Onsite File Sue Tawn Estate #2 Block 3 Lot 1 #051-501-27 Municipality of Anchorage On -Site Water and Wastewater Section • (907) 343-7904 Page of ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP201051 PID Number: 051-501-27-000 Dwelling: ❑ Single Family (SF) ❑ with ADU ❑ Duplex (D) ❑ Two Single Family Project: ❑ New ❑ Upgrade Name BANACH TODD & HEIDI ABSORPTION FIELD ❑ Deep Trench ❑ Wide Trench ❑ Bed ❑ Mound Site Address 23262 Ricky Way Chugiak ❑ Other Phone Number of Bedrooms Soil Rating Total depth from original grade 907.240.6511 4 0.7 GPD/SF varies 3 to 8 Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade varies 0.5 to 3.5 Ft. Gravel depth beneath pipe 0.5 Ft. Subdivision Block Lot SUE TAWN ESTATE #2 3 1 Fill added above original grade 0 to 4 Ft. Gravel length 57 Ft. Township Range Section Gravel width 15 Ft. Beds: Number of Lines 3 Distance between lines 5 Ft. SEPARATION DISTANCES To Septic Absorption Lift Station Holding Sewer Total absorption area Number of trenches Dist. between trenches From Tank Field Tank Line 8j5 Ftz Ft. Well >100' >1 00' NA NA NA TANK 9 Septic.❑ S.T.E.P. ❑ Holding ❑ Other Manufacturer (2) Anchorage Tanks Capacity 2 tanks at 1,250 Gal. Surface Water >100' >1 00' NA NA Material Number of compartments Lot Line >10' >10' NA NA NA both are steel both tanks have 2 comp. Foundation > 10' >10' NA NA I LIFT STATION Manufacturer Capacity ---�" i Remarks field and garage tank installed in 1995 Gal. additional septic tank installed in 2001 to drain house Alarm location Electrical installed by PIPE MATERIAL House to tankTank to Installer PVC drainfield PVC homeowner Drainfield PVC CO/MT PVC Inspector ,Jim Vail, PE and Curtis Townsend, PE BENCH MARK (Assumed elevation) 570 ft Inspdection 1�t 10-13-1995 2nd 10-16-1995 Location and description 3`d 3/16/20 4"' 4/11/20 NE corner of garage slab ON-SITE WATER AND WASTEWATER SECTION APPROVAL Engineer's Stamp Conditional Approval: Date Septic System' Approved Date 301�62 i) �•, Dat, �P FESSIO��L Note: this approval does not include well permit requirements. Co Q ! .�J��Lyj W i 9 R "l W oz I— 0 1 T Ito Q � ECl 4�%V� Eklutna Engineering, LLC curtistownsend@grnaiI.com April 17, 2019 Subject: Sue Tawn Estate #2 Block 3 Lot 1 Septic System Permit Request Narrative OSP 201051 Septic permit SW950198 was issued by MOA for the installation of a bed absorption field and a 1250 gallon steel septic tank. The bed and tank were installed. An inspection report was submitted by the engineer. MOA had additional comments on the inspection report that were never addressed. This permit application serves to address the MOA comments from June 1997. An additional 1250 gallon steel septic tank was installed in 2001 without the benefit of a permit. This permit application serves to document the install of that septic tank. MOA provided the following comments June 26, 1997. Their resolution is described. Middle distribution pipe 0.3' higher than outside distribution pipes. A profile level was performed April 2020 and all the distribution pipes are at the same elevation. Monitor tube not deep enough and not perforated. A steel pipe was driven deeper into the existing monitor tube and is now at the correct elevation. It is perforated in the area where the septic rock is present. No topsoil/seed over mound. The ground over the septic system has been topsoiled and seeded. A nice green lawn now grows over the field. Structures (shed) over septic. The shed was moved by the homeowner and is now 5' minimum away from the septic tank. Soils. Two test holes were dug in July 1995. Percolation tests were performed in a soil strata that contained sandy gravel with boulders. The percolation rate was 2.6 and 2.9 mpi. The engineer used 0.7 gpd/sf to calculate the required size of the bed. Groundwater was discovered while digging the test holes. This information was previously provided to MOA and is on file. Test hole locations shown on the currently submitted drawings are based on dimensions provided on the 1995 soils logs. Soil Absorption System Design. See Sheet 1 of the design package. This field was tested for adequacy in March 2020. 