Loading...
HomeMy WebLinkAboutDRAKE BLK 2 LT 2BDrake Block 2 Lot 2B #017-461-29 kmuv uoiuu ion Municipality of Anchorage On-Site Water and Wastewater Section • (907) 343-7904 Page 1 of 3 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP231218 PID Number: 017-461-29 Dwelling: ❑® Single Family (SF) ❑ with ADU ❑ Duplex (D) ❑ Two Single Family Project: ❑ New ❑o` Upgrade Name Ted McGovern ABSORPTION FIELD El Deep Trench [P Wide Trench E] Bed E] Mound Site Address 3150 Huffman Rd ❑ Other Phone (907) 632-8747 Number of Bedrooms 4 Soil Rating Total depth from original grade 4 GPD/SF 2.0 Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade 1.5 Ft. Gravel depth beneath pipe 0.5 Ft. Subdivision Block Lot Drake Subdivision 2 26 Fill added above original grade 1.0 Ft. Gravel length 40 Ft. Township Range Section Gravel width 5 Ft. Beds: Number of Lines n/a Distance between lines n/a Ft. SEPARATION DISTANCES To Septic Tank Absorption Lift Station Holding Sewer Total absorption area Number of trenches 1 Dist. between trenches From Field Tank Line 200 Ftz —10.5 Ft. Well N/A >100' N/A N/A >25' K ❑ Septic ❑ S.T.E.P. ❑ Holding ❑ Other Manu fac r Capacity Surface Water N/A >100' N/A N/AGal. Material Number of compartments Lot Line N/A >10' N/A N/A NA Foundation N/A >10' N/A N/A LIFT STATION Manufacturer Ca t Gal. Remarks Field is insulated Alarm location Electrical installed b Installer k to PIPE MATERIAL House to tank D3034 Tank to D3034 ainfield JR's Septic Drainfield D3034 CO/MTD3034 Inspector B. Schiller BENCH MARK (Assumed elevation) 100 ft Inspection 1s` 8/17/23 Location and description 3rd °d Garage man-door threshold 4'n ON-SITE WATER AND WASTEWATER SECTION APPROVAL Engineer's Stamp NaF Conditional Approval: Date 7, CO (�� Benjamin Schiller 0 Septic Syste Approved Date - Zs a ¢d��'srF9•.C$21/232..-,\§`,®�,�G PROFESS10W �� Note: this approvd does not include well permit requirements. kmuv uoiuu ion Benjamin Schiller CE 12592R E GISTEREDPROFES S I O N A L E N GINEER 1"=50' CO - CLEANOUT 2CO - DOUBLE CLEANOUT FCO - FOUNDATION CLEANOUT FS - FLOW SPLITTER VALVE MH - MANHOLE MT - MONITORING TUBE SV - SEPTIC VENT TH - TEST HOLE LEGEND PERMIT # OSP231218 PID # 017-461-29 DRAKE SUBDIVISION, BLOCK 2 LOT 2B A B FCO 64.2 SV 65.7 MH1 67.5 MH2 75.3 MT1 48.4 MT2 21.5 8.2 12.0 19.4 21.1 71.3 85.8 FEET 0 50 100 HUFFMAN ROAD 4-BDRM HOME 295 PLAN AS-BUILT 8/21/23 300 305 1500-GAL STEP TANK W/ AX20 POD AUX PUMP VAULT EXISTING 42' LONG x 5' WIDE, 0.5' EFFECTIVE DEPTH ABSORPTION TRENCH IN FAILURE, KEEP AS A BACKUP TRENCH EXISTING FRENCH DRAIN 10' UTILITY EASEMENT 10' UTILITY EASEMENT DECK SHED SHEDS NEW 40' LONG x 5' WIDE, 0.5' EFFECTIVE DEPTH ABSORPTION TRENCH 8/2013 TEST HOLE MT1 MT2 A B MH1 MH2 FCO SV BM EXISTING FIELD DECOMMISSIONED PROFILE AS-BUILT (NO SCALE) 40' DRAINFIELD ROCK MT 1 TH # 1 GROUNDWATER @ 92.0 7/19/2013 97.6 84.6 97.6 MT 2 Benjamin Schiller CE 12592 R E GISTEREDPROFES S I O N A L E N GINEER 8/21/23 PERMIT # OSP231218 PID # 017-461-29 DRAKE SUBDIVISION, BLOCK 2 LOT 2B 100.6 FINAL GRADE MOA-APPROVED SAND 96.6 99.6 ORIGINAL GRADE 98.1INSULATION WOODFFENCE HUFFMAN ROAD 4 EAST 160.00 CHAIN LINK FENCE OFgt4%%4 C'9`49 r SHANE A. HOLT...' p LS -6914 0` Q�a d o �ArO fessiona\ foo EAST 170 00 THE INFORMATION HEREON IS FOR THE USE OF LENDING INSTITUTIONS SPECIFICALLY TO SHOW ANY CONFLICTS BETWEEN EXISTING STRUCTURES AND PLATTED LOT LINES AND/OR EASEMENTS; AND IS NOT TO BE USED FOR POSITIONING ADDITIONAL STRUCTURES, IMPROVEMENTS, OR FENCELINES. EASEMENTS OF RECORD OR OTHER RIGHTS OF WAY, OR ANY ENTITY NOT ON THE RECORD PLAT ARE NOT SHOWN HEREON, UNLESS NOTED. NOTE. FENCELINES THAT MAY APPEAR ON THIS DRAWING ARE NOT TO BE USED TO DETERMNE PROPERTY LINES OR POSITION ADDITIONAL IMPROVEMENTS. ANY PAVING SHOWN HEREON MAYBE APPROXIMATE DUE TO EXCESSIVE SNOW AND/OR ICE. ONLY VISIBLE IMPROVEMENTS ARE SHOWN HEREON 0 THESURVEYDATA AND MEASUREMENTS HEREONAREPREPARED FOR THE OWNER OFRECORD AS OF THEDA TE OF THIS SURVEY ANYUSE OF THIS DRAWING BY THIRD PARTIES IS PROHIBITED UNLESS WRITTEN PERMISSION IS PROVIDED. AS-BUILTSURVEY I" =301 NO CORNERS SET THIS DATE I HEREBY CERTIFY THA T I HA VE PERFORMED A SURVEY OF THE FOLLOWING DESCRIBED PROPERTY LOT25 BLOCK 2DRAKESUB (PLAT78-267) A NCHORA GE RECORDING DISTRICT, ALASKA, AND THAT THE VISIBLE IMPROVEMENTS SITUA TED THEREON ARE WITHIN THEPROPERTYLINESANDNO VISIBLEENCROACHMENTS EXIST OTHER THAN NOTED. DATED ATANCHORAGE,ALASKA THIS 18 - DAYOF AUGUST 2023 HOLT LAND SURVEYING 9309 GROVER DRIVE ANCHORAGE,AK 99507 15896 234-3 PP3-sez5 MUNICIPALITY OF ANCHORAGE On -Site Water & Wastewater Program PO Box 196650 4700 Elmore Road Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997 hftp://www.muni.org/onsite On -Site Wastewater Disposal System Permit Permit Number: OSP231218 Work Type: Septic Upgrade Tax Code Number: 01746129000 Site Legal Address: DRAKE BLK 2 LT 26 G:2834 Site Mailing Address: 3150 HUFFMAN RD, Anchorage Owner: MCGOVERN THEODORE J & Design Engineer: FORGE ENGINEERING This permit is for the construction of: Effective Date Expiration Date: lz�ent S �o Q�v Department Lot Size in Sq Ft: Total Bedrooms: 7/20/2023 7/19/2024 46450 Q Disposal Field ❑ Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage All construction shall be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80) 3. The wastewater code requires inspections during the installation. The engineer shall notify the Development Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather shall be either: a. Opened and Closed on the same day, or b. Covered, sealed, and heated to prevent freezing i Special Provisions: • The 1980 trench is to be decommissioned. Regi may: % . SS�tP�1 e— Issued By: Date: Date: ZU r 4 MUNICIPALITY OF ANCHORAGE Community Development Department Phone: 907-343-7904 Development Services Division Fax: 907-343-7997 On -Site Water & Wastewater Program ON-SITE SEWER/WELL PERMIT APPLICATION Parcel I.D. 017-461-29 Property owner(s) Ted McGovern Day phone (907) 632-8747 Mailing address 3150 Huffman Rd, Anchorage, AK 99516 Site address 3150 Huffman Rd, Anchorage, AK 99516 Legal description (Sub'd., Block & Lot) Drake Subdivision, Block 2 Lot 213 Legal description (Township, Range & Section) Lot Size 46,450 Sq. Ft. Number of Bedrooms 4 APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: (N all that apply) Absorption Field ❑X Initial ❑ Single Family (SF) ❑X Septic Tank ElUpgrade ❑X (w/wo AD U) (D) ❑ Holding Tank ElRenewal ElDuplex Multiple Dwellings ❑ Privy ❑ (SF and/or D) Private Well ❑ Water Storage ❑ THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR: Distance: I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit/Rush Fees: 19-1 Z Waiver Fees: Date of Payment: Receipt Number: Permit No. as P 2312 1 e Permit App_::-: ,—.,:c; Date of Payment: Receipt Number: Waiver No. July 18, 2023 MOA Development Services, On-Site Water & Wastewater Program 4700 Elmore Rd Anchorage, AK 99507 Subject: Drake Block 2 Lot 2B – 3150 Huffman Road Trench Replacement Dear On-Site Services Engineer: The existing trench on the above lot is in failure, so we are submitting this permit application for the construction of a new septic trench. The attached site plan identifies the location of the home and existing systems as well as the new trench. The ground surface on the lot is basically flat with only very slight slopes in any direction. Contours are shown on the site plan showing the grade and direction of flow. The new trench will be constructed parallel to the slope as much as possible. Wells on this and adjacent lots are shown. The new trench will be a minimum of 50’ from all wells and surface water, and more than 6’ away from the existing trench. There is an older trench that was connected to the pump vault, which will be decommissioned because it appears to be in groundwater. Inside the pump vault is a connection to that old trench, and that connection will be used for the new trench. This will allow both this new trench and the existing failed trench to be used in the future. Please refer to the attached test hole log, plan and profile pages for the septic design. If this design is followed, there will be no adverse impacts to adjacent properties. Sincerely, Benjamin Schiller, PE