CASE NUMBER: ~ ~"~9 ~' '"' DATE RECEIVED: I COMMENTS DUE BY:
S-8128 ~~7 April 25, 1985 I May 17, 1985
SUBDIVISION OR PROJEC~ TITLE:
Lots 1 - 15 Bending Birch Subdivision
PUBLIC WATER AVAILABLE ( )(~') PUbLiC SEWER AVAILABLE
COMMUNITY WATER AVAILABLE
~'/,?_~ -' , . .
/
71-014 (Rev, 5/83)
DEPT.'eF ENV IRON MENTAL CONSERVATION
ANCHOI~E/WESTERN DISTRICT OFFICE
437 "E' STREET, SUITE 303
ANCHOiII~E, ALASKA 99501
BILL .SHEFFIELD, GOVERNOR
274-2533
Mr. To~en Spurkland, P.E.
203 W. ~5th Avenue "C"
Suite ~
Anchorage, Alaska 99501
March 14, 1985
SUBJECT: Bending Birch Subdivision', Lots 1-15
ChugiaX, Alaska (8521-DA-126)
Dear Sir:
We ha~ reviewed the plans and specifications for the subject project.
This l~tter constitutes the permit required by A.S. 46.03.720(a) for
approw~l of sewerage systems.
It should be remembered tnat final approval will necessitate the submission
of En~neer As-Built Plans. This will conseouentiy manoate tnat a orivate
profe:ional engineer conauct basic inspection of this oro3ect so as to De
able Im sign off on as-built plans. Arranoement fo~ t~is inspection work
is the responsibility of the aeveloper. Any future expansion of subject
projec~. will require aoditional approval from this office.
Sincerely,
Environmental Engineer
SWE/ms~
_CONSULTING ENGINEER
203 W. 15th AVE '°C" SUITE 203
ANCHORAGE, ALASKA 99501
TELEPHONE: (907) 279-391G
LOG OF' TEST HOLE NO.
LOT' ~: 1B.1ENI~IN~ 'E~II~'C..I-%
DATE:
LOCATION:
TEST PIT
LOGGED BY
MATERIAL DESCRIPTION
CONSULTING ENGINEER
203 W. 15th AVE "C" SUITE 203
ANCHORAGE, ALASKA. 99501
TELEPHONE: (907) 279-39;~
LOG OF TEST HOLE NO.
DATE; ..
LOCATION=
TEST PIT
LOGGED BY=
MATERIAL DESCRIPTION
CONSULTING ENGINEER
203 W. 15th AVE 'C' SUITE 203
ANCHORAGE, ALASKA 99501
TELEPHONE: (907) 279-3916
LOG OF TEST HOLE NO.
LOT ~, '~ENDtNG
DATE=
LOCATION:
TEST PIT
LOGGED BY~ LO~ ~'1"~. -..-
MATERIAL DESCRIPTION
o~~c~
CO.__NSU LTING ENGINEER
203 W. 15th AVE "C" SUITE 203
ANCHORAGE, ALASKA 99501
TELEPHONE: (907) 279-3916
LOG OF TEST HOLE NO.
LOT 14 ~.ENI)IN& 'lS~lACH
DATE:
LOCATION:
TEST PIT
LOGGED BY: ~0~ BOT~.g:~-~.. ....
MATERIAL DESCRIPTION
~CONSULTING ENGINEER
203 W. 15th AVE "C" SUITE 203
ANCHORAGE, ALASKA 9~a01
TELEPHONE: (907) 279-391-
LOG OF TEST HOLE NO. 5
D~TE~
LOCATION:
TEST PIT
LOGGED BY: ~O~ ~U'['~.1:r~A .....
MATERIAL DESCRIPTION
Spurkland Engineering
203 W 15th #203
Anchorage, AK 99501
279-3916
BENDING BIRCH SUBDIVISION
Supplemental Bid Specifications
(Preliminary-subject to change by Engineer)
Sewer Line
a. Ail main sewer line to be 8" Class 50, Ductile Iron pipe
with o-ring bell and spigot "Tyton" type joints, properly bedded
and backfilled. (Class C bedding). Tolerance from established
line and grade not to exceed 0.03 feet.
b. Manholes to be type A, 48" diameter with a 25" access
diameter. Precast concrete or poured in place concrete type.
c. Pipe laying to proceed uphill. Native materials may be
used for bedding above the spring line of the pipe when properly
compacted to 95% density.
d. Cleanout at East end of sewer line to be installed as
per AWWA C-151.
e. System may be subject to pressure testing to' be provided
by contractor as an extra charge.
Sewer Connections
a. 4" service connect stub to be installed for each lot, 5'
inside lot line with location marked with a 2x4 post.
b. Acceptable pipe is Ductile Iron with. Tyton joints, cast
.iron with Ty-seal joints, cast iron with "Romax" no-hub joints.
