ON-SITE WASTEWATER INSPECTION REPORT
Permit Number: OSP161218 PID Number:05105223
Dwelling: ❑■ Single Family(SF) ❑ Duplex (D) ❑ Multiple (SF and/or D) Project: ❑ New ■❑ Upgrade
Name:
JAY VALLIERES ABSORPTION FIELD
Address
■❑ Deep Trench ❑ Shallow Trench ❑ Bed ❑ Mound
22536 MILLER RD ❑ Other
Phone Number of Bedrooms Soil Rating Total depth from original grade
688-2461 2 0.6 GPD/SF 10 (MAX) Ft.
LEGAL DESCRIPTION Depth to pipe invert from original grade Gravel depth beneath pipe
Subdivision Block Lot 4'-6.5' Ft.3.5 Ft.
LAKE HILL ACRES#1 LOT 19, 20 Fill added above original grade Gravel length
Township Range Section 0 FL 55 Ft.
Gravel width Beds:Number of Lines Distance between lines
SEPARATION DISTANCES N3 Ft. NA NA Ft.
To; Septic Absorption Holding 1 Sewer Total absorption area Number of trenches Dist.between trenches
Tank Field Lift Station Tank Line
From 385 Ftp 1 0 Ft.
,
Well 52 76' - - c7 5 TANK NI Septic ❑ S.T.E.P. ❑Holding 0 Other
Manufacturer Capacity
Surface Water +100 +100' - _ EXISTING Gal.
Material Number of compartments
Lot Line +5' +10' - -
NA
Foundation +5' +10' - - LIFT STATIONManufacturer Capacity
Curtain Drain ! +50' +50' - - NO LIFT Gal.
Remarks * INSPECTED POST INSTALLATION Pump on level at Pump off level at High water alarm at
TO DOCUMENT SYSTEM. TN5Ti4O in. in. in.
R6'14 O / / Pump make and model Electrical Inspections performed by
PIPE MATERIAL House to tank UNK Tank ldto 3034
Installer drainfield
HOMEOWNER Drainfield3034 corm-r3034
Inspector CHARLES BALZARINI BENCH MARK (Assumed elevation)100 ft
Inspection t, Location and description
dates: 1 20°
3`1 4"' BOTTOM STEP AT PORCH
COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL 4:6e, le Q ■4
iii,
Conditional Approval: _ Date__ ..4:y.-..•
.."01'lP.• • .� t
I .40
---'--- r ••..........yt......
r* CharietG.$ahartai , a.
.t`� ►'•. CE•104 aw-
oiyto
IP
Approved A!. (�vi� I Date CAt asl yS ,oN%~
Inspection Report_9-1-12.doc
f / 4�\\\\�V
/ LOT 21 ^I= Atkpii
~lI
•
WELL 700.^-....,, N . .,„„
USEDLFOR VER /ON FILE, E(4 R �qa`
JUSTIFICATION) s HARLES G BALZARIN,.
LOT 36 i. ` ,�FG' ••(ym 8� .' �
G' SEPTIC F '�• •'
47/ Rk`DPROFESS\°°"4'
AREA
LAKE HILL ACRES ,``��\�
Jw /1 LOT 20
4'x55' TRENCH
7 OLD CRIB/ 3.5' EFFECTIVE MIN
4r LOT 20
r
TI-I-1
0
*411 11;
100'
LAKE HILL ACRES `
/ •4 /ti 1 NEIGHBORING
/ X11 LOT 19 , / WELL RADII
LAKE HILL ACRE
A ,, #1 LOT 7
/ /'.
'�1 f 12x12 TIMBER,
DIVERTERVALVE
1`\., PIN IN PLACE
/ w/ 33 x 48"
REBAR \
C O• / fD C.MIN.
t00 we oh.
R '' \---:N---
/ EXIST WELL AaUS APPROX. 100'(NO LOG) g /� NEIBORING
// l WELL RADII
LAKE HILL ACRES
/ #1 LOT 8
LEGEND /
a CLEANOUT
• MONITOR TUBE / SWING TIES
\PA B
® TEST HOLE C 53.7 82.3
LOT 18 \
PLAN — SCALE: 1" = 40'
NOTE: DISTRIBUTION PIPE ELEVATION
IS BELOW SLOPE OF ROAD CUT/DITCH.
