HomeMy WebLinkAboutALPINE TERRACE BLK 1 LT 10Municipality of Anchorage On-Site Water and Wastewater Section • (907) 343-7904 Page 1 of 3 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP191253 PID Number: 015-243-34 Dwelling: ❑i Single Family (SF) ❑ with ADU ❑ Duplex (D) ❑ Two Single Family Project: ❑ New ❑■ Upgrade Name KELLY POSTON ABSORPTION FIELD ❑ Deep Trench ❑■ Wide Trench El Bed ❑Mound Site Address 11601 HILLSIDE DRIVE *ANCHORAGE, AK 99507 ❑ Other Phone Number of Bedrooms Soil Rating depth from original grade 907-240-2319 4 1.2 GPD/SF JTotal 8 Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade SEE DWG. Ft. Gravel depth beneath pipe 4.02 Ft. Subdivision Block Lot ALPINE TERRACE; BLOCK 1, LOT 10 Fill added above original grade SEE DWG. Ft. Gravel length 25+25=50 Ft. Township Range Section N/A Gravel width 5 Ft. Beds: Number of Lines - Distance between lines - Ft. SEPARATION DISTANCES To Septic Absorption Lift Station Holding Sewer Total absorption area Number of trenches Dist. between trenches From Tank Field Tank Line 500 Ftz 1 - Ft. Well 100'+ 100'+ N/A N/A 25'+ TANK X Septic ❑ S.T.E.P. ❑ Holding ❑ Other Manufacturer Capacity INFILTRATOR 1530 Gal. Surface Water 100' + *80'+ N/A N/A Material HDPE Number of compartments 2 Lot Line 5'+ 10'+ N/A N/A NA Foundation 10'+ 10'+ N/A N/A LIFT STATION Manufacturer N/A Capacity _ Gal. 1 1 I Remarks OLD TANK DECOMMISSIONED PER UPC PER CONTRACTOR *WR#OSV191059 Alarm location Electrical installed by PIPE MATERIAL House to tank D3034 drainfieldTank to D3034 Installer A+ HOME SERVICES Drainfield D3034 CO/MTD3034 Inspector DAVID GARNESS & TIM ECKLUND BENCH MARK (Assumed elevation) 99.73 ft Inspection 151 7/8/2019 7/29/19 Location and description 2nd OF MANHOLE 3`tl 7/29/19 4117/29/19 ITOP ON-SITE WATER AND WASTEWATER SECTION APPROVAL Engineer's Stamp OF.A����4 Conditional Approval: Date QQ�P.. ..•,�40 T oma. 4 00 ........... ................. Septic System O •.J A. ess:Q 00 E 7953 �QQ Approved (/r(1L _ QC!UZ Date q 30 4p�� e '•. �� �o�Q Note: this approval does not include well permit requirements.#nec1884 ��Oo0o� c' (Rev 05/02/18) PERMIT NUMBER: OSP191253 A I B I C MH 33.7 14.5 36.8 ST1 25.6 15.3 46.8 DBL1 26.9 17.1 46.7 DBI -2 27.6 18.1 46.8 C01 68.4 55.6 47.0 MT1 66.6 54.5 47.5 CO2 37.3 26.7 44.1 MT2 1 35.7 1 25.1 44.3 MT3 1 54.5 1 34.8 25.6 I I I I I I I I I RECORD DRAWING NEW DRAINFIELD ��, :�, OM1. • r <' v'• PARCEL ID NUMBER: 015-243-34 NEW IM -1530 INFILTRATOR SEPTIC TANK SHED DBL182 0 /A 1 C T2\ I>. T1 '� •, H .B DECK H.#1 \ FCO C� EXISTING '� •,�..�•, •+•: \ BEDROOM HOUSE ENGINEERING o SALES o CONSULTING ---- -------- 3701 E. TUDOR ROAD. SUITE 101 -ANCHORAGE. AK 99507 • PHONE (907) 337-6179 • FAX (907) 336-3246' WEBSITE: w+ rv/.gamessengineenng.cam PREPARED FOR: PHONE NUMBER: PAGE NUMBER: I 907-240-2319 W •i` r' CO T 80'+ TO ROAD t '• a'\ I u DITCH/SURFACE WATERS N :� .,.:�•'• .,. -tom'{,. '` �; •"'r � SHE 0 I W I ;• % T 9/25/2019 -j. DRIVEWAY .•' •'. '•' •f aa.••.••,. _ a (APPROXIMATE LOCATION OF _I WATER LINE PER ONE STOP _ SERVICES LOCATE - SEE ATTACHED PHOTOS NEW DRAINFIELD ��, :�, OM1. • r <' v'• PARCEL ID NUMBER: 015-243-34 NEW IM -1530 INFILTRATOR SEPTIC TANK SHED DBL182 0 /A 1 C T2\ I>. T1 '� •, H .B DECK H.#1 \ FCO C� EXISTING '� •,�..�•, •+•: \ BEDROOM HOUSE e4v � I ya�v ALPINE TERRACE; BLOCK 1, LOT 9 / d / CSEPTIC I ARE�D GARNESS ENGINEERING GROUP, Ltd ENGINEERING o SALES o CONSULTING ---- -------- 3701 E. TUDOR ROAD. SUITE 101 -ANCHORAGE. AK 99507 • PHONE (907) 337-6179 • FAX (907) 336-3246' WEBSITE: w+ rv/.gamessengineenng.cam PREPARED FOR: PHONE NUMBER: PAGE NUMBER: KELLY POSTON 907-240-2319 2 OF 3 LEGAL DESCRIPTION: DRAWN BY: ALPINE TERRACE; BLOCK 1, LOT 10 D.J.G. :� .,.:�•'• .,. -tom'{,. '` �; •"'r � SHE I SEPTIC SYSTEM RECORD DRAWINGS 9/25/2019 -j. DRIVEWAY .•' •'. '•' •f aa.••.••,. _ a e4v � I ya�v ALPINE TERRACE; BLOCK 1, LOT 9 / d / CSEPTIC I ARE�D GARNESS ENGINEERING GROUP, Ltd ENGINEERING o SALES o CONSULTING ---- -------- 3701 E. TUDOR ROAD. SUITE 101 -ANCHORAGE. AK 99507 • PHONE (907) 337-6179 • FAX (907) 336-3246' WEBSITE: w+ rv/.gamessengineenng.cam PREPARED FOR: PHONE NUMBER: PAGE NUMBER: KELLY POSTON 907-240-2319 2 OF 3 LEGAL DESCRIPTION: DRAWN BY: ALPINE TERRACE; BLOCK 1, LOT 10 D.J.G. TYPE OF WORK: DATE: SEPTIC SYSTEM RECORD DRAWINGS 9/25/2019 Ql V=40' Ar � c : AV te •• ; rey A. W i # CE -795 i .q.,N e17, 417 LICENSE #141k J%6FES"�.,.,� #AECC884 i PERMIT NUMBER: OSP191253 RECORD DRAWING TOP OF MH = 99.73 TOP OF TANK AT INLET = 96.67 INVERT OF BUNG AT INLET = 96.08 TH#1 ORIGINAL GRADE AT HIGHEST POINT= 99.50 FINAL GRADE = 99.27-99.45 IM -1530 TWO-COMPARTMENT INFILTRATOR SEPTIC TANK �v►sje;p PARCEL ID NUMBER: 015-243-34 2" HIGH DENSITY INSULATION (PER CONTRACTOR) — TOP OF TANK AT OUTLET = 96.60 MT CO f— FINAL GRADE= 98.63-99.81 INVERT OF BUNG AT OUTLET = 95.63 INSULATION OVER "WEST LEG' OF TRENCH PER CONTRACTOR - FILTER FABRIC RELATIVE ELEVATION OF BOTTOM OF T.H. = 83.0 (GW AT 14.1' BELOW GRADE ON 7/29/2017) INVERT OF PIPE THROUGHOUT DRAINFIELD = 95.52 BOTTOM OF TRENCH = 91.50 •��\\\\ 11, 41 --- -- - – — - -- AN * • 4 ski GARNESS ENGINEERING GROUP, Ltd(.O ............. . - ---- -- -- - ---- - ENGINEERING o SALES CONSULTING ------------ -- - s 3701 E. TUDOR ROAD, SUITE 101 ' ANCHORAGE, AK 99507' PHONE (907) 3376179' FAX (907)338-3246 ' WEBSITE: vrvrvi.gamessengineenng.com . . . . ...............•• ••., . 0 PREPARED FOR: PHONE NUMBER: PAGE NUMBER: ;•, rey . Games4-1 AV KELLY POSTON 907-240-2319 3 OF 3 �Off s�.- ' CE -79 :° LEGAL DESCRIPTION: DRAWN BY: S.f AV ALPINE TERRACE; BLOCK 1, LOT 10 D.J.G. Sj Fp p..l......... 48• TYPE OF WORK: DATE: LICENSE 11 � :S`S` w��• � SEPTIC TANK AND DRAINFIELD PROFILE 9/25/2019 #AECC884 i SGS Ref.# 1194277001 Client Name Garness Engineering Group, Ltd (GEG) Printed Date/Time 08/07/2019 16:03 Project Name/if Alpine Terrace B 1 L10 Collected Date/Time 07/31/2019 15:19 Client Sample ID Alpine Terrace B1 L10 Received Dateirime 07/31/2019 16:15 Matrix Drinking Water Technical Director Stephen C. Ede Sample Remarks Allowable Prep Analysis Parameter Results LOQ Units Method Container ID Limits Date Date Init Metals by ICP/MS Arsenic ND 5.00 ug/L EP200.8 B (<10) 08/05/19 08/05/19 DSH Waters Department Total Nitrate/Nitrite-N Microbioloav Laboratory E. Coli Total Coliform 3.09 Negative Negative 0.200 mg/L SM21450ONO3-F C (<10) 1 100mL SM219223B A 1 100ml- SM219223B A 08/02/19 EWW 07/31/19 VDL 07/31/19 VDL i is � - _. - _ _ .. - ._ • + •' t Y.. i,rn i$ ter _ • ,dy,' •5 . r. - - � �„' � � ,..�/.d' - y. +• r,_ ..tib � CL _ � r r�j •, • rX'.v ' = .. _ � 7 7 � _ .. Ir. r '•A S• r ,� .• NI ' y •. ii p' IV 1 •� V f. '•1 5 g. i e � � 1 _ r t'r ti 1 ♦.. y, _ L' • r '1 1 F Y 4 _ �. '• � ,,. tr� � m � i�• r - .. ; -q t` 't � r S u n , re. L �, 3�{ r • r ` s r tires-�_• r r. ��,,. r '� � _ ; r y. _ x m � f • -� - 'S + r •' F r i •� - �— . _ _ _�.. .. �.___ ..l.__. _.�...__ �. _� r��._ �.__ .��=YyS"y'- _ __.a �..._�C i— _�_ _ ._-..J�� _ t...4 M t�=`._ a•W�_ __._.._ _."• _— •p. OF ... �0 �., 49 TH �G o a s� SHANE A. HOLT a ld� LS -6914 6pA'ofession?A S 89 58' E 210.00 N 89 58' E 2 10. 00 THE INFORMATION HEREON IS FOR THE USE OF LENDING INSTITUTIONS SPECIFICALLY TO SHOW ANY CONFLICTS BETWEEN EXISTING STRUCTURES AND PLATTED LOT LINES AND/OR EASEMENTS; AND IS NOT TO BE USED FOR POSITIONING ADDITIONAL STRUCTURES, IMPROVEMENTS, OR FENCELINES. EASEMENTS OF RECORD, OTHER THAN THOSE APPEARING ON THE RECORD PLAT , ARE NOT SHOWN HEREON ( UNLESS INDICATED) NOTE: FENCELINES THAT MAY APPEAR ON THIS DRAWING ARE NOT TO BE USED TO DETERMNE PROPERTY LINES OR POSITION ADDITIONAL IMPROVEMENTS. ANY PAVING SHOWN HEREON MAY BE APPROXIMATE DUE TO EXCESSIVE SNOW AND/OR ICE. AS -BUIL T SURVEY i " = 30, NO CORNERS SET THIS DATE SURVEY ORDERED SY: DAR ✓ILDE„ YELLER Mi LUAMS I HEREBY CERTIFY THAT I HAVE PERFORMED A SURVEY OF THE FOLLOWING DESCRIBED PROPERTY LOT 10, BLOCK 1, ALPINE TERRACE SUB. ANCHORAGE RECORDING DISTRICT, ALASKA, AND THAT THE VISIBLE IMPROVEMENTS SITUATED THEREON ARE WITHIN THE PROPERTY LINES AND NO VISIBLE ENCROACHMENTS EXIST OTHER THAN NOTED. DATED AT ANCHORAGE, ALASKA THIS _6 TH DAY OF _AUGUST , 2019 25C'5, lc2_40' HOLT LAND SURVEY/NG 9309 GROVER DRIVE ANCHORAGE,AK 99507 907223.8615 MUNICIPALITY OF ANCHORAGE On -Site Water & Wastewater Program PO Box 196650 4700 Elmore Road Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997 http://www.muni.org/onsite On -Site Wastewater Disposal System Permit Permit Number: OSP191253 Work Type: Septic . Upgrade Tax Code Number: 01524334000 Site Legal Address: ALPINE TERRACE BLK 1 LT 10 G:2740 Site Mailing Address: 11601 HILLSIDE DR, Anchorage Owner: POSTON MICHAEL R & KELLY E Design Engineer: GARNESS ENGINEERING GROUP LTD This permit is for the construction of: R� Disposal Field Q Septic Tank ❑ Holding Tank ❑ Privy Effective Date: Expiration Date: moment O De 1)a rtinent Lot Size in Sq Ft: Total Bedrooms: 6/26/2019 6/25/2020 44000 ❑ Private Well ❑ Water Storage All construction shall be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80) 3. The wastewater code requires inspections during the installation. The engineer shall notify the Development Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather shall be either: a. Opened and Closed on the same day, or b. Covered, sealed, and heated to prevent freezing Received B) Issued By: Date: 61 -?