MUNICIPALITY OF ANCHORAGE
�t�,cnr
On -Site Water & Wastewater Program
PO Box 196650 4700 Elmore Road �.
Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997
http://www.muni.org/onsite Q
t; f
DelrtrUnent
On -Site Wastewater Disposal System Permit
Permit Number: OSP231343 Effective Date: 10/6/2023
Work Type: SepticTank Upgrade Expiration Date: 10/5/2024
Tax Code Number: 01549214000
Site Legal Address: BUBBLING BROOK LT 2 G:2638
Site Mailing Address: 6251 BUNNYSHOE CIR, Anchorage
Owner: BIGALKE ANDREW & YVONNE Lot Size in Sq Ft: 46250
Design Engineer: FORGE ENGINEERING Total Bedrooms: 4
This permit is for the construction of:
Disposal Field Q Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage
All construction shall be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80)
3. The wastewater code requires inspections during the installation. The engineer shall notify the Development
Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
shall be either:
a. Opened and Closed on the same day, or
b. Covered, sealed, and heated to prevent freezing
-#-I " p , T tc L-0 t I/ 6/'20--_'�
Received By: s�i F_Lr) t� G Date:
Issued By: Date:
-
Community Development Department:,_ Phone: 907-343-7904
Development Services Division Fax: 907-343-7997
On -Site Water & Wastewater Program
ON-SITE SEWER/WELL PERMIT APPLICATION
Parcel I.D. 015-492-14
Property owner(s) Andrew Bigalke
Mailing address 6251 Bunnyshoe Drive, Anchorage, AK 99516
Day phone
Site address 6251 Bunnyshoe Drive, Anchorage, AK 99516
Legal description (Sub'd., Block & Lot) Bubbling Brook, Lot 2
Legal description (Township, Range & Section)
Lot Size 46,250 Sq. Ft. Number of Bedrooms 4
APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING:
(® all that apply)
Absorption Field ❑ Initial n
Single Family (SF) ❑x
Septic Tank ❑x Upgrade p
(w/wo ADU)
.Holding Tank ❑ RenewalDuplex
❑
(D) El
Multiple Dwellings ❑
Privy ❑
(SF and/or D)
Private Well ❑
Water Storage ❑
THIS APPLICATION INCLUDES A VARIANCE / WAIVER REQUEST FOR:
Distance:
I certify that the above information is correct. I further certify that this is in accordance with
applicable Municipal Codes.
I
U
(Signature of property owner or authorized agent)
Permit/Rush FeesA 225
Date of Payment: laZ � -2
Receipt Number: 0502.273
Permit No. 05 P Z3 I 3-7, 9 3
Permit App_'- : -
Waiver Fees:
Date of Payment:
Receipt Number:
Waiver No.
r �J`
Gi4j• r,;�'
September 19, 2023
PO BOX 240773 C_
ANCHORAGE, AK 99524
522-7773
677-7766 (FAX)
FORGECIVIL.COM
MOA Development Services, On -Site Water & Wastewater Program
4700 Elmore Rd
Anchorage, AK 99507
Subject: Bubbling Brook Lot 2 - Bunnyshoe Circle
Septic System Replacement
Dear On -Site Services Engineer:
The owner of the above lot has a septic tank that has reached its end of useful life along with a
failed trench, so we are submitting this permit application for a new system. The attached site
plan identifies the location of the home as well as the wells and septic location. No conflicts exist
between this proposed system and any other wells or septic system, whether on this lot or
adjacent lots.
The lot is primarily flat, with minor slopes in varying directions. The new trench will be placed
where there is a gentle slope down from the neighboring property, and will be placed parallel to
the contours. There are no steep slopes within 50' of this new trench. Storinwater will not affect
the system. It will be placed 16' away from the existing trench, which will be decommissioned.
