HomeMy WebLinkAboutHOMESTEAD HILLS BLK 2 LT 3Onsite File Homestead Hills Block 2 Lot 3 #015-173-18 Municipality of Anchorage On-Site Water and Wastewater Section • (907) 343-7904 Page of ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP211229 PID Number: 015-173-18 Dwelling: ® Single Family (SF) ❑ with ADU ❑ Duplex (D) ❑ Two Single Family Project: ❑ New ® Upgrade Name ROBERT LYNN TRUST.... ABSORPTION FIELD -EXISTING ❑ Deep Trench ❑ Wide Trench ❑ Bed ❑ Mound Site Address 4400 TRAPLINE DRIVE, ANCHORAGE ❑ Other Phone Number of Bedrooms Soil Rating Total depth from original grade 3 GPD/SF Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade Ft. Gravel depth beneath pipe Ft. Subdivision Block Lot Fill added above original grade Ft. Gravel length Ft. HOMESTEAD HILLS 2 3 Township Range Section Gravel width Ft. Beds: Number of Lines Distance between lines Ft. SEPARATION DISTANCES To Septic Absorption Li ft Station Holding Sewer Total absorption area z Number of trenches Dist. between trenches From Tank Field Tank Line Ft Ft. Well *150'+ -- 25'+ TANK ® Septic ❑ S.T.E.P. ❑ Holding ❑ Other Manufacturer GREER Capacity 1000 Gal. Surface Water 100'+ -- Material HDPE Number of compartments 2 Lot Line 10'+ 7N Foundation 10'+ __ LIFT STATION Manufacturer Capacity Gal. Remarks WATERLINE LOCATED BY MIKE ANDERSON, PE *ADEC 150' WAIVER TO COMMUNITY WELL Alarm location Electrical installed by Installer MIKE N. ANDERSON PIPE MATERIAL House to tank 3034 Tank era of e o 3034 Drainfield CO/MT 3034. Inspector FWCS BENCH MARK (Assumed elevation) 100 ft Inspection ection 1s' 7/19/21 7/20/2021 Location and description 2nd 3`d 4'h TOP OF MANHOLE ON-SITE WATER AND WASTEWATER SECTION APPROVAL OF It Conditional Approval: Date .�,f.��} /��Q.,.•' " ........1 Septic System... A pp rov Curtis Huffman i� �'�`•• •`fir ,_ Z_z) Ing-. Date ZS ( CE 128991 • 7/22/202J. •����s tkAF, PROFEWQO -r Note: this approval does not include well permit requirements.\ tmev voiu/i 1 o) PID: 015-173-18 PERMIT. [lSP211229 N���"���`1 �''UV �� ��' /vuu ^�u /u v, uu.�v EXISTING 'CO INSTALLED NEW MT T NEW MTA TIME OF TESTING. ST ONE FIELD CO PIP WAS FOUND. ORIG1111 L FIELD SERVICE LINE PORTIONS OF FIELD RE INSULATED E G DRIVE 20-30+ YEARS W/ NO KNOWN Z C) FREEZING ISSUES. r iw A—C=40.1' B—C=34.3' A—D=4U.O' B—D=39.0' A—E=4O.6' B—E=43.9' A—F=41.5' B—F=47.5' 3�5' DECOMMISSIONED EXISTING / S.T. /b INSTALLED NEW / 1000—GAL HDPE SEPTIC TANK WITH NEW DCO. DCO \ Co ` MH CO C STAKED 150' W LL ELL RADIUS RWIOR TO CONST. A FCO 1 0 26. 0'jB 06 WATERLINE EXISTING LOCATED '�(lUTA �[lU�� lz ~~'`'�~ SOUTH HOUSE . O� �lTA�� �I�� ~ ~...^-.` `.~^- | ' 41.3' OF AOUc�� i ` HOUSE. SEPTIC SECTION HOMESTEAD��T��HOMESTEADHILLS BLOCKBLOCK2, LOT 3 SUPPORT SERVICE PREPARED FOR: ROBERT LYNN SR TRUST 8525 BUGGY WHIP ROAD RANCH CUCAWONGA' CA 91701 FIRST WATER CONSULTING DATE: 7/27/2021 SURVEY: JLS 13030 SUES WAY DRAWN: FWCS ANCHORAGE, AK 99516 SCALE: 1 20' 907-350-9566 firstwaterAK@gmail.com 7/27/2021 NTS 0 N89°58'15"W 56.66' ID D OO� PAVED MH D/W 28.0 33.5' 26.0' EXISTING " HOUSE 32.5' 41.3' 10.0'ui 12.7' O 1 SHED DECKS 0 LLJ tC� O CC t•7 p LO Lij P LOT 3 z CD BLOCK 2 _{ z a � Q 02 O 0 O z 10' UTILITY ESMT NEIGHBORS _ GR6LL PARKINQ N89°58'15" 126.66' MWELL ui HSE ANCHORAGE RECORDING DISTRICT, ALASKA s.o' AS -BUILT OF: HOMESTEAD HILLS SURD LOT 3 BLOCK 2 PLAT 71-191 _ SURVEY" CERTIFICATE: I, John L. Schuller, Have conducted a physical survey of this property as shown on this drawing and that the improvements situated hereon are within the property lines and no enchroachments exist other than noted. Under no circumstance should any information on this drawing be used for construction of fences, structures, improvements, or for establishing boundary lines. EXCLUSION NOTES: It is the owners responsibility to determine the existence of any easements, covenants; or restrictions which do not appear on the recorded subdivision plat. JULY 24, 2021 1"=30' schuller9ok.net 21-110 DRAWN BY; CHECKED BY vRD NUMBER: 600K/PAGE JLS SW2636 210232 Asr 49TH�� ................. r.��r........ r L .... ...: . ` 9 -,JOHN L. SCHULLER. � �el LS -1+0408 ' 00, c� °fessiono\ �O �D LAND 5���" 1831 Talkeetna Street Anchorage, Alaska 99508 (907) 227-1455 office (907) 274-4992 fax MUNICIPALITY OF ANCHORAGE On-site Watar & Wastewater Program PO Box 196850 440 Ek=Fe Row Anchorage, Alaska 99519-6650 Pham: (007) 3d-7804 Pax; (91)7j 343-7997 hktpj)&.vw,mU111.br iGl it On -Site Wastewater Disposal System Permit Permit Number. O P2112-29 Work Type: Septiciank Upgrade Tax Code Number; 01517010000 Site Legal Address; HOMES-EAD HILLS BLIP 2 LT 3 G.-2636 Site Malling Address., 4400 TRAPLINE DR, Anchorage Owner. I YNN ROBERT S SIR TRUST Design Englnenr: FIRST MATER COMSULTING This permit is for the construction of. Effective Date: Expirali€xn Dai:e Let Size in Sq Ft= Total Bedrooms: h De 110vtin ell t 7172021 71712022 2-2391 Disposal Field 0 Septic Tank ❑ Holding Tank ❑ Prlvy ❑ Priv8te VVelf ❑ Water Storage All construction shall be in accordance vyith: 1, The attached approved design - 2. All requirements specified in Anchorage Municipal code Chapters 15,55 and 15.65 and the State of Alaska Wa!stew.ater Disposal Regulations (13AAC72) and Drinking Water Regulations (18AAO84) 0. The wastewater coda mquim,% inspections during the instalialioii- Tiit; t;:i i�fimmr uliail riul.ify ulit� Develupment Services Department per AMC 15-55. Provide notification by calling {907} 343,7904 (247). 4. From October 15 to April 15, a subsurface coir absorption system under cpn$[ryjcjj n futiilg freezing weather shall be either. -a- Opened and Closed on the same day, or b- Covered, sealed, anal heated to prevent freezing Special Provisions: The water service line shall be located prior to installation of the septic tank, to confirrn Mmlfnim�am separations to the septic system. The water service line routing sha.IC be shown on the record drawings. Racel'ved Fay: Issued By: 7f712021 Date. Date: 3 Development Services Department On -Site Water & Wastewater Section ON-SITE SEPTICM/ELL PERMIT APPLICATION Parcel I.D. 015-173-18 Phone: 907-343-7904 Fax: 907-343-7997 Property owner(s) ROBERT LYNN TRUST Day phone Mailing address 8525 BUGGY WHIP ROAD, RANCH CUCAMONGA, CA 91701 Site address 4400 TRAPLINE DRIVE, ANCHORAGE, AK 99516 Legal description (Sub'd., Block & Lot) HOMESTEAD HILLS BLOCK 2, LOT 3 Legal description (Township, Range & Section) Lot Size 22381 Sq. Ft. Number of Bedrooms 3 APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: (® all that apply) Absorption Field ❑ Initial ❑ Single Family (SF) 0 (w/wo ADU) Septic Tank 0 Upgrade Q Duplex ElHolding (D) Tank ElRenewal ElMultiple Dwellings ❑ Privy ❑ (SF and/or D) Private Well ❑ Water Storage ❑ THIS APPLICATION INCLUDES A WAIVER REQUEST FOR: Distance: I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes. (Signature of property owner or authorized agent) Permit/Rush Fees: t g �2 5 Date of Payment: �II L21 Receipt Number: 311 23Z Permit No. O S L2 [ 12 �2 q Waiver Fees: Date of Payment: Receipt Number: Waiver No. GADevelopment Services\Building Safety\On Site Water and Wastewater\Forms\Client Forms\Permit Application.doc 13030 Sues Way, Anchorage, AK 99516 907-350-9566 / firstwaterAK@gmail.com June 18, 2021 Municipalities of Anchorage On-Site Water & Wastewater Program 4700 Elmore Road Anchorage, AK 99507 RE: SEPTIC TANK UPGRADE PERMIT LEGAL: HOMESTEAD HILLS BLOCK 2, LOT 3 The owner has requested that we obtain a septic permit to upgrade the existing aged steel septic tank on the above referenced lot. We propose to install a 1000-gallon HDPE tank per the attached design to serve the existing 3-bedroom residence. The lot and area are served by a Community Class A water system. The design will not impact any of the neighboring properties. Please contact us if you have any questions. Sincerely, Curtis Huffman, P.E. Municipality of Anchorage On-site Water and Wastewater REVIEWED FOR CODE COMPLIANCE OSP211229, Rebecca Carroll, 07/07/21 FIRST WATER CONSULTING HOMESTEAD HILLS BLOCK 2, LOT 3 DESIGN DETAILS: STAKE 150' WELL RADIUS PRIOR TO CONSTRUCTION. Municipality of Anchorage On-site Water and Wastewater REVIEWED FOR CODE COMPLIANCE OSP211229, Rebecca Carroll, 07/07/21 Department of Environmental Conservation DIVISION OF ENVIRONMENTAL HEALTH Drinking Water Program 555 Cordova Street Anchorage, Alaska 99501 Main: 907.269.7631 Fax: 907.269.7650 