HomeMy WebLinkAboutMOUNTAIN PARK ESTATES #2 BLK 2 LT 12Onsite File 2 0"07c=022-1 Municipality of Anchorage Community Development Department Page 1 of 3 On-Site Water&Wastewater Program 4700 Elmore St. •P.O. Box 196650 Anchorage, AK 99519-6650 •http://www.muni.org/onsite•(907)343-7904 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP191053 PID Number: 017-022-12 ❑ New •Upgrade Name: MATTHEW MAHONEY ABSORPTION FIELD Address: ❑ Deep Trench ❑ Shallow Trench • Bed ❑ Mound 7301 DEARMOUN ROAD*ANCHORAGE, AK ❑ Other Phone: No.of Bedrooms: Soil Rating: Total Depth from original grade: 306-979-6359 3 "1.0 GPDisg.Ft. SEE DWG. Ft Depth to pipe invert from original grade. Gravel depth beneath pipe: LEGAL DESCRIPTION SEE DWG. Ft 0.5 Ft Subdivision: Block: Lot: Fill added above original grade: Gravel length: MOUNTAIN PARK ESTATE#2 2 12 SEE DWG. Ft 30+ Ft. I ownship: Range: Section: Gravel width. Beds Number of lines: Distance between lines. 15 Ft Ft SEPARATIONDISTANCES Total absorption area- Number of trenches: Dist.between trenches: To Septic Absorption Lift Holding PubliciPrivate From Tank Field Station Tank Sower Lines 450+ SD Ft 1 - Ft Well 100'+ 100'+ 100'+ - 25'+ TANK ■ Septic ❑ S.T.E.P. ❑Holding ❑Other - Manufacturer: Capacity: Surface Water 100'+ 100'+ 100'+ - INFILTRATOR 1060Gal ? Material. Number of compartments Lot Line 5'+ 10'+ 5'+ N/A HDPE 2 Foundation 10'+ 10'+ 10'+ LIFT STATION _ Curtain Drain Manufacturer Capacity. NONE KNOWN INFILTRATOR/QUANICS 540 Gal ) Remarks: OLD TANK DECOMMISSIONED PER UPC PER CONTRACTOR 'Pump on'level at: 'Pump off'level at High water alarm at �•' TIMER TIMER 42" `THIS IS A CAT II QUANICS AEROCELL SYSTEM Pump Make 8 Model: Electrical Inspections performed by SEPTIC TANK WAS INSTALLED ON 3/15/21019.PUMP TANK,AEROCELL GOULDS PE-51-M MOA -g—') UNIT,AND DRAINFIELD UPGRADE WERE INSTALLED 4/8-9/2019. PIPE MATERIAL D3034/ k to SCH.40 PVC 1785/ Tan House to tank EXISTING/D3034 Tankftld SCH.40 PVC 2665 draiInstaller WILCO EXCAVATION Drainfield D3034 CO/MT D3034 Inspector GEG, Ltd. BENCH MARK (Assumed elevation) 100.00 Ft. Inspection Dates: 1st 3/15/2019 2nd 4/8/2019 Location and Descrip on 3rd 4/8/2019 4th 4/9/2019 BOTTOM OF TRIM AT NE CORNER ENGINEER'S SEAL Community Development Department Approval oQo�Oo�\ OFA ',4p Conditional approval: Date: a'Q'• 0 • ��Q c2.. 49 HA` ...T.,00 • - 6 t- -, t --. UQ '•.J- fr: • >•G.aPr&n.g e ga - - -' o.1 . . CE–w9• 000 L( Z217 Approved: Date: LICENSE rofesstof #AECC884 000006 Inspection Report_1-1-12 doc / PERMIT NUMBER PARCEL ID NUMBER: OSP191053 RECORD DRAWING 017-022-12 y � 1 I 1 `� NOTE:PER THE CONTRACTOR, `� EXISTING STNA 1 -- -----` `� DECOMMISSIONED EPTIC CF.TEA UK PWC S _ __,_------------- (TANK HAULED OFFSITE) I THE ` ii `��� NEW 1060 2-COMPARTMENT I `• 1 INFILTRATOR SEPTIC TANK 1 ' I Q ` ` 1 DOUBLE CLEANOUTS(DBL1&DBL2) i' I Q 100' •`/JEU-RP�pNS \`� 1i INSTALLED POLYLOK 11 1 O \\i FLOW DIRECTOR(FD) �1 N I 1 71 �+- 1\ EXISTING 1 i/� 1 �` 1977 TRENCH L_-- 1 VJ I I C/ i 1� ^-I \VS i 11 N , , w , , . .4* CO6 w\ `S Q Nt*", i 1 •'S •�i •1 T5 I / �\ • 1� .:pCo 1 M t.1 NEW 540 INFILTRATOR ` i I PUMP TANK WITH QUANICS i �/ `� 1 / G �' i I �j PUMPS/CONTROL Q \• rte'(\N �.' , et 40. EIC\pa00M : 1 c' n'2.,` • �� / VISUAL 1 O W Q I,``` 1�1 EXISTING WELL \\\\� IPORTCTION 1 ��,, ACo3? W (VP ) 1 '`,, cal J N 1 •• . NEW CAT II / ' 1 i � J �,� 1 1 ✓fy'•• ATS 6 AC \� .'•' ;' AEROCELL UNIT NEW 15'X 30'DRAINFIELD • 2 I 1 --- _ •.• / I D \ I i ------------ - •• ; DOUBLE CLEANOUTS(DBL3&DBL4) I o �\ i , i ' I � 1 ,�' ` I/ A B f I --------------- A B DBL1 43.2 54.4 FCO 19.0 5.2 DBL2 45.1 56.3 DEARMOUN ROAD ST1 35.6 30.8 MT1 48.6 58.9 --/ _ -------------------ST2 39.8 35.8 -MT2 44.5 59.4 ----- DBL1 42.0 38.4 MT3 76.6 88.6 DBL2 42.8 39.5 CO2 76.2 88.4 ,'' N FD 45.2 42.2 CO3 75.2 88.7 �' NOTE:THE PUMP TANK MAY ENCROACH CO1 42.4 41.2 C04 74.5 89.2 ' SLIGHTLY ON THE 1977 TRENCH.LOCATION MI-I1 39.3 40.5 MT4 74.3 89.1 S ALE: WAS APPROVED BY TIM EKLUND WITH THE VP1 36.7 46.5 C05 46.0 43.6 MOA ONSITE DEPARTMENT ON 4/9/2019. 1•=40' POD1 39.3 49.6 CO6 72.8 74.4 POD2 41.2 51.9 MT5 72.6 74.5 - -r 1 1 1 1 ♦.(c, OF . 44/h 4 111 fi ♦1• 1 t GARNESS ENGINEERING GROUP, Ltd • 4' •�* •• ENGINEERING-,SALES CONSULTING -- - --- -- 00 3701 E.TUDOR ROAD,SUITE 101•ANCHORAGE,AK 99507•PHONE(907)337.8179•FAX(907)336-3246'WEBSITE:www.gamessengileering.com \!•• •• aC f,_, PREPARED FOR: PHONE NUMBER: PAGE NUMBER: ~•f^ ,' ' = 'SS i AX CIO MATTHEW MAHONEY 360-979-6359 2 OF 3 /•J,;•.... C - ' • .' PROJECT/LEGAL DESCRIPTION: •DRAWN BY: �♦ . l • <C/N-� MOUNTAIN PARK ESTATES S/D#2; BLOCK 2,LOT 2 J.L.M. 1/ ♦ ••'�O���ll,•����•••• }(`.�P\, �• TYPE OF WORK: DATE: LICENSE 11•1 ESS` 4•• RECORD DRAWING OF SEPTIC TANK UPGRADE 4/15/2019 LICENSE ����� J / PERMIT NUMBER PARCEL ID NUMBER: OSP191053 RECORD DRAWING 017-022-12 i MYSPY WIFI MESSENGER UNIT SJE RHOMBUS INSTALLER FRIENDLY QUANICS AEROCELL ATS-6-AC TREATMENT MODULE (REMOTE MONITORING SYSTEM) A SERIES(IFS)TIMED CONTROL PANEL WITH INTERNAL DIVIDER WALL AND CLEANOUTS 4'BY 4 WIDE RIGID DBL3&DBL4 W ,...-1 DBL1&DBL2 TOP OF MANHOLE INSULATION CENTERED 4'BY 4 WIDE RIGID =98.94 OVER PIPES INSULATION CENTERED Z OVER PIPE i FINAL GRADE Q FINAL GRADE=99.20± POD1PGD2\=98715EE NFILTRATOR # # �.• co i 2 MH _ .. , ± li CO Q1 7 4, 4,ii. ._. 4, W ' ce r \. z- OZQZ • m TOP OF aU Zm wM -•; uiv TANK `:; a a a o 0 I! • TOP OF TANK =94.34 1111 ::® 20% I @ OUTLET=95.37 eor RETURN .,: . • rTt r ■.. ! - . . . . i•i�l� TODRAINFIELD TOP OF TANK ` '' �, ��� „OR PUMP VAULT @ INLET=95.35 2'OF INSULATION r- (PER CONTRACTOR) \ 1 11.4 s 1.25"SUPPLY LINE WEEP ' HOLE �IMMESSIMISIMI 4"RECIRCULATION LINE w INLET ' I� in IFI im 1■2Alw In J r — , '. - TIMER OVERRIDE FLOAT u W L3 Z_ INVERT OF PIPE HIGH WATER FLOAT 3 @ INLET=94.72 LOW LEVEL CUTOFF z PI PI 0 q '. VII ; FLOAT(ON/OFF) h I:: 0 NEW IM-1060 GALLON 2-COMPARTMENT �II_ 1 - IM-540 GALLON SINGLE COMPARTMENT �/ �g Z INFILTRATOR TANK INSTALLED ON 315/2019 1 J INFILTRATOR PUMP TANK Z Z L N f9// GOULDS PESIM PUMP UO•^ O W 1] jj \ILI "-if •• ...0...... . ' CINDER BLOCKS FOR PUMP PEDESTAL M >- INVERT OF PIPE INVERT OF PIPE W J� Y W @ OUTLET=94.45 @ INLET=94.09 r, (/),•-,g 0 w M+rl o –I U CO2 �1 CO a m 0 MT1 NOTE:ENTIRE MOUND CO3 MT4 ��..) W FINAL GRADE=100.76 100.97 DBL3 DBL4 8 H Q �r � � HAS TOPSOIL AND SEED_._ Jt1 ,I. w 0 0 v Z cn H OPeS 2"OF INSULATION INVERT OF 4"DISTRIBUTION LINES=97.87 3' S�Op q5 ' [Z] W 0 Q t� 3:1 S� FS O VD s w c9 Z FROM ATS-6-AC AEROCELL UNIT – - - 7,7 v1 CL .;!: ;!;!: :•..-... : :! 1: .:•:•:!:!!:!:!:!t!!!:! :.:.:la:11:. .: !:!: :! ! !:!:!:! !:!:!:!: !: :!:•c '. .: w T H a U r N Z '.f• '��� BOTTOM OF DRAINROCK/ � .•`•: \.� .SAI :��` ," • u; U ~A• LL TOPOF SAND FILTER= 7. 7 O 9 3 O ,.' W - O 'f• .{��' Y4 � FEET ", :.tOF MOA APPROVED SAND FILTER\ •,...,:`_�� ;�. ,;;`• � 2 wcc .. ;�.. • , + .• iii �: . w �S J .._: .T. ..j•\ V'�S. .`•s, . ,• .\ ♦ V • . \/ t• f4••?'•Z; .tom •Y.w•� -4\..OLD MONITORING DRAINFIELD ELEVATION IN .*- _- ...T.Aq•• AV i •,...�♦ OLD MONITORING TUBE=93.37 1, LIMITS OF EXCAVATION AND i • 4• /� �.* ♦, REMOVAL OF CONTAMINATED MATERIAL=92.61-93.11 • TIM EKLUND WITH MOA ONSITE PRESENT FOR INSPECTION AND 1 ♦1'^•,••J: rey •. " amess APPROVED LIMITS OF EXCAVATION BOTTOM OF 1977 TRENCH 2"MONITORING TUBE(MT1)=87.15± ♦��,' C 79 3 a (INSTALLED ON 3/1/2019)DRY ON 3/4/2019,3/6/2019,&3/25/2019 .•(<1)...'•SFO,••// -?/iC�;•pRoF �< � • LICENSE•♦111 \SS\ •••• #AECC884 2 8481E W Lot 11 co co 30 N89°56'06"W 216.00 of 50 ,t, L 15'1 o O p O < CD .� O O 2.0 OH _ CO Septic vent(typ) W ct O 0 o eli 4 •, ND 2.0 Chimney OH Manhole E c 54.8 A 112Nose 'o p a me a ta AB.o 108.2 CC) W F 0 en W p ' i Z -- ..c0'� 0 0- �Q MO 9, `2.0 OH E O J J ° � L �n O J �/ _ Op c-> a w Z = Z c.; I 30 . a a I 50 N89°56'06"W 216.00 il . in 0 I DeARMOUN ROAD RECERTIFIED 4-12-19 z-'(-) RECERTIFIED 3-20-19 AS-BUILT NO CORNERS SET THIS DATE %`"`\� A 1 ' I hereby certify that I have performed a Mortgagee's inspection P�� � •F • . . A , of the following described property: LOT 12. BLOCK 2. � ..• •S,� I, MOUNTAIN PARK ESTATES SUBDIVISION No. 2 Cr):11. 49th 'IOp. l'N ••9 O {• .* / Anchorage Recording District,Alaska,and that the improvements situated thereon are within the property lines ••• •• •� • ��• and do not overlap or encroach on the property lying / lizabeth L. Walotka . / adjacent thereto,that no improvements on the property lying , 'PI, 8036. • - LS .•• � on the premis in that there are reto noencroach roadways transmission 1 nesQstion oreother and SCALE: 1��—— 40' ,, ••�• y Al visible easements on said properly except as indicated n. 4 k eFESsio tM- �*� Dated at Anchorage,Alaska EASEMENTS OF RECORD, OTHER THAN , ���� this 5th day of_MARCH ,2019. THOSE SHOWN ON THE RECORDED FB 19-2, pg 474.