HomeMy WebLinkAboutRABBIT CREEK VIEW & HEIGHTS BLK 1V LT 6ARabbit Creek View Heights Block i V Lot 6A #020-521-11 Flowline Construction LLC PO Box 102221 Anchorage, AK 99510 907-748-0878 October 9, 2023 Municipality of Anchorage Attn: Development Services- Onsite Site 632 W 6th Ave Anchorage, AK 99501 Subject: Decommission Septic Tank @ Lot 6A Jamie Dr- RABBIT CREEK VIEW & HEIGHTS L6A 131V Dear Sir/Madam: This letter is in response to your request to decommission the septic tank at the above location. Flowline Construction Llc recently conducted a thorough search on the property in an attempt to locate the septic tank. Unfortunately, we were unable to find it. We did, however, find several standpipes, two of which we identified to be consistent with the placement of the tank based on the installers sketch. We also located the drainfield stand pipe. We proceeded to dig down to the bottom of the septic tanks pipes. We discovered that the septic tank was absent. The pipes were placed to make the appearance of a tank but terminated into the soils. It appears the tank had been removed with the pipes placed back into the ground as a ruse. During our investigation, we noticed a significant dip in the area where the septic tank should have been located. This led us to speculate that the septic tank had already been removed and backfilled. We believe that the property is free from any septic tank. Sincerely, Noah G Groskreutz Flowline Construction Llc u nl' el' p a t y Anchorage POUCh 6-650 ANCHORAGE, ALASKA 99502-0650 (907) 264-4111 TONY KNOWLES, MAYOR DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION October 17, 1983 Rick Daniels SRA 4074-B Anchorage, AK 99507 Subject: L6 Bl Rabbit Creek View Dear Mr. Daniels: This Department has reviewed the information regarding the subject lot. The soils test submitted to this office shows two test holes and no evidence that ground water was encountered down to 12 feet. A permit was issued by this Department giving the specific design specifications. Pyramid Excavating installed a system, which was inspected by S&S Engineers and they submitted an as -built to this Department. This as - built shows the trench depth to be deeper than the permit specifica- tions, however, a note by the inspector stated that the overlaying terrain to the south caused this change. Also, on the inspection as - built there was no mention of water being present in the system's installation. Mr. Robinson has talked with S&S Engineers and there appears to be water in the sewer system, plus the drainlines appear to be installed so they run up-slope from the tank. Another test hole was installed in the area of the trench by Alaska Environmental Control Services and after a monitoring period ground water was at 8 feet. Based upon all the information submitted to this Department we can not accept the as-builts for the on-site sewer installation as installed. In addition further research may be needed before installation of another on-site system can be