ON-SITE WASTEWATER INSPECTION REPORT
Permit Number: OSP211330 PID Number: 015-521-38
Dwelling: n Single Family (SF) ❑ with ADU ❑ Duplex (D) ❑ Two Single Family Project: ❑ New X Upgrade
Name
DAVID HOPKINS ABSORPTION FIELD
Site Address ❑ Dee
11050 GAMACHE DRIVE *ANCHORAGE, AK p Trench El Wide Trench El Bed ound
❑ Other
Phone :74
mber of Bedrooms Soil Rating Total depth original grade
907-830-4649 GPD/SF Ft.
LEGAL DESCRIPTION Depth to pipe invert from original grade Gravel depth beneath pipe
Subdivision Block Lot
T1 2N R3W SECTION 22 LOT 26 E220' OF S396'Ft. Ft.
Fill added above original gr a Gravel length
Township Range Section
_ Ft. Ft.
Gravel width Beds: Number of Lines Distance between lines
SEPARATION DISTANCES Ft. Ft.
To Septic Absorption I Holding Sewer Total orption area Number of trenches Dist. between trenches
From
Tank Field Lift Station Tank Line Ft2
Ft.
Well 100'+ TANK A Septic [IS.T.E.P. ElHolding 171Other
Manufacturer Capacity
Surface Water 100'+ GREER TANK 1250 Gal.
Material Number of compartments
Lot Line51+NA HDPE 2
Foundation 10'.+. I LIFT STATION
Manufacturer Capacity
Remarks OLD TANK DECOMMISSIONED PER UPC Gal.
PER CONTRACTOR Alarm location Electrical installed by
PIPE MATERIAL House to tank EXISTII� Tarok O �NSYII ^d
Installer drainfi Id
A+ HOME SERVICES �—
Drainfield EXISTING CO/MT D
Inspector GEG AND MOA BENCH MARK (Assumed elevation) 100.00 ft
Inspection 15t 10/8/21- Location and description
dates: 2nd
3'd 4�
TOP OF MH
- -
ON-SITE WATER AND WASTEWATER SECTION APPROVAL Engineer's Stamp
Conditional Approval: Date
Septic System
Approved
Note: this
(Rev 05/02/18)
Date /D y 23
I does of include well permit requirements.
#AECC884
PERMIT NUMBER: RECORD
PARCEL ID NUMBER:
OSP211330 R E C O R D DRAWING 015-521-38
A I B I C
DBL1 47.7 51.1 58.7
DBL2
48.2
51.5
59.1
MH
50.5
53.5
60.7
ST1
54.9
56.6
63.5
DBL3
56.2
57.5
64.4
DBL4
57.1
58.4
65.1
C/O
47.3
52.2
60.0
T12N R3W SECTION 22
LOT 26 W 110' OF S396'
T12N R3W SECTION 22
LOT 26 N264'
PROPOSED GARAGE
(NOT 1M)
C/O �•
S
NEW 1250 GALLON
HDPE GREER TANK
I
I `
N \
/ SCALE: \ \
1" = 40' .
'A
A: • : y.
A NESS FriNGINEERING
GRO Ltd
9
- - - �`-_ ENGINEERING �� SALES - CONSULT ING
3701E TUDOR ROAD SUITE 101 ' ANCHORAGE. AK 99507 -PHONE (907) 337-6179 -FAX (907) 338-3246' WEBSITE:
www g esse pn g cam
PREPARED FOR:
PHONE NUMBER:
PAGE NUMBER:
DAVID HOPKINS
907-830-4649
2 OF 3
LEGAL DESCRIPTION:
DRAWN BY:
T12N R3W SECTION 22 LOT 26 EAST 220' OF S 396'
D.J.G.