ONITOR TUBE
BLUE BOARD INSULAIT.
FILTER FABRIC '6.30 NISHED TH-1 96.3
-+100.0' BOTTCM STEP AT PORCH GRADE
11 6 z .�.
t o+Plr+^'+`ES q5. 3
COVER
: ::; .: . QD.3 .:�... r
i=i;i:i:i„0 r. :9.8 INVERT v 0 �_ff.( e 1.cvKfeet f' lir
4"0 DISTRIBUTION PIPE ;.3 YdNCr6,4#10Agii
3.5' EFFECTIVE SEWER ROCK c.-,-€uj ljor.z..(,-i*S 4.04/73001
• ��?.rpire.st..6te tkyrr,f,,,
80.3 NO DWT
SCHEMATIC ELEVATION — SCALE: NTS
LEGAL DESCRIPTION: LAKE HILL ACRES #1 LOT 19
C&M ENGINEERING SERVICES OWNER: JAY VALLIERES DATE:2/25/17 REV:1 DRAWN: CB REF:
907-854-5558
SEPTIC RECORD DRAWING
,ncnr
Municipality of Anchorage _
), rF
P.O. Box 196650 • 4700 Elmore Road
Anchorage, Alaska 99519-6650 • (907) 343-7904 • Fax (907) 343-7997
http:llwww.muni.orglOnsite
Development Services Division
On-Site Water and Wastewater Program
**** VARIANCE/WAIVER REVIEW ** **
Waiver#: OSV161089 COSA#: Permit#: OSP161218
PID#: 051-052-23
Legal Description: Lake Hill Acres #1 Lot 19
Engineer:
Applicant: Jay Vallieres
Your request for a waiver of the required 100 feet horizontal separation from the absorption field
to the private well has been approved. The approved separation distance is 75.0 feet. In addition,
a 0 foot to lot line waiver and a field to field separation is approved to be 8 feet. See the
engineers letter.
This waiver approval applies to the existing absorption field only. Any future upgrade to the on-
site wastewater disposal system will require all separation distances be met or another approval
from this department.
❑ The affected adjacent property owner(s) have been given a 7 day notice regarding this
waiver.
n Notarized letter(s) of nonobjection have been received from the owner(s) of the affected
adjacent property.
® Adjacent properties are not affected by this waiver.
Waiver is Granted: X Waiver is not Granted:
Date: Approved by:
Name of Review
Vfr
**** VARIANCE/WAIVER REVIEW ****
Lake Hill Acres #1 Lot 19
Parcel ID: 051-052-23
Well to field - 75 feet
4/5/2017
General
1. The Leachfield is down gradient of the well.
2. Total nitrates in well at 0.379 mg/L
ADEC Criteria Points
Water Table
Depth to water bearing layer(Lot 36) 198 feet
Depth of field 10 feet
188 feet 7.5
Soil Sorption
Soil descriptions per well log for L36
DEC PTS Depth From Depth To Thickness Calc. Pts
Clay 6 10 20 10 0.29
Clay and Gravel 3 20 40 20 0.29
gravel Sand 0.7 40 70 30 0.10
Clay 6 70 80 10 0.29
boulders 0 80 120 40 0.00
Silty gravel 1.7 120 213 93 0.76
gravel 0 213 218 5 0.00
208 1.73
2.9
Permeability
Soil descriptions per well log for L36
DEC PTS Depth From Depth To Thickness Calc. Pts
Clay 0 10 20 10 0.00
Clay and Gravel 3 20 40 20 0.29
gravel Sand 1 40 70 30 0.14
Clay 0 70 80 10 0.00
boulders 0 80 120 40 0.00
Silty gravel 1 120 213 93 0.45
gravel 0 213 218 5 0.00
208 0.88
1.0
Water Table Gradient-
Not calculated XX
Horizontal Separation
75 feet 2
Total Points 13.4
As per ADEC waiver guidelines, with a minimum point value of 13.4, no bacteriological pollution possible
but chemical pollution possible but unlikely from household chemicals.
