Loading...
HomeMy WebLinkAboutALPINE TERRACE BLK 1 LT 7 Municipality of Anchorage On -Site Water and Wastewater Section • (907) 343-7904 Page of ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP231075 PID Number: 015-243-31 Dwelling: ® Single Family (SF) ❑ with ADU ❑ Duplex (D) ❑ Two Single Family Project: ❑ New ® Upgrade Name LOUIS & JANICE CAMPBELL ABSORPTION FIELD — EXISTING BED ❑ Deep Trench ❑ Wide Trench ❑ Bed ❑ Mound Site Address 11851 NEBESNA DRIVE, ANCHORAGE ❑ Other Phone Number of Bedrooms Soil Rating Total depth from original grade 4 GPD/SF Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade Ft. Gravel depth beneath pipe Ft. Subdivision Block Lot ALPINE TERRACE 1 7 Fill added above original grade Ft. Gravel length Ft. Township Range Section Gravel width Ft. Beds: Number of Lines Distance between lines Ft. SEPARATION DISTANCES To Septic Absorption Lift Station Holding Sewer Total absorption area Number of trenches Dist. between trenches From Tank Field Tank Line Ft2 Ft. Well 100'+ __ 25,+ TANK ® Septic ❑ S.T.E.P. ❑ Holding ❑ Other Manufacturer ANCHORAGE TANK Capacity 1500 Gal. Surface Water 100'+ __ Material EPDXY STEEL Number of compartments 2 Lot Line 10'+ -- NA Foundation 10'+ __ LIFT STATION Manufacturer Capacity Gal. Remarks Tank insulated, anchored & 2 MH risers, but gravity fed to existing field. Alarm location Electrical installed by Installer DENALI EXCAVATION PIPE MATERIAL House to tank 3034 drainfie d nk3034 Drainfield CO/MT 3034 Inspector FWCS BENCH MARK (Assumed elevation) 100 ft Inspeection 15' 6/13/23 2rd 6/14/23 Location and description 3'd 4 th TOP OF MH — 1ST RISER ON-SITE WATER AND WASTEWATER SECTION APPROVAL Conditional Approval: Date � • / %�F'•F�C.utis Huffman Septic Syste �CE128991 ,W Date 7/7/2023 •��6r FO ... � x pROFESSIONA 'ir -� Note: this approval does not include well permit requirements. \ROFESA kf uv VJ/VL! 10) PID:015-243-31 PERMIT:OSP231075 FIRST WATER CONSULTING ALPINE TERRACE BLOCK 1, LOT 7 MUNICIPALITY OF ANCHORAGE On -Site Water & Wastewater Program PO Box 196650 4700 Elmore Road Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997 hftp://www.muni.org/onsite On -Site Wastewater Disposal System Permit Permit Number: OSP231075 Work Type: SepticTank Upgrade Tax Code Number: 01524331000 Site Legal Address: ALPINE TERRACE BLK 1 LT 7 G:2740 Site Mailing Address: 11851 NEBESNA DR, Anchorage Owner: CAMPBELL LOUIS D & JANICE C Design Engineer: FIRST WATER CONSULTING This permit is for the construction of: Effective Date: Expiration Date Lot Size in Sq Ft Total Bedrooms: ni Department 5/1/2023 4/30/2024 51200 ❑ Disposal Field Q Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage All construction shall be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80) 3. The wastewater code requires inspections during the installation. The engineer shall notify the Development Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather shall be either: a. Opened and Closed on the same day, or b. Covered, sealed, and heated to prevent freezing Received By: I S 5� O �/ G Date: Issued By: (,�,� , �- Date: r -zo z 4 MUNICIPALITY L.ITY OF Development Services Department On -Site Water & Wastewater Section Parcel I.D. 015-243-31 ON-SITE SEPTICIWELL PERMIT APPLICATION Property owner(s) LOUIS & JANICE CAMPBELL Day phone Mailinq address 11851 NEBESNA DRIVE, ANCHORAGE, AK 99507 Site address 11851 NEBESNA DRIVE, ANCHORAGE, AK 99507 Legal description (Sub'd., Block & Lot) ALPINE TERRACE BLOCK 1, LOT 7 Legal description (Township, Range & Section) Lot Size 51,200 Sq. Ft. Number of Bedrooms 4 Phone: 907-343-7904 Fax: 907-343-7997 APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: (N all that apply) Absorption Field p ❑ Initial 0 Single Family (SF) X❑ (w/wo ADU) Septic Tank 21Upgrade ElDuplex (D) ElHolding Tank ElRenewal ElMultiple Dwellings ❑ Privy ❑ (SF and/or D) Private Well ❑ Water Storage ❑ THIS APPLICATION INCLUDES A WAIVER REQUEST FOR: Distance: I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes. .......... . (Signature of property owner or authorized agent) Permit/Rush Fees: 2 Z Date of Payment: !X Z_q�23 Receipt Number: 950L(Z Y5 Permit No. Waiver Fees: Date of Payment: Receipt Number: Waiver No. GADevelopment Services\Building Safety\On Site Water and Wastewater\Forms\Client Forms\Permit Application.doc 10' UTILITY EASEMENTS ��•- 5'x30' UTILITY �� EASEMENMENTS I. 49.70' Lot 8 SEPTIC Lot 6 S 89'50' Lot 7 49,809 S.F.(COMPUTED) 51.200 S.F.