TYPE OF WORK:
DATE:
,,_ SEPTIC TANK RECORD DRAWINGS
10/28/2021
EXISTING
HOUSE
AV
AV
♦ 4l
..p / ...0
�y . .m
Cn yA_Garness
AF
`I%T CE -7953
LICENSEa 4%FESS ®®®�
#AECC884 J
PERMIT NUMBER: RECORD D RAW I N G PARCEL ID NUMBER:
OSF2113300015-521-38
TOP OF TANK AT INTLET = 95.93
INVERT OF BUNG AT INLET = 95.26
TOP OF MANHOLE = 100.00
NAL GRADE = 99.5-99.84
NEW 1250 GALLON
H.D.P.E. SEPTIC TANK
2" HIGH DENSITY INSULATION
TOP OF TANK AT OUTLET = 95.92
INVERT OF BUNG AT OUTLET = 95.14
ff
""ROUP, Ltd
ENGINEERING SALES. -CONSULTING
3701 E. TUDOR ROAD. SUITE 101 - ANCHORAGE. AK 99507' PHONE (907) 337-6179' FAX 19071339-3246'vlrm)TF
PREPARED FOR:
DAVID HOPKINS
PHONE NUMBER:
907-8304649
LEGAL DESCRIPTION:
Tl 2N R3W SECTION 22 LOT 26 EAST 220' OF 396'
TYPE OF WORK:
�, SEPTIC TANK PROFILE
PAGE NUMBER:
30F3
DRAWN BY:
D.J.G.
DATE:
10/25/2021
o®.�� QF 'q/ 1
0 4,....... ...
Air �® P.• i I � ®o
0
#00
...........�........::...
.......... .u.............d
re Garn6SS :"�
lo
A. Air
B . C6-795 aAV
11.
v AV
LICENSE®®'it itF ®+� �. 0�
#AECC884 /
ASBUILT SURVEY OF:
SCALE:
GRID No:
WORK ORDER No.
DRAWN:CHECKED:
DATE:
FB BOOK/PAGE:
OCT, 18, 2022 50'
MECB SW2637 151/43-44
The E. 220' of the S. 396' of Gov't. Lot 26,
Sec. 22, T. 12 N., R. 3 W., Seward Meridian
Anchorage, Alaska
SERVI N G A L A S KA SI
N
C
E
1
9
8
2
EXCLUSION NOTES: It is the owners responsibility to determine
the existence of any easements, covenants, or restrictions which
do not appear on the Plat used for this survey. NOTE: Under no
circumstances should any data hereon be used for construction
or for the establishing of property lines.
SURVEY CERTIFICATION: FARPOINT has conducted a physical
survey of the subject property, the improvements situated
thereon are within the property lines as shown.
Monument
Septic Vent
Power pole
PREPARED FOR:
David HopkinsonZONING:
R6
House Detail
Well
1.Bearings and distances are record per referenced plat unless otherwise noted.
2.Sufficient boundary evidence was recovered to establish the subject parcel on the ground. Not all
controlling evidence is shown hereon.
Detail
Robert O. Lumpkin
No. 10459
MUNICIPALITY OF ANCHORAGE
On -Site Water & Wastewater Program
PO Box 196650 4700 Elmore Road
Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997
http://www.muni.org/onsite
On -Site Wastewater Disposal System Permit
Permit Number: OSP211330
Work Type: SepticTank Upgrade
Tax Code Number: 01552138000
Site Legal Address: T12N R3W SEC 22 LT 26 E220' OF S396' G:2637
Site Mailing Address: 11050 GAMACHE DR, Anchorage
Owner: HOPKINSON DAVID J LIVING TRUST
Design Engineer: GARNESS ENGINEERING GROUP LTD
This permit is for the construction of:
Effective Date:
Expiration Date:
Lot Size in Sq Ft:
Total Bedrooms:
�t��enr
= _s�
Department
8/26/2021
8/26/2022
87120
❑ Disposal Field Q Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage
All construction shall be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80)
3. The wastewater code requires inspections during the installation. The engineer shall notify the Development
Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
shall be either:
a. Opened and Closed on the same day, or
b. Covered, sealed, and heated to prevent freezing
Received By:
Issued By: h GJOC er+SS
"N 1 Date: 2- _1
Date:
4
Municipali
P.O. Box 196650 0 4700 Elmore Road
Anchorage, Alaska 99519-6650 a (907) 343-7904 ® Fax (907) 343-7997
http://www.muni.org/Onsite
Development ices Department
On -Site Water and Wastewater Section
eN
)e pa r C file lit
xx�X / VT -,R REVIEW
KXX?�C
Waiver#: OSV211063 COSA#: Permit#:OSP211330
PID#: 015-521-38
Legal Description: T12N RM Section 22 Lot 26 E220' of S396'
Engineer: Garness Encgineerinq Group
Applicant: David Hopkinson
Your request for a waiver of the required 10 feet horizontal separation from the absorption field
to the property line has been approved. The approved separation distance is 5.0 feet. See
engineer's waiver request for justifications.