The septic tank will be replaced with a 1500-gallon steel STEP tank in the same location as the
old tank. Wells on this and adjacent lots are shown, and there are no conflicts, whether on this lot
or adjacent lots. The tank and trench are 100' away from surface water.
Please refer to the attached test hole log, plan and profile pages for the septic design. If this
design is followed, there will be no adverse impacts to adjacent properties.
Sincerely,
Benjami Schiller, PE
BUBBLING BROOK, LOT 2
/
i
i
/
/
/
/
/
r
j WIRE FENCE
I ®,
1\
LOT
LOT 7
\
'CREEK
\ MAINTE NCE
EASEM61T�
�i L0f \2 -
I \
r r /
/ CgNFIRM LOCATION �F
NEIGHBORING WELL AND 10 '
/ SE�ARATtION DISTANC
/ r
1-1
\\ / / 4-BDRM HOME /
L'06ATE EX STING CLEANOUT, /
REPAIR IF NEI<D, AND INSTALL /
A NEW DR\(EABLE—COVER
SMOKER
10' UTILITY
EASEMENT
*' 48 TH ...:*
.� .
Benja i Schiller
��%
c%1T� • C11013o 233 , • •�()
i\�� PROFE SSIONP�'
m
FRENCH TO
IN SERVICE
BUNNYSHOE COURT
SEPTIC PLAN
0 50 100
FEET
1 "=50'
co �I-
LOT 6
DECOMMISSION
EXISTING 1250 GAL
SEPTIC TANK PER UPC
i NEW 1500 GAL
\ STEP TANK
PROVIDE VALVE
\ AND PIPING TO
\ BOTH TRENCHES
NEW 65' LONG x 8' DEEP ABSORPTION/
TRENCH - MAINTAIN 16' SEPARATION FROM
EXISTING TRENCH
DECOMMISSION LOT 3
EXISTING TRENCH
LEGEND
CO - CLEANOUT
2CO - DOUBLE CLEANOUT
FCO - FOUNDATION CLEAN(
FS - FLOW SPLITTER VALVE
MH- MANHOLE
MT - MONITORING TUBE
SV - SEPTIC VENT
TH - TEST HOLE
BUBBLING BROOK, LOT 2 C-0 a.2
DESIGN FACTORS: SYSTEM REQUIREMENTS:
600 GPD PEAK FLOW 8' DEEP TRENCH SYSTEM
PERK RATE: 6.0 MIN/IN 1500-GAL STEP TANK
APPLICATION RATE: 0.6 GPD/SF (CONSERVATIVE)
600 GPD / 0.6 GPD/SF / 8 DEEP / 2 SIDES = 62.5 LF TRENCH REQUIRED (65 LF SPECIFIED)
BOTTOM OF TRENCH: 9' BELOW GRADE
FLOW LINE ELEVATION: 1' BELOW GRADE
"�" "r��'TI �"'"' FILL TO ENSURE
R AFTER SETTLEMENT
RIC
7
TYPICAL TRENCH SECTION
(NO SCALE)
NOTES:
1. GRADE AREA OVER TRENCH TO DRAIN AWAY
2. PROVIDE 3' OF COVER OVER TRENCHES AND 4' OVER SEPTIC TANK, OR 2'
WITH 2" OF INSULATION
3. CHECK GROUNDWATER AT TIME OF CONSTRUCTION. IF LEVEL IS HIGHER
THAN PREVIOUSLY OBSERVED, CALL ENGINEER IMMEDIATELY
F a GE
^�, J_ E N G I NE E R I NG
l
s 1
1
'497H *�
. . ..�.
• . .. Benja'n Schiller
II�6, CE 12592 s
10130123
�li\e�PROFESSIONP�� �
DEPTH
(feet)
1-
2-
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
GE SOILS LOG AND PERCOLATION TEST
ENGINEER 1 N G
LEGAL DESCRIPTION: BUBBLING BROOK, LOT 2
PERFORMED FOR: ANDREW BIGALKE
DATE: 10/13/2023 PARCEL ID#: 015-492-14
TEST HOLE 1
1' OB
• L•.