(M.O.A.) VA rjySHEDS II�JJ / � �S0 0 30.0' CIRCLE DRIVE � Q �Ov \-s, 44'58'00"W 25.00' R=25.00' PLOT PLAN AS BUILT —2L SCALE 1" = 60' GRID SW 2740 Project No. 23-135/A2 p y 11500 Daryl Avenue, Anchorage, Alaska 99515-3049 Lang & A S S O C i a t e S, inc. (907) 522-6476 Phone _"` kenOlangsurvey.com `�'►OF A``\�l Professional Land Survey ors jonothanOlangsurvey.com troviaOlangsurvey.com �r�P'�� q i�� I hereby certify that I have surveyed the following described property: ng.' LOT 7, BLOCK 1, ALPINE TERRACE SUBDIVISION (PLAT No. 64-63-1)*: 48TH *�� Anchorage Recording District, Alaska, and that the improvements situated thereon are within the property lines and do not encroach onto the property adjacent thereto, that R % no Improvements on the property lying adjacent thereto encroach on the surveyed • • • • • • • • • • • • • premises and that there are no roadways, transmission lines or other visible (tr KENNETH G. LANG QMo easements on said properly except as indicated hereon. F��. 0 202 rAW— Dated Dated this the 2ca Day of duh" "°i 1a at Anchorage, Alaska �11 ? � ESS O If is the responsibility of the owner to determine the existence of any easements, �\\k�keetw covenants, or restrictions which do not appear on the recorded subdivision plat. State of Alaska AECC963 13030 Sues Way, Anchorage, AK 99516 907-350-9566 / firstwaterAK@gmail.com ! !! April 24, 2023 Municipalities of Anchorage On-Site Water & Wastewater Program 4700 Elmore Road Anchorage, AK 99507 RE: SEPTIC TANK UPGRADE PERMIT LEGAL: ALPINE TERRACE BLOCK 1, LOT 7 The owner has requested that we obtain a septic permit to upgrade the existing aged steel septic tank on the above referenced lot. We propose to install an anchored 1500-gallon epoxy coated steel septic tank per the attached design to serve the existing 4-bedroom residence. Shallow groundwater was noted in the MOA on-site file and an anchored epoxy coated steel septic tank is required. The lot and area are served by private water as shown on the design. The design will not impact any of the neighboring properties. Please contact us if you have any questions. Sincerely, Curtis Huffman, P.E. Municipality of Anchorage On-site Water and Wastewater REVIEWED FOR CODE COMPLIANCE OSP231075, Curtis Townsend, 05/01/23 FIRST WATER CONSULTING ALPINE TERRACE BLOCK 1, LOT 7 DESIGN DETAILS: Municipality of Anchorage On-site Water and Wastewater REVIEWED FOR CODE COMPLIANCE OSP231075, Curtis Townsend, 05/01/23 i;i 10' UTILITY EASEMENTS 5'x30' UTILITY EASEMENTS N 00'02'00"W 49.70' Lot 8 SEPTIC Lot 6 Lot 7 49,809 S.F.(COMPUTED) 51,200 S.F.(M.O.A.) O I 03ESIDEN C 3 M C,,i \ X4.20 PPJ�� BO . 00 'z AS°q0, 00 O,Az` . NOTE: DUE TO SNOW & ICE COVER, SOME SURFACE LEVEL FEATURES ARE APPROXIMATE. 30.0' o � 0 0 SHEDS N O O — —rq CIRCLE DRIVE W \ 9.6' i -WELL ^ / Cc I q � ii O/ Ov 5 / `S 44'58'00"W 25.00' ,-L=39.27' R=25.00' PLOT PLAN ___ AS BUILT _X_ SCALE -11_= 60__ GRID _ SW 2740__ Project No. ____23=135fA1____ 11500 Daryl Avenue, Anchorage, Alaska 99515-3049 Lang & Associates, inc. (907) 522-6476 Phone \\ kenOlongsurvey.com �� \\kl Professional Land Surveyors jonathanolongsurvey.com E OF. Atq`il� travisOlangsurvey.com A.—W .. sL , I hereby certify that I have surveyed the following described property:/C-39 LOT 7, BLOCK 1, ALPINE TERRACE SUBDIVISION (PLAT No. 64-63-1)*; 49TH Anchorage Recording District, Alaska, and that the improvements situated thereon are •• 0, within the property lines and do not encroach onto the property adjacent thereto, that ;W40 ... . . • • • • • no Improvements on the property lying adjacent thereto encroach on the surveyed premises and that there are no roadways, transmission lines or other visible 90 9 • KENNETH G. LANG -,•o easements on said property except as indicated hereon. �+ cNo. 202 Dated this the --- Day Day of ___1 " _______, _---'__, at Anchorage, Alaska ,l �lFgF�PQ�2o�2�,,�Dsp�� 1` ROfESSIONP��P � It is the responsibility of the owner to determine the existence of any easements, covenants, or restrictions which do not appear on the recorded subdivision plat. State of Alaska AECC963 Municipality of Anchorage Page / of ~' DEPARTMENT OF HEALTH AND HUMAN SERVICES ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 · Anchorage, Alaska 99519-6650 · Telephone: 343-4744. On-Site Wastewater Disposal System and/or Well Inspection. Report Permit Number: ,.