This waiver approval applies to the existing absorption field only. Any future upgrade to the on-
site wastewater disposal system will require all separation distances be met or another approval
from this department.
aaaIII aaIII aa■aa■aaaaaa■■ III aaaavvIII s®aaaa2000s®III III ®a III ■eea■aaaaaaaaaaaaaaaaaIII aaeaaIII ■®at
Waiver is Granted: X Waiver is not Granted:
Date: p
0 �/,.go a 1 Approved by:
Name of Reviewer
a a o ... a a a .. a a a ... ■ a a .. e e a a■ a a a a■ a v a a a■ a m a a m a a a e a a v a a e a a a o s a a a e a a a s a m .... o a v a .. �
4�
Development Services Department � � Phone 907-34,3 7904
On -Site �]Vcater & �\lastevvater Section l=ax. 907-341,3-7997
ON-SITE SEPTICM/ELL PERMIT APPLICATION
Parcel I.D. 015-521-38
Property owner(s) DAVID HOPKINSON
Mailing address 11050 GAMACHE DRIVE *ANCHORAGE, AK
Site address 11050 GAMACHE DRIVE *ANCHORAGE, AK
Day phone 907-830-4649
Legal description (Sub'd., Block & Lot) T12N R3W SECTION 22 LOT 26 EAST 220` OF S396'
Legal description (Township, Range & Section)
Lot Size
Sq. Ft. Number of Bedrooms 3� H
APPLICATION IS FOR:
APPLICATION IS AN:
TYPE OF DWELLING:
(® all that apply)
Absorption Field ❑
Initial ❑
Single Family (SF) 0
(w/wo ADU)
Septic Tank Q
Upgrade ❑
(D) ❑
Holding Tank ❑
RenewalDuplex
❑
Multiple Dwellings ❑
Privy ❑
(SF and/or D)
Private Well ❑
Water Storage ❑
THIS APPLICATION INCLUDES A WAIVER REQUEST FOR:
lJ 5o r - 1or\1"
VU e c
Distance:
I certify that the above information
is correct. I further certify that this is in accordance with
applicable Municipal Codes.
r-ra-'- a ess
ti�2e�, iitU, 6__/_L)LA�7.
�C
(Si�ature of property owne>,& authorize(I aunt)
ono a
Permit/Rush Fees: 9; ZZ 5 Waiver Fees: � 2v5
Date of Payment: W1 [mi1 Date of Payment: 8b 7 102 1
Receipt Number: 05 19 3 Ca Receipt Number: d 4� 9'r7 G
Permit No. O SP -2 113 30 Waiver No. O S V V 1 b 1 3
G:\Development Services\Building Safety\On Site Water and Wastewater\Forms\Client FormsTermit Application.doc
✓ 1
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP211330, Rebecca Carroll, 08/26/21
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP211330, Rebecca Carroll, 08/26/21
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP211330, Rebecca Carroll, 08/26/21
Municipality of Anchorage4P.I.
Development Services Department -
Building Safety Division
On-Site Water and Wastewater Program, 4700 S. Bragaw St.
P.O. Box 196650 Anchorage, AK 99519-6650 Page of
www.d.anchorage.ak.us (907) 343-7904
ON-SITE WASTEWATER DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT
Permit Number: %gro o 13 PID Number. 016'— I _
Name:V1 OD r'
Wastewater System: [YNew ❑ Upgrade
Address.
2I aD 4 a
ABSORPTION FIELD
Phone Numberof Bedrooms
'1
0 Deep Trends b Slulbw Trench O Bad 13 Mound [3 Other.
LEGAL DESCRIPTION
Sol RaGnp:
Total Deplh from original grade:
P ,�
g
Block: Lot Subdivision:
f 06
Depth to pipe bottom from angtrlal grade:
Gravel depth beneath pipe:
15 S 4 f.., 6
Ft.
Ft
Township: Range: Sedion
2
FR added above original grade:
Gravel Lerignsn
2- t4 3
" O Ft.
Ft.
Well: ❑ Upgrade.
jgNew rade
Gravel width
Numberoflines:
Distance between lines '
Ft.
t o FL
Classification (Private. A, B. CY.
Taal Depth:
Cased to:
Total absorption ares
Pipe Material:
a Ft.