Municipality of Anchorage On-site Water and Wastewater REVIEWED FOR CODE COMPLIANCE OSP231218, Deb Wockenfuss, 07/20/23 Benjamin Schiller CE 12592REGISTEREDPROFESSION A L E N GINEER 1"=50' CO - CLEANOUT 2CO - DOUBLE CLEANOUT FCO - FOUNDATION CLEANOUT FS - FLOW SPLITTER VALVE MH - MANHOLE MT - MONITORING TUBE SV - SEPTIC VENT TH - TEST HOLE LEGEND DRAKE SUBDIVISION, BLOCK 2 LOT 2B FEET 0 50 100 HUFFMAN ROAD 4-BDRM HOME 295 SEPTIC PLAN 7/17/23 300 305 DECOMMISION OLD DRAIN FIELD 1500-GAL STEP TANK W/ AX20 POD AUX PUMP VAULT EXISTING 42' LONG x 5' WIDE, 0.5' EFFECTIVE DEPTH ABSORPTION TRENCH IN FAILURE, KEEP AS A BACKUP TRENCH EXISTING FRENCH DRAIN 10' UTILITY EASEMENT 10' UTILITY EASEMENT DECK SHED SHEDSHED PROPOSED 40' LONG x 5' WIDE, 0.5' EFFECTIVE DEPTH ABSORPTION TRENCH WITH 0.5' SAND LAYER 8/2013 TEST HOLE 10' MIN MT MT Municipality of Anchorage On-site Water and Wastewater REVIEWED FOR CODE COMPLIANCE OSP231218, Deb Wockenfuss, 07/20/23 DRAKE SUBDIVISION, BLOCK 2 LOT 2B TYPICAL TRENCH SECTION (NO SCALE) NOTES: 1. GRADE AREA OVER TRENCH TO DRAIN AWAY 2. PROVIDE 3' OF COVER OVER TRENCHES AND 4' OVER SEPTIC TANK, OR 2' WITH 2" OF INSULATION 3. CHECK GROUNDWATER AT TIME OF CONSTRUCTION. IF LEVEL IS HIGHER THAN PREVIOUSLY OBSERVED, CALL ENGINEER IMMEDIATELY Benjamin Schiller CE 12592REGISTEREDPROFESSION A L E N GINEER 5' DESIGN FACTORS:SYSTEM REQUIREMENTS: 600 GPD PEAK FLOW PERK RATE: 28 MIN/IN APPLICATION RATE: 4 GPD/SF 5' WIDE TRENCH SYSTEM 1500-GAL ADVANTEX SYSTEM STEP TANK W/ AX20 POD & PUMP VAULT BOTTOM OF TRENCH: 2.5' BELOW GRADE PLACE SAND BELOW TO TOP OF RECEIVING SOILS (3' BELOW GRADE) FLOW LINE ELEVATION: 2' BELOW GRADE 600 GPD / 4 GPD/SF / 5' WIDE * 1.0 RED FACTOR [0.5 DEEP])= 30 LF TRENCH REQUIRED (40 LF SPECIFIED) GEOTEXTILE FABRIC AND INSULATION 1.25" PVC w/ 20 x 1 8" ORIFICES EVENLY SPACED @ 2' OC (HOLES DOWN) 7/17/23 1' PROVIDE ADDITIONAL 6" FILL TO ACCOUNT FOR SETTLEMENT 2' 6" 6" DRAINFIELD ROCK 6" MOA APPROVED SAND Municipality of Anchorage On-site Water and Wastewater REVIEWED FOR CODE COMPLIANCE OSP231218, Deb Wockenfuss, 07/20/23 AJ NIS OF ANCHORAGE ADVANCED WASTTE WATERTRE' AT -NJ ENT SYSTEM VIATNTENANCr. AND REPAIR AGREEMENT THIS MAINTENANCE AND REPMR AGIZEBIENT. herein the-AGREEMENT"inadcarId entered i lito as of this -Z� �t Day of by and betweeii the Municipality of Anchorage. herein the -MUNICIPALITY". in accordance with Alichorage Mui)icipal Code (AMC) 15,65.365. 111 consideration ol'the Mutual co\,criarits contained herein, the parties to this A2recincrit a<�ree as follows: 1. Advanced WasteNvater Treatment Systems. 'I'lie Municipality grants a permission to the Owner to utilize and operate an Advanced Wastewater Treatment System (A\VW-I*S), described as Advantex System located at (legal description) Drake Block 2 Lot 2B 1 71VIrairitenance. ReL)aii-s and Alterations. (Owner is required to read, understand and initial each section) Throughout the term off this Agreement. the Ow�ncr shall enter into a service Z�agreement. With an Ate WTS service and maintenance provider approved by the Municipality or the 111,1111tracturer's representative. The ANVWTS shall be maintained in a satisfactory condition capable of performing as designed and producing treated septic effluent In zr - accordance with, the equipment's approval for operation in the IMurilcipality. It shall be the responsibility of the ON�aner during the term of this Agreement to pay for all repair(s), maintenance, adJUStInellt(s), replacement costs'. and inspection costs. This includes an annual maintenance fee (typically $400 to $600). Owner agrees that only maintenance and repair personnel approved by the INIwilcipality or the manufacturer's representative will inspect and make any necessary maintenance, repairs or permitted alteratiotis to the systein. ':jF&ptA Owneracknowledgesthat regular maintenance of anAWWTS reduces the potential failure or tile sy=stem, which Could include sewage backup and costly repairs or draii-Ifield 7C\ , 1)2 ! ,]'-I.7! it 11ctulc 1 0,11 i 0xvner acknovviedges that the NfunicipalitN may request records of maintenance and repairs fi-orn the nianUftiCtUreCs representative Or maintenance provider. Owner acknowledges that the fine for failing to maintain and repair an A TS may tae Z� assessed in accordance with ANIC 14.60.0' )0. Owner agrees to grant the reasonable access to test and inspect the J_ AWWFS. The N141.11liCipalit). will give at least 24-hour notice. 11—M Owner agrees that any sale or transfer of title of tile propert�v Will not OCCLIr%VitllOLIt a new - Certificate of On -Site Systems Approval. Owner agrees that the AWWTS installation and maintenance requirements as provided by the A\VN\I'TS vendor,i nstal ler and approved by the Municipalivy are the governing guidelines for the construction. maintenance and repair Of the Owner's AWWTS. Owner agrees to maintain remote monitoring of the ANN"WTS as required by the AWWTS approval. 3. Term. The term of this Agreement shall begin on the date of approval by the Municipality to operate the installed sNIstern. or Lipoll transfer of title. and shall continue while the AWW"FS is operational or until title is transferred. 4. 'Nonivaivet-. The failure of the Municipality at any time to enforce a provision of this Agreement shall in no 'LlY constitute a Waiver Of tile provisions. nor in any way aftlect the validity of the Agreement or any part hereof, or the riolit of the MtInic ipality thereafter to enforce every provision hereof. 5. Amendment. This Agreement shall only be amended by authorized representatives of the Owner and N'lunicipality. Any attempt to amend this agreement by either all unauthorized representative or unauthorized means shall be void. 6. Jurisdiction: Choice of Law. Any civil action arlsing, fi-orn this Agreement shall be brought in the Superior Court for the Third i Judicial District of the State of Alaska at Anchorage. The laws of the State of Alaska shall govern the rights and obligations of the parties under this Agreement. 7. Severability. Any provisions of this Agreement decreed invalid by a court of competent Jurisdiction shall not invalidate the remaining provisions of the Agreement. (rev. 0 /1812015) Page 2 of 3 OMVNER: By: /4 �G cyerl" (slUnaturc) Date: Z -a ? Z3 l��i2 C ame) STATE OF ALASKA ) ss. THIRD JUDICIAL. DISTRICT ) The 6, regoin� instrument was acknowledged before me this �Uclal' of off, >'.-- - I t1✓ ,16mel-l? �. J. Johmon NOT LIC FOR ALASKA �. "official scar" Notary Public ,� Cr lllllSS1011 ZXj�ll'C5:—// State of Alaska Coaunusia�,p 191024010 IM4=3 MUNICIPALITY: By:--��(/� (signature) Date: (print name) Title: (rev. 0-118/2018) Page 3 of inspeCti iI KUP011 I -I -V-7 O Municipality of Anchorage Community Development Department Page 1 of 3 On -Site Water and Wastewater Program 4700 Elmore St. • P.O. Box 196650 Anchorage, AK 99519-6650 • http://www.muni.org/onsite • (907) 343-7904 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP131224 PID Number: 017-461-29 ❑ New ❑✓ Upgrade Name: Joyce Swanson ABSORPTION FIELD ❑ Deep Trench ❑✓ Shallow Trench ❑ Bed ❑ Mound Address 3150 Huffman Road ❑ Other Phone Number of Bedrooms Soil Rating Total depth from original grade 4 4 GPD/SF 1.5 Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade 1.0 Ft. Gravel depth beneath pipe 0.58Ft. Subdivision Block Lot Drake 2 2B Fill added above original grade 1.5 FL Gravel length 42 FL Township Range Section Gravel width 5Ft. Beds: Number of LinesDistance n/a between lines n/aFt. SEPARATION DISTANCES To Septic Absorption Lift Station Holding Sewer Total absorption area Number of trenches Dist. between trenches From Tank Field Tank Line 210 Flz 1 n/aFt. Well 100.3 144.3 114.0 N/A 93.1 TANK ❑ Septic p S.T.E.P. ❑ Holding ❑ Other Manufacturer Anchorage Tank/ Orenco Capacity 1500Gal. Surface water 100+ 100+ 100+ N/A Material Number of compartments Lot Line 30.3 43.3 22.7 N/A Plastic 2 NA Foundation 7.7 40.7 19.9 N/A LIFT STATION Manufacturer Capacity Curtain Drain 123.2 37.3 137.0 N/A Orenco 500 Gal Remarks Pump on level at 42 in. Pump off level at 40h.1 High water alarm at 43 in. Pump make and model P2005 Electrical Inspections performed by / " ' (3 A Installer PIPE MATERIAL House to tank sank to 3034 draintield 3034 A+ Home Services Drainfield 3034 CorMT 3034 Inspector Pannone Engineering Services BENCHMARK (Assumed elevation) 100ft Inspection f" g/14/2013 dates: a 2^ 8/14/2013 Location and description 3rd 8/15/2013 4" Corner of House COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL Engineers Stamp Conditional Approval: Date "10, t'te -e`n 1�' �annome * , OE 8149 Approved Date -1:13 inspeCti iI KUP011 I -I -V-7 O /M 1 M , HUFFMAN ROAD 10' UTILITY EASEMENT 1 � 3 1 WELL (E) 3 a r L2.3 0 100.3 i 48R HOUSE (E) a 15009 S.T. E. P. TANK (P) T;.I DECK W/ AX20 POD LS 11 AND AUX PUMP VAULT LS2 ...... 