~ h2 ~ ~.O/~ ~ PID Number: ~/~ - ~ ~ - ~ / N,~,: Wastewater System: D New ~pgrade Address: ABSORPTION FIELD s oo ~ D Deep Trench D Shallow Trench ~Bed D Mound D Other LEGAL DESCRIPTION so. Rating: O, ~ GPD/Sq. Ft, Total /.Depth~'fr°m original grade: Lot: ~ Block: Subdivision: Depth to pipe bottom from original grade: Gravel Gep[h ~,ea~h pi~ )~' ]Range: ~W' ]Section: ~ FIll added above original grade: Gravel length: Township: ~-F F,. WELL: D New Gravel ~h: ~,~ / ~ Ft. ~ I ~ Ft. Classifi~tion (Private. A,B.C): ~h: Cased To: Totalabsorption area: Pipe material: Driller: ~ Date Drilled: Static Water Level: Installer: Date in~// Yield: ~pM IPump Set at: Ft. I~sing Height A~ve Ge°and:Ft. TANK ~ SEPARATION DISTANCES ~septic ~ Holding ~ S.T.E.P. From Tank Field Station Tank Sewer Lines ~ ~ ~ 4 ~ Material: Numar of Co~psr[mei~lS: Sudace W.~.r N/A LIFT STATION Lot i , ' s'ze 'n ga"°ns: I Manufacturer Foundation ~6' ~' N/~ ,,Pump on,, level at: ~" level at: Cu~ain ' P~I Drain ~/~ Pun El~trical Inspections pedormed by: Remarks: BENCH MARK Location and Description:  Assum~ Elevatipn~ Inspections performed by: ~l~~ Dates: ls~ =n, Department of Health and Human Services approval ,.vi.w., an, a,,rov., 72..013 (1/91) MOA 25 Permit No. ~"~"~ ~"~/~ ~ Page of Municipality of Anchorage DEPARTMENT OF HEALTH AND HUMAN SERVICES ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 · Anchorage, Alaska 99519-6650 · Telephone: 343-4744 On-Site Wastewater Disposal System and/or Well Inspection Report Legal Description: ~-~7:' /9 z:~'//,/-/'/ //-/,/~/,~,c' ~"~,rr',,c~5._ PID No.: 91.9' 196,8~ 30' 18' N 89°50~40' W LOT7 BLK1 NEW 1250 GAL, TANK; HOUSE WELL 100,00' ~ R-25,00' ELEVATIONS L=39,27 (NOT TO SCALE) ~ BOTTOM Dr S]O]N~ NV CORNER ~ ASSUMED ELrV = t00,OO' GRND ~ S.EN]] 94,9' GRND ~ N.END 93,7' ~ GRND. ,96.1' [ [ TEST HOL SCALE' 14=50, ~¥/[NG TIES A-C=35,7' A-D=41,7' A-E=45.8' A-F=50,5' A-G=54,0' A-H=84,5' A-1=80.8' B-C=2B,6' B-D=36,7'i B-E=41,6' B-F=48.7' B-G=51.P' B-H=69.6' B-I=64.4' B-J=66,5' ~ -- TEST HOLE · - MONITOR TUBE o - SEWER CLEANOUT + - WELLi .-EN(~iNI~Eq!s SEAL. ~-.'~ L~'~ '~,~: , ':-::' 72-013 A (Rev. 9/91) MOA 25 PAGE 1 OF 1 MUNICIPALITY OF ANCHORAGE ~ ~ DEPARTMENT OF HEALTH AND HUMAN SERVICES P.O. 196650. "L" STREET. ROOM 502 ANCHORAGE, ALASKA 99519-6650 ---- ON-SITE WASTEWATER DISPOSAL SYSTEM (UPGRADE) PERMIT PERMIT NUMBER:SW920169 DESIGN ENGINEER:EAGLE RIVER ENGINEERING SERVICES OWNER NAME:CAMPBELL LOUIS D & OWNER ADDRESS:il851 NEBESNA DR ANCHORAGE, AK. 99516 DATE ISSUED: 7/02/92 EXPIRATION DATE: 7/02/93 PARCEL ID:01524331 LEGAL DESCRIPTION: ALPINE TERRACE BLK 1 LT 7 LOT SIZE: 51200 (SQ. FT.) NUMBER OF BEDROOMS: 4 THIS PERMIT: 4 THIS PERMIT IS FOR THE CONTRUCTION OF: DISPOSAL FIELD /SEPTIC TANK SYSTEM ALL CONSTRUCTION MUST BE IN ACCORDANCE WITH: 1. THE ATTACHED APPROVED DESIGN. 2. ALL REQUIREMENTS SPECIFIED IN ANCHORAGE MUNICIPAL CODE CHAPTERS 15.55 AND 15.65 AND THE STATE OF ALASKA WASTEWATER DISPOSAL REGULATIONS (18AAC72) AND DRINKING WATER REGULATIONS (18AAC80). 3. THE FOLLOWING SPECIAL PROVISIONS. SPECIAL PROVISIONS: THE BED MUST BE INSTALLED IN ACCORDANCE WITH THE APPROVED ENGINEER'S DESIGN DATED 6/26/92. THE ORGANICS MUST BE EXCAVA TED TO A DEPTH OF APPROXIMATELY 1.5 FT. BELOW GROUND LEVEL. A MINIMUM OF 2 FEET OF SAND FILTER MUST THEN BE INSTALLED PRIOR TO PLACING THE SEPTIC ROCK. THE EXISTING SEPTIC TANK AND DRAINFIELD MUST BE PROPERLY ABANDONED. / DATE: DATE: Louis Butera, P.E. Registered Civil Engineer June 29, 1992 John Smith, P.E. Manager, On-Site Services Municipality of Anchorage P.O. Box 196650 Anchorage, AK 99519 Re: Lot 7, Block 1, Alpine Terrace Narrative Dear Mr. Smith: The proposed septic upgrade will have very limited impact on adjacent properties for the following reasons: 1. The area has large lots allowing sufficient room for septic sites. 2. Immediate neighboring septic systems are all +30' distance. 3. Reserve space is adequate, due to absorption capacity. 4. Drainage will not be altered, and is not a major consideration in our design. If you have any questions please call our office at 694-5195. Sincerely, Louis Butera, P.E. P.O. Box 773294 · Eagle River, Alaska 99577 · Telephone (907) 694-5195 · Fax (907) 694-3297 LEGAL: SPECIFICATIONS FOR ON-SITE SEPTIC SYSTEM LOT 7, BLOCK 1, ALPINE TERRACE Ae GENERAL 1. The well and septic plan are for a single family residence only. 2. The drawing and or site plan shall be a part of this specification. 3. All materials and workmanship shall meet the Anchorage Department of Health and State Department of Environmental Conservation requirements. 