Municipality of Anchorage
On -Site Water and Wastewater Section • (907) 343-7904 Page 1 of 3
ON-SITE WASTEWATER INSPECTION REPORT
Permit Number: OSP201179 PID Number: 018-331-08
Dwelling: ❑ Single Family (SF) ❑ with ADU ❑ Duplex (D) ❑ Two Single Family Project: ❑ New ❑ Upgrade
Name
Merit Homes, LLC
ABSORPTION FIELD
❑ Deep Trench ❑ Wide Trench ❑ Bed ❑ Mound
Site Address
4020 Rabbit Creek Rd. Anch., AK 99516
❑ Other
Phone
Number of Bedrooms
Soil Rating
Total depth from original grade
(907)334-9233
4
1.2 GPD/SF
7.5 Ft.
LEGAL DESCRIPTION
Depth to pipe invert from original grade
3.4 Ft.
Gravel depth beneath pipe
4.1 Ft.
Subdivision Block Lot
Lot 193 Less E 30'
Fill added above original grade
2.0 Ft.
Gravel length
50 Ft.
Township Range Section
12N 3W 33
Gravel width
5.0
Beds: Number of Lines
Distance between lines
SEPARATION DISTANCES
Ft.
Ft.
To
Septic
Absorption
Lift Station
Holding
Sewer
Total absorption area
Number of trenches
Dist. between trenches
From
Tank
Field
Tank
Line
500 Ft2
1
Ft.
Well
>100'
>1 00'
N/A
N/A
>25'
TANK X Septic El S.T.E.P. ❑ Holding ❑ Other
Manufacturer
Greer
Capacity
1,250 Gal.
Surface Water
>100'
>1 00'
N/A
N/A
Material
Number of compartments
Lot Line
>5'
>10'
N/A
N/A
NA
Plastic
2
Foundation>
1 0'
>1 0'
N/A
N/A
LIFT STATION
Manufacturer
Capacity
Remarks Pitless for well installed by Red Dog Masonry
Gal.
@ 10' TD. Pitless manufactured by Campbell.
Alarm location
Electrical installed by
Installer
PIPE MATERIAL House to tank D3034 Tank to D3034
drainfield
Red Dog Masonry
Drainfield D3034 CO/MTD3034
Inspector L. Tidwell
BENCH MARK (Assumed elevation) 100 ft
Inspeates
d 151 4/6/20 2nd 4/7/20
Location and description
3ro 4th
Top of Foundation
ON-SITE WATER AND WASTEWATER SECTION APPROVAL
Engineer's Stamp
Conditional Approval:
01-.......�9(
Date
0-0
•"
49th
�....a...r.................../ . �w..9...n
................... ......................'..... ffi
MICHAEL E. ANDERSON ffi
���- ; No ass, ,::��`"
���TF•'°••.,
Septic System Q n
Approved ���1 C C�, ��an
Date 2 I��21
1/13/21 ,.••''��
Note: this approval does not include well permit requirements.
®��
Tl 2N R3W SEC33, LOT 193 LESS 301
RABBIT CREEK ROAD,
33'ROADWAY EASEMENT -PATENT 1148546 (BK 19T, PG 31-0)_
TEGORY III
ALTERNATE SITE CA
SEPTIC SYSTEM W/24'L��ONG EAST 30'NOT
INCLUDED
WIDE x.5'EFFEC-VIVE DEPTH
ABSORPTION TR
RATE 5 GPD/SF.
EXISTING WELL
MT
col
EFFECT! DEPTH
4-BDRM HOME
1,2501GALLON SEPTIC
1170
000
LOT 193
`OFIV0 VA 0 50 10000'% him hem 11 I`EEI1113121
A B
FCO
14.5
10.0
C01
44.65
53.5
MH
57.0
66.3
SV1
61.4
71.1
2CO
64.15
73.85
CO2
85. 5
95.85
ivi 11
90.15
100.3
MT2
29.2
141.1
CO3
134.3
146.0
LEGEND
cV'CLEANOUT
xro'DOUBLE CLEANOUT
FCO ' FOUNDATION CLEANOUT
w*'MANHOLE
mT-mow|TomwsTuos
nv'SEPTIC VENT
To TEST HOLE
82.6
Al.I e, -, - ENGINEERING
T12N RM SEG 33 LOT 193 LESS 30'
P I D # 018-331-08
O�
88.0 FINISH GRADE
�— 86.0 ORIGINAL GRADE :E0 c)
n n
-�— 78.5501 78.5
r'
GROUNDWATER @ 71.5 10/22/19
71.0
PROFILE AS -BUILT
(NO SCALE)
E N G I N E E R I N G
PO BOX 240773
ANCHORAGE, AK 99524
522-7773 677-7766 (FAX)
January 10, 2021
MOA Development Services Dept, On -Site Water & Wastewater Program
4700 Elmore Rd
Anchorage, AK 99507
Subject: T12N R3W SEC 33 Lot 193, Less E30'— 4020 Rabbit Creels Road
Septic System Design
Dear On -Site Services Engineer:
The owner of the above lot intends to build a 4 -bedroom home on the property. We are submitting
this permit application for the construction of a new well and septic system. The attached site plan
identifies the location of the home and the proposed well, septic location and alternate site. No
conflicts exist between this proposed system and any other well or septic system on this lot or
adjacent lots.
The ground surface on the lot slopes to the southwest at grades greater than 25% within 50 feet
downslope of the primary and alternate sites. The absorption trenches have been designed to meet
the steep slope provisions of the Municipal Code. In addition, slopes greater than 46% are within
100' of the absorption sites. The subsurface soils in the area however are clean gravel with very
good absorptive characteristics. No horizontal migration of effluent is expected. The attached
slope analysis diagram shows the distance from the edge of the absorption trench to the steep slope
to be 20'. At its closest point the north end of the trench is 20' from the slope. The majori of
the trench is more than 20' from the edge of the steep slope. aE S I op e_
Subm%�-Aea u3/ deslr u3a.� Conserv�lve c�ncl co�1vu)s4vAled bcaJftr),— VMC-.
Ground surface contours are shown on the site plan indicating the grade and direction of flow. (/I? ( U2.
Storm water drainage will not impact this septic system. The new trenches will be constructed t
parallel to the slope as much as possible.
Wells on this and adjacent lots are shown. The new system will be a minimum of 100' from all
wells and surface water, and more than 5' away from the septic tank.
Please refer to the attached test hole log and plan and profile sheets for the septic design. If this
design is followed, there will be no adverse impacts to adjacent properties.