12 TH-1 M,.� 12509 SEPTIC TANK (E) ss ABANDONED PER CODE ss M1 SEPTIC AREA (E) 3A 148.3 SHED I � -43.3 " ... 4z FRENCH DRAIN (E) 37.3--4 i DRAIN FIELD (P) 42LF x 5'W x 0.5'ED x 1.5'TD DRAIN FIELD (E) WITH t1.5' SAND IN FAILURE ❑ SHED RE -USE AS RESERVE SHED 10' UTILITY EASEMENT 7 10' UTILITY EASEMENT SEPTIC AREA (E) SEPTIC AREA (E) e� \M M "' NOTES: DRAWING PAMONE ENG SVC, LLC P.O. BOX 100217 ANCHORAGE, AK 99510 PHONE (907) 272-8218 FAX (907) 272-8211 DRAKE, BLOCK 2, LOT 2B JOYCE SWANSON 3150 HUFFMAN ROAD ANCHORAGE, AK 99516 ry •.. StevenR. -P r CE 8149 10/3/2013 Scale P.I'DNO . 017-461-29 e j PERMIT N0. OSP131224 Sheet 2 OF A B FC 12.5 T1 12.5 64.4 LS1 19.6 62.9 LS2 21.4 75.5 M1 86.9 57.8 M2 102.7 41.2 /M 1 M , HUFFMAN ROAD 10' UTILITY EASEMENT 1 � 3 1 WELL (E) 3 a r L2.3 0 100.3 i 48R HOUSE (E) a 15009 S.T. E. P. TANK (P) T;.I DECK W/ AX20 POD LS 11 AND AUX PUMP VAULT LS2 ...... 12 TH-1 M,.� 12509 SEPTIC TANK (E) ss ABANDONED PER CODE ss M1 SEPTIC AREA (E) 3A 148.3 SHED I � -43.3 " ... 4z FRENCH DRAIN (E) 37.3--4 i DRAIN FIELD (P) 42LF x 5'W x 0.5'ED x 1.5'TD DRAIN FIELD (E) WITH t1.5' SAND IN FAILURE ❑ SHED RE -USE AS RESERVE SHED 10' UTILITY EASEMENT 7 10' UTILITY EASEMENT SEPTIC AREA (E) SEPTIC AREA (E) e� \M M "' NOTES: DRAWING PAMONE ENG SVC, LLC P.O. BOX 100217 ANCHORAGE, AK 99510 PHONE (907) 272-8218 FAX (907) 272-8211 DRAKE, BLOCK 2, LOT 2B JOYCE SWANSON 3150 HUFFMAN ROAD ANCHORAGE, AK 99516 ry •.. StevenR. -P r CE 8149 10/3/2013 Scale P.I'DNO . 017-461-29 e j PERMIT N0. OSP131224 Sheet 2 OF SPECIAL PROVISIONS TO SPECIFICATIONS 1. ALL CONSTRUCTION WAS INSTALLED AS SPECIFIED IN THE MOST CURRENT EDITION OF THE MUNICIPALITY OF ANCHORAGE STANDARD SPECIFICATIONS (MASS) FOR COMPONENT PARTS AND MATERIALS USED IN CONSTRUCTION OF ON-SITE WASTEWATER DISPOSAL SYSTEMS. 2. SCOPE OF WORK: INSTALLED NEW 1500g S.T.E.P. TANK WITH AX20 POD AND AUXILIARY PUMP VAULT, AND SOIL ABSORPTION SYSTEM. 3. GROUNDWATER WAS OBSERVED AT A DEPTH OF 7.6 FEET BELOW EXISTING GRADE AS EVIDENCED BY THE SOIL TEST HOLE. AN APPARENT WATER TABLE WAS NOT OBSERVED IN ANY OF THE EXCAVATIONS LESS THAN 7.6 FEET BELOW EXISTING GRADE. TH-1 OR101.]— 0.5= oL 100.2 ML 4- INSULATION ER FABRIC WIN ROCK 6' ABOVE PIPE INV .25" 0 DRAIN PIPE WRH P HOLES 24" D.C. -DRAIN ROCK REMOVE OL REPIWCE WITH SAND 21.5' SECTION DESIGN PARAMETERS UPGRADE SEPTIC SYSTEM NO. BEDROOM: 4 (600 gpd) TANK SIZE: 1500g S.T.E.P. W/ AX20 POD AND AUX PUMP VAULT PERC RATE = 28.0 MPI SOIL RATING: 4 GPD/SF AREA ROD: 150 SF SYS. TYPE: 5' WIDE TRENCH 0.5' E.D. MIN LENGTH: 30 LF USED: 42 LF X 5' WIDE, 0.5' E.D., 1.5' TD TOTAL AREA: 210 SF LEGEND W, WATER LINE/ WELL RADIUS — SS — NEW SEPTIC NOTES: PANNONE ENG SVC, LLC RECORD DRAWING P.O. BOX 100217 ANCHORAGE, AK 99510 PHONE (907) 272-8218 FAX (907) 272-8211 DRAKE, BLOCK 2, LOT 2B JOYCE SWANSON 3150 HUFFMAN ROAD DESIGN DETAILS ANCHORAGE, AK 99516 G::► G o\. CU COPPER DIP u m RIGID INSULATION m o FC FOUNDATION CLEAN OUT -15'0 BOH FILTER FABRIC c a z o MONITOR TUBE NO. o pRAIN ROCK 8" ABOVE PIPE INV C DCO DOUBLE CLEAN OUT DV s FS s BFG BELOW FINISH GRADE OG ORIGINAL GRADE GRAIN PIPE WITH FINISH GRADE TS&V TOPSOIL & VEGETATE x a 7§" HOLES 24" O.C. 3 103.2 "20 -1 OO. POD 4.0' MIN ",' -'° x x i x _,;. °a, -q, - -100.2 11 �"s`?x:^xz 4,>� ---98.] TRENCH SEE DESIGN DRAIN ROCK 95.5 NEW 15008 —sANp S.T.E.P. TANK PROFILE DESIGN PARAMETERS UPGRADE SEPTIC SYSTEM NO. BEDROOM: 4 (600 gpd) TANK SIZE: 1500g S.T.E.P. W/ AX20 POD AND AUX PUMP VAULT PERC RATE = 28.0 MPI SOIL RATING: 4 GPD/SF AREA ROD: 150 SF SYS. TYPE: 5' WIDE TRENCH 0.5' E.D. MIN LENGTH: 30 LF USED: 42 LF X 5' WIDE, 0.5' E.D., 1.5' TD TOTAL AREA: 210 SF LEGEND W, WATER LINE/ WELL RADIUS — SS — NEW SEPTIC NOTES: PANNONE ENG SVC, LLC RECORD DRAWING P.O. BOX 100217 ANCHORAGE, AK 99510 PHONE (907) 272-8218 FAX (907) 272-8211 DRAKE, BLOCK 2, LOT 2B JOYCE SWANSON 3150 HUFFMAN ROAD DESIGN DETAILS ANCHORAGE, AK 99516 G::► G o\. CU COPPER DIP DUCTILE IRON PIPE TH TEST HOLE FC FOUNDATION CLEAN OUT T# TANK CLEAN OUT N0, C# CLEAN OUT NO. M# MONITOR TUBE NO. R.I. RIGID INSULATION DCO DOUBLE CLEAN OUT DV DIVERTER VALVE FS FLOW SPLITTER BFG BELOW FINISH GRADE OG ORIGINAL GRADE FG FINISH GRADE TS&V TOPSOIL & VEGETATE Steven R. Par PF.•. CE 8149 10/3/2013 *y, NTS " P.I.D. NO 017-461-29 e PERMIT N0. 3 OF mnrC*lA 9LlLNa Cal NFv. (AraAA:n) =away— - — - — - — ------------------ "T BIMBea SRIQ' o HUFFMAN ROAD qF/4 1%tLai' 21eAa( 160.00' N90'OD'OD"E 3 cg o 0 0 A a m Z WELL 8 N90. 00' 001-E iv Ta.Ga o 2A 3A _ w . .. ...... SHED o .. _...... ,i ......., .. Ya 5' C oEXISTING o HOUSE y p C.O. F r Z q CO. M.H. 6 H � GP�E00 'V^/I/ SHFA Soso SHED ------------ -------- 10' UTIL ESMT N90' 00' W"W 170.00' UNDER NO CIRCUMSTANCES SHOULD AN AS-BUILT BE USED FOR CONSTRUCTION OR FOR ESTABLISHING BOUNDARY OR FENCE ONES. THE SURVEYOR TAKES RESPONSIBILITY FOR THE INITIAL TRANSACTION ONLY AND ASSUMES FINANCIAL LJADILITY ONLY FOR THE COST OF THE SURVEY. LISTED DISTANCES PREVAIL OVER SCALING. REPRODUCTION MAY CAUSE ERRORS IN SCALE. LJ LOT SURVEY SURVEY TYPE SYMBOLS ❑ FOUNDATION AS-BUILT SET REBAR ' DRAINAGE ASPHALT El FINAL STRUCTURE AS-BUILT 0 FOUND REBAR ❑ PLOT PUN ... AS-BUILT ... LOT SURVEY ... TCPDORAPHY 9.� WOOD FENCE CONCRETE ® AS-DUILT... NO WF114M SET 0REcmnncAnox As- IL7 CORNERS SET ODa ASSUMED ELEV. ,rK )( METAL FENCE WOOD DECK PLOT PLANS & LOT SURVEYS NOTE: IT IS THE RESPONSIBILITY OF THE BUILDER OR OWNER, PRIOR TO ONLY THOSE IMPROVEMENTS ABOVE GROUND AND VISIBLE WILL BE CONSTRUCTION. TO VERIFY PROPOSED BUILDING GRADE RELATVE SHOWN. FENCES, WELLS, SEPTIC CLEANOUTS. SIDEWALKS, DRIVEWAYS, TO FINISHED GRADE AND UTILITY CONNECTIONS AND TO DETERMINE ETC., ARE SHOWN IN THEIR APPROXIMATE LOCATION, ONLY. SNOW THE EXISTENCE OF ANY EASEMENTS, COVENANTS OR RESTRICTIONS MAY PREVENT SOME IMPROVEMENTS FROM BEING SEEN AND LOCATED, WHICH DO NOT APPEAR ON THE RECORDED SUBDIVISION PLAT. ALL DISTANCES ARE RECORD UNLESS OTHERWISE NOTED. SURVEY CERTIFICATIONPrepared ♦lE_ C • OF s by I ,L I _ I_ ._ I.- 0. A R6D�1`t E. jurmS, if. a: /-\SSOC. PLOT PLAN +•�P. .................��♦ Professional Land Surveyors ew lat bawl ak a«..a»e Nwaal eH tlwt new rwar « wnawwa a a w NA eunwa ••''•• •'�� 1700 Brink Drive. a• �^ ae � e'w' � u � aaw «mT ANCHORAGE, ALASKA 99504 w,ar.aa. w,a mNua a sw,www new can': i {% . Scale: ,I _ I 1 �O Rec. Lot S.F. Rec. Plat File No. wae..r w wb . t ! 49 FOUNDATION AS-BUILT I. AwwH E a• nwlby bws I �• ••• •••• ••••✓•a.: ....... �q • _ byM .Iam, ..wr - / '"�� ,.. / •,. • 'AT '.• Date Surve d: K 10/09/13 Drawn b Y REJ Checked J K w w.�. ^ ROGER NS, JR. Date Drawn: 10/10/13 Grid: 2834 W.O. 13-533 aw' waro~i.wamaana wt . AW -�2�— FlNhLa STRUCTURE AS-BUILT*`pli`-• I, Amwa c Awa, i. nwly nae ,e� (r r° ''>, Legal Description: awmr Pa 1 ,.�' ase oE� °d p "'•••,••••••"`,�h ��` Lot 2B BLOCK 2 aMwwaea ..a nTwn,euen m www, Awawl ` i ro f t T-t DRAKE On -Site Wastewater Disposal System Permit MUNICIPALITY OF ANCHORAGE Development Services Department On -Site Water & Wastewater Program 4700 Elmore Road, PO Box 196650 Anchorage, AK 99519-6650 Telephone: (907) 343-7904 Permit Number: OSP131224 Tax Code Number: 01746129000 Work Type: Septic Permit Effective Dates: August 13, 2013 to August 13, 2014 Design Engineer: PANNONE ENGINEERING SERVICE Subdivision: DRAKE Site Legal Address: DRAKE BLK 2 LT 2B G:2834 Owner/Address: SWANSON JOYCE E LIVING TRUST SWANSON JOYCE E / TTE 3150 E HUFFMAN RD ANCHORAGE AK 995162043 Site Mailing Address: 3150 HUFFMAN RD, Anchorage This permit is for the construction of: Y Disposal Field Y Septic Tank N Holding Tank Lot Size in Sq Ft: 46450 Total Bedrooms: 4 N Privy N Private Well N Water Storage All construction must be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80). 