roy.robertson@alaska.gov July 7, 2021 File: AWWU – Homestead Hills Lot 3 Block 2 Curtis Huffman, PE PWSID: 211669 First Water Consulting Class: Community 13030 Sues Way Source GW Anchorage, AK 99516 Re: Homestead Hills Lot 3 Block 2 Separation Distance Waiver Reauthorization Dear Curtis: On June 29, 2021, this office received a submittal requesting approval of a modification to a waiver that was previously approved on September 30, 1991. This letter approves the requested reduction in the State’s minimum separation distance requirement between drinking water well and the new septic tank as detailed in the engineers request and the Separation Distance Table below. Project Description The department approved a waiver on September 30, 1991, between Well WL001 and the nearest portion of a septic tank and soil absorption system 150-ft away. The owner of the wastewater system has requested to replace the aging steel tank with an HDPE tank. The following items were taken into consideration in issuing this waiver request: 1. The well log indicates the well is 258-feet deep; 2. The distance to water according to the well log is 198-feet; 3. The nitrate levels are detectable but appears to be relatively low and stable; 4. The bacteriological testing is consistently free from coliforms; 5. The water table gradient appears it would carry contamination away from the well; 6. The ground slope would carry contamination away from the well; and 7. The new construction and the new HDPE tank represent an improvement and reduces the risk of contamination posed by the aging likely leaking existing steel septic tank. Waiver Approval and Limitations Based on an evaluation of the available information and in accordance with the State’s Drinking Water Regulations, 18 AAC 80, the separation distance waiver request is approved. Any changes, constructed or natural, that affect the conditions to which this waiver was granted will void this waiver. This approval does not imply the granting of additional authorizations, nor obligate any federal, state, or local regulatory body to grant required authorizations. This is not an approval of omissions or oversights by this office or noncompliance with any applicable regulation. The Department’s issuance of this separation distance waiver does not guarantee correctness of the functional design or waive the owner’s responsibility for continued compliance with State regulations. Matthew Edge, PE 2 July 7, 2021 210707 Homestead Hills waiver reauthorizatio 211669 WA.docx Any person who disagrees with this decision may request by mail, e-mail, or facsimile an informal review or adjudicatory hearing in accordance with 18 AAC 15.185 and 15.195-15.340. Informal review requests must be delivered to the Division Director within 15 days of receipt of this decision. Adjudicatory hearing requests must be delivered to the Commissioner within 30 days of this decision. If a hearing is not requested within 30 days, the right to appeal is waived. Visit http://www.dec.state.ak.us/commish/ReviewGuidance.htm for more information. If you have any questions regarding this approval please do not hesitate to contact me. Sincerely, Roy Robertson, P.E. Engineer II Drinking Water Program, Anchorage Office Encl.: none Cc: Jana Littlewood via email jana_littlewood@awps.com Brent Western via email firstwaterak@gmail.com Municipality of Anchorage Page DEPARTMENT OF HEALTH AND HUMAN SERVICES ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 · Anchorage, Alaska 99519-6650 · Telephone: 343-4744 On-Site Wastewater Disposal System and/or Well Inspection Report Permit Number: S'GO ~'~ O~IO PID Number: ~\Z~_ \--~_~, Name: ~ t~.l~ e,-c~ ~ t l ev~ Wastewater System: ~ New ~ Upgrade Address: ~o ~ 7Z~ ABSORPTION FIELD Phone: ~~ ~O,~~ ~A~ No. of B~rooms: ~ Deep Trench ~ Shallow Trench ~Bed ~Mou~d ~Other Soil Rating: Total Depth from original grade: LEGAL DESCRIPTION .~5 ~,~sq.~. ~1 ' ~ ~'l~' Lot: ~ Block: ~~O~ ~-- Subdivision: ~)~ Depth to pipe~bottom~ ~fr°m original grade: Ft. Gravel dept~ beneath~ pipe Ft. Township: Range: J Section: Fill added above original grade: Gravel length:~ I ~ ~ ~ ~ ~ ~o~ ~t. Ft. WELL: ~ New ~ Upgra~ Gravel depth:~ Number of lines: Distance between lines: Classification (Private, A,B,C): Total ~ Cased To: Total absorption area: Pipe material: Driller: ~ Date Drilled: SlaticWater Level: Installer: Date in.ailed: Yield~ Pump Set at: Casing Height Above Ground: TAN K ~ GPM Ft. Ft. SEPARATION DISTANCES ~septic ~ Holding ~ S.T.E.P. To Septic Absorption Lift Holding ~ublic/Private Manufacturer: Capacity in gallons: From Tank Field Station Tank Sewer Lines ~O~a~ t ~ 0 Surface ~ ~ Water +t~ ~' ~oo LIFT STATION Lot Size in gallons: Line ~O' ~0' +~' Foundation ~, ~O/ ~ "Pump on" level a~' level at: High water alarm at: CurtainDrain +J~ ~ ~* ~ I OO' ~1 Electrical Inspections performed by: Remarks: ~ 4~ ~ ~1~ ,~l~J BENCH MARK I~ Location and Description* ~ssumed Elevation: Inspections performed by: ¢~S~'~~Dates: 1st O~ t~t ::~:...~,.~.~...-.-~...?'~ uepartment of Heath and Human Services approval ", Reviewed and approved by:~ '~ ~~ Date://-/-~/ ~' 72-013 (1/91) MOA 25 Perr~lt No.~C,c¢~ 0"~0 P&ge of Municipality of Anchorage DEPARTMENT OF. HEALTH AND HUMAN SERVICES ENVIRONMENTAL SERVICES DIViSiON P.O. Box 196650 e Anchorage, Alaska 99519-6650 · Telephone: 343-4744 On-Site Wastewater Disposal System and/or Wel~ InspecUon Report Legal Description: PiD No.: :~ ,. ENGINEER'S SEAL PAGE 1 OF 1 MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND HUMAN SERVICES P.O. BOX 196650, 825 "L" STREET, ROOM 502 ANCHORAGE, ALASKA 99519-6650 ON-SITE WASTEWATER DISPOSAL SYSTEM (UPGRADE) PERMIT PERMIT NUMBER:SW910310 DESIGN ENGINEER:CONSTRUCTING ENGINEERS, OWNER NAME:SELLERS RICHARD V OWNER ADDRESS:PO BOX 721 ANCHOR POINT, AK 99556 PARCEL ID:01517318 INC. DATE ISSUED: 9/30/91 EXPIRATION DATE: 9/30/92 LEGAL DESCRIPTION: HOMESTEAD HILLS BLK 2 LT SEC22, T12N, R3W, SM LOT SIZE: 22381 (SQ. FT.) NUMBER OF BEDROOMS: 3 THIS PERMIT: 3 THIS PERMIT IS FOR THE CONTRUCTION OF: DISPOSAL FIELD /SEPTIC TANK SYSTEM ALL CONSTRUCTION MUST BE IN ACCORDANCE WITH: 1. THE ATTACHED APPROVED DESIGN. 2. ALL REQUIREMENTS SPECIFIED IN ANCHORAGE MUNICIPAL CODE CHAPTERS 15.55 AND 15.65 AND THE STATE OF ALASKA WASTEWATER DISPOSAL REGULATIONS (18AAC72) AND DRINKING WATER REGULATIONS (iSAACS0). 3. THE FOLLOWING SPECIAL PROVISIONS. SPECIAL PROVISIONS: INSTALL PER ATTACHED APPROVED PLANS. NOTE: THAT TRENCH IS TO BE 72' MINIMUM IN LENGTH. .VERIFY SOILS ARE SAME AT SOUTHERN EXTREMITY OF TRENCH. ~SORPTION SYSTEM DESIGN Z P~o ENGINEER'S SEAL SITE PLAN DETAILS--PROPOSED ABSORPTION SYSTEM LOT 3, BLOCK 2 HOMESTEAD HILLS SUBDIVISION PREPARED FOR: JANI SELLERS PO BOX 721 ANCHOR POINT, ALASKA~ SCALE 99556 DRAWN BY CAL CONSTRUCTING ENGINEERS346-2000 9601 BUDDY WERNER DR 694--9098 ANCHORAGE, AK, 99516 DRAHING # 91-$I-09-1 ABSORPTION SYSTEM DESIGN ABSORPTION AREA CALCULATIONS: 3 Bedrooms x 150gpd/bedroom = 450 gpd (soils rating : 0.45 gpd/sf) 450 gpd / .45 gpd/sf = 1000 sf area 1000 sf/(2 x 7'/') =~L1~ tr~h Minimum trench length ~ (~c_~ IMPACT ON ADJACENT LOTS: This lot is served by a public water system. The proposed absorption system is located such that there is no impact to any adjacent lot. ENGINEER' S SEAL SITE PLA~ DETAILS--PROPOSED ABSORPTION SYSTEM LOT 3, BLOCK 2 HOMESTEAD HILLS SUBDIVISION PREPARED FOR: JANI SELLERS PO BOX 721 ANCHOR POINT, ALASKA, 99556 hOT TO SCALE DRAWN BY CAL CONSTRUCTING ENGINEERS346-2000 9601 BUDDY WERNER DR 694-9098 ANCHORAGE, AK, 99516 DRAWING # 91-S2-09-I ABSORPTIOI~ SYSTEM DESIGN ENGINEER'S SEAL SITE PLAN DETAILS--PROPOSED ABSORPTION SYSTEM LOT 3, BLOCK 2 HOMESTEAD HILLS SUBDIVISION PREPARED FOR: JANI SELLERS PO BOX 721 ANCHOR POINT, ALASKA, SCALE 99556 DRAWN BY CAL CONSTRUCTING ENGINEERS 346-2000 9601 BUDDY WERNER DR 69&-9098 ANCHORAGE~ AK, 99516 DRAWING # 91-S3-09-1 PERFORMED FOR: LEGAL DESCRIPTION: / Mu.icipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST / ~J,, ~n L ~ll ~ DATE PERFORMED: ~k ~ I~~ ~ Township, Range, Section:~ 'i 2 3 5 8 7 g 10 11 12 13 14 15 16 17 18 19 2O COMMENTS SLOPE WAS GROUND WATER ENCOUNTERED? ~:~ IF YES, AT WHAT DEPTH? D~pth Io Water Alter Monitoring? _~_~ Dale: d~ I Gross Rea Date Time PERCOLATION RATE TEST RUN BETWEEN Net Time Depth to Net Water Drop . (minutes/inch) PERC HOLE DIAMETER ._~"" FT AND _~" FT PERFORMED BY: C~)l~'~qi~c.~'Jt~'~'~ ~_.