1) Ft
Ft'
Ib f $v'5%4
Driller
Date D
be.:
I1 d
Stade WajF
L
Installer.
IUs t
Data Insteled.
W w t0 =y Lo
Yield.
Pump set at
Casing Moot Abo
TANK
I GPM
O TT•O F
t
SEPARATION DISTANCES
Zseptic (:)Holding ❑ S.T.E.P. O Other.
To
Septic
Absorption
Lift
Holding
PubilOPrIvatel
Manufacturercapaatr.
From
Tank
Field
Station
Tank
Sewer Una
I AN7NLi-i i AN v,
1 't7Gal.
Well
1 ^ 1.%
es--
! .' u
t/
t�
Malarial: _
S «
Number of Compartments-
9—
Surface
Surface Water
O NIE
,i
W,
LIFT STATION
Line
I I 0
`7
,}
t D
✓
✓
Size'.
Gal.
Manufacturer.
Foundation
'Pump W level at
'Pump oM by at
High water alarm at
3,2
II
h
h
h.
Curtain Drain
,i
!vN>`
Pump Make i Molal
EbCtr" peaions Performed by
Remarks
BENCH MARK
Location and Description:
Er F- 51-Aa
Assumed Elevation:
l�pd' FL
+cc 017 A t.
: %tg
yp•�4aaeeaeeee
Inspections performed by: I, S Dates: 1at !d IA310>
t
a9IH«•«•«.•....-
2ndto .2`i v
I •»
T�
Developmen Services Department Approval
:�
Reviewed and approved by: Date: o
��e `�9F ~'a•.....•w''� Eon.
=�V
tae .luoot
OFESS���
H41111 mill 1 I
\� e hFVEL
flltl mm,
G ....,
Testhote, t ' '`._� �' �•
t n XeO{eneni Slte I
Ie #3...� I
"f I
IY I• f. ..i• I
D'I-� �� BEACH MARK sw1HG ncx C ... • :; I I
AC 39 IT
BC 75 '�, ::•..•
AD 46.5 r -
BD 79.5 .• a'i
AE 56 I i
BE 83.5AF 143
A I
BF 158 I I
AG 131
BG 119.5
I AH 158.5 ¢ Well I I
..•�\� '�'���� I u 149 I I
........ �♦♦ all t N6 I
'�. �� `�y ♦ 1V I I
49th ° ♦� I
..."= ............................... •i I
� I I
.. ! .rBEN
.......... ...... .I
90. TrRKLAND 2225 '=�...or�
I I �
25 0 25 5075 100 125 VW I
SCALE, 1 = 50 FT,
I— — — — — — — — — — — — — — — — -j
L_
BENCH MARK,
GARAGE SLAB
0BBEN 5P.E.
203 W 15TH.
AVENUE I I E ,2,20, S 396, LOT 26 SEPTIC SYSTEM AS BUILT I
2AVENUE
ANCH. AK. 99501 SEa 22, T/1H, R3W DATE: OCT. 30, ?003
(907) 229-3916 DAVE HOFKiNSON SHEET: 2/3 GRID: 1637
PERMIT # SVO3030137 PIN 015-521-38 12322262TV6 I
2 5 -WIDE TRENCHES
5 FT WIDE
55 FT LONG
2 FT OF ROCK
7 FT TOTAL DEPTH
2 FT FILTERSAND
3 FT Or COVER
NO SCALE
3' cow.
88.4
86.0
84.0 r`"`r=
24' Sewer Rock
82.0
86.0
84.0
96.51
1250 GAL SEPTIC TANK
5
WWI 140 —" / I I BENCH MARK.•
2' OR#*r Sand _/ IL JI GAR4GE SLAB
ASSUREQ £LEV 100,00 FT
TOBBEN TP-th Ave AND P.E.
W1
203 E220' S396 LOT 26 SEPTIC SYSTEM AS BUILT
A cho fg Ave Ak 9950111 SEC. 22 T12M R3W DA Tr.* OCT. 30, 2003
DAVID HOPKINSON SHEET • 3/3 GRID: 2637
PERMIT # SVO30137 PM # 015-521-38 123222633
M -W Drilling, Inc.