3. The wastewater code requires inspections during the installation. The engineer must notify the Development Services Department at least 2 hours prior to each inspection. Provide notification by calling (907) 343-7904 (24 hours). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather must either: A. Open and Close on the same day. B. Covered, sealed, and heated to prevent freezing. Received Issued By: MUNICIPALITY OF ANCHORAGE WMIN Community Development Department Phone: 907-343-7904 Development Services Division Fax: 907-343-7997 On -Site Water & Wastewater Program ON-SITE SEWER/WELL PERMIT APPLICATION Parcell.D. 017-461-29 Property owner(s) Joyce Swanson Day phone Mailing address 3150 E. Huffman Road, Anchorage, AK 99516 Site address 3150 E. Huffman Road Legal description (Sub'd., Block & Lot) Drake, Block 2, Lot 2B Legal description (Township, Range & Section) Lot Size 46,450 Sq. Ft. Number of Bedrooms 4 APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: (M all that apply) Absorption Field Initial ❑ Single Family (SF) 0 (w/wo ADU) Septic Tank Q Upgrade N Duplex (D) ❑ Holding Tank El Renewal ElDuplex Dwellings ❑ Privy ❑ (SF and/or D) Private Well ❑ Water Storage ❑ THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR: Distance: I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes. property owner or autnorized agent) Permit/Rush Fees: G 3 O' Date of Payment: IA Ll 112) JyR_ Receipt Number: 'I ;i G Permit No. Mi�'3��a Permit App_: :�.:c; Waiver Fees: Date of Payment: Receipt Number: Waiver No. Pannone Engineering Services uc Steven R. Pannone, Principal Registered Professional Engineer E-mail: steve(cDpanenzak.com July 22, 2013 Municipality of Anchorage Development Services Department On -Site Water & Wastewater Program 4700 S. Bragaw Street P. O. Box 196650 Anchorage, Alaska 99519 Subject: Drake, Block 2, Lot 2B Septic System Upgrade Permit Request Ladies and Gentlemen: I am writing to request a permit to install a septic system be issued for this property. The proposed systems will serve an existing four (4) bedroom house. Currently the lot is developed. The existing field is in failure and will be re -used as a reserve. The existing septic tank will be abandoned per code and a new 1500g S.T.E.P. tank with AX20 Pod and Auxiliary Pump Vault will be installed. This lot is served by a private well that is over 100 feet from the existing and proposed system. The surrounding developed lots are also served by private wells. There are no wells within 100 feet of this system. 1. Soils. One test hole was excavated in the area of this drain filed by Pannone Engineering Services in July of 2013, and groundwater was monitored at 7.6 feet below the surface. It is my opinion, based on the results of the percolation tests and overall soils appearance; an application rate of 4.0 gallons/day/square feet should be used for a CAT III wastewater system. 2. Soil Absorption System Design. a. See Sheet 2 of the design package. 3. Surface Water: There is no surface water within 100 feet of the proposed septic tank and drain field. The proposed drain field upgrade will maintain at least 100 feet from all surface water and drainage ditches. 4. Topography: The existing topography slopes from southeast to northwest at approximately 2% in the area of the proposed drain field. There are no steep slopes in the vicinity of the drain field. S. Drawing Markings: The Drawings are marked "For MoA Review Only". When written notification that the review is complete and that there are no further comments is received from MoA On -Site Department, the note will be removed and "Issued for Construction" drawings will be issued. Mailing: P.O. Box 100217, Anchorage, AK 99510-0217 Physical: 332 East Manor, Anchorage, AK 99501 Telephone: (907) 272-8218 FAX: (907) 272-8211 Page 2 of 2 The proposed installation will not affect the future development of the surrounding or existing lots. There are no wells or septic systems within 100 feet of the proposed septic location. If you have any questions or concerns, please contact me at 272-8218. Sincerely, Steven R. Pannone, P.E. Owner/Civil Engineer Attachments -Soils Log -Septic System Design Mailing: P.O. Pox 100217, Anchorage, AK 99510-0217 Physical: 332 East Manor Ave, Anchorage, AK 99501 Telephone: (907) 272-8218 FAX: (907) 272-8211 M /M 147.9 �\ w — u\ N1 uni roh HUFFMAN ROAD 10' UTILITY EASEMENT \ l _ � 3 WELL (E)� �. �3 wL2B 15008 S.T. E.P. TANK W/ AX20 POD AND AUX PUMP VAULT i 1250g SEPTIC TANK (E) ABANDON PER CODE 4BR JSE (E) DECK T I H — 1 ss 152.2 3A SHED � -46.8 �y FRENCH DRAIN (E) 40.8-1 ILSEPTIC AREA (E) DRAIN FIELD (P) 40LF x 5'W x 0.5'ED x 1.5'TD DRAIN FIELD (E) WITH t1.5' SAND IN FAILURE UUUUUU SHED SHED w____ RE—USE AS RESERVE 10' UTILITY EASEMENT 10' UTILITY EASEMENT - SEPTIC AREA (E) SEPTIC AREA (E) IF M �M �41 1 NOTES: �����\ Date PANNONE ENG SVC, LLC OF AC h 8/9/20,3 FOR CONSTRUCTION P.O. BOX 100217 ANCHORAGE, AK 99510 �� ""' q5' 1, PHONE (907) 272-8218 FAX (907) 272-8211 /�g�P �y'+ Scale *; 1,.=50' P.I.D. NO DRAKE, BLOCK 2, LOT 2B �i 017-461-29 an fi. JOYCE SWANSON Steven PERMIT NO. CE 8149 OSP131224 3150 HUFFMAN ROAD+�s., A PLAN ANCHORAGE, AK 99516 �>Il`fD.....p.. Sheet __ \,ROFESS �' 1 OF 4 SPECIAL PROVISIONS TO SPECIFICATIONS 1. ALL CONSTRUCTION SHALL BE INSTALLED AS SPECIFIED IN THE MOST CURRENT EDITION OF THE MUNICIPALITY OF ANCHORAGE STANDARD SPECIFICATIONS (MASS) FOR COMPONENT PARTS AND MATERIALS USED IN CONSTRUCTION OF ON-SITE WASTEWATER DISPOSAL SYSTEMS. 2. SCOPE OF WORK: INSTALL NEW 1500g S.T.E.P. TANK WITH AX20 POD AND AUXILIARY PUMP VAULT, AND SOIL ABSORPTION SYSTEM. 3. GROUNDWATER WAS OBSERVED AT A DEPTH OF 7.6 FEET BELOW EXISTING GRADE AS EVIDENCED BY THE SOIL TEST HOLE. IF AN APPARENT WATER TABLE IS OBSERVED IN ANY OF THE EXCAVATIONS LESS THAN 7.6 FEET BELOW EXISTING GRADE NOTIFY THE ENGINEER IMMEDIATELY. FOR RIGID INSUTATION -FILTER FABRIC COPPER DIP DUCTILE IRON PIPE TH TEST HOLE DRAIN ROCK 6' ABOVE PIPE INV FOUNDATION CLEAN OUT T# TANK CLEAN OUT NO. C# CLEAN OUT NO. M# 1.25" 0 DRAIN PIPE WITH R.I. RIGID INSULATION DCO DOUBLE CLEAN OUT DV DIVERTER VALVE Ye" HOLES 24" O.C. FLOW SPLITTER BFG BELOW FINISH GRADE OG ORIGINAL GRADE TH-1 25 TS&V TOPSOIL & VEGETATE -1.0 OR 0.5 05 i OL DRAIN ROCK -3.0 REMOVE OL REPLACE WITH SAND 11.5' ML a _7.6 - 7/19/13 SECTION m RIGID INSULATION m a r -15'0 BOH FILTER FABRIC F' z 'o o a DRAIN ROCK 6" ABOVE PIPE INV E 1.25" 0 GRAIN PIPE WITH a �" HOLES 24' O.C. M20 F00 4.0" IN TRENCH SEE DESIGN DRAIN ROCK 1500y SAND S.T.E.P. TANK (P) PROFILE DESIGN PARAMETERS UPGRADE SEPTIC SYSTEM NO. BEDROOM: 4 (600 gpd) TANK SIZE: 1500g S.T.E.P. W/ AX20 POD AND AUX PUMP VAULT PERC RATE = 28.0 MPI SOIL RATING: 4 GPD/SF AREA ROD: 150 SF SYS. TYPE: 5' WIDE TRENCH 0.5' E.D. MIN LENGTH: 30 LF USE: 40 LF X 5' WIDE, 0.5' E.D., 1.5' TD TOTAL AREA: 200 SF LEGEND W WATER LINE/ WELL RADIUS — SS — NEW SEPTIC NOTES: PANNONE ENG SVC, LLC RUCTION P.O. BOX 100217 ANCHORAGE, AK 99510 PHONE (907) 272-8218 FAX (907) 272-8211 DRAKE, BLOCK 2, LOT 2B JOYCE SWANSON 3150 HUFFMAN ROAD DESIGN DETAILS ANCHORAGE, AK 99516 ►_1.01:1CSav/ FIR IINa CU COPPER DIP DUCTILE IRON PIPE TH TEST HOLE FC FOUNDATION CLEAN OUT T# TANK CLEAN OUT NO. C# CLEAN OUT NO. M# MONITOR TUBE NO. R.I. RIGID INSULATION DCO DOUBLE CLEAN OUT DV DIVERTER VALVE FS FLOW SPLITTER BFG BELOW FINISH GRADE OG ORIGINAL GRADE FG FINISH GRADE TS&V TOPSOIL & VEGETATE CE 8149 013 Scale P.I.D. NO 017-461-29 1e PERMIT NO. ,q_/� OSP131224 r Sheet 2 OF SOILS LOG - PERCOLATION TEST SLOPE X TH SITE PLAN w 4BR HOUSE (E) WAS GROUNDWATER ENCOUNTERED? Y IF YES. AT WHAT DEPTH? 15.0' DEPTH TO WATER AFTER MONITORING? -7.6- DATE: 7/19/2013 IH -1 SHED SHED SHED 10' UTILITY EASEMENT 10' UTILITY EASEMENT SLOPE TH X READING DATE TEST HOLE NETTIME WATERTIME LEVEL READING OR ORGANICS 1 --- 4.80 — 2 10:40 30 MIN ORGANIC 2 3 OL SILTS 3 --- 4 11:10 30 MIN 5.90 4- 5 11:10 -- 4.80 5- 58SILT 6 11:40 30 MIN 5.87 6— SILT W/ 7 ML TRACES OF SAND AND GRAVEL S 9 10 11 12 13 14 15 BOH 16 17 18 DATE PERFORMED: 7/8/13 SOILS LOG - PERCOLATION TEST SLOPE X TH SITE PLAN w 4BR HOUSE (E) WAS GROUNDWATER ENCOUNTERED? Y IF YES. AT WHAT DEPTH? 