~lb~¢ i ~ CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: ~1.(~-~[ CML & ENVIRONMENTAL ENGINEERING * ENERGY CONSERVATION & ANALYSIS TttEODORE F. MOORE, P.E. 14530 ECHO ST. iH: (907) 345-1355 July 29, 1991 ANCHORAGE, ALASKA 99516 Jani Sellers P. O. Box 721 Anchor Point, AK 99556 Dear Ms. Sellers: Per your request, on July 24 - 25, 1991 we Conducted an adequacy test of the wastewater disposal system serving the house you own on Lot 3, Block 2, Homestead Hills S/D, located at 4400 Trapline Drive in Anchorage. Copies of relevant backup documents are enclosed. According to the as-built inspection reports on file at the Municipality, the wastewater disposal system consists of a 1000 gallon steel septic tank followed by an 8' x 8' x 5.5' deep log crib seepage pit installed in 1973. The soil absorption system was upgraded in 1979 by the addition of a 32 foot long soil absorption trench containing 6 feet of sewer gravel. The system was mo§t recently tested in 1986 by Alaska Environmental Control Services and found to be adequate for a three bedroom residence. At the same time a waiver was obtained from the State D.E.C. recognizing grandfather rights to the less than normally required 200 foot separatiou distance between the community well serving Homestead Hill S/D and the existing septic system components on your lot. To assess the present adequacy of the wastewater disposal system we added measured quantities of water directly into the seepage pit while monitoring fluid levels in the septic tank, seepage pit and soil absorption trench, before, during and after the flow of water was stopped. The addition of 173 gallons of water caused the fluid levels in the seepage pit and septic tank to rise 14" and 10" respectively, and to start to back up into the septic tank. We then monitored the performance of the system through several cycles of absorption and refilling. Based on the data obtained from this testing, we determined that the soil absorption system is now capable of absorbing water at a rate of approximately 240 gallons per day when completely full. This measured soil absorption rate is adequate for a one bedroom residence only. We regret to inform you that the system will have to be upgraded before it could qualify for a Health Authority Approval cecdficate. As we discussed on the phone, in order to upgrade the system it will be necessary to first conduct soils tests to determine if there is a suitable site on the lot and to come up with the design parameters. The following is a breakdown of the necessary s[eps and an estimate of the costs involved. Backhoe for soils tests $300 Visual soils logs, percolation tests and groundwater monitoring (2 test holes) $410 System design (site plan, plans, specifications and design narrative) $450 M.O.A. permit fee $ 90 Construction costs by excavating contractor $5000 - $10,000 Construction inspections and preparation of as-built drawings $450 Since the septic tank was installexl in 1973, it is probable that it will have to be replaced at the time the upgrade work is done. It is also probable that a new waiver will have to be issued by the State D.E.C. allowing the new system to be less than 200 feet fi'om the well. If this is the case, there will be another $300 in engineering costs to prepare ~:he necessary waiver request application. We are enclosing a copy of your property as-built survey on which we have marked additional information pertinent to the water supply and wastewater disposal systems and possible upgrade sites. It seems highly unlikely that the D.E.C. would allow a new system to be at a lesser separation distance from the well than the present system (possibly they will insist on at least 150 feet), so you can see that there is a relatively small area on the lot potentially available for an upgrade, and even this is dependent on finding suitable accepting soils in that area. Please feel free to give me a call if you have any questions on this report. I am enclosing a refund check for the $170 Health Authority Approval fee which is no longer applicable at this time. Sincerely, Ted Moore, P.E. Ide, the u~oersigned, 'hereby certify that there has been no ~tructual changes .~he property sl~e d~of ~/}~/73., ~N Robert L~ Doutb4t / ~ /, . .J LOT 3 DIBI~T. OF ~;~'iRON;MENT&L ~CHORAGE/UESTE~N DISTR~cT OFFICE 437 ~E' STREET~ SUITE 303 ANCHORAGE, ALASNA 99~01 ~LL .~f[FFIELD, 274-2533 Alaska Environmental Control Services 1200 U. 33rd Avenue, Suite B Anchorage, Alaska 99503 SUBJECTI Horizontal Grandfather Rights Separati.on betueen. Ual! and Septic Systems for Lots 3 thru 5, BlOck Homestead Niils Subdivision, Anchorage, Alaska (8621-UA-086) & (8621-FA-094) Dear Sirs The Department has received and revieued' ~our request for grandfather righ{s on separation for the subject Project° Approval ts hereby g*ven for the oaten system and the "Certificate to Operate" is attached. Any ~uture expansion of the subJect project ~i!] require additional approve from this office. Sincerely, Hichael p. Le~is Environmenta! Engineer .MPL~msm DEPT. OF ENVIRONMENTAL CONSERVATION WALTER J. HICKEL, GOVERNOR ANCHORAGE DISTRICT OFFICE 3601 C STREET, SUITE 322 ANCHORAGE, ALASKA 99503 563-6775 September 30, 1991 Mr. Chuck Landers Constructing Engineers HC83 Box 192-A Myrtle Drive Eagle River, Alaska 99577 Subject: Lot 3, Block 2, Homestead Hills Subdivision, Anchorage, Alaska, ADEC Project Number 9221-WA-006; Review Dear Mr. LanderS: This is in response to your submittal, receved in this office on September 20, 1991, in which you address the concern noted in my September 13, 1991 letter. The submitted information regards the request to waive the separation distance between a ClaSs A Public Water System Source Well and a the wastewater disposal system located on the above- referenced lot. I have completed my review of the submitted information and have the following comments. .. As a result of my review, I find no reason that this waiver should be denied. This iS based on the fact that this Department issued a waiver on January 3,. 1986 for a lesser separation between the source well and the wastewater disposal system that is to be replaced° The separation distance between the existing source well and the nearest portion of the proposed septic tank and soil absorption system will be 150 feet. Thus, as noted, the Department has found the information provided to be satisfactory for allowing a waiver in accordance with 18 AAC 72.035 and 18 AAC 80.020 (e), State Wastewater Disposal and Drinking Water Regulations, respectively. The separation distance between the Class A Public Water System Source Well and the Wastewater Disposal System on Lot 3, Block 2, Homestead Hills Subdivision has been waived from 200 feet to 150 feet. If the proposed wastewater disposal system fails, any changes to the existing public water system or the influent volume increases above that of a three bedroom home will invalidate this waiver. RECEIVED SEP 0 1991 Municipalffy ot Anchorage Dept. Health & Human Service¢ ........ Mr. Chuck Landers September 30, 1991 Page 2 Thank you for your cooperation with this Department. do not hesitate to contact me. cc: John Smith, DHHS, KKK/pf If you have any questions, please ,~cerely, /1 Ko¥on K. KIowono En¥ironm~ntal finginoor RECEIVED SEP ~ 0 1991 Municipality cf Anchorage Dept. Health & Human 8ervic~ DEPT. OF ENVIRONMENTAL CONSERVATION ANCHORAGE DISTRICT OFFICE 3601 C ,STREET, SUITE 322 ANCHORAGE, ALASKA 99503 Mr. Chuck Landers Constructing Engineers 9601 Buddy Wemer Drive Anchorage, Alaska 99516 Subject: WALTER J. HICKEL, GOVERNOR / SEP 1 6 1991 / / Municipality of Anchorage PHONE: (90?) 563~?75 September 13, 1991 Lot 3, Block 2 Homestead Hills Subdivision, Anchorage, Alaska, Waiver Request, ADEC Project Number 9221-WA-006; Review Dear Mr. Landers: In response to the separation distance waiver received in this office on September 9, 1991; I have reviewed the submitted information and this office's file on the above- referenced subdivision. Before the requested waiver can be granted, the Department will need to have the non-objection of the owner of the existing Class A Public Water System. The letter will need to state that the owner of the public water system is aware of the separation distance between the existing source well and the wastewater disposal system on Lot 3, Block 2. If you have any questions, please do not hesitate to contact me. Keven K. Kleweno Environmental Engineer KKK/cf ,~ "~c'~ printed on recycled paper ABBOTT LOOP 4320 AMAZING GRACE LUTHERAN CHURCH 10830 BRAGAW ST, {70 [1001 TRACT 8 TRAPLINE DR, 2 11320 11340 4 11400 5 4420 ~ L-TAYLOR SUB L0941 .04, ~b~ mOl I a: zoc J [PACER O' MALLEY 4530 4600 4700 13 10841 10901 ~3 CLARE SUBD.! ~o9ol 4705 4741 4820 lOB 4835 ? 