Sincerely,
Michael E. Anderson, PE
03i 0 i1C21D '2: s:; 90%3'415-L12C,2 ALPINEIRILLIh!.G PAGE 9i/OIL
Alpine Drilling Enterprises
Well Log
Perntii Number: 4SW2qjj '0 Dafe. of Issue, 6-17-20 Parcel Ideiatifica.tion Number, 0.18:3-3106000
17atc3 Started° fi-��-1?0 ste.C'o3ZappHetE;cH: G -?Q- O_ Is well looated at approved pennit location? x. dies El No
Legatl Description- T 2N R3W SEC 33 Lt193 Less F30'
Prc>ge y (Owner Ptis>we & AdAress: Verit Homes LLC
Burebole luta:
Depth (ft)
Soil .type, Thickness & Wator StrMa
}"Tom
To
slick up
0
�>
gr•uvell}'silt
2
�1
silt)= V'm el
21
55
gravelly silt
55
MI
siXay grafi el
%;
95
eobb?y gravell
95
120
gravelly silt
120
149
Sill
1119
160
gravelly silt mull uiid J-120
160
163
sill
I 11;3
!S
water scud & gravel
&5
1113
vdarER QUALITY TESTING
Coilibrm YVel CoUiMmL
i,mrates Nr5 rrjL
A'rssrtic N P ug/L
n -1 -0q -
Y
Meth od ref Drifling x :air rotmv ❑ caL",.e total II
Casing type:gte—el
)Alall Ttziokness:.250 inclies
Diamt:ter: h inches Depth- 19j feat
Liner Type: _
Diameter: __ inches Depth: Leet
C ssing. stickup above ground.: 2 feet ---
�� Static water Level (f om, ground level): I615_feet
Pumping level:_:190 feet after
2 hours pumping 100 Bpm,
Recovery Rate: jOO gpm
Method of Testicle: air lift
Well Intake. Qpeni..ng Type:
a Open End ❑ Open Hol;: 4
Scrortaed Start feet "ti>pped -- feet )
❑ Perfam ons stall _feet Stopped Feet q
GrDut Type: bentonite !mrurlc. Volume.: 2 bgs
Purmpr Intake Deptb __ feet
F'ump sire_ _ hn fi.rand dame, _
14ye>l Disineected TTpon Comptetioti? x Yes No
Method of DhLnH'eetion: c1�le, ilia t.Yrt lets
Cann mems:
Well Driller: Alpine Drilling & E!aterpr•ises
F0 Box 110496
nch&rua?e ,4 99511
0 7 ,, 1=,8.::0'21 *,.-j 02: S'--- ,01 -.3 4 5 - 0,17, "_-T2 ALPINE DRILLIN.,'-, . �jAJi-. ,J'*.' U2
MUN I—lp A
q,.o ALITY OF ANCHORAGE
Phone: 90-72343-7904
wo
DevelopMeTit Services Deparinnellt
Water &IA/a,,tewater Section Fax: 907-343-7997
Pur np Install,,-.1tion Log
201179 6 -17.2020
Nx/;:Jj Drffilngff Pan-& Numb— - Dateof INsue.
Parcul identifivatim Number; 019 -391268
Block j,pt propp-rty OwnerNaine
Tj 2i 4 R3W Ser, 33 U! 93 merit Homes LLC
Less E30' P,O. Box 220128
Anchorage, AK 99520-0128
-23 2010
; Y0 casing.- 170 --
"Sugin TiAlthe'Deptb BeJow Top of I feet
u
o u s
Piunp.Manufacturer's NaMe" GL
rump .mtudel: 'IHS07
'Fumv Size- 3/4 �v
,
llitle5s Adapter Barial Deptlw N/A f .-- t
llidcss Adapfr,,' Name; N/A
hitless AdapmrkliMfflev:
Weill Disinfected Upoll COMP[etiMA? Cl yes F1 NO
Method of Disinfection: chlorine tablets
commeats.,
PLEASE SAVE FOR COSA
Pump lusbiller N .91he,
Aarow Pump & Well LLC
Main ing Address*, 1P, 0, Box 1-104-96
Andhorage— K 9951
. 1�ta If La -s ofpw . 1L
T . )P1.0"'idle a vornp iwial' tic,.tt log to Oa-slw vithin 30 days mp mlt-5ta!14
n
J
Q
m p
J �
Q p
UW
LL.=
O~
W U
2 �
OQ
C7 O
Z
� p
O0
UO
U U
Q W
w
Z W
Q 0
O ir
LLI
�O
mol
LLI
MaNLL.
=Q M
W H L,
NZO QN
W
W
�W� _
U� ~
C�
W OJ (~j Z
LD
ZU� a.
ZN W
.mpX
W
�O
Z W
N =
EL
2 �
N
ON
~ Z
W
W
O Z
U Q
W
V) p
Z
LL.
C) O
O
00
6
rn
N
w
O
O
0
O
0
rn
VA
0
0 03amONI lON SOC 1SV3
,00'L6Z Mii9-V,80o00 N
w
H
r�
H
H
..
AV ._ •. o .
AV
v� E5
• • (.7ON •
ID
o
�; a1N
0):AIF
�.6 ••�. •�• rete.♦
Wb
ON
V
ZQ
Q U
�W
M�
W
H �
og0t-
o Q
F- Woz
Z d Y
Z U W W O Z� O Z g 0
QHQZZEONaZ� Q
lA
x 2 O V> V U=
O N D W Q= m O D W ~
a QLu z aW�oNN�`` 0 w
=;
MUNICIPALITY OF ANCHORAGE
On -Site Water & Wastewater Program
PO Box 196650 4700 Elmore Road
Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997
http://www.muni.org/onsite
On -Site Water & Wastewater System Permit
Permit Number: OSP201179
Work Type: WellSeptic Renewal
Tax Code Number: 01833108000
Site Legal Address: T12N R3W SEC 33 LT 193 LESS E30' G:3135
Site Mailing Address: 4020 RABBIT CREEK RD, Anchbrage
Owner: MERIT HOMES LLC
Design Engineer: FORGE ENGINEERING
This permit is for the construction of:
C✓( Disposal Field Q Septic Tank ❑ Holding Tank ❑ Privy
Effective Date:
Expiration Date:
Lot Size in Sq Ft:
Total Bedrooms:
n�cnt S'
C~0
lle-partIII C11t
6/17/2020
6/17/2021
95700
Q Private Well ❑ Water Storage
All construction shall be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80)
3. The wastewater code requires inspections during the installation. The engineer shall notify the Development
Services Department per AMC 15.65. Provide notification by, calling (907) 343-7904 (24/7).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
shall be either:
a. Opened and Closed on the same day, or
b. Covered, sealed, and. heated to prevent freezing
Received By: 1� �'; G`�
M__ avv
Issued By: J�IH —
Date: (01// -//ZZ2
Date: 6 7 b2
4
MUNICIPALITY OF ANCHORAGE
n
Community Development Department Phone: 907-343-7904
Development Services Division Fax: 907-343-7997
On -Site Water & Wastewater Program
ON-SITE SEWER/WELL PERMIT APPLICATION
Parcel I.D. 018-331-08
Property owner(s) Merit Homes, LLC Day phone 334-9233
Mailing address 1920 W. Dimond Blvd., Suite F Anchorage, AK 99515
Site address 4020 Rabbit Creek Road Anchorage, AK
Legal description (Sub'd., Block & Lot) T12N R3W SEC 33, Lot 193, Less E 30'
Legal description (Township, Range & Section)
Lot Size 95,700 Sq. Ft. Number of Bedrooms Four
APPLICATION IS FOR:
APPLICATION IS AN:
TYPE OF DWELLING:
(® all that apply)
Absorption Field
❑X
Initial ❑
Single Family (SF) ❑X
(w/wo ADU)
Septic Tank
❑X
Upgrade ElDuplex
(D) ❑
Holding Tank
❑
Renewal ❑X
Multiple Dwellings ❑
Privy
❑
(SF and/or D)
Private Well
❑X
Water Storage
❑
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
Distance:
I certify that the above information is correct. I further certify that this is. in accordance with
applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit/Rush Fees: t q5
Date of Payment:
Receipt Number: 6674Ga D
Permit No. 135pg6 !(--� I
Permit App_.;- : •
Waiver Fees:
Date of Payment:
Receipt Number:
Waiver No.
COVID-l9 l
257o' DISCOUNT APPLIED ?
MUNICIPALITY OF ANCHORAGE
On -Site Water & Wastewater Program
PO Box 196650 4700 Elmore Road
Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997
http://www.muni.org/onsite
On -Site Water & Wastewater System Permit
Permit Number: OSP191172
Work Type: WellSeptic Initial
Tax Code Number: 01833108000
Site Legal Address: T12N R3W SEC 33 LT 193 LESS E30' G:3135
Site Mailing Address: 4020 Rabbit Creek RD, Anchorage
Owner: MERIT HOMES LLC
Design Engineer: FORGE ENGINEERING
This permit is for the construction of:
Effective Date
Expiration Date:
Lot Size in Sq Ft
Total Bedrooms:
��»cnr
o�
,j
■ v.