798 gallons of water were inserted into the double cleanouts downstream of the septic tank near the garage. The water level in the monitor tube was measured before, during and after the test. At no point was water detected in the monitoring tube. This field is adequate as a 4 bedroom field. 3. Wells. This lot and the surrounding lots are served by private water wells. The location of wells are shown on the drawing. The quality of the water was tested in March 2020 of the subject property. The results of those tests are included. The adequacy of this well was also tested. It produced 798 gallons of water in 253 minutes Neighboring Wastewater systems. The neighboring septic systems areal I greater than 10' from the property line. 5. Surface Water: There is no surface water within 100 feet of the septic tanks and drain field. The drain field maintains at least 100 feet from all surface water. b. Topography: The area where the field was installed has a surface slope of approximately 2%. The installation will not affect the future development of this or the surrounding lots. Sincerely, Curtis L. Townsend, P.E. Attachments -QRRIaP�OF4R d� 7H . � bptE I Zr��`i; 4 '`1►�pROfE85fOX���+ I SKY WAY \ 2" INSULATION PLACED OVER <'OJ \ I LINE FROM TANK TO FIELD \ �y �I 1250 GAL TANK, 100' INSTALLED 2001 \ i -1 )DCO2 B / 108' \ A BM FCO r \ GARAGE 2 BR J 1 / HOUSE �� \ ,WELL > 80'/FROM J \ \\ / PROPERTY/LINE I FROM CPR PROPERTY \ �� LINE ) I `\ O 100' I ON—SITE CONSTRUCTION HISTORY 1. 101' DEEP WATER WELL WAS DRILLED AUG 1995 2. 1,250 GALLON SEPTIC TANK AND NEW 57' x 15' x 0.5' EFFECTIVE DEPTH ABSORPTION BED WAS CONSTRUCTED NOVEMBER 1995. 3. 1250 GAL SEPTIC TANK WAS INSTALLED IN 2001 AND CONNECTED TO FIELD. \ -�-57'x15'x0.5'ED BED, INSTALLED 1995 Oy G �G 7 O \DCO 12 0 TANK, NNS LLE b 1995 —SkiED \� —2" II SU L TI( OVER l IN F HOUSE TO SEPTIC > 100' FROM PROPERTY LINE PLACED DESIGN PARAMETERS PRIMARY SEPTIC SYSTEM NO. BEDROOMS: 4 (600 gpd) TANK SIZE: 1250 G PERC RATE: 2.9 MPI SOIL RATING: 0.8 GPD/SF AREA REQUIRED: 750 S.F. SYSTEM TYPE: BED 57' X 15' X 0.5' EFFECTIVE DEPTH, 4' COVER PROVIDES 855 SF. SWING TIES ON PAGE 2 As Built Prepared for ...�""�,I, TODD AND HEIDI BANACH ••�P�E,OF 23262 Ricky Way Chugiak, Alaska 99567�,.•�'• ••'' ��� SUE TAWN ESTATE #2 BLOCK 3 LOT 1 q TH •, .............. T........................... OSP201051 1,�00 0 EKLUTNA ENGINEERING, LLC DATE: 4/17/202............. -\ CURTIS"TOWNSEND' 19162 MOUNTAIN ROAD DRAWN: CLT �j��J`'•.,•N ��1 Z021 �� CHUGIAK, ALASKA 99567 = �j<'co�•••E.....•••'' ��•� 907 355-9820 SCALE: 1" 50' , , I�ss� ���� PID: 051-501-27 SHEET 1 OF 2 ,�%vlaws � FCO 569.5' 569.4' DC01 569.1' FINISH GRADE MT 567.7' 569.1' CO 566.7' 2" INSULATION 564.0' 1250 GAL TANK INSTALLED 1995 560.20'561.1 561.6' 1' SEPTIC ROCK—/2' SAND BED — 559.1' FCO 575.6' 570.1' 570.4' FINISH GRADE DCO2 567.7' 567.4' MT 2" INSULATION 1250 GAL TANK INSTALLED 2001 561.1'----561.6' 559.8' 559.1— 2' SAND BED 1' SEPTIC ROCK BENCH MARK WAS NORTHEAST CORNER OF GARAGE SLAB, ASSUMED ELEVATION 570' As Built Prepared for TODD AND HEIDI BANACH .•�P•..•• �� # 23262 Ricky Way Chugiak, Alaska 99567 �,.�'� •�'' 0 AV SUE TAWN ESTATE #2 BLOCK 3 LOT 1 A 49 T OSP201051 %... f I ...."""""' EKLUTNA ENGINEERING LLC '�� �������{ ���.�7 DATE: 4/17/2020 CURTIS TOWNSEND : 19162 MOUNTAIN ROAD �j�'�°• No. CE 11904 DRAWN: CLT J CHUGIAK, ALASKA 99567 SCALE: 1" - 5' ��� ••......1�.••• (907) 355-9820 PID: 051-501-27 SHEET 2 OF 2 ,, IL MARK A B C 1995 Tl 24'-10" 23'-4" 1995 T2 18'-6" 30'-10" DC01 1 16'-5" 34'-3" DC01 2 15'-6" 35'-7" MT 81'-11" 65'-2" CO1 95'-9" 84'-9" CO2 100'-6" 87'-0" CO3 105'-2" 90'-6" 2001 Tl 27'-9" 47'-2" 2001 T2 25'-5" 39-11 " DCO2 1 24'-9" 37'-8" DCO2 2 25'-2" 36'-7" LOT 2 R� 0��,�-�" S -,o�z� R= 30. 00' SUE TA WN ESTATE ADDITION NO. 2 �s2s. LCT 1 BLOCK 3 PLA, 76-268 s. SUE TA WN ES TA TE DECK PLA T 64-9 1 LOT 3 I LEGEND ;S; SEPTIC VENT cw WELL � I 2 STREET SIGN I I – – GUY WIRE ' - z L -J POWER POLE I OVERHEAD UTILITY N 9.26*W W –7.58' NOTES 1. DIMENSIONS ARE RECORD PER PLAT 76-268. 2. UTILITIES OTHER THAN THOSE SHOWN MAY EXIST. so, s OFAL `�P�C■. ' F ■u • Dayna M. Rumfelt ■ No,13 1 22 AW }�1f�pRD�'fSSiQHAL���-� o 3. THIS SURVEY DOES NOT CONSTITUTE A BOUNDARY SURVEY AND IS SUBJECT TO ANY INACCURACIES THAT A SUBSEQUENT BOUNDARY SURVEY MAY DISCLOSE. UNDER NO CIRCUMSTANCES SHOULD ANY DATA SHOWN BE USED TO ESTABLISH ANY FENCE, STRUCTURE OR ANY OTHER IMPROVEMENTS. 