♦ P.O. Box 110378 ♦ Anchorage, AK 99511
•907-345-4000 • 907-345-3287 Fax*
Job No.: 03-138 Project No.: N/A Permit No. SW030137
♦ Well Owner. _
♦ Legal Description:
Groundwater Well As -Built & LoQ
David
—
n 22. Lot
Construction
♦ Use of Well: Domestic
♦Hole Depth: 91' ♦Casing Size. 6" ♦Cased To: 90.43' ♦Materlal: A53Steel
♦Drill Method: Air Rotary
Perf.
*Well Completion- Open end X Screen Perforated _ Method.
♦Sereen/Perforatlon description: None
♦Grout Notes: (3) Sacks- No. 8 bentonite granules
♦ Notes.
♦ Well Development. Method: Air surge Notes:
♦Static water level (Slf'L) 54.4' (&bare) (below) top of casing (TOC).
♦ Well yield test at 10 gallons per minute (GPM)/gallons p" hour (GP#) for 1 hours
with 100% of drawdown (DD) from static level (SWL).
*Method: Air lift
♦ Date of completion:
11 June 2003
Woll T ....
♦ Pump Install.
Depth in feet from
top of casing.
Details of formations penetrated,
size of material color and hardness.
0
TO
2
Casing stickup
2
TO
4
Overburden
4
TO
10
Gravel
10
TO
54
Silt: fine, some water
54
TO
85
Silty ravel: wet ---
85
TO
90
Water bearing gravel
TO
TO
TO
TO
TO
TO
TO
TO
TO
TO
TO
t;fied-coatra
CeQ,cate NA 814 & 973
15-4/42 3 & 370cr-
MUNICIPALITY OF ANCHORAGE
Development Services Department
On -Site Water& Wastewater Program
4700 South Bragaw Street
P.O. Box 196650, Anchorage, AK 99519-6650
(907) 343-7904
ON-SITE WASTEWATER DISPOSAL SYSTEM / WATER SUPPLY PERMIT
Initial
Permit Number: SW030137
Legal Description: T12N R3W SEC 22 LT 26 E220' OF S396'
Design Engineer: 0007 Tobben Spurkland, PE
Owner Name: DAVID HOPKINSON
Owner Address: 11050 GAMACHE DRIVE
ANCHORAGE, AK 99508 -
Date Issued: May 19, 2003
Expiration Date: May 18, 2004
Parcel ID: 015-521-38
Site Address:
Lot Size: 87120 SQ. FT.
Total Bedrooms: 3 Permit Bedrooms: 3
This permit is for the construction of.
❑✓ Disposal Field ❑✓ Septic Tank ❑ Holding Tank ❑ Privy
All construction must be in accordance with:
1. The attached approved design.
❑✓ Private Well ❑ Water Storage
2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations (1 BAAC80 ).
3, The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling
(907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only ).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
must be either. A. Open and closed on the same day.
B. Covered, sealed, and heated to prevent freezing.
5. The following special provisions.
1.) THE SAND USED IN THE FILTER LAYER MUST BE A CLEAN COARSE SAND WITH 4% OR LESS PASSING
THE #100 SIEVE AND 2% OR LESS PASSING THE #200 SIEVE. A SIEVE ANALYSIS MUST BE PROVIDED ON
THE SAND USED OR OBTAINED FROM AN APPROVED SOURCE.
2.) THE MAXIMUM TOTAL DEPTH OF THE SUBJECT WIDE DRAINFIELD SHALL BE NO DEEPER THAN 6
FEET.
Received B
Issued B
Date: -9 L 6b
Date: -3— o _
Municipality of Anchorage
j • �� Development Services Department
Building Safety Division
On -Site Water and Wastewater Program
4700 South Bragaw St.
P.O. Box 196650 Anchorage, AK 99519-6650
www.ci.anchorage.ak.us
(907) 343-7904
ON-SITE SEWER/WELL PERMIT APPLICATION
FOR A SINGLE FAMILY DWELLING
Parcel I.D. 01952130 Permit Number SWO3o/37
Property owner(s) aVC'e4 L'faXeX srtSsD-.% Day phone X30—,Y(:W5
Mailing address (1) ZFYJ Z7. -;76— 4 v&
SlT13
44a4i ig address (2) 1050 (r tmewEQRI ve Zip Code 115
Legal description (Lot, Block & Sub'd.) T1Z,1I/ If -?4'' Sc LL Z�124� _� d �o gar S3g�_
Legal description (Section, Township & Range)
Lot Size fAcre Ft
871/20
THIS APPLICATION IS FOR:
Number of Bedrooms 3
Sewer Only ❑ Well Only ❑
Sewer and Well M Water Storage ❑
Sewer Upgrade ❑
THIS PROPERTY CONTAINS:
Hot Tub ❑ Jacuzzi ❑
Swimming Pool ❑ Water Softening Unit ❑
Therapy Pool ❑
I certify that the above information is correct. I further certify that this application is being made for a
Single Family Dwelling and is in accordance with applicable Municipal Codes.