Department
5/16/2019
5/15/2020
95700
Q Disposal Field 0 Septic Tank ❑ Holding Tank ❑ Privy R1 Private Well ❑ Water Storage
All construction shall be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80)
3. The wastewater code requires inspections during the installation. The engineer shall notify the Development
Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
shall be either:
a. Opened and Closed on the same day, or
b. Covered, sealed, and heated to prevent freezing
0
00-#1 n ' cI� P4h c W; 3,1
0o ©� e �
C�e,c.� �'v�,vvwaA t o �� e � O�}1 � Yl �•J l�-'E.Q-Q C� r'•t � I e ci �-JJ S� � h
x,.51-{�P,,210 210
Received By: Date: �1
Issued By: Date: 1� �/
MUNICIPALITY OF ANCHORAGE
s
Community Development Department Phone: 907-343-7904
Development Services Division Fax: 907-343-7997
On -Site Water & Wastewater Program
ON-SITE SEWER/WELL PERMIT APPLICATION
Parcel I.D. 018-331-08
Property owner(s) Merit Homes, LLC Day phone 334-9233
Mailing address 1920 W. Dimond Blvd., Suite F Anchorage, AK 99515
Site address 4020 Rabbit Creek Road Anchorage, AK
Legal description (Sub'd., Block & Lot) T12N R3W SEC 33, Lot 193, Less E 30'
Legal description (Township, Range & Section)
Lot Size 95,700 Sq. Ft. Number of Bedrooms Four
APPLICATION IS FOR:
APPLICATION IS AN:
TYPE OF DWELLING:
(® all that apply)
Absorption Field
❑X
Initial ❑X
Single Family (SF)
❑X
ADU)
Septic Tank
❑X
Upgrade El(w/wo
Duplex
ElHolding
(D)
Tank
❑
Renewal ElMultiple
Dwellings
❑
Privy
❑
(SF and/or D)
Private Well
19
Water Storage
❑
THIS APPLICATION INCLUDES
A VARIANCE / WAIVER REQUEST FOR:
Distance:
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit/Rush Fees: 0'5--f g 5- Waiver Fees:
Date of Payment: 6_17'1/9 Date of Payment:
Receipt Number: 60g3LgD Receipt Number:
Permit No.Sp Ali?g Waiver No.
Permit App_.;- :- :'_.,:c;
January 8, 2020
MOA Development Services Dept, On -Site Water & Wastewater Program
4700 Elmore Rd
Anchorage, AK 99507
Subject: T12N R3W SEC 33 Lot 193, Less E30'— 4020 Rabbit Creels Road
Septic System Design
Dear On -Site Services Engineer:
The owner of the above lot intends to build a 4 -bedroom home on the property. We are submitting
this permit application for the construction of a new well and septic system. The attached site plan
identifies the location of the home and the proposed well, septic location and alternate site. No
conflicts exist between this proposed system and any other well or septic system on this lot or
adjacent lots.
The ground surface on the lot slopes to the southwest at grades greater than 25% within 50 feet
downslope of the primary and alternate sites. The absorption trenches have been designed to meet
the steep slope provisions of the Municipal Code. In addition, slopes greater than 46% are within
100' of the absorption sites. The subsurface soils in the area however are clean gravel with very
good absorptive characteristics. No horizontal migration of effluent is expected. Ground surface
contours are shown on the site plan indicating the grade and direction of flow. Storm water
drainage will not impact this septic system. The new trenches will be constructed parallel to the
slope as much as possible.
Wells on this and adjacent lots are shown. The new system will be a minimum of 100' from all
wells and surface water, and more than 5' away from the septic tank.
Please refer to the attached test hole log and plan and profile sheets for the septic design. If this
design is followed, there will be no adverse impacts to adjacent properties.
Sincerely,
. .. �F..�L:�S°�i
Michael E. Anderson, PE`;` 49tH
MICHAEL E. ANDERSON
�n'•. NO. CE -4381 .'• _®
®�TFp 1/8/20 je.,..••'•����®
T12N R3W SEC33, LOT 193 LESS 30' C041
RAB IT CREEK ROAD,
33' ROADWAY E ASEME'NT-PATENT 1148146 (BK 197ZP 31-0-
\ T
\ � ALTERNATE SITE: CATEGORY/III � \
SE4!STIC SYSTEM W/24' LON i� AST 30' NOT `\I
\ ADE X.5- EFFECTIVE DEP .PROPOSED WE�L INCLUDED
\ /ABSORPTION TRENCH. � LOC-ATl9N (\
RATE 5 GPD/SF. \
J
/ EXISTING W/LL TO BE `� \
DECOMMIStIONED
\\ I TH2 I 0
MT
TH3 I CO
\ 2CO
S MH
\ \ \ FCO TH1 I
�0' LONG x 'WIDE x 4A,
\ ` EFFECTI DEPTH \ 4 -BDA Q -ME _
A \ \ ABSORPTION ENCH.
\\ \ 1,250 GALL SEPTIC
\ \ '�ANK W/20" M NWAY
lko 2 \ I
LOT 193
\ 10' T & E EASiMENT (BK 806,�G 435-4
.A.Aadrtun\forge logo.jpg
NOTE:
NO SURFACE WATER WITHIN 100' OF THE PROPOSED SEPTIC SYSTEM LEGEND
ALL WELLS ON SURROUNDING LOTS WITH IMPACTS TO THIS CO - CLEANOUT
PROPERTY ARE SHOWN. NO CONFLICTS WITH WELLS OR SEPTIC 2CO - DOUBLE CLEANOUT
SYSTEMS. FCO - FOUNDATION CLEANOUT
FS - FLOW SPLITTER VALVE
0 50 100 MH - MANHOLE
FEET MT - MONITORING TUBE
SV - SEPTIC VENT
1 "=50' TH - TEST HOLE
T12N R3W SEC 33, LOT 193, LESS 30' Co# 1
DESIGN FACTORS:
600 GPD PEAK FLOW
PERK RATE: 2-3 MIN/IN
APPLICATION RATE: 1.2 GPD/SF
SYSTEM REQUIREMENTS:
S WIDE TRENCH SYSTEM
1,500 -GAL SEPTIC TANK w/20" MANWAY
600 GPD / 1.2 GPD/SF / 5' WIDE *.5 RED. FACTOR = 50 LF TRENCH REQUIRED (50 LF SPECIFIED)
BOTTOM OF TRENCH: 7.5' BELOW GRADE LOW SIDE 8.75' BELOW GRADE HIGH SIDE
FLOW LINE ELEVATION: 3.5' BELOW GRADE LOW SIDE
TOP OF TRENCH: 0.5' ABOVE GRADE
nft 11 iH 1— —1 /r PY ---K Il l , -11
TYPICAL DEEP TRENCH SECTION
(NO SCALE)
NOTES:
1. GRADE AREA OVER TRENCH TO DRAIN AWAY
2. PROVIDE 3' OF COVER OVER TRENCHES AND 4' OVER SEPTIC TANK, OR 2'
WITH 2" OF INSULATION
3. CHECK GROUNDWATER AT TIME OF CONSTRUCTION. IF LEVEL IS HIGHER
THAN PREVIOUSLY OBSERVED, CALL ENGINEER IMMEDIATELY
�l J
(HOLES DOWN)
vi
•'''49th ••���
;f u
.... ........... .........................a
.� ;MICHAEL E. ANDERSON p (�
NO.1/9120
CE -4387 `
T
fir,
Lo
v
r
Ab
O��''.��.M
..O
•••S
Any
'IT
d
o
N • ? Z `r
_� c w
f
cLI
(D
a� d
eon
p
AY
AV
Q
®,
o
'L^
V
In
O
N
L
W
O
In
�
� z
07) W
o
Q
Oz
W
--JO
U Q
o
W
U
O
N
(w
N
-
n-
_0
0
F—
`n
o
-
r
_II o
o
Q�
~J
Z Q
O
J N�
O U) O ic)
N r- —0
In O
O i
0 N
U p W
co = >
r� r7 r7
N
DEPTH
(I'ect)
1-
2-
J -
4-
5-
6-
7-
8-
9-
10-
ll-
12-
13-
14-
15-
16-
17-
18-
19-
20-
MUNICIPALITY OF ANCHORAGE
DEVELOPMENT SERVICES DEPARTMENT
4700 ELMORE ROAD ANCHORAGE, AK 99519-6650
SOILS LOG AND PERCOLATION TEST
LEGAL DESCRIPTION: T 12N R3W SEC33 L193 LESS E30'
PERFORMED FOR: CHRIS PETERSEN
DATE: 10/1/19 PROJECT No.:
PARCELID#: 018-331-08 TECHNICIAN: L. TIDWELL
TEST HOLE #2
M-
-s"`i ORGANICS MIXED W/ GRAVEL
CV� 1
Stamp:
SITE PLAN
SEE SITE PLAN
U
COMMENTS:
DATE
READING
WAS GROUND WATER ENCOUNTERED? NO
NET TIME
(MINUTES)
DEPTH TO
WATER
(INCHES)
NET DROP
(INCHES)
IF YES n WHAT DEPTH? -
L
1
12:48/12:58
DEPTH OF WATER AFTER MONITORING: 17.0
0
3 15
2
DATEOFMONITORING: 10/22/19
P
5 16 / 8 16
314
3
E
10
COMMENTS:
DATE
READING
GROSS TIME
(MINUTES)
NET TIME
(MINUTES)
DEPTH TO
WATER
(INCHES)
NET DROP
(INCHES)
10/1
TEST HOLE PRESOAKED PRIOR TO TESTING:
1
12:48/12:58
10
5 16 / 8 16
3 15
2
12:59/1:09
10
5 16 / 8 16
314
3
1:10/1:20
10
519 / 812
312
4
1:24/1:34
10
5-%/8 / 8 16
3 16
5
1:35/1:45
10
5 16 / 8 16
3 16
6
1:46/1:56
10
519 / 81s
31s
PERCOLATION RATE: 2.9 (MIN/INCH) PERC. HOLE DIA. 6 (INCHES)
TEST RUN BETWEEN: 4 FT. and 5 FT.