'
GM (SILTY SAND WITH
SOME COBBLES)
17_
NO WAS WATER ENCOUNTERED?
- IF YES « WHAT DEPTH?
13' DEPTH TO WATER AFTER MONITORING
10/20/23 DATE OF MONITORING
DATE
READING
START TIME
NET TIME
(MINUTES)
DEPTH TO
WATER
NET DROP
INCHES)
(INCHES)
---
1
10:30
21:19
5"
1111
6"
2
33:09
5"
1111
611
3
35:49
5"
11"
6"
PERCOLATION RATE: 6.0 (MIN/INCH)
COMMENTS: USCS SOIL CLASSIFICATION WAS VISUALLY DETERMINED
SITE PLAN
TECHNICIAN: B SCHILLER
Lot 7
j 1 i
_ s /
66 4, 08 F 21
Lot 6
Lot 2
FyS, FN AFF \ \
\F�q�c /
/ U 46,250 S.F.
CHAIN—LINK ` \
L�FENCE \
4 \
WELL
k
4.0x24.4' \
DECK CANT f
Lot 1 32.4'* r
48.4' 2 STORY Cry
�
14. a' RESIDENCE
N
a o
N
V
\ WIRE FENCE --,,,.,,Z DECK o I 3-�NEIGHB0R'S SHED
2.0'x4.8' 24.2' Q
\ CANT / O Lot 3
6.7.
V k /
-:1I SEPTIC
N / PIPES
3'x3' SMOKER n x1 }
\ / CHAIN-LINK FENCE
SEPTIC PIPES J
9a;90RSD
10' UTILITY
EASEMENT / 1
ro
L O I
U
I
r.
BUNNYSHOE COURT
PLOT PLAN AS BUILT _X_ SCALE _1" =50=_ GRID _ SW 2638Project No. 2_3-4481A1 __
11500 Daryl Avenue, Anchorage, Alaska 99515-3049
Lang & Assoc ! a t e s , inc. (907) 522-6476 Phone
ken®Iangsurvey.com
Professional Land Surveyors jonatha n®longsurvey.com OF At kk
travis®Iangsurvey.com ��
AWP' •. ••�
I hereby certify that I have surveyed the following described property: ��.'
LOT 2, BUBBLING BROOK SUBDIVISION (PLAT No. 78-110) 10 49TH ••*��J
Anchorage Recording District, Alaska, and that the improvements situated thereon are � • • • • • • • • I
within the property lines and do not encroach onto the property adjacent thereto, that F • • 0
no improvements on the property lying adjacent thereto encroach on the surveyed
premises and that there are no roadways, transmission lines or other visible �� • • '
y ' KENNETH G. LANG
easements an said property except as indicated hereon.
kt•5t>[�sc l�na%u6l �jJ'fF� •' •Y�Uij•' •S�l�_�
Dated this the Day of _ _ at Anchorage, Alaska ``�;;
It is the responsibility of the owner to determine the existence of any easements,
covenants, or restrictions which do not appear on the recorded subdivision plat. State of Alaska AECC963
Municipality of Anchorage ."¥
Development Services Department
Building Safety DMsion
On-Site Water and Wastewater Program. 4700 S. Bragaw ~L
P.O. Box 196650 An~omge. AK 9951~650 Page of
~.d. ancho~e.ak.us (90D 343-7904
ON-SITE WASTEWATER DISPOSAL SYSTEM ANDIOR WELL INSPECTION REPORT
Permit Number: S~O~O~ PIDNumbe~ 015- ~-
"~: ~ ~A~, ~ ~,~ ~0,~ Wastewater System: DNew ~Upgrade
A~ress:
[~1 ~o~s~o~ ~ ABSORPTION FIELD
q
LEGAL DESCRIPTION O, ~ ~,~.f
Bl~ Lot: S~ ~ ~ ~ ~ ~ ~ ~e: ~ ~ ~a~ ~:
Well: ~ New D Upgrade. ~ ~ n.