4. ALL VISIBLE ABOVE GROUND FEATURES OF THE EXISTING SEPTIC SYSTEM WERE LOCATED AT THE TIME OF SURVEY AND SHOWN HERE ON. LLV D E R SURVEY & MAPPING 2890 S. BARNYARD OR,, WASILLA, AK 99654 DAYNACEAVENDERSURVEY,COM DAYNA RUMFELT {907}301-5177 PAGE 1 OF 2 Q 1'ZlZZt��4 SCALE 1" = 50' ASBUILT – NO CORNERS SET THIS DATE I HEREBY CERTIFY THAT I HAVE PERFORMED A SURVEY OF LOT 1, BLOCK 3, SUE TAWN ESTATE, ADDITION NO. 2, PLAT NO. 76-268, ANCHORAGE RECORDING DISTRICT, ALASKA, AND THAT THE IMPROVEMENTS AS DEPICTED HEREON EXIST AS SHOWN IN RELATION TO THE PROPERTY LINES. EASEMENTS OF RECORD OTHER THAN THOSE SHOWN ON RECORDED PLAT No. 76-268 ARE NOT SHOWN HEREON UNLESS OTHERWISE NOTED. DATE: 4/1/2020 FB: 2020-1 GRID: NW1160 DRAWN: DMR SCALE: 1" = 50' FILE: 20-005AB GRAVEL DRIVEWAY ' ' ' 8'x12 SHED GARAGE t W/ SHOP Imo— 1–STORY 1 FRAME HOUSE WITH LOFT , SEE PAGE 2 FOR 1 66, DIMENSIONS , Yf LOT 2 s OFAL `�P�C■. ' F ■u • Dayna M. Rumfelt ■ No,13 1 22 AW }�1f�pRD�'fSSiQHAL���-� o 3. THIS SURVEY DOES NOT CONSTITUTE A BOUNDARY SURVEY AND IS SUBJECT TO ANY INACCURACIES THAT A SUBSEQUENT BOUNDARY SURVEY MAY DISCLOSE. UNDER NO CIRCUMSTANCES SHOULD ANY DATA SHOWN BE USED TO ESTABLISH ANY FENCE, STRUCTURE OR ANY OTHER IMPROVEMENTS. 4. ALL VISIBLE ABOVE GROUND FEATURES OF THE EXISTING SEPTIC SYSTEM WERE LOCATED AT THE TIME OF SURVEY AND SHOWN HERE ON. LLV D E R SURVEY & MAPPING 2890 S. BARNYARD OR,, WASILLA, AK 99654 DAYNACEAVENDERSURVEY,COM DAYNA RUMFELT {907}301-5177 PAGE 1 OF 2 Q 1'ZlZZt��4 SCALE 1" = 50' ASBUILT – NO CORNERS SET THIS DATE I HEREBY CERTIFY THAT I HAVE PERFORMED A SURVEY OF LOT 1, BLOCK 3, SUE TAWN ESTATE, ADDITION NO. 2, PLAT NO. 76-268, ANCHORAGE RECORDING DISTRICT, ALASKA, AND THAT THE IMPROVEMENTS AS DEPICTED HEREON EXIST AS SHOWN IN RELATION TO THE PROPERTY LINES. EASEMENTS OF RECORD OTHER THAN THOSE SHOWN ON RECORDED PLAT No. 76-268 ARE NOT SHOWN HEREON UNLESS OTHERWISE NOTED. DATE: 4/1/2020 FB: 2020-1 GRID: NW1160 DRAWN: DMR SCALE: 1" = 50' FILE: 20-005AB Name: Eklutna Engineering Lab ID#: M200200 Mailing Address: 19162 Mountain Road Date Sampled: 03/16/2020 Chugiak, AK 99567 Time Sampled: 1700 Legal Description: Sue Tawn Estate #2 B3 L1 Sampled By: CLA Date Received: 03/17/2020 Sample Site Location: First Floor Bathroom Sink Time Received: 1533 Health Guard I Parameter Method Result Unit MRL MCL Date Total Coliforms Colilert (SM 9223B) A --- --- --- 03/18/2020 E. coli Colilert (SM 9223B) A --- --- --- 03/18/2020 Total Nitrate - N TNTplus 835/836 (Hach 10206) 1.92 mg/L 0.200 10.0 03/19/2020 Arsenic Arsenic by ASV EPA 7063 <MRL µg/L 1.000 10 03/18/2020 Method Reporting Limit (MRL): the lowest concentration that can be reported reliably Maximum Contaminant Level (MCL): highest acceptable level in public water systems as set by EPA mg/L: milligrams per liter; 1/1000th of a gram µg/L: micrograms per liter; 1/1,000,000th of a gram Absent (A): none of this type of bacteria was detected Present (P): one or more bacterial cells of this type were detected Results Reported By: _____________________________ Patience Lynch Laboratory Analyst Reviewed By: 9131 E Frontage Rd, Ste 15 Palmer, AK 99645 (907)745-3005 matsutestlab.office@gmail.com Signature: Email: Jen Williams (Mar 24, 2020) Jen Williams matsutestlab.office@gmail.com MUNICIPALITY OF ANCHOkAGE Development Services Department Phone: 907-343-7904 On -Site Water & Wastewater Section W`' Fax: 907-343-7997 ON-SITE SEPTIC/WELL PERMIT APPLICATION Parcel I.D. 051-501-27-000 Property owner(s) BANACH TODD & HEIDI Day phone 907.240.6511 Mailing address PO Box 770956 Eagle River AK Site address 23262 Ricky Way Chugiak Legal description (Sub'd., Block & Lot) SUE TAWN ESTATE #2 BLK 3 LT 1 Legal description (Township, Range & Section) Lot Size 55,416 Sq. Ft. Number of Bedrooms 2 APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: (N all that apply) Absorption Field ❑ Initial ❑ Single Family (SF) [] o A[� Septic Tank ❑ Upgrade X ❑ I Holding Tank ❑ Renewal ❑ Duplex lex (D) ❑ Privy ❑ Multiple Dwellings ❑ (SF and/or D) Private Well ❑ Water Storage ❑ THIS APPLICATION INCLUDES A WAIVER REQUEST FOR: Distance: I certify that the above information is correct. I further certify applicapl�. Municipal Codes. I (Signature of property owner or authorized agent) Permit/Rush Fees: aa� Date of Payment: �f �1 420,10 Receipt Number: 1gO331) Permit No. 05,0261C)6-1 this is in accordance with Z- C) Lo Waiver Fees: Date of Payment: Receipt Number: Waiver No. GADevelopment Services\Building SafetylOn Site Water and WastewaterWorrm\01ent FormsTermit Applicafion.doc MUNICIPALITY OF ANCHORAGE Date Legal Description Site Address Engineer/~ Inspection Findings ON. SITE WASTEWATER DISPOSAL SYSTEM FIELD AUDIT Excavator (~L_ PI?