of property owner or authorized agent)
Date of Payment:
Date of Payment:
Receipt Number: 0 3 j/ 0 7 Receipt Number:
(Rev. 12/00)
Mwiicipality of Anchorage A
Mayor
Department of Health and Human Services
825 "L" Street
Rick rom. P.O. Box 196650 Anchorage, Alaska 99519-6650
343-4744
August 16, 1996
David J Hopkinson
Greta H Kirkevold
7511 Huckleberry Circle
Anchorage, Alaska 99502 2880
Subject: T12N R3W Section 22 Lot 26 E200' of 5396'
Permit #SW950222, PID #015-521-38
The subject permit, issued August 16, 1995 by this office for a
single family well and/or on-site wastewater system, has
expired as of August 16, 1996.
A new permit must be obtained from this office for a well
and/or on-site wastewater system NOT installed by the
expiration date.
If you have drilled the well, a well log must be sent to
this office for documentation of the installation and to
close the permit.
If a licensed Professional Engineer has inspected the
installation of the on-site wastewater system, the original
as -built inspection report must be sent to this office for
review, approval and documentation. All inspection reports
must be submitted within 30 days of construction completion.
When applying for a new permit, the fees are: $320.00 for an
on-site wastewater permit; $120.00 for a well permit and
$440.00 for a combined on-site wastewater and well permit.
If you have any questions, please call this office at 343-4744.
inc rely,
J mes Cr�ss, P. E.
Program Manager
On-site Services
enc: Copy of Permit
cc: Tobben Spurkland, P.E.
a.
MUNICIPALITY OF ANCHORAGE
DEPARTMENT OF HEALTH AND HUMAN SERVICES
P.O. BOX 196650, 825 "L" STREET, ROOM 502
ANCHORAGE, ALASKA 99519-6650
ON-SITE WELL AND WASTEWATER DISPOSAL SYSTEM PERMIT
PERMIT NUMBER:SW950222
DESIGN ENGINEER:TOBBEN SPURKLAND, P.E.
OWNER NAME:HOPKINSON DAVID J &
OWNER ADDRESS:7511 HUCKLEBERRY CIRCLE
ANCHORAGE, AK 99502=2880
PARCEL ID:01552138
LEGAL DESCRIPTION:
T12N R3W SEC 22 LT 26 E200' OF 5396'
LOT SIZE: 79200 (SQ. FT.)
NUMBER OF BEDROOMS: 4 THIS PERMIT: 4
THIS PERMIT IS FOR THE CONSTRUCTION OF:
DISPOSAL FIELD /SEPTIC TANK / WELL SYSTEM
ALL CONSTRUCTION MUST BE IN ACCORDANCE WITH:
PAGE 1 OF 1
DATE ISSUED: 8/16/95
EXPIRATION DATE: 8/16/96
1, THE ATTACHED APPROVED DESIGN.
2_ ALL REQUIREMENTS SPECIFIED IN ANCHORAGE MUNICIPAL CODE CHAPTERS
15.55 AND 15.65 AND THE STATE OF ALASKA WASTEWATER DISPOSAL
REGULATIONS (18AAC72) AND DRINKING WATER REGULATIONS (18AAC80).
3. THE ENGINEER MUST NOTIFY DHHS AT LEAST 2 HOURS
PRIOR TO EACH INSPECTION. PROVIDE NOTIFICATION BY
CALLING 343-4744 ( 24 HOURS ) (NOT REQUIRED FOR WELL ONLY PERMIT)
4. FROM OCTOBER 15 TO APRIL 15 A SUBSURFACE SOIL
ABSORPTION SYSTEM UNDER CONSTRUCTION DURING FREEZING
WEATHER MUST BE EITHER:
A. OPENED AND CLOSED ON THE SAME DAY
B. COVERED, SEALED AND HEATED TO PREVENT FREEZING
5. THE FOLLOWING SPECIAL PROVISIONS.
SPECIAL PROVISIONS:
THE SAND ASED AS A FILTER LAYER MUST BE LAKE OTIS GRAVEL OR
OTHER SAND MEETING DHHS REQUIREMENTS.