- 17 —t CI FRED WALATKA&ASSOCIATES.L.L.C. PLAT ARE NOT SHOWN HEREON. FB 19-1, pg 45 Engineers and Surveyors UNLESS OTHERWISE NOTED FB 19-1, pg 40 BE 907-248-1666 MUNICIPALITY OF ANCHORAGE ,z,cnr. On -Site Water & Wastewater Program PO Box 196650 4700 Elmore Road Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997 http://www.muni.org/onsite v 1. Departnient On -Site Wastewater Disposal System Permit Permit Number: OSP191053 Effective Date: 3/14/2019 Work Type: Septio Upgrade Expiration Date: 3/13/2020 Tax Code Number: 01702212000 Site Legal Address: MOUNTAIN PARK ESTATES #2 BLK 2 LT 12 G:2839 Site Mailing Address: 7301 DE ARMOUN RD, Anchorage Owner: DUNFORD RICHARD C Lot Size in Sq Ft: 23760 Design Engineer: GARNESS ENGINEERING GROUP LTD Total Bedrooms: 3 This permit is for the construction of: 56 Disposal Field Q Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage All construction shall be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80) 3. The wastewater code requires inspections during the installation. The engineer shall notify the Development Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather shall be either: a. Opened and Closed on the same day, or b. Covered, sealed, and heated to prevent freezing Received By: �— Issued By: Date: 31-51111 Date: 3 % I MUHMpQUTYOF Community Development Department Development Services On -Site Water & Wastewater Program Mayor Dan Sultho On -Site Sewer/Well Permit Application For A Single Familv Dwelling Parcel I.D. 6 � 10 22r 1100 Property owner(s) RICHARD DUNFORD Mailing address 7301 DEARMOUN ROAD, ANCHORAGE, AK 99516 Site address SAME AS ABOVE C/O MATTHEW MAHONEY (BUYER) . Day phone (360) 979-6359 Legal description (Sub'd, Block & Lot) MOUNTAIN PARK ESTATES #2; BLOCK 2, LOT 12 Legal description (Township, Section & Range) Lot Size APPLICATION IS FOR: ( ® all that apply) Absorption Field FA Septic Tank Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage ❑ Sq.Ft. Number of Bedrooms APPLICATION IS AN: Initial ❑ Upgrade Renewal ❑ 3 THIS APPLICATION INCLUDES A VARIANCE/ WAIVER REQUEST FOR: NONE TYPE OF DEWELLING: Single Family (SF) (w/wo ADU) Duplex (D) ❑ Multiple Dwellings ❑ (SF and/or D) Distance: — I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal codes. GARNESS ENGINEERING GROUP, Ltd. (Signature of property owner or authorized agent) Permit/RushFees: IT0o # � 3 7 o Waiver Fees: Date of Payment: U 90 0�03 11 Date of Payment: Receipt Number: I�b61�� O$' -(03G Receipt Number: Permit No. oar IQ 10 S3 Waiver No. (Rev. 01/11) April 3, 2019 Municipality of Anchorage Development Services On -Site Water & Wastewater Program 4700 Elmore Road Anchorage, Alaska 99507 Phone: (907) 343-7904 Attention: Rebecca Carroll Reference: Quanics Aerocell System and Drainfield Upgrade for Mountain Park Estates S/D #2; Block 2, Lot 12 Ms. Carroll: The 3 bedroom house on the referenced property is served by a private well and septic system. On March 14, 2019, you issued a septic tank upgrade permit based upon our design (Permit Number OSP191053). The new septic tank was installed on 3/15/2019 and was inspected by GEG. As part of our design, additional cleanouts were required to be installed to verify the accuracy of the septic adequacy test performed on the 1983 drainfield. After the installation of these cleanouts, it was found that the liquid level elevation in the monitoring tube was at the invert of the cleanouts and the house has been vacant for an extended period of time. We also attempted to test the 1977 trench which did not pass an adequacy test as well. In short, both the 1977 and 1983 drainfields are technically failed. The 1983 drainfield appears to be absorbing water without back into the septic tank; however, the absorption appears to be occurring above the invert of the distribution lines. Based upon this information, the drainfield will need to be upgraded. It may be possible to rebuild the existing 1983 drainfield; however, we have discussed this with the buyers, and they have opted to have an advanced wastewater treatment system installed with a new drainfield. The 1983 drainfield is 53'+ wide x 26'+ long with 6" of effective and we are proposing that the a new drainfield be installed within the footprint of this drainfield. We are proposing that the new drainfield be installed 2 foot higher in elevation than the existing 1983 bed bottom elevation. We are proposing the contractor shoot down the monitoring tube for the 1983 drainfield to establish this elevation, excavate a 30 foot long by 15 wide area to the bottom of the 1983 drainfield, remove all contaminated material in the excavated area, install 2+ feet of MOA approved sand filter, and then installed clean, washed drainrock on top of the sand. We are also proposing to utilize a Cat II Quanics Aerocell system for this property that will consist of using the new 1060 2 -compartment Infiltrator septic tank that was installed on 3/15/2019, installing a new 540 Infiltrator pump tank (equipped with Quanics pumps & controls) after this tank, and installing a new Quanics ATS -6 -AC Aerocell unit on top of the proposed drainfield. We are requesting the existing sewer permit (Permit Number OSP191053) be amended to include the installation of the Quanics Aerocell System and the new drainfield. Comments regarding the design are summarized as follows: 3701 East Tudor Road, Suite 101 * Anchorage, Alaska 99507-1259 Phone: (907) 337-6179 * Fax: (907) 338-3246 * Website: www.garnessengineering.com Page 2 of 2 1. SOILS: Attached is a soil log that was performed by Lee Reid, P.E. prior to the 1983 drainfield installation. Mr. Reid performed a percolation test between 1.5 to 2.0 feet that had a percolation rate of 47.6 minutes/inch. According to the 1983 inspection report, the drainfield was installed at a depth of 3 feet. Based upon Mr. Reid's percolation rate, we are proposing to use a 1.0 gpd/sq.ft. application rate. 2. DRAINFIELD DESIGN: See attached design drawing for drainfield specifications. 3. SURFACE WATERS: There are no surface water concerns. 4. TOPOGRAPHY: The topography in the area of the existing and proposed drainfield is generally flat. There are no cutbanks or steep slopes with 50 feet of the proposed drainfield. In short, the there are no slope concerns with this installation. We are unaware of any adverse impacts this installation would have on adjacent wells or septic systems. If you have any questions, please contact us at 337-6179. Thank you for your assistance. 3701 East Tudor Road, Suite 101 * Anchorage, Alaska 99507-1259 Phone: (907) 337-6179 * Fax: (907) 338-3246 * Website: www.garnessengineering.com GARNESS ENGINEERING GROUP, Ltd ENGINEERING SALES CONSULTING March 11th, 2019 Municipality of Anchorage Development Services On-Site Water & Wastewater Program 4700 Elmore Road Anchorage, Alaska 99507 Phone: (907) 343-7904 Reference: Septic Tank Upgrade for Mountain Park Estates S/D #2; Block 2, Lot 12 To whom it may concern: The 3 bedroom house on the referenced property is served by a private well and septic system. Per MOA records, the original septic system serving the subject property was installed on 8/291977 and was sized for 3 bedrooms. A new drainfield was added septic system on 10/17/1983 with inspection report showing the 1977 septic tank remaining to be used. The septic system consists of a 1000 gallon steel septic tank, a deep trench type drainfield (30 feet long with 7.5 feet of effective) and a bed type drainfield (53'+ wide x 26'+ long with 6" of effective). New monitoring tubes have been recently installed in both the trench and bed drainfields. The house has been vacant and a presoak and septic adequacy test has been recently performed on the 1983 bed drainfield. This bed drainfield appears to have passed a septic adequacy test, however the septic tank is 41+ years old. Per the MOA policy, septic tanks over 30 years old must be physically inspected and deemed structurally sound or be replaced. Given the age of the tank, replacement is our recommended course of action. We request a septic tank upgrade permit be issued. We are proposing that the contractor install new cleanouts and an additional monitoring tube in the bed type drainfield as shown on the design. Once these cleanouts are installed or when the distribution lines are exposed, all distribution lines in both the trench and bed should be jetted and cleaned by a professional sewer service company. Once we have these cleanouts and the additional monitoring tubes installed, we will verify elevations in the bed to confirm the septic adequacy test was performed accurately. Please do not h- itate to call us at 337-6179 if you require further information. Thank you for your assistanc= CJtriirel , (jr dr y, A / arness, P.E., M.S. Preidet� 3701 East Tudor Road, Suite 101 *Anchorage.Alaska 99507-1259 Phone: (907)337-6179*Fax: (907)338-3246*Website: www.garnessengineering.com I J 1 n 10 I co r +� I W iz Icn I j I I I I I I I I ! ' APPROXIMATE LOCATION OF HOLDING TANK— ?,Noll EXISTING WELL EX\5Vp0M 3803se NOTE: PER THE CONTRACTOR, THE EXISTING SEPTIC TANK WAS DECOMMISSIONED PER UPC. (TANK HAULED OFFSITE) NEW 1060 2 -COMPARTMENT INFILTRATOR SEPTIC TANK INSTALLED ON 3/15/2019 INSTALLED DOUBLE CLEANOUTS (DBL1 & DBL2) ON 3/15/2019 DURING NEW TANK INSTALLATION INSTALLED POLYLOK FLOW DIRECTOR ON 3/15/2019. v I I i i i PROPOSED DRAINFIELD (SEE DESIGN CRITERIA AND DETAIL PAGE 3 OF 3) EXISTING 1983 DRAINFIELD i APPROXIMATE LOCATION _/ OF LEE REID TEST HOLE J L-- NUMBER OF BEDROOMS: 3 EXISTING PERCOLATION RATE/S: 47.6 1977 TRENCH. PROPOSED APP. RATE: '1.0 GPD/SQ.F.T D_EARM OU NROAD MINIMUM DRAINFIELD SQ.FT.: 450 'USING A CAT II QUANICS AEROCELL SYSTEM MT DRAINFIELD DESIGN: PROPOSED —INFILTRATOR PUMP TANK WITH QUANICS PUMPS AND CONTROLS —PROPOSED I QUANICS ATS -6 -AC' AEROCELL UNIT I Z W IL i IQ I� W I ,J 2 i APPROXIMATE LOCATION _/ OF LEE REID TEST HOLE J DESIGN CRITERIA: NUMBER OF BEDROOMS: 3 GALLONS PER DAY (GPD): 450 PERCOLATION RATE/S: 47.6 PROPOSED APP. RATE: '1.0 GPD/SQ.F.T D_EARM OU NROAD MINIMUM DRAINFIELD SQ.FT.: 450 'USING A CAT II QUANICS AEROCELL SYSTEM --------- _ _ _ _ - DRAINFIELD DESIGN: MAXIMUM DEPTH: SEE DETAIL DRAWING N WIDTH: 15 FEET GEG, Ltd. HAS AN 8 PAGE SPECIFICATION LETTER LENGTH: 30 FEET THAT PERTAINS TO THIS DESIGN. BY PROCEEDING M.O.A. APPROVED SAND FILTER: 4+ FEET FORWARD WITH THIS INSTALLATION, THE EFFECTIVE: 0.5 FEET ENGINEER, WELL DRILLER, CONTRACTOR AND SCALE: REDUCTION FACTOR: N/A PROPERTY OWNER AGREE THAT THEY HAVE 1"= 40' READ THESE SPECIFICATIONS AND AGREE TO ACTUAL SQ.FT.: 450 ACCEPT THE TERMS AND CONDITIONS OUTLINED. — — — — — — — — — — — — — — — — — I I GARNESS ENGINEERING GROUP, Ltd ENGINEERING o SALES o CONSULTING --- 3701 E. TUDOR ROAD, SUITE 101 - ANCHORAGE. AK 99507 - PHONE (907) 337-6179 - FAX (907) 338-3246 - WEBSITE: w .gamessengineedng.wm PREPARED FOR: PHONE NUMBER: PAGE NUMBER: C/O MATTHEW MAHONEY 360-979-6359 1 OF 3 PROJECT/LEGAL DESCRIPTION: DRAWN BY: ll MOUNTAIN PARK ESTATES S/D #2; BLOCK 2, LOT j J.L.M. �, TYPE OF WORK: DATE: REIVED �.