& ©,~ ~ ~-~ Follow-up Notes /nitials~i /463-5-92 Municipality of Anchorage Page / of DEPARTMENT OF HEALTH AND HUMAN SERVICES ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 · Anchorage, Alaska 99519-6650 · Telephone: 343-4744 On-Site Wastewater Disposal System and/or Well Inspection Report Name: ~ ~A~ Wastewater System: ~New ~ Upgrade Address: ABSORPTION FIELD Phone: ~ ~ No. of~ooms: ~ Deep Trench O Shallow Trench ~Bed OMound ~Other Total Depth from original grade: ~ Fill added above original grade: Gravel length: Tow.ship: [5~ Range'. [WISecU°": t~ VA~E5 0 ~ ~ Number of lines: ~ Distance baleen lines: WELL: ~ New ~ Upgrade Gr.velwidth: /~ Ft. ~I ~ Ft. Classification (Private. A.B.C):p~,O~V~ Total Depth:l~. ~ Ft. Cased To:[~l;VFt. Total absorption~ SQ. ,~"ipe ~aterial: Yield: [~ GPM ~ Pump Set at: 70 Ft. Casing Height Above~,o,n,:,~. TAN K SEPARATION DISTANCES ~Septic ~ Holding D S.T.E.P. To Septic ~ Absorption ~iff Holding Public/Private Manufacturer: Capacity in gallons: Prom Tank Field Station Tank Sewer Lines AHC~O ~A~ ~ ~K Material: Number of Compa~ments: Sudace Water J 1o f17~ ~ LIFT STATION Lot I ~ Size in gallons: I Manufacturer: Line ~ I ~ 0 / "Pump on' level at: ~ "Pump off" level at: High water alarm at: Foundation CuHain Pump Make & Model ~ Electrical inspections pedormed by: Remarks: BENCH MARK Location and Description: Assumed ~ Ft Elevation: Department of Health and Human Se~ices approval Reviewed and approved by: Date: 72-013 (Rev. 9/91) MOA 25 PermitNo. ~.~/--,/--J ~"~/'~'~ Page Municipality of Anchorage DEPARTMENT OF HEALTH AND HUMAN SERVICES ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 · Anchorage, Alaska 99519-6650 · Telephone: 343-4744 On-Site Wastewater Disposal System and/or Well Inspection Report Legal Description: ~oT' I .,\ 72-013 A (Rev. 9/91 ) MOA 25 ~IEET OF 4 L erIifiei rilling by SULLIVAN WATER WELLS P.O. SOX 670272, CHUGIAK, ALASKA 9956}' * TELEPHONE 688.2759 OWNER OF LAND ADDRESS ,dO '77o?C6 .E: ~ DRAW DOWN FT, DATE-Started Ended ~ PERMIT NUMBER DEPTH OF WELL ' /~0 T ~' STATIC LEVEL OF W~TER FF. {'"L~) '".~ ~"~ GALS. PER HR ~'O O K,N, oE c^s~,~G 6 ~o0 KIND OF FORMATION: From O From ~'~ From /to _Ft, to ~,.,o~ .Ft, to~ .Ft. ff~ '~0 ~ ''J From ~ Ft. to Ft.- ~ O~'S From .Ft. to F~m_~Ft. to~ .~ <~' ~ t ~ ~'l ~/~J~ ~ From~t. to From_/'O Ft. to~ _Ft. From ..Ft From __ Ft. to From_ Ft. to.~ Ft.. -- From Ft. From-- _Ft. to-- Ft.- From___Ft. to , From Ft. to. Ft. From -- Ft. to From .... Ft. tot Ft.. From Ft. to From Ft, to_ ,,Ft.. From .Fl. to__ From.__- Ft. to__ __Ft. From __ Fi, (o From_ _Ft. to__ _Ft._ From. Ft. to From~Ft. to_ Ft._ .Ft. Ft. Ft, Ft __.Fl. FI. .Ft. __ Fl, Ft. Ft.. Ft. Ft .Ft. Ft. MISCL. INFORMATION: :~ ~'o cFC DRILLER'S NAblE February 26, 1997 Reference: Subject: _: VAIL CONSULTING 19258 Citation Road Eagle River, Alaska 99577 Ph/Fax (907) 696-8245 RECEIVED MAR 5 1997 Municipality of Anchorage Dept. Health & Human Services Lot 1, Block 3, Sue Tawn Estate Subdivision Septic System Response to As-Built Submittal Review Questions 1. "Owner installed without permission." The regulations clearly require that the septic system be designed and, the construction of same, be inspected by a qualified engineer. It may have been misunderstanding on my pad but I was not aware that an owner, under the supervision of a qualified engineer, is not allowed to do the labor involved in constructing a septic system. I have known Mr. Banach for five or six years and knew him to be capable and conscientious. He constructed his house. I provided full time inspection and assisted with the construction. All materials used were per MOA Regulations. Quantities equaled or exceeded those calculated per original design. 