MUNICIPALITY OF ANCHORAGE
DEVELOPMENT SERVICES DEPARTMENT
4700 ELMORE ROAD ANCHORAGE, AK 99519-6650
SOILS LOG AND PERCOLATION TEST
LEGAL DESCRIPTION: T 12N R3W SEC33 L-193 LESS E30'
PERFORMED FOR: CHRIS PETERSEN
DATE: 10/1/19 PROJECT No.:
PARCELID#: 018-331-08 TECHNICIAN: L. TIDWELL
DEPTH r TEST HOLE #3
(feet)
1
2
J
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
ORGANICS MIXED W/ GRAVEL
Stamp:
SITE PLAN
SEE SITE PLAN
i
U
COMMENTS:
DATE
READING
WAS GROUND WATER ENCOUNTERED? NO
NET TIME
(MINUTES)
DEPTH TO
WATER
(INCHES)
NET DROP
(INCHES)
IF YES n WHAT DEPTH? -
TEST HOLE PRESOAKED PRIOR TO TESTING:
1
12:46/12:56
DEPTH OF WATER AFTER MONITORING: 14.5
0
41s
2
DATE OF MONITORING: 10/22/19
P
416 / 8 6
4 A
16
3
E
10
COMMENTS:
DATE
READING
GROSS TIME
(MINUTES)
NET TIME
(MINUTES)
DEPTH TO
WATER
(INCHES)
NET DROP
(INCHES)
10/1
TEST HOLE PRESOAKED PRIOR TO TESTING:
1
12:46/12:56
10
416 / 8 8
41s
2
12:57/1:07
10
416 / 8 6
4 A
16
3
1:08/1:18
10
4 16 / 8 16
41s
4
1:22/1:32
10
4-1/8 / 8 16
4 0
5
1:33/1:43
10
4 16 / 8 16
41s
6
1:44/1:54
10
4 16 / 8 16
41s
PERCOLATION RATE: 2.5 (MIN/INCH) PERC. HOLE DIA. 6 (INCHES)
TEST RUN BETWEEN: 4 FT. and 5 FT.
LEGAL DESCRIPTION:
PERFORMED FOR:
DATE:
PARCEL ID#:
SOILS LOG AND PERCOLATION TEST
TECHNICIAN:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
DEPTH
(feet)
PROJECT No.:
TEST HOLE 1
SLOPE
SLOPE
SITE PLAN
See Site Plan
DATE READING GROSS TIME
(minutes)
NET TIME
(minutes)
DEPTH to
WATER NET DROP
TEST HOLE PRESOAKED PRIOR TO TESTING:
PERC. HOLE DIA. (INCHES)PERCOLATION RATE: (MIN/INCH)
TEST RUN BETWEEN: FT. and FT.
COMMENTS:
(inches)(inches)
T12N R3W SEC33 L193 LESS E30'
4/30/19
J. Millette
Development Services Department
4700 Elmore Road Anchorage, AK 99519-6650
Municipality of Anchorage
DATE OF MONITORING:
WAS GROUND WATER ENCOUNTERED?
DEPTH OF WATER AFTER MONITORING:
IF YES @ WHAT DEPTH?
NO
-
none
6.7 6
5 6
018-331-08
Chris Petersen
Professional Engineers Stamp:
17:27
4/30
1
2
3
4
5
6
30
30
30
4 10
16
9 5
16 4 11
16
9 2
16 4 8
16
17:57
17:58
18:28
18:29
18:59
1' OB
5/6/19
SANDY GRAVEL
ORGANICS MIXED W/ GRAVEL
4 10
16
4 10
16
9 2
16 4 8
16
HARD PAN-
IMPERMEABLE
5/6/19
GW/GM
Municipality of Anchorage
On-site Water and Wastewater
REVIEWED FOR CODE COMPLIANCE
OSP191172, Rebecca Carroll, 05/16/19
Municipality ,of Anchorage
George~~. II uerch, Ma!lo~
Btfllding Safety Division
l'.O. I~)x 1,~1~,"30 * 4700 S. Ilragaw Street
Anchorage, Alaska !~.)51.0-CW~O * (907) 343.8301
6/7/2001 hnp://www,cl.anchomgc.ak.us
Depar,ment of
Public Works
Al Baez
2451 Tradewind Drive
Anchorage AK
Subject:
Expired On-Site Water and/or Wastewater Permit.
Permit Number: SW000076,
Parcel ID: 018-331-08
Dear Al Baez:
An On-Site Water/Wastewater Permit, number SW000076, issued by this office for a
single-family system, expired on April 25, 2001. This permit was valid for 365 calendar
days.
If this was a well permit and the well has been drilled, a well log must be sent to this
office for documentation of the installation and to close the permit.
If this permit was for a wastewater disposal system, an original as-built inspection report
must be sent to this office for review, approval and documentation. This as-built
inspection report must be signed by the licensed Professional Engineer who inspected the
installation of the system. As-built inspection repons are required to be submitted within
30 days of the completion of the system.
If no system was installed under this permit, and you are still planning to install a well or
wastewater disposal system, a new permit must be obtained from this office. When
applying for a new permit, the fees are: $320.00 for a wastewater permit and $120.00 for
a well permit.
If you have any questions, please call this office at 343-7904.
Sincerely,
~{Letters Sent 6/7/01 without copies being made, second printing for file copies}
James Cross, PE
Manager
On-Site Water and Wastewater Program
ene: Copy of permit
MUNICIPAUTY OF ANCHORAGE
Department of Health and Human Serv/ces
On-Sire Services Program
825 L Street, Room 502
P.O. Box 196650, Anchorage, AK 99519-6650
(907) 343-4744
ON-SITE WASTEWATER DISPOSAL SYSTEM I WATER SUPPLY PERMIT
Renewal
Date Issued: Apr25, 2000
Expiration Date: Apr 25, 2001
Permit Number: SW000076
Legal Description: T12N R3W SEC 33 LT 193 LESS E30'
Design Engineer:. 0041 AK Water & Wastewater Consulta
Owner Name: Al Baez
Owner Address: 2451 TRADEWIND DRIVE
ANCHORAGE, AK 99516-3402
Parcel ID: 018-331-08
Site Address: 004020 RABBIT CREEK RD
Lot Size: 95700 SQ. FT.