RECEIVED
ISSUED BY:
DATE: F3 — / q6
DATE: l." G'
T.SPURKLAND P.E.
203W 15th. Avenue, Suite 203
ANCHORAGE, ALASKA 99501
(907) 279-3916
Fax (907)-276-6013
SEPTIC SYSTEM DESIGN
E220, S396 LOT 26 SEC..z22 T12N R3W
DAVID HOPKINSON
Ground water at 12 ft
Use 5 -Wide Pressurized with 2 feet of Rock
Use 2 -Feet of Filter Sand
Soil Rating. From test April 6, 1994
6.6 min/in
Use .8 gal/ft.sq
Required Area per Bedroom:
150/ .8 = 187.5 sq.ft..
Number of Bedrooms 4
Absorption Area 4 x 187.5 = 776 sq. ft.
Reduction Factor .7
Required Bottom Area: 776 x .7 = 543
Required Length: 543/5 = 109 ft.
SYSTEM CONFIGURATION
5 -WIDE
TOTAL LENGTH 109 FT.
USE 2 TRENCHES EACH 55 FT.
TOTAL WIDTH 5 FT.
SEPTIC TANK 1500 GAL STEP.
Import 2 feet of "Filter" Sand from Qufiity Sand
/�. �! �� ► and Gravel Wasilla, or "Lake Otis" gsand I IXR
6 inches of d.Concrete-Sand::and \
�Sl X24 inches of sewer rock�C
l" 3 feet of cover
The installation of this well and septic systems will not prevent
wells and septic systems from be installed on the adjacent lots.
The proposed septic system will not change the general slope of
the area. Ponding and/or concentration of surface runoff will not
result from this installation.
PRESSURE CALCULATIONS
Total head loss: 30 ft.
Pump delivery at 30 ft. From pump curve: 33 gpm
Discharge per 1/811 hole at 5 feet of head: 0.42gpm
Number of holes: 33/0.42 = 80
Spacing of holes: 110x12/80
110x12/80 = 17[inches]
VrA — 1—D, -`�S � , ,*A 01141 Lt 1 lc�.�
Septic System Design
pg.'
LEVEL
h
In
1 #2
I
I
I
I
I
Replacement Site
I
ITesthole #1
lil
I
I
I
1 I 1 I
I
25 0 25 50 75 100 125 150
SCALE• 1 = s0 FL I
L _— L
L — — — — — — ——————— — — I
—
—�
— —i— — — — — — — —
TOBBEN SPURKLAND P.E. E 220, S 396, LOT 26 SEPTIC SYSTEM DESIGN
203 W 15TH. AVENUE DATE: JULY 15, 1994
ANCH. AK. 99501 SEC. 22, T7KR3W
___ __._ DAVE HDPINSON SHEET: 2/3 GRID: 2637
�TI
I III OQ II I II II
—O�C OOS
O
Welo O \
q�
OT
2
Lar Zs LaFLY
--
I
I II
I III , i
I
Well
(D I i
II I LaT 2
I
� lY I III I I
112TH, AVE
III �
I
so 0 �0 1190 Iqo 2s0LOT309 I LOT 7 LOT 8
ly
so
SCALE- 1' = 100 FT �� q r\
LOT 3 LOT 4 I I 7
7
—
J
I LOT 6LOT �'LOT 8 I LOT 5
P II
TOBBEN SPURKLAND P.E.SEPTIC SYSTEM DESIGN
203 W 15TH. AVENUE E 220, S 396, LOT 26
ANCH. AK. 99501 SEC. 22, T12N, R3W DATE: JULY 15, 1994
„_„ DAVE HOPKINSON I I SHEET: //3 GRID: 207
55
5
• O r-� A 118" Holes @ 17* O
on
A r
K6,
2 5-V/IDE TRENCHES
5 FT WIDE
55 FT LONG
2 rr OF ROCK
FT /L IDENPDTH
3FTFOFCRA
24' Sewer Rock -
1-1/4" Distribution Pif
Hiroo 140
2' "Filter Sand
10
A 1/8" Holes ® 17"
W
T
/ 6" Hollpipe
��— 1-1/4 PVC Holes Pointing Vp
SECTION A -A %
NO SCALE
3' Cover
/— 4" Topsoil
Discharge
1500 Gal STEP
rel
0
BENCH MARK:
BOTTOM SIDING
0 1' `'"e I.L.