-4o Date: b 611 % TTI,unicipality of Anchorage- P.O. Box 196650 ® 4700 Elmore Road Anchorage, Alaska 99519-6650 0 (907) 343-7904 ® Fax (907) 343-7997 http://www.muni.org/Onsite Development Services Department On -Site Water and Wastewater Section 11�� Il t A L)cp:u•rment x x x x VALIANCE/WAIVER REVIEW x x x x Waiver#: OSV191059 COSA#: Permit#:OSP191253 PID#: 015-243-34 Legal Description: Alpine Terrace Block 1 Lot 10 Engineer: Garness Engineering Group Applicant: Michael & Kelly Poston Your request for a waiver of the required 100 feet horizontal separation from the absorption field to the surface water has been approved. The approved separation distance is 80.0 feet. See engineer's waiver request for j ustifications. This waiver approval applies to the proposed absorption field only. Any future upgrade to the on-site wastewater- disposal system will require all separation distances be met or another approval from this department. ■.............................................. ■ ....... t ..................... ■ 1 Waiver is Granted: X Waiver is not Granted: Date:7 [,,/)I Approved by:�1.&nu ' Name of Reviewer ................... a ........................... ■ ............................. ■ 1 **** VARIAN C EMAIVE R REVIEW **** MUNICIPALITY OF ANCHORAGE Community Development Department Development Services On -Site Water & Wastewater Program Mayor Dan Sullivan On -Site Sewer/Well Permit Application For A Single Family Dwelling Parcel I.D. 015-243-34 Property owner(s) KELLY POSTON Mailing address 11601 HILLSIDE DRIVE "ANCHORAGE, AK 99507 Site address 11601 HILLSIDE DRIVE 'ANCHORAGE, AK 99507 Legal description (Sub'd, Block & Lot) ALPINE TERRACE; BLOCK 1, LOT 10 Legal description (Township, Section & Range) Lot Size APPLICATION IS FOR: (Z all that apply) Absorption Field Septic Tank Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage ❑ 56788 Phone: 907-343-7904 Fax: 907- 343-7997 Day phone 240-2319 Sq.Ft. Number of Bedrooms 4 APPLICATION IS AN: Initial ❑ Upgrade Renewal ❑ THIS APPLICATION INCLUDES A VARIANCE/ WAIVER REQUEST FOR: DRAINFIELD TO SURFACE WATERS TYPE OF DEWELLING: Single Family (SF) (w/wo ADU) Duplex (D) ❑ Multiple Dwellings ❑ (SF and/or D) Distance: 80 FEET I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal codes. GARNESS ENGINEERING GROUP, Ltd. (Signature of property owner or authorized agent) Permit/Rush Fees: o(2 Waiver Fees: 390 t q06 Date of Payment: % Date of Payment: Receipt Number: _ OS 3�G Receipt Number: 69 -36 Permit No. Ospf f 2 3 Waiver No. V% A 10 (Rev. 01 /11) GARNESS ENGINEERING GROUP, Ltd — - - – ----- ENGINEERING SALES -CONSULTING =- -_ --- - July 16th, 2019 Municipality of Anchorage Development Service Department On -Site Water & Wastewater Program 4700 Elmore Road Anchorage, AK 99507 Ref: Proposed Septic System Upgrade for Alpine Terrace; Block 1, Lot 10 To whom it may concern: Qual cs ____ AdvanCcd T.-ca[mcnt System de O The existing 4 -bedroom house is served by a private well and septic system. A tank permit was issued on 6/26/2019. Per the approved permit, the drainfield was to be exposed and new C/O's and MT's were to be installed during the septic tank replacement. During the tank install, it was noted that the existing drainfield did not have drainrock and the distribution line was structurally unsound "Orangeburg pipe". Do to this fact, the MOA employee present (Tim Eklund) determined that the drainfield would not be accepted and must be replaced. A testhole was excavated and the drainfield was designed around its 30 -foot radius. Comments regarding the design are summarized as follows: 1. SOILS: See attached 2019 testhole by Garness Engineering Group, Ltd. which shows, soil classification, percolation test and groundwater monitoring. 2. DRAINFIELD DESIGN: See attached design drawing for drainfield specifications. 3. SURFACE WATERS: See waiver request. 4. TOPOGRAPHY: There are no topography concerns. 5. WAIVERS: There is surface water approximately 85' west of the proposed drainfield. We are requesting that your department issue a variance from drainfield to surface waters of 80 feet. Justification for granting this waiver is as follows: • The existing drainfield was installed in 1978. It is likely that the drainfield has always encroached upon this "surface water". • The surface waters may be intermittent. • The driveway is located between the proposed drainfield and the surface waters. If effluent were to overflow, it would be noted by the homeowner and corrective action taken. • The home has a "daylight" basement. It is plausible that effluent would surface in the home, prior to surfacing from the top of the cleanouts and/or monitoring tubes. We are unaware of any questions, plea Ztffre�A.�C�arne P.E., M Presi ent // rse impacts this installation would have on adjacent wells or septic systems. If you have t us at 337-6179. Thank you for your assistance. 3701 East Tudor Road, Suite 101 * Anchorage, Alaska 99507-1259 Phone: (907) 337-6179 * Fax: (907) 338-3246 * Website: www.garnessengineering.com CROMWELL HEIGHTS; / \ BLOCK 2, LOT 1 I / w ❑ CARR; LOT 3A li I I VACANT PER MOA fy p� RECORDS Q o _I r� :1si S9•L ALPINE TERRACE; BLOCK 1, LOT 5 THE SUMMIT; \ 10 'WELL DIUS I \\ // (SEPTIC ALPNE TERRA AREn -131_00-rLOT9 / ALPINE TERRACE; BLOCK 1, LOT 6 - - I I I THE SUMMIT; \ TRACT Al / GARNESS ENGINEERING GROUP, Ltd -- ENGINEERING � SALES CONSULTING ------ — 3701 E. TUDOR ROAD, SUITE 101 ' ANCHORAGE, AK 99507 • PH(apE (907) 337-6179 -FAX (907) 338-3246 - WEBSITE: w .gamessengineering.com PREPARED FOR: KELLY POSTON PROJECT/LEGAL DESCRIPTION: ALPINE TERRACE; BLOCK 1, LOT 10 TYPE OF WORK: SEPTIC SYSTEM DESIGN UPGRADE PHONE NUMBER: 907-240-2319 PAGE NUMBER: 1 OF 2 DRAWN BY: D.J.G. DATE: 7/15/2019 1" =1100' OF . �P........... E......... ...... .....v O ♦♦♦ �=. ff Garn ss ♦ •'sl CE -79 •' -7/h LICENSE 1111O\\SS\Ok�' • #AECC884 / DESIGN CRITERIA: NUMBER OF BEDROOMS: 4 GALLONS PER DAY (GPD): 600 PERCOLATION RATE/S: 1.33 MIN/INCH PROPOSED APPLICATION RATE: 1.2 GPD/FT' MINIMUM DRAINFIELD SQ.FT.: 500 FT' DRAINFIELD DESIGN: MAXIMUM DEPTH: 8 FEET WIDTH: 5 FEET LENGTH: 50 FEET EFFECTIVE: 4 FEET REDUCTION FACTOR: 0.5 ACTUAL SQ.FT.: 500 FT' GEG, Ltd. HAS AN 8 PAGE SPECIFICATION LETTER '_� . •„: _” APPROXIMATE LOCATION OF NEW '•°%' • PROPOSED DRAINFIELD ; IM 1530 INFILTRATOR SEPTIC TANK THAT PERTAINS TO THIS DESIGN. BY PROCEEDING �.... �( NOTE: THE CONTRACTOR ............................ 0 FORWARD WITH THIS INSTALLATION, THE SHED SHALL HAVE THE WELL RADII CE -79 AV AV ENGINEER, WELL DRILLER, CONTRACTOR AND r; i9••.• 4v FLAGGED BY A REGISTERED PROPERTY OWNER AGREE THAT THEY HAVE / �':�• READ THESE SPECIFICATIONS AND AGREE TO LAND SURVEYOR PRIOR TO ACCEPT THE TERMS AND CONDITIONS OUTLINED. CONSTRUCTION. THE PROPOSED DRAINFIELD IS PLACED SURFACE WATER WAIVERST CARPORT : OVER/THROUGH THE EXISTING / �j� M � °•�..., \ DRAINFIELD, WHICH DID NOT CONTAIN T.H.#1 � CF' •� �.':. DRAINROCK PER GEG INSPECTION \ CARR; LOT 3A 10' UTILITY EASEMENT I- — — — — — — — ----- — — — — — — — — — — — — — — —— �I APPROXIMATE (ASSUMED) LOCATION OF SUBSURFACE DRIVEWAY DRAIN PER MOA RECORDS; NO C/O'S WERE FOUND APPROXIMATE LOCATION OF AS SHOWN ON THE 7/1993 DRAWING BY TED MORE, P.E. ! \ / SURFACE WATERS IN ROAD DITCH \ Ad GARNESS ENGINEERING GROUP, Ltd --_ — -- __ ENGINEERING o SALES,,) CONSULTING =--- 3701 E. TUDOR ROAD, SUITE 101 • ANCHORAGE, AK 99507 • PHONE (907) 337-6179' FAX (907) 338-3246' WEBSITE: w .gamessengineedng.com PREPARED FOR: KELLY POSTON PROJECT/LEGAL DESCRIPTION: ALPINE TERRACE; BLOCK 1, LOT 10 TYPE OF WORK: 11 DESIGN OF SEPTIC TANK UPGRADE PHONE NUMBER: PAGE NUMBER: 907-240-2319 2 OF 2 DRAWN BY: D.J.G. DATE: 7/15/2019 T : (AN '_� . •„: _” APPROXIMATE LOCATION OF NEW '•°%' • PROPOSED DRAINFIELD ; IM 1530 INFILTRATOR SEPTIC TANK •.....� �.... �( .. ............................ 0 SHED CE -79 AV AV �� ,, r; i9••.• 4v pROFESS1�Pi��' LOCATE DRAIN OUTLET •�" • • ' / �':�• _�. 4. SURFACE WATER WAIVERST CARPORT : •{ coo - / �j� M � °•�..., o 1 T.H.#1 � CF' •� �.':. ,,• m m \ EXISTING 4 GRAVEL BEDROOM HOUSE i : `' DRIVEWAY •% z i GRAVEL DRIVEWAY ' •` : J4. �.. '� •. ,.; �i. HE . ,.}..:�•:.:��s. f ' '. ` :..•.: • :+ `� DRIVEWAY Ad GARNESS ENGINEERING GROUP, Ltd --_ — -- __ ENGINEERING o SALES,,) CONSULTING =--- 3701 E. TUDOR ROAD, SUITE 101 • ANCHORAGE, AK 99507 • PHONE (907) 337-6179' FAX (907) 338-3246' WEBSITE: w .gamessengineedng.com PREPARED FOR: KELLY POSTON PROJECT/LEGAL DESCRIPTION: ALPINE TERRACE; BLOCK 1, LOT 10 TYPE OF WORK: 11 DESIGN OF SEPTIC TANK UPGRADE PHONE NUMBER: PAGE NUMBER: 907-240-2319 2 OF 2 DRAWN BY: D.J.G. DATE: 7/15/2019 T : (AN •� ■.....:.....4 •.....� �.... �( .. ............................ 0 Gar ess .- -Q M CE -79 AV AV �� ,, r; i9••.• 4v pROFESS1�Pi��' LICENSElI%k1% #AECC884 / GA,l,R'.Nl,v,.:jSS SEN GEN EERING GROUP, Lt: ENGINEERING SALES CONSd 3101 E. TUDOR ROAD. SUITE 101 'ANCHORAGE. AK 99507' PHONE (907) 337-6179' FAX (907)33"246 - WEBSITE: vnnv.game engineenng.cam SOIL LOG - PERCOLATION TEST LEGAL DESCRIPTION: ALPINE TERRACE; BLOCK 1, LOT 10 PERFORMED FOR: KELLY POSTON DATE: 7/8/2019 DEPTH (feet) ORGANICS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 GM SP TEST HOLE #1 SOIL CLASSIFICATIONS ' 1111"111 NET TIME (MINUTES) WATER LEVEL READING 112111w'I i//iI 0:00 %��/% MEN • wY,YY 111111111 6:42 'Rilm1 6" 3 0:00 �iZZ000A l/� • - 4 7:38 DEPTH TO DATE GROUNDWATER 16' 7/8/2019 14' 7/15/2019 SITE PLAN DATE READING CLOCK TIME NET TIME (MINUTES) WATER LEVEL READING NET DROP (INCHES) 7/8/2019 1 0:00 - 6" - 2 6:42 6:42 0" 6" 3 0:00 - 6" - 4 7:38 7:38 0.. 