- DESIGN OF PROPOSED QUANICS AEROCELL & DRAINFIELD 4/4/2019 r so ��,p J. ff,eCy�.-7&r e . :�� /• Zi AV LICENSE S\,�� #AECC884 / APPROXIMATE LOCATION N I-Th I f I OF HOLDING TANK \ GEG,Ltd.HAS AN 8 PAGE SPECIFICATION LETTER THAT PERTAINS TO THIS DESIGN.BY PROCEEDING I FORWARD WITH THIS INSTALLATION,THE �\ ENGINEER,WELL DRILLER,CONTRACTOR AND NOTE:THE CONTRACTOR SHALL HAVE THE PROPERTY OWNER AGREE THAT THEY HAVE NORTH LOT LINE,AND ALL WELL RADII \\ READ THESE SPECIFICATIONS AND AGREE TO SHOWN FLAGGED BY A REGISTERED LAND ACCEPT THE TERMS AND CONDITIONS OUTLINED. J SURVEYOR PRIOR TO CONSTRUCTION. -- \\ j �\ \ 1 / I \ 1 \ I // I \• \ PROPOSED 1060 2-COMPARTMENT I • 1 INFILTRATOR SEPTIC TANK / I INSTALL DOUBLE CLEANOUTS RADIUS \ I I / I 100 WELL \ I EXISTING SEPTIC TANK TO BE 1 % 0N \\4 DECOMMISSIONED PER UPC I L.L IN I \ 71 '^ \ EXISTING L vJ 1 \ ; • 1977 TRENCH 1:L1 \ •ot°' (SEE NOTES) `\\\ W ��\ePD / 10 co CO I w T \\ I a ; .;; / I co INSTALL POLYLOK FLOW DIRECTOR/ INSTALLNEWCLEANOUTI-` AND MONITORING TUBEI _ IN THIS CORNER OF BED W / j r • 1 i W \ \J 1 I a I} / Y t\� \ EXISTING WELL EXISTING BED I -1 (/) .'�••• r, MT I ? J • \ (SEE NOTES) co :. .•..: ; L -J I o J I I • t INSTALL NEW EXISTING CLEANOUT. \\ ter`-- •-- •-'.; *: CLEANOUTS / EXCAVATE DISTRIBUTION 2 I\ --_________- .. (SEE NOTES)/ LINE AND INSTALL DOUBLE \\ :• !,• CLEANOUTS(SEE NOTES) / i J , L , / , , 1., ,, .. i; ...., .... , ... __ ...„ ._ .__ ... / - ____________ / I / I DEARMOUN ROAD / / NOTES: / 1.NEW MONITORING TUBES WERE INSTALLED IN THE 1983 BED AND 1977 TRENCH ON 2/28/2019. THE 1983 BED /// WAS PRESOAKED WTH 2500+GALLON OF WATER ON 3/5/2019 AND ON 3/7/2019,THE BED APPEARED TO PASSED ,/ AN ADEQUACY TEST.THE 1977 TRENCH WAS DRY PRIOR TO TEST AND REMAINED DRY DURING THE PRESOAK AND ADEQUACY TEST. 2.AFTER THE INSTALLATION OF THE NEW CLEANOUTS IN 1983 BED,THE CONTRACTOR SHALL HAVE BOTH THE S ALE: BED AND TRENCH DISTRIBUTION LINES JETTED AND CLEANED BY A PROFESSIONAL SEWER SERVICE COMPANY. Il 3.AFTER JETTING/CLEANING OF THE DISTRIBUTION LINES,THE CLEANOUTS AND MONITORING TUBE ELEVATIONS 1"=40' SHALL BE CONFIRMED TO INSURE SEPTIC ADEQUACY TEST WAS ACCURATELY PERFORMED. I ��.....Z.4 —401111hiiiii •41- \Jr 14.((.. ..4" GARNESS ENGINEERING GROUP, Ltd , •••• ••••• . .�.. •. �. ...• , ENGINEERING•SALES•CONSULTING • is 3701 E.TUDOR ROAD,SUITE 101•ANCHORAGE.AK 99507•PHONE(907)337-6179 FAX FAX(907)338-3246•WEBSITE:www.gamessengNee4ng.com •• •. • PREPARED FOR: PHONE NUMBER: PAGE NUMBER: 0 fn• '�' •'J ' '. Gam-- :4�i CIO MATTHEW MAHONEY 360-979-6359 1 OF 1 •�J, ..•. • CI-71 3 /' • PROJECT/LEGAL DESCRIPTION: DRAWN BY •••., 11 iq . MOUNTAIN PARK ESTATES S/D#2; BLOCK 2, LOT12 J.L.M. �1�♦♦ •• •••:.••• �•P�,:.• TYPE OF WORK: DATE: ,. � ��.• DESIGN OF SEPTIC TANK UPGRADE 3/11/2019 LICENSE84 %%walks STANDARD TANK CONFIGURATION - -- --- • • - -- - - "" — --1 Iii a rROM BOTTOM OF TANK. LAPmrvNENTS SUPPLY NOTE: 1. TANKS AND RISER ADAPTER RINGS ARE INFILTRATOR— PRODUCTS AND ARE SUPPLIED BY FERGUSON. 2. THE INSULATED RISERILID, PUMP, FLOATS, INTERNAL PIPING, GROMMETS, CONTROL PANEL, AND AEROCELL UNIT ARE SUPPLIED BY GARNESS ENGINEERING, THE ALASKA STATEWIDE DISTRIBUTOR FOR QUANICS INC. 3. ALL OTHER EXTERNAL COMPONENTS SUCH AS PIPING, FITTINGS, WIRING, INSULATION, ETC., SHALL BE SUPPLIED BY THE CONTRACTOR. INFILTRATOR TANK NOTES: • PER INFILTRATOR SYSTEMS, INC., THESE TANKS HAVE A MAXIMUM BURIAL DEPTH OF 48 INCHES OVER TOP OF TANK. • PER INFILTRATOR SYSTEMS, INC., THE TANKS ARE TO BE BURIED SO THAT THE INVERT OF THE OUTLET OF THE IM -1060 AND THE INLET OF THE IM -540 INFILTRATOR TANKS ARE NOT SUBMERGED DURING HIGH GROUNDWATER CONDITIONS. • GEG RECOMMENDS ALL PIPE PENTRATIONSMOINTS ASSOCIATED WITH THE INFILTRATOR TANKS BE ENCASED IN BENTONITE CHIPS. • IF GROUNDWATER IS ENCOUNTERED, THE CONTRACTOR SHALL CONTACT THE ENGINEER TO EVALUATE IF THE EXISTING SOIL COVER IS ADEQUATE TO RESIST BUOYANCY FORCES, OR IF ADDITIONAL BALLASTING WILL BE NECESSARY TO OVERCOME BUOYANCY FORCES. THE CONTRACTOR SHALL INSURE THAT SOIL COVER AND/OR BALLASTING IS PROVIDED AS OUTLINED IN THE INFILTRATOR "SEPTIC TANK BUOYANCY CONTROL GUIDANCE" BROCHURE. ELECTRICAL WIRE/S (SUPPLIED BY CONTRACTOR). SEE INSTALLATION MANUAL FOR SPECIFICATIONS FINAL GRADE (SEE NOTE) 4" CLEANOUT 4" CLEANOUT 4" OF INSULATION OVER TANKS " MAXIMUM INSTALLATION REGARDLESS IS RECOMMENDED ON ALL *48 OF BURIAL DEPTH INLET OPERATING LIQUID LEVEL (1,094 GALLONS) NEW IM -1060 GALLON 2 -COMPARTMENT INFILTRATOR TANK INSTALLED ON 315/2019 - KHUMBUS INSTALLER FRIENDLY SERIES (IFS) TIMED CONTROL PANEL WITH DRY CONTACTS FOR MYSPY WIFI MESSENGER UNIT 24" INSULATED LID SIM/TECH PRESSURE FIL IM -540 GALLON SINGLE COMPARTMENT INFILTRATOR TANK WITH INFILTRATOR PIPE ADAPTER RING - QUANICS AEROCELL CAT, 11 QUANICS AEROCELL SYSTEM CATEGORY 11 CONFIGURATION (3 TO 4 BEDROOM SYSTEMS) 4" BY 4' WIDE RIGID INSULATION CENTERED OVER PIPES - MYSPY WIFI MESSENGER UNIT (REMOTE MONITORING SYSTEM). INSTALLED IN HOUSE AS CLOSE TO INTERNET "BOX" AS POSSIBLE. � 80% RETURN 1.25" SUPPLY LINE 2" RECIRCULATION LINE WEEP HOLE *TIMER OVERRIDE FLOAT (38") - 475 GALLONS CAPACITY WHEN FLOAT IS ACTIVATED. - *HIGH WATER FLOAT (32") - 455 GALLONS CAPACITY WHEN FLOAT IS ACTIVATED � �— *LOW LEVEL CUTOFF / FLOAT (ON/OFF) - (20") - 261 GALLONS CAPACITY WHEN FLOAT IS DEACTIVATED. — GOULDS PE51 M FROM ALASKA PUMP OR EQUIVALENT (SUPPLIED BY GARNESS ENG.) 2 - 8" CONCRETE CINDER BLOCKS FOR PUMP PEDESTAL - STACKED SIDE B SIDE (SUPPLIED BY CONTRACTOR) QUANICS AEROCELL ATS -6 -AC TREATMENT MODULE WITH INTERNAL DIVIDER WALL AND CLEANOUTS 4" BY 4' WIDE RIGID INSULATION CENTERED OVER PIPE 20% 2" DISCHARGE LINE NOTE: MAKE THIS PIPE RUN AS SHORT AS POSSIBLE (<12") 4" VISUAL PORT 2X4 BUSHING TO DRAINFIELD OR PUMP VAULT *FLOAT NOTE: MEASUREMENT IS WHERE FLOAT WIRE ATTACHES TO PIPING WITH A 3.5 INCH MINIMUM TETHER FROM PIPING TO FLOAT. ALL FLOATS MUST BE NARROW ANGLE FLOATS. (SEE FLOAT INSTALLATION INSTRUCTIONS) NOTE: ALL PIPING FROM PUMP TANK TO AEROCELL MODULE SHALL BE PLACED ON SUITABLE BEDDING MATERIAL THAT IS MECHANICALLY COMPACTED. ALL LINES SHALL BE GRADED SO THAT THEY WILL DRAIN AFTER EACH PUMP CYCLE AND WILL NOT RETAIN ANY STANDING WATER. NOTE: ALL PRESSURIZED PIPES ARE TO BE SCHEDULE 40 PVC UNLESS NOTED OTHERWISE W Z O 2 Q Lu 2 OQ U 2i ¢0 w Ci w CL a7 L0 44" E E, NEW IM -1060 GALLON 2 -COMPARTMENT INFILTRATOR TANK INSTALLED ON 315/2019 - KHUMBUS INSTALLER FRIENDLY SERIES (IFS) TIMED CONTROL PANEL WITH DRY CONTACTS FOR MYSPY WIFI MESSENGER UNIT 24" INSULATED LID SIM/TECH PRESSURE FIL IM -540 GALLON SINGLE COMPARTMENT INFILTRATOR TANK WITH INFILTRATOR PIPE ADAPTER RING - QUANICS AEROCELL CAT, 11 QUANICS AEROCELL SYSTEM CATEGORY 11 CONFIGURATION (3 TO 4 BEDROOM SYSTEMS) 4" BY 4' WIDE RIGID INSULATION CENTERED OVER PIPES - MYSPY WIFI MESSENGER UNIT (REMOTE MONITORING SYSTEM). INSTALLED IN HOUSE AS CLOSE TO INTERNET "BOX" AS POSSIBLE. � 80% RETURN 1.25" SUPPLY LINE 2" RECIRCULATION LINE WEEP HOLE *TIMER OVERRIDE FLOAT (38") - 475 GALLONS CAPACITY WHEN FLOAT IS ACTIVATED. - *HIGH WATER FLOAT (32") - 455 GALLONS CAPACITY WHEN FLOAT IS ACTIVATED � �— *LOW LEVEL CUTOFF / FLOAT (ON/OFF) - (20") - 261 GALLONS CAPACITY WHEN FLOAT IS DEACTIVATED. — GOULDS PE51 M FROM ALASKA PUMP OR EQUIVALENT (SUPPLIED BY GARNESS ENG.) 2 - 8" CONCRETE CINDER BLOCKS FOR PUMP PEDESTAL - STACKED SIDE B SIDE (SUPPLIED BY CONTRACTOR) QUANICS AEROCELL ATS -6 -AC TREATMENT MODULE WITH INTERNAL DIVIDER WALL AND CLEANOUTS 4" BY 4' WIDE RIGID INSULATION CENTERED OVER PIPE 20% 2" DISCHARGE LINE NOTE: MAKE THIS PIPE RUN AS SHORT AS POSSIBLE (<12") 4" VISUAL PORT 2X4 BUSHING TO DRAINFIELD OR PUMP VAULT *FLOAT NOTE: MEASUREMENT IS WHERE FLOAT WIRE ATTACHES TO PIPING WITH A 3.5 INCH MINIMUM TETHER FROM PIPING TO FLOAT. ALL FLOATS MUST BE NARROW ANGLE FLOATS. (SEE FLOAT INSTALLATION INSTRUCTIONS) NOTE: ALL PIPING FROM PUMP TANK TO AEROCELL MODULE SHALL BE PLACED ON SUITABLE BEDDING MATERIAL THAT IS MECHANICALLY COMPACTED. ALL LINES SHALL BE GRADED SO THAT THEY WILL DRAIN AFTER EACH PUMP CYCLE AND WILL NOT RETAIN ANY STANDING WATER. NOTE: ALL PRESSURIZED PIPES ARE TO BE SCHEDULE 40 PVC UNLESS NOTED OTHERWISE W Z O 2 Q Lu 2 OQ U 2i ¢0 w Ci w CL a7 L0 E E, M 6� I? \ W 0) x Ill C) rn Z ' � LL m O N wco z0 z_i Q 0 REVISION: 1.30.2018 E E, \ ^^ MSI E Ow Y Q O L� M cn ° J Z N Z O Z W JA N Y Z) Z) WU)U "' O �o a J m P U) T ` w° J V Wa 4 _Zm cl) (f)U J Oo W O W Wzo F- < W W _Q 6, TIS w L Y ~ W y Q U < z LL Z Z O o aQ o 0� Y F— (r J_ ' �!:) U 00 Lu Z 0 LL �4 00 LL °Lu O a2 nnom REVISION: 1.30.2018 4" VISUAL INSPECTION PORT REMOVE ALL CONTAMINATED MATERIAL !UANICS ATS -6 -AC AEROCELL UNIT TION —TOP OF IMPORTED MOA SAND SHALL BE 4 FEET HIGHER IN ELEVATION THAN THE BOTTOM OF DRAINROCK IN THE EXISTING BED FEED