installed, and/or the other alternative may be that only a holding tank can be installed. Before any construction is undertaken, permits will need to be obtained from this Department. If you have any further questions, please contact Mr. Robinson or myself. Sincerely, Cory Willis, R.S. Acting Sewer and Water Program Manager CW3/p/EH z t'ulmit 6v®L> ���� P41/lelp— low 7a,04Z lej 4,.a4 J--)eU A&W 7125 OLD SEWARD HIGHWAY • ANCHORAGE, ALASKA 99502 September 15, 1983 Pyramid Excavating Attn: Mr. Dan Thompson 1048 W. Int -1 Rd., Suite 103 ANchorage, AK 99502 Re: Rabbit Creek View Subdivision, Lot 6, Block 1, Rick Daniels Property Septic:. System Gentlemen: Our involvement in the construction of a septic system at the subject property has been as follows: 1. On July 22, 1983 Mr. Bill Evans, of our office, performed a percolation test at a location 35 feet south of the proposed house site. The percolation test indicated that the silty material encountered would not support a septic system. 2. On July 28, 1983 Mr. Evans returned to the site and performed a second percolation test at a different location on the lot. The second test indicated an acceptable percolation rate. The results of the percolation test were submitted to the Anchorage Municipality, and a permit was issued to build the septic system on August 2, 1983. 3. The septic system was constructed and Mr. Evans inspected the system as the work progressed. The inspection form was completed and submitted to the Municipality. 4. Subsequent to the successful completion of installation of the system, a period of rainy weather occured. Surface water moved downslope across the lot, and flooded the septic system and the excavation for the house foundation. 5. After inspection and a brief analysis of the problem, it was determined that the solution to the water problem would be cost -prohibitive. 6. In summary, a passing percolation test was performed, the Anchorage Municipality issued a permit, and the system was successfully and correctly installed. After the system was put in, changed conditions occured due to weather. The changes( "'.'�ondition could not have been anticipated. Even had the possibility of the surface:.. water problem been suspected before installation, it is likely that the owner would have taken some risk to install the system. WASILLA ANCHORAGE SOLDOTNA (907) 376-3770 (907) 349.6561 (907) 262-9534 Pyramid Excavating Page 2 Should you have any questions regarding this matter, please do not hesitate to contact us at 349-6561. Sincerely, David A. Stanley Geotechnical Manager DAS:sc 4 Job 3738 72-013 (Rev. 3/78) MUNICIPALITY OF ANCHORAGE 1. DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTION ' ENVIRONMENTAL ENGINEERING DIVISION 825 L Street - Anchorage, Alaska 99501 Telephone 264-4720 ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT NAMED PHONE e! NEW TA M ( YC.C__. - 'Ci� ��I�IC_l� �f `�-1� El UPGRADE MAILING ADDRESS 1ATERIJAII L A rR'P' 1 .r S;UI 103 Arco A k w -c2 LEGAL DESCRIPTION L,o% 6 BC C'C- J- f CJZC-GK V I W .SU. DIV B! og) LOCATION NO. OF BEDROOMS ®N SAmliil AVE/UVE 01 F CLARKS ROA DISTANCE TO: Well i ��� Absorption area 0 Dwelling PERMIT NO. �0•, U Y i _ 1.