· ,.,.. ~ ..w s,~.~ I c,,~..~ ~ TANK
SEPARATION DISTANCES ~s~ptic ~ Holding D S.TZ.P. D Othe~
~o Septic Abso~tio~ LI~ Holaing Publl~l~ M~
Tank Field Station Tank S~r Une ~ ~ ~ ~
/ X
~*~"~': BENCH
)~d ~L
Development Se~ices Depaflment Approval ~ ~%
Reviewed and approved by: ~ Date: ~
I1 FT Lk'Z'P
I
I 10' /
SWING11ES:
AC 41.4 ri'
· c 18
AD 40.5
afl 19.5
A,g 52.5
~O 44.$
!1I
/
/
N
49th
TOB% ~PURKLAN~
No. C£-E225
L~ O Z'5 .~0 75 100
SCALD 1' = 58
IL~5 150
· L'N~H W,4RK:
A,~IJWL'D L'ZLrV. IO0.O0 fT
TOBBEN SPURKL4ND P.E.
203 VI 15Tit. AVENUE
ANCH. AK. 99501
(907) 279-3916
LOT £ B~IBBLING BROOK $/D
J. DAVID SV/ANSON
6251 BUNN¥SNOE CIRCLE
SEPTIC SYSTEW AS BUILT
DATE: SEPT. 30, 2003
SHEEr: 2/3 GRID: 2638
PERMIT #Sh~030362 PID # 015-49£-I4 BBBOOO£~.DV6
to
1250 ga! Septic ~ank
10 ~4~
Standard Trench:
2'
65' Lon~
I1' Beep
8,0' Sewer rock
$' Cover
NO SCALE
Monltor
Cleanouts
3' Cover
B,O F't oF Septic Rock
Effective
NO SCALE
AS BUILT
1250 GAL SEPTIC TANK
!0 ~4Gg
803 ~/15'th Ave
Anchorage Ak 99501
P79-2916
PERt, Ill' I~ SWOJO$$2
LOT 2 BUBBLING BROOKS
S25I BUNNYSHOECIRCLE
SEPTIC SYSTEM SCHEMATIC
DATE, SEPT. $0,
PARCEL I0 / 015-492-I4 BBBOOO25.OWG
MUNICIPALITY OF ANCHORA GE
Development Services Department
On-Site Water & Wastewater Program
4700 South Bragaw Street
P.O. Box 196650, Anchorage, AK 99519-6650
(907) 343-7904
ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT
Upgrade
Date Issued: Sap 08, 2003
Expiration Date: Sap 07, 2004
Permit Number: SW030362
Legal Description: BUBBLING BROOK LT 2
Design Engineer: 0007 Tobben Spurkland, PE
Owner Name: J. David Swanson
Owner Address: 6251 BUNNY SHOE CIR
ANCHORAGE, AK 99516-2411
Parcel ID: 015-492-14
Site Address: 006251 BUNNY SHOE CT
Lot Size: 46250 SQ. FT.
Total Bedrooms: 4 Permit Bedrooms: 4
This permit is for the construction of:
[] Disposal Field [] Septic Tank [] Holding Tank [] Privy
[] Private Well [] Water Storage
All construction must be in accordance with:
1. The attached approved design.
2. All requirements specified in Anchorage Municipal Code Chapters 15.55 and 15.65 and the State of Alaska
Wastewater Disposal Regulations ( 18AAC72 ) and Drinking Water Regulations ( 18AACBO ).
3. The engineer must notify DSD at least 2 hours prior to each inspection. Provide notification by calling
(907) 343-7904 ( 24 hours ). ( Not required for a Water Supply Permit only ).
4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather
must be either: A. Open and closed on the same day.