LINE FROM PUMP TANK •f4" MONITORING TUBE • • 2+ FEET OF COVER REQUIRED. CONTRACTOR SHALL TOPSOIL AND SEED ENTIRE MOUND 050F RECIRCULATION LINE BACK TO PUMP TANK � I I a.. i QUANICS ATS -6 -AC Z I AEROCELL UNIT O I 4" SOLID PIPE H I U I W 1 a 1 U 1 z I J I I • f4" MONITORING TUBE v � �rl_ v(5�-DI NOTE: CONTRACTOR TO REMOVE ALL CLEANOUTS AND MONITORING TUBE FOR OLD DRAINFIELD AT COMPLETION OF NEW DRAINFIELD. -OLD DRAINFIELD. CONTRACTOR TO SHOOT DOWN MONITORING TUBE TO ESTABLISH OLD DRAINFIELD BOTTOM ELEVATION. DESIGN CRITERIA: NUMBER OF BEDROOMS: 3 GALLONS PER DAY (GPD): 450 PERCOLATION RATES: 47.6 PROPOSED APP. RATE: •1.0 GPD/SQ.F.T MINIMUM DRAINFIELD SQ.FT.: 450 'USING A CAT II QUANICS AEROCELL SYSTEM DRAINFIELD DESIGN: MAXIMUM DEPTH: SEE DETAIL DRAWING WIDTH: 15 FEET LENGTH: 30 FEET M.O.A. APPROVED SAND FILTER: 4+ FEET EFFECTIVE: 0.5 FEET REDUCTION FACTOR: WA ACTUAL SQ.FT.: 450 4" MONITORING TUBE — 0 4" CLEANOUT--/ "PERFORATED PIPE 4"CLEANOUT " PERFORATED PIPE 4" CLEANOUT 4" MONITORING TUBE* 2'26 FOOT LONG LATERALS - I 2' 30 FEET LONG GARNESS ENGINEERING GROUP, L ENGINEERING o SALES o CONSULTING,, 3701 E. TUDOR ROAD, SUITE 101 -ANCHORAGE. AK 99507' PHONE (907) 337-6179' FAX (907) 33&3246 • WEBSITE: www.gamessengineedng.com PREPARED FOR: PHONE NUMBER: PAGE NUMBER: C/O MATTHEW MAHONEY 360-979-6359 3 OF 3 PROJECT/LEGAL DESCRIPTION: DRAWN BY: MOUNTAIN PARK ESTATES S/D #2; BLOCK 2, LOT 2 J.L.M. TYPE OF WORK: DATE: REVISED �,_ DETAIL DRAWING OF PROPOSED DRAINFIELD 4/4/2019 VIDE 8481E w Lot 11 ao v co 30 N89°56'06"W 216.00 1 oI 50 L 15'1 ci O ott o ° 0 3O ,co Septic vent(typ) j (Y O 2.0 OH....oWell / tea.to...., n 2.0 Chimney OH C 54.8 A 112 Hose •o p W n F tem 48 0 108.2 _ w in o cg) 0 Z ++++ i� °O 10 M 2.0 OH m O J O 0 o 02 O J 0 / o `" ° lw Z = T Z N i 30 I 50 N89°56'06"W 216.00 0 0 � 1 DeARMOUN ROAD AS-BUILT NO CORNERS SET THIS DATE .A I I I hereby certify that I have performed a Mortgagee's inspection P`�• �F (,q i of the following described property: LOT 12. BLOCK 2. 4.:1 •,• ,S,�a, MOUNTAIN PARK ESTATES SUBDIVISION No. 2 `''.' .49th ) �':� �0 .* / Anchorage Recording District.Alaska,and that the ` //�• //• improvements situated thereon are within the property tines •• h�X.g and do not overlap or encroach on the property lying / t . lizabeth L. Walotka... / adjacent thereto,that no improvements on the property lying / adjacent thereto encroach on the premises in question and "_ sr� • 8036 - LS �� that there are no roadways,transmission lines or other SCALE: 1 = 40 •, `' visible easements on said property except as indicated • • • • • ' a� I I�(4IssiONA� �� Dated at Anchorage,Alaska EASEMENTS OF RECORD,OTHER THAN 1' �/%%_ ''�.� this 5th day of MARCH ,2019. THOSE SHOWN ON THE RECORDED 3'L)- 1FRED WALATKA&ASSOCIATES,L.L.C. PLAT ARE NOT SHOWN HEREON. Engineers and Surveyors UNLESS OTHERWISE NOTED FB 19-1, pg 40 BE 907-248-1666 MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTION ENVIRONMENTAL ENGINEERING DIVISION *D 825 L Street - Anchorage, Alaska 99501 Telephone 264-4720 ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT NAME !/hn-14�e 4ce e -. PHONE NEW UPGRADE MAILING ADDRESS " 3!6� n,�a—`�/ LEGAL DESCRIPTION LOCATIONw +/� : CfUROO '••� �V f�i Wim' �i/Z VJ • •� U Y DISTANCE TO: Well/ � a Abso � i� Dwellin / / f ,n Gey •. ', •• ••, I- zz W< Manufacturer LkWKAJ©u9�--c�c/sT/�v6- Material t nt 0 ... . N Liq, capacity in gallons IF HOMEMADE: Inside length Width Li � % N . CE-4488 • D Y DISTANCE TO: Well Dwelling T•Mp.•,•••••,• AV.��z o 2 Manufacturer Material w = DISTANCE TO: Well 4 //:5- Foundation Nearest lot line PERMIT NO. J LL z No. of lines Length of each line Total len th of lines ! Trench width Distance betweer1lines 15 P z W 41� inches ccH. Top of tile to finish grade / Z Material beneath tile/� / Total effective absorption area //inches 3 �fLi�/� D p P !Y -.57 X 24. Length Width Depth PERMIT NO. W a I- W° Type of crib Crib diameter Crib depth Total effective absorption area DISTANCE TO: Well Building foundation Nearest lot line -' Class G Depth DUler no��o w N Distance to lot line IdAl eiv a w �%G RULT NO. A 5 7/ LU TO: Building foundation / Sewer line �� % Septic tankQ,DISTANCE p 0 ! +Absorptionar/at> 15/Q OTHER PIPE MATERIALS SOIL TEST RATTING �e•� 'ice ✓J < t-Pi� I NSTALnnLER I,ta AC_ SON., Nz! REMARKS D--�-.ri 7T O Co V -P j' -------------- LL I 3 resn. c,t.cc..k g r APPROVE DATE LEGAL 72-013 (Reiy3/78)" I MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTION ENVIRONMENTAL ENGINEERING DIVISION 825 L Street- Anchorage, Alaska 99501 Telephone 264-4720 ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT MAILING ADDRESS LEGAL DESCRIPTION PHONE [] NEW LOCATION Well x I Absorpt on area Dwe ine ~ Manufacturer ~ ~-~- ~--~ - ~ ~,~ · ,/ IMaterial Liq. capacity in gallons Inside length ~ Width ~/~ ~O I I" HOME'DE: I :E-4488 ' ~ Well Dwelling _ . x// ~ Manufacturer I- / ~ ' Material / IWell ~ . / Foundation ~ I Nearestlotline PERMITNO ~= I DiSTANC~TO: ~ ~ ~/E-- ~ i ' I ~ ~ o. of lines Length of each ]ioe Total le~qth of lines / I Trench w dth Distance betwee~[ines ~ ~ ~ Top of tile to finish grade ~ Material beneath tile ~ /~ Total effective absorption area m [ Length [ Width Depth PERMIT NO. ~ ~ [ Type of crib Crib diameter /~ Crib depth Total effective absorption area ~ Well ' / / [ Building foundation Nearest  DISTANCE TO: . ~ /Class ~ ~Depth ~..~ ..... Driller ~_ . ., Distance ~ / DISTANCE T~ I Building foundation Sewer line ~ ~_ / Septic t~ ~ OTHER ' ~--~ PIPE MATERIALS SOl L TEST RATING INSTALLER REMARKS APPROVE DATE LEGAL 72-013 IRe~/3/78)~ MUNICIPALITY OF ANCHORAGE Department,~ Health and Environmenta,~rotection 825 ~ Street, ~nchorage, AK. J9501 ~' · ~ 264-4720 '~ ~ ~ * * * HANDWRITTEN PERMIT * * * Permit #' ~ O~S~[ WELL AND/OR 0N-SITE SEWER PERMIT Applicant:~. ~ /~;-~./~/~ Mailing Address: ~ Location: ~ ~ - ~z~- ~ ~6c; Phone Nuraber: -~3~ Legal Description:~ ~2 ~ /~/~ ~;-, Lot Size: TYpe of Soil Absorption System Is: Trench: Drainfield: Seepage Bed.'%// Holding Tank Maximum Number of Bedrooms: Soil Rating (sq. ft/br) DEPTH The Required Size of the Soil A]Dsorption System Is: ' ~,0 LENGTH ,3",~, GRAVEL DEPTH &' WIDTH ~'~ The length dimension is the length(in feet) of the trench or drainfield. The depth of a trench or pit is the distance between the surface of the ground and the bottom of the excavation(in feet). There is no set width for trenches. The gravel depth is the minimum depth of gravel between the outfall pipe and the bottom of the excavation(in feet). * * REQUIRED SEPTIC(HOLDING) TANK SIZE = /~dO GALLONS * * Permit applicant has the responsibility to inform this department during the installation inspections of any wells adjacent to this property and the number of residences that the well will serve. * * * TWO(2) INSPECTIONS ARE REQUIRED * * * Backfilling of any system without final inspection.and approval by this department: will be subject to prosecution. Minimum distance between a well and any on-site sewage disposal system is 100 feet for a private well or 150 to 200 feet from a public well depending upon the type of public well. Minimum distance from a private well to a private sewer line is 25 feet and to a community sewer line is 75 feet. Well logs are required and must be returned to this department within 30 days of the well completion. Other requirements may apply.. Specifications and construction diagrams are available to insure proper installation. * * * PERMIT EXPIRES DECEMBER ~1~ 1 9 ~ 3 * * * I certify that: (1) I am familiar with the requirements for on-site sewers and wells as set forth by the Municipality of Anchorage. (2) I will install the system in accordance with codes. (3) I understand that the on-site sewer system may require enlargement if the residence is remodeled to include more that 3 bedrooms.. Signe~: Issued by: Applicant SWP/024 (1/81) ~ 0' ,~ ' ¢~ 'SO~LS LOG MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION J~ PERCOLATION TEST 825 L. Street, Anchorage, Alaska 99501 264-4720 SOILS LOG - PERCOLATION TEST PERFORMED FOR: LEGAL DESCRIPTION: .1 3 4 7 8 10 19 13 1~- 17 2O SLOPE COMMENTS DATE PERFORMED: SITE PLAN No 0 Reading Date Gross Net Depth to Net Time Time Water Drop Jo ,o3 ~ )t ,'.¥1 ,~-8 TEST RUN BETWEEN ~'~. ~ 7,~ I0 ~ ,~z. , OZb PERCOLATION RATE ~'~¢ ~ (minutes/inch) t i'~FT AND--~ FT 'Z q ~ ~ /~g~  DAT~ E: ~/Z~ PERFORMED BY: L. ~EI~ 72-008 (6/79) 5"3" 83~2. Oi, CERTIFI ED BY: ALASKA ~P~onm~NTAL CONTROL $~RUI~ES, I~C. ~in~erin9 ~, ~nuironm,nlol Studits PERCOLATION TEST DATA SHEET ADDRESS DATE ZIP CODE LEGAL LOCATION Lo't TOTAL DEPTH OF HOLE ZONE TESTED ¢'-~. TH # ft. ft TO ~ ft TEST HOLE DIAMETER ~ ~ READING # CLOCK TIME liET TIME DEPTH TO NET DROP RATE (min/in) OATUM ~!~.L P£RCOLATION F~ATE ~0 /~7 (min/in) PERFORMED BY ~--oAJ~ ~ MUNICIPALITY OF ANCHORAGE Hear~, and Environmental Proter"''on Fourth Floor West .. 825 L Street Anchorage, Alaska 99501 279-2511, x 224, 225 REPORT ON-SFJ'E SEWAGE DISPOSAL SYSTE/'_A LOC^T,O, ', _L .... SEPTIC TANK: t ~ I NUMBER OF DISYANCE f (~C) _ ~4ANUFACTL RER L ~ MAri:RIAI ................ C ~ ARTMENTS EROM WELL ................. ~ ~t O~ P INS DE LENGTH ............... INSIDE WIDI'It t IQUID DE PTH ...... [ IQLIID CAPACITYL~_¢__~_ GALLONS. [ I I TOTAL LENGTH DISTANCE FROM WELL_~..¢_FOUNDATION _~_ __NEARESf LOT LINE _ /~ _~_ .... OF LINE _~~_.__ ~ of Lines ] DISTANCE BETWEEN LINES __~____TRENCH WIDIH~ IN. TOTAl_ EFFECTIVE ____ - SQ. FT. LENGTH OF EACH t INE ~OI OEPDh TOP OF TILE 10 F!NIStt GRADE 5'¢ ............. MATERIAL UENEAfH TILE IN. ABOVE TILE ¢ .1N, SEEPAGE PIT: Log Crib Rings BUILDING FOUNDATION____ DIAMETER _.