MUNICIPALITY OF ANCHORAGE
Community Development Department Phone: 907-343-7904
Development Services Division Fax: 907-343-7997
On-Site Water & Wastewater Program
ON-SITE SEWER/WELL PERMIT APPLICATION
Parcel I.D. 05105223
Property owner(s) jay and mary vallieres Day phone
Mailing address 22536 miller road
Site address 22536 miller road
Legal description (Sub'd., Block & Lot) lake hill acres #1 lot 19
Legal description (Township, Range & Section)
Lot Size 1500 Sq. Ft. Number of Bedrooms 2
APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING:
(®all that apply)
Absorption Field x❑ Initial I I Single Family (SF) x❑
(w/wo ADU)
Septic Tank ❑ Upgrade Duplex (D) ❑
Holding Tank ❑ Renewal ❑ Multiple Dwellings ❑
Privy ❑ (SF and/or D)
Private Well ❑
Water Storage ❑
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
Well to leachfield Distance:75
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
(Signature of property owner or authorized agent)
Permit/Rush Fees:r5-65) Waiver Fees: 4-9z 0
Date of Payment: c l —/A Date of Payment: 0-1—,/g
Receipt Number: OS-364 B Receipt Number: or 366 3
Permit No. 65-7/6iz fr Waiver No. QSV/4/0 -
Permit App_.• • c
C&M ENGINEERING SERVICES
Ph: 907-854-5558
Municipality of Anchorage
Onsite Water& Wastewater Program
4700 Elmore Rd Anchorage, Ak 99507
RE: Septic System for Lake Hill Acres #1 Lot 19
Dear Reviewer,
The above referenced property has recently had a new leachfield installed to replace a failed crib.
As you are aware. a permit was not issued for the installation, which was done by the homeowner. A test
hole revealed a sandy gm material near the East end of the drainfield. A subsequent testhole revealed a
silty sm material near the West end of the drainfield. see attached soils log.
We are requesting approval of the leachfield, the installed system is adequate to meet the needs of the 2
bedroom home.
A diverter valve was installed to connect the old crib to the system When the home installed system
does eventually fail. the diverter can be switched to the old crib which will likely have recovered to
functional condition. It is believed that the old crib system will recover within the next 2 years, and may
become adequate for use and future adequacy testing at that time.
Well to Septic Separation Distances.
We are requesting a waiver be granted for 75' from the well to the septic leachfield. The onsite well is not
logged, however neighboring well logs show a water table of approximately 200 feet and at least one clay
layer between the surface and the aquifer. The presence of the clay layer makes it exceptionally difficult
for raw effluent, or nitrates to contaminate the well. The well depth is indicated as 207' on the septic
inspection report dated 5/1972.
Surface contamination of the well from the leachfield is not of concern. as the leachfield is down gradient
of the well.
Note that the existing 750 gallon concrete tank is only 54' from the well, which was code compliant when
it was installed in 1972.
While 75 feet is significantly less than the code required 100' separation. we believe granting the waiver
does not present an adverse health risk to the occupants of the trailer. or the neighboring lots. The depth
of the well and soil conditions are the primary mitigating factors.
Water samples may be desirable prior to granting this waiver. It may be advisable to take water samples
after the system has been in place for a period of months or years to determine if the well will have nitrate
issues C&M Engineering will defer to the MOA's judgment on if and when samples should be drawn.
Encroachment on Lot 20.
The leachfield encroaches on a significant portion of lot 20. The owner of lot 19 also owns lot 20, and has
filed an access agreement for the encroachment. We are requesting a waiver from the lot line to the
leachfield for 0 feet of separation.
Leachfield encroachment to existing crib.
We are requesting a waiver of the leachfield to crib separation distance to 8'. The last 20' of the new
leachfield encroaches on the required separation. The soils near the encroachment location were found
to be free draining and would tend to reduce interference between the two systems. Additionally, little can
be done as the system is already installed.
Driveway Crossing.
The leachfield crosses under a driveway which provides access to an old building pad, currently used to
park a trailer. The driveway will be blocked using railroad ties staked into the ground, as shown on the
drawing.
Included with this letter is a site plan, calculations, neighboring well logs and a soil log.
Test Hole Limitations.
The original test hole TH-1, was excavated by the homeowner and a monitor tube was installed to a
depth of 16' the engineer did not verify the soils below six feet of depth at this location. However, the
owner reported the soils were relatively consistent to the full depth. A review of neighboring well and soils
logs revealed no impermeable layers or groundwater concerns in the immediate area, to a depth well
below the depth concerning this system. For example, Lake Hill Acres#1 lot 14 and 11 have test holes to
a depth of 16' with similar soils and no groundwater. Many of the well logs in the area are either missing
or illegible, however, the well log for lot 36 indicates a clay layer at a depth of about 20', while the well log
at lot 9 indicates a no impermeable layers until much deeper. We believe this information, coupled with
the lack of groundwater in the monitoring tube indicates that there is no impermeable layer within 6' of the
bottom of the system.