61, 5 0:00 - 6" - 6 7:42 7:42 0" 6" 7 0:00 - 6" - 8 7:58 7:58 0" 6" 9 0:00 - 6" - 10 8:02 8:02 0" 6" 11 0:00 6" - 12 8:05 8:05 0" 6" 19 PERCOLATION RATE 1.3 (MIN./INCH) PERC. HOLE DIA. 6 (INCHES) TEST RUN BETWEEN 4 FT. AND 5 FT. 20 A FOUR HOUR PRESOAK WAS PERFORMED: ❑ YES NO SOILS LOGGED BY: DAVID GARNESS PERCOLATION TEST PERFORMED BY: DAVID GARNESS COMMENTS: PERCOLATION READINGS ARE WITHIN 1/16 OF INCH.; PERK WAS PERFORMED WITH MOA ONSITE EMPLOYEE TIM ECKLUND OVERSIGHT PERFORMED BY GEG, Ltd. I, JEFFREY A. GARNESS, CERTIFY THAT THIS WAS PER OR�/ ED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE: �// c/ / V t. __ Quanics GARNESS ENGINEERING GROUP, Ltd AdvancedTreatment System ENGINEERING SALES CONSULTING Dealer June 19, 2019 Municipality of Anchorage Development Service Department On-Site Water &Wastewater Program 4700 Elmore Road Anchorage, AK 99507 Ref: Proposed Septic Tank Upgrade for Alpine Terrace; Block 1, Lot 10 To whom it may concern: The subject lot is served by a private well and septic system. Per MOA memorandum, a steel septic tank over 30 years of age must be physically inspected and/or replaced. Based upon this fact, we are proposing to install a new septic tank. We are proposing to decommission the existing septic tank per UPC and install a new IM-1530 infiltrator septic tank. See attached design drawings for tank location and other MOA requirements. We are unaware of any adverse impacts this installation would have on adjacent wells or septic systems. If you have any questions, please contact us at 337-6179. Thank you for your assistance. Sincerely, Jeffr A. came '.E., M.S. President 3701 East Tudor Road, Suite 101 *Anchorage,Alaska 99507-1259 Phone: (907)337-6179*Fax: (907)338-3246*Website: www.garnessengineering.com i 1 1 I 1 GEG,Ltd.HAS AN 8 PAGE SPECIFICATION LETTER I THAT PERTAINS TO THIS DESIGN.BY PROCEEDING NOTE:THE CONTRACTOR SHALL HAVE THE FORWARD WITH THIS INSTALLATION,THE ENGINEER,WELL DRILLER,CONTRACTOR AND WELL RADII FLAGGED BY A REGISTEREDI PROPERTY OWNER AGREE THAT THEY HAVE LAND SURVEYOR PRIOR TO CONSTRUCTION. READ THESE SPECIFICATIONS AND AGREE TO I ACCEPT THE TERMS AND CONDITIONS OUTLINED. CARR;LOT 3A \ TRENCH ORIENTATIONS AND LOCATIONS ARE UNKOWN;SOUTHEAST PORTION OF ALL THREE TRENCHES TO BE LOCATED TO CONFIRM 5' 10'UTILITY EASEMENT SEPARATION DISTANCE OF PROPOSED TANK SOUTHEAST PORTION OF BED TO BE EXPOSED; INSTALL CLEANOUT AND MT IN SE CORNER •%••'i• PROPOSED IM-1530 INFILTRATOR SEPTIC ••• ',..."•••••• ?••':' ....4 TANK;EXISTING SEPTIC TANK TO BE •! DECOMMISSIONED PER UPC. �.. • • '• • • "...'e• "�':'' -...7.i.• • SHED EXISTING MT;INSTALLC/O AND FUNCTIONAL MT •\ • • • +•f•: :r i AT BEGINNING OF TRENCH.GEG TO BE .y. / PRESENT DURING C/O INSTALLATION • •; CARPORT o c•:- O \ S— 1 :r r_ F�<� :•::•' \ EXISTING4 GRAVEL m \ BEDROOM HOUSE ••`y DRIVEWAY z {J. GRAVEL ';%• �' ; DRIVEWAY ' •`4 '�I. :.. ..•.., .•; :.. .. • : ?: ..:•�: ..+' SHED •4 `'~ . il(\1 •' .4% �J DRIVEWAY :.•+ ".*•••• •:.•••••"./...;. ,• . '"-,-. "•''• }}hht SCALE: 1"=40' .616\\\ . .. ..x �j• GARNESS ENGINEERING GROUP, Ltd ; • ENGINEERING SALES.CONSULTING or 3701 E.TUDOR ROAD,SUITE 101•ANCHORAGE.AK 99507•PHONE(907)337.6179•FAX(907)338-3246•WEBSITE:www.gemessengneering.00m • • ; PREPARED FOR: PHONE NUMBER: PAGE NUMBER: ,0 ••/•• I: '. Garne s /W: KELLY POSTON 907-240-2319 1 OF 1 ts�J, CE-\.53 *= PROJECT/LEGAL DESCRIPTION: DRAWN BY: ALPINE TERRACE; BLOCK 1, LOT 10 D.J.G. ., IFI ...4./242. �(' �P�,.'•. TYPE OF WORK: DATE: LICENSE.4 ,. ESS JJ\� ��• DESIGN OF SEPTIC TANK UPGRADE 6/20/2019 #AECC884 ������ ! /IUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTION ENVIRONMENTAL ENGINEERING DIVISION 825 L Street- Anchorage, Alaska 99501 Telephone 264-4720 ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT NAME IPHONE MAILING ADDRESS LEGAL DESCfllPTION LOGATION NO. OF BEDROOMS-- JWeU I Absorption area Dwelling PERMIT NO. ~ DISTANCE TO: i ~.~ [~ t ~< Manufacturer ~ r~_ ~r M~te~ 7~ , No. of compartments ~ ~ Liq. capamty in g~lons IF HOmE,DE: Inside length Widt~ Liquid depth ~ ~ ~ Well Dwelling PERMIT NO. ~ ~ Z DISTANGE TO: O ~ ~ Manufacturer Material Liquid capacitV in gallons = Well Foundation Nearest lot line PERMIT NO. DISTANCE TO: ~ ~ ~o. of lines ken,th of each line Total length of lines Trench ~idth ~istance between lines inches ~ ~ Top of tile to finish ~rade Material beneath tile Total effective absorotion area ~ inches Length Width Depth PERMIT NO, ~ ~ Type of crib Crib diameter Crib depth Total effective absorption area ~ Well Building foundation Nearest lot line ~ DISTANCE TO: ~ Class Depth Driller Distance to lot line PERMIT NO. ~ DISTANCE TO: Building foundation Sewer line Septic tank ~ (~: (~.~ Absorption area(s) OTHER .~P. MATEmALS ~ NJ~ SOIL TEST RATING INSTALLER REMARKS () 72-013 (Rev. 3/78) GRE '-:R ANCHORAGE AREA BO', IGH Del)lrtment of Environment Quality 3500 Tudor RoKI Anchor~. Alaska 99S07 INSPECTION REPORT ON-SITE SEWAGE DISPOSAL SYSTEM LOCATION MAILING Al)DRESS ?'f/~- /J~/ g-.2~'7 ~ ,,. SEPTIC TANI~ ,~t~' H NUMBER OF WM ~ ~ INSI~ WIDTH ~ LIQU~ ~ ~ , LI~ CN~I DIAGRAM OF SYSTEM / · · b/eL/- DAT~~ APPROVED GRE,_.ER ANCHOragE AREA Bo~ugh DEPARTMENT OF ENVIRONMENTAL QUALITY :3500 TUDOR ROAD POUCH 6-6§O ANCHORAGE, ALASKA 99502 TELEPHONE 279-8686 SEWAGE DISPOSAL SYSTEM -- APPLICATION AND PERMIT . ~_ ., / MAILING INSTALLATION OF: SEPTIC TANK ~ SEEPAGE PiT PERMIT NO. - PHONE DRAIN FIELD OTHER DRAIN FIELD SEPTIC TANK TO SEEPAGE PiT WALL I SEPTIC TANK . SEEPAGE PIT , TO NEAREST LOT LINE. WELL TO SEPTIC TANK DRAIN FIELD WATER MAIN TO SEPTIC TAN_~K DRAIN FIELD /~"~/: SEPTIC TANK, I . SEEPAGE PIT TO RIVER. LAKE. STREAM. DRAIN FIELD SEEPAGE PIT ALSO CONSIDER AREA WELLS. SEEPAGE PIT., /~r~ / , DRAIN FIELD CAST IRON INTO AND OUT OF SEPTIC TANK AND INTO CRIB CROSSING GAP OF EXCAVATION S FEET INTO UNDISTURBED SOIL, 4 INCH DIAMETER CAST IRON SIPHON PIPES ON SEPTIC TANK AND SEEPAGE PiT FIT'TED WITH AIRTIGHT REMOVABLE CAPS, CONFORM TO BOROUGH REGULATIONS REGARDING INSTALLATION. OR LICENSED DESIGNER FOUNDATION TO SEEPAGE PIT _ _ TYPE MINIMUM DISTANCES, REQUIREMENT~ FOUNDATION TO SEPTIC TANK '~ / DIAGRAM OF SYSTEM I CERTIFY THAT I AM FAMILIAR WITH THE REQUIREMENTS OF GREATER ANCHORAGE AREA BOROUGH ORDINANCE NO. 28-68 AND THAT THE ABOVE DATE~' ~[~ / ¢ 7 ~-~''''DE$CRISED SYSTEM'S IN ACCORDANCE WITH SAID CODE.__ APPLICANT'S SIGNATURE ~'"~L ~"~ 0' ~' J'~~_ PINAI. IN~PEC. TION~ 14 HOUR NOTICE RIQUlRED. B&CKPILLING OF' ANY SYSTEM WITHOUT FINAl., INSPECTION IBY 'rHIE HEALTN DWPARTMENT AUTHORITY ~II.L BE SUBJ~'I=T TO PROSW~UTION. TO BE IN T L'~ S A LED BY / ~'~--)'~l~/ ~ / NOTE: THIS PERMIT IS NOT VALID WITHOUT ~,OIL TEST SEWAGE DISPOSAL SYSTEM -- APPLICATION AND PERMIT GRE,,,, ,.-:R ANCHORAGE AREA BOF.<,...JGH DEPARTMENT OF ENVIRONMENTAL QUALITY 350(') TUL')OR ROAD F'C}UCH 6-650 ArqCHO~AGE ALASKA 99502 TELEPHOTO[ 279-8686 PERMIT NO, N^ME OF ^PPL~CANT INSTALLATION LOCATION PHONE INSTALLATION OF: SEPTIC TANK ~ SEEPAGE PIT DRAIN FIELD OTHER SOIL TEST RESULTS ~P ~//~"; ~ NOTE~ THI~ PERMIT IS NOT VALID WITHOUT ~IL ~ST PFRMTT VAI ID ~NF YFAR FINAL INSPEGTION~ 24 HOUR NOTI~ REGUIRED. BACKFILLING OF ANY ~Y~M WITHOUT FINAL IN~E~TION BY THE H~A~TH D~PARTM~NT AUTHORI~ WILL BE ~U~J~CT TO PROSECUTION. SEPTIC TANK SIZE /('~¢)L¢~ TYPE~te~-] Ol' ct~ncTR[eSEEPAGE AREA SIZE TYPE MINIMUM DIBTANCES, REQUIREMENTS 5 ft. FOUNDATION TO SEPTIC TANK FOUNDATION TO SEEPAGE PIT 20 f~e DRAIN FIELD 10 SEPTIC TANK TO SEEPAGE PIT WALL [.5 SEPTIC TANK 5 fg, , SEEPAGE PIT 20 fi' . DRAIN FIELD TO NEAREST LOT LINE. WELL TO SE.lC TANK~'~ ~ ' SEEPAGE Pli /~ ' WATER MAIN TO SEPTIC TANK l0 ft~ . SEEPAGE PIT [0 DRAIN FIELD [0 rte SEPTIC TANK, 25 ft. SEEPAGE PIT 100 fi,, Oe*,N F,ELD 50 ft. TO RIVER, LAKE. STREAM. CAST IRON INTO AND OUT OF SEPTIC TANK AND INTO CRIB CROSSING GAP OF ......... EXCAVATION 5 FEET INTO UNDISTURBED SOIL. 4 INCH DIAMETER CAST IRON SIPHON PIPES ON SEPTIC TANK AND SEEPAGE PIT FITTED WITH AIRTIGHT REMOVABLE CAPS. GRAVEL BACKFILL. CONFORM TO BOROUGH REGULATIONS REGARDING INSTALLATION. OR ( ~" LICENSED DESIGNER DIAGRAM OF SYSTEM 4" CAf:T iRON SIPUON · $~PTIC PIPC .lT. AIRTIGHT CRIB IMJt: / CAPS ~ . ,.,.~".=,: ....... - ........... . ...... n ..... CAS~ ],o, I.'::":'.q- .... 1.:;'::.. I · JaTo I;..:{'VL-: ~ :. ' ' ~RAVEL C J required Ml~n~ver line crosses (CRIB 4~ HINI~U~ A~0~'[ ~ATER: undcr dr~ve~'ay. IABLE) i ' -~ Grade; ;.'.per ICO' / or 1/4" p r foot ! except 10' prec~udin. HOUSE ! tank & fha. s~uld not exceed / 6~ per 100 on f)at J terrains. (,AST ]~rflfh .-~ /SEPTIC PI?/ 5' ~ ...... /~TAN~ / Ir;To u~- I I~1 4 ]r~cH ~ISTL~E~ ~ [ CAST IRO~ SIPHON PIPE I CERTIFY THAT IAM FAMILIAR WITH THE REQUIREMENTS OF GREATER ANCHORAGE AREA BOROUGH ORDINANCE NO. 2S-68 AND THAT THE ABOVE DATE __ ' ?' ? APPLICANT'S SIGNATURE ~' EATER ANCHNRAGE AREA BOROI, DEPARTMENT OF ENVIRONMENTAL QUALITY 3500 TUDOR ROAD ANCHORAGE, ALASKA 99502 CASE # Performed For Joh~ /~-mm~-o~ Date Performed ?/29/72 Lemal Description: Lot 10 Block 1 Subdivision ~lme Terrace This Form Reports Soils Log x Percolation Test qeoth Feet 5 6__ 7-- 8 9__ Soil Characteristics Well graded sand & gravel (~2~) Was Ground Water Encountered?.