15.0' DEPTH TO WATER AFTER MONITORING? -7.6- DATE: 7/19/2013 IH -1 SHED SHED SHED 10' UTILITY EASEMENT 10' UTILITY EASEMENT SLOPE TH X READING DATE CLOCK NETTIME WATERTIME LEVEL READING NET DROP 1 7/8/13 10:10 --- 4.80 — 2 10:40 30 MIN 6.08 1.28 3 10:40 — 4.80 --- 4 11:10 30 MIN 5.90 1.10 5 11:10 -- 4.80 -- 6 11:40 30 MIN 5.87 1.07 PEROLATION RATE 28.0 (minlinch) PERC HOLE DIAMETER 6 inches TEST RUN BETWEEN 3.5 FT AND 4.5 FT COMMENTS: Test hole excavated by A+ HOME SERVICES. Prec hole was Dresoaked.Perc test ran for at least 1 hour. Last three readings reported. PERFORMED BY: Steven R. Pannone, P.E. I CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDLINES IN EFFECT ON THE DATE OF THIS TEST. NOTES:OF PANNONE ENG SVC, LLCDate P.O. BOX 100217 ANCHORAGE, AK 99510 PHONE (907) 272-8218 FAX (907) 272-8211 q����l �-"••'•qs �) /�g�P9�+` • • I .. a nnone / �.•. CE 8149 j t♦+�sr ik,%... `=` 8/9/2013 FOR CONSTRUCTION scale NTS P.I.D. NO 17-461-29 PERMIT NO. OSP131224 DRAKE, BLOCK 2, LOT 2B JOYCE SWANSON 3150 HUFFMAN ROAD ANCHORAGE, AK 99516 SOILS LOG Sheet 4 ADVANTEX DESIGN AD 24" PASSIVE 4° JIM CAP AX20 PODS INSULATED AUXILIARY AIR RISER PUM VENT B IN 4" PUMP -OUT i i i 10 GAUGE 1500 --------- — — GALLON 64" ANCHORAGE TANK SLIDE SECTION OF 6" PIPE OVER THIS CONNECTION TO PROVIDE SHEER PROTECTION- 14' EXTEND TO BRIDGE EXCAVATION CAM oil r 1 Q� NOTES SVCLLC s���� Date F v e �.►.,� OF ?Cgsl�` 7/22/2013 P.O. BOX 100217 ANCHORAGE, AK 99510 r L' PHONE (907) 272-8218 FAX (907) 272-8211y+0, Scale 272-821100, Scale NTS �... .. ... ..... P.I.D. NO DRAKE, BLOCK 2, LOT 2B 07-461-29 JOYCE SWANSON / Steven f2. 'anno e j PERMIT N0. �F:. CE 8749 r 3150 HUFFMAN ROAD OSPxxXXXX fj �s r SITE SECTION ANCHORAGE, AK 99516 <<i� �s"= SheetOF 4 ADVANCED WASTEWATER TREATMENT SYSTEM MAINTENANCE AND REPAIR AGREEMENT DETWEEN MUNICIPALITY OF ANCHORAGE THIS MAINTENANCE AND REPAIR AGREEMENT made and entered into as of this Day of of 20 by and between herein the "OWNER," and the Municipality of Anchorage, herein the "MUNICIPALITY." In consideration of the mutual covenants contained herein, the parties to this Maintenance and Repair Agreement agree as follows: 1. Advanced Wastewater Treatment Systems. Municipality grants permission to Owner to utilize and operate an Advanced Wastewater Treatment System (AWWTS), described as D I/,{ I/ 7F Y�;, located at (legal description). 2. Definitions. Alteration. Any change to the design or function of an AW WTS that includes the installation or removal of any parts, components or pieces not included in the original construction permit and design. Certificate of On -Site Systems Approval (COSA). An approval by the Municipality of existing water and wastewater disposal systems given at the time of property sale and title transfer in accordance with Anchorage Municipal Code (hereinafter, "AMC") 15.65. These approvals certify that the systems are adequate for the homes that they support and meet the codes that were in place at the time of system construction. Damage. Any man-made or natural change in a system that would inhibit the system from performing as designed. Maintenance and Repair. The scheduled and as needed replacement of existing parts, components and pieces of an AWWTS that were included in the original design which would allow the AWWTS to continue to perform as designed. Permit. An On -Site Wastewater Disposal Permit as required by AMC 15.65 to construct and operate an AWWTS. 3. Term. The term of this Maintenance and Repair Agreement shall begin on the date of approval by the Municipality to operate the installed system or issuance of a COSA, and shall continue while the AWWTS is in use or is operational or until the property is sold or title is transferred by the owner and a new COSA is issued to the new owner or transferee of the property. 4. Alterations. Installation and Removal of Additional Equipment. Prior to performing any alterations to an AWWTS, the owner agrees to obtain an On-site Wastewater Disposal Permit from the Municipality in accordance with AMC 15.65. 5. Maintenance and Repairs. A. Throughout the term of this Maintenance and Repair Agreement, the Owner shall maintain their AWWTS in a satisfactory condition capable of producing treated septic effluent in accordance with the equipment's approval for operation in the Municipality. The owner shall enter into a service agreement with an AWWTS service and maintenance provider approved by the municipality and the manufacturer of the AWWTS for the entire term of the AWWTS. In addition, it shall be the responsibility of the Owner during the term of this Maintenance and Repair Agreement, and any renewals thereof, at the owner's sole expense, to pay for any and all: (1) repair(s), (2) maintenance, (3) adjustment(s), (4) replacement costs, and (5) inspection costs. B. Owner agrees to comply with all applicable ordinance, laws, regulations, rules and orders for the AWWTS. C. Upon request by the Municipality, the owner agrees to provide the Municipality a written schedule of routine maintenance and repairs which have been performed on the system. When a record of maintenance is documented and maintained by the system vendor, the owner agrees to allow the Municipality access to this information. D. Owner acknowledges that the fine for failing to maintain and repair an AWWTS may be assessed in accordance with AMC 14.60 for improper discharge. E. Owner agrees that only maintenance and repair personnel approved by the Municipality will inspect and make any necessary maintenance, repairs or permitted alterations to the system. F. Owner agrees to grant the Municipality reasonable access to test and inspect the AWWTS upon 24 hours written notice. G. Owner agrees that any sale or transfer of title of the property will not occur without a new Certificate of On -Site Systems Approval. H. Owner agrees that the AWWTS installation and maintenance requirements as provided by the AWWTS vendor/installer and approved by the Municipality are the governing guidelines for the construction, maintenance and repair of the 6. Nonwaiver. The failure of either party at any time to enforce a provision of this Maintenance and Repair Agreement shall in no way constitute a waiver of the provisions, nor in any way affect the validity of the Maintenance and Repair Agreement or any part hereof, or the right of such party thereafter to enforce each and every provision hereof. 7. Amendment. A. This Maintenance and Repair Agreement shall only be amended, modified or changed by a writing, executed by authorized representatives of the parties, with the same formality that this Maintenance and Repair Agreement was executed with, and such writing shall be attached to this Maintenance and Repair Agreement as an amendment. B. For the purposes of any amendment modification or change to the terms and conditions of this agreement, the only authorized representatives of the parties are: a. Owner: b. Municipality: Director, Community Development or designated authority C. Any attempt to amend, modify, or change this contract by either an unauthorized representative or unauthorized means shall be void. 8. Jurisdiction: Choice of Law. Any civil action arising from this Maintenance and Repair Agreement shall be brought in the Superior Court for the Third Judicial District of the State of Alaska at Anchorage. The laws of the State of Alaska shall govern the rights and obligations of the parties under this Maintenance and Repair Agreement. 