Total Bedrooms: 4 Permit Bedrooms: 4
This permit is for the construction of:
[] DisposalField [] SepticTank [] Holding Tank [] Privy
[] Private Well [] Water Storage
Ail construction must be in accordance with:
1. The attached approved design.
2. Ail requirements specified In Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations ( 18AAC72 ) and Ddnking Water Regulations ( 18AAC80 ).
3. The engineer must notify DHHS at least 2 hours prior to each inspection. Provide notification by calling
(907) 343-4744 ( 24 hours ). ( Not required for a Water Supply Permit only ).
4. Fram October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
must be either. A. Open and closed on the same day.
B. Covered. sealed, and heated to prevent freezing.
Received By:
Issued By:
Rick Mystrorn.
Mayor
Municipality of Anchorage
Department of Health and Human Services
825 "L' Street
P.O. Box 196650 Anchorage. Alaska 99519-6650
htr p://www.ci.anchorage.ak.us
December 30, 1999
BAEZ ALFRED A & CHRISTY JO
2451 TRADEWIND DRIVE
ANCHORAGE, AK 995163402
Subject:
TI2N R3W SEC 33 LT 193 LESS E30'
Permit# SW990069 PID# 1833108
The subject permit #SW990069 issued by this office for a single family well and/or on-
site wastewater system, is due to expire 365 days after it's issuance on 26-Apr-99.
If this is a well permit and you have drilled the well, a well log must be sent to this office
for documentation o f the installation and to close the permit.
If this is an on-site wastewater system and a licensed Professional Engineer has inspected
the installation, the original as-built inspection report must be sent to this office for
review, approval and documentation. All inspection reports must be submitted within 30
days of construction completion.
A new permit must be obtained from this office for a well and/or on-site wastewater
system NOT installed by the expiration date. However a new permit can be issued free of
charge for a second year if the application for the renexval is received on or before the
date of expiration of the original permit for which a fee was paid.
When applying for a new permit after the original permit has expired or for more than a
second year, the fees are: $320.00 for an on-site wastewater permit and $120.00 for a well
permit.
Ifyou have any questions, please call this office at 3434744.
Program Manager
On-site Services
eno: Copy of Permit
MUNICIPALITY OF ANCHORAGE
Deparfment of Health and Human Sen'ices
On-Site Services Program
825 L Street, Room 502
P.O. Box 196650, Anchorage. AK 99519-6650
(907) 343-4744
ON-SITE WASTEWATER DISPOSAL SYSTEM I WATER SUPPLY PERMIT
Initial
Date Issued: Apr26, 1999
Expiration Date: Apr 25, 2000
Permit Number: SW990069
Legal Description: T12N R3W SEC 33 LT 193 LESS E30'
Design Engineer:. 0041 AK Water & Wastewater Consulta
Owner Name: Al Baez
Owner Address: 2451 TRADEWIND DRIVE
ANCHORAGE, AK 99516-3402
Pamel ID: 018-331-08
Site Address: 004020 RABBIT CREEK RD
Lot Size: 95700 SQ. FT.
Total Bedrooms: 4 Permit Bedrooms: 4
This permit is for the construction of;
[] Disposal Field [] Septic Tank [] Holding Tank [] Privy
[] Private Well E] water storage
All construction must be in accordance with:
1. The attached approved design.
2. Ail requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations ( 18AAC80 ).
3. The engineer must notify DHHS at least 2 hours prior to each inspection. Provide notification by calling
(907) 343-4744 ( 24 hours ). ( Not required for a Water Supply Permit only ).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
must be either:. A. Open and closed on the same day.
B. Covered, sealed, and heated to prevent freezing.
D ,te:
Date: 4- - 2~- ~"~
Alaska Water & Wastewater Consultants, Inc.
6901 Debarr Road, Suite 2B ~ Anchorage ~ Alaska 99504
Phone (907) 337-6179 ~ Fax (907) 338-3246
Consulting Engineers
April 7, 1999
Municipality of Anchorage
Department ofttealth & Human Services
Division of Environmental Services
On-Site Services Section
P.O. Box 196650
Anchorage, Alaska 99519-6650
Reft Well and Septic System for Lot 193, Section 33, TI2N, R3W
PROPOSED BOTTOMLESS INTERMITTENT SAND FILTER SYSTEM
To whom it may concern:
1. GENERAL: The proposed 4 bedroom home will be served by a private septic system and a
private well. This property was issued a well and septic permit (SW910246) on 8/22/91 by your
department. This property was at one time partially developed and consisted ora building that has
been removed and a well which is still there. We propose to abandon this well according to
M.O.A. well ordinance and have a new well drilled in the location shown on the site plan and
design. This property has had numerous test holes and percolation tests performed over a major
portion of this lot. It has been found that the soils have very poor permeability. Given this site
constraint, we are proposing to install a Bottomless Intermittent Sand Filter (ISF) system.
Attached are copies of two soil logs and a total of five percolation tests performed by Tobben
Spurkland, P.E.. Two other test holes were excavated and percolation tests performed by our
company. The soils are summarized as follows:
2. SOIL CONDITIONS: Attached are logs which shows the soil profde, and the percolation
test results. Test hole #I was found to have unsuitable soils for an on-site septic system. In Test
hole #2, the soils below the organic layer are a SM/ML material to a depth of 13 feet (bottom of
the testhole). No groundwater was encounter6d during the excavation of the test hole. After 13
days, the monitoring tube in the test hole was checked and water was found to be at 10 feet. Two
percohtion tests were performed between the depth of 3.5 feet to 4.0 feet and at 6.0 feet to 6.5
feet in TH#2. The percolation rate was 12 minntes?mch in the upper bench and 120+
minutes?tach in the lower bench.
3. TRENCH DESIGN: Bottomless Intermittent Sand Filter (IS1e)
a. Percolation Rate: 12 minutes/inch
b. Allowable Application Rate for ISF: 2 gallons/day/fi2
c. Number of Bedrooms: 4
d. De. sign Flow: 600 gallons per day _
e. Minimum Absorption Area: 300 fi2
f. Effective Depth below pressure pipes: 3+ inches
g. Width: 10 feet
h. Length: 36 feet.
i. Effective absorption area = 360 it2 (>300 fl2 OK)
j. Air Supply: Thomas Industries, Model 5070, "Anchorage Tank".
k. Air Supply Line: "Wasteflow" emitterlinc, 1/2 inch I.D, "Anchorage Tank".
I. Sand Material: M.O.A. Approved Sand Filter
m. Pea Gravel: 100% passing 3/8" sieve, less than 20% passing the 1/4" sieve, and
less than 1% passing the//8 sieve.
We are proposing to excavate down to a depth of 1.5 feet (remove all organics), place a minimum
of 6 inches of sand, install the air supply line, and cover it with 1.5 feet of sand. On top of the
sand, we will place 6 inches of 3/8 inch pea gravel, with the pressure laterals midway in the layer.
We will use a conventional lift station (Anchorage Tank), equipped with a programmable timer so
that flow can be intermittently dosed to the ISF.
4. MATERIALS AND CONSTRUCTION PRACTICES: The materials used, and the
construction practices will comply with DHHS' "Intermittent Sand Filter Design, Installation &
Maintenance Manual". The contractor should read this document prior to construction. Copies
are available at the Municipal Onsite Services office (Sth floor, 9th & L St.).
5. SURFACE WATER: There are no surface waters within 100 feet of the proposed septic
system.
6. TOPOGRAPHY: There is slope that is greater than 25% approximately 50 feet southwest of
the test hole #2. The slope in the area ofthe proposed septic system is a 5-10% grade running
approximately from northeast to southwest. We request you issue a 35 foot waiver to a slope
greater than 25% to insure adequate area for the new drainfield. The proposed drainfleld is to be
installed parallel to the slope contour.