E220' 5396 LOT 26 I I SEPTIC SYSTEM DESIGN I
203 Wa Ave SEC. 22 T12N R3W DATE: JULY 17, 1994
��gh 39, 6 Ak 99501 DAVID HOPKINSON SHEET. 3/3 GRID: 207
-1H
1
Municipality of Anchorage
DEPARTMENT OF HEALTH & HUMAN SERVICES
825 ••L•• Street, Anchorage, Alaska 99502-0650
SOILS LOG — PERCOLATION TEST
`1M
.'(ENGINEER'S SEAL).42
1
CL
T.'.... �nJ c. ,✓
PERFORMED FOR: Pnkiyn So✓1 . -bo—y -d DATE PERFORMED: 1 i4q. '
1.♦
LEGAL D
1
2 / Lo 0. w1
3
4
lro?`ti�
y 5
6-
71 7
8
11
12
13
14
15
16
17
18
19
20
COMMENTS
I LoTt p4. Township, Range, Section: j )
SLOPE
WAS GROUND WATER
ENCOUNTERED? 0
S
IF YES, AT WHAT L
O
DEPTH? p
E
Depth to Water All
Monitoring? Date: 9
PLAN
PERCOLATION RATE (minutewin�ch)�P�ERC HOLE DIAMETER
TEST RUN BETWEEN FT AND FT
PERFORMED BY: -- `#—s 1 CERTIFY THAT THIS/TEST WAS PERFORMED IN:
ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE(
72-008 (Rev. 4185) `1
Y.
:. 741 w 2
a Municipality of Anchorage
DEPARTMENT OF HEALTH & HUMAN SERVICES
825 "U' Street, Anchorage, Alaska 99502-0650
SOILS LOG - PERCOLATION TEST
(ENGINEER'S SEAL!
PERFORMEDFOR: p ✓� H Sin i �✓0.�l t DATE PERFORMED: b l
1 ownsa Section: n
LEGAL DESCRIPTION: E o�D $ 3Wb 2re Township, P. Ran 9 o' -d ` I I; -N { t2 3 ✓�
SLOPE SITE PLAN
Lcf0.w�
1
2 /
3-
4-
5-
6-1 456 1 `
7-
8-
9-
10-
11 8 91011 ,
12-
13-
14-
15-
16-
17-
18-
19
213141516171819
20
COMMENTS
WAS GROUND WATER
ENCOUNTERED?
S
IF YES, AT WHAT L
O
DEPTH? P
11'' �� /C' II ///� E
Bo 4'1 o --t . �`�'i' �'t OIC Depth to Water Alter
Monitoring? Date:
PERCOLATION RATE (minutesimCh) PERC HOLE DIAMETER
TEST RUN BETWEEN FT AND FT
PERFORMED BY: 1 CERTIFY THAT THIS =WSMED IN
ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE:
72-008 (Rev. 4185)
• I (ENGINEER'S SEAL)' "-
Municipality of Anchorage
DEPARTMENT OF HEALTH & HUMAN SERVICES
825 "L:' Street, Anchorage, Alaska 99502-0650 i
SOILS LOG — PERCOLATION TEST
\� \ ,Q alb 1 g'
PERFORMED FOR: O p �I vl C vN •1��✓ r DATE PERFORMED:`
LEGAL DESCRIPTION: E42201 S 3 9 L L.4 Township, Range, Section: 1 3 L_ Se c.,z';�
SLOPE SITE PLAN �—
DEPT
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
COMMENTS
WAS GROUND WATER
ENCOUNTERED?
S
IF YES, AT WHAT L
O
DEPTH? P
E
�,,D
BO ' +f ' 4 4"1e Depth to Water After
Monitoring? Date:
PERCOLATION RATE (minutes/inch) PERC HOLE DIAMETER
TEST RUN BETWEEN FT AND FT
PERFORMED BY: I CERTIFY IHAT THIS TEST WAS PERFORMED IN
ACCORDANCE WITH ALLSTATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: 7 /If
72-008 (Rev. 4/85)