__ OR WlOTtl ....... LENGTH ., DEPTH Crib Size: DIAMETER ..... DEPTH DISTANCE FROM: WELL TOTAL EFFECTIVE NEAREST LOT LINE ....... ABSORPTION AREA (WAL. L AREA) SQ. F"F. Class :~ Depth: Well Distance To: Lot Line r ' _~ Bldg.' ~ Sewer L~ne: lo~---1 ~ of Bedrooms: ~ I Installer: Remarks: Well Owner DRILLING, DRILLING LOG Use of WeD Location (address of: Township Range, Section, if known; or distance main road ~'~ot !:2" "~?B~ock 2 MOuntain -o.,.,~.,_ ,~..~,., Es'i:ate. s : Size. of casing Static water leve] Screen ( Depth of Hole ', :~a ft. ); Perforated ( Describe screen or perforation ~.;, Well pumping test at ! :) gallons per (I{~{~) of drawdown from static level. 2 2 5 feet Cased.to =':' ~ · 2 feet (below) land surface. Finish of well (check one) open end ( x ). (minute) for hours with I 3 0]~, WELL LOG Depth in feet from ground surface Give details of formations penetrated, size of material, color and hardness TO. ~ft. .TO_ .TO. . .... tt'y ~rava].. .TO. .TO. ,TO. .TO_ .TO_ Sand Silty ~rave 1 Loose 2raval. med:!.'L~zn - Loose~sveilv sand $i.!~~- sandy cravel C].ay'cy %:cave / NWWA Certified Contractor ~ertiiitmi~e No%, 81,1 & 970 2 -- STATE * [,EpAF.'TMEI'.,IT. ' HERLTH AN[:, ENVI F. ONHENTFII.. 'OTECT 1 ON ^ r,.~. ^~.~ ~--;n~4"- ~7 - 825 '"L'" STREET., RNCHORRGE., FIK. 9950± F'ERMIT NO. ( 7}"6:1 ..... ) LuFIF'F'L I_,:_.HTCRNTI uN ~~''-ARRY POND ,.'m,---"~¢¢'7~', *.608 STFIN'rON H'v'E LEGRL 1_2.2 E;2 HT PK EST SI_IDB L. OT SIZE: 2'4'192 SQURRE FEET TYPE OF SOIL. RBSORBTION SYSTEM I5: TRENCH I"IR,'.'-,'IMUH NUMBER OF BEDROOHS = Z: SOIl._ RFITING (SQ FT,.-"BR)= THE REQIJIRE[:, SIZE OF THE SOIL FIBSORPTION SYSTEM IS: [:,EF'TH= ~_;=%_" [.~.. E ir-41E-~ T H = 2--::4 13 F-: R %-' i L~ B, EF'TH= THE LENGTH DIHENSION IS THE LENGTH (IN FEET) OF THE TRENCH OR DRRINFIELD. 'THE DEPTH' OF R TRENCH OR PIT IS THE DISTFINCE BETWEEN THE SURFFICE OF THE GROUND FIND THE BOTTOH OF THE EXCFIVRTION (IN FEET). 'THERE tS NO SET WIDTH FOR TRENCHEr.--.,. THE GRFIVEL. DEPTH IS THE HINIHUI"J DEPTH OF GRFIVEL BETWEEN THE OUTFRLL. PIPE FIN[.., THE BOTTOH OF ]'HE EXCR'v'FITION (IN FEET). FI PFICKFIGE PLFINT HFIY BE INSTFILLED FIT THE PERMITTEE"S OPTION '=:U8JECT TO THE FOLLOWING CONDITIONS.' :1.. EITHER FI CLFISS I OR II NSF FIPPROVE[:, PLRNT i',IFIY BE INSTFILLED. R. FI CONTINUOUS MFIINTENFINCE FIGREEMENT IS REQUIRED. IF FI MFIINTENFINCE RGREEHENT IS NOT KEPT CURRENT YOU MFIY 8E REQUIRED TO ENLFIRGE THE SOIL FIBSORPTION SYSTEM FIND/OR YOU MFIY 8E SUBJECT TO PROSECUTION. BRCKFILLING OF RNY SYSTEM WITHOUT FINRL INSPECTION RN[:' RPPROVRL. BY THIS DEPRRTMENT WILL BE SUBJECT TO PR. OSECUTION. HINIMLIM [:,ISTFINCE BETWEEN R WELL FIN[.., RNY ON-SITE SEWRGE [:,ISPOSRL SYSTEH IS :1.00 FEET FOR FI PRIVRTE WELL OR 200 FEET FOR R PUBLIC WELl,... WELl.. LOGS FIRE F.~EQUIRED RND HUST BE RETURNED TO ]'HE DEPFtRTHENT WITHII",! Z::O [:,FLYS OF THE WELl,_ COMPLETION. [. I IdbiF..HH=, RRE ]THER RE~. IREHENTS HRY RPPLY. =,FEL. IFICRTIONS RN[:, ].']d'.~STRJr.'TION ' --'-"- RVRILRBLE TO INSURE PROPER INSTRLLRTtON. F E.F~.[ g Z T E~::F' I F~:E5 [:.EL-EflBEF-. _--.-.-: :.:L .- ::L:977 I CERTIFY THRT "' _.,ENER=, AND WELL_:; RS SET :I.: I AM FRHILIRR WITH THE RE..-,~JIREMENTS FuR ON-SITE c - '- FORTH BY THE HUNICIPRI,~ITY OF RNCHORRGE. 2: I WILL INSTRLL THE SYSTEM IN RCCOR[:,RNCE WITH THE CODES. ]':: I UNDERSTRN[:, THR'f' ]"FIE GN-SITE SEWER SYSTEM MRY REQUIRE ENI_RRGEHENT IF THE RESIDENCE IS REMODELED TO INCLUDE MORE THRN 3: BEDROOMS. '~'AFi'F'L I~IS:ANT LARRY PON[:, I ::-;SUED B"f~.}_~_,~'~* .................. ~?Z~m~ ...... DFITE.c'~%Z~._*~ ...... ~-X ....... VZ.: 0 April 8, 1977 R & M No. 751137 Ms. Mildred F. ~irth c/o Globe Realty 2805 Dawson Street, Suite 101 Anchorage, Alaska 99503 RE: Test Hole and Soil Log Report for Sanitary System, Lot 12, Bl~ck 2, Mountain Park Estates, No. 2, Anchorage, Alaska Dear Ms. Hirth: We are submitting herewith the test boring results and our comments regarding soil conditions encountered at the subject site. This in- vestigation was performed in accordance with the April 6, 1977 request of Anita Bates and those procedures outlined in a letter dated July 15, 1975, by ~. Roll Strickland of the Municipality of Anchorage, Department of Environmental Quality. A single test hole was drilled within the subject site area for the purpose of defining general subsurface soil conditions for the proposed sanitary system. Drilling was accomplished with an auger type drilling ? rig and the test hole was extended to a total depth of 20 feet below ground surface. The final log of the test hole has been included on Drawing A-01. Groundwater was not encountered in the test hole while drilling. A percolation test was performed from a depth indicated on the attached table and reflects average infiltration from that depth to the bottom of the hole. We appreciate being given this opportunity to be of service to you. Should you have any questions with regard to the above, please do not hesitate to contact us. Very truly yours, R & M CONSULTANTS, INC. Edward Yarmak, Jr. Geotechnical Engineer EY/pe Lot 12, Block 2, Mountain Park Estates No~ 2 O TH-1 ~ DeARMOND ROAD Not to Scale The test hole location is approximate and has not Oeen located by survey methods. TH - 1 4-6-77 Ail Samples A 0.0~ · ORGANIC ~t~TERIAL SANDY SILT W/TRACE GRAVEL Moist, Firm, Brown SILTY SAND W/SOME G~%VEL --3.5' Moist, Medium Dense, Brown 6.0~ SANDY GRAVEL W/SOME SILT Moist., Medium Dense, Brown SILTY SAND ~,~/SOME GRAVEL Moist, Medium Dense, Brown ---- 12.0' S~DY SILT Moist, Firm, Brown 20.0'TD .,Groundwater Table Not Encountered This log represents subsurface soil conditions wmthin Lot 12, Block 2, Mountain Park Estates s,mbdivision Do. 2 Anchoraqe, Alaska KD: EY nTFj 4-8-77 SCAL?:: 1"=3' SA.~.~ITARY SEWER TEST HOLE MILDRED HIRTH AMCHOP~AGE, ALASKA FB. [,D;VG. NO. 751137 A-01 PERCOLATION TEST MILDRED'HIRTH Lot 12, Block 2 MOUNTAIN PARK ESTATES NO. 2 R & M NO. 751137 April 7, 1977 ELASPED TIME TIME INCHES 1:55 0 12.00 1:56 1 17.00 1:57 ~ 2 17.50 1:58 3 18.00 1:59 4 18.25 2:00 5 18.50 2:01 6 18.75 2:02 7 19.00 2:03 8 19.25 2:04 9 19.50 2:05 10 19.75 2:10 15 20~50 2:15 20 21'.25 2:20 25 22'.00 2:25 30 22.50 2:35 40 23~50 2:45 50 24.~5 2:55 60 25.75 DROP IN INCHES 0.00 5.00 5.50 6.OO 6.25 6.50 6.75 7.00 7.25 7.50 7.75 8.50 9.25 10.00 10.50 11.50 12.75 13.75 13.75 INCHESI TOTAL DROP OR 4.36 MINUTES PER INCH ,~ ¢' ' DATE RECEIVED INSPECTION APPOINTMENTS TIME. TIME TIME DATE DATE DATE INSPECTOR INSPECTOR INSPECTOR ...... ~ r~ ANCHORAGE MUNICIPALITY OF ANCHORAGE ' DEPT. OF HEALTH 8, PROTECTION. DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTIOI~I~VIRONMENIAL  825 L Street- Anchorage. Alaska 99501 AUG 1 5 ENVIRONMENTAL SANITATION DIVISION Telephone 264-4720 RECEIVED REQUEST FOR APPROVAL OF INDIVIDUAL WATER AND SEWER FACILITIES DIRECTIONS: ComPlete all parts on page 1. Incomplete requests will ,not be prqcessed, Please allow ten (10) days for processing, 1. PROPERTYOWNER J PHONE 333-$591 Carol VanNortrick HumberdtI 345-2130 MAILING ADDRESS SRA Box 377-U, Anchorage, Alaska 99507 PROPERTY RESIDENT (If different from above} PHONE Corner of Hillside and DeArmound 2. BUYER PHONE unknown MAILING ADDRESS 3. LENDING INSTITUTION I PHONE I MAILING ADDRESS 4. REALTOR/AGENT ~ PHONE Vivian Gayton RE/MAX PropertiesI 276-2761 MAI LING ADDRESS 2702 Gambell Street, #200, Anchorage, Alaska 99503 ofc. 5. LEGALDESCRIPTION Lot 12, Block 2 Mt. Park Estates #2 STREET LOCATION DeArmound and Hillside 6. TYPE OF RESIDENCE {~ SINGLE FAMILY [] MULTIPLE FAMILY NUMBER OF~BEDROOMS [] One [] Four [] Two [] Five [~ Three [] Six [] Other 7. WATER SUPPLY [] INDIVIDUAL* [] COMMUNITY [] PUBLIC UTILITY * ATTACH WELL LOG. A well log is required for all wells drilled since June 1975. For wells drilled prior to that date, give well depth (attach log if available.) 8. SEWAGE DISPOSAL SYSTEM [] INDIVIDUAL/ON-SITE** [] PUBLIC UTILITY 1977 YEAR ON-SITE SYSTEM WAS INSTALLED. NOTE: THE INSPECTION FEE MUST ACCOMPANY EACH REQUEST BEFORE PROCESSING CAN BE INITIATED. 72-010 (Rev. 6/79) THIS SIDE FOR OFFICIAL USE ONLY 1. TYPE OF RESIDENCE NUMBER OF BEDROOMS [] SINGLE FAMILY [] ONE [] THREE [] FIVE [] OTHER [] MULTIPLE FAMILY [~] TWO [] FOUR [] SIX PERMIT NUMBER 2. WATER SUPPLY [] INDIVIDUAL DEPTH OF WELL [] COMMUNITY DATE DRILLED [] PUBLIC UTILITY Connection Verified LOG RECEIVED 3. SEWAGE DISPOSAL SYSTEM PERMIT NUMBER []INDIVIDUAL/ON ~SITE DATE INSTALLED []PUBLIC UTILITY Connection Verified. INSTALLER [~Septic Tank or F-IHolding Tank Size: If Tank is homemade SOILS RATING give dimensions: / TYPE OF TANK MANUFACTURER TOTAL ABSORPTION AREA MATE~L'~ ~ 4. DISTANCES Septic/Holding Tank Absorption Area Sewer Line I Nearest Lot Line WELLTO: /'~ ~ ~' ~ I Absorption Area to nearest Lot Line 5. COMMENTS ,~.o J~' APPROVED FOR BEDROOMS [] CONDITIONAL APPROVAL (letter must accompany certificate} E~] DISAPPROVED DATE BY , .-2 ! 72-010 (Rev. 6/79) ~.O W. Bcnson Blvd. Suite ~06 May 1, 1984 PENINSULA ENGINEERING Anchorage, Alaska 99503 (907) .