B. Covered, sealed, and heated to prevent freezing.
Received By:
Issued By:
Date:
Date:
· Municipality of,Anchorage
.' . DeveloPment ServiceS Department
Building Safety Division
On*Site Water and Wastewater Program
4700 South Bragaw St.
P,O, Box 196650 Anchorage, AK 99519-6650
www,ci.anchorage:ak.us
(907) 343-7904
ON-SITE SEWER/VVELL PERMIT APPLICATION
FOR A SINGLE FAMILY DWELLING
Permit Number SW 0 .~0 Y~;~.
Property owner(s)
Mailing address (1)
Mailing address (2)
Legal description (Lot, Block & Sub'd,)
, [")Avt~ g, tY.//~r/xJSC)N Dayphone
,\
Zip Code
~J
Legal description (Section, Township & Range)
Lot Size ~ [o ~ ~ ~
AcresG . Number of Bedrooms
THIS APPLICATION IS FOR:'
Sewer Only
Sewer and Well
Sewer Upgrade
THIS PROPERTY CONTAINS:
Hot Tub
Swimming Pool
Therapy Pool
Well Only. []
Water Storage []
Jacuzzi
Water Softening Unit
I certify that the above Information is COrrect. I further cedify that this application Is being made for a
Single Family Dwelling and is in acCOrdance with applicable MunicilJal Codes.
(Signature of property owner o.~' authorized agent)
· , ~t
I
Permit Fees: ~ /7'/~:~~ ~ ' ' WaiVer Feesi '
Receipt Number: q OS ~ .L~
(Rev. 12/00)
Date of Payment:
Receipt Number:
203 W 15th. Avenue, Suite 203
ANCHORAGE, ALASKA 99501
(907) 279-3916
Fax (907)-276-6013
SEPTIC SYSTEM DESIGN
LOT 2 BUBBLING BROOK S/D
J. DAVID SWANSON
Municipality of Anchorage
Development Services Department
Building Safety Division
On-Site Water and Wastewater Program
4700 Bmgaw Street
Anchorage, Alaska 99519-6650
August 20, 2003
We are submitting an application for the upgrade of the septic system for this lot. The submittal
consists of three (3) drawings showing the present improvements on the lot and the adjoining
properties, (sheet I/3), the proposed improvements of the lot, of which only the septic system is
subject to this permit application, (sheet 2/3), and a schematic of the septic system, (sheet 3/3). Soil
logs and percolation tests of applicable testholes are also enclosed. The septic system design is
based on the following:
No Ground Water or Impervious Layer to 17 iL
Use Standard Trench
Soil Rating. From Testhole 07/12/02
17 min/in=0.6 gal per sq.ft/day
No. of Bedrooms 4
Required Area per Bedroom: 150/0.6 = 250 sq.iL
Total area required: 250 x 4 = 1000 sqR
Testhole depth 17 feet
Bottom Rock At 11 feet
Top Rock At 3 feet
Rock Depth 8 feet
Minimum Trench Length 1000 / 16 = 62.5 iL
Use 65 ft
SYSTEM CONFIGURATION
STANDARD TRENCtt
TOTAL LENGTtt 65 FT
TOTAL WIDTH 2 FT
TOTAL DEPTH I 1 FT
ROCK DEPTH 8 leT
COVER 3 FT
SEPTIC TANK 1250 GAL 10 GAGE THICK WALL
The installation ofthis septic system will not prevent wells and septic systems from being installed on the adjacent
lots.
There are no developed or natural surface / sub surface drainage courses on this or the adjacent lots.
The proposed septic system will not change the general slope ofthe area. Ponding and/or concentration of surface
runoffwill not result from this installation.
I
I
I
I
!
p,,,.---"~ '" iii I iiI
5O 0 5O 100 15O PO0 PSO ,9O0
SCALD 1' = loft FT.