- ZManufacturer w /� ,�— Rc— Material _ _ STEE No. of compartments la- CS L N Liqc arty in gallons C �9 IF HOMEMADE: Inside length NA Width � ' Liquid depth IVA DISTANCE TO: Well Dwelling PERMIT NO. 0z< za ManufacturerMaterial Liquid capacity in gallons DISTANCE TO:(1 Well% 00+ Foundation/ Neares Int Iine� PER�4�T-AVO. W = LL z No. of lines �n gtthof ach Ii e Total len h o linesf, Trench w�h��µ Distance betrinJjngs �Zw , % jj Q F Top the t finish Material beneath tile Total absorption o of grade c. ' , effect' area O �' r<iS'H �-✓L -3.S 4,Onches r Z 0 Length Width Depth PERMIT N. ` �~ �" -- F Af Qa I— W d Type of crib Crib diameter AIACrib depth Total effective absorption area ((�� vF p, °®opO°°OGo- h ,a 0 0 °o Q� y DISTANCE TO: WellLu Building foundation Nearest lot line €:; J Class Depth Driller Distance to lot line P � - JA 44 � DISTANCE TO: Building foundation Sewer line IVIV Septic tank q•s 18`3 H -E o (� OTHER M� PIPE MATERIALS Sfi��z .2 i1 - �� V \ ..� ".T SOIL TEST RATING \ Z J INSTALLER NMnA(D ExcAV AI -W _ 1 REMARKS '%�E C H DC -PTO IIVC?E E3 O rku cc fru ��,► �� � sk 1� S - TO aVE L1 aV -- G- 2/t1 AS' 7q Z. 3 V 1jG R Se W G2 PA IS 1= -t _ � a PIPE CLGANOM 6 &Aj6 OF &A, LINE ,> 17 CaIU SEPTic [ � &UE C- MOT I* N APPROVED DATE LEGAL SLO 72-013 (Rev. 3/78) TYPE OF SOIL AB_,ORPTIT N SYSTEM I E, : TRENCH i'iAY1 I i'ii_ H NUMBER OF BEDROOMS = _ SOIL RATING &SQ FT/ BR) = 287 THE REQUIRED SIZE OF THE SOIL ABSORPTION SYSTEM I S : n $ R0i 0- E? d--0= 1=1 J -I = -1 : Qa CB FR FA N? E= L iL-n F F=° -�` -ii — -:9 - THE LENGTH DIMENSION I THE LENGTH &IN FEET) OF THE TRENCH OR DRA I NF I ELD. THE DEPTH OF H TRENCH CH O R PIT IS THE DISTANCE BETWEENd THE SURFACE OF THE GROUND D AN•, D THE BOTTOM OF THE EXCAVATION 0N FEET). THERE IS NO SET WIDTH FOR TRENCHES. THE GRAVEL DEPTH IS THE MINIMUM DEPTH OF GRAVEL BETWEEN WEEN THE OUTFALL PIPE AND THE BOTTOM i iF THE EXCAVATION I N•d FEET). a--: E= a -q i,_n 11: m iii E > in E" 9=- -T TL C_ -7- 1=1 hi F -T _„+, 1 no, a 7 = _!L C --u C --n C-1 a:3 �_-,fl 9_ L_ a_n F -"if PERMIT APPLICANT HAS THE RESPONSIBILITY TO INFORM iF: M THIW DEPT= RTHEN•dT DURING THE INSTALLATION INSPECTION+i` OF ANY WELL_ ADJACENT ACEN'dT Ti i TH I _. PROPERTY AND THE NUMBER OF RESIDENCES THEN THE WELL WILL SERVE. — — — E-„ 10 > F=" E= C::_ _6_' g 0011141 d=f1 FZ E= F_ ER= C -A 9_6 _+ ice' F= E::-1 — — BA KF I LL I N• G OF ANY SYSTEM WITHOUT FINAL INSPECTION AN• D APPROVAL BY THIS DEPARTMENT WILL BE SUBJECT TO PROSECUTION. MINIMUM DISTAN'CE BETWEEN A WELL AND AN'd'T ON-SITE SEWAGE DISPOSAL SYSTEM I iOO FEET FOR H PRIVATE WELL OR 1.50 TO 200 FEET FROM A PUBLIC WELL DEPEN DIN 13 UPON THE TYPE OF . PUBL I C WELL. MINIMUM DISTAN'dCE FROM Ei PRIVATE WELL TO H PRIVATE SEWER LINE IS 25 FEET AND TO A i .ilMM iN•:!ITY _,EWER LINE I E 75 FEET. OTHER REQUIREMENTS MAY APPLY. SPECIFICATIONS AND CONSTRUCTION DIAGRAMS ►= RE AVAILABLE TO INSURE PR iPER INSTALLATION. 