A second test hole TH-2 was excavated by Guaranteed Services to a depth of 14', depth was limited by
the size of the equipment, near the West end of the trench.
Thank you for your time in reviewing this permit request. Please do not hesitate to contact me at 907-854-
5558 or by email cgbalzarini aagmail.com with any questions or concerns. Since this is a non-typical
installation, we anticipate providing additional information at your request.
Sincerely,
Charles Balzarini, PE
i
sGs
SGS Re!# 1154774001
Client Name Residential Testing-Cash Account Printed Date/time 08/31/2015 12:24
Project Name/# Jay Collected Date/lime 08/25/2015 9:30
Client Sample Ill Kitchen Sink Received Date/time 08/25/2015 10:45
Matrix Drinking Water Technical Director Stephen C.Ede
Sample Remarks:
Allowable Prep Analysis
Parameter Results LOQ Units Method Container ID Limits Date Date !nit
Metals by ICP/MS
Arsenic ND 5.00 ug/L EP200.8 C (<10) 08/26/15 08/27/15 EAB
Waters Department
Total Nitrate/Nitrite-N 0.379 0.100 • mg/L SM21 4500NO3-F B (<10) 08/28/15 SLC
Microbiology Laboratorjy
E.Coli Negative 1 IOOtnL SM21 9223B A 08/25/15 MEV
Total Coliform Negative 1 1O0mL SM21 9223B A 0825/15 MEV
n
C&M ENGINEERING SERVICES
907-854-5558
Septic Design Calculations
Residence: LAKE HILL ACRES#1 LOT 19
RESIDENCE/LOT INFO
number of bedrooms 2 br
Water usage/bedroom 150 gpd/br
Water Usage 300 gpd
Water Table NONE ft bgs
Test Hole Depth 16 ft bgs
DRAINFIELD
system type: CONVENTIONAL
type: DEEP TRENCH
Application Rate 0.8 gpd/sqft average
required absorption area 375 sqft
trench width (W) 4 ft
gravel depth (D) 3.5 ft+ below distribution pipe
Min Required Length: 53.5714286 ft
Use Length: 55 ft
Total Depth: ; Ia ft
Cover: 4 ft+/-
Insulation: 2" blueboard
Effluent Pipe: 4" ASTM 3034
Design Summary
System type: Conventional
Tank: 750 gal concrete
Total absorption area: 385 sqft+
Calc By: CGB Date: 2/10/2017
..•wsni~ .
G.6alzarini •'
**Pk\••Fikf*Y47/NPEF
•t,k sOEEsstt t�.-
7/- I �...ik,�t�,, OF At4._,.„‘‘..
(EfIGINEE SSE -��
Municipality of Anchorage �V, •.....5, c
�— Development Services Department -(/)'' . *19
• Building Safety Division • '—1 •• ....t•••'#
/4, i .li.�r On-Site Water and Wastewater Program ••����••
fr 4700 Elmore Road r ,I
\ -�..S.. P.O. Box 196650 Anchorage,AK 99507 re. ,II *.' • '{ll�:
www.ci.anchorage.ak.us , ' . -1 • •
(907)343-7904 �,'s�.••• �• � ••• ar
Soils Log - Percolation Test • "'. L�
Performed For: jay valleries Date Performed: 10/20.ek,
Legal Description: Lake Hill Acres#1 Lot 19 Township, Range,Section:
SlopeSite Plan
Depth
0 (Feet).
elkori1",,-TerSoAc
1- -
2- [tee ION fiy -
3- : £,(f-f 664D - ,
4- r
1..7 1%1. .
5-. I. .