2. "Date installed wrong." Date has been corrected to 10-16-95. 3. "Need elevations." See amended drawing, Page 4 of 5. "Need tle-tns. See amended drawing, Page 3 of 5. 5. "Need to show sand filter installed and sand specs." See amended drawings. A two foot sand filter was installed per the approved design. Sand was from MOA approved pit in the valley providing filter material per Paragraph D, 15.65.060 Subsurface Disposal Fields. 6. "Was leachfield or tank insulated?" No. The septic tank and leachfield have three feet or more of cover. The drain line from the house to the septic tank was insulated with 2 inch blue board for eight feet, at which point the cover exceeded three feet. RESPONSE CONT. PAGE 2 RECEIVED 7. "Replacement area shown under driveway - no!" Mumc~pality of Anchorage Bept. Health & Humaq 8e~ ~e~8 We are depicting the location of the proposed replacement area at the current driveway location. Mr. Banach is aware of the fact that the driveway cannot be located over an active leachfield and must therefore relocate the driveway should replacement of the existing leachfield be required. 8. "Is water present in ditch shown along Rickey Way?" There is normally no flow in this ditch, even during periods of high rainfall. However, intermittent flows may be experienced during breakup. 9. "Need to show test hole location." See amended drawing, Page 3 of 5. 10. "Need X- Section showing separation from the water table and to explain the 2 to 7' variation in total depth from original ground." See amended drawing, Page 4 of 5. Separation distance between bottom of gravel and water table is greater than four feet. Variance from finish grade has been corrected to read, "varies 0 to 4 feet." 11. "No legal on sheet 2/3." Corrected. 12. "When was system instafled 1995 -19967 If NOV, 1995, as -built is late.' System was installed 10-16-95. recognize that the as - built submittal made in September, 1996 was late, and that this re-submittal is late. I apologize for the tardiness of these responses and will endeavor to provide timely responses in the future. 13. Note that the Well Log has changed to Page 5 of 5. Sincerely, VAIL CONSULTING James P. Vail, P.E. MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND HUMAN SERVICES P~O. BOX 196650, 825 "L" STREET, ROOM 502 ANCHORAGE, ALASKA 99519-6650 ON-SITE WELL AND WASTEWATER DISPOSAL SYSTEM PERMIT PAGE 1 OF 1 PERMIT NUMBER:SW950198 DESIGN ENGINEER:VAIL CONSULTING OWNER NAME:BANACH TODD OWNER ADDRESS:P.O. BOX 770956 EAGLE RIVER, AL 99577 DATE ISSUED: 8/08/95 EXPIRATION DATE: 8/08/96 PARCEL ID:05150127 LEGAL DESCRIPTION: SUETAWN ESTATE #2 BLK 3 LT 1 LOT SIZE: 55416 (SQ. FT.) NUMBER OF BEDROOMS: 4 THIS PERMIT: 4 THIS PERMIT IS FOR THE CONSTRUCTION OF: DISPOSAL FIELD /SEPTIC TANK / WELL SYSTEM ALL CONSTRUCTION MUST BE IN ACCORDANCE WITH: 1. THE ATTACHED APPROVED DESIGN. 2. ALL REQUIREMENTS SPECIFIED IN ANCHORAGE MUNICIPAL CODE CHAPTERS 15.55 AND 15.65 AND THE STATE OF ALASKA WASTEWATER DISPOSAL REGULATIONS (18AAC72) AND DRINKING WATER REGULATIONS (iSAACS0) . 3. THE ENGINEER MUST NOTIFY DHHS AT LEAST 2 HOURS PRIOR TO EACH INSPECTION. PROVIDE NOTIFICATION BY CALLING 343-4744 ( 24 HOURS ) (NOT REQUIRED FOR WELL ONLY PERMIT) 4. FROM OCTOBER 15 TO APRIL 15 A SUBSURFACE SOIL ABSORPTION SYSTEM UNDER CONSTRUCTION DURING FREEZING WEATHER MUST BE EITHER: A. OPENED AND CLOSED ON THE SAME DAY B. COVERED, SEALED AND HEATED TO PREVENT FREEZING 5o THE FOLLOWING SPECIAL PROVISIONS. SPECIAL PROVISIONS THE SAND BED DATE Lot 1, Block 3, Sue Tawn Estate Subdivision Septic System and Well Permit Application Response to Review Comments Comment Responses: 1. Topo is illustrated on re-submittaL Main road drainage along Sue Tawn Dr. is on the east side and no surface drainage has been seen in this ditch, even after the heavy rains experienced the past month. I suspect there is surface flow during breakup but that it is very short lived. There is a natural swale along the west side of Sue Tawn which is heavily grassed and shows no signs of surface flow. A culvert diverts the east ditch flow along the south side of Rickey Way via a roadside ditch. Again, since my first visit to the site in May, I have not observed any surface flow in this area. 2. A second test pit was dug and TP#1 & TP#2 are indicated on the Site Plan. 3. Pero Tests are being submitted herewith on MOA forms. 