SEPTIC SYSTEY flESI6'Y
DATE: AU~. 20, 2003
SHEET: I/3 CRID: 2838
/
~ ~eH
8 fT
I
I0
TANI~
FT COV~
VAL V~
.4~ Rrell
~XIST. DIb~N f
, N
49-~h
SPURKLi~]~
CE-e~.5
SCALE, I' = 50 FT.
TOBBEN SPURKLANO P.E.
205 ~7 151H. AVENUE
ANCI. I. Al(. 99501
£OT £ BUBBHNG BROOK
J. DAVID SWANSON
$251 BUNNYSMOE CIRCLE
] SEPTIC SYSTEM DESIGN
DATE: AUG. 20, 2.005
SHEET: 2/$ GRID: 2636
PERMIT # SVO30xxx PID # 015-49£-14 BBB000£3.DVG
1250 ga! Septic tank
~0 ~
0
Standard Trench,
Vide
~5' Long
Beep
E.O' Sewer rock
Cover
NO SCALE
/Monltor
Cleanoufs
B' Cover
B.O £~ of' Septic Rock /
Effective
1250 GAL SEPTIC TANK
fO CaC£
NO SCALE
TDB~EN SPURKLAND P.E. Ii
203 ~15~h Ave
Anchorage Ak 99501
LOT 2 BUBBLING BROOKS S/D
625I BUNNYSHOECIRCLE
J. DAVID SWiNe. ON
SEPTIC SYSTEM SCHEMATIC
SHEET, ,,.T,/,,,.T GRID, 2638
! P£Rt~IT {f SWO$OOXX PARCEL ID ~ 015-4~2-I4 BBBOOO2$.DIC8
Pe.'formed For:
Legal Descripticn:
o
1.
2-
3-
4-
5.
6-
7-
8-
10-
11-
12-
13-
14-
15.
15-
17
COM:,tE,'-;T$
Municipality of Anchorage
Development Services Departmenl
Building Safely Division
On-Sile Water and Wastewater Prcgram
4700 South Bragaw SL
P.O. Box 1.~66,~0 Anchorage. AX 99519-6650
ww, v cl.anch~aqe .a~( .us
(9O7) 343-79O4
Soils Log - Percolation Test
Township, Range. SecSon: Site Plan
st,-1
WAS GROUND WAT£R
EXCCU;:TERED? ["~ ~O S
IF YES. AT WPAT DEPTH?
Depth to Water' A~er
Monitoring?
I I I I
I i
Gross Time I Net Time I Dep~,h to WaterI I'tet D'c;:) [
I
I::E R~CLATICH RATE J "~ . (,"¢~ue~,'~C~} F=RC ECLE Ct,~.'.t=TE=,
TEST Ru~,: B.-'r~/£~H ~ ~ ,~.,~o ~,,. ~
I I
PERFORMED BY: - i ,,,- ~ I "~...-.~ CERTIFY THAT THiS TEST
PERFOR:,,!ED h',l ACCORDANCE WITH ALL STATE AND MU.',;:CIPAL GUIDELINES IH EFFECT DJ"! Ti~IS DATE. DATE: ~"/~..
//~t"IJ//~'1, ~__~t/-"; "~ DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTECTION
ENVIRONMENTAL ENGINEERING DIVISION
825 L Street- Anchorage, Alaska 99501 Telephone 264-4720
ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT
NAME 1PHONE / a'EW
MAILING ADDRESS
LEGAL DESCRIPTION
LOCATION NO. OF BEDROOMS
~ Material No. of compartments
I-Z Manufacturer(-~
Liq. capacity in galJons Inside length Width Liquid depth
i~0 IF HOMEMADE:
6 v DISTANCE TO: Well Dwelling PERMIT NO.