4830 10850 9 10950 I 2 3 445C BIRCHBARK AVE, 11~50 11300 23 240 E, 115 AVE. 451 4 3 ~841 4901 E. 114 AVE. E. 115 AVE, I 6 5 4 E. 115 AVE. JUMAR RD~ //OUTCROP KLATT GR, 2636 215 © COPYRIGHT 1987 JMR 200 X 214 -<~ 216 23O DeArmoun Area Reference Map--P14 Rick Mystrom, Mayor Municipality of Anchorage Department of Health and Human Services 825 "L" Street P.O. Box 196650 Anchorage, Alaska 99519-6650 November 2, 1994 Mr. Henry Wilson, P.E. Constructing Engineers 9601 Buddy Werner Dr. Anchorage, AK 99516 Dear Mr. Wilson: We have finished reviewing the paper work for the projects we have been discussing, and I have the following comments: Lot 20, Block 1, Schroeder East Subdivision. The as-built for this project must be resubmitted in the spring after the additional work is completed. Items missing on this as-built include both tank inverts, the elevation of the bottom of the test hole, and the elevation of any groundwater encountered in the test hole. Also, the Certificate of Health Authority must be signed. Lot 10, Block 1, Eagle Park Subdivision. This as-built needs some additional data, including the second tank invert, the second distribution pipe invert, the elevation of the bottom of the test hole and the elevation of any ground water encountered in the test hole. Lot 7, Block 1, Sampson Estates Subdivision. This as-built should include the second tank invert and the second distribution pipe clean-out invert. A lot line waiver must be obtained for the trench to lot line distance of 3 feet. We have no record of any waiver in our files. Also, the Certificate of Health Authority approval must be signed. Lot 9, Block 4, Hylen Crest Subdivision. After modifications to the surface water on the property, the as-built should be resubmitted. Updated information should include corrected distance from tank to surface water and from field to surface water. Also, the elevation of the bottom of the test hole should be shown on the profile, including any ground water encountered. The Health Authority Approval Checklist should be completed (information is missing). The Certificate of Health Authority must be signed. Lot 3, Block 2, Homestead Hills Subdivision. A new soils log must be submitted to replace the incorrectly signed soils log submitted with the original permit. Mr. Henry Wilson, P.E. November 2, 1994 Lot 12, Block 3, Mountain Valley Estates Subdivision. No additional information is needed. Lot 2, Block 1, Broadwater Heights Subdivision. The elevation of the bottom of the test hole and any ground water encountered must be shown on the as-built profile. The Certificate of Health Authority Approval must be signed. Sincerely, ~ Program Manager On-Site Services PERFORMED FOR: LEGAL DESCRIPTION: Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST DATE PERFORMED: Township, Range, Section: 1 2 3 4 5 6 7 8 9 10 11 12 13- 14- 15 16 17 18 19 2O COMMENTS (J ~' ~'O'~ 1,5 SLOPE was GROUND WATER ENCOUNTERED? S L IF YES, AT WHAT ~ O DEPTH? p E Depth to Water Alter Monitoring? r, Jo~as Date: Gross Net Depth to Net Reading Date Time Time Water Drop ~ ~ ~ ~'/~" ~ia" PERCOLATION RATE TEST RUN BETWEEN __ (minutes/inch) PERC HOLE DIAMETER FT AND ~' FT PERFORMED BY: C<~r,,~.JrV~..J~v'~) ~.~j/y.~2,~ i C..~= .-'~.,~,j...~.. CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: ?f' ~-~-<~[ HENRY WILSON 9601 BUDDY WERNER DR.: ANCHORAGE, AK 99516 (907) 346-2000 En neers CHARLES A. LANDERS HC83 BOX 192~A, MYRTLE DR. EAGLE RIVER, AK 99577 (907) 694-9098 3 July ~, 1994 Muncipality of Anchorage DHHS, On-Site Services Po Box 196650 Anchorage, AK, 99519 re: Lot 3 Block 2 Homestead Hills Sub Septic design report Gentlemen: Please substitute the attached original signed reports for the reports originally submitted and processed, and remove the file copies and send to me at the above address. Henry H. Wilson, P.E. ABSORPTION SYSTEM DESIGN 4 SITE PLAN DETAILS--PROPOSED ABSORPTION SYSTEM LOT 3, BLOCK 2, HOMESTEAD HILLS SUBDIVISION PREPARED FOR: JANI SELLERS PO BOX 721 ANCHOR POINT, ALASKA, 99556 SCALE: 1" = 100' DRAWN BY CAL CONSTRUCTING ENGINEERS346-2000 9601 BUDDY WERNER DR 694-9098 ANCHORAGE, AK, 99516 DRAWING # 91-S1-09-1 ABSORPTION SYSTEM DESIGN ' 14-o~$e ' I ABSORPTION AREA CALCULATIONS: 3 Bedrooms x 150gpd/bedroom = 450 gpd ~s°ils rating : 0.45 gpd/sf) 450 gpd / .45 gpd/sf = 1000 sf area (!i i/i!~: 1000 sf/(2 x 7'/') = 72' trench Minimum trench length = 72' IMPACT ON ADJACENT LOTS; This lot is served by a public water system. The proposes absorption system is located such that there is no impact to any adjacent lot. ENGINEER SITE PLAN DETAILS--PROPOSED ABSORPTION SYSTEM LOT 3, BLOCK 2, HOMESTEAD HILLS SUBDIVISION PREPARED FOR: JANI SELLERS PO BOX 721 ANCHOR POINT, ALASKA, 99556 NOT TO SCALE DRAWN BY CAL CONSTRUCTING ENGINEERS346-2000 9601 BUDDY WERNER DR 694-9098 ANCHORAGE, AK, 99516 DRAWING # 91-S2-09-I ABSORPTION SYSTEM DESIGN ENGINEER'S SEAL SITE PLAN DETAILS--PROPOSED ABSORPTION SYSTEM LOT 3, BLOCK 2, HOMESTEAD HILLS SUBDIVISION PREPARED FOR: JANI SELLERS PO BOX 721 ANCHOR POINT, ALASKA, SCA,~: ~" -- 3o' q~l O0 /e.,'dL-,W~: PA. CONSTRUCTING ENGINEERS 346-2000 9601 'BUDDY WERNER DR 694-9098 ANCHORAGE, AK, 99516 99556 DRAWN BY CAL ~q~ - -$ fl z DRAWING # 91-S3-09-1 UIUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTION ENVIRONIVIENTAL ENGINEERING DIVISION 825 L Street- Anchorage, Alaska 99501 Telephone 264-4720 ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT PHONE / [] NEW /. ~oczr~' / r ,S c/ c/ %q6~Vl ~ADE LEGAL DESCRIPTION NOi OF BED~,~OMS We)l Absorption area Dwe[ling PERMIT NO. o I DISTANCE TO: ) /c:~O J I --7 I- Z Manufacturer ~ ~ ' ~' Material No. of compartments /Liq. capacity in gallons IF HOMEMADE: Inside length v I Width Liquid depth ~ v DISTANCE TO Well DWelling I P_.~ )T o ~ < I Manufacturer / -~t-~," ..... ~ Liquid capacity in gallo~ Q I I WelJ ~ ~ Foundatio~ ~ INearest lot Hne ! PERMIT NO.~/~ ~ D,STANCETO= I /o LO -F~/(~ ! /(D /-/Uj ~ ";' ~ No. of )ines ~ ) Length of each I~e__ Total length of lin~ ~ J Trench width~ Distance I:j~tw~e~line~ = _z ~ I ~/9 ~ I ~J~, ~'~L I ~G inches z~ / ~ ~- ~ ~- Top of tile to fin sh grade x, ~ Material beneath tile Total effecti(m abso~p~,~n/ar/ea O ~ ~7'), inches : I Length Width Depth ~m [PERMIT NO. .~l- I Type of crib Crib diameter Crib depth Total effective absorption area ~' Well Building foundation Nearest lot line DISTANCE TO: icw . D pth Dr,,,er D,stanceto,ot,ne PERM,T,O. ~ i ~ Building foundation Sewer line Septic tank _ +- Absorption area(s) ~IDISTANCE TO: /'.~O / OTHER PIPE MATERIALS INSTAntER -- DATE / LEGAL PERMIT NO. 8PPLICSNT LOCSTION LEGSL ROBERT L. DOUTHIT TRSPLINE DR L~ B~ HOMESTESD HILLS SR8 BOX LOT =.I/E ~44-4i54 ~1~,.,0 ~..JSRE FEET TYPE OF SOIL RBSORBTION SYSTEM IS: TRENCH MSXlMUM NUMBER OF BEDROOMS = ,~--- SOIL RSTING <9~ FT/BR)= i90 THE REQUIRED SIZE OF THE SOIL 8BSORPTION SYSTEM IS: C~E:P1FH=~ ~ 0 LEr-,IGTH= ~ GRI~'-/EL DEPTH= THE LENGTH DIMENSION IS THE LENGTH (IN FEET) OF THE TRENCH OR DRRINFIELD. THE DEPTH OF 8 TRENCH OR PIT IS THE DISTRNCE BETWEEN THE SURFRCE OF THE GROUND 8ND THE BOTTOM OF THE EXCSVSTION (IN FEET)~ THERE IS NO SET WIDTH FOR TRENCHES. THE GRSVEL DEPTH IS THE MINIMUM DEPTH OF GRSVEL BETWEEN THE OUTFSL. L PIPE 8ND THE BOTTOM OF THE EXCSVRTION (IN FEET). REm~I_I I RED SEPT I C TBr4F( S I ZE= 1[~00 13FILLOi'4'=: PERMIT 8PPLIC~NT HSS THE RESPONSIBILITY TO INFORM THIS DEPSRTHENT DURING THE INSTSLLSTION INSPECTIONS OF 8NY WELLS RDJSCENT TO THIS PROPERTY 8ND THE NLIMBER OF RESIDENCES THFIT THE WELL. WILL SERVE. T~JO ( 2 > INSPECT I Or~S RRE REOIJ I BSCKFILLING OF 8NY SYSTEM WITHOUT FINRL INSPECTION 8ND 8PPROVSL BY THIS DEPSRTMENT WILL BE SUBJECT TO PROSECUTION. MINIMUM DISTSNCE BETWEEN 8 WELL. 8ND 8NM ON-SITE SEWSGE DISPOSSL SYSTEM IS i00 FEET FOR 8 PRIVRTE WELb OR 150 TO 200 FEET FROM R PUBLIC WELL DEPENDING UPON THE TYPE OF PUBLIC WELL. OTHER REQUIREMENTS MRY 8PPLY. SPECIFICSTIONS 8ND CONSTRUCTION DISGRSMS 8RE 8VSILRBLE TO INSURE PROPER INSTSLLRTION. PER~q I T ~XP I RE_ [:,ECENBER _~l~ 1979 I CERTIFY THST 1: I 8M FSMILISR WITH THE REQUIREMENTS FOR ON-SITE SEWERS 8ND WELLS 8S SET FORTH BY THE MUNICIPSLITY OF 8NCHORRGE 2: I WILL INSTRLL THE SYSTEM IN 8CCORDSNCE WITH THE CODES. ~: I UNDERSTSND THST THE ON-SITE SEWER SYSTEM MSY REQUIRE ENLSRGEMENT IF THE RESIDENCE IS REMODELE[~_INC~IORE THSN ~ BEDROOMS. SIGNED: 8~PLICSNT ROBERT L. DOUTHIT S UED BY___:_ [] SOILS LOG MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION Pouch 6~650, Anchorage, Alaska 99502 276-2224 SOILS LOG - PERCOLATION TEST PERCOLATION TEST PERFORMED FOR: LEGAL DESCRIPTION: 1 2 3 4- 5- 6- 7 8 9- _10 - 11 12 13 14 15 16 L3 i3 c_ LOPE IF YES, AT WHAT Gross Net Depth to Net Reading Date Time Time Water Drop 17 18 19 2O COMMENTS / PERCOLATION RATE /~ ~'e O minutes/inch) TEST RUN BETWEEN ~. O FT AND CE.TIFIED BY~~ ~:~ DATE: ALASKA ENVIRONMENTAL CONTROL SERVI(~'~, INC. 1200 West 33rd Aven~. Suite B ANCHORAGE. ALASKA 99503 (907) 561-5040 SHEET NO CALCULATED BY CHECKED BY SCALE /~I. /~/~/ DATE DATE /-'~0 : % ANC'HORAGE AREA BOe' uGH Department of Environmental Quality 3330 C Street Anchorage, Alaska 99503 INSPECTION REPORT ON-SITE SEWAGE DISPOSAL SYSTEM LOCATIO /./// - - w , SEPTIC TANK: ~- C')MAN U FAcTu RER FROM WELL 'fl INSIDE LENGTH ~,-.'