4. Used falling head test for sandy soil with little clay. Pre-soak period is noted on new forms. 5. Noted. 6. The excavation will vary from roughly 7 feet on the south end of the bed to 3 feet on the north end. This is required primarily because we are picking up the sanitary waste from the one bedroom appartment, the south half of the garage. The owner plans to live in the appartment until he can afford to build his four bedroom house. He understands that the kitchen must be removed from the appartment when he finishes his house. He has designed the garage/apt, so that he can expand his garage after the house is completed. The drainline from the garage is for sanitary waste from the appartment, only. If floor drains are installed in the garage portion, they will NOT be connected to the septic system. 7. See #1, above. 8. See #6, above. 9. Corrected. 10. Narrative is included below. 11. OK. Prepared By: Jim Vail August 3,1995 MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH & HUMAN SERVICES On. Site Services Transmittal Sheet The attached paperwork has been reviewed and is being returned for the following reason(s): Discrepancy in legal description and/or owner name. Discrepancy in number of bedrooms. Signature and/or stamp missing on Show measured distances to sewers/wells,, curtain drains and streams within 200 feet of proposed system. Replacement disposal site not shown and/or tested. Calculation error in design. Show locations of all soils, percolation or water table tests. Proposed system too deep for soil test submitted. Topographic information missing or inadequate. Narrative missing or inadequate. -- Additional soil/perc test needed. -- Sand filter requirements not satisfied. Water monitoring results missing or inadequate because Incomplete; missing Well log required. Water sample unacceptable because. Please supply the necessary information and re-submit your request. Your cooperation is appreciated. Reviewer Date LEA VE THIS FORM ATTACHED TO PAPERWORK /203-rev. 4/93 Lot 1, Block 3, Sue Tawn Estate Subdivision Septic System Design Narrative Mr. Banach is proposing to build a garage with a one bedroom appartment this year and then when he can afford it, he plans to build a four bedroom house and convert the garage-appartment into a large garage-shop. He has therefore requested that the septic system be designed for four bedrooms. Topography: The lot generally slopes (10%+/-)to the north. There is a ridge that parallels Little Peters Creek that divides the property with steep slopes (25%+/-) to the west and gentler slopes (8%+/-) to the east. The hill to the east of Sue Tawn Drive has steep slopes. The property north of Rickey Way continues to slope to the north. Surface Drainage: Main road drainage along Sue Tawn Dr. is on the east side and no surface drainage has been observed in this ditch, even after the heavy rains experienced the past month. I suspect there is surface flow during breakup but that it Js very short lived. There is a natural swale along the west side of Sue Tawn which is heavily grassed and shows no signs of surface flow. A culvert diverts the east ditch along the south side of Rickey Way via a roadside ditch. Again, since my first visit to the site in May, I have not observed any surface flow in this area. Impact on Surrounding Properties: The proposed siting of the absorbtion bed should not impact the surrounding pmpedies. The nearest existing well and drainfield are shown on the Site Plan and are on the west side of Little Peters Creek well beyond MOA's separation requirements. Properties to the north and east are separated by 60 foot right-of-ways and are undeveloped within 100 feet of the proposed absorbtion bed and its replacement area. The lot to the south is presently undeveloped and is upslope from this lot and as such should not be impacted. Prepared By: Jim Vail, P.E. August3,1995 I/ 0 Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L' Street, Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST PERFORMED FOR: LEGAL DESCRIPTION: 1 2 3 5- 6- 7 ~'"'7'~1 ~ DATE PERFORME Township, Range, Section: 'T' [~'i"4, ,, 10 - ~0 1~p~¢/~5 WAS GROUND WATER ENCOUNTERED? 