~61-5107 Municipality of Anchorage Department of Environmental Protection Pouch 6-650 Anchorage, Ak 99502-0650 Attn: Keith E. Bandt RE: Lot 12 Block 2 Mountain Park Estates M.O.A. letter of May 1, 1984 Dear Mr. Bandt, As per your letter I Offer the following as further clarification of my inspection report dated October 17, 1983. (Copy attached.) The drainfield area was excavated to an average depth of three feet below the original natural ground level and then six,inches of clean washed rock was placed throughout the total drain field area. The four inch perforated drain pipe was then laid and cowered with three inches of washed rock. Thus the top of the four inch perforated pipe was approximately two point one feet below original ground level and the bottom of the pipe was approximately two point five feet below the original ground. The entire area was then backfill with the existing stockpiled material such that the finished grade in the area was built up one feet to two feet above the original grade thus providing the additional cover over the pipe which varied from four feet to six feet throughout the drainfield area. At the time of my inspection prior to backfilling I questioned the excavation depth to three feet and hense the resulting installation of the bottom of pipe at two point five feet below original grade since the perc test was performend from one point five to two point zero feet. The contractor, Mr. Acheson, contacted Mr. Lee Reid who had performed the perc test for an approval to extend the depth from two feet to two point five feet. Mr. Reid gave verbal approval at that time and was to follow up with a letter to Mr. Acheson. Mr. Acheson performed an excellent job during construction of this system and in my opinion constructed this system adequately as direc- ted to by the design engineer. If I can be of any further assistance in this matter please call. Sincerely, cc Jack Humbard WH:prr h u ic pal ty POUCia 6-650 ANCHORAGE, ALASKA 99502-.0650 (907) 264-4111 TONY KNOWLES. MA YOR DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION May 1, 1984 Jack and Carol Humbard Star Route A Box 3773-U Anchorage, Alaska 99516 Subject: Lot 12 Block 2 Mountain Park Estates Subdivision #2 Re-ActivatiOn of Health Authority Approval This Department will re-activate your Health Authority Approval application originally received August 15, 1983, and will at that time reconsider approval, provided that the following items are received: (1) The septic tank pumping receipt for pumping services rendered within the last year. A letter from Mr Wayne Henderson addressing the total (2) depth of the bed'system with resepct to the,soils log dated September 8, 1983 and this Department s permit dated September 19, 1983. The inspection report is clear as to this depth, and Lee Reid's letter dated November 22, 1983 does not allow any further assumption~/ to be made. This Department will not require an additional water sample, however, the lending institution may require a new test. If this is the case, contact this Department for that sample collection or one of our certified Health Authority Approval engineers. If there are any further questions, please call this office at 264-4720. Keith E. Bandt Environmental Engineering Manager KEB/lw ALASKA el ulROlqlllelqTAL COF1TROL ~nqinee¢inq November 22, 1083 Department of Health & Environmental Protection 825 L. Street Anchorage, Alaska 99501 Attn: Cory Willis Dear Cory: In reference to your letter on Lot 12 Block 2 Mountain Park Estates, you may want to check the total depth because our soil test was taken in the low part of the lot where it had not been filled. It is possible that they decided to fill that part of the lot in and then the total depth of cover would certainly imply that it was down into the im~permeable soils. Under no reasons would I tell someone to put the sewer system in impermeable soils. If you have any questions please let me know. Sincerely, Leroy C. Reid Jr. President , PhD PE 1200 LU~st 33rd J~urmug, Suite [~ · J~nchore§¢, Alnske 99503 · {907) 276-1381 Dear Dr. Reid: t l~ave ~:eceived an as-built sub~)~itted by ~'h~. Wayne i. ien'Jerso~] o~ Pe~is~Jl~.~ Engineering. In his co~i~:~t~r)ts he statec~ "i~xcavation depth exten~ed to 3° %~pon approval from engineer (Lee ;.-ieid)". Yoo did the o~igia~l soils on 9-~--83 for matioa shov}in~ you approved thee extra foot total bed depth, then t can approve the as-builts. Sincerely, c;-;o 4/e ]/~',i COFy Wiil. is~ ?..S. Acting Sewer a ~ater POUCH 6-650 ANCHORAGE, ALASKA 99502-0650 (907) 264-4431 TONY KNOWtLS. MA YOI~ OFFICE OF THE MAYOR Jack and Carol Humberd SRA Box 3773-U Anchorage, Alaska 99516 RE: On-Site Wast°Water Disposal System Lot 12, Block 2, Mountain Park Estates ~2 Dear Mr. and Mrs. Humberd: Your letter dated September 29, 1983, discussed several problems that you are having in attempting to sell your home and requested this office to investigate the matter. After a ~nmprehensive review of all available files and information pertinent to your particular situation, the following observations and conclusions have been made: Prior to the issuance of the original "On-site Sewer Permit (Noo 77615 dated 8-1-77), a soils test was taken by R & M Consultants, Inc. On the sketch submitted by R & M, the soils test was located in the southwest corner of the lot near the intersection of DeArmond Road and Saunders Drive° From the percolation test results and the soils charac- teristics, the soil was rated at 125 square feet per bedroom° 2 ° Based on the soil rating of 125 square f~t per bedroom, Permit NOo 77615 was issued on August 1, 1977. The design criteria shown on this permit called for a deep absorption trench system 12 feet deep, 24 feet in length, with a gravel depth of 8 feet° This system would provide a total of 384 square feet of absorption area which is slightly in excess of the requirement of 375 square feet for a 3-bedroom house in a soil rated at 125 square feet per bedroom. During August 1977, the on-site wast°water disposal system was installed (installer unknown) and inspected by Mr. Cory Willis, an MOA inspector° For some reason unknown at this time, the installer or owner located the disposal system (deep trench) due east of the house running towards Hillside Drive. In this configuration, the actual trench was approxi- Jack and Carol Humberd Page 2 mately 90 feet from the soils test site. It should be noted that the original soils test was an augured hole, probably 6 inches in diameter, and its location was probably not visually obvious at the time the trench was excavated. However, it is the direct responsibility at the excavator/ installer to locate the wastewater disposal system in the immediate vicinity of the soils test. On August 16, 1983, a request was made to the Department of Health and Environmental Protection (by Jack Humberd) for a Health Authority Approval Certificate as a prerequisite for selling the h6use. In accordance with established guidelines and procedures, the Department of Health and Environmental Protection sent a letter to Carol VanNortrick Humberd requesting (1) submittal of a well log; (2) septic tank be pumped; and (3) performance of an adequacy test on the dispo- sal system. Pursuant to the above, an adequacy test was performed by Alaska E~vironmental Control Services, Inc., during August, 1983, the results of which indicated that the system was capable of handling 30 gallons of water per day. (The requirement for a three-bedroom house is 450 gallons per day.) Subsequent to receiving the results of the adequacy test, you had several meetings with Mr. Robert W. Robinson, the Environmental Engineering Manager at the Environmental Health Divsion, in an effort to determine how your system could best be upgraded to meet the requirements of a three-bedroom resi- dence. In an effort to locate a suitable site for a replace- ment disposal system, a soils test was taken by Alaska Environmental Control Services on September 8, 1983, near the southeast corner of your lot, approximately 50 feet south of the existing system. The results of this test showed the soils to be very tight and dense. However, there was a strata of soil between 1-1/2 feet and 2 feet which was rated (by perc testing) at 294 square feet per bedroom° This test is no doubt more indicative of the soils characteristics at the location of the existing system than were the results of the original soils test located 90 feet from the site. Based on the above soils test data, a new On-site Sewer Permit (No. 830951) was issued on September 19, 1983, spe- cifying a shallow absorption bed type system 26 feet wide by 52 feet long to a depth of 2 feet with a 6 inch gravel bed. Jack and Carol Humberd P~ge 3 e As indicated on an "as-built" drawing prepared ~by Wayne Henderson, P.Eo, dated October 17, 1983, a shallow bed type absorption system was installed by Acheson Excavating. This as-built drawing shows that the bed system was installed at a depth of 3 feet instead of the 2 feet designated on the per- mit, and the Environmental Health Division is withholding their final approval until they have verification from Alaska Environmental Control Services, Inc., that the accepting soils strata extends at least to a depth of 3 feet. From the above chronology of events, it does not appear that the Municipality of Anchorage (DHEP) was remiss in any duty or obli- gation beginning with the issuance of the original On-site Sewer Permit and continuing through the recent Health Authority Approval process. It is unfortunate for you that the original owner or excavator opted to locate the on-site wastewater dispo- sal system at a site considerably removed from the soils test site. The Municipality does not usurp the right of the property owner to select the site of the soils test or of the disposal system° It is, however, the responsibility of the Division of Environmental Engineering to take whatever action necessary to insure the integrety of an on-site sewer system. It is my opi- nion that the Division of Environmental Engineering carried out their duty and responsibility in a prudent manner while at the same time, giving you their full cooperation and assistance in attempting to solve your problem at the least possible cost and inconvenience to you. Sincerely, Tony Knowles Mayor Mayor's signature. R EM I NDER , you were sent a copy of a le~from~,_:~.A~ to write a response The response was due in this office on Please call Debbie Palco at 264-4431 and let her know the status of the above mentioned letter. Thanks. Anita McGrath Special Assistant to the Mayor aS-built .... ' ........ en '~ t ~o ~ on-site lns~a.].latio~]s and a-.].6~ter ]iuog~ ~4r. Lee any fuFther ~.~.,aeations" .... - ..pleasd~. call me at 204-~7Z0o September 29, 1983 Mayor Tony Kno~les City Hall Anchorage, Alaska 99502 Dear Sir; In or effort to sell our'home, located at Hillside and DeArmoun, we.ha~e encountered a situation which the Muncipa~ity of Anchorage should be made aware of. This house was built in 1977 and purchased in 1980. ~o comply with existing codes,.a adequacy test was performed on the septfc system by Alaska Environmental Control Services, Inc. This test fa~ted. Then a pert test was conducted, which was also not acceptable; therefore to meet code for a 3 bedroom house, the existing system has to be up-graded. The cost to ;upgrade the system has been quoted at a figure of $9759.00. Note: This does not £nc~ude the $660.00 spent for 'testing to tell us the system is not acceptable ....... In pursuing this further with the Dept. of Health & Environmental ~ortection, we ffnd that when the home was built in 1977, the s@ptic system was approved by the Municipali~-y on Aug. 29, 1977, but in fact is only good for a 1/2 bedroom home. There are not too many 1/2 bedroom homes on the hillside. .Further investigation reveals that the system was not installed in the location where the original pert test was conducted, but yet still approved by the Municipalitiy. According to Mr. Robison of the Dept. of Health, the original pert test was conducted im- pro-er ly. According ~o the Dept. of Health, wa have entit Oct.14, 1983 to upgrade the system and'be approved, or after this date inspections will be done by private Engineering firms. (Again more costs) From a article in the paper, it appears that some lending institutions indicated they~ will not make a home loan on septic sytems approved by a engineers report. Our questions to your Mr. Mayor are: 1. Will the Municipality waive the codes and approve the system as is. 2. Will the Municipality pay for upgrading a system that they approved in the first place. 3. Can we get a reduction -in taxes from a 3 bedroom home to a 1/2 bedroom home. page. 2 4. Will the Municipality purchase our home at the current market price ~ $139,000.00. Frankly, we are at a loss as to which direction to turn. Hopefully a miracle will ~appen and $9,759.00 will appear; however, it is very doubtful. Thank you for the opportunity to present our case, and would be more than pleased to discuss this further w£th all p.arties concerned. ~/~/~ncerned taxpaye~ Jack & Carol Humberd SRA Box 3773~U Anchorage, ARf 99516 345~2130 cc; Dept. of Health & Protection Mr. Robinson Public Services- Mr. Dennerlein Mr. Don Smith, Assemblyman ALASKA E P-" RonmEnTAL CONTROL Irlc, SEPTEMBER 1 1983 CAROL VANNORTRICK .SRA BOX 7377 U .ANCHORAGE AR 99516 SELLER - CAROL VANNORTRICK BUYER - SUBDIVISION - MOUNTAIN PARK ESTATES ~2 BLOCK - 2 LOT - ll ADEQUACY TEST FOR SEWER SYSTEM THE TYPE OF ABSORPTION SYSTEM IS A TRENCH WITH A/~ AREA OF 450 SQFT. THE SYSTEM IS CAPABLE OF ACCEPTING 30 GALLONS OF WATER PER DAY. THE SURGE CAPAC-ITY OF THE SYSTEM IS 165 GALLONS. BASED UPON THE TEST DATA THE SYSTEM IS NOT ACCEPTABLE FOR A ~OME OF 3 BEDROOMS. SEPTIC TANK ADEQUACY THE EXISTING SEPTIC TANK VOLUME OF 1000 IS ADEQUATE FOR THIS 3 BEDROOM ,SOUSE. August 23, 1953 Carol VanNortrick Humberdt Si{A Box 377-U A.,~ c, n 507 Subject: Lot 12, block 2, f4to Park ust.~ .c.~ ~2 Aoproval ~o'r the individual sewer and water ii,gAs have been corapleted be granted un :l~ the following ' ~', ~ ~.~ ~well log ~-'ouoml~.ted' ~' ' = to thiso~+={~-'~_~u~ ~or our files and ~~eview. o ..... ~ne~ septic' tank pumped with a receipt submitted to this department. ' -,~. 'e performed on the existin9 An adequacy t.,;.,t needs to D= ~ ' tA~ system is 1 hi~9 area. Th~s test will determin~ ~equ~te according to National Stanaards. A iistinU ~/~)rJ. va:~.e ~-aS performin9 the test is enclosed. This repo~:t notify this Department for a reinspection wiien the discrepancies have been corrected. Ii there are any .her questioHst please call this oirice at 264-,i720. Sincerely O. S. Roberts Assistant Environmental Specialist JJ;(li/ej/~2 ~]Dcio sure ; INSPECTION APPOINTMENTS (~:::~z2_~£ ) ~-~'~). TIME TIME TIME DATE DATE DATE INSP ECT~ , INSPECTOR INSPECTOR MUNICIPALI~ OF ANCHO~Gfi BUNIOIPALITY OF ANOHORAGE DEPT. OF IZALTH &  DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTIO~vIRONMENT 825 L Street - Anchorage, Alaska 99501 " (~) ENVIRONMENTALTelephoneSANITATION264.4720 DIVISION FEB 2 9 1980 DIreCTIONS: Complete ~ll pa~ts on page 1. I~complete ~equests will ~ot be proce~ed. Please allow ten {10) days for p~ocessing. MAILING ADDRESS PROPERTY RESIDENT (If different from above) PHONE i2' - PHO~ MA~I N~AD OR ESS 3. LENDING INSTITUTION ~ PHONE~ MAILING ADDRESS 4. RE~L~/AGENT PHONE MAI~I~G ~D ~R ESS LEGAL DESCRIPTION ST R ~j~T LOCATION 6, TYPE OF RESIDENCE ~' SINGLE FAMILY [] MULTIPLE FAMILY NUMBER OF~BEDROOMS [] One [] Four [] Other [] Two [] Five J~ Three [] Six 7. WATER SUPPLY J~] INDIVI DUAL* * ATTACH WELL LOG. A well log is required for all wells drilled [] COMMUNITY since June 1975. For wells drilled prior to that date, give well [] PUBLIC UTI LITY depth (attach log if available.) 8. SEWAGE DISPOSAL SYSTEM [] INDIVIDUAL/ON-SITE** ,/C~'~7 YEAR ON-SITE SYSTEM WAS INSTALLED. E~ PUBLIC UTILITY NOTE: THE INSPECTION FEE MUST ACCOMPANY EACH REQUEST BEFORE PROCESSING CAN BE INITIATED. THIS SIDE FOR OFFICIAL USE ONLY 1. TYPE OF RESIDENCE NUMBER OF BEDROOMS [] SINGLE FAMILY [] ONE [] THREE [] FIVE [] OTHER [] MULTIPLE FAMILY [] TWO [] FOUR [] SIX PERMIT NUMBER 2. WAI'ER SUPPLY [] INDIVIDUAL DEPTH OF WELL [] COMMUNITY DATE DRILLED [] PUBLIC UTILITY Connection Verified LOG RECEIVED 3. SEWAGE DISPOSAL SYSTEM PERMIT NUMBER [] INDIVIDUAL/ON -SITE DATE INSTALLED []PUBLIC UTILITY Connection Verified INSTALLER []Septic Tank or []HoldingTank Size: _ I' ~)~~C) If Tank is homemade SOILS RATING give dimensions: j TYPE OF TANK MANUFACTURER~-? TOTAL ABSORPTION AREA MATERIAL 4. DISTANCES Septic/Holding Tank Absorption Area Sewer LineINearest Lot Line WELL TO: I Absorption Area to nearest Lot Line 5, COMMENTS L~ APPROVED FOR ~ BEDROOMS [] CONDITIONAL APPROVAL (letter must accompany certificate) [] DISAPPROVED DATE BY ~.~/,.~_.,~ 72-010 (Rev. 6/79) 825 "L" STREET ANCHORAGE, ALASKA 9950'1 (907) 264-4111 GEORGE M. SULLIVAN, MAYOR DEPARTMENT OF HEALYH AND ENVIRONMENTAL PROTECTION March 3, 1980 Krogseng Rea]. Estate 6025 Winding Way ~chorage, Alaska 99502 Subject: Lot 12 Block 2 M~.nn~n-h-~R~rk Estates Subdivision #2 Frederick/Pamel Upton Approval for your individual sewer and water facilities can not be granted until the following items have been completed: (1) The water analysis report be delivered to this office from Chem Lab, 5633 B Street, for our review. (2) The septic tank p~nped with a receipt submitted to this office. If there are any further questions, please contact this office at 264-4720. Sincerely, Robert C. Pratt, R.S. Associate Specialist RCP/ljw CC: Alaska Bank of Commerce Mortgage Loan Department Pouch 7-012 716 West 4th Avenue 99510 #1: Time Date Insp Street, 10- ~7 7 M~a Date Buc~olz .~Y~%x ~-. ,UN IC I PAL II-Y OF DEPARTMEk ~F HEALTH AND ENVIRON, .. i rpROTECTION 825 L Anchora¢¢.. Alaska 99501 264-4720 Date Received: Insp ~__ September 29, 1977 #3: Time Date Insp REQUEST FOR APPROVAL OF INDIVIDUAL SEWER AND WATER FACILITIES Mailing Address: Pouch 7007 99510 2.. Property Owner: Larry Pond - PDQ Homes Mailing Address: 6920 Burlwood Lending Institution Request: Peoples Bank and Trust Phone: Phone: 279-7511 344-0823 ,3. Legal Description: Lot 12 Block 2 Mountain Park Estates #2 4: Single Family Residence: (x) Multiple Family Residence: ( ) Number of Bedrooms: Three Number of Bedrooms: o o Well System: Individual Well (x) Community/Public System ( ) Permit Depth of Well .~.~-- Well Log on File (x~ Construction ~9~ Bacterial Analysis Sewage Disposal System: On-site System (x~ Public Utility ) Permit # 77~/ ~ Installed 1977 Installer Septic Tank Size /~ d90 ~C~ Manufacturer Absorption Area ~-O ~ Soils Rate /~ Material ! Distances: Well to Septic Tank /~ to Sewer Line ~ Nearest Lot line to Nearest Lot Line to Absorption Area /~.~O~ Absorption Area : .... | , - ....... MUNICIPALITY OF ANCHORAG[ ~ .... ~ Department of Health and Environmental Prto~ection' ~~\/ 825 L Street, Anchorage, Alaska Property Owner: Pond (PDQ Hc~es) Mailing AddresS: ~920Burlwood, Anchoraqe, Alaska Phone: 344-0823 Se Name of Buyer: Frederick G. & Pamela S. Upton Mailing Address: Phone: Lending Institution: People's Bank & Trust Attn: Mortgage Loan Dept. Mailing Address: Pouch 7007, Anchoraqe, Alaska Phone: 279-7511 Realtor/Agent: Gene Bates & Associates, Realtors , /Anita Bates Mailing Address: 2438 Chilligan Drive, Anchoraqe,AlaskaPhone: 274-5676 Legal Description: Lot 12, Block 2, Mount~'~n Park Estates #2 Street Location: corner of Dearmoun & Hillside (NW corner) Single Family Residence: (x) Number of Bedrooms: 3 Multiple Family Residence: ( ) Number of Bedrooms: Water Supply: *Individual Well (x) If Individual Well, well depth 225' If Community System, name of system Public/Community System ( ) Sewage Disposal System: On-site System (x) Public System If On-site System, date of installation: 8/29/77 *NOTE: A well log is required on ALL wells drilled since 6/75. 