1 CERTIFY THAT i: I AN FAMILIAR WITH THE REQUIREMENTS F O R ON-SITE SEWERS AND WELLS AS SET FORTH BY THE MUNICIPALITY � �F ANCHORAGE. 2: I WILL INSTALL THE SYSTEM IN ACCORDANCE WITH THE CODES. : I UNDERSTAND TH_: - - �I�N•d-- S I TE SEWER SYSTEM MAY REQUIRE ENLARGEMENT IF THE RESIDENCE- I=, F:EW »I OELEF u TO f I r,iCLi = N' L3 --..'E THAN BEDROOMS. � �.,!,,�,;,�•�-tet � �, �+r � �, APPLICANT RICK DAN•+iI.ELS CJ C1 bon ISSUED �)A� E-----_�_.__SSSS 1 01--------- �:t DEPARTMENT L HEALTH MN D, Ei'•dV I RON•dMEi' i T HL , I f T EC :I( I ON PC) V a25 5 - L •• STREET, ANCHORAGE, AK. 99501. 264-4720 PEI 01 _ ..,; 4 n • HEE 4-1 n- 11 : 8=` EE ((= .k 6 PERMIT NO. K 82071.7 . APPLICANT RICK DANIELS SRA 4074-8 99507 688-2119 LOCATION JAMIE RD L6 B1- RABBIT CREEK VIEW S/D LEGAL T •i iN•d R .W SECTS LOT T _+IEE x•74.2:_ Sf-'.i_iM=RE FEET TYPE OF SOIL AB_,ORPTIT N SYSTEM I E, : TRENCH i'iAY1 I i'ii_ H NUMBER OF BEDROOMS = _ SOIL RATING &SQ FT/ BR) = 287 THE REQUIRED SIZE OF THE SOIL ABSORPTION SYSTEM I S : n $ R0i 0- E? d--0= 1=1 J -I = -1 : Qa CB FR FA N? E= L iL-n F F=° -�` -ii — -:9 - THE LENGTH DIMENSION I THE LENGTH &IN FEET) OF THE TRENCH OR DRA I NF I ELD. THE DEPTH OF H TRENCH CH O R PIT IS THE DISTANCE BETWEENd THE SURFACE OF THE GROUND D AN•, D THE BOTTOM OF THE EXCAVATION 0N FEET). THERE IS NO SET WIDTH FOR TRENCHES. THE GRAVEL DEPTH IS THE MINIMUM DEPTH OF GRAVEL BETWEEN WEEN THE OUTFALL PIPE AND THE BOTTOM i iF THE EXCAVATION I N•d FEET). a--: E= a -q i,_n 11: m iii E > in E" 9=- -T TL C_ -7- 1=1 hi F -T _„+, 1 no, a 7 = _!L C --u C --n C-1 a:3 �_-,fl 9_ L_ a_n F -"if PERMIT APPLICANT HAS THE RESPONSIBILITY TO INFORM iF: M THIW DEPT= RTHEN•dT DURING THE INSTALLATION INSPECTION+i` OF ANY WELL_ ADJACENT ACEN'dT Ti i TH I _. PROPERTY AND THE NUMBER OF RESIDENCES THEN THE WELL WILL SERVE. — — — E-„ 10 > F=" E= C::_ _6_' g 0011141 d=f1 FZ E= F_ ER= C -A 9_6 _+ ice' F= E::-1 — — BA KF I LL I N• G OF ANY SYSTEM WITHOUT FINAL INSPECTION AN• D APPROVAL BY THIS DEPARTMENT WILL BE SUBJECT TO PROSECUTION. MINIMUM DISTAN'CE BETWEEN A WELL AND AN'd'T ON-SITE SEWAGE DISPOSAL SYSTEM I iOO FEET FOR H PRIVATE WELL OR 1.50 TO 200 FEET FROM A PUBLIC WELL DEPEN DIN 13 UPON THE TYPE OF . PUBL I C WELL. MINIMUM DISTAN'dCE FROM Ei PRIVATE WELL TO H PRIVATE SEWER LINE IS 25 FEET AND TO A i .ilMM iN•:!ITY _,EWER LINE I E 75 FEET. OTHER REQUIREMENTS MAY APPLY. SPECIFICATIONS AND CONSTRUCTION DIAGRAMS ►= RE AVAILABLE TO INSURE PR iPER INSTALLATION. 1 CERTIFY THAT i: I AN FAMILIAR WITH THE REQUIREMENTS F O R ON-SITE SEWERS AND WELLS AS SET FORTH BY THE MUNICIPALITY � �F ANCHORAGE. 2: I WILL INSTALL THE SYSTEM IN ACCORDANCE WITH THE CODES. : I UNDERSTAND TH_: - - �I�N•d-- S I TE SEWER SYSTEM MAY REQUIRE ENLARGEMENT IF THE RESIDENCE- I=, F:EW »I OELEF u TO f I r,iCLi = N' L3 --..'E THAN BEDROOMS. � �.,!,,�,;,�•�-tet � �, �+r � �, APPLICANT RICK DAN•+iI.ELS CJ C1 bon ISSUED �)A� E-----_�_.