/~"¢' INSIDE WIDTH NUMBER OF I ~'~/2~4`A'-~h''-~ MATERIAL C) .(~¢_.A.. (' COMPARTMENTS ~' LIQUID DEPTH __.LIQUID CAPACITY GALLONS. SEEPAGE PIT: ~_ t NUMBEROFPITS (~. DIAI'CETER?-~/'~OR WIDTH__ LENGTH: DEPTH ...... LINING MATERIAL ~. (>,~r,~C~RIB SIZE: DIAMETER~EPTH .:':DISTANCE FROM: WEL '~::f:: BUILDING FOUNDATION NEAREST LOT LINE ~ ~ TOTAL EFFECTIVE ~ . ABSORPTION AREA (WALL AREA) S~. FT, ADDITIONAL ABSORPTION TYPE ( ../~I pf CONSTRUCTION BU I'LD~~ ............ NEAREST NEAREST FOUNDATION LO~'Ei'&i~ .............. ; ,SEWER L NE CESSPOOL APPROVED DEPTH SEPTIC TANK __ OTHER SOURCES ....... .... DISAPPROVED REMARKS DISTANCE FROM: SEEPAGE / SYSTEM / 2. ~Z DISTANCES: INSTALLED BY: //~4..::&¢~. PIPE MATERIAL:_~/~C~-0/~/-'N ') Form No. EQ-031 DIAGRAM Of SYSTEM DATE / 7-7¢''w~ '/e'~??APPROVEE~ G.A.A.B. . GREATER ANCHORAGE AREA BOROUGH ; [)EPARTMENT OF ENVIRONMENTAL QUALITY PER&tlTNO.- . SEWAGE DISPOSAL SYSTEM -- APPLICATION AND PERMIT~ ~/ . ~ ' :. LEGAL / OTHER Ut. TS /~J<"--O ~ ~-z-' '"'~TE'~S PER~IT IS ~OT VALID WITHOUT ~IL ~S~ ~OIL TEST RES ~ .......... ~ ~ FINAL INSPE~TION~ 24 HOUR NOTl~ EEQUIEED, ~ACKF~LLING OF ANY BYSTE~ WITHOMT FINAL IH~PE~TION BY THE H~ALTH D~PA~TE1EHT AUTHORI~ WILL ~E ~U~JECT TO pRO~ECUTIOH. : ~.II NI~I U M DISTANCE~, FOUNDATION TO SEEPAGE Pit - 20 ~t. DRATN FIELD WATER "AIN TO SEPTIC TANK 10 ft ~ SEEPAGE PIT DRAIN FIELD- 10 ~PTIC TANK, 2~ ~o SEEPAGE PIT ]__~0 ~, DRAIN FIELD EXCAVATION § FEET INTO UNDISTURSED SOIL. 4 INCH DIAMETER CAST IRON SIPHON PIPES ON SEPTIC TANK AND SEEPAGE pit PITTED WITH AIRTIGHT REN~OVABLE CAPS __ TYPE DIAGRAIVI OF UMCC P A T Y o f ANCHORAGE r `i J, Development Services Department -' Phone: 907-343-7904 On -Site Water & Wastewater Section Fax: 907-343-7997 Certificate of On -Site Systems Approval Parcel I.D. 015-173-18 1. GENERAL INFORMATION Expiration Date: �—ILN_,02_3 Complete legal description HOMESTEAD HILLS BLOCK 2, LOT 3 Location (site address) 4400 TRAPLINE DRIVE, ANCHORAGE, AK 99516 Current property owner(s) ROBERT LYNN TRUST.... Day phone Mailing address Real estate agent 8525 BUGGY WHIP ROAD, RANCH CUCAMONGA, CA 91701 2. TYPE OF DWELLING: ® Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) Day phone 3. NUMBER OF BEDROOMS: 3 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Private Well ❑ Private Septic Water Storage ❑ Holding Tank ❑ Community Well ® Community ❑ Public Water System ❑ Public Sewer ❑ Waiver request for: Distance: Received by: COSA to be released to the engineer, unless otherwise requested by the engineer. COSA Fee $ 55-0 Date of Payment 7 93 2091 Receipt Number q% 3 2 8 3 COSA # OS�Z I 1 y 18 Date: Waiver Fee $ Date of Payment Receipt Number Waiver # 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is (are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. I acknowledge that On -Site staff may visit the site to verify the information submitted. Name of Firm FIRST WATER CONSULTING Phone 907-350-9566 Address 13030 SUES WAY, ANCHORAGE, AK 99516 Engineer's Printed Name CURTIS HUFFMAN, PE Date 7/20/2021 Comments: This investigation was completed in compliance with MOA guidelines, regulations, and best industry practices / methods. The assessment of the condition of the well and septic applies only to the conditions as of the day tested. The flow and absorption rates may change due to subsurface conditions that may not be observed from the surface, changes in land use, local soil characteristics, groundwater levels that may fluctuate during the year, quality of construction (workmanship & materials), the water usage of the family being served by the\l system and maintenance. The operational life of all well and septic systems are subject to rSli� these various and dynamic characteristics and are outside the control of the evaluator of the i well and septic system. Therefore, any estimate of how long a system will function satisfactory g�Q:•' • • ����� for current or future occupants or guarantee that no unseen encroachments, deficiencies or J discrepancies exist can be given by First Water Consulting & FWN ' 0 * . � TH .....:* r 6. DSD SIGNATURE III • '.. Curtis Huffman System #1 Approved for bedroomsrd�+�F"9* .CE 128991 �l PROFESS0P System #2 Approved for bedrooms X10\\ PROESS0P�� Disapproved Conditional approval for bedrooms, with the following stipulations: .4 OF A4� ,�6 O' /j j 0 �TG.R AND �a WASTLv''ATER o^ G PROGtJ\111 -1 F _15y: Original Certificate Date: -2- The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 7. ATTACHMENTS: COSA Checklist X Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other Legal Description: HOMESTEAD HILLS BLOCK 2 LOT 3 Parcel ID: 015-173-18 If more than 1 septic system on lot: COSA Checklist # _of A. WELL DATA — COMMUNITY CLASS A ❑ Well log is filed with Onsite (or attached) Date drilled Total depth _ft Cased to _ft ❑ Sanitary seal is functioning correctly ❑ Wires are properly protected Casing height (above ground) _in. Date of flow test for COSA Static water level at beginning of test ft. Comments B. TANK DATA Age of tank(s) 0 — NEW TANK years Tank type/material SEPTIC / HDPE Measured operating fluid level in septic tank NEW ® Standpipes/foundation cleanout per record drawing Date of pumping NEW TANK D. ABSORPTION FIELD DATA Which system tested (date installed) 10/19/1991 ® ALL standpipes present per record drawing Total measured depth from grade 9_5 ft (max) Measured depth to pipe invert from grade 3_3 ft (min) ❑ N/A — pressurized field Structure served by this system Well production at time of test _gpm Water storage tank volume_ gallons Well disinfected for coliform test? ❑ Yes ❑ No ❑ Coliform bacteria is Negative Nitrate _mg/L ❑ Nitrate less than MRL (ND) Arsenic ug/L ❑ Arsenic less than MRL (ND) Collected by Date of Sample C. LIFT STATION ❑ Required maintenance completed Age of lift station _ years Lift station material Comments: Adequacy test date 6/14/2021 Results Z Pass For 3 bedrooms Fluid depth prior to test 7 in Water added 450 gal New depth 11 in ❑ Monitor tubes go to bottom of effective. If not, state depth into effective APPROX. 