ST L. itB MATERIALS TESTING ' QUALITY CONTROL SOILS ENGINEERING 710 Third Ave. P.O. Box 2540 Fairbenks, AK. 99707 4§2-1267 · 456-5155 SEPTIC SYSTEM ADEQUACY REPORT JOB NO. 79-27'] DATE OF REPORT 10-15-79 DATE OF TEST 10-11-79 LEGAL DESCRIPTION ' LOT 4B OR __ ) BLOCK 5 SECTION Mt. Park Estates , T N, R W, SUBDIVISION S.M. , ALASKA PERFORMED FOR; Don Delk SRA Box 372C Anch., Ak. 99507 344-6760 PHONE NO. REQUESTED BY: Same PHONE NO. TYPE OF SYSTEM ' NUMBER OF BEDROOMS SEPTIC TANK WAS PUMPED ~ YES [] NO ABSORPTION RATE: AVERAGE 24 HOURS 50 SURGE RATE.' 125 GALLONS IN .] .~ )t~5] SEPTIC TANK - SIZE · ] CRIB OR SEEPAGE PIT [] LEACH FIELD 2 1000 GALLONS GALLONS. MINUTES. NOTES & OBSERVATIONS' TEST PERFORMED __ REPORT PREPARED BY: APPROVED BY; . (Fill out in Triplicate) house ~ ~ ~ , n . /, b. Detepgent Well data: ' ¢. Casing Size 6j Distance from well to closest existinK 3. ~eepage Aree~/.'~ / 4. Cesspool' 5. Property Line_~. 6. Other sources of possible contamination, i.e., creeks, lakes, houses, barn, drainage ditch, etc. Sewage disposal system. a. Age of system ~ ~.0-~, . b. Septic tank capacity in gallons c. Name of septic tank manufacture.p: o3,4 1. If "home made" show diagram on reverse side of this form. Disposal field or seepage pit size and type .... ~C~_~-~. _ " 1. Distance to property line to house foundation . .' * THIS SIDE FOR OFFICIAL USE ONLY DATE RECEIVED , " - INSPECTION APPOINTMENTS Ti'ME ' ' TIME ' DATE DATE DATE INSPECTOR I NSPECTO~ · ' INSPECTOR DIRECTIONS: ' 1. TYPE OF RESIDENCE NUMBER OFBEDROOMB ' [] SINGLE FAMILY [] ONE [] THREE [] FIVE [] OTHER [] MULTIPLE FAMILY [] TWO [] FOUR [] SlX 2. WATER SUPPLY PERMIT NUMBER [] INDIVIDUAL DEPTH'OF WELL , r i [] COMMUNITY .... DATE DRILLED [] PUBL C UTILITY , Connection Verified, , LOG RECEIVED , 3. SEWAGE DISPOSAL SYSTEM PERMIT NUMBER [] INDIVIDUAL/ON -SITE DATE INSTALLED ~ []PUBLIC UTI LITY · C~)nnect on Vet f ed INSTALLE~ []Septic Tank or [] Holding Tank Size: . if Tank is homemade SOILS RAT NG ' give dimensions: , ' ' ~'Y'pErO F TANK MANUFACTURER ' ' TO'~AI- ABSORPTION AR EA MATERIAL ....... ~, DIS1~A CES · N sept clH° d ng Ta~ll~ I'Abs°rPt °n Area ISew~'Line ' INearest LOt L ne WELL TO~ A'bsorption Area to nearest Lot Line ' ~PPROVED FOR~ ~ BEDROOMS [~] ' CON DITIONAL ~PPROVAL (letter must accompany certificate) [] DISAPPROVED / / 72-010 (Rev. 3/78) e, Peraola t Jori Test f. Percol;~tion Test performed by Use the reverse side of this form to show dis[ram. Dis?ram should include the following informaticm: p~roperty linea;.well location, house location, septic tank location, disposal area location, location of percolatic~-~ 'kes~, and direction of ground slope, 9. The [nformatJ.on on this form is true an~] correct to the best of my knew!edge. ~i[:matu~e of Applicant Date S'gned TO BE FILLED OIJT BY HEALTH DEPART~.~ENT PERSOI~[NEL Conditions: The above described sanitary facilities are dJE;epproved for the followin[! Approval is valid for one year following the date of approval. CPJ: aw