6
7-
8-
WAS GROUND WATER
9- ENCOUNTERED? no
S
10- IF YES,AT WHAT DEPTH? none `
-
Depth to Water After o
11- Monitoring? n6
one1ol 'v
E
12- Dale: gf 16 -
13-
o
14- Reading Date Gross Time Net Time Depth4eWater Net Drop
15- l NO/ 4 7 17 a 46-C,14. 0
17- 17 7,14 0 . 6 -046 a B,
�
18- 41 Vali [ 0 :?- 14.4 3T j/ ,
19- S 7' Y, 0 (o' o
20- 6
a- ink 3 Yti
PERCOLATION RATE 3.33 (mihuteshnch) PERC HOLE DIAMETER 6
TEST RUN BETWEEN
4 FT AND5 FT
COMMENTS ?F,..R4- Cal, POLE 644eitio TT^ -rp / 13tdr //&'7 WV .
°
% turry . "'Kr L s ?v5TALL Ari> Tti,‘,/ 7e_Prr
_
PERFORMED BY: charles balzarini I charles balzarini CERTIFY THAT THIS TEST WAS
PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: gip' llr
T(4 - a-
Municipality of Anchorage (:N� >rsig .
Development Services Department F, OF•:A( 1.
• Building Safety Division ...4:° ..* Q;��r,
On-Site Water and Wastewater ProgramsirwA.-- .� #
i 1.s 4700 Elmore Road • ,:1 ' ...�At♦,
�` P.O.Box 196650 Anchorage,AK 99507 •� i.
. /
\ www.cLanchoraqe.ak.us 0 `�'� z�--
(907)343-7904 f' ' /
Soils Log - Percolation Test .'s,'•, 854 ..
Performed For JAY VALLIERES Date Performed:8� 48.
OF SFA '��
"t Vt•Iklall'
Legal Description: LAKE HILL ACRES #1 IT 19 Township,Range,Section:
Slope Site Plan
Depth
(Feet)
1- L .
2 ~� 5P/Basi
3
• ice
4-
5-
6- t S ,
7- ( I 5:1Y1
8- 1,- d
WAS GROUND WATER
9- i ENCOUNTERED? NO
S
10- IF YES,AT WHAT DEPTH? NONE
o
Depth to Water After P
11- / Monitoring? NONE E
12- : Date:8/25/16
13- ` d
14 Reading Date Gross Time Net Time Depth ht�j Water Net Drop
15- 0 8/2616 6:00 0 5 0
16- 1 8/26/16 6:30 :30 7-8/16 as 1/4
17- 2 8/26/16 6:31 0 5 0
18- 3 8/26/16 7:01 :30 7-8/16 2— 13/1.6 1
19- 4 8/26/16 7:02 0 5 0
20- 5 8/26/16 7:32 :30 7-7/16 <w It
PERCOLATION RATE 13 (minutes/inch) PERC HOLE DIAMETER 6"
'FEST RUN BETWEEN 4 FT AND5 FT
COMMENTS
PERC HOLE PRESOAKED OVERNIGHT
PERFORMED BY: CHARLES BALZARINI I CHARLES BALZARINI CERTIFY THAT THIS TEST WAS
PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES IN EFFECT ON THIS DATE. DATE: 8/26/16
A
2011 - 005400 - 0
Recording District 301 Anchorage
A 02/0912017 12:07 PM Page 1 of 2
I I IIII IIII 111111111 JIIIII I�liI II 1111 llllll1111111111111lill Illi IiII
GRANT OF EASEMENT
This easement agreement is made between .S 0,..k Ucx t�c�►c ,whose address
'3 rock (Grantor),owner of the land
described as L-a-t 20 Lake_ Hifi I`irres './ r7L.,hri,vlsr'or\ (hereafter
subservient parcel),according to the Plat No. - q0 , records of the Anchorage recording
District,Third Judicial District, State of Alaska,for good and valuable consideration, the receipt whereof
is hereby acknowledged,and does hereby grant unto Ja.-t Mari, Uc, 1-41c-5
whose address (291-5-3i: rn,lkcr C ` (Grantee),
owner of the land described as Lot ICI a4ce. H-11( I4cre SlAh( iv►5for1
(hereafter dominant parcel),according to the Plat No. J 4- 90 , records of the Anchorage
recording District,Third Judicial District,State of Alaska,the following grant of easement described as:
A perpetual, non-exclusive easement to provide access for the construction, maintenance,
repair,removal,and inspection of a wastewater system serving exclusively the dominant parcel: and
Said easement is more particularly described as: 1_01- 20 LAk4 14 I4 cres �u4ar��'v�'sion
1. The easement granted hereby shall not in any manner be dedicated for,or subject to, use by the
public. The easement shall be exclusive to the wastewater system of the dominant parcel.