^ I~ Yes, At what Depth? Readinq Date Gross Time Net Time Depth to H20 Net Drool Percolation Rate Hinute Proposed Installation: Seeoaae Pit x Drain Field Deoth of Inlet Deoth To Bottom Of Pit Or Trench C~M!~ENTS· 125 f~ sqper~6'~;~t~. Data Certified By: Date · $850 Runarnuck Place ANCHORAGE, ALASKA 99502 ' 3~.9692 Mr.. Gary Seese 409 Taylor Str.eet Anahorage, Alaska PLEASE DETACH AND RETURN WITH YOUR REMITTANCE DATE June 21, 1978 NUMBER Hillside Drive. 5/23 tank lot 5/24 6/12 6/17 CHARGES AND CREDITS BALANCE BALANCE FORWARD ~ (2500 00) 8 hrs. Drott 40 move septic system & dig for new 8 hrs. labor 3 hrs..Drott 40 dig on basement B hrs';, labor 46 ft. sew. er pipe 1-22½ & 1-45 degree Septic. Tank 3½ hrs. truck pick up tank deliver &'move 850 to 3 hrs. 850 dozer push out hole 8 hrs. Drott 40 dig out fdtn. & driveway 8 hrs. labor 7 hrs. truck haul off 1 hr. truck move loader to lot 3 hrs. loader backfilling 5½ hrs. dozer baokfill 5 hrs. Dr-ott 40 complete sewer service 5 hrs.. labor 110 ft. sewer .pipe 60 ft. perforated pipe 4½ hrs..dozer backfill drain ditch & grade i id. washed rock Ziegler Excavating Company Thank You 680 00 180 00 255 00 67 50 ll7 59 695 00 136 50 150 O0 680 00 180 O0 27B O0 39 O0 165 00 247 50 425 00 112 50 222 20 75 00 202 50 !39 00 $2497~ 29 PAY LAST AMOUNT IN THIS COLUMN Ge Municipality of Anchorage �.". - On -Site Water and Wastewater Program (907)343-7904 5 'A F E T Y Certificate of On -Site Systems Approval . Parcel 1.D.015-243-34 Expiration Date: 1. GENERAL INFORMATION: Complete legal description ALPINE TERRACE; BLOCK 1 LOT 10 Location (site address) 11601 HILLSIDE DRIVE *ANCHORAGE, 99507 Current Property owner(s) KELLY POSTON Day phone 240-2319 Mailing address Real Estate Agent BETH SIMPSON Day phone 2. TYPE OF DWELLING: ® Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: 4 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Individual Well; ® Individual Individual Water Storage ❑ Holding Tank ❑ Community Class Well ❑ Community FJ Public Water System ❑ Public Sewer ❑ WaiverNariance request for: Distance: Received by: Date: COSA to be released to the engineer, unless otherwise requested by the engineer. COSA Fee $ Jed Waiver Fee ' $` ` Date of Payment o1.jILIbpbAo Date of Payment Receipt Number 0`53 Receipt Number COSA# Q�Gy1053- VVaiver# 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm: Garness Engineering Group, Ltd (GEG) Phone: 907-337-6179 Address: 3701 East Tudor Road Suite 101- Anchorage, Alaska 99507 Engineer's Printed Name: Jeffrey A. Garness Date: 7i�1 ilZ� In conducting this evaluation, GEG provided an engineering evaluation of the well and/or septic system in accordance with the guidelines and regulations established by the Municipality of Anchorage and industry practices. The reported results describe the condition of the system/s on the date/s of the evaluation. Separation distances were measured to readily identifiable features. Hidden defects or encroachments may exist that were not identified during the evaluation. The operational life of all wells and septic systems depend upon a variety of variables, including but not limited to, soil conditions, groundwater levels (that may fluctuate during the year), quality of construction (materials and workmanship), and the water usage of the family utilizing the system/s. These conditions can vary, and are outside the control of GEG. Satisfactory test results do not guarantee future performance of the system/s; therefore, GEG makes no warranty (express or implied) regarding the future performance of the well or septic system. GEG makes no representation whether an alternative well or septic system can be installed on the property in the event either of the current systems fail to perform adequately in the future. The content of this report is for the sole benefit of the person/party that retained GEG to perform the evaluation. Reliance upon the information provided in this report by any other person or party (including subsequent property purchasers) is not authorized, nor will it confer any legal right whatsoever. 6. DSD SIGNATURE 0 System #1 Approved for Y__ bedrooms System #2 Approved for Disapproved Conditional approval for bedrooms bedrooms, with the foll OF T*� .... . ....... ........... f A. G ness•: �a 49, • •, CE- •' � � 0os cG e -2�.)31:�b 4�Pa P� o f e s slo'°ao ��00000�� OF OIC -SITE WATER AND > silk R`V STERlS.m moi, n 9' �)tP1tP11� By: '�, tom/ �"' Original Certificate Date: The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 7. ATTACHMENTS: COSA Checklist Septic System Advisory Well Flow Advisory Nitrate Advisory '� fW Arsenic Advi4ory'�` Other c <.. ,. COSA Checklist Legal Description: ALPINE TERRACE; BLOCK 1, LOT 0 If more than 1 septic system on lot: COSA Checklist # of A. WELL DATA I *PER 1972 INSPECTION REPORT l ❑ Well log is filed with Onsite (or attached) Date drilled 1172(?) Total depth *47 ft Cased to LINK ft ❑ Sanitary seal is functioning correctly ❑ Wires are properly protected Casing height (above ground)12+ in. Date of flow test for COSA 6114/19 Static water level at beginning of test 12.3 ft. Comments B. TANK DATA Age of tank(s) NEW years Tank type/material HDPE Measured operating fluid level in septic tank - 0 Standpipes/foundation cleanout per record drawing Date of pumping N/A '.D. ABSORPTION FIELD DATA __ - Which system tested (date installed) 0 ALL standpipes present per record drawing Total measured depth from grade 8.3 ft (max) Measured depth to pipe invert from grade 3.1 ft (min) ❑ N/A — pressurized field Al Monitor tubes go to bottom of effective. If not, state depth into effective ❑® Code -required soil cover over field ❑ System presoaked (Required if vacant for greater than 30 days prior to date of test) Gallons introduced N/A gallons Comments/Deficiencies: COSA Checklist yellow sheet Parcel ID: 015-243-34 Structure served by this system Well production at time of test 6.2+ gpm Water storage tank volume N/A gallons Well disinfected for coliform test? ❑ Yes ❑ Nc [JQ16—oliform bacteria is Negative Nitrate 3,5 V mg/L ❑ Nitrate less than MRL (ND) Arsenic ug/L rsenic less than MRL (ND) Collected by GEG, LTD Date of Sample 2/5120 C. LIFT STATION ❑ Required maintenance Age of lift station Lift station mate Comme . Adequacy test date N/A Results ❑✓ Pass For 4 bedrooms Fluid depth prior to test - in Water added - gal New depth - in Elapsed time - min Final fluid depth - in Absorption rate - gpd Any rejuvenation treatment (past 12 months) If yes, enter date - E. SEPARATION DISTANCES From Private Well on Lot to: (Please enter distances if less than required or if community well) Septic Tank/Lift Station on Lot > 100' Yes if No Community Sewer Manhole/Cleanout > 100' ❑✓ Yes if No ft ✓❑ Yes if No Neighboring Tank > 100' 0 Yes if No ft Private Sewer/Septic Line > 25' Q Yes if No Absorption Field on Lot > 100' E] Yes if No ft Holding Tank > 100' Yes if No Neighboring Absorption Fields > 100' Animal Containment > 50' Yes if No 0 Yes if No ft Manure/Animal Excreta Storage > 100' Community Sewer Main > 75' 21 Yes if No ft R] Yes if No From Septic/Holding Tank on Lot to: (Please enter distances if less than required) Building Foundations > 10' ❑✓ Yes if No ft Surface Water > 100' ft ft ft ft M ❑✓ Yes if No ft Property Line > 5'✓❑ Yes if No ft Wells on Adjacent Lots: Absorption Field > 5' ✓❑ Yes if No ft Private Wells > 100'✓❑ Yes if No Water Main > 10' ✓❑ Yes if No ft Community Wells > 200'✓❑ Yes if No Water Service Line > 10' ❑✓ Yes if No ft If septic tank is under driveway comment below From Absorption Field on Lot to: (Please enter distances if less than required) Building Foundation > 10' ✓❑ Yes if No ft If absorption field is under driveway comment below Property Line > 10' 0 Yes if No ft Wells on Adjacent Lots: Water Main > 10' 0 Yes if No ft Private Wells > 100' 0 Yes if No Water Service Line > 10' 0 Yes if No ft Community Wells > 200' 0 Yes if No Surface Water > 100' ❑ Yes if No *80'+ ft F. ENGINEER'S COMMENTS *WR#OSV191059 G. ENGINEER'S CERTIFICATION l certify that 1 have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. COSA Checklist yellow sheet 0 9 �Oe fr A. Go ness.•• Q� (�E-79 � � Z11, :_- LD �Ao 0 �Dea or f e s"'00 #AECC884 ft ft ft ft c r: 49 49 THW .'.7 D O N� SHANE A. HOLT .' G �pe LS -6914 v O 44ap... �a v� essio�a� S 89 58' E 2 10. 00 ........... .. ,%, GRAVEL PARKING AREA S a{ ------------------------------- `G �I 00 00 �O 1 01.1 K CARP117 I O m: ry. 1 t '.3 E FPM���SE INOL ENO UD<LK 49.8 WELL � j 1v1 ASPHALT .^DRIVEWAY Al 89 58' E 2 10. 00 AS-BU/LTSURVEY 1 " =30' NO CORNERS SET THIS DATE SURVEY ORDLFREO SK LIAR !'.