6.2' OF THE TED Elapsed time 1220 min ® Code -required soil cover over field Final fluid depth 5 in ❑ System presoaked Absorption rate 450 gpd (Required if vacant for greater than 30 days prior to Any rejuvenation treatment (past 12 months) N date of test) Gallons introduced gallons If yes, enter date Comments/Deficiencies: F.u. E. SEPARATION DISTANCES From Private Well on Lot to: (Please enter distances if less than required or if community well) Septic Tank/Lift Station on Lot > 100' ® Yes if No Community Sewer Manhole/Cleanout > 100' ❑ Yes if No ft ❑ Yes if No Neighboring Tank > 100' ❑ Yes if No ft Private Sewer/Septic Line > 25' ❑ Yes if No Absorption Field on Lot > 100' ❑ Yes if No ft Holding Tank > 100' ❑ Yes if No Neighboring Absorption Fields > 100' if No ft Animal Containment > 50' ❑ Yes if No ❑ Yes if No ft ft If septic tank is under driveway comment below Manure/Animal Excreta Storage > 100' Community Sewer Main > 75' ❑ Yes if No ft ❑ Yes if No From Septic/Holding Tank on Lot to: (Please enter distances if less than required) Building Foundations > 10' ® Yes if No ft Surface Water > 100' ® Yes if No _ Property Line > 5' ® Yes if No ft Wells on Adjacent Lots: ® Yes Absorption Field > 5' ® Yes if No ft Private Wells > 100' ® Yes if No Water Main > 10' ® Yes if No ft Community Wells > 200' ® Yes if No _ Water Service Line > 10' ® Yes if No ft If septic tank is under driveway comment below From Absorption Field on Lot to: (Please enter distances if less than required) Building Foundation > 10' ® Yes if No _ ft If absorption field is under driveway comment below Property Line > 10' ® Yes if No —ft Wells on Adjacent Lots: Water Main > 10' ® Yes if No ft Private Wells > 100' ® Yes if No —ft Water Service Line > 10' ® Yes if No ft Community Wells > 200' ® Yes if No Surface Water > 100' ® Yes if No ft F. ENGINEER'S COMMENTS G. ENGINEER'S CERTIFICATION l certify that l have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date. Asw Ave TH Curtis Huffman j.. CE 128991 •��� `r�F,Q' • .7122/2 1 . • •�� FDPROFEWO. ft ft ft ft ft ft ft ft MUNICIPALITY OF ANCHORAGE ~ DEPARTMENT OF HEALTH & HUMAN SERVICES Division of Environmental Services On-Site Services Section P.O. Box 196650 Anchorage, Alaska 99519-6650 343-4744 '-- CERTIFICATE OF HEALTH AUTHORITY APPROVAL FOR A SINGLE FAMILY DWELLING cO/ 5'-~-/3 -a ~ Parcel I. D. # 1. GENERAL INFORMATION Complete legal description Location (site address or directions) P/dpe~t~owner'. ',"Ko.{ & Mary Reff Mailing add, ross "~40~. Tra~gAn~. ELending agency 4400 Trapline Anchorage, AK Anoh.~ag~.; AK Day phone 99516 Day phone 346-3112 Day phone 276-1033 .... NOTE: 4."' TYPE 0 F WASTEWATER DISPOSAL: Individual on-site ......... '~ ..... ~ .. ',' Ho d~n' tank ..... on-site NOTE: . .. Public water- If community well system, provide written confirmation from S~a, fo.ADEC t~ttest~ ing to the legality and status of system.... ~' If community wastewater system, provide written confirmation from State ADEC attesting to the legality and status of system .... ~, ~. 72-025[Rev, Il91) Front MOA#21 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation of this Health Authority Approval application shows that the on-site water supply and/or wastewater disposal system is safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is in compliance with all Municipal and State codes, ordinances, and regulations in effect on the date of this inspection. $ & $ ENGINEERING Name of Firm ]7~ E.w:- ;;,,r -' ,~, Address ~le Rl.~995~ EngineeFs signature ~~Z_ ~~/r¢ DHHS SIGNATURE Approved for -P~ ' ' bedrooms. Disa roved ...... ,.,:~:' ~.:,.,, ,.~,~' '~.. . - .~.-,.,~..;,~.~.~.,;~',~?,~,.~;;~; ..~ '. ~ tend t 0nal approval. fo[:~':~" ........ bedrooms, ".W t, the i' ~? /~ditionar Comments The Municipality of Anchorage Department of Health and Human Services (DHHS) issues Health Authority Approval Certificates based only upon the representations given in paragraph 5 above by an independent professional engineer registered in the State of Alaska. The DH HS does this as a courtesy to purchasers of homes and their lending institutions in order to satisfy certain federal and state requirements. Employees of DHHS do not conduct inspections or analyze data before a certificate is issued. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 72-025(Rev. 1/91) Back MOA#21 Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES Environmental Services Division 825"L" Street, Room 502 · Anchorage, Alaska 99501· (907) 343-4744 Legal Description: A. VqELL DATA Well type Log present ((~/N) Health Authority Approval Checklist t~l-q7 & ~i~,',.(~*,~,,ta J/t~3' Parcel I.D.: OI j""- / 73' ~/ ff r'rl ~->< I~)B, or C, attach ADEC letter, water system number ~ Date completed ~ / J / 7 2_ ~ ~ Total depth_ D- ~'-? ' Cased to Casin~d3~ Sanita~ seal (Y/N) ~jresqStoperly protected (Y/N) FROM~Q.~ AT INSPECTION Date of test ~ Static wat~/ Well~uction g.p.m, g.p.m. WATER SAMPLE RESULTS: Coliform Nitrate ~ ~Other bacteria D.~te ~: ~ Collected by: B.~/HOLDING TANK DATA Date installed to' } I ~ [q I Tank size [ o o O Number of Compartments oZ __ Cleanouts 0//N) V ~ 5 Foundation cleanout (~/N) x/ti. ~ Depression (Y/~ /o 0 High water alarm (V/~) Date0fpumpingil//~/aiff' Pumper/~-+ ilom~/ ~,el,c~3 C. ABSORPTION FIELD DATA Dateinstalled I0'/i q/q] Soilrating 'orft2/bdrm) O.~/ ~' Systemtype Length. 7 bt Width 3 Gravel thickness below pipe '7 / Total depth Effective absorption area }O '3 (o Monitoring Tube present(i~q'q) Y* J Depression over field (Y/I~) '~' o Date of adequacy test Il / ~ / ~ F Results (Pass/Fail) ~ 5.,( For 3 bedrooms Fluid depth in absorption field before test (in.); ] g hnmediately afier~0~ gal. water added (in.): ~ ') Fhfid depth ~ ~ (ins.) Minutes later: /3~O }n ~ et, Absorption rate = ~'t--~O ~ .g.p.d. Peroxide treatment (past 12 lnonths) (Y/N) /~ o,~ ~,,~o ~.,x) If yes, give date D. LIlT STATION Date installed Size in gallons ~ Manhole/Access (Y/N) "Pump~'Pump off' level at* High water alarm level at* ~*Datum E. SEPARATION DISTANCES SEPARATION DISTANCES FROM WELL ON LOT TO: ~vJA- - ,,-0 ~,.,4. t.,_ o~,/ cO7" Building foundation Surface water Curtain drain t~ 0,,, 4 ~-~holding tank on lot : On adjacent lots Absorption field on lot Public sewer main ~ Public sewer manhole/cleanout Sewer~ce/ line Lift station SEPARATION DISTANCES FRO~OLDING TANK ON LOT TO: Building foundation ~ q- Property line ~ ~ Abso~tion field Water mai~semice line ] 0 ~ Surface water/drainage / ~ 0 ~¢ Wells on adjacent lots SEP~A~ON DISTANCE FROM ABSOR~ON FIELD ON LOT TO: ~6 / ~ Water maiWse~ice line Driveway, parking/vehicle storage area 0 Wells on adjacent lots-~ 13~0 -4- Property. line lO / (e~/~/~r~ F. ENGINEER'S CERTIFICATION I certify that I have detertnined thrufield inspections and review of Municipal records th~~ ~n~s are in conformance with MOA HAA guidel3nes in effect on this date. ........................................................................................................... a~&¢~.!..~g~=~ .... HAA Fee * ~ ba ~ ~ Waiver Fee $ Date of Payment //- 7-- 7 S Date of Payment / Receipt Number ~ ~ ~ Receipt Number Rev. 8/95 OSS: haa.wk.doc MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH & HUMAN SERVICES Division of Environmental Services On-Site Services Section P.O. Box 196650 Anchorage, Alaska 99519-6650 343-4744 Parcel I.D. # CERTIFICATE OF HEALTH AUTHORITY APPROVAL FOR A SINGLE FAMILY DWELLING I '-~ .?~ - ~.~ HAA# ~e\~"~c~c)L\c~tz; 1. GENERAL INFORMATION Complete legal description Location (site address or directions) ~rz~Do T"~PI~%'~' ~' Property owner Mailing address Lending agency Mailing address Agent Address Day phone Day phone Day phone 2. NUMBER OF BEDROOMS: 3. TYPE OF WATER SUPPLY: Unless otherwise requested, HAA will be held for pickup, NOTE: Individual well Community well X Public water If community well system, provide written confirmation from State ADEC attest- ing to the legality and status of system. TYPE OF WASTEWATER DISPOSAL: Individual on-site Holding tank Community on-site NOTE: Public sewer If community wastewater system, provide written confirmation from State ADEC attesting to the legality and status of system. s3uewwoD leUO!l!PPV :suo!Jelnd!is 8U!MOIIOJ eqi q),!M 'suJooJpeq 'SLUOOJpeq JO,~ le^oJdde leUO!l!puoo 'pe^oJddes!(3 Jot peAoJdd¥ --~ =II-IN/VNDIS SHHO /~, ~ 2.. ~,/ e3eC] 'uo!~oedsu! s!q~ ~o e~ep sql uo loej~e u! suo!leln§eJ pus 'seoueu!pJo 'sepoo e3g),S pus led!o!unlAJ lie LI3!~ eoUe!ldUJoo u! $! uue),s~s lesods!p ~ele~e~,s~ ~o/pue/~lddns ~e3e~ ei!s-uo eq~ 'uo!3oedsu! pus uo!~eDp, se^u! ~LU UJOJ~ pus sel!~ e§eJoqouv ,to ~!led!o!unlAI ~uo~ peu!elqo uo!),~u~o~u! eq~ uo peseq ~eql ~Me^ ~eq~Jn,t I 'u!e~eq pe~eo!pu! e~n3onJ3s ¢o ed~ pus SLUOOJpeq ~O ~eq~unu eq~ Jot e3enbepe pus leuo!~3un; 'e,tes s! uJe~,s~s lesods!p ~e3e~else~ Jo/pus ~lddns ~el~ e3!s-uo sql 3eLl~ S~OLIS uo!~eo!ldde le^o~dd¥/~!Joqlnv qileeH s!q3 ¢o uo!ie§p, se^u! /~LU :~eq~./~J!JeA I 'MOleq UMOqS e~ep uo!~ep!le^ sql ~o se pue o~eJeq pex!~e legs ,~uJ ~q pe!j!~JeO sv '9 I~=I=INIDN:1 Aa NOI.LO::IdSNI dO .I.N=IRI=I/V/S  Municipality of Anchorage Department of Health & Human Services HEALTH AUTHORITY APPROVAL CHECKLIST Legal Description: /..