3/77 #1: Time Date Insp /-.~MUNICIPALITY OF ANCHORAGE~-~ DEPARTME{' 'OF HEALTH AND ENVIRONMENT--PROTECTIO~ 825 L Street, Anchorage, Alaska -99501 279-2511, ext. 224 or 225 Date Received: April 14, 1977 4-1~77 Friday Pr/~ tt~ #2: Time _d~,,~%~O #3: Time Date .C/_J~77 Date REQUEST FOR APPROVAL OF INDIVIDUAL SEWER AND WATER FACILITIES 1. Lending Institution Request: Alaska Mutual Savings Bank Mailing Address: Post Office Box 1120 99510 Phone: 274-3561 2. Property Owner: Fred M. Beavon Mailing Address: 718 Barrow Street 99501 Phone: 344-4492 3. Legal Description: Lot 12 Block 2 Mountain Park Estates 4: Single Family Residence: (~ Multiple Family Residence: ( ) Number of Bedrooms: 4 Number of Bedrooms: Well System: Permit # Construction Public/Community System: ( ) Individual Well: ~x) Depth of Well 260' Well Log on File ( Bacterial Analysis e Sewage Disposal System: Permit # Septic Tank Size Absorption Area On-site System (x~ Public Utility ( ) Installed Approx. 197~nstaller Manufacturer Soils Rate Material 7. Distances: Well to Septic Tank to Absorption Area to Sewer Line Nearest Lot line Absorption Area to Nearest Lot Line Pa~e Two Department of Health and Environmental Protection Request for Approval of Individual Sewer and Water Facilities Legal Description: Lot 12 Block 2 Mountain Park Estates ~2 Comments: Affadavit Attached: '( ) Letter Attached: ( Disapproved: Date: Date: Department Worksheet: MUNICIPALITY OF ANCHORAG Department of Itealth and Environmental Pr.otect~o~ . .... _ · · ~ ........ _ ~ ~ ~uT, ~,- ,~.,~o~A.~ 279-2511, ext. 224, 225 Property Owner: . ,/~-/-~.~ ~ ~/O/~/ Name of Buyer: 4/~ ~ J~//~A/ ? Mailing Address: ~/~ ~/~/~ Lending Institution: Mailing Address: Phone: Realtor/Agent: Mailing Address: Phone: Single Family Residence: (~ Number of Bedrooms: Multiple Family Residence: ( ) Number of Bedrooms: Water Supply: If Individual Well, well depth ~ If Community System, name of system *Individual Well ~.~ Public/Community System '( ) Sewage Disposal System: On-site System If On-site System, date of installation: /'~ / Public System ( ) /¢ 7~ *NOTE: A well log is required on ALL wells drilled since 6/75. 3/77 ?~ge'Two Department of Health and Environmental Protection Request for Approval of Individual Sewer and Water Facilities Legal Description: Lot 12 Block 2 Mountain Park Estates Subdivision Affadavit Attached: Approved: D±sapproved: Date: Date: Letter Attached: ( ) Department Worksheet: 37 9/7 / / • Municipality of Anchorage `P �Eeo • i_ 1 On Site Water&Wastewater Program 4 •- (907)343-7904 ice CERTIFICATE OF ON—SITE SYSTEMS APPROV, A � Parcel I.D. 017-022-12 Expiration Date: tY, V art' 1. GENERAL INFORMATION Complete legal description MOUNTAIN PARK ESTATES#2; BLOCK 2, LOT 12 Location (site address) 7301 DEARMOUN ROAD, ANCHORAGE,AK 99516 Current Property owner(s) C/O MATTHEW MAHONEY Day phone 360-979-6359 Mailing address 7301 DEARMOUN ROAD, ANCHORAGE,AK 99516 Real Estate Agent Day phone 2. TYPE OF DWELLING: U Single Family(w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 3 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Individual Well Individual On-site Individual Water Storage ❑ Individual Holding tank ❑ Community Class Well ❑ Community On-site ❑ Public Water System (1 Public Sewer ❑ WaiverNanance request for. N/A Distance: - Received by: Date: COSA to be released to the engineer,unless otherwise requested by the engineer. COSA Fee $ 0126 Waiver Fee $ Date of Payment 4`/S7S Date of Payment Receipt Number 3_e�a6 Receipt Number COSA# octet Iris Waiver# 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On-Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm GARNESS ENGINEERING GROUP, Ltd. Phone 337-6179 Address 3701 E. TUDOR ROAD, SUITE 101 *ANCHORAGE,AK, 99507 I Engineers Printed Name JEFFREY A. GARNESS, P.E. Date Li 111 ! lri Engineers Comments: In conducting this evaluation,GEG provided an engineering evaluation of the well and/or septic system in accordance with the ♦����1MC11% guidelines and regulations established by the Municipality of Anchorage and industry practices.The reported results describe the 444,- (Thr O 1 .* condition of the system/s on the date/s of the evaluation.Separation distances were measured to readily identifiable features. •••P\ 4 �. Hidden defects or encroachments may exist that were not identified during the evaluation.The operational life of all wells and septic • '•••••••••••••, �• • systems depend on a variety of variables including,but not limited to,soil conditions,groundwater levels(that may fluctuate during l•`�_•••••• �• the year),quality of construction(materials and workmanship),and the water usage of the family utilizing the system/s.These * A o �� /', •:* •• conditions can vary,and are outside the control of GEG.Satisfactory test results do not guarantee future performance of thet • % COSA Checklist Legal Description: MOUNTAIN PARK ESTATES#2; BLOCK 2, LOT 12 Parcel ID: 017-022-12 If more than 1 septic system on lot: COSA Checklist# 1 of 1 Structure served by this system 1 A. WELL DATA ❑■ Well log is filed with Onsite (or attached) Well production at time of test 6.2 gpm Date drilled 8/18f77 Water storage tank volume N/A gallons Total depth 225 ft Well disinfected for coliform test? ❑ Yes ❑■ No Cased to 221.2 ft ■❑ Coliform bacteria is Negative Sanitary seal is functioning correctly Nitrate 2.11 mg/L [' Nitrate less than MRL (ND) ■❑Wires are properly protected Arsenic ug/L III Arsenic less than MRL (ND) Casing height(above ground) 12+ in. Collected by GARNESS ENGINEERING GROUP LLC. Date of flow test for COSA 3/4/19 Date of Sample 2/20/19 Static water level at beginning of test 179.5 ft. Comments B. TANK DATA C. LIFT STATION Age of tank(s) NEW years ❑■ Required maintenance completed Tank type/material s" Age of lift station NEW years ❑� Standpipes/foundation cleanout per record drawing Lift station material HDPE Date of pumping NEW Comments: N/A D. ABSORPTION FIELD DATA BED Which system tested (date installed) *3/15/19,4/8-9/19 Adequacy test date 3/6/19 ❑ALL standpipes present per record drawing Results ❑✓ Pass For 3 bedrooms Total measured depth from grade 3.4-3.6 ft (max) Fluid depth prior to test NEW in Measured depth to pipe invert from grade 2.9-3.1 ft(min) Water added NEW gal ❑ N/A—pressurized field p NEW New depth in • Monitor tubes go to bottom of drainfield. If not, state Elapsed time NEW min depth into effective Final fluid depth NEW in ❑■ Code-required soil cover over field ❑ System presoaked Absorption rate 450+ gpd (Required if vacant for greater than 30 days prior to Any rejuvenation treatment(past 12 months) N/A date of test) N/A Gallons introduced N/A gallons If yes, enter date Comments/Deficiencies:*SEPTIC TANK INSTALLED ON 3/15/19.PUMP TANK,AEROCELL,&DRAINFIELD INSTALLED ON 4/8-9/19 COSA Checklist yellow sheet E. SEPARATION DISTANCES From Private Well on Lot to: (Please enter distances if less than required or if community well) Septic Tank/Lift Station on Lot> 100' Community Sewer Manhole/Cleanout> 100' ❑✓ Yes if No ft ❑✓ Yes if No ft Neighboring Tank > 100' ❑i/ Yes if No ft Private Sewer/Septic Line> 25' ❑✓ Yes if No ft Absorption Field on Lot> 100' ['Yes if No ft Holding Tank> 100' ['Yes if No *75+ ft Neighboring Absorption Fields> 100' Animal Containment> 50' ❑✓ Yes if No ft Q Yes if No ft Manure/Animal Excreta Storage > 100' Community Sewer Main > 75' Q Yes if No ft ❑✓ Yes if No ft From Septic/Holding Tank on Lot to: (Please enter distances if less than required) Building Foundations > 10' ❑✓ Yes if No ft Surface Water> 100' ❑✓ Yes if No ft Property Line > 5' ❑✓ Yes if No _ ft Driveway/Parking > 0' ❑✓ Yes if No, comment ** Absorption Field >5' ['Yes if No ft Wells on Adjacent Lots: Water Main > 10' ❑✓ Yes if No ft Private Wells> 100' ❑Yes if No 50+ ft Water Service Line > 10' ❑✓ Yes if No ft Community Wells > 200' ❑✓ Yes if No ft From Absorption Field on Lot to: (Please enter distances if less than required) Building Foundation > 10' ❑✓ Yes if No ft Driveway/Parking> 0' ❑✓ Yes if No, comment Property Line > 10' ❑✓ Yes if No ft Wells on Adjacent Lots: Water Main > 10' Q Yes if No ft Private Wells > 100' [' Yes if No 50+ ft Water Service Line > 10' Q Yes if No ft Community Wells >200' ['Yes if No ft Surface Water> 100' Q Yes if No ft F. ENGINEER'S COMMENTS THIS IS A CAT II QUANICS AERCEOLL TREATMENT SYSTEM. *MET CODE AT TIME OF INSTALLATION. **540 PUMP TANK MAY SLIGHTLY ENCROACH UPON 1977 TRENCH INSTALLATION LOCATION APPROVED BY TIM EKLUND WITH MOA ONSITER DEPARMTNET DURING INSTALLATION. ,„- .. .N.-‘,,,, o \ G. ENGINEER'S CERTIFICATION OF �� Com ........ 6A I certify that I have determined through field inspections and review Q���P t • T„ %\ �00A of Municipal records that the above systems are in conformance with a * : . * /i MOA COSA guidelines in effect on this date. O '''1 I, •.J- ' 'y A. • -ss. OD v0A%. CE—/9k3 e�O 'N'' , -'• I•/ / 4 ,Deaprofess!o0°ao COSA Checklist yellow sheet #AECC884��DOOooc.a