Minimum slope 1/4" per foot.
c. Construction and materials for connects shall be as
specified in the 1985 AWWA Design Criteria for Sanitary Sewer
Sections 33.01 - 33.03.
Septic Tank
a. 10,750 gallon-2 compartment, 8' diameter septic tank'
approved by State D.E.C. and Municipal codes.
be
outlet.
c.
Mechanical couplings to be installed on inlet and
Two 4" stand pipes .to be installed for cleanout.
d. Tank to be ~roperly bedded and backfilled. If high
water table is encountered appropriate anchoring may be necessary
as designed by engineer as extra charge.
LIFT ~TATION
a. A lift station to be instal, led of poured in place Class
A-3 concrete or pre fab corrosion resistant steel with a 3000
.gallon storge capacity.below the septic tank outlet invert. Ac-
cess to lift station to be thru a lockable steel manhole type
cover.
b. Two wastewater pumps to be provided to operate in
alternating fashion. Each pump to have a capacity of 100 G.P.M.
at a total lead of 40 feet with inlets capable of passing 3"
spheres. Each pump shall have an individual intake with wet well
floor designed to avoid turbulance near the intake.
c. Submersible pumps and motors shall be designed and
supplied by the same manufacturer, specifically for effluent sew-
age use including totally submerged operation during a portion of
each pumping cycle. .The motor shall be of squirrel-cage type
design without.brushes or other arc producing mechanisms.
d. Suitable Anchorage Water and Wa~tewater approved shut-
off and check valves shall be placed on the discharge line of each
pump. The check valve shall be located between the shutoff valve
and the pump. Check valves shall be suitable for the material
being handled, and at an elevation higher than the maximum wet
well level. Valves shall be capable of Withstanding normal pres-
sure and water hammer, and be of the sprint'and level type 'to
allow manual back flushing of pumps.
e. Mercury switch type level controls shall be used to
control sump level. To .control automatic operation of pumps,
three mercury switch level controls shall be supplied. Two of
these controls act to close circuit for on-off operation at se-
lected levels required and to oper'ate alternator for alternation
of pump on each cycle of operation. A third control acts as
override and closes circuits of override to operate.both pumps
together. A fourth control acts at.high water'level to close
circuit of alarm.system.
f. Control Cabinet of Specifidation NEMA 4 enclosure shall
be furnished. For single phase pumps the control panel shall
include - contractors' for each pump, circuit breakers for each
pump, and H-O-A switches for each pump, and an alternating relay
circuit.
g. The high water alarm shall include an alarm bell or
alarm horn and to be supplied in separate enclosure mounted 8"
high. Includes a warning light and silencing switch.
Force Main
a. 4' Ductile Iron pipe, Class 52, installed with 10'
minimum burial depth properly bedded and backfilled.
b. Type II Continuity straps to be installed on each
joint in accordance with M.O.A. standard specifications for water
systems. Continuity test to be made on completed system.
c. Pressure testing by contractor is required.
d. ~orce main to spill into a type "A" manhole exiting from
which will be the leach.field header.
Septic Leach Field
a. Leach field to.be installed as per Municipal and State
codes with levels taken from engineer established benchmark with
deviation from level not to exceed 3" per 100' ih length of trench.
b. A 4" P.V.C. ASTM - 3034 header pipe to exit manhole to
supply the trench system leach field. Each trench leach pi~e will
tee into header with a drop in elevation from header.
· c. Trenches are 5' wide, 4' total 'depth with 2' of gravel
under leach pipe and 4' of mounded soil cover (over completed
trench). There are 21 wide trenches, 75' long and spaced 6' apart
(trench wall to trench wall).
d. Trenches to be excavated so that no machinery is run on
the trench bottom and septic rock is to be placed from the side so
as not to compact trench bottom.
e. Septic rock is to be 1/2" to 2 1/2" screened gravel
specified sewer drain rock. Washed gravel is preferred if availa-
ble.
trench.
A filter fabric material is to be placed over completed
g. All M.O.A. construction standards and State D.E.C. guide-
lines ~are applicable to the construction of septic leach area.
h. The elevation of the trenches may be changed upon final
construction survey. This would possibly change total depth of
trench to 3' and 1' additional mounded cover required.
General
Unless otherwise noted here in, on the plan or'by written
notice from the engineer all sewer system installation will be as
required by AW-WU. 1985 Design Criteria for Sanitary Sewer, M.O.A.
1984 Standard Specifications Division 50, 1983 State of Alaska
D.E.C. Wastewater Disposal Regulations 18-AAC 72, M.O.A. Waste-
water disposal ordinance and code, latest editions of the Uniform
Mechanical Code, Uniform Plumbing Code and National Electrical
Code.
All work subject to inspection and approval of engineer.
,/l
I , I|'
I
!
!