__SSSS 1 01--------- �:t SOILS LOG MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION PERCOLATION TEST 825 L. Street, Anchorage, Alaska 99501 264-4720 SOILS LOG PERCOLATION TEST OA 5Tq,3 0.24 - PERFORMED FOR: R; - k Q,Fn, c I s DATE PERFORMED:— 13 i /,q,3 LEGAL DESCRIPTION: -,Sub, DEPTH SLOPE Z'i[TE PLAN IF E E T) 2 3 4 5 6 7 8 9 10 11 12 13 14- 15- 16- 17- 18 - 19- 20 - 5P 4- 15 -16- 17- 18- 19- 20- 5P S,,,dy, Si Few J_ Fe , 9;,: 1.s (,41L ) WAS GROUND WATERS ENCOUNTERED? - ye,5 L 0 P nci IF YES, AT WHAT 91311$3 - Is, E DEPTH? C_r 4,-r f A Reading Date Gross Time Net Time Depth to Water Net Drop PERCOLATION RATE (millutes/inch) TEST RUN BETWEEN FT AND--""FT� IA netrc Avie On Rr0RMEDBY: _(".C'11r),.',,, CERTIFIED BY: (6/79) DATE: 7125 OLD SEWARD H\4'Y. ( ,. _ ENGINEERS. i[C. ANCHORAGE, ALASKA 99503 S 349-6561 'rrall ntlr7N SOILS LUG f'Efi(:OI-A1ION r�sl 3 1BELRoorn - N j±_ „n1C I•Flrl rrltr_a�:ll /Z ��J .. /.'f T7- �J - r ' I.LCn, I7CSCi+I� TrUN .(��s�?— i —�LtK J1 I'til��T�E�K UIGy� TSS? my IV SIGN ,' T fd , trey 0-2•001;&ANic MATIERiAL 3 O-� 2.0 12.0 BLUE &RAY 5ANcbY S+uT w/ SGIhE 6?F,VE4, r ORL.Y r r t?ADED-MOSTLY F 7NES ✓r COA U S MOIST, CC Ht 51Vt, NON -A AST, G, o, Hrir?h MCKEP, SCA—,1E—RED C0B13LE ti 3� •� � 7 .Q c M Imo. l\lY ~ �l 2 C � G ' S ,8 �4 E 20 u� NOT To 5cAi-L= t:nSGROUND V:nTERS ENCOUNTERED' )/� _ - O 1F YCS AT WMinT (_ VrDIN iJ[l Dcpth 10 _- {ienO, nr) Clatr .... !o Ilk+Z' ! I• !,� .� M . n . !I / . -20 c I I l: GS 5 ro,rt. �'b JOHN E. SWANSON; �R� —� �- -- - i I : r0 S s/,b.. s •.°• V834 -E Fq "°•�...?t°° Fes' �� � J i � 55 � �v,rn. J. r - �► pROfES510hP �j� J� v PE RCOLr TIl']N F+r.TE TES: ttUr; (I(T.:(Cr. _—�.� (T� T— T InJ LCl� r�— C[ I t t r f I t t7 u Y --- PERrOFlr.A(O By DXTE z'Ll LIA. M le A VE. t^ND 5W VASS CA? v kaf 5 b a Ouse /o ` 4r1'14tTY EASEMt✓/�(i� �Oso�sry u� _ {-5774 6 , 4� 0 hereby certify that i have surveyed the following described property: LOST & SL01-1K I PA-Ssl-r 6Z5EK. VIEW szj&D. as recorded in the Anchorage Recording Precinct, Alaska , and that the improvements situated thereon are located as shown in this plot, vWN. 114.5. M. PLOT PLAJ F8. AS-sutcT ;lt l GV -v. ci iC . NGfN 1Nc� GoMPAN Lo -r 6 , &L.oc.K 1 Gr'tD: F7LAT70-15 PATS: 7/Its/s3 i P2o�tEcTt4o. DATS1 P'X0688 RA9SIT C -Z6 k VIEW SUGO. ANe W,�OAAGS, AIC. �Ig51 i 34S - G 7�efa. t~!n l of 1 Jule G; 1977 Derr,''Ut ;i7i:272 Mir. William R. Robe � s Star Route A Lox 441 anchorage, Alaska 99507 Subject2 Permit Expiration Dear Mir. Roberts A permit issued by this department for well and/or on-site sewer installation on Lot 6 s3 -lock 1 Rabbit Creek View Subdivision has expired since the issue date exceeds one (1) Year. In the event you still elan to install the well and/or on-site sewer system, a new permit is required. The original soil test may be used to'obtain a current permit. if the well has been drilled, a well log should be sent to this department to document the installation_ date. If you have any questions regarding the above matter, please do not hesitate to contact this office immediately at 279- 2511, extension 224 or 225. Sincerely, Les N. Buchholz, R.S. Sanitarian LNIB .1 j h 1 --, , ����1��� .