4. All soil tests are advisory to the design and are to be verified or modified in the field by the engineer. 5. All excavations and depths are advisory and are to be verified in the field by the contractor to meet Municipality of Anchorage, Department of Environmental Conservation requirements. 6. It is the responsibility of the owner to obtain all necessary permits or easements and to locate any adjacent multi-family wells. 7. The excavation is to be exactly in the area shown on the site plan, any deviation requires engineer approval. 8. It is always recommended that a surveyor locate the nearest lot line position and the location of any easements. BED 1. 2. 3. 4. 5. 6. 7. 8. The bed is to follow the natural land contour to maintain uniform total depth of the bed bottom. The bottom of the bed shall be level, plus or minus 1.5". The total depth of the bed gravel layer is not to exceed 4.3' below the top of monitor tube #1 at any point. The sewer line is to replace the existing sewer line that leads to the existing tank and pit. The bed gravel is to be covered with typar fabric material. Soil or combination of soil and extruded board insulation to a depth of 3' or equivalent is to be placed over the leachfield. The area over the bed is to be finish graded to prevent ponding of surface water runoff. The septic tank and leachfleld must not be closer than 100' to any existing private well, 150' to any Class "C" well, or 200 feet to any community well. RECOMMENDED LEACHFIELD DIMENSIONS: TOTAL DEPTH = 1.4' at test hole #2 GRAVEL DEPTH = 6" below pipe BED LENGTH = 48' BED WIDTH = 18' 7~:~: SOIL RATING = 0.7 GPD/ft2 BEDROOM CAPACITY = 4 SEPTIC TANK SIZE = 1,250 NOTE: Abandon both existing tank and pit to code. Overexcavate and place 2' sand filter layer below leach gravel. Twenty-four (24) hours notice required for all inspections. EAGLE RIVER ENGINEERING SERVICES P. O. Box 773294 EAGLE RIVER, ALASKA 99577 Phone 694-5195 JOB A'I pine SHEET NO. CALCULATED BY CHECKED BY SCALE Terrace, Lot 7, Blk 1 92-098 OF L.B. 06/26/92 DATE DATE CalCUlation for FOur BedroOm Single F~y DWelii.g: ~ B~ ~ ~ GPD Soil Rating = 0:7 Z + 10 0',~,~/~ 30' ND PRIVATE WELLS +100' 6 VACANT LOT 196,83 N 89d50'40' W LOT7 BLK1 ExEXIS NB SURFACE WATER CBURSE NO KNOWN CURTAIN DRAINS T.H,~2 ~ 48' NEW T,H,~I · g 18' ]XISTING TANK GAL, TANK HDUSE WELL lO0,O0' ,-.z ~ " PS,00' WITHI~ L=N 100' 30' / [] - TEST HOLE · - MONITOR TUBE o - SEWER CLEANOUT + - WELL :Xxll:~:l- PROPOSED LEACHFIELD EASEMENT SEPTIC SITE PLAN LEGAL: ALPINE TERRACE LOT 7 BLK. 1 OWNER' LOU CAMPBELL CONTRACTOR: N/A JOB # 92-0981 DATE' 06/24/92 SCALE 1" = 50' A EAGLE RIVER ENGINEERING SERVICES P.O. Box 773294 EAGLE RIVER, AK. 99577 (907) 694-5195 FAX: (907) 694-3297 Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST (ENGINEER'S SEAL) I~ERFORMED FOR: DATE PERFORMED: LEGAL DESCRIPTION: >~7~- 7 ,~/,'~'/ 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 2O Township, Range, Section: ~'/~ ~/ ~ 3' /.~ ~'~¢ ~' SLOPE SITE PLAN O' · D WAS ~ ENCO~ IF YE= - PER~ GROUND WATER :OUNTERED? 7 S L · AT WHAT /,'7 ~ / 0 P E W,ler After , /~ '-//9 ~ g? '7, ~. Date:. ~ Gross Net Depth to Net Reading Date Time Time Water Drop ~ ~//~ / '/ /~: ~,~ ,,r,--- z.~ / .3 ~ ~" J I' ll;l~ ~'-5~" ~ / ~/. PERCOLATION RATE TEST RUN BETWEEN (minutes/inch) PERC HOLE DIAMETER FT AND ~Y' FT PERFORMED BY: ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. 72-008 iRev. 4/85~ CERTIFY THAT THIS TEST WAS PERFORMED IN DATE: Municipality ol Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST (ENGINEER'S SEAL) PERFORMED FOR: /~P" ~'~'~"~,,~ ~ ~// DATE PERFORMED: LEGAL DESCRIPTION: ~-~'-;2 ¢~:::'/,,/-¢/ *~o,~ 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 2O Township, Range, Section: 7'/~ ,~ ~ 3 ~) x'~¢ .~' SLOPE SITE PLAN .-" 5.~ ENC~ IF Y~ DEP' R PER, GROUND WATER TERED? ;, AT WHAT 'H? dh to Water Alter b~ ~' Gross Net Depth to Net Reading Date Time Time Water Drop ~ ~, //; 5~ ~/-~" 7,~~ ~ '~ ~ " //;¢~ 3~ 30" 3.~' &" 3.~,~,, _- ~, ~ 3OLATION RATE __ {minutes/inch) PERC HOLE DIAMETER ( '''/ TEST RUN BETWEEN '~ FT AND z/' FT PERFORMED BY: ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. 72-008 (Rev. 4/85) CERTIFY THAT THIS TEST WAS PERFORMED IN GREf-'~R ANCHORAGE AREA BOP"UGH Department of Environmental Quality 3330 C Street Anchorage, Alaska 99503 INSPECTION REPORT ON-SITE SEWAGE DISPOSAL SYSTEM NAME //~/0X /~tV6'7l)~°z MAILING ADDRESS · OCAT,ON LEGAL PHONE SEPTIC TANK: DISTANCE FROM WELL/~~ MANUFACTURER ~/~ ~----~-' M AT E R I A L ~? ,/¥£/~' ~:~_ NUMBER OF COMPARTMENTS ~"~ INSIDE LENGTH INSIDE WIDTH LIQUID DEPTH LIQUID CAPACITY /.