Within this easement, rock,soil,sand,gravel,and vegetation may be excavated and removed to
construct, improve, maintain and repair the easement area.
2. Grantor may not place permanent structures over the existing wastewater systems or otherwise
restrict access to the wastewater system.
3. The Easement granted shall run with the land,with the benefit of the easement appurtenant to
the respective dominant parcel and the burden of the easement appurtenant to the servient
parcel. This Easement shall be binding upon and inure to the benefit of the parties successors
and assigns, heirs, beneficiaries and personal representatives. J 0.4 U0.t
70 box J� 7,-6r
GRANTOR: a. le tick c-cce5 (Printed name)
��/ ' (Signature) Date: .2.2/41/4V 7
GR
7TEE: ,c. 1 ��cti 1 i v-ct4 sill‘it (Printed name)
7
a 9,n..7 Tei l er r�
(Signature) Date: r( do/ 2
THIRD JUDICIAL DISTRICT )ss.
STATE OF ALASKA )
The foregoing instrument was acknowledged before me this Q day of c-b20 l7 by
\O.a-j, \.) a. . 'i e-r e—.. ,an individual.
Notary Public ` idiL _ . .� I Lam. .4
MICHELLE CAMPBELL
State of Alaska f NOTARY PUBLIC IN AND FOR THE STATE OF ALASKA
My Commission Expires March 28,2018 ' My Commission Expires: T 2,13)261r
THIRD JUDICIAL DISTRICT ) ss.
STATE OF ALASKA ) Gy
The foregoing instrument was acknowledged before me this ( day of . 20212,by
Ha.-4(11 V 0.,I!f1 .fGS ,an individual.
Notary rub.l1c ( I l Lr(.ell't.�� c_. 1 �"�
MICHELLE CAMPBELL
State of Alaska NOTARY PUBLIC IN AND FOR THE STATE OF ALASKA
My Commission Expires March 28,2018 My Commission Expires: Ai-Gly. 20 ZOI?
111R111311111l11B11E!Jl
Page 2 of 2
2017—005400-0
~J~A'~ ,~J'~,,'C~O~AC-~: afi~A ]~OAO~:.:.:~, "~"r--r'-R ANCHORAGE AREA BOROU~-~
3500 Tu~or R~d ~ Pouch 8~ ..... ~ ....... ~ y ' - _. _ - ...... ~
~ ,~ho:age,~aslc~ 88~PECTiON REPORT ON-linE SEWAGE DISPOSAL SYSTEM
°. 913
LOCATION
SEPTIC TANK:
DISTANCE FROM WELL
LIQUID CAPACITY
GALLONS.
LEGAL DESCRIPTION(
/ .
NUMBER OF
MATERIAL ~,O~.,~Z~ COMPARTMENTS
'/ '~'~'~ ~//~Z~/~/~' ~'~/~/~/~ LIQUID
INSIDE LENGTH INSIDE WIDTH DEPTH
SEEPAGE SYSTEM: SEEPAGE PIT:
NUMBER OF PITS /
LININO MATERIAL 2 ~.O~JP-~
NEAREST LOT LINE ~-0 / ~c-
OUTSIDE DIAMETER ~ OR WIDTH ./Z / , LENGTH ~'-~' I , DEPTH ~:~
~--I~(j~S DISTANCE FROM WELL
TOTAL EFFECTIVE ABSORPTION AREA (WALL AREA) ~'~ SQ. FT.
BUILDING FOUNDATION
TILE DRAIN FIELD:
DISTANCE FROM WELL , FOUNDATION NEA~/
NUMBER OF LINES DISTANCE BETWEEN ~ TRENCH WIDTH
ABSORPTION AREA ~ LENGTH OF EACH LINE
DEPTH: TOP OF TILE TO FIN HfS~RGRADE DEPTH OF FILTER MATERIAL BENEATH TILE
TOTAL LENGTH
, OF LINES
IN. TOTAL EFFECTIVE
IN. ABOVE TILE
WELL:
LOT LINE
~"~//'~"~?-Jr~5'~ .~. / DISTANCE FROM
TYPE ~-//-~ DEPTH _ , BUILDING FOUNDATION
NEAREST . SEPTIC I SEEPAGE
/~'/'~ SEWER LINE/~' /-/~ ~J
, , TANK SYSTEM
WATER
SAMPLE
, CESSPOOl
NEAREST
OTHER
SO URC ES/~/vG~-~A/
DISTANCES:
~lL~
DIAGRAM OF SYSTEM
. I ..... - ...... ;. ~ - ': ':, ...... -
~ ~,'/ ' . : ~ - - ..