-5 ~ 1'~3w',er~'~c~ ~-~ Parcel I.D. A. WELL DATA Well type Co~h~n~-~ If A, B, or C, attach ADEC letter. Log present (Y/N) Total depth Sanitary seal (Y/N) Date completed Cased to Casing height Wires properly protected (Y/N) ADEC water system number ~'Z.ZI- Driller Date of test Static water level Well flow Pump level FROM WELL LOG g.p.m. AT INSPECTION MUNICIPALITY OF ANCHORAGE ENVIRONMENTAL SERVICES DIVISION R[CEIVED SEPARATION DISTANCES FROM WELL TO: Septic/holding tank on lot Absorption field on lot J '~-'~ Public sewer main Public sewer service line '+'~OO~ ; On adjacent lots ; On adjacent lots Public sewer manhole/cleanout Petroleum tank WATER SAMPLE RESULTS: Coliform Date of sample: Nitrate Other bacteria Collected by: B. SEPTIC/HOLDING TANK DATA Date installed Cleanout.s=(y/N)' y "~ High water alarm (Y/N) Date of pumping Tank size Compartments Foundation cleanout (Y/N) )/ Depression (Y/N) ~ ~ Alarm tested (Y/N) J~ ~ SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK TO: Well(s) o~ Ici ~ ':' ":~J~ //~- On adjacent lots To property line ~C)' Absorption field ~" Surface water/drainage -x. Co ,~ c,,~ ~'~z,/ lc),- 11 72-026 {Rev. 3/91) Fron~5-i~O~2~ ~:> '~ Foundation Water main/service line ~// ""~"'Y~" ~'~"~/"'¢'X /'~"~'??'TZ CONTINUED ON BACK PAGE C. LIFT STATION Date installed Size in gallons Vent (Y/N) "Pump on" level at High water alarm level Meets MOA electrical codes (Y/N) ~J'J- SEPARATION DISTANC~'~RoM LIFT STATION TO: Wo. Jl~- On adiacent lots Manufacturer Manhole/Access (Y/N) .-~-~ ~ level at Surface water D. ABSORPTION FIELD DATA Date installed O c.~t- ~.~ Length -7 4-' Width Total absorption area Depression over field (Y/N) Results (pass/fail) Soil rating Gravel thickness '7 ' Cleanouts present (Y/N) Date of adequacy test for Peroxide treatment (past 12 months) (Y/N) t~ System type -}Y~r, Total depth Y bedrooms If yes, give date SEPARATION DISTANCE FROM ABSORPTION FIELD TO: Well on lot ~ /L),/'//~ On adjacent lots -/' /~,~' ! Property line To building foundation '~_o' To existing or abandoned system on lot On adjacent lots Surface water Curtain drain -+- h~O' '" lO0' ' Cutbank 4- I oo: Water main/service line Driveway, parking/vehicle storage area E. ENGINEER'S CERTIFICATION I certify that I have checked, verified, or conformed to all MOA and HAA guidelines in effect on the date of this inspection. Signature Engineer's Name ~/~' Date £~ - HAA Fee $ /~9, (2 C~ Date of Payment Receipt Number Waiver Fee: $ Date of Payment Receipt Number WALTER J. HICKEL, GOVERNOR DEPT. OF ENVIRONMENTAL CONSERVATION ANCHORAGE DISTRICT OFFICE 3601 C STREET, SUITE 322 ANCHORAGE, ALASKA 99503 563-6775 September 30, 1991 Mr. Chuck Landers Constructing Engineers HC83 Box 192-A Myrtle Drive Eagle River, Alaska 99577 Subject: Lot 3, Block 2, Homestead Hills Subdivision, Anchorage, Alaska, ADEC Project Number 9221-WA-006; Review Dear Mr. Landers: This is in response to your submittal, received in this office on September 20, 1991, in which you address the concern noted in my September 13, 1991 letter. The submitted information regards the request to waive the separation distance between a Class A Public Water System Source Well and a the wastewater disposal system located on the above- referenced lot. I have completed my review of the submitted information and have the following comments. As a result of my review, I find no reason that this waiver should be denied. This is based on the fact that this Department issued a waiver on January 3, 1986 for a lesser separation between the source well and the wastewater disposal system that is to be replaced. The separation distance between the existing source well and the nearest portion of the proposed septic tank and soil absorption system will be 150 feet. Thus, as noted, the Department has found the information provided to be satisfactory for allowing a waiver in accordance with 18 AAC 72.035 and 18 AAC 80.020 (e), State Wastewater Disposal and Drinking Water Regulations, respectively. The separation distance between the Class A Public Water System Source Well and the Wastewater Disposal System on Lot 3, Block 2, Homestead Hills Subdivision has been waived from 200 feet to 150 feet. If the proposed wastewater disposal system fails, any changes to the existing public water system or the influent volume increases above that of a three bedroom home will invalidate this waiver. Mr. Chuck Landers September 30, 1991 Page 2 Thank you for your cooperation with this Department. do not hesitate to contact me. cc: John Smith, DHHS, KKK/pf If you have any questions, please ~'[ncerely, Keven K. Kleweno Environmental Engineer DEPT. OF ENVIRONMENTAL CONSERVATION WALTER J. HICKEL, GOVERNOR ANCHORAGE DISTRICT OFFICE 3601 "C" STREET, SUITE 322 ANCHORAGE, ALASKA 99503 563-6775 October 23, 1991 FOR: Chuck Landers PWSID#211669 My review of the records on file in this office reveals that the Homestead Hills Subdivision Class "A" Public Water System, is in compliance with the routine coliform bacteria samples requirements listed in Table C, and with the inorganic sampling listed in Table B of 18 AAC 80.200. Sincerely, Byron Roys Environmental Engineer BR/cf MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION DIVISION OF ENVIRONMENTAL HEALTH CERTIFICATE OF INSPECTION FOR HEALTH AUTHORITY APPROVAL OF ON-SITE SEWER AND WATER FAC LITY 264-4720 Application Date GENERAL INFORMATION (a) Legal Description (include lot. block, subdivision, section, township, range) Location (address or directions) (b) Applicant Name /~1(~;(~ '5~'"ZL4'~5 Telephone:Home -~"/~'"/~2~'~'/ Bus,ness Applicant Address (c) Applicant is (check one): Lending nstitution []; Owner/builder'l~; Buyer I-1; Other [] (explain); (d) Lending Institution Address Telephone (e) Real Estate Company and Agent Addr(}ss Telephone (f) Mail the HAA to the following address: TYPE OF RESIDENCE Single-Family'S' Multi-Family [] Number of Bedroc ms Other WATER SUPPLY individual Well [] Community~{~ Public [] Note: If commumty well system, must have written confirmation from the State Department of Environmental Conservation attesting to the legality and status. 4. SEWAGE DISPOSAL Onsite~( Public [] Community [] Holding Tank Note: If community well system, must have written confirmation from the State Department of Environmental Conservation attesting to the legality and status. 72-025 [11/84) Page 1 of 2 ENGINEERING FIRM PROVIDING INSPECTIONS, TESTS, FILE SEARCH, DATA AND INFORMATION As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation of this Health Authority Approval shows that the on-site water supply and/or wastewater disposal system is safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is in compliance with all Municipal and State codes, ordinances, and regulations in effect on the date of this inspection. Name of Firm /¢~W"~(~'""~ Telephone Date ^,,p oved,or & Approved ~ Disapproved ConOitional Date Terms of Conditional Approval CAUTION The Muncipality of Anchorage Department of Health and Environmental Protection (DHEP) issues Health Authority Approval certificates based solely upon the representations given in paragraph 5 above by an independent professional engineer registered in the State of Alaska. The DHEP does this as a courtesy to purchasers of homes and their lending institutions in order to satisfy certain federal and state requirements. Employees of DHEP do not conduct inspections or analyze data before a certificate is issued. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. Page 2 of 2 ¢ WELL DATA Well Classification MUNICIPALITY OF ANCHORAGE (MOAJ MUNICIPALITY OIFIr~,~'~JETHORITY APPROVAL (HAA) DEPT. OF HE^LT~;I~IECKLIST- FEBRUARY 1984 ENVIRONMENTAL PROTECTION 264-4720 MAY 0 8 RECEIVED Legal Description: IfA, B, C, D.E.C. Approvec~)'~::~L~ I, ~,~ ~'/I(¢(~? ent (Y/N) Date Completed Yield Cased to ____ Depth of Grouting -- Static Water Leve~l"~ Pump Set At -- Above Gro-~'b¢~____- Sanitary Seal on Casing (Y/N) Casing Height Electrical Wiring in Conduit (Y/N)"~~ Depression Around Wellhead (Y/N) Separation Distances from Well: To Septic/Holding Tank on Lot ~ ; On Adjoining Lots To Nearest Edge of Absorption Field on Lot To Nearest Public Sewer Line Cleanout/Manhole Water Sample Collected by Water Sample Test Results Comments ewer Oining Lots -' To Nea er st Sewer ;%~.,~on Lot - B. SEPTIC/HOLDING TANK DATA Date Installed ('~ -/'~ ~' ~-~ siZe /¢t'C'-~J ~/¢¢ No. of Compartments Standpipesj~N) Air-tight Capsj~) " Foundation CleanoutON) Depression over Tank (Y~) Date Last Pumped. Pumping/Maintenance Contract on File (Y/N) ////~ ; for Holding Tank High-Water Alarm (Y/N) ~-!