~.-)'C~ GALLONS. SEEPAGE PIT: t NUMBER OF PITS I DIAMETER __ OR WIDTH /,~, LINING MATERIAL AOf/~* (2 CRIB SIZE: DIAMETER BUILDING FOUNDATION 3C"~, NEAREST LOT LINE~C ADDITIONAL ABSORPTION ~//~ / LENGTH /~, DEPTH ~/~ "~3E PTH DISTANCE FROM: WELL/(~'~ ~ ~ TOTAL EFFECTIVE . ~:;7~ ABSORPTION AREA (WALL AREA) ~ ~/~ISQ. FT. WELL: 'tYpE P^~, //~ BUILDING FOUNDATION CESSPOOL APPROVED , OTHER SOU DISAPPROVED REMARKS SEEPAGE __ , SYSTEM DISTANCE FROM: DISTANCES: INSTALLED BY: LOT SLOPE: REMARKS: Form No. EQ-031 DIAGRAM OF SYSTEM APPROVED " ~., ZATER ANCHnRAGE ARE& BOROU . DEPARTMENT OF ENVIRONI!ENTAL QUALITY ., 3500 TUDOR ROAD ~)~~¼~%-~,~-----'~0--', ANCHORAGE, ALASKA 99502 Performed For ~3 ~i ~.S;[~¢ ~. Leeal Descrintion: Lot ¢ Block This Form Re~orts Soils Log ~ qepth Feet CASE # Date Performed ?Subdivision Percolation Test Soil Characteristics m m Was Ground Water Encountered? IF Yes, At what Depth?_ I.~/ Readin~ Date Grmss Time Net Time [ Denth to H20 I Net Dropl I Percolation Rate Minute Proposed Installation- SeeDaqe Pit Drain Field De~th of Inlet Denth To Bottom Of Pit Or Trench CnU~ENTS' Test Performed !By Pata Certified By: Date' GRE^'r R ^NCHOR^Gr A EA BOROUGH DEP^RTMENT OF EN¥1'RONHENT^L 3330 "C" Street ANCHORAGE, ALASKA 99503 Case # Performed For_ 1}} f II~ ~', i~ ~¢ ~ Dated Performed Legal Description: Lot ? Block_ ILl,Subdivision This Form Reports Soils Log_ ~ Percolation Test ,, - Soil Test Must Be Logged To 4' Below Proposed Seepage System - Soil Characteristics Depth Feet 2~ 3~ 4~ 5~ 6~ 7~ 8~ 9~ 10-- 11~ 13-- 14~ Was Ground Water Encountered? If Yes, At What Depth? ,,/F~ ~ Reading Date Gross Time Net Time Depth to H20 Net Drop Percolation Rate Minute Proposed Installation: Seepage Pit Drain Field Depth of Inlet Depth to Bottom of Pit or Trench COMMENTS: Test Performed BY. ~)~::::~'~-~- Date Certified BY: Date ' · GREATER ANCHORAGE AREA BOROUGH .- DEPARTMENT OF ENVIRONMENTAL QUALITY Case # 3330 "C" Street ANCHORAGE, ALASKA 99503 Performed For ~o_~z ~--~(~c~a~X Dated Performed (o/~77~ Legal Description: Lot ~f'~ Block -S~"/' Subdivision ~/~;.~_ ~r~/ This Form Reports Soils Log Percolation Test - Soil Test Must Be Logged To 4' Below Proposed Seepage System - Depth Feet 2~ 3~ 4~ 5~ 6-- 7-- Soil Characteristics m 9~ 10~ 11~ 12-- 13~ 14-- Was Ground Water Encountered? If Yes, At What Depth? Reading Date Gross Time I Net Time Depth to H20 Net Drop! I Percolation Rate Minus_ Proposed Installation: Seepage Pit Drain Field Depth of Inlet Depth to Bottom of Pit or Trench COMMENTS: / Test Performed BY /~_ ~$?'~_~/ Date Certified BY: Date: GREATER ANCHORAGE AREA BOROUGH Department of Environmental Quality 3330 "C" Street, Anchorage, Alaska 99503 274-4561 ~ Date Received July ~~ ~/.~/ Time of Inspection ~u~/.~_~/~j ~ a 0.~ Date of Inspection a/~ ! INDIVIDUAL SEWER & WATER FACILITIES FOR 7~ 1976 1:30 7-8-76 Conv, 1. Approval requested by: National Bank of Alaska Mailing Address: Post Office Box 600, 99510 Phone: 2. Property Owner: Robert Leidiq Phone: Mailing Address: Star Route A Box 394-J, 99507 (house is vacant) 3. Legal Description: Lot 7 Block 1 Alpine Terrace Subdivision 4. Location: Off of Hillside Drive 5. Type of facility to be inspected 6. Well Data: Individual A. Type C. Construction Single Family No. of bedrooms 4 7. Sewage Disposal System: A. Installed C. Septic Tank: D. Seepage Pit: E. Disposal Field: 8. Distances: On-site system 1. Size 1. Absorption Area Total length of lines B. Depth 200' D. Bacterial Analysis B. Installer 2. Manufacturer 2. Material , Sewer Lines A. Well to: Septic tank ?0 + , Absorption area /d Nearest lot line , Other contamination B. Foundation to septic tank , Absorption area C. Absorption area to nearest lot line EQ-034 (1/74) Page 1 of two pages ~ge 2 of two pages - Re'--st for Approval of Individual f er & Water Facilities L~gal Description Lot 7 Block 1 Alpine Terrace Subdivision Comments Approved ~. ~/~ Disapproved Date Approval Valid for one year from date signed Greater Anchorage Area Borough, Department of Environmental Quality DIAGRAM OF SYSTEM I certify that the information contained in this request for approval to be a true and accurate representation of the subject sewer and water facilities and these facilities are operating satisfactorily. Date SIGNED EQ-034 (1/74) MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION 2510 East Tudor Road, Anchorage, Alaska 99504 276-2221 REQUEST FOR APPROVAL OF INDIVIDUAL SEWER and WATER FACILITIES 1. Type of Inspection: CMRO 2. Property Owner:. J~~'e~¢ Mailing Address: -~'' ~'~ 3. Name of Buyer: r~--~"~ Mailing Address: ~'/~:~ VA FHA CONV ~ Day Phone: 4. Name of Lending Institution: Mailing Address:~~ / Phone: 5. Name of Realtor or Agent: '"~-~ ~' ~ ~~- Mailing Address: ,~)~,~ O / ~ ,~'~'~- Phone: Legal Description: ~'~ O '/~' /~. ~--- ~/, .