7. CLOSING: I am open to any suggestions from your department that would be an
improvement to the propgsed system. I am unaware of any negative impacts that this installation
would impose on adjacent wells, or septic systems. If you have any questions, please call me at
337-6179. .I/I
S' ,
~ '~. LOT 190. S~CTION 33. T12N, ~ LOT 191. Sr'C~ON
~ RABBIT CREEK ROAD
~T~,~i~
LOT ~9~, SECTION 33, TI2N, R3W
AL BAEZ ~45-6054
%'~2'....: ........
RABBIT CREEK ROAD
I~ =ERCOLATION TESTS
PflOPOSE~ I \ DONE BY TOBBEN
W~LL LOC~T',O~ ~ I SPURKLAND. P.E.
I
U3 I
--~' I
IDiS"nN0 WiLL TO BE-*-t
~DONED COMPLE'~LY [
...J Wrll OROINANC[
._J
hi
'- _'- .... 4 BDRU~ ~
'"--._.._ HOUSE
IN~U TED
(SEE DETNL ANO PRORL.~ PAGE 3 OF 3)
.MASKA WATERAND WASTEWATER CONSUlTANTS, INC. ~~.
PHONE: (gOD 3,~7-817g/}"AY: (gOD 3,.38-3246
LOT 193, SECTION 33, T12N, R3W,
P~N VIEW
PROFILE VIEW
AL~KA WATER. & WAS'IF. WATER. CONSULTANTS~ INC. ,=',-~"'"' ~ uF...~/. '~ '-%'~':,'~,,
pHQNE (907) ..~7-6179 · FAX (907)
[SOIL LOG - PERCOLATION TEST] [~'7 491 l,];~. "..'~.~,
LEGAL DESCRIPTION: LOT 193. SECaqON 33. 712N. R3W F'~C ....... ; '- j[' ~ ';."'
PERFORMED FOR: AL BAEZ ~: .~ .~---~
DATE PERFORMED: 7/23/98 k~, :.. NO. g608 .~-:
I I
..... TEST HOLE #1 ',,--' ........
1-
2 --.,.,~? ,
. t ' .~ '~'o ' GW ..... ORG
,',C,~! ~ GP III1111ML
,,, ,; ,'~ / GC .I , OL
,,,,~,, ; SH/HL SM SITE pLAJ~
,,,t'~t, ' W~TH ~ S~LT
~ LENSES & LITTLE
'~"~ ; GRAVEL (BECOMES DEPTH TO DATE
7-- '~!t~l~° ' t DENS~ WI DEPTH) GROUNDWATER
8--, ~it ,~ DRY 7/25/98
.t' ' oRY e/4Da
10-- !t i,
' '",,
~ ' ; CLOCK NET TIME WATER LEVEL NET DROP
11 --,~,t~l. i DATE READING
,;.~ TIME (MINUTES) READING (INCHES)
,"I'I1"~'.~ i 7/24/gE, - PRESO~ KED OVERNI HT
12--,,1%11~ I .
, I~,1~ 7/24/g8 - PERC ENCH BE-~! £N ~HE DEPTH OF 6.0 FEET TO 6.5
- B.O.H. LOWER 1 5:01 6'
BENCH 2 5:~1 ~0 MIN. 5 3/4' 1/4'
1~-! --I a ~:Ol ao ~N. 5 5/8' 1/8'
15--
8?4/98 - PERC BI ~CH BL--~gEE N THE DEFTH F' ,3.5 FEET TO .0 FEET
16 -- UPPER I 3:25 8
BENCH 2 3:45 20 MIN. 8 1/2' 1/4'
,3 4:15 ,30 MIN. n' 1/2'
17-- __
,3 4:45 ,~0 MIN. 7 1/2' 1/2'
18--
19-- PERCOLATION RATE 120+/50+(HIM.lINCH) PERC. HOLE DIA. 6' (INCHES)
20---- TEs =.5'-4.0' . .
PERFOMED BY ALASKA WATER & ~ASTEWATER I. K(~*~L~4 I , k,l\t~'~ .
CER'~FY THAT
xzms~ wx~_~ m WAS~WATm~ co~sur~xwrs, ~c.
ISOIL LOG - PERCO~TION TESTI
PERFORMED FOR: ~ ~ P
~ :-~'~'~:~ ~o~cs ITEST HOLE
3-- :.t~,:"~, ~ GP ~ ML
4-- .,,;,, GC '1'1' ~
6 ,,.,.~;t ~ SlL~ ~ SC ~ ' = I~'
7 ,~, .,,,, ~ DE~H TO
w/~H) DATE
?.,, · SRO~WATER
--' · .," 7/23/98
''" "' 10' 8/4/98
,t;'~;~.'~ - ....
'""' "' CLOCK N~ TIME WATER ~EL NET DR~
11 -- [:t,: ';,~ DATE ~ING TIME (MIN~ES) RE, lNG (INCHES)
~;,;t,t 7/24/98 - PERC ENCH B~I EN
12-- ,.... ...............................................................
',t .,:'~,~ LOWER 1 32~.- ~ ........
~- ~ B.O.H. BENCH ~_ _~:~.~
14-- 8/4/98 - PERC BI ~CH B~EEN
UPPER 1 3:45 ~ 6'
15-- BENCH 2 4:15 30 MIN. 3 1/2" 2 1/2~_
~ 3 4:16 ~ 6'
16-- 3 4:~6 ..... 30 MIN. 2'
17~ ~ ........
18--
19-- , ~TI~ ~TE 120+/12 (MIN./IN~) ~. H~ DI~' . 6' .(l~)
T~T ~ B~ 6.0'-6.5'.~. ~D 3.5'-4.0'..~.
20--~ ~
DA~. DA~
Mun c pa ' y Ancho 'age
Department of Health and Human Services
825 "L" Street
P.O. Box 196650 Anchorage, Alaska 99519-6650
343-4744
August 24, 1992
Tome W. Rueter
PO Box 103644
Anchorage, Alaska
99503
Subject: T12N R3W Section 33 Lot 93 Less E 30'
Permit ~SW910246, PID #018-331-08
The subject permit, issued August 22, 1991 by this office for a
single family well and/or on-site wastewater system, has
expired as of August 22, 1992.
A new permit must be obtained from this office for a well
and/or on-site wastewater system NOT installed by the
expiration date.
If you have drilled the well, a well log must be sent to
this office for documentation of the installation and to
close the permit.
If a licensed Professional Engineer has inspected the
installation of the on-site wastewater system, the original
as-built inspection report must be sent to this office for
review, approval and documentation. All~ inspection reports
must be submitted within 30 days of construction completion.
When applying for a new permit, the fees are: $200.00 for an
on-site wastewater permit; $75.00 for a well permit and
$275.00 for a combined on-site wastewater and well permit.
If you have any questions,
Sincere l~y, / J
~?hn Smith,/P. E. /
~ogram Manager
On-site Services
please call this office
at 343-4744.
enc: Copy of Permit
PAGE 1 OF 1
MUNICIPALITY OF ANCHORAGE
DEPARTMENT OF HEALTH AND HUMAN SERVICES
P.O. BOX 196650, 825 "L" STREET, ROOM 502
ANCHORAGE, ALASKA 99519-6650
ON-SITE WELL AND WASTEWATER DISPOSAL SYSTEM PERMIT
PERMIT NUMBER:SW910246
DESIGN ENGINEER:TOBBEN SPURKLAND, P.E.
OWNER NAME:RUETER TOM W & TOSHIKO
OWNER ADDRESS:P.O. BOX 103644EK RD
ANCHORAGE, ALASKA 99503
DATE ISSUED: 8/22/91
EXPIRATION DATE: 8/22/92
PARCEL ID:01833108
LEGAL DESCRIPTION: T12N R3W SEC 33 LT 193 LESS E3
0'
LOT SIZE: 95700 (SQ. FT.)