9. Severability. Any provisions of this Maintenance and Repair Agreement decreed invalid by a court of competent jurisdiction shall not invalidate the remaining provisions of the Maintenance and Repair Agreement. OWNER: By: signature) Date: 15 (print name) STATE OF ALASKA ) ) ss. THIRD JUDICIAL DISTRICT ) The foregoing instrument was acknowledged before me this/J day of 4,?Us/ 20_U by :;G yC-2 . �Gc �rSyf2 NOTARY C PUBLIC FOR ALASKA My Commission expireawe:,c , aW6 l llJl\1CIPAL11 1 : By: �es C -re wJE d L-) (signature) Jr(print name) 6117 Date: Title: CC=ff 72-013 (Rev. 3/78) /) MUNICIPALITY OF ANCHORAGE 0 DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTION ENVIRONMENTAL ENGINEERING DIVISION 825 L Street - Anchorage, Alaska 99501 Telephone 264-4720 ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT NAME PHONE EW ❑UPGRADE MAILING ADDRESS N 7 LEGAL DESCRIPTION LOCATION /-/1 ^ NO. OF BEDROOMS DISTANCE TO: Well / fC9Q Abs or tign area Dwelling �/ I, &I PERMIT Imo.. �O3 7f (J vY /Vvt CL Q Manufacturer Mat eri No. of compartments W F. rn Liq. capacity��allons IF HOMEMADE: Inside length Width Liquid depth _jaz DISTANCE TO: Well Dwelling PERMIT NO. O Z Fa- Manufacturer Material Liquid capacity in gallons 0 DISTANCE TO: Well f /00 -j— Foundation , Nearest lot line PERMIT NO. Lu OT.LIv,/01 J LL Z No. of lines Len f e ch Lino, To I I gth f lin Trench w' th Distance between lines F Z W s inches Top tile to finish i Material beneath tile Total oF. of grade effective area -r�eMre Length Width Depth PERMIT NO. W 0 a H Type of crib Crib diameter Crib depth Total effective absorption area Wd W DISTANCE TO: Well Building foundation Nearest lot line Class Depth Driller Distance to lot line PERMIT NO. J W � DISTANCE T0: Building foundation i Sewer line I Septic tank I - Absorption area(s) OTHER PIPE MATERIALS SOIL TEST RATI NG 2 5- - 2 INSTALLER REMARKS �f— Q s / Nor c okT" votes n N� t t 71. APPROVED DATE LEGAL 7- 23' c --.--k 72-013 (Rev. 3/78) /) MI -l" I IG I L a L» I T'-ro ID F" F=l h• FR F113 E 2 t n1 - 12 - q 0 DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTIONAchal� 825 'L" STREET, ANCHORAGE, AK 99501 /C7�3U 264-4720 44EL L_ F4 NC> CSM-- I TE E;EWEF~ F•E:FZr-1 I T X10 PERMIT NO. C X300030 � pn� �. �`2 Q APPLICANT ,TAMES A. SWAMSON 2405 N TAHITI 344-8919 LOCATION HUFFMAN ROAD .� LEUAL LOT STYE 45950 SQUARE FEET TYPE OF SOIL ABSORPTION SYSTEM IS: TRENCH MAXIMUM NUMBER OF BEDROOMS 4 SOIL RATING CSO FT/BR)= 1w THE REQUIRED SIZE OF THE SOIL ABSORPTION SYSTEM IS: A7v OEF•TH- :..�2 L_EN0"r H- :30 L f;ZF91 E:L_ E>EF'TH-- = :S THE LENGTH DIMENSION IS THE LENGTH CIN FEET) OF THE TRENCH OR DRAINFIELD. THE DEPTH OF A TRENCH OR PIT IS THE DISTANCE BETWEEN THE SURFACE OF THE GROUND AND THE BOTTOM OF THE EXCAVATION CIN FEET). THERE IS NO SET WIDTH FOR TRENCHES. THE GRAVEL DEPTH IS THE MINIMUM DEPTH OF GRAVEL BETWEEN THE OUTFALL PIPE AND THE BOTTOM OF THE EXCAVATION CIN FEET). F;ZEQUf I F;ZEL� 4--EF'T I lG TFIt' K � I 2!E= �L;2" 0 PERMIT APPLICANT HAS THE RESPONSIBILITY TO INFORM THIS DEPARTMENT DURING THE INSTALLATION INSPECTIONS OF ANY WELLS ADJACENT TO THIS PROPERTY AND THE NUMBER OF RESIDENCES THAT THE WELL WILL SERVE. .._.,.-._._. TW0 <;2> 1NSF'EE3T I aMS HSE MEQU I ME ry.-- BACKFILLING OF ANY SYSTEM WITHOUT FINAL INSPECTION AND APPROVAL BY THIS DEPARTMENT WILL BE SUBJECT TO PROSECUTION. MINIMUM DISTANCE BETWEEN A WELL AND ANY ON-SITE SEWAGE DISPOSAL SYSTEM IS 100 FEET FOR A PRIVATE WELL OR 150 TO 200 FEET FROM A PUBLIC WELL DEPENDING UPON THE TYPE OF PUBLIC WELL. WELL LOGS ARE REQUIRED AND MUST BE RETURNED TO THE DEPARTMENT WITHIN 30 DAYS OF THE WELL COMPLETION. OTHER REQUIREMENTS MAY APPLY. SPECIFICATIONS AND CONSTRUCTION DIAGRAMS ARE AVAILABLE TO INSURE PROPER INSTALLATION. F'E MM I T EXF' I ME.'= E>ECEM0l-=M a �L:9Elo I CERTIFY THAT 1: I AM FAMILIAR WITH THE REQUIREMENTS FOR ON-SITE SEWERS AND WELLS AS SET FORTH BY THE MUNICIPALITY OF ANCHORAGE. 2: I WILL INSTALL THE SYSTEM IN ACCORDANCE WITH THE CODES. 3: I UNDERSTAND THAT THE ON --SITE SEWER SYSTEM MAY REQUIRE ENLARGEMENT IF THE RESIDENCE 1$'REMODELED�TO P4CLUDE MORE THAN 4 BEDROOMS. SIGNED: ICANT JAMES A. SWAMSON I r -4 V4 0 1 �. • Road bow /7N.14 rNb ; i • — r - - - — — r r r -*Too*- r r r r r r -- r rr r 00 laww0.1 + V M•• 1. O �0L , -.• L u &47). ID N j �t r.r rr. iMN—r ww 8 a7r r•rwr•t•r J '�—w r- ww ww wr w. -r rr w.:•.• -- Aw ,•-. .. ..r1 w+►+s 44 40 1p • waw �.•w .;. /'. .. - s+a 0t wpr a i•ra sTo �! iter• l.r.st l�e.w ... .. Avenue) : Avenue- 1Tt.H e•s... a 7•. 1b.K I�aaO •10 to . Uo. ee Ofa.at A iV wl 0 n Z A �I i� 2 B o Z C ;i 3 • - x11;. W VI �O D WI 8 - `-� a UJ + 44 O Z f M pa.• WiM y•/M •. .. 2w 01 Tls 17061 lyses = Avenue •td• total* cowl. i i 1 �. Test Hole #1 Table A WO #A18696 Logged By: T.L. Barber Date: 10--31-78 Depth in Feet From To Soil Description 0.0' - 0.5' Brown moss and peat (Pt), damp, soft. 0.5' - 17.0' F-4, brown Silt (ML), damp to wet, stiff, - NP to Pl-, traces gravel at 5.5' and 151. 17.0' - 20.0' F-1 to F-3, brown very Silty Sandy Gravel (GM), damp to wet, very dense, sharp and subrounded particles to'3/4". Bottom of Test Hole: Frost Lane: Free Water Level: Sam le 1 2 3 4 5 Depth 2.5' 5.0' 10.0' 15.0' 20.0' 20.0' None Observed None Observed Type of Sample G G G G G Unified ML ML ML ML GM to ML Remarks: 1. Type of Sample, G=Grab, SP = Standard Penetration, U = Undisturbed. t;.. 2. Dry Strength, N=None, L=Low, M=Medium, H=High. 3. Group refers to similar material, this study only. 4. General Information, see Sheet 1. 5. Ftrost and Textural Classification, see Sheet 2. 6. Unified Classification, see Sheet'3. r 4 WATER WILL LOG FOSS DRILLING ASSOCIATED 909 CHUGACH DR. #37 ANCHORAGE, ALASKA 99503 WELL OWNER James Swanson USE OF WELL Domestic WELL LOCATION Lot 2 Block 2B Drake Subdivision SIZE OF CASING 6" DEPTH OF HOLE 47 FT. CASED TO 47 FT. STATIC WATER LEVEL 20 FT. REMARKS G. P. M. 9 WITH 25 FT, OF DRAWDOWN, DATE COMPLETED 3/19/80 PUMP TO BE SET AT 46' 0 to 10 10 to 20 20 to t...+4 int ,to 47 to to to to to _,__to to to t0 t0 to to to to to - Alluvium: brown color and soft Alluvium: grey color, medium hardness Till: grey color and hard Sand'and Gravel: grey color with water MUNICIPALITY OF ANCHORAGE ENVIRONiv?E.di,4.L _CTION LAW 1 1900 C4- Y(T 2- A,4A-04 el�— 4"l au -1� otp Azr �m', Alspach - Plan:i1Vit; ii z ,Iwfi,arm�_lwtal Ennin-02rin" Nio. S-4723- Sub —Sur"ItIC-1, In s C I qw?.J n-, I of '0, Cin Lot 23 Ellk 2'. �-,-,aimrtpnemnt ha-� rMeimd S'oile, Tnrl; 'CA"O! nticl v;o have to t�L agqri�e with. the 'ngim!er 'Oat thtn Pen `;R S IC f or I) i nin pcn e d room "I iis, rat , . pm Pp. rc Tai's':. s n a ve s " j 'pair lun- to the Soils ratinf IX, t 1 1 1 - - ­ n , id I M t o W � Lidi� C s hepar 0 IS ; s q, . ft. per bedroom. 0 be �rmcm ratinti, if I IOU a 5 Id go so far as 'to recov,v2 n d ,-'.IOU size so pormitu.. Gy all mri.auris, !�t V -&-s nov" the tfin,, oMild conC, tructfion, so as f instally tion of septic tank,t uh, I � - -11-o have an Twiector out at that !, --- if. Lynn nviontnental Env fincnInq V I! �9 9 5: ".3 5 MUNICIPALITY OF ANCHORAGE o ti Development Services Department a Phone: 907-343-7904 On -Site Water & Wastewater Section Fax: 907-343-7997 Certificate of On -Site Systems Approval Parcel I.D. 017-461-29 Legal description DRAKE BILK 2 LT 213 Site address 3150 HUFFMAN RD Expiration Date: 11/24/23 Current property owner(s) MCGOVERN THEODORE J &JENNIFER J X The On-site system(s) is/are approved for 4 bedrooms Conditional approval for Comments or advisories: bedrooms, with the following stipulations: By: Original Certificate Date: S Z5 Z This Certificate of On -Site Systems Approval (COSA) is intended to demonstrate the subject system(s) is/are in substantial compliance with municipal code. The Municipality of Anchorage, Development Services Department (DSD) issues COSAs based upon representations provided by an independent professional engineer. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. ATTACHMENTS: COSA Checklist X Well Flow Advisory Absorption Field Advisory Nitrate Advisory Tank Age Advisory Arsenic Advisory Other COSA ApprovMjune 2022 MUNICIPALITY OF ANCHORAGE o �i ,� Development Services Department Phone: 907-343-7904 On -Site Water & Wastewater Section Fax: 907-343-7997 Certificate of On -Site Systems Approval Application 1. GENERAL INFORMATION Parcel I.D. 017-461-29 Complete legal description Drake Block 2 Lot 2B Location (site address) 3150 Huffman Road, Anchorage, AK 99516 Current property owners) Ted & Jennifer McGovern Day phone (907) 632-8747 2. ON-SITE SYSTEMS SIZED FOR 4 BEDROOMS 3. TYPE OF WATER SUPPLY: ❑■ Private Well ❑ Private Well serving 2 dwelling units ❑ Private Well serving 3+ dwelling units ❑ Community Well or Public ❑ Water Storage 4. TYPE OF WASTEWATER DISPOSAL: K Private Septic ❑ Private Septic serving 2 dwelling units ❑ Holding Tank ❑ Community Septic or Public Sewer 5. SEPTIC TANK: ❑ Steel ❑■ Plastic ❑ Concrete ❑ Fiberglass Age 10 - See advisory if steel older than 20 years 6. ABSORPTION FIELD: ❑■ AWWTS ❑ Bed X Deep Trench ❑ Wide Trench ❑ Seepage Pit Waiver request for: Expedited review requested: ❑■ Distance: By applying for this entitlement, this property is subject to inspection by municipal On-site staff to verify the accuracy of the information provided. COSA Fee $ f�w Waiver Fee $ Date of Payment COSA# Date of Payment Waiver # COSA Application—June 2022 Drake Block 2 Lot 2B 017-461-29 5.2 3/19/80 47 N/A 47 4.70 18 6/27/23 Forge Engineering 4.9 6/27/23 8/17/23 2.5 10 New Installation Benjamin Schiller, P.E.8/21/23 (907) 522-7773 MUNITCIPt'VLITY OF ANCHORAGE ADVANCED WASTEWATER TREATIMENT SYSTEM MAINTENANCE AND REPATR AGREEMENT THIS MAINTENANCE AND REPAIR AGREEMENT, herein the "AGREEMENT" made and entered into as of this _14Lh Day of June of 20.23 , by and between Richard A. Cooper , herein the "OWNER." and the Municipality of Anchorage, herein the ",MUNICIPALITY", in accordance with Anchorage Municipal Code (AMC) 15.65.365. In consideration of the mutual covenants contained herein, the parties to this Agreement agree as follows: 1. Advanced Wastewater Treatment Svstems. ne Municipality grants permission to the Owner to utilize and operate an Advanced Wastewater Treatment System (AW'Wrs), described as Advantex located at (legal description) im Drake 8Lock 2 Lo-- 28 2. Maintenance, Repairs and Alterations. (Owner is required to read, understand and initial each section) Throughout the term of this Ag -regiment, the Owner shall enter into a service agreement with an AWWTS service and maintenance provider approved by the Municipality or the manufacturer's representative. The AWWTS shall be maintained in a satisfactory condition capable of performing as designed and producing treated septic effluent in accordance with the equipment's approval for operation in the Municipality. 1 le-- It shall be the responsibility of the Owner during the term of this Agreement to pay for all repair(s), maintenance, adjustment(s), replacement costs, and inspection costs. This includes an annual maintenance fee (typically $400 to S600). Owner agrees that only maintenance and repair personnel approved by the Municipality or the manufacturer's representative will inspect and make any necessary maintenance, repairs or permitted alterations to the system. ONvner acknowledges that regular maintenance of an AWWTS reduces the potential failure of the system, which could include sewage backup and costly repairs or drainficid replacement. (rev. 05118/2018) Pagel of3 Owner acknowledges that the Municipality may request records of maintenance and repairs from the manufacturer's representative or maintenance provider, Y'{ , Owner acknowledges that the fine for failing to maintain and repair an AWWTS maybe assessed in accordance with AMC 14.60.030. ONvneragrces to grant the Municipality reasonable access to test and inspect the ANNINN'TS. The Municipality will give at least 24-hour notice. Owner agrees that any sale or transfer of title of the property will not occur without a new Certificate of On -Site Systems Approval. Owner agrees that the AWWTS installation and maintenance requirements as provided by the ANVWTS vendor/installer and approved by the Municipality are the governing guidelines for the construction, maintenance and repair of the Owner's AWWTS. Owner agrees to maintain remote monitoring of the AWIArl'S as required by the AWWTS approval. 3. Term. The term of this Agreement shall begin on the date of approval by the Municipality to operate the installed system, or upon transfer of title, and shall continue while the AWWTS is operational or until title is transferred. 4. Nonwitiver. The failure of the Municipality at any time to enforce a provision of this Agreement shall in no way constitute a waiver of the provisions, nor in any way affect the validity of the Agreement, or any part hereof, or the fight of the Municipality thereafter to enforce every provision hereof. 5. Amendment. This Agreement shall only be amended by authorized representatives of the Owner and Municipality, Any attempt to amend this agreement by either an unauthorized representative or unauthorized means shall be void. 6. Jurisdiction: Choice of Law. Any civil action arising from this Agreement shall be brought in the Superior Court for the Third Judicial District of the State of Alaska at Anchorage. The laws of the State of Alaska shall govern the rights and obligations of the parties under this Agreement. 7. Severabltity Any provisions of this Agreement decreed invalid by a court of competent jurisdiction shall not invalidate the remaining provisions of the Agreement. (rev. 05/18/2018) Page 2 of 3 OWNER• BY (signature) Date: - %_ / / % 2- (print name) STATE OF ALASKA ) S5. THTRD JUDICIAL DISTRICT 1 The foregoi-ny� instrument w:• acknowledged before me this t-57 day of VYVC- /� (l I f � 1• ✓ �� �' iL GEORGINA HENDERSON NOTARY UBLIC FOR ALAS Notary Public My Commission expires: L' , 2 State of Alaska My Commission Expires Apr 4, 2027 MUNICIPALITY: By: (signature) Date: (print name) Title: (rev. 05/18/2018) Page 3 of 3 Jun -12-2025 04:10 PM At 9075686770 44'63 .� on monew Monson ■ tspoil on ■ow N Irommu■ It on ■ I Its wlrr ���■��� ■�■■� a so *lvarfrWe Field Maidenancei Re poi Annual Inspection P 5/ 9 news ■ ■ ■ titi b An�harageTank 07-272-3543 Property Qweorlrrh6ki6g a artm i OperAlo _, Pr Theodore. & Jennifer Mc worn i"r CLIInt 7 Current A+ HirI,e Previous Services tech Sllo Addraas I i Pr I 4aninat Phono 3150 E. Huffman Road, Anchorage AK 99596 Previous 1 Pump 907) 632-8746 Ax $ue ID # connly ID a pod FM aA1L N I! f�nte of 6a911npaotlon AX -982386I 17176 L -1—i RTU1278I 06/12/2023 Rgtrl�g� f]$rM info Bally Recht ratio Timer settings: Perform Field SamplinglObservations NTU (15 x NTUS) pH ((-8) DO (2-6) Odor of S'Im le Typ{c91 Musty [ Earthy,,. Moldy Non-tYPI081 F1 Sulf(de r _.l Cabbage F-1 Decay Oily film in PVU [I Yos L No Foam in titin 12 YQa [,NQ Check Control Panel Recira limps Discharge Amps Audible and visual alarms F] Olt Dial tone (telernetry only) 0 Yes Cl No inspeeWClean Pump System In poet Clean Riser/Lid ..................... Spline fox .................... Float Cords . ..... ...... . . . Float$ ........................ Dlotube Filter. . ..............` HlQtube Pump Vault ............ Recirculating Splitter Valve...... , mebsu1 511+'ef7 Slud e I $cU111 tsticom artm i (Nrre _, Pr I i"r CLIInt 7 Current ❑ Ex Previous 2nd Cornpartm Syn I Curqnt Pr I us Previous Box Float Dj$cn rge t e Other Sy Iry clean CI aned ile sheets? 1`1 R lace otheY ''mil? Parts ed: 711arranty. B m Billable I# em Number f? for P-01 - \f2v- signature �- I A f1u h valves c tldati ns no fur her adon Fax completed f rml 1-800- 8+4-7e I apart Clean Giapereal Latnr*Iu/0dfiran N I . I Replaced UV Remo? selectlnn) Lids bolted on 0 Controll panel reactivated (�1 Tank ndads pumping ❑ Other7 i,....,.._ .... —7 - Inspect clean Pug !nt Later0s/Orlfices U I:x I Five Pool 0§11oln ] ❑ Ex a sive Intako,Vent Syn Inspect Glean Floats; Pump clean CI aned ile sheets? 1`1 R lace otheY ''mil? Parts ed: 711arranty. B m Billable I# em Number f? for P-01 - \f2v- signature �- I A f1u h valves c tldati ns no fur her adon Fax completed f rml 1-800- 8+4-7e I apart Clean Giapereal Latnr*Iu/0dfiran N I . I Replaced UV Remo? selectlnn) Lids bolted on 0 Controll panel reactivated (�1 Tank ndads pumping ❑ Other7 i,....,.._ .... —7 - 484 343 Eggs on ■■ ■ moons Nunn ■ on IIIII� ■ ■ ■ NONE ■ ■ ■ on ■ ■E■ ■ ■■■ ■■N■ on ■ ■ [A:�dvanTex® Field Maintenance Report Unscheduled on ■■.■11■ s AnchorageTank 907-272-3543 Property Owner/Tracking # _ ) operator Theodore & Jennifer McGovern Pump Operational?Yes F1 No A+ Home Services Tech Site Address Corrtact Phone 3150 E. Huffman Road, Anchorage AK 99516 Discharge..... ❑ Tripped ® On (907) 632-8746 AX Sit* ID x County ID H Pod f RTU #AUL # Date of last Inspection 132386 417176 RTU127803 06/26/2023 Dispatcher Comments Date: 07/14/2023 Time: 12:00 AM COSA follow-up. Annual inspection says tank was empty. Please check present condition of the tank water level. Notification of site condition ❑ Made by VeriComm® Monitoring System ❑ Made by Homeowner ❑ Other Site condition at time of call ❑ Alarm [_l Tank Overflow ❑ Odor ❑ Sewage Backup ❑ Other Field Sampling/Observations ❑ Necessary ❑ Not necessary NTU (15 s NTUs) pH (6-9) DO (2-6) Sit �.D Odor of Sample. Typical (] Musty ❑ Earthy ❑ Moldy Non -typical ❑ Sulfide ❑ Cabbage ❑ Decay Conditions at site Alarm On ❑ Yes ❑x,No (If yes, alarm type _ ) Tank Liquid Level �QNorrnal ❑ High ❑ Low Pump Operational?Yes F1 No [ On ❑ Off KFIashing Circuit Breakers Recirc........ ❑ Tripped ® On ❑ Off Discharge..... ❑ Tripped ® On ❑ Off Controls...... ❑ Tripped KOn ❑ Off VCOM° ATRTU Board: (if applicable) Document the panel status by shading the appropriate inputs and outputs as indicated by the yellow and red LEDs. Inputs Travel Time Outputs 10 OO Power (Green LED) [ On ❑ Off KFIashing Cause of Malfunction: ❑ Mechanical ❑ Process -Related Services Rendered: 1' 04 '� h,V' ^ �h \ ,(-K\ th L.Ak. 16'\ Jr.. �\' w t, Parts Used: W = Warranty, B = Billable (✓ appropriate selection) Item Number Notes/Final Recommendations: System performing; no further action needed ❑ Additional service needed Final/Safety Inspection: Lids bolted on? ..Yes ❑ No (If damaged, comment Control Panel reactivated? Yes ❑ No Circuit Breakers: Recirc: &jOn ❑ Off Discharge: C� On ❑ Off Controls. Xj On ❑ Off Time at Site Travel Time Total Time Signature 4/ Date 1 -- Time Fax completed form to 1-866-384-7404 MUNICIPALITY OF ANCHORAGE Development Services Department Phone: 907-343-7904 On -Site Water & Wastewater Section Fax: 907-343-7997 Lift Station/Pump Vault Maintenance Log Street Address�5 i, •� ��� R�` Septic Tank: -Sludge level -_inches -Pumping: required yes o -Pumping completedey s no Lift station: -Pump basket cleaned 'e no -Effluent filter cleaned�sy� no -Control floats cleaned es no -Proper float settings confirmed a22 no -Operation satisfactory es no Alarm System: -Dedicated electrical alarm cir t no -Audible and visual alarm inside dwelling es no -Alarm system operatio satisfact not satisfacto i Manhole Riser -Ground water intrusion at riser to tank connection yes Qno -Ground water intrusion around pipe penetrations es na, -Weep hole functional a no -Manhole lid: Functional no Insulateda no Properly Secured a no Other -All manufacturer required inspections and maintenance completed es` no Comments: Qualified Maintenance Provider: Technician Date of maintenance ��`13 Company A+ __ Signature Z Date? / i. 1 � I 1114Gk $4i • '� CeM� I nicipality of Anchorage _� a 6 U A + A !mw �;, `�� •.�' On -Site Water and Wastewater Program 0 (907)343-7904 , 9 s,{, 9 T I Certificate of On -Site Systems Approval C�✓ Parcel I.D. 017-461-29 Expiration Date: 1. GENERAL INFORMATION Complete legal description Drake Subdivision, Block 2, Lot 2-B Location (site address) 3150 Huffman Rd. Current Property owner(s) Joyce Swanson Mailing address 3150 Huffman Rd. Real Estate Agent 2. TYPE OF DWELLING: Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 4 Day phone Day phone 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Individual Well Il Individual (] Individual Water Storage ❑ Holding Tank ❑ Community Class Well ❑ Community ❑ Public Water S`Jr stem P� � Public Sewer P,i Waiver/Variance request for: �„^.., Received by,.�' Date.�A°''�' i COSA to be released to the engineer, unless otherwise requested by the engineer. COSA Fee $ b 7 Y W �2 Waiver Fee $ Date of Payment io/ Bll3 Date of Payment Receipt Number Receipt Number COSA # DSC! 31503 Waiver # 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm Pannone Engineering Services LLC Address P.O. Box 100217, Anchorage Ak. 99510 Engineer's Printed Name Steven R Pannone 6. DSD SIGNATURE System #1 Approved for bedrooms System #2 Approved for _ bedrooms Disapproved Phone (907) 272-8218 Date 10/7/13 Conditional approval for bedrooms, with the following stipulations: By:/e raOriginal Certificate Date:%/ 3 The nic lily' C orage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. ATTACHMENTS: COSA Checklist X Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other COSAbluesheet f L, c If more than 1 septic system is on the lot: COSA Checklist # of _ Structure served by this syst— em Certificate of On -Site Systems Approval Checklist Legal Description: Drake Subdivision, Block 2, Lot 2-B A. WELL DATA Well type Private If A, B, or C provide PWSID # Date completed 3/19/80 Sanitary seal (Y/N) Y Total depth 47 ft. Cased to 47 ft. FROM WELL LOG Date of test 3/19/80 Static water level 20 Well production Q ft. g.p.m. Parcel ID: 017-461-29 Well Log (YIN) Y Wires properly protected (Y/N) Y Casing height (above ground) 24 in. AT INSPECTION 10/4/13 13 6.2 ft. g.p.m. WATER SAMPLE RESULTS: /a/y/(3 Coliform%� Ionies/100mL Nitrate q•`%u' mg/L r Arsenic A) J�> ug/L Date of sample: I < / f I Collected by: B. SEPTIC/HOLDING TANK DATA Tank Type/Material S.T.E.P/Plastic Tank size 1,500 gal. Number of Compartments 2 Foundation cleanout (Y/N) Date of pumping New Y Depression over tank (Y/N) N Pumper Date installed 8/14/13 Cleanouts (Y/N) Y High water alarm (YIN) Y C. ABSORPTION FIELD DATA Date installed 8/14/13 Soil rating (g.p.d./ft2 or ft2/bdrm) 4 GPD/SF System type Shallow Trench Length 42 ft. Width 5 ft. Gravel below pipe 0.58 ft. Total depth 3 ft. Eff. absorption area 210 ft Monitoring tube Y Depression over field N Date of adequacy test New Results (Pass/Fail) New For 4 bedrooms Fluid depth in absorption field before test New in. Water added New gal. New depth New in. Elapsed Time: New min. Final fluid depth New in. Absorption rate , 600+ g.p.d. Any rejuvenation treatment (past 12 mo.) (YIN & type) No If yes, give date D. LIFT STATION Date installed 8/14/13 "Pump on" level at 42 in. Datum Bottom of Tank E. SEPARATION DISTANCES WELL ON LOT TO: Size in gallons 500 "Pump off level at 40 in. Cycles tested New Septic tank/lift station on lot 100+ Absorption field on lot 100+ Public sewer main 75+ Sewer /septic service line 25+ Manhole/Access (Y/N) Y High water alarm level at 43 Meets alarm & circuit requirements? Yes On adjacent lots 100+ On adjacent lots 100+ Public sewer manhole/cleanout 100+ Holding tank 100+ Animal containment areas 100+ Manure/animal excrete storage areas 100+ SEPTIC/HOLDING TANK ON LOT TO: Building foundation 5+ Property line 5+ Absorption Feld 5+ Water main 10+ Water service line 10+ Surface water 100+ Wells on adjacent lots 100+ ABSORPTION FIELD ON LOT TO: Property line 10+ Building foundation 10+ Water Service line 10+ Surface water 100+ Curtain drain 50+ Wells on adjacent lots 100+ F. COMMENTS G. ENGINEER'S CERTIFICATION I certify that 1 have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. Engineer's Printed Name Steven R. Pannone Date 10/7/13 COSA brown sheet 10-10-12.doc Water main 10+ Driveway, packing/vehicle storage 10+ in. 5." LEGAL DESCRIPTION o ck o;.ke_ STREET LOCAT 6. TYPE OF RESIDENCE NUMBER=OF,BEDROOMS [A ---SINGLE FAMILY E] One [B�Four ❑' Other CI Two ❑ Five ❑ MULTIPLE FAMILY E3 Three ❑ Six 7. WATER- SUUP LY :INDIVIDUAL*_ * ATTACH -WELL -LOG. A well lag is required for all wells drilled ❑ COMMUNITY since June 1975. For wells drilled prior to that date, give well ❑ PUBLIC UTILITY depth (attach log if available.) ` 8.- SEWAGE DISPOSAL SYSTEM - 1�r'INDIVIDUAL/ON-SITE** YEAR ON-SITE SYSTEM WAS INSTALLED. ❑ PUBLIC UTILITY NOTE: THE -INSPECTION FEE MUST ACCOMPANY EACH REQUEST BEFORE PROCESSING CAN BE INITIATED. } 72-010 (Rev. 6/79)/,�h THIS SIDE FOR OFFICIAL USE ONLY 1. TYPE OF RESIDENCE ❑ SINGLE FAMILY ❑ MULTIPLE FAMILY _ NUMBER OF BEDROOMS ❑ ONE ❑ THREE ❑ FIVE ❑ OTHER ❑ TWO ❑ FOUR ❑ SIX 2. WATER SUPPLY ❑ INDIVIDUAL ❑ COMMUNITY ❑ PUBLIC UTILITY Connection Verified PERMIT NUMBER DEPTH OF WELL DATE DRILLED LOG RECEIVED 3. SEWAGE. DIS1'OSALSYSTEM ❑ INDIVIDUAL/ON`-SITE ❑PUBLIC UTILITY�� Connection Verified PERMIT NUMBER DATE INSTALLED INSTALLER E] Septic Tank or ❑ Holding Tank Size: / If Tank is homemade give dimensions: SOILS RATING TYPE OF TANK - MANUFACTURER TOTAL- ABSORPTION AREA MATERIAL 4. DISTANCES WELL TO; Septic Holding Tank Absorptio*Area Sewer Line Nearest Lot Line Absorption Area to nearest Lot Line 5. COMMENTS R51 -'APPROVED FOR 4f BEDROOMS El CONDITIONAL APPROVAL (letter must accompany certificate) ❑ DISAPPROVED - 1-12 DATE BY