^.LDEN C iKELLER .h lLUfi:.fS I HEREBY CERTIFY THAT I HAVE PERFORMED A SURVEY OF THE FOLLOWING DESCRIBED PROPERTY LOT 10, BLOCK 1, ALPINE TERRACE SUB. ANCHORAGE RECORDING DISTRICT, ALASKA, AND THAT THE VISIBLE IMPROVEMENTS SITUATED THEREON ARE WITHIN THE INFORMATION HEREON IS FOR THE USE OF LENDING INSTITUTIONS SPECIFICALLY TO SHOW ANY THE PROPERTY LINES AND NO VISIBLE ENCROACHMENTS CONFLICTS BETWEEN EXISTING STRUCTURES AND PLATTED LOT LINES AND/OR EASEMENTS; AND IS EXIST OTHER THAN NOTED. NOT TO BE USED FOR POSITIONING ADDITIONAL STRUCTURES, IMPROVEMENTS, OR FENCELINES. DATED AT ANCHORAGE ALASKA THIS 6 TH DAY OF EASEMENTS OF RECORD, OTHER THAN THOSE APPEARING ON THE RECORD PLAT , ARE NOT SHOWN — HEREON ( UNLESS INDICATED) _AUGUST , 2019 NOTE: FENCELINES THAT MAY APPEAR ON THIS DRAWING ARE NOT TO BE USED TO DETERMNE PROPERTY LINES OR POSITION ADDITIONAL IMPROVEMENTS. HOLTLANDSURVEYING ANY PAVING SHOWN HEREON MAY BE APPROXIMATE DUE TO EXCESSIVE SNOW AND/OR ICE. 9309 GROVER DRIVE ANCHORAGE,AK 99507 12505, FE 162-40, 198-67 907223.8615 Parcel I.D. # MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH & HUMAN SERVICES Division of Environmental Services On-Site Services Section P.O. Box 196650 Anchorage, Alaska 99519-6650 (907) 343-4744 CERTIFICATE OF HEALTH AUTHORITY APPROVAL FOR A SINGLE FAMILLY DWELLING 015-243-34 1. GENERAL INFORMATION complete legal descriPtion ALPINE TERRACE SUBDIVISION: LOT 10. BLOCK 11 Location (site address or directions) 11601 HILLSIDE DRIVE ANCHORAGE AK, 99516 Property owner VICKI AND LELAND CliO Mailing address 11601 HILLSIDE DRIVE Lending agency. Mailing address Agent REAGAN RUSSEY - REAL'P¢ EXECUTIVES Address Day phone` (907) 545'1283 Day phone Day phone (907) 244-0225 Unless otherwise requested, HAA will be held for pickup. 2. NUMBER OF BEDROOMS: 4 3. TYPE OF WATER SUPPLY: Individual well xx Community well Public water NOTE: If community well system, provide written qonfirmation from State ADEC attest- ing to the legality and status of system. 4. TYPE OF WASTEWATER DISPOSAL: Individual on-site Holding Tank Community on-site Public sewer NOTE: xx If community wastewater system, provide written confirmation from State ADEC lng to th~ legality and status of system. 72q325 (Rev. 1191) Front MOA#21 Computer Version 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown bel°w, I verity that my investigation of this Health Authority Approval application shows that the on-site water supply and/or wastawater disposal system is safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verity that based on the information obtained from the Municipality of Anchorage files and from my investigatior{ and inspection, the on-site water supply and/or wastewater disposal system is in compliance with all Municipal and State codes, ordinances, and regulations in effect on the date of this !nspection. NameofFirm ALASKA WATER & WASTEWATER CONSULTANTS, INC. Phone (907)337-6179 Address 6901 DEBARR ROAD, SUITE 2B ANCHORAGE. ALASKA 99504 :. / / Date Engineer's signature ALASKA WATER & WASTEWATER CONSULTANTS, !NC. SHALL BE PAID $250:00 AT, OR PRIOR TO, CLOSING FOR THE ENGINEERING SERVICES PROVIDED. 6. DHHS SIGNATURE X Approved for 4 Disapproved Conditional approval for bedrooms bedrooms, with the following stipulations: Additional Comments Date The Municipality of Anchorage Department of Health and Human Services (DHHS) issues Health Authority Approval Certificates based only upon the representations given in paragraph 5 above by an independent professional engineer registered in the State of Alaska. The DHHS does this as a courtesy to purchasers of homes and their lending institutions in order to satisty certain federal and state requirements. Employees of DHHS do not conduct inspections or analyze data before a certificate is isSUed. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 72-025 (Rev. 1/91) Back MOA 1/21 Computer Version Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES Environmental Services Division 825 "L" Street, Rm 502 Anchorage, Alaska 99501 (907) 343-4744 Health Authority Approval Checklist Legal Description: ALPINE TERRACE; LOT 10, BLOCK 1 Parcel I.D.: 015-245-34 A. WELL DATA Well Type~ PRIVATE If A, B, or C, attach ADEC letter. ADEC water system number LOg present (Y/N) NO Date completed 1972 Total depth 47' (PER 1972 AS-BUILT) Cased to ¢0% Casing height (above ground) N/A 2`3" Sanitary seal (Y/N) YES Wires pmperiy protected (Y/N) YES Date of test Static Water level Well production FROM WELL LOG AT INSPECTION 10/29/99 25' g.p.m. 2.87 g.p.m. WATER SAMPLE RESULTS: Coliform ~ Date of sample: `3/8/2000 Nitrate _~, ~'~ /"~C~ /.~., Other bacteria. Collected by: A.W.W.C., INC. B. SEPTIC/HOLDING TANK DATA Date installed 4-/78 Tank size Foundation cleanout (Y/N). Date of Pumping 10/29/99 C. ABSORPTION FIELD DATA Date installed 8/72 YES Depression (y/N); NO Pumper NORTHLAND PUMPING 1500 Number of Compartments 2 Cleanouts (y/N) YES High water alarm (Y/N) N/A Soil rating (g.p.d./ff2 or fl2/bdrm) 125 * WATER DID NOT BACK UP J INTO THE SEPTIC TANK. NOJ CLEAN-OUTS IN TRENCHES. SEE A1TACHED LETTER. SHALLOW System type DRAINFIELB Length 11.3' .Width 4' Gravel thickness below pipe 0.5' Total depth 6.7' BGL Effective absorption area Date of adequacy test 10/29/99 Results (Pass/Fail) PASS For Fluid depth in absorption field before test (in.); 0 Immediately after 644- Fluid depth 0 (ins) Minutes later: 95 Absorption rate = 452 SQ Fl' Monitoring Tube present (Y/N) YES Depression over field (Y/N) NO 4 Bedrooms gal. water added (in.): 19.5' 600+ Peroxide treatment (past 12 months) (Y/N) NONE KNOWN If yes, give date 72-026 (Rev. 3196) ComputerVerslon D. LIFT STATION Date installed ~ Manhole/Access [Y/N) ~P~m~on" level at* High water alarm level..e~ .*Datum "Pump off' level at* E. SEPARATION DISTANCES SEPARATION DISTANCES FROM WELL ON LOT TO: Septic/holding tank on lot Absorption field on lot Public sewer main Sewer/septic service line 100'+ 100'+ N/A 25'+ On adjacent lots 100'+ On adjacent lots 100'+ Public sewer manhole/cleanout Lift station SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO: Foundation 7' TO CO Property line 5'+ Water main/service line 10'+ Surface water/drainage *85' SEPARATION DISTANCES FROM ABSORPTION FIELD ON LOT TO: Property line 10% Building foundation 10'+ *65' N/A **36' PER ORIGINAL INSPECTION. UNKNOWN AFTER UPGRADE. Absorption field Wells on adjacent lots * SEE WAIVER LETTER (AUGUST 26, 1995) Surface water Curtain drain F. ENGINEER'S/~I I certify that I/ha~ of Munic/pal/rec~ with MOA I~AA Signature ~ Engineer's Naml Date Water main/service line Driveway, parking/vehicle storage area Wells on adjacent lots 100'+ ~ field inspections and review ,e systems are in conformance ~t on this date. *'51'+ JEFFREY A. GARNESS 100'+ 10'+ 10'+ HAA Fee $ Date of Payment Receipt Number 72-026 (Rev. 3/96)* Computer Version Waiver Fee $ Date of Payment Receipt Number Alaska Water & Wastewat :r Consultants, Inc. 6901 Debarr Road, Suite 2-B - Am orage ~ Alaska 99504 Phone (907) 337.6179 ~ Fan 907) 338-3246 Consulting Engi~ ers November 9, 1999 Municipality of Anchorage Department of Health & Human Services Division of Environmental Services On-Site Services Section P.O. Box 196650 Anchorage, Alaska 99519-6650 Subject: Septic System Test at Lot 10, Bk 1, Alpine ierrace S/D. To whom it may concern: Attached is the HAA "brown sheet" for the subject pro ,erty. It should be noted that there are no clean-outs in the trenches and only one monitoring tul ':. The effective depth of the system is 6 inches per the 1972 inspection report. Water was intr ~duced into the monitoring tube (the only pipe available) at a rate of 2.87 gpm for 231 minutes. 'l'his caused the liquid level to rise in the MT to 19.5 inches. It is assumed that the majority of i!~e rise was due to a build-up of hydraulic head in the monitoring tube and that the liquid level ':~'~ the trenches was not 19.5 inches. The monitoring tube was dry 95 minutes after we stopl d introducing water. If you have any questions, please call us 337-6179. h.s. MUNICIPALITY Of ANCHORAGE DEPARTMENT OF HEALTH & HUMAN SERVICES Division of Environmental Services On-Site Services Section P.O. Box 196650 Anchorage, Alaska 99519-6660 343-4744 Parcel I.D. # CERTIFICATE OF HEALTH AUTHORITY APPROVAL FOR A SINGLE FAMILY DWELLING 015-243'-34; 1. GENERAL INFORMATION Complete legal description Lot 10; Block 1; Alpine Terrace Subdivision Location (site address or directions) Property owner Mailing address Lending agency Mailin. g address Agent Address 11601 Hillside Drive Anchoraqe~ AK Vicki & Leland Cho Dayph0ne 345-1283 11601 Hillside Drive Anchoraqe, AK 99516 Day phone Reaqan Russey/~k--~l~i-k~t . Day phone 244-0225 Unless otherwise requested, HAA will be held for pickup. 4 NUMBER OF BEDROOMS: TYPE OF WATER SUPPLY: ×× Individual well Community well Public water NOTE: If community well system, provide written confirmation from State ADEC attest- ing to the legality and status of system. TYPE OF WASTEWATER DISPOSAL.- Individual on-site Holding tank Community on-site Public sewer NOTE: XX If community wastewater system, provide written confirmation from State ADEC attesting to the legality and status of system. 72-025(Ray. I/91) Front MOA~21 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation of this Health Authority Approval application shows that the on-site water supply and/or wastewater disposal system is safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is in compliance with all Municipal and State codes, ordinances, and regulations in effect~stJ~~ (~c~is inspection. Name of Firm W~$fm~v; , Cnn~n~t~rits; /n~ Phone Address ~0~[ ~r/~FSuit! 2B ncnee seignature Date Wastewater Consultants, Inc. Shall be PAID ,$ IlOO~'- or prior to, closing for tho Engineerin~ So.ices Provided. 