~.~g ~ %e~_.~j~_ ~_=_ Location:~~, 7. Type of Facility to be Inspected' No. Bdrms. Water Supply Type of Supply: Public Utility Individual If Individual, number of dwellings presently served ~ '~' If Individual, depth of well. Sewage Disposal System Type of System: Public Utility If Individual, date of installation ~,~V ~/~ ~-~ A.J Individual (on-site) 72-OO3(3/76) YENNEY'S CONSTRUCTION CO. 9100 Lake Otis Pkwy. ANCHORAGE, ALASKA 99507 Phone 349-2242 Page No. Pages PROPOSAL SUBMITTED TO STREET ARCHITECT ,~ [ DATE OF PLANS and eshm We hereby submit specifications ' : PHONE I DATE JOB NAME IJOB PHONE I[ ~le ~Iropose hereby to fur~sh rr~ri~labor -- complete in accordance with above specifications, for the sum of: ~ ~ .' ~ollars ($ )' Pay~nt to b~de as f~llo~ : All material is guaranteed to be as specified. All work to be completed in a workmanlike manner according to standard practices. Any alteration or deviation from above specifica- tions involving extra costs will be executed only upon written orders, and will become an extra charge over and above the estimate. All agreements contingent upon strikes, accidents or delays beyond our control. Owner to carry fire, tornado and other necessary insurance. Our workers are fully covered by Workmen's Compensation Insurance. Authorized Signature Note: This proposal may be withdrawn by us if not accepted within days. Arreptanre of lroposal--The above prices, specifications and conditions are satisfactory and are hereby accepted. You are authorized to do the work as specified. Payment will be made as outlined above. Date of Acceptance: Signature Signature FORM 118-3 COPYRIGHT 1960 ' Avaitable from t't4D~} Inc.. Townsend, Mass. 01469 Development Services Department t Phone: 907-343-7904 On-Site Water & Wastewater Section Fax: 907-343-7997 Certificate of On -Site Systems Approval Parcel 1. D. 015-243-31-000 Expiration Date: Legal description ALPINE TERRACE BLK 1 LT 7 Site address 11851 NEBESNA DR Anchorage AK 99507 Current property owner(s) ESTATE OF CAMPBELL LOUIS D & J 11/1/2023 X The On-site system(s) is/are approved for 4 bedrooms Conditional approval for bedrooms, with the following stipulations: Comments or advisories: By, Original Certificate Date: 8/1/2023 This Certificate of On -Site Systems Approval (COSA) is intended to demonstrate the subject system(s) is/are in substantial compliance with municipal code. The Municipality of Anchorage, Development Services Department (DSD) issues COSAs based upon representations provided by an independent professional engineer. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. ATTACHMENTS: COSA Checklist X Well Flow Advisory Absorption Field Advisory Nitrate Advisory X Tank Age Advisory Arsenic Advisory Other COSA Approval—June 2022 MUNICIPALITY OF ANCHORAGE Development Services Department Phone: 907-343-7904 On -Site Water & Wastewater Section Fax: 907-343-7997 Certificate of On -Site Systems Approval Application 1. GENERAL INFORMATION Parcel I.D. 015-243-31 Complete legal description ALPINE TERRACE BLOCK 1, LOT 7 Location (site address) 11851 NEBESNA DRIVE, ANCHORAGE, AK 99507 Current property owner(s) LOUIS & JANICE CAMPBELL Day phone 2. ON-SITE SYSTEMS SIZED FOR 4 BEDROOMS 3. TYPE OF WATER SUPPLY: ® Private Well ❑ Private Well serving 2 dwelling units ❑ Private Well serving 3+ dwelling units ❑ Community Well or Public ❑ Water Storage 4. TYPE OF WASTEWATER DISPOSAL: ® Private Septic ❑ Private Septic serving 2 dwelling units ❑ Holding Tank ❑ Community Septic or Public Sewer 5. SEPTIC TANK: ® Steel ❑ Plastic ❑ Concrete ❑ Fiberglass Age NEW - See advisory if steel older than 20 years. 