11 13- 14- 15- 16- 17- 18- 19- 20- COMMENTS ~'~ ~:~ ~¢~ ~' PERFORMED BY: SLOPE SITE ~SLAN IF YES, AT WHAT ~,G FT pO DEPTH? E DeCh to Water Alter. Monitoring? ~ ,C)'- Dale: ?~Zg-~' Gross Net Depth to Net Reading Date Time Time Water Drop I 7-~'%' I~ *~,'- /~ ,~,'~ -¢, ')-~'' PERCOLATION RATE ~ ' ~ (m,nutes/mch) PERC HOLE DIAMETER TEST RUN BETWEEN -~'~ FTAND z.~, ~ FT CERTIFY THAT THIS TEST WAS PERFORMED ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: 72-008 (Rev. 4/85) Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST PERFORMED FOR: LEGAL DESCRIPTION: "FPZ 1 2 3~ 5- 6- 7- 10- 11 13- 14- 15- 16- 17- 18- 20- Township, Range, Section: SLOPE WAS GROUND WATER ENCOUNTERED? iF YES. ATWRAT . SITE ~SLAN x S DEPTH? E Monitoring? / ~ ~"1' Dale: Gross Net Depth to Net Reading Date Time Time Water Drop I 7-Z7-¢~ 10 ,'~ ,'~ /0~;~ ~" ~," ~- " " 'Zo" ~" ~" ~ " " ~ 4. >'" ~, 5 ~ ,, ,/ ~0 ~, z~" ~,~ COMMENTS PERFORMED BY: z4//~'~ V'~t/'~-.' /~*~'' I ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES iN EFFECT ON THIS DATE. PERCOLATION RATE ~-' ~ [minutes/inch) PERC HOLE DIAMETER TEST RUN I~ETWEEN c~ ET AND ~' ~ FT CERTIFY THAT THIS TEST WAS PERFORMED IN DATE: ~" Z 7 -- q~' 72-008 (Rev. 4/85) VAIL CONSULTING 19258 Catation Road Eagle River, Alaska 99577 (907) 696 - 8245 Ph/Fax SOILS LOG - PERCOLATION TEST Performed For: Todd Banach Date Pedormed: 7-15~95 Legal Description: Lot 1, Block 3, Sue Tawn Estate Subdivision, Peters Creek I Organic Overburden 2 3 4 5 Moist Loamy Peat 6 7_ 8 9 -- High Water Table 10 '~ GP Sandy Gravel with Large Boulders 11, 12 13 Bottom of Pit Slope COMMENTS: Backhoe Pit. Few improvements on lot. Groundwater encountered. Soil from 7' thru 13' pero's @ 2.5 min./in, and is rated @ 188 SF per Bedroom. Performed By: Jim Vail, P.E. Date: 7-15-95 Certificate of On -Site Systems Approval Parcel I.D. 051-501-27-000 Expiration Date: GY�� 1. GENERAL INFORMATION Complete legal description SUE TAWN ESTATE #2 BLK 3 LT 1 Location (site address) 23262 Ricky Way Chugiak AK 99567 Current property owner(s) BANACH TODD & HEIDI Day phone 907.240.6511 Mailing address Real estate agent PO Box 770956 Matt Baxter Eagle River AK 99577 2. TYPE OF DWELLING: Fx� Single Family ( wo ADU ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: Day phone 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Private Well 0 Private Septic 0 Water Storage ❑ Holding Tank ❑ Community Well ❑ Community ❑ Public Water System ❑ Public Sewer ❑ Waiver request for: Distance: Received by: Date: COSA to be released to the engineer, unless otherwise requested by the engineer. sc.o �_k^A C COSA Fee $ G Date of Payment 50 X020 Receipt Number © 9 5 � 1 COSA# OSC2011 qD Waiver Fee $ Date of Payment Receipt Number Waiver # e� 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is (are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. I acknowledge that On -Site staff may visit the site to verify the information submitted. Name of Firm Eklutna Engineering, LLC Address 19162 Mountain Rd Chugiak AK 99567 Engineer's Printed Name Curtis Townsend, PE 6. DSD SIGNATURE is System #1 Approved for t_1 bedrooms System #2 Approved for Disapproved Conditional approval for bedrooms Phone 907.355.9820 Date 2 • y .:.... ........... eeoos . e�. l ..... e Date ko. cE 1V AW 1904 . •��``�a' .a w_pROFESSlO �' bedrooms, with tli"g wing stipulations: `l��ttttt(( r By: Original Certificate Date: The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 7. ATTACHMENTS: COSA Checklist X Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other l e e Uy'isn,t iC COSA Checklist blue sheet ON-SITE _ m D .- WASTE=V''ATER Z PROGRAM 1 By: Original Certificate Date: The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 7. ATTACHMENTS: COSA Checklist X Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other l e e Uy'isn,t iC COSA Checklist blue sheet COSA Checklist Legal Description: SUE TAWN ESTATE #2 BLK 3 LT 1 If more than 1 septic system on lot: COSA Checklist # of A. WELL DATA ❑■ Well log is filed with Onsite (or attached) Date drilled 811995 Total depth 101 ft Cased to 101 ft ❑■ Sanitary seal is functioning correctly ❑E Wires are properly protected Casing height (above ground) '24 in. Date of flow test for COSA 311212020 Static water level at beginning of test 16 ft. Comments B. TANK DATA Age of tank(s) 5119 years Tank type/material septic steel Measured operating fluid level in septic tank 511"149.5" 0 Standpipes/foundation cleanout per record drawing Date of pumping both tanks pumped Sept 2019 D. ABSORPTION FIELD DATA Which system tested (date installed) 1995 0 ALL standpipes present per record drawing Total measured depth from grade 6.6 ft (max) Measured depth to pipe invert from grade 5.1 ft (min) ❑ NIA — pressurized field ■❑ Monitor tubes go to bottom of effective. If not, state depth into effective 0 Code -required soil cover over field ❑ System presoaked (Required if vacant for greater than 30 days prior to date of test) Gallons introduced gallons Comments/Deficiencies: COSA Checklist yellow sheet Parcel ID: 051-501-27 Structure served by this system Well production at time of test 3.15 gpm Water storage tank volume 0 gallons Well disinfected for coliform test? ❑ Yes ❑■ Nc ❑■ Coliform bacteria is Negative Nitrate 1.92 mg/L ❑ Nitrate less than MRL (ND) Arsenic ug/L [W Arsenic less than MRL (ND) Collected by Curtis Townsend Date of Sample 31612020 C. LIFT STATION ❑ Required maintenance comp Age of lift station y Lift station material Comment Adequacy test date 3!1212020 Results QPass For 4 bedrooms Fluid depth prior to test 0 in Water added 798 gal New depth 0 in Elapsed time 253 min Final fluid depth 0 in Absorption rate ' 600 gpd Any rejuvenation treatment (past 12 months) If yes, enter date no E. SEPARATION DISTANCES From Private Well on Lot to: (Please enter distances if less than required or if community well) Septic Tank/Lift Station on Lot > 100' Z Yes Community Sewer Manhole/Cleanout > 100' ❑✓ Yes if No ft M Yes if No ft Neighboring Tank > 100' ❑✓ Yes if No ft Private Sewer/Septic Line > 25'�f✓ Yes if No ft Absorption Field on Lot > 100' Q✓ Yes if No ft Holding Tank > 100' ❑✓ Yes if No ft Neighboring Absorption Fields > 100' ❑✓ Yes if No ft Water Main > 10' Animal Containment > 50' ❑✓ Yes if No ft ❑✓ Yes if No ft ❑✓ Yes if No ft Water Service Line > 10' ❑✓ Yes if No Manure/Animal Excreta Storage > 100' If septic tank is under driveway comment below Community Sewer Main > 75' ❑✓ Yes if No ft ❑✓ Yes if No ft From Septic/Holding Tank on Lot to: (Please enter distances if less than required) Building Foundations > 10' Z Yes if No ft Surface Water> 100' E Yes if No ft Property Line? 5' ❑� Yes if No ft Wells on Adjacent Lots: Q Absorption Field > 5' E✓ Yes if No ft Private Wells > 100' ❑✓ Yes if No ft Water Main > 10' ❑✓ Yes if No ft Community Wells > 200' ❑✓ Yes if No ft Water Service Line > 10' ❑✓ Yes if No ft If septic tank is under driveway comment below From Absorption Field on Lot to: (Please enter distances if less than required) Building Foundation > 10' 0 Yes if No ft If absorption field is under driveway comment below Property Line? 10' 0 Yes if No ft Wells on Adjacent Lots: Water Main > 10' Q Yes if No ft Private Wells > 100' Yes if No ft Water Service Line > 10' Yes if No ft Community Wells > 200' Yes if No ft Surface Water? 100' 0 Yes if No ft F. ENGINEER'S COMMENTS G. ENGINEER'S CERTIFICATION 1 certify that 1 have determined through field inspections and review of Municipal records that the above systems are in conformance with MOA COSA guidelines in effect on this date.OF ,Q���t COSA Checklist yellow sheet `��'�•. Mcki9a4 Z'%'RDFE3910�L� MUNICIPALITY OF ANCHORAGE DEVELOPMENT SERVICES DEPARTMENT 907‐343‐7904 On‐Site Water and Wastewater Section Fax: 343‐7997 www.muni.org/onsite Mailing Address: P. O. Box 196650 * Anchorage, Alaska 99519‐6650 * www.muni.org Septic Tank Advisory Certificate of On‐Site Systems Approval # OSC201170 Subdivision: Sue Tawn Estates #2 Block:3, Lot: 1 One of the septic tanks for this property is 25 years old. The average life for a steel septic tank is 20 years. Typical replacement costs range from $7,000 to $11,000. This advisory must be attached to all copies of the subject Certificate of On‐Site Systems Approval. This is an example of what the metal of a 30 year old steel tank MAY look like.