; ~: '~: Z.! ' - : ~ i ~.~
.... ~/~'l.; :Z:[l~.:..s.:.t -4 :: :.; ~ ~ ~ : :-.' ~-
- .~1 .......... ~ ........... ~ ~ ...... ~.-; -~ .... ' ......
; . . : :' : :- .~-~ ; ,~.: .,..--..-;
- ~ . - . '. ~,/~"~.. ' : : ; ...... : .; ~ ~.;. ,} : ~-; : ~ .
': ~ : ~ :, ' :. L '..;. '. : ~ .... ; ~.: .... L-~. ~ ', .~ ~.:-;,- ~ ,
; I - : - · ..... ?-~ ': ~'?'~ ~"~ "~ :"?"':~' : ' -i '
. ~ ~ - -~ ~( : : .... : ~,.~ -.: :.~ ..... [ .... ; :.: ...... ~.~. ...... ,. :..
. , . ; ~ ; : ~,.~ ~- -;,. ......
· ~1~ ~ - ~ ;' : ~ 4.-.;- .....
. - : - ; : : , :. .: .. ~ . :.~. .~ ~ ~..~ '. ;.~. '4 : ..-.
' - ' ~'~r~ - , ' ~ - ' .... . - , ' : ' ,
' ~m~'- L - : - . ::: : : ' ~' : ' ~ ~ , : ..... : ,-,': ..... .... ~ ~-~.: ...... :-: :
GREA~',~ ANCHORAGE AREA BOROUGH
DEPARTMENT OF' ENVIRONMENTAL QUALITY PERMIT NO,~:'~J '/ /
3500 TUDOR ROAD POUCH 6-650
ANCHORAGE, ALASKA 99502
TELEPHONE 279-8686
SEWAGE DISPOSAL SYSTEM -- APPLICATION AND PERMIT
INSTALLATION LOCATION ~//~~~~ ¢~' ~¢
SOIL TEST RESULTS /~'--H//~ ~~ fP~ NOTE.' THIS PERMIT IS NOT VALID WITHOUT SOIL ~ST
FINAL INSPECTION: 24 HOUR NOTICE REQUIRED. BACKFILLING OF ANY SYSTEM WITHOUT FINAL INSPECTION BY THE
HEALTH DEPARTMENT AUTHORITY WILL BE SUBJECT TO PROSECUTION.
MINIMUM DISTANCES, REQUIREMENTS
FOUNDATION TO SEPTIC TANK
SEPTIC~T/AIqK TO SEEPAGE PIT WALL
SEPTIC TANK ~/ _, SEEPAge Pit .
TO NEAREST LOT LINE.
WELL TO SEPTIC TANK
DRAIN FIELD
· DRAIN FIELD
WATER MAIN TO SEPTIC TANK
DRAIN FIELD
SEPTIC TANK,~~/~ SeEPAGe Pit
TO RIVER, LAKE. STREAM.
SEEPAGE PIt J~2~
ALSO CONSIDER AREA WELLS.
I ~[~P~E PIT /~
CAST IRON INTO AND OUT Of SEPTIC TANK AND INTO CRIB CROSSING GAP OF
EXCAVATION ~ FEET INTO UNDISTURBED SOIL.
4 INCH Diameter CAST IRON SIPHON PIPES ON SEPTIC TANK AND SEEPAGE PIT
FITTED WITH AIRTIGHT REMOVABLE CAPS.
GRAVEL BACKFILL
CONFORM TO BOROUGH REGULATIONS REGARDING INSTALLATION.
or
LICENSED DESIGNER
DIAGRAM OF SYSTEM
[ CERTIFY THAT I AM FAMILIAR WITH THE REQUIREMENTS OP GREATER ANCHORAGE AREA BOROUGH ORDINANCE NO. 28-6S AND THAT THE ABOVE
DESCRIBED SYSTEM IS IN ACCORDANCE WITH SAID CODE.