6. ABSORPTION FIELD: ❑ AWWTS ® Bed ❑ Deep Trench ❑ Wide Trench ❑ Seepage Pit Waiver request for: Distance: Expedited review requested: ❑ By applying for this entitlement, this property is subject to inspection by municipal On-site staff to verify the accuracy of the information provided. COSA Fee $ --150 Date of Payment 2 cZ3 COSA # D5c-23 ► 2 Waiver Fee $ Date of Payment Waiver # COSA Application 2022.doc COSA Checklist copy.docx COSA Checklist Legal Description: ALPINE TERRACE BLOCK 1, LOT 7 Parcel ID: 015-243-31 If more than 1 well and/or septic system on lot, provide separate checklist. Structure served by this system ____ A. WELL DATA Well log is filed with Onsite (or attached) Date drilled CIRCA 1973 Total depth 200+/- ft Cased to UNKNOWN ft Sanitary seal is functioning correctly Wires are properly protected Casing height (above ground) 12+ in. Date of flow test for COSA 4/17/2023 Static water level at beginning of test 20 ft. Well production at time of test 4 gpm Water storage tank volume NA gallons Well disinfected for coliform test? Yes No Coliform bacteria is Negative Nitrate 7.46 mg/L Nitrate less than MRL (ND) Arsenic ug/L Arsenic less than MRL (ND) Collected by Date 4/17/2023 Comments _New sanitary seal, conduit & scoped by Sullivan – see Sullivan letter. B. TANK DATA Measured operating fluid level in septic tank NA Date of pumping NEW TANK Required maintenance completed, if AWWTS Comments: C. LIFT STATION Required maintenance completed Age of lift station years Lift station material Comments: D. ABSORPTION FIELD DATA Which system tested (date installed) 8/11/1992 ALL standpipes present per record drawing Total measured depth from grade 5.3 ft (max) Measured depth to pipe invert from grade 3.4 ft (min) N/A – pressurized field. Per record drawings, field is insulated. Monitor tubes (MT) go to bottom of effective. (ED) If not, state depth into effective Presoaked required if (Required if house vacant or field not used for more than 30 days prior to date of test) Gallons introduced 2000 gallons 4/16/23 date Any rejuvenation treatment (past 12 months) N If yes, enter date Adequacy test date 4/17/20223 Results Pass Fluid depth prior to test 0 in Water added 620 gal New fluid depth 4 in Elapsed time 240 min Final fluid depth 0 in Absorption rate 600 gpd FIELD STATUS – POST RECOVERY Effective depth (per record drawings) 6 in (0.5’ ED) Effective depth used 0 in Effective depth (ED) remaining 6 in Comments/Deficiencies: Approximate total measured depths from existing grade. ED per elevation measured shots & appears approximate. COSA Checklist copy.docx E. SEPARATION DISTANCES From Private Well on Lot to: (Please enter distances if less than required or if community well on lot) Septic Tank/Lift Station on Lot > 100’ Yes if No ft Neighboring Tank > 100’ Yes if No ft Absorption Field on Lot > 100’ Yes if No ft Neighboring Absorption Fields > 100’ Yes if No ft Community Sewer Main > 75’ Yes if No ft Community Sewer Manhole/Cleanout > 100’ Yes if No ft Private Sewer/Septic Line > 25’ Yes if No ft Holding Tank > 100’ Yes if No ft Animal Containment > 50’ Yes if No ft Manure/Animal Excreta Storage > 100’ Yes if No ft N/A – Served by Community Well (not on lot) or Public Water From Septic/Holding Tank and Absorption Field(s) on Lot to: (Please enter distances if less than required) Building Foundations > 10’ Yes if No ft Tank to Property Line > 5’ Yes if No ft Field to Property Line > 10’ Yes if No ft Water Main > 10’ Yes if No ft Water Service Line > 10’ Yes if No ft Surface Water > 100’ Yes if No ft Wells on Adjacent Lots: Private Wells > 100’ Yes if No ft Community Wells > 200’ Yes if No ft If tank or field is under driveway comment below F. ENGINEER’S COMMENTS G. CERTIFICATION & STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On-Site Systems Approval Guidelines, indicates that the on-site water supply and/or wastewater disposal system appears to comply with applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation, unless noted otherwise. Name of Firm FIRST WATER CONSULTING Phone 907-350-9566 Engineer’s Printed Name CURTIS HUFFMAN, PE Date 7/7/2023 Comments: This investigation was completed in compliance with MOA guidelines, regulations, and best industry practices / methods. The assessment of the condition of the well and septic applies only to the conditions as of the day tested. The flow and absorption rates may change due to subsurface conditions that may not be observed from the surface, changes in land use, local soil characteristics, groundwater levels that may fluctuate during the year, quality of construction (workmanship & materials), the water usage of the family being served by the system and maintenance. The operational life of all well and septic systems are subject to these various and dynamic characteristics and are outside the control of the evaluator of the well and septic system. Therefore, any