��1��� ��� ����� �� - � �/ ��// DEPHRTMEN � HEALTH AND ENVIRONMENTAL oOTECTION 2510 E. TUDOR RD., ANCHORAGE, HK. 99507 276-2221 K���--���-FF- ��G��J E—= F-,-" ����F���1 -� PERMIT NO. ( 76272 ) APPLICANT STH BOX 441 NONE LOCATION OFF LARK ROAD LEGAL L6 B1 RABBIT CREEK VIEW SID LOT SIZE 45000 SQUARE FEET TYPE OF SOIL HBSORBTION SYSTEM IS: TRENCH MHXIMUM NUMBER OF BEDROOMS = ] SOIL -RATING (SQ FT/BR)= 125 ^ THE REQUIRED SIZE OF THE SOIL ABSORPTION 5YSTEM IS:, ` THE LENGTH DIMENSION IS THE LENGTH <IN FEET) OF THE TRENCH OR DRAINFIELD. THE DEPTH OF A TRENCH OR PIT 15 THE DISTANCE BETWEN THE SURFACE OF THE GROUND AND THE BOTTOM OF THE EXCAVATIONAIN FEMN). THERE 15 NO SET WIDTH FOR TRENCHES. _7 THE GRAVEL DEPTH IS THE MINIMUM DEPTH OF GRAVEL BETWEEN THE OUTFALL PIPE AND THE BOTTOM OF THE EXCAVATION (IN FEET). !EE- BACKFILLING OF ANY SYSTEM WITHOUT FINAL INSINTION AND APPROVAL BY THIS DEPARTMENT WILL BE SOBJECT TO PROSECUTION., MINIMUM DISTANCE BETWEEN A WELL AND ANY Chy SITE SEWAGE DISPOSAL SYSTEM IS 100 FEET FOR A PRIVATEAELL OR 200 FEET qbR A PUBLIC WELL. SPECIFICATIONS AND CONSTRUCTION DIAGRAM /ARE AVAILABLE TO INSURE PROPER I -IF flD F -R �ri'41E- �UEE'F:�F? L----. \ I CERTIFY THAT , 1: I HM FAMILIAR WITH THE REQUIREMENTS FOR ON-SITE SEWERS AND WELLS AS SET FORTH BY THE MUNICIPALITY OF ANCHORAGE. 2: I WILL INSTALL THE SYSTEM IN ACCORDANCE WITH THE CODES. ]: I UNDERSTAND THAT THE ON-SITE SEWER SYSTEM MAY REQUIRE ENLARGEMENT IF THE RESIDENCE IS REME) ED TO INCLUDE MORE.THAN -1 BEDROOMS. SIGNED: ----- _L_-�_-- _ --------- APPLICANT— 4ILLIAM R ROBERTS ISSUED BY___ _-L~��-�� DHTE___������-L�{��__ �� �� - _"AMA; 'y Performed forR� S C3tt: L CJ C -+>L W+! LL I ROB_ERTS Legal Description :RABBIT CREE-K VIEW SUBDIVI This form reports:— Soils log -x: —'--- Depth Feet l- T 2 - 3 - �J N`4=. v 6 -- / OVERBURDEN( DARK PEAT) BROWNISH CLA-YEY LOAM GRAYISH CLAY (7350, S$11,.TY SAS•D AND GRAVEL (225) GRAYISH SAND WITH SILT (250)", cfl LAT -1 o N T�sT Performed MAj 2LF 1 6 1.0N�- Percolation test -` STRATIFIED SAND AND GRAVEL (125) S/0 Was ground water encountered? N'6' _ _ If ves, at what depth? -- ( NOTE: GROUND APPEARED FROZEN AT 2-6 FT. LEVEL; ICE WATER SEEPING DOWN) Reading Date Gross Time _ Net Time gD-'�pth to Water Net Drop --------- -- -------- ----=------------- 1--- — -- -----... ---- Pe--rco—lation----rate minute. i'roElosed .instal iat Ion.- Setvbaacje Pit _ Drain Fieri ;jepth of Inlet _ _ _ 3Ueptlltto bortom of pit or- Lrellci, _---- - _--------- COHIIJEiiTS:8 BELD_W___&'__DEPTH LE-V_ELr_GR.011.ND..._I-S-.P-OB-O-US_-E-MOUG-M_T-O.AB_S.O.F_.BFIDL_F_ _ SE_ E-FL_U-ENT AT RATE OF 125 SQ.FT. PER BEDROOM.UFLUENT"- ELEVATUON, PIT OI'} -SRAIN FIELD, SHOULD BE NO _H IGHER .THA.N _8.FT,_B.ELOW_ GROU1,I_D_ .LEVEL.-ABD_V.E_E_PT}i--U.S. NOT- RE.C-O-M.MENDED.- . Perforr ed Ly: LEO M. THOMPSEN -- - f.C'r-tl Fi"(i L,y:, 'Da Le: JUNE! 1976 li(1 040 (61 %4) __.. ..