6. DHHS SIGNATURE X A?proved for Disapproved. Conditional approval for bedrooms. bedrooms, with the following stipulations: Additional Comments Date ///-/¢ -// The MuniciPality of Anchorage Department of Health and Human Services (DHt4S) issues Health Authority Approval Certificates based only upon the representations given in paragraph 5 above by an independent professional engineer registered in the State of Alaska. The DHHS does this as a courtesy to pumhasers of homes and their lending institutions in order to satisfy certain federal and state requirements. Employees of DHHS do not conduct inspections or analyze data before a certificate is issued. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work, Municipality of Anchorage NOV 0 DEPARTMENT OF HEALTH & HUMAN SERVlC,~,_,. Environmental Services Division ENViRONM~-N'~A~ S~kv,L.~.S Di 825 L Street, Room 502 · Anchorage, Alaska 99501 · (907) 343-4744 Health Authority Approval Checklist Legal Description: ~ PlNF TFRRA~F'; I OT 10. BLOCK 1 Parcel I.D.: -O15-243-34 A. WELL DATA Well type PRIVATF' If A, B, or C, attach ADEC letter. ADEC water system number N/A Log present (Y/N) NO Date completed Total depth ~-7' (PER 1972 AS-BUiLT) Cased to 1972 Casing height (above ground) 25" Sanitary seal (Y/N) YES Wires properly protected (Y/N) YES Date of test Static water level Well production WATER SAMPLE RESULTS: FROM WELL LOG AT INSPECTION J g.p.m. 2 87 g.p.m. Coliform ~3 Nitrate 3.05 mq/L Other bacteria Date of sample: 10/29/99 Collected by: A.W.W.C., INC. B. SEPTIC/HOLDING TANK DATA Date installed 4/7~ Tank size Foundation cleanout (Y/N) YES 1500 Number of Compartments 2 Cleanouts (Y/N).__ Depression (Y/N) NO High water alarm (Y/N) N/A YES Date of Pumping 10/29/99 C. ABSORPTION FIELD DATA Date installed Fi/7? Pumper NORTHLAND I * WATER DID NOT BACK UP INTO THE SEPTIC TANK. J NO CLEAN-OUTS IN TRENCHES. 1 Soil rating (g.p.d./ft2 or ff2/bdrm) 1 ?5 System type SHALLOW DRAINFIELD Length 11 ~' Width 4' Gravel thickness below pipe R.5' Total depth 6.7' BGL Effective absorption area 452 SO FT Monitoring Tube present (y/N) YFS Depression over field (y/N) NO Date of adequacy test 10/29/99 Results (Pass/Fail) PASS For bedrooms Fluid depth in absorption field before test (in.); Fluid depth 0 (ins) Minutes later: 0 Immediately after 64-~ga1. water added (in.): 19.5' 95 Absorption rate = 600+ ~.p.d. Peroxide treatment (past 12 months) (y/N) NONE KNnWN If yes, give date 72-026 (Rev. 3/96)* D. LIFT STATION ., _ ~ Date installed ~ ..~ Manhole/Access (Y/N). ~t* "Pump off" level at* E. SEPARATION DISTANCES SEPARATION DISTANCES FROM WELL ON LOT TO: Septic/holding tank on lot 100'+ On adjacent lots Absorption field on lot 100'+ On adjacent lots Public sewer main N/A Public sewer manhole/cleanout Sewer/septic service line 25'+ Lift station SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOTTO: Foundation 7' TO CO Property line 10'+ Absorption field Water main/service line 25'+ Surface water/drainage ~85' Wells on adjacent lots SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOTTO: 10'+ 50'+ Building foundation Property line Surface water Curtain drain 100'+ 100'+ N/^ N/A *'51 '+ 100'+ 25'+ Water main/service line 30'+ TO CARPORT * 65' Driveway, parking/vehicle storage area 100'+ '5' - 10' Wells on adjacent lots F. ENGINEER'S CERTIFICATION If A. GARNESS Date HAA Fee $. Date of Payment Receipt Number 72-026 (Rev, 3/96)* Waiver Fee $ Date of Payment Receipt Number Alaska Water & Wastewater Consultants, Inc. 6901 Debarr Road, Suite 2-B - Anchorage - Alaska 99504 Phone (907) 337-6179 ~ Fax (907) 338-3246 Consulting Engineers November 9, 1999 Municipality of Anchorage Department of Health & Human Services Division of Environmental Services On-Site Services Section P.O. Box 196650 Anchorage, Alaska 99519-6650 Subject: Septic System Test at Lot 10, Bk 1, Alpine Terrace S/D. To whom it may concern: Attached is the HAA "brown sheet" for the subject property. It should be noted that there are no clean-outs in the trenches and only one monitoring tube. The effective depth of the system is 6 inches per the 1972 inspection report. Water was introduced into the monitoring tube (the only pipe available) at a rate of 2.87 gpm for 231 minutes. This caused the liquid level to rise in the MT to 19.5 inches. It is assumed that the majority of the rise was due to a build-up of hydraulic head in the monitoring tube and that the liquid level in the trenches was not 19.5 inches. The monitoring tube was dry 95 minutes a~er we stopped introducing water. If you have any questions, please call us !: 337-6179. S' ely,l~ me ,P.E., .S. NOV 09 1999 MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH & HUMAN SERVICES Division of Environmental Services On-Site Services Section P.O. Box 196650 Anchorage, Alaska 99519-6650 343-4744 Parcel I.D. # CERTIFICATE OF HEALTH AUTHORITY APPROVAL FOR A SINGLE FAMILY DWELLING GENERAL INFORMATION Completelegaldescription _Z.o'/-(0/ ~/c,c/~ .~'~ ,,4/~,,,~ 7-'¢r,",~¢e -~/~ Location (site address or directions) II ~'o ! /-/-~ lis/c.~'e ~r't u ~. Property owner Mailing address Lending agency Mailing address Day phone '~.5'7 - Day phone Agent .~,.~jc~,o d'~z~/~, b~l( ) "~O01 R¢-.~I I~..s~/"~_ Address ~gO0 P~/~I; Unless otherwise requested, HAA will be held for pickup. NUMBER OF BEDROOMS: Day phone '~.'7~' - ~ / TYPE OF WATER SUPPLY: Individual well Community well Public water NOTE: If community well system, provide written confirmation from State ADEC attest- ing to the legality and status of system. TYPE OF WASTEWATER DISPOSAL: Individual on-site Holding tank Community on-site Public sewer NOTE: If community wastewater system, provide written confirmation from State ADEC attesting to the legality and status of system. 72-025 (Rev. 1/91) Front MOA #21 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation of this Health Authority Approval application shows that the on-site water supply and/or wastewater disposal system is safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is in compliance with all Municipal and State codes, ordinances, and regulations in effect on the date of this inspection, u./~,~,,,r Phone Name of Firm Address engineer's signature DHHS SIGNATURE /~, Approved for Date ~7-~, bedrooms. Disapproved. Conditional approval for bedrooms, with the following stipulations: Additional Comments Date ~ -2 ~- ~'~ The Municipality of Anchorage Department of Health and Human Services (DHHS) issues Health Authority Approval Certificates based only upon the representations given in paragraph 5 above by an independent professional engineer registered in the State of Alaska. The DHHS does this as a courtesy to purchasers of homes and their lending institutions in order to satisfy certain federal and state requirements. Employees of DHHS do not conduct inspections or analyze data before a certificate is issued. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 72-O25 (Rev. 1/91) Back MOA#21 Municipality of Anchorage Department of Health and Human Services HEALTH AUTHORITY APPROVAL CHECKLIST Legal Description: LoT I0 1~_1< [, r~L?//,l{ 7£/~,~ACE Parcel I.D. A. Well Data Well type Log present (Y/N) Total depth Sanitary seal (Y/N) Date of test Static water level Well flow Pump level1 ¥ If A, B, or C, attach ADEC letter. ADEC water system number Date completed l 'J-/2 Driller I Cased to ~'~ H '7 Casing height Wires properly protected (Y/N) Y FROM WELL LOG AT INSPECTION MUNiCIPALiTY OF ANCHORAGE Et,,W'IRONMENTAL SERVICES DIVISION 1995 g.p.m. SEPARATION DISTANCES FROM WELL TO: Septic/holding tank on lot Absorption field on lot Public sewer main N. Sewer service line 12 o ; On adjacent lots '>./o o ; On adjacent lots ~. /o o Public sewer manhole/cleanout N./}, Petroleum tank NONE WATER SAMPLE RESULTS: Coliform 0 ¢o! //Or2 r,', ~ Date of sample: 7J-//~q :~ Nitrate I.-II ~,j~' /"-~ Other bacteria Collected by: ~-/_,4 T'rO? TECfl B. SEPTIC/HOLDING TANK DATA Date installed Cleanouts (Y/N) High water alarm (Y/N) Date of pumping Foundation cleanout (Y/N) Tank size I $ o O G 4z. Compartments 2 7' Depression (Y/N) Alarm tested (Y/N) I'q,~ · Pumper / N SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK TO: Well(s) on lot 12 o On adjacent lots To property line c/5' ' Absorption field Surfacewater/drainage ~ ~'5" (_£~(~ Foundation '7 Water main/service line 72-026 (3/93)* Front CONTINUED ON BACK PAGE C. LIFT STATION Date installed Manufacturer Size in gallons Vent (Y/N) "Pump on" level at High water alarm level Meets MOA electrical codes (Y/N) Manhole/Access (Y/N) "Pump off" Level at Cycles tested SEPARATION DISTANCE FROM LIFT STATION TO: Well on lot On adjacent lots Surface water D. ABSORPTION FIELD DATA Date installed ~/72 Length I 13 ~ Width Total absorption area ~.52_ Date of adequacy test Water level in absorption field before test Peroxide treatment (past 12 months) (Y/N) Soil rating (GPD/FF) Gravel thickness Cleanout present (Y/N) Results (pass/fail) ~',~5 $ ~'PD/F~~ System type Total depth Depression over field (Y/N) for After test If yes, give date N o N~- k'No Bedrooms SEPARATION DISTANCE FROM ABSORPTION FIELD TO: Well on lot I oo' On adjacent lots '~/oo ' Property line I To building foundation [ '7, To existing or abandoned system on lot On adjacent lots ~>/oo ' Cutbank N. A · water maiwsewi~ line Sudace water ~ d3" ~ c~F ~~ Driveway, parkin~ehicle storage area Cu~aindrain 0~1~ h'~ ~ ~ ~,'~ ~ ~o' o~ ~;~ ~ - E. ENGINEER'S CERTIFICATION I certify that I have checked, verified, or conformed to all MOA and HAA guidelines in effect on the date of this inspection. Signature J~ ~ ~ - * Waiver Fee $ HAA Fee $ /~70) o o Date of Payment ~-~0- ~)-% Receipt Number c~4c~ ~ Date of Payment Receipt Number 72-026 (3/93)* Back Munk ality of Anch ra e Department of Health and Human Services Tom Fink, 825 "L" Street Mayor P.O, Box 196650 Anchorage, Alaska 99519-6650 343-4744 August 26, 1993 Ted Moore, P.E. Flattop Technical Services 14530 Echo Street Anchorage, Alaska 99516 Subject: Waiver Request for Lot 10 Block 1 Alpine Terrace S/D Waiver Request #WR930043, PID #015-243-34, HA930412 Dear Mr. Moore: Your request for a waiver(s) of the required 100 foot horizontal separation of a septic system to the surface water has been approved. The approved separation distance(s) are 65 feet. This waiver approval applies to the existing septic system to surface water separation only. Any future upgrade to the septic system will require all separation distances be met or another approval from this department. Should the operation of the subject wastewater disposal system cause any contamination or degradation of the subject surface water, this waiver will become void. Sincerely, Daniel J. Roth Civil Engineer On-site Services anager On-site Services ljm:#5 MUNICIPALITY OF ANCHORAGL Department of Health and Human Services On-site Services Section Waiver Review Worksheet WR9 WR930043 PID# 015-243-34 HA# HA930412 Permit 9 Date Received: July 20, 1993 Legal Description: Lot 10 Block 1 Alpine Terrace Subdivision Engineer: Ted Moore, P.E., Flattop Technical Services 14530 Echo street Anchoraqe, Alaska 99516 Applicant: Randy Taylor Waiver Requested: Drainfield to surface water of 65 feet (to two road ditches) Criteria: 1. Geology: Points: A. Water Table B. Soil Sorption C. Permeability D. Water Table Gradient E. Horizontal Separation TOTAL: 2. Special Conditions: 3. Other: Waiver is Granted: ~ Waiver is NOT Granted: List Conditions or Reasons for above: Rec #: 24948/9077 BY' ~~of Reviewer Amount: $ 590.00 Date Paid: July 20, 1993 J/VhIV~R /~E~ u£~T 'E CIVIL & ENVIRONMENTAL ENGINEERING * ENERGY CONSERVATION & ANALYSIS THEODORE F. MOORE, P.E. ~:Tul~"...,1~, 1993 14530 ECHO ST. PH: (907) 345-1355 ANCHORAGE, ALASKA 99516 M.O.A. DHHS P.O. Box 19-6650 Anchorage, AK 99519 Dear Sirs: By means of this letter we are requesting issuance of a waiver allowing the closest portion of the existing wastewater disposal system serving the residence on Lot 10, Block 1, Alpine Terrace S/D to be as close as 65 feet from two roadside ditches, both of which still contain small amounts of surface water. A site plan and other relevant backup documents are enclosed to assist you in your review of this waiver request. According to the as-built inspection report on file at DHHS the original wastewater disposal system was installed in September of 1972, and consisted of a 1000 gallon septic tank followed by a soil absorption bed with an effective absorption area of 452 square feet. An inspection report dated April, 1978 documents the fact that a 1500 gallon septic tank had been installed, and approved the system for 4 bedrooms. The system was tested and reapproved for 4 bedrooms in June of 1990. On July 7, 1993 we conducted adequacy tests of the water supply and wastewater disposal systems serving this lot. Since the residence had been unoccupied for a couple of weeks prior to our adequacy test, we arranged for a water truck to pre-soak the system with 3000 gallons of water added through the second compartment of the septic tank. The monitor tube in the drainfleld was dry at the start of the test, and while the presoak water was being added at a rapid rate the fluid level in the monitor tube rose a maximum of 19.5 inches. Thirty f~ve minutes later, after the septic tank had been pumped, the monitor tube was again dry. We then ran another 724 gallons of water from the well directly into the monitor tube. This caused a maximum fluid buildup of 30 inches in the monitor tube as the water was being added, but the monitor tube was again dry 1.5 hours after the water had been added. (Since the monitor tube is not plumbed directly into the horizontal distribution pipe network, we believe that the maximum fluid depth measured in the monitor tube is not reflective of the actual fluid depth in the field, but rather was a result of the attenuated rate of flow through the sewer gravel from the monitor tube into the distribution pipe network.) Based on the demonstrated surge capacity being over 6 times the design daily demand of a 4 bedroom residence, we concluded on the basis of our test data that the drainfield continues to function adequately for a 4 bedroom residence. We conducted a previous adequacy test of this system in June of 1990 in conjunction with an earlier sale. At that time the presence of a small amount of water in the roadside ditches was also noted, but after several discussions with DHHS, it was decided that a separation distance waiver to surface water was not necessary. This decision was based on the assumption that the small flow of water observed in the roadside ditch would probably not be present during most of the year. The fact that a small flow of surface water was again found during July of this year means that it now is necessary to go through a formal waiver process. As was the case at the time of the 1990 adequacy test, the discharge pipe from the sub-surface driveway drain which passes close to the drainfield was dry at the time of our test. Because of it's relatively shallow burial depth relative to the drainfield, there does not appear to be cause for concern over this drain collecting and transporting effluent from the drainfield. Based on visual observation, we estimated the flow of surface water to be approximately 5 gpm, both in the westward trending ditch parallel to the north property line and in the the north sloping roadside ditch along the east side of Hillside Drive. Both ditches are heavily overgrown, and the presence of any water is not apparent unless one walks in the immediate area. In our opinion, the presence of water in these ditches is attributable to a shallow water table perched on a relatively impermeable substratum. Surface water is present in these locations only because deep ditches were cut to improve the runoff characteristics along Hillside Drive and the driveway accessing Lot 3 of Carr S/D. The ditch depth is sufficient that the bottoms of the ditches penetrate into the top of the groundwater table. On July 14, 1993 we measured the elevation of the bottom of the monitor tube in the drainfield to be 12.4 feet higher than the water level in the ditch midway along the north property line. These measurements indicate that there is more than the required 4 foot vertical separation between the bottom of the soil absorption system and groundwater. The exact underground configuration of the soil absorption system serving this lot and the discharge pipe from the subsurface driveway drain is unknown. The configuration plotted on the site plan is based on the locations of standpipes coupled with information from DHHS files indicating the lengths of the various laterals and that the closest drainfield lateral is 100 feet from the well. The 65' separation distance to the water in the ditch along the north property line is a slightly conservative figure based on the locations of the system components as plotted on the site plan. In the event that effluent were to overflow from one of the standpipes as a result of the system being unable to function adequately, the flow path to surface water would be over 100 feet due to the northwesterly trending slope of the topography. The potential of effluent daylighting in this manner is negligible, because it would back up into the residence before this could happen, forcing the property owner to repair the problem. In consideration of the above information, it is our opinion that the requested waiver can be safely granted without concern as to the potential for contamination of the surface water in the roadside ditches by effluent originating in this wastewater disposal system. Please give me a call if you have further questions on this analysis. CC.' Dr. Randy Taylor Susan Campbell, 2001 Real Estate Sincerely, Ted Moore, P.E. DITCId LoT :~ C/t~R SUB. ~ CLE~N OUt~ Su~ - ~v~F~C~ I o~a '~-.,. 1 1 q BDR~ .. 1 HouSE C~. ~ELL ~ I 2.10' UT IL IT~t LoT ~ BI_~ I ~L~INE ?£RRACE Lot ct BLK I AL PtNE TERR4c~,latt0P ~- Technical Services e.-- ..s~,r,~.. "' .... ~:' 14530 Echo Street ~,sT~-~ /~r]chorage, -Alaska 99518 LOT lO, BLK 1, ALPINE TERRACE SITE PLAN --cCFJL£: I"-- .5'0 ' DATE: -7 J q S NOTE: THIs Is NoT ~u~Vs: YED PLAT. ALL LOCATIoN~ ARE APPI~ox ~MATE. A MUNICIPALITY OF ANCHORAGE Department of Health & Human Services DIVISION OF ENVIRONMENTAL SERVICES 343-4744 CERTIFICATE OF INSPECTION FOR HEALTH AUTHORITY APPROVAL OF ON-SITE SEWER AND WATER FACILITY FOR SINGLE FAMILY DWELLING 1. GENERAL INFORMATION (Must be completed prior to submittal) (a) Legal Description (include lot, block, subdivision, section, township, range) Location (address or directions) II~ool ~ lL~ $1o~ DR (b) Property owner Mailing Address Telephone'(home) 3qS'-3zl.¢ Business (c) Lending Institution Mailing Address Telephone (d) Real Estate Company and Agent Address J2~O0 CoRDOCfJ qqs-o Telephone 27/~- 2-7(,/ (e) Mail the HAA to the following address: (or check here ~, if hold for pick up.) List contact person and day phone number below: 2. TYPE OF RESIDENCE Single-Family~ Number of bedrooms ~ 3. WATER SUPPLY Individual Well 15¢ Community [] Public [] Note: If community well system, must have written confirmation from the Staie Department of Environmental Conservation attesting to th legality and status. 4. SEWAGE DISPOSAL On-site J:~ Public [] Community [] Holding Tank [] Note: If community well system, must have written confirmation from the State Department of Environmental Conservation attesting to the legality and status. 72-025 (Rev. 7/88) Page 1 of 2 5. ENGINEERING FIRM PROVIDING INSPECTIONS, TESTS, FILE SEARCH, DATA AND INFORMATION As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation of this Health Authority Approval shows that the on-site water supply and/or wastewater disposal system is safe, functional .and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is in compliance with all Municipal and State codes, ordinances, and regulations in effect on the date of this inspection. Name of Firm ~'Z. Pr TTO P "T'E ¢'/~ · ~,"C$ Telephone Address 1~ 5 3o ECl-fo ST, /~,~cl~ . r~l< Engineer's Seal 6. DHHS APPROVAL Approved for/~(/¢-~,~oedrooms by Approved ~ Disapproved Conditional Terms of Conditional Approval The Municipality of Anchorage Department of Health and Human Services (DHHS) issues Health Authority Approval cerificated based only upon the representations given in paragraph ,5 above by an independent professional engineer registered in the State of Alaska. The DHHS does this as a courtesy to purchasers of homes and their lending institutions in order to satisfy certain federal and state requirements. Employees of DHHS do not conduct inspections or analyze data before a certificate is issued. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 72-025 (Rev. 7/88) Back Page 2 of 2 ~ MUNICIPALITY Of ANCHORAGE (MOA) MUNIC~ALII~.~I. fO Health Authority Approval (HAA) RAGE CHECKLIST. FEBRUARY 1984 ENVIRONMENt. s DIVISION N 4 1990 R£C£1V D A. WELL DATA Well Classification P[~ I V~TE 343-4744 Legal Description: L Well Log Present (Y/N) No Date Completed 1972 Total Depth ¥7' Cased to ~ ~'~ Depth of Grouting Static Water Level ,~ $ / Casing Height Above Ground ,~, I" Electrical Wiring in Conduit (Y/N) /O Tgli' RAc E' SEPARATION DISTANCES FROM WELL: To Septic/Holding Tank on Lot J ~O To Nearest Edge of Absorption Field on Lot To Nearest Public Sewer Line ~ 100' To Nearest Sewer Service Line on Lot ; On Adjoining Lots '~/00 1 O0 ' ; On Adjoining Lots ~' To Nearest Public Sewer Cleanout/Manhole 12o Water Sample Collected by ~'/. ltl-roe 'T'£cd. ~vc~' ; Date WaterSampleTestResults ~/tT~$FFtCTORY - 0 CoztFoR~ ///oo Comments Dc,RiNG ~./El.c. FLOC,,./ TEST O~ G/z't/clO ~TEAb¥ B. SEPTIC/HOLDING TANK DATA Date Installed Z/'/7~ Size~No. of Compartments '2_ Standpipes (Y/N) yEg Air-tight Caps (Y/N) ¥£$ Foundation Cleanout (Y/N) Depression over Tank (Y/N) Pumping/Maintenance Contact on File (Y/N) Holding Tank High-Water Alarm (Y/N) N/A ! too '7 /00 / 18 '71 G,4l I.E.V'E& To Date Last Pumped Temporary Holding Tank Permit (Y/N) SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK: To Water-Supply Well [ 2. ID To Building Foundation -~. 2 F'RoPt To Property Line ~JS' ~ To Disposal Field ~ ~ ~ To Water Main/Service Line To Stream, Pond, Lake or Major Drainage Course Comments 'TANK ~v'H~C~ W'~r~ C_AR,~ Y cNG ;:; ~EPTIC 014 THE I)t~T6 oF THE "['EST. 72-026 (Rev. 7/88) Front ~)iT¢~ c~o NORTH oF THE' "T'ms ~$ P'~oc3,~Bz ¥ bRY Mo~T oF THE Page 1 of 2 '727 ' Sanitary Seal on Casing (Y/N) Depression Around Wellhead (Y/N) Pump Set At Yield ~' 7.g GPM If A, B, C, D.E.C. Approved (Y/N) C. ABSORPTION FIELD DATA Soils Rating in Absorption Strata Date Installed I~/'~ 2 Width of Field z~ ' ! Square Feet of Absortion Area Depression over Field (Y/N) No Results of Last Adequacy Test SEPARATION DISTANCE FROM ABSORPTION FIELD: To Water-Supply Well /OO 17.5- To Building Foundation Lot HONE' To Water Main/Service Line '/BD$1~ Type of System Design DRAt Length of Field I I~ I Depth of Field Gravel Bed Thickness {o Statndpipes Present (Y/N) Date of Last Adequacy Test To Stream, Pond, Lake, or Major Drainage Course ~ /oo ' To Driveway, Parking Area, or Vehicle Storage Area (¢ ! ' Comments * DdR~NG ~bE4:)uAc¥ TE57/ 5Y'~T6/'4 To Property Line ~O / To Existing or Abandoned System on ; On Adjoining Lots '~/Oo ' To Cutback (if present) ( 5~£ Coe~m Date Installed size in Gallons "Pump on" Level at High water Alarm Level at Tested for Dimensions Manhole/Access (Y/N) "Pump Off" Level at Vent (Y/N) Pumping Cycles during Adequacy Test. Meets MOA Electrical Codes (Y/N) I certify that I have checked, verified, or conformed to all MOA and HAA g~~fect ~ ....... ~2 ~ inspection. signe ~5' '::': ':' :¢ ~5.~ Engineer's Seal Date ~n ~o~o~ ~. ,4o0~ . Receipt No. ~- Date of Payment Amount: $ Receipt No. Waiver Fee: $ Date of Payment 72-026 (Rev. 7/88) Back Page 2 of 2 ~INICIPALITY OF ANCHORAGE -- '~EPARTMENT _. HEALTH AND ENVIRONMENTAL .ROTECTION 825 L Street, Anchoraa~, Alaska 99501 264-4720 Date Received: April 19, 1978 #1: Time i;';~ ~ #2: Time #3: Time Date Date Date Insp Insp REQUEST FOR APPROVAL OF INDIVIDUAL SEWER AND WATER FACILITIES 1. Lending Institution Request: Mailing Address: 2. Property Owner: James H. Patterson Mailing Address: 3500 La Touche 99504 Phone: Phone: 274-2252 3. Legal Description: Lot 10 Block 1 Alpine Terrace Subdivision 4: Single Family Residence: (~ Multiple Family Residence: ( ) Number of Bedrooms: Four Number of Bedrooms: 5. Well System: Individual well (~ Community/Public System ( ) Permit # Depth of Well C o n s t r u c t i o n__ __ Well Log on File ( ) Bacterial Analysis ~ Sewage Disposal System: On-site System Public Utility Permit # Installed 1972 Installer Septic Tank Size tOOQ Manufacturer ~C.~-. ~ Absorption Are~~ /~ Soils Rate ~2- Material 7. Distances: Well to Septic Tank to Absorption Area to Sewer Line Nearest Lot line Absorption Area to Nearest Lot Line Page Two ' Department of Health'and Environmental Protection Request for Approval of Individual Sewer and Water Facilities Legal Description: Lot 10 Block 1 Alpine Terrace Subdivision Comments: Affadavit Attached: ( ) Approved: ~ Disapproved: Letter Attached: ( ) Date: Date: Department Worksheet: MUNICIPALITY OF ANCHORAGE //~~""i~'~ 825 L Street, Anchorage, Alaska 99501 ~~equest for Approval of Individual Sewer and Water Facilities Property Owner: James ![. Patters~ TM B I~.~ouco_e ;.rchora~e: ;lc. 99501,~ Mailing Address: 3500 m , Phone: 27A-72%? I Name of Buyer: Mailing Address: Phone: I.endJ_ng Institution: Mailing Address: Phone: Realtor/Agent: Mailing Address: Phone: 5. Legal Description: Lot 10 ]tloe] 1 M?:~e Terr.~ee Street Location: /'l~!~lde [)rivc Single Family Residence: (,~ Multiple Family Residence: ( ) 3 present Number of Bedrooms: p~3~Qse tc~d 1 Number of Bedrooms: Water Supply:. *Individual Well ( ) If Individual Well, well depth If Community System, name of system Public/Community System ( ) Sewage Disposal System: *~n-site System (]:~) If On-site System, date of installation: Public System ( ) *NOTE: A well log is required on ALL wells drilled since 6/75. ** If on-site sewer system is over two(2) years old, an adequacy test is required by this department. A fee of $25.00 must accompany each request before processing 'can be initiated. 3/77 Apr±l 24, 1978 R&M No. 851519 Mr, James Patterson 3500 LaTouche, Suite 250 ' Anchorage, Alaska 99504 Subject: Adequacy Test on Existing Sanitary Sewer System; Lot 10, Block 1, Alpine Terrace Subdivision, Anchorage, Alaska Dear Mr. Patterson: At your request of April 21, 1978, we conducted a test of the septic system on the above described property. During this test the liquid level in the septic tank was monitored as water was added to the system. table: The measurements are summarized in the following Liquid Level Below Top Total Gallons Time of Standpipe Added 1:35 6.2 0 1:42 6.2 25 1:46 6.2 50 1:55 6.1 100 2:04 6.1 150 2:13 6.1 200 2:35 6.2 200 The meter used during the test was a Rockwell 5/8" standard water meter which had previously been calibrated by R&M Consultants, Inc. If the proposed 4 bedroom residence on the property is to house 8 people, the average load on the system can be expected to be 600 gallons per day or .41 gallons per minute. During the test, the system accepted 200 gallons in 60 minutes. This indicates an average effluent acceptance rate of approximately 3.4 gallons per minute at the time of the test. April 24, 1978 Mr. James Patterson Pa§e -2- Because the house on the lot is occupied, we assume that the leach field was at its normal degree of saturation. We can therefore conclude that the system is disposing of effluent' at an adequate rate for a 4 bedroom resi- dence. We appreciate this opportunity to be of service to you. Please contact us if you have any questions concerning this test or if we can be of additional service. Very truly yours, R&M CONSULTANTS, INC. Lynne Kosikowski Staff GeoloEist Jim McCaslin Brown, Ph.D Head, Earth Science Department JMB/kah