or NO estimate of how long a system will function satisfactory for current or future occupants or guarantee that no unseen encroachments, deficiencies or discrepancies exist can be given by First Water Consulting & 7/7/23 Date: 7/19/23 P.O. Box 670269 Chugiak, AK 99567 P: (907) 688-2759 F: (907) 688-2259. TO: First Water Consulting Services Cap and conduit repair has been completed. The well was scoped for high nitrates and logging. No issues were found that would lead to elevated nitrate levels. Well was logged to 42 feet where pump sits. Without pulling the pump the total depth of the well could not be determined, but it is likely not deeper than 50 feet. Casing Stickup : 18” Pitless depth : 11’ Static: 14’ Pump intake: 43’ Total Depth: NA Steel cased : to 42’+ www.muni.org/onsite Nitrate Advisory Certificate of On -Site Systems Approval # OSC231255 Subdivision: Alpine Terrace, Block: 1, Lot: 7 A water sample revealed a nitrate concentration of 7.46 milligrams per liter (mg/L). The Environmental Protection Agency (EPA) has established a maximum contaminant level (MCL) of 10.0 mg/L for public drinking water systems. While private wells are not subject to this regulation, EPA standards are based on existing health information and can therefore be used to gauge the relative quality of water from private wells. Since nitrates are known to slowly increase, we recommend you monitor the water quality. Please see the attached "Nitrate Fact Sheet" for important information regarding nitrate. This advisory must be attached to all copies of the subject Certificate of On -Site Systems Approval. Ma�lmg Address P O Box 196650 *Anchorage, Alaska 99519 6650 *www muni org From Northern Testing Laboratories, Inc. Nitrate is a negatively charged compound of nitrogen and oxygen, which is very soluble in water. Nitrate is not readily filtered or otherwise removed in the soil and can pass rapidly into ground water wells. SOURCE: Nitrate is a major component of fertilizer and wastewater. Often the nitrate is in the form of ammonia or protein first, which through contact with oxygen and certain bacteria, converts to the oxidized form known as nitrate. Sources of nitrate from wastewater include urea, ammonia cleaners, food solids, and bacterial cells. It may also result from the breakdown of organic matter buried in the soil. TOXICITY: Nitrate is generally not toxic to adults or children over the age of two or three years, but is associated with a potentially fatal infant disease called methemoglobinemia. In the digestive system of young children, nitrate converts to nitrite, which can pass through the intestinal wall into the blood stream. There it combines with the hemoglobin and interferes with the ability of the blood to carry oxygen. For this reason, methemoglobinemia is referred to as "blue baby" disease. The EPA limits the concentration of nitrate in public drinking water supplies to 10 mg/L. The standard has been lowered from a previous level of 45 mg/L set by the US Public Health Service and the World Health Organization. TREATMENT: due to its solubility in water and negative ionic charge, filtration and other common home water treatment systems such as softening or iron filtration does not readily remove nitrate. The best method for limiting nitrate in well water is source control. This can include avoiding overdosing of fertilizer near the well and maintaining good separation distances between septic tank leach fields and the well. A special anion exchange filter that contains a media with a strong affinity for negatively charged ions in water, or by a reverse osmosis treatment system or distillation can remove nitrate. TESTING: Nitrate analysis is usually done by one of the several "wet chemical" methods using a spectrophotometer to read the final color endpoint. Specific ion electrodes also can be used to detect the activity of nitrate in water. This laboratory uses several different wet chemical methods approved under the public water supply laboratory certification program. They also have test kits available, which the laboratory uses to perform an inexpensive "screening test", and with which the homeowner can monitor the change in nitrate levels from their well. They recommend comparing the test kit results against a certified analysis from the lab occasionally to verify the accuracy of the kit. We recommend using a specially prepared bottle that has been rinsed in hydrochloric acid for collecting samples.