NUMBER OF BEDROOMS: 5 THIS PERMIT: 5
THIS PERMIT IS FOR THE CONTRUCTION OF:
DISPOSAL FIELD /SEPTIC TANK / WELL SYSTEM
ALL CONSTRUCTION MUST BE IN ACCORDANCE WITH:
1. THE ATTACHED APPROVED DESIGN.
2. ALL REQUIREMENTS SPECIFIED IN ANCHORAGE MUNICIPAL CODE CHAPTERS
15.55 AND 15.65 AND THE STATE OF ALASKA WASTEWATER DISPOSAL
REGULATIONS (18AAC72) AND DRINKING WATER REGULATIONS (18AACS0).
3. THE FOLLOWING SPECIAL PROVISIONS.
SPECIAL PROVISIONS
RECEIVED BY:
ISSUED B¥::~ :
DATE:
{?(7~ S!7'!- _'-? i a
'f [J l'i RIJETER
TO-//~L LEHBI'H 80 FT~
rO-t' AL [,.~ l D'I- I{ 2.4
1-i]TAL bEPVH 2 F'F.
COVER 5 FT.
STEP i'ANK .tT::]O 6AL
\
L~TT
LDT ]9]
0 SET]£ SYSTEM
Lf]T 194
LDT ]93
LD? £i9
I~.~,,~,,~"..~,.~,~1.=~ ~ -- ~
0 50 ]00 150 ~00 ~50 $00 3.50
S£ALE~ 1.' -- I00 FT,
PRflPERTY HAS Nlgl' BEEN SU£VEYE]9,
LIlT Cfl£flERS ARE MDT STAKED
STAKE CDf~NERS AND LI?TLINES
Pf~II?A~ TI] ANY CDNST~UCTIDN
~ ?IDN ~
1750
STEP
S6ALD I~ -- 50 FT.
PtPI]PEI~TY HAS NDT ~E£-N £Uf?V£Y£~,
LDT £DfaNE,q'£ ARE NDT ~fAKEB
2TAKE C~¢NE~2 AN¢ LBTLINE~
PBIO~ TO ANY CDNST~UCTI~N
TB]~BEN SPUI;?Kt_~N]) P,E,
6751 W, BIMBND BLVI),
ANCH, AK, 99502-3904
il '
LOT 193 SECTION 33 ZT£N £3~/
TON £U£TER
]OM1 ]?ETUL~ DBIVE
SEPTIC SYSTEM DESIGN
DATE, AUSU£T 12 1991
SHEET, 2/3 GRID, 3135
203 ~/15th, Avenue
ANCH, AK 99501
LIlT 193 SECTION 33 TI2N R3W
TD~Z RUETER
10141 ~ETULA ££1VE
£' PV£ TO Si",
I! SEPTIC SYSTEM DESIGN
DATE: AUGUST 13, 1991
}!J~ET, 3/3 GRI~, 3135
PERFORMED FOR:
Municipality of Anchorage
DEPARTMENT OF HEALTH & HUMAN SERVICES
825 "L' Street, Anchorage, Alaska 99502-0650
SOILS LOG -- PERCOLATION TEST
LEGAL DESCRIPTION:
5
6
7
8
9
10
11
12
13
14
15-
16-
18-
19-
20-
Township, Range, Section:
SLOPE
ENCOUNTERED?
IF YES, AT WHAT
DEPTH?
Oeplh to Waler After
SITE PLAN
Reading Date Gross Net Depth to Net
Time Time Water Drop
PERCOLATION RATE __
(m~nutes/i~lch) PERC HOLE DIAMETER __
. F7 AND _ FT
PERFORMED BY: I
ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE.
72-008 (Rev. 4/85)
CERTIFY 1HAT THIS TEST WAS PERFORMED IN
DATE:
Municipality of Anchorage
DEPARTMENT OF HEALTH & HUMAN SERVICES
825 "L" Street, Anchorage, Alaska 99502-0650
SOILS LOG -- PERCOLATION I'EST
5
S,L'F
6
8
10
11
12
13
14
15-
16-
17-
18-
19-
20-
(ENGINEER'S SEAL)
Township, Range, Section: TF~.,IN\ ~ ~,'~ gl~
SLOPE
WAS GROUND WATER
ENCOUNTERED?
S
YES, AT WHAT nL
DEPTH? p
E
Deplll to Water
fdonitorieg?
Dale:
SITE PLAN
Reading Date Gross Net Depth to Net
Time Time Water Drop
PERCOLATION RATE
(minutes/inch) PERC HOLE DIAMETER
COMMENTS
TEST RUN BETWEEN FT AND ._ F~
PERFORMED BY: I CERTIFY THAT THIS TEST WAS PERFORMED IN
ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE DATE:
72-008 (Rev. 4/85)
Municipality of Anchorage
DEPARTMENT OF HEALTH & HUMAN SERVICES
825 "L' Street, Anchorage, Alaska 99502-0650
SOILS LOG -- PERCOLATION 'rEST
PERFORMED FOR:
LEGAL DESCRIPTION:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15-
17-
18-
19-
20-
COMMENTS _
(ENGINEER'S SEAL)
DATE
Township, Range, Section:
WAS GROUND WATER
ENCOUNTERED?
SLOPE
S
L
IF YES, AT WHAT O
DEPTH? p
E
SITE PLAN
Daplh 1o Water AFter
Reading Date Gross Net Depth to Net
Time Time Water Drop
lO :'.tfl to ~; '1~ I'l1
PERCOLATION RATE "~) (m~nutes/inch) PERC HOLE DIAMETER
PERFORMEDBY: ..~/~' I ~'"' ~r'~ OER]IFYTHATTHISTESTWASPERFORMEDiN
ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE, DATE:
72-008 (Rev. 4/85)
PERFORMED FOR:
LEGAL DESCRIPTION:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19-
20-
COMMENTS
Municipality of Anchorage
DEPARTMENT OF HEALTH & HUMAN SERVICES
825 "L" Street, Anchorage, Alaska 99502-0650
SOILS LOG -- PERCOLATION TEST
(ENGINEER'S SEAL)
Township, Range, Section:
SLOPE
WAS GROUND WATER
ENCOUNTERED?
IF YES, AT WHAT
DEPTH?
Oepth Io Waler Alter
Monitoring? Dote:
SITE PLAN
Reading Date Gross Net Dopth to Net
Tired Time Water Drop
PERCOLATION RATE '"'~) (minutes/inch) PERC HOLE DIAMETER
1ESTRUNBETWEEN /'¢ FIAND ~"~ II't~ FT
PERFORMED BY: ~ ~'%" I ~, ~"~
ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE.
72-008 (Rev 4/85)
CERTIFY THAT THIS TEST WAS PERFORMED IN
Municipality of Anchorage
DEPARTMENT OF HEAL-FH & HUMAN SERVICES
825 %" Street, Anchorage, Alaska 99502-0650
SOILS LOG -- PERCOLATION TEST
(ENGINEER'S SEAL)
PERFORMED FOR:
LEGAL DESCRIPTION: LoT Lq.Z
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
18-
19-
20-
COMMENTS_
Township, Range, Section:
WAS GROUND WATER
ENCOUNTERED?
IF YES, AT WHAT
DEPTH?
lloplh Io Waler
Monitoring?
SLOPE SITE PLAN
S
Reading Date
Time
Depth to
Water
tt
PERCOLATION RATE
_ (minutes/inch) PERC HOLE DIAMETER __
Drop
PERFORMED BY: I CERTIFY THAT THIS TEST WAS PERFORMED IN
ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE DATE:
72-008 (Rev. 4/85)
Municipality of Anchorage
DEPARTMENT OF HEALTFI & HUMAN SERVICES
825 "L" Street, Anchorage, Alaska 99502-0650
SOILS LOG -- PERCOLATION 'rEs'r
(ENGINEER'S SEAL)
LEGAL DESCRIPTION: L~"~ t(~
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16-
17-
18-
19-
20-
COMMENTS
Township, Range, Section:
SLOPE
WAS GROUND WATER
ENCOUNTERED?
fF YES, AT WHAT
DEPTH?