/f¢' Temporary Holding Tank Permit (Y/N) Separation Distances from Septic/Holdi~,g Tank: To Water-Supply Well '-~¢' To Property Line To Water Main/Service Line /'~ Course Comments "~ ~'~:-&" /¢";~/~f/YfA-~) To Building Foundation To Disposal Field To Stream, Pond, Lake, or Major Drainage Page 1 of 2 ABSORPTION FIELD DATA Soils Rating in Absorption Strata Date Installed C~//~ - (~-/3 "?.5 Width of Field ~,~//~ ~ /3 Type of System Design Length of Field Depth of Field ¢~ravel Bed Thickness Square Feet of Absorption Area -~07-/~--- ~"/Z Standpipes Present~N) Depression over Field (Y&. Date of Last Adequacy Test Results of Last Adequacy Test ,/~E'~///~'7~- - ~'~'~' ,~27~//~-'¢ ,~'~,¥~-'/'~. Separation Distance from Absorption Field: TO Water-Supply Well '-~ To Building Foundation Lot ~/c~,~/~,~" ~/ "~-E~ //,/7~ To Water Main/Service Line ~ / To Stream/Pond/Lake/or Major Drainage Course To Driveway, Parking Area, or Vehicle Storage Area /~ / ~ Comments -~--9'~'-~" ~ /~¢/~'Y~,~ )~H /o / / To Property Line To Existing or Abandoned System on ~'X3/~'; On Adjoining Lots ~'~ To Cutbank (if present) LIFT STATION /; High Water Alarm Level at Tested for Electrical Codes (Y/N) Comr~ents Dimensions Manhole/Access (Y/N) "Pump Off" Level at Vent (Y/N) s MOA ** Check Permitted Bedroom Rating Against HAA Request ** I certify that I have c~ecked,,ve~lified, or conformed to all MOA and HAA guidelines in effect on the date of this inspection. Signed ~¢~----~' Date 3 Date of Payment ~ Page 2 of 2 72-026 {11/84) ^LASKA ellOl[qOIlm8IlTAL COIITI OL SelquIC $, IIqC. ~.§in¢¢rJn§ $ ~nuir~nmcnld Studies RICHARD SELLERS 4400 TRAPLINE DRIVE ANCHORAGE AK 99501 SELLER-RICHARD SELLERS 05~08~86 RICHARD SELLERS 4400 TRAPLINE DRIVE ANCHORAGE AK 99501 60187 LEGAL:HOMESTEAD HILLS BLOCK 2 LOT 3 ADEQUACY TEST FOR SEWER SYSTEM ADEQUACY TEST DATE-04/30/86 THE TYPE OF ABSORPTION SYSTEM IS A TRENCH/CRIB WITH AN AREA OF 813 SQFT. THE SYSTEM IS CAPABLE OF ACCEPTING 450 GALLONS OF WATER PER DAY. THE SURGE CAPACITY OF THE SYSTEM IS 472 GALLONS. BASED UPON THE TEST DATA THE SYSTEM IS ACCEPTABLE FOR A 3 BEDROOM HOME. SEPTIC TANK ADEQUACY THE EXISTING SEPTIC TANK VOLUME OF 1000 IS ADEQUATE FOR THIS 3 BEDROOM HOUSE. THE SEPTIC TANK/PACKAGE PLANT WAS PUMPED ON 05/01/86 · THIS REPORT DOES NOT VERIFY THE INTEGRITY OF THE PIPING FOR THE WATER SUPPLY OR WASTEWATER SYSTEM. DEPT. OF ENVIRONMENTAL CONSERVATION ANCHORAGE/WESTERN DISTRICT OFFICE 437 "E" STREET, SUITE 303 ANCHORAGE, ALASKA g9501 BILL .~'IEFFIELD, GOVERNOR Telephone: (907) Address: 274-~533 DATE: To Whom it May Concern: According to records on file in this office the Water Regulations Water System is in compliance with the State Drinking Sincerely, DEPT. OF ENVIRONMENTAL CONSERVATION ANCHORAGE/WESTERN DISTRICT OFFICE 437 'E' STREET, SUITE 303 ANCHORAGE, ALASKA 99501 BILL SHEFFIELD, GOVERNOR 274-2533 January 3, 1986 Alaska Environmental Control Services 1200 W. 33rd Avenue, Suite B Anchorage, Alaska 99503 SUBJECT: Horizontal Grand{ather Rights SeparatJ_on between- Well and Septic Systems tot Lots 3 thru 5, Block 2, Homestead Hills Subdivision, Anchorage, Alaska (8621-WA-086) & (8621-FA-094) Dear Sir: The Department has received and revieued your request ~or grandfather righ{s on separation tot the subject project. Approval is hereby given ~or the uater system and the "Certificate to Operate" is attached, Any ~uture expansion o~ the subject project uill require additional approve from this o¢~ice. Sincerely, Michael P. Leuis Environmental Engineer MPL:msm J MUNICIPALITY OF ANCHORAGE ~" DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTj~ICIPALI~' ©~ ANCHORAGE  Alaska 99501 DEPT. O; ~ : ~ 825 L Street Anchorage, ENVIRONMENTAL [ ;: 0'~ kCTION ENVIRONMENTAL ENGINEERING DIVISION ~, ~ Telephone 264-4720 d J N 8 iC)~9 REQUEST FOR APPROVAL OF INDIVIDUAL WATER AND SEW~E~EI~D DIRECTIONS: Complete all parts on page 1, Incomplete requests will not be processed, Please allow ten (10) days for processing. 1.~OPERTYOWNER [ PHONE PROPERTY RESIDENT (If different from above) ' PHONE ~' 2, BUYER PHONE '~, MAILING ADDRESS ' MAI~ [ ~ ~ ' ~~LINGADDRESS '~ , ,~~ V~ ~, -- ~ ~ MAI'L~G ADDRESS 5, LEGAL,DESCRIPTION A ~ ~, . ~ A 6. TYPE OF REIglDENCE NUMBEROFBEDROOMS ~ SINGLE FAMILY [] MULTIPLE FAMILY 7. WATER SUPPLY [] INDIVIDUAL* ~ COMMUNITY [] PUBLIC UTILITY [] One [] Four [] Other [] Two [] Five [~ Three [] Six ¢ *ATTACH WELL LOG. A well log is required for ail wells drilled since June 1975. For wells drilled prior to that date, give well depth (attach log if available.) 8. SEWAGE DISPOSAL SYSTEM INDIVIDUAL/ON-SITE** PUBLIC UTILITY **If individual/on-site, give installation date 7 ff If system is over two (2) years old an adequacy test is required by this Department. 72-010(3/78) NOTE: THE INSPECTION FEE MUST ACCOMPANY EACH REQUEST BEFORE PROCESSING CAN BE INITIATED. THIS SIDE FOR OFFICIAL USE ONLY I DATE RECEIVED INSPECTION APPOINTMENTS TIME TIME TIME DATE DATE DATE INsPECTOR INSPECTOR INSPECTOR DIRECTIONS: 1. TYPE OF RESIDENCE NUMBER OF BEDROOMS [] SINGLE FAMILY [] ONE [] THREE [] FIVE [] OTHER [] MULTIPLE FAMILY [] TWO [] FOUR [] SIX PERMIT NUMBER 2. WATER SUPPLY [] INDIVIDUAL DEPTH OF WELL [] COMMUNITY DATE DRILLED [] PUBLIC UTILITY Connection Verified LOG RECEIVED 3, SEWAGE DISPOSAL SYSTEM P~:RMIT NUMBER [] INDIVI DUAL/ON -SITE DATE INSTALLED []PUBLIC UTILITY ~.~ '~ Connection Verified iNSTALLER []Septic Tank or []Holding Tank Size: /'~O<~ If Tank is homemade SOILS RATING give dimensions: , TYPE OF TANK MANUFACTURER 4. DISTANCES Septic/Holding Tank Absorption Area ISewer Line Nearest Lot Line WELL TO: Absorption Area to nearest Lot Line 5. COMMENTS [] APPROVED FOR ~ BEDROOMS [] CONDITIONAL APPROVAL (letter must ~'(~ ~mpany certificate) [] DISAPPROVED DATE ~ LEGAL DESCRIPTION 72-010 (Rev, 3/78) 907/ .:'fi4-4I 1 ~ June 13, 1979 Robert Douthit Star Route A Box 1735-T Anchorage, Alaska 99507 Subject: Lot 3 Block 2 Homestead Hills Subdivision Approval for your individual sewer and water facilities will not be granted until the following items have been completed: (1) A four(4) inch cast iron cleanout be installed to the septic tank and leaching area. (2) The septic tank be pumped with a receipt submitted t.o this effice. (3) A percolation test be performed on the existing leaching area. This will determine if the system is adequate according to National Standards. A list of private firms who perform the test is enclosed. Notify this department for a re-inspection when descrepancies have been corrected. If there are any further questions, please contact this office at 264-4720. Sincerely, Robert C. Pratt, R.S. Associate Specialist RCP/ljw CC: First Federal'Savings and Loan % Rick Ansley Post Office Box 4-2200 99509 Ritg' Rosenbegg - Area Realtors 3300 C Street 99503 TION MATERIALS TESTING * QUALITY CONTROL SOILS ENGINEERING 2204 Cleveland Ave. / P.O. Box 10-1126 / Anchorage, AK 99510 / 277-0231 710 3rd Ave. / P.O. Box 60547 / Fairbanks, AK 99706 / 452-1267 · 456-5155 June 28, 1979 Mr. and Mrs. Douthit S~A Box 1735 Anchorage, Alaska 99507 Re: Adequacy Test, Lot 3, Blk 2, Homestead Hills Dear Mr. and Mrs. Douthit: The Septic System located on the above referenced project tested as follows: 300 gallons of water in 24 hours If you have any questions concerning this test, please contact our office. Yours very truly, CONSTRUCTION TEST LAB Managing Engineer RJP/gak GREATER ANCHORAGE AREA BOROUGH Department of Environmental Quality 3330 "C" Street, Anchorage, Alaska 99503 274-4561 Time of Inspection I ' ~.)0 Date of Insoectton lO'- - ~' R£QU~ST FOR APPROVAL OF ~ INDIVIDUAL SE~ER & WA~R FACILITIES ,, V Addres~: '~. b Number of Bedrooms: A. TyPe (_..Er"~,,~, ~ C. Construction D. 7. Sewage Dtsoosal System: A. Z~tan~d lq q ~ C. Septic Tank: 1. D. Seepage Pit: 1. Size /S ~ X~_~' 2. Disposal Field: Depth .... Bacteria] Analysis Phone Total Length of Lines Distances: A. Septic Tank i~r)~ I ........ , ^~orpt~on Area ~1{ To' ~ , Nearest Lot Line ~ ~ I.~ , Other Contamination Fecundation to Septic Tank J] / "~ Absorption Area Absorption Area to Nearest Lot Line ~' ; ~ , Sewer Lines "'Request for Approval ot zndivi~ual Sewer ~ Wate'~ Faoilitz~s Pag~ Two 9. Comments: ~_,.~;~ Approval Valid ~or One Year From Date Signed ' G~ea~er Anchorage Area Borough, Department of Environmental Quality DIAGRAM OF SYSTEM ! certify that the information contained in this request for eppreval to be · true and accurate representation of the subiect sewer and water facilities located at: