Subject: Lot 2 Bakic Subdivision
Permit #SW970341, PID #015-163-76
The subject permit, issued September 30, 1997 by this office for a
single family well and/or on-site wastewater system, has
expired as of September 30, 1998.
A new permit must be obtained from this office for a well
and/or on-site wastewater system NOT installed by the
expiration date.
If you have drilled the well, a well log must be sent to
this office for documentation of the installation and to
close the permit.
If a licensed Professional Engineer has inspected the
installation of the on-site wastewater system, the original
as-built inspection report must be sent to this office for
review, approval and documentation. Ail inspection reports
must be submitted within 30 days of construction completion.
When applying for a new permit, the fees are: $320.00 for an
on-site wastewater permit; $120.00 for a well permit and
$440.00 for a combined on-site wastewater and well permit.
If you have any questions, please call this office at 343-4744.
ross! PPr~gram Manage~g. ~
On-site Services
enc: Copy of Permit
cc: Anderson Engineering
PAGE 1 OF 1
MUNICIPALITY OF ANCHORAGE
DEPARTMENT OF HEALTH AND HUMAN SERVICES
P.O. BOX 196650, 825 "L" STREET, ROOM 502
ANCHORAGE, ALASKA 99519-6650
ON-SITE WELL AND WASTEWATER DISPOSAL SYSTEM PERMIT
PERMIT NUMBER:SW970341 DATE ISSUED: 9/30/97
DESIGN ENGINEER:ANDERSON ENGINEERING EXPIRATION DATE: 9/30/98
OWNER NAME:~AK~MARY F F~ILY TR%~f~°
OWNER ADDRESS:D. ZANE & TERI L. HOUGH
1120 E. HUFFMAN RD. ANCHORAGE, AK 99515
PARCEL ID:01516376
LEGAL DESCRIPTION:
BAKIC LT 2
LOT SIZE: 40802 (SQ. FT.)
NUMBER OF BEDROOMS: 4 THIS PERMIT: 4
THIS PERMIT IS FOR THE CONSTRUCTION OF:
DISPOSAL FIELD /SEPTIC TANK / WELL SYSTEM
ALL CONSTRUCTION MUST BE IN ACCORDANCE WITH:
1. THE ATTACHED APPROVED DESIGN.
2. ALL REQUIREMENTS SPECIFIED IN ANCHORAGE MUNICIPAL CODE CHAPTERS
15.55 AND 15.65 AND THE STATE OF ALASKA WASTEWATER DISPOSAL
REGULATIONS (18AAC72) AND DRINKING WATER REGULATIONS (18AAC80).
3. THE ENGINEER MUST NOTIFY DHHS AT LEAST 2 HOURS
PRIOR TO EACH INSPECTION. PROVIDE NOTIFICATION BY
CALLING 343-4744 ( 24 HOURS ) (NOT REQUIRED FOR WELL ONLY PERMIT)
4. FROM OCTOBER 15 TO APRIL 15 A SUBSURFACE SOIL
ABSORPTION SYSTEM UNDER CONSTRUCTION DURING FREEZING
WEATHER MUST BE EITHER:
A. OPENED AND CLOSED ON THE SA/~E DAY
B. COVERED, SEALED AND HEATED TO PREVENT FREEZING
5. THE FOLLOWING SPECIAL PROVISIONS.
SPECIAL PROVISIONS:
1)ALL FEATURES OF THE WASTEWATER DISPOSAL SYSTEM ~gJST BE AT/
LEAST 100 FEET FROM MEAN ANNUAL FLOOD LEVEL OF SURFACE WATE~
2) ON ASZBUILT SUBMIT LOCATION OF ALL SURFACE WATER WITHIN
200 FEET OF SYSTEM/
RECEIVED BY: "/T/~~
ISSUED BY:
DATE:
DATE:
I0,
September 22, 1997
Municipality of Anchorage
Department of Heath & Human Services
825 "L" Street
Anchorage, AK 99502-0650
Subject:
Lot 2, Bakic Subdivision
Septic System Design
Impacts to Adjacent Properties
MUNICIPALITY OF ANr, JHORAGt:
ENVIRONMENTAL SERVICES DIVISION
SEP 2 2 1991
RECEIVED
Dear On Site Services Engineer:
We are hereby applying for a well and septic system permit for Lot 2,
Bakic Subdivision. The attached Site Plan shows the area for the new and
reserve absorption system and the location of the new well. The lot is
currently vacant with a stream flowing through the southern half. The
septic system will be placed a minimum of 100' from the stream.
The testholes placed in the area of the proposed absorption trenches
revealed well graded gravel with a percolation rate of 1 to 2 minutes per
inch. This gravel is underlain by a coarse sand which will slow the
absorption rate and assist in treatment of the septic effluent. No
groundwater was found in Testhole No.1. Groundwater was found, however
in Testhole No. 2 at 12' below the surface. The original ground elevation
of Testhole No. 2 is 10' lower than Testhole No. 1. We are placing the
primary absorption trench around Testhole No. 1 with the reserve site at
Testhole No. 2. The absorption trench will be 50' long by 5' wide by 4'
effective depth. The distribution pipe will be placed at 3.5' below the
surface. The maximum depth of the trench will be 7.5' below the ground
surface.
The ground surface of the lot slopes at a rate of 14% to 18% from south to
north in the area of the absorption trenches. The trenches will be placed
parallel to the ground contours in this area consistent with Municipal
requirements. We are confident the trenches can be successfully placed
on this slope.
Lot 2, Bakic Subdivision
September 22, 1997
Page Two
If the system is constructed as designed the following statements apply:
1. The system, if constructed as designed, will have no adverse impact
on the wells in the area or those to be constructed in the future.
The system, if constructed as designed, will have no adverse impact
on existing septic systems in the area or those to be constructed in
the area.
The system, if constructed as designed, will have no adverse
impact on reserved space, either surface or subsurface, on any lots
located in the area.
The system, if constructed as designed, will have no adverse impact
on drainage patterns in the area. The current drainage pattern will
be maintained.
Sincerely,
Michael E. Anderson, P.E.
Attachments
SHEET NO.
CALCULATED BY ·
CHECKED BY
OF
DATE
Lot 1 BAKIC
SCALE
/
UND'P.V;-LOPED
-- /,,
//.
*/
./
/
/:'--
i
2f
./
AREA MAP
SCALE 1" -- 100'
Lot 2B
Lot 2t Bakic Subd.
~HE~'I' NO. ' OF
' ~/~./~
~,ALCULATED BY DATE ~
/
CHECKED BY. DATE ,
FOUR BEDROOM
HOME
DRIVEWAY
1,250 GALLON
· SEPTIC TANK
, UTILITY EASEMENT
HILL DRIVE
SYSTEM PLAN
SCALE 1" = 20'
LOT 2, BAKIC SUBDIVISION
DESIGN FACTORS:
SYSTEM REQUIREMENTS:
FOur Bedroom Home
Perc. Rate: 1.5 Min./Inch
Application Rate: 1.2 GPD/SF
5' Wide Trench System
1,250 Gallon Septic Tank
4' Drainfield Rock
4 Bedrooms X 150 GPD / 1.2 GPD/SF = 500 SF of Absorption Area
500 SF/5 LF (Width) X .5 (Red. Factor) = 50 LF Trench Length
Therefore: Construct a 5' Wide Absorption Trench System With One
Lateral 50' in Length with 4' of Drainfield Rock Beneath the Lateral.
Distribution Pipe in Trench Placed at 3.5' Below the Original Ground
Surface.
NOTE:
TYPICAL 5' WIDE TRENCH SECTION
(NO SCALE)
Grade Area Over Trench to Drain ~way.
Minimum 3' of Cover over Septic System.
Minimum 4' Separation From Groundwater.
PERFORMED FOR:
LEGAL DESCRIPTION:
Municipality of Anchorage
DEPARTMENT OF HEALTH & HUMAN SERVICES
825 'L" Street, Anchorage, Alaska 99502-0650
SOILS LOG -- PERCOLATION TEST
Acreage Systems
DATE PERFe!
Lot 2, Bakic Subd. Township, Range, Section:
1
2
3
4
5
6
7
8
9
10
11
WAS GROUND WATER
ENCOUNTERED?
IF YE~, AT WHAT
DEPTH?
SLOPE SITE PLAN
Reading Date Gro~ Net Depth to
Time Time Water
~/~9/~ ~ /~:~ f -~. ~"'
/~,~ q'4- ~ -7.
/"rof,,':'/~-- /2". 7'?'""
.. I /toY: ~=, ./
PFJ~,COLAI'ION RATE '~' ?'" (m,nute~,nch) PERC HOLE DIAMETER
72-nn8 (Rev. 4/851
Municipality of Anchorage
DEPARTMENT OF HEALTH & HUMAN SERVICES
825 '%" Street, Anchorage, Alaska 99502-.0650
SOILS LOG --- PERCOLATION TEST
PERFORMED FOR:
LEGAL DESCRIPTION:
Acreage Systems
Lot 2, Bakic Subd.
DATE PERFORME[
Township, Range, Section:
1
2
3
4
5
6
7
8
9
10
11
~2
13
18
COMMENTS
SLOPE
WAS GROUND WATER
ENCOUNTERED?
SITE PLAN
$
IF YES. AT WHAT (,~-/ ~
DEPTH?
E
Gro~ Net Del~h m Net
Reading D~e Time Time Water Dm~
~l~J~ /~'~ ~ ~ ~
'/- .im~ ~ ~ I1,~ ~,/~
PERCOLATION RATE '/' '7 (mmute~,nch) PERC HOLE DIAMETER
· r.T.,u..~,~ f F'rA.D ~' ~
ACC;ORDANC;E WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE:' q/~"'/q 7
WAS PERFORMED IN
72-{'~38 IRev. 418.~
ON-SITE WASTEWATER DISPOSAL SYSTEM
CONSTRUCTION AND MATERIAL SPECIFICATIONS
SUBJECT: LOT 2, BAKIC SUBDIVISION
GENERAL:
1. The scope of this project includes the procurement and
placement of a new 1,250 gallon septic tank and the
construction of a new 50' long by 5' wide by 4' effective
depth absorption trench. The distribution pipe in the trench
to be placed 3.5' below the existing ground surface. Total
depth of the absorption trench will be 7.5' below the
existing ground surface.
2. Construction shall be in accordance with the approved site
plan, design drawings, Municipal Permit with any special
provisions or conditions, and all applicable State and
Municipal Wastewater Disposal Regulations.
3. The Contractor shall be responsible for obtaining all
underground utility locates and for the layout of the septic
system and verification of the location of all lot lines.
4. Unless specifically agreed otherwise, the contractor shall
be responsible for final grading areas subsequently
depressed from soil settling. Property owner shall be
responsible for revegetation of affected areas unless
specifically agreed otherwise.
5. Contractors installing wastewater disposal systems must
be certified by the Municipal Department of Health and
Human Services for system installations. Owners installing
their own systems must receive prior approval from D.H.H.S.
before beginning system installation.
SEPTIC TANK INSTALLATION
1.A new 1,250 gallon septic tank must be procured from an
approved source and installed at the location shown on the
plans.
Lot 2, Bakic Subdivision
September 22, 1997
Page Two
2. A septic tank is to be constructed by a certified septic tank
manufacturer. Construction shall include two 4" cleanouts
for pumping access.
3. The septic tank shall be sufficiently
settling or shifting of the tank.
bedded to prevent
4. All standpipes on the septic tank shall extend a minimum of
12 inches above final grade.
5. Tanks installed without 4' of cover shall have a minimum of
2" of direct burial insulation.
6. A foundation cleanout shall be installed one to four feet
from the building foundation. Two cleanouts are required
between the tank and the drainfield.
7. Final grading over the tank shall be such that a positive
slope exists away from the septic tank.
DRAINFIELD CONSTRUCTION:
1. The drainfield shall be constructed to the dimensions shown
on the design. The bottom of the trench shall be within 2"
of level.
2. Distribution piping must be placed level with perforations
down atop a level bed of drainfield rock. Rock should then
be placed over the pipe to provide a minimum of 2" of cover.
3. A silt barrier or geotextile fabric must be placed between
the drainfield rock and the natural soil backfill.
4. Monitor tubes must be 4" in diameter and installed at the
locations shown on the design. The portion below ground
must be perforated.