Oeplh 1o Water Alter
MonitorinD? Oate:
SITE P LA~I--
S
Reading Date Gross Net Depth to Net
Time Time Water Drop
__ ,;:, ,' ¢;"2 t~¢ [3 :" _ [
PERCOLATION RATE -~ (mmuteshnch) PERC HOLE DIAMETER
~ESTRUN.ETWEEN I'Jz. FTAND _'~ FT
PERFORMED ~Y: I
ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE.
72-008 (Rev. 4/851
CERTIFY THAT THIS TEST WAS PERFORMED IN
DATE:
] ,, 0
MUNICIPALITY OF ANCHORAGE=h-j°�.-:,
w
i pa
Development Services Department ;.d ° Phone: 907-343-7904
On -Site Water & Wastewater Section Fax: 907-343-7997
Certificate of On -Site Systems Approval
Parcel I.D. 018-331-08
1. GENERAL INFORMATION
Expiration Date: 16, Z-/
Complete legal description T1 2N R3W Section 33 Lot 193 Less E30'
Location (site address) 4020 Rabbit Creek Road
Current property owner(s) Merit Homes, Inc Day phone 727-9782
Mailing address 1920 W Dimond Blvd Ste F, Anchorage, AK 99515
Real estate agent Day phone
2. TYPE OF DWELLING:
■❑ Single Family (w/wo ADU) t�
❑
Duplex
❑ Multiple Dwellings (Single Family and/or Duplex)
3. NUMBER OF BEDROOMS: 4
4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL:
Private Well Private Septic ❑■
Water Storage ❑ Holding Tank ❑
Community Well ❑ Community ❑
Public Water System ❑ Public Sewer ❑
Waiver request for: Distance:
Received by:
COSA to be released to the engineer, unless otherwise requested by the engineer.
Date:
COSA Fee $ 120 Waiver Fee $
Date of Payment /16 1 lao) 1 Date of Payment
Receipt Number O G y 1 j_b Receipt Number
COSA,, OSC211045 Waiver #
5. STATEMENT OF INSPECTION BY ENGINEER
As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based
on procedures outlined in the Certificate of On-Site Systems Approval Guidelines for this application, shows that the
on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of
bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the
Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater
disposal system is (are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in
effect at the time of installation. I acknowledge that On-Site staff may visit the site to verify the information submitted.
Name of Firm Forge Engineering Phone (907) 522-7773
Address 1399 W. 34th Ave Suite 101, Anchorage, AK 99503
Engineer's Printed Name Benjamin Schiller Date
of ALq��ll
*: 49 TH • * r
6. DSD SIGNATURE.
�- ' • • . "
SystemApproved for bedrooms f Benjamtry5chiller
System #2 Approved for bedrooms c��;•, CE 12592��/
Disapproved +lPROFESSIONA���
Conditional approval for bedrooms, with the following stipulations:
."Ififili..
1�
By: �" J` Original Certificate Date:
The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the
representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is
not responsible for errors or omissions in the professional engineer's work.
7. ATTACHMENTS:
COSA Checklist X Nitrate Advisory
Septic System Advisory Arsenic Advisory
Well Flow Advisory Other
COSA Checklist blue sheet
Legal Description: T12N R3W Section 33 L193 Less E30'
If more than 1 septic system on lot: COSA Checklist # of
A. WELL DATA
❑ Well log is filed with Onsite (or attached)
Date drilled 06/20/20
Total depth 193 ft
Cased to 193 ft
❑ Sanitary seal is functioning correctly
❑ Wires are properly protected
Casing height (above ground) 24 in.
Date of flow test for COSA 06/20/20
Static water level at beginning of test 105 ft.
Comments
B. TANK DATA
Age of tanks) 4/7/20 years
Tank type/material SEPTIC/PLASTIC
Measured operating fluid level in septic tank NEW
❑ Standpipes/foundation cleanout per record drawing
Date of pumping NEW
D. ABSORPTION FIELD DATA WIDE TRENCH
Which system tested (date installed) 04/07/20
❑ ALL standpipes present per record drawing
Total measured depth from grade 9.5 ft (max)
Measured depth to pipe invert from grade 5.4 ft (min)
❑ N/A — pressurized field
❑ Monitor tubes go to bottom of effective. If not, state
depth into effective
❑ Code -required soil cover over field
❑ System presoaked
(Required if vacant for greater than 30 days prior to
date of test)
Gallons introduced gallons
Comments/Deficiencies: NEW CONSTRUCTION
COSA Checklist yellow sheet
Parcel ID: 018-331-08
Structure served by this system
Well production at time of test 100 gpm
Water storage tank volume gallons
Well disinfected for coliform test? ❑ Yes ❑ No
❑ Coliform bacteria is Negative
Nitrate mg/L ❑ Nitrate less than MRL (ND)
Arsenic ug/L ❑ Arsenic less than MRL (ND)
Collected by Forge Engineering
Date of Sample 02/04/21
C. LIFT STATION
❑ Required maintenance completed
Age of lift station years
Lift station material N/A
Comments:
Adequacy test date NEW
Results ❑ Pass For 4 bedrooms
Fluid depth prior to test in
Water added gal
New depth in
Elapsed time min
Final fluid depth in
Absorption rate gpd
Any rejuvenation treatment (past 12 months)
If yes, enter date
E. SEPARATION DISTANCES
From Private Well on Lot to: (Please enter distances if less than required or if community well)
Septic Tank/Lift Station on Lot > 100'
✓0
Yes
Community Sewer Manhole/Cleanout > 100'
✓v Yes
if No
ft
ED Yes
if No ft
Neighboring Tank > 100' 0✓ Yes
if No
ft
Private Sewer/Septic Line > 25' 0✓ Yes
if No ft
Absorption Field on Lot > 100' ❑✓ Yes
if No
ft
Holding Tank > 100' F✓ Yes
if No ft
Neighboring Absorption Fields > 100'
Yes
if No
Animal Containment > 50' F/ Yes
if No ft
0✓ Yes
if No
ft
Manure/Animal Excreta Storage > 100'
Community Sewer Main > 75' 0✓ Yes
if No
ft
2 Yes
if No ft
From Septic/Holding Tank on Lot to: (Please enter distances if less than required)
Building Foundations > 10' Q✓ Yes if No ft Surface Water > 100' Q✓ Yes if No ft
Property Line > 5'
✓0
Yes
if No
ft
Wells on Adjacent Lots:
Absorption Field > 5'
F/
Yes
if No
ft
Private Wells > 100' Yes if No_
Water Main > 10'
✓Q
Yes
if No
ft
Community Wells > 200' Yes if No_
Water Service Line > 10'
✓�
Yes
if No
ft
If septic tank is under driveway comment below
From Absorption Field on Lot to: (Please enter distances if less than required)
Building Foundation > 10' ✓l Yes if No ft If absorption field is under driveway comment below
Property Line > 10'
El
Yes
if No
ft
Wells on Adjacent Lots:
Water Main > 10'✓®
Yes
if No
ft
Private Wells > 100' ®✓ Yes if No
Water Service Line > 10'
0
Yes
if No
ft
Community Wells > 200' Q✓ Yes if No
Surface Water > 100'
✓0
Yes
if No
ft
F. ENGINEER'S COMMENTS
G. ENGINEER'S CERTIFICATION
I certify that l have determined through field inspections and review
of Municipal records that the above systems are in conformance with
MOA COSA guidelines in effect on this date.
COSA Checklist yellow sheet
%g, y �l
*, 49 TH
.......
_.. ..
vSc
Benja 'rhiller
CE 12592
't �`rl<c�• . 02/12/21 F1 �s
���F�PROFESS10Np .--aw
ft
ft
ft
ft