.jt3Z
O Z <[ Manufacturer Material Liquid capacity in gallons
C~ We/J Foundation Nearest lot line PERMIT NO,
-- ''7' Z ~°[~c e.~l cf lines Trench wid~ ~ D is tan c e bet we~l~/~l~S
~ No. of lines Lengt h line Total I
I- ~ ~ inches
- Total effective al~lsorption area
. re~- Top of ti~e~.f~inish grade Material beneath tile
Length Width Depth PERMIT NO.
uJ
<~ I- Type of crib Crib diameter Crib depth Total effective absorpuon area
'" Well Building foundation Nearest lot line
;o DISTANCE TO:
. Class Depth Driller Distance to lot line PERMIT NO,
tu Building foundation Sewer line Septic tank Absorption area(s)
~ DISTANCE TO:
OT~:R
SOIL TEST RATING
INSTALLER \.
REMARKS
APPROVED ~ DATE LEGAL
72-013 (Rev, 3/78)
UNWIN- SCHEBEN 'KORYN TA
su.v ¥o.s
2515 A ST.,
December 5, 1977 ·
ANCHORAGE 99503 . (907) 276-4245
Mr. Buster Newton "~ '-
411' East 36th Avenue -~'''
Anchorage, Alaska 99503
Re: Proposed Bubbling Brook Subdivision
Subsurface Soils Investigation
Dear Mr. Newton:
This report presents the results of our soils investigation for the proposed
subdivision of a l0 acre tract located east of Birch Road and just west of '
Ravenwood Subdivision. The investigation was~conducted on November 15 and 16,
1977. The results of this investigation are included in this report as follows:
Vicinity Map
Test Hole Location Sketch
Test Hole Logs (Sheets 1 through 9)
Standard Explanatory Information
Drilling was accomplished utilizing a mobile drill B-50 mounted on a flex
track Nodwel vehicle, owned and operated by Denali Drilling, Inc. Test holes
were logged and perculation tests conducted by our firm.
The purpose of the investigation was to provide soils data and perculation
tests for establishing the feasibility of on-site disposal of sanitary wastes
using seepage pits. To accomplish this, we drilled 9 borings distributed
across the site with 1 test hole on each lot at the probable septic system
location. The test hole locations are shown on the attached location sketch.
All borings were drilled to a depth of 16 feet. During the drilling, our
engineer was present to log the materials encountered and obtain grab samples
of the sol) types. All soils were visually classified in the field in accord-
ance with the unified soil classification system as described in the standard
explanatory information attached herewith.
Since the site is fairly small and readily accessible from both sides, per-
culation tests were conducted in all holes at the completion of the drilling
and logging. The perculation tests were conducted from the 6 to 12 foot
levels in each of the holes in accordance with the Manual For Septic Tank
Practice published by the PHS. A ground water table was encountered in test
hole Number 9 at the 12 foot level. Therefore, the perculation test in this
hole was conducted between the 4 to 8 foot level.
'NWIN,P.E. LEO SCHEBEN,JR.,P.E.,L.S. EARL O. KORYNTA~ RE.
Mr. Buster Newton
December 5, 1977
Page Two
SITE.AND SOIL CONDITIONS'
The site is a~660 foot ~quare parcel having access from Rockridge Drive on the
east and Ravenwood Subd.~¥isi~n on the south. The site is dissected in a
southeasterly/northwesterly 'direction by a fork of the Little Campbell Creek.
The parcel slopes uniformly from southeast to northwest at an approximate 6%
to 8% average slope. A small 'knoll is located in the southeasterly corner.
There are no areas with slopes in excess of 25%. The parcel may be divided
into two very distinct soil map units for purposes of identifying perculation
characteristics. A 300~4J~O~.~ot wide band center~d. Qn the creek channel is
cha~acte~~c_~_~)..d alluvial..depositS-~nd-c~n~Sts primarily of well g~aded
.~anos and gravels with~'~'O~ perculation characteristicS, Test holes 2,
9__arreStor this deop.~9_it. Beyond this band, th~
siltier and tig~e~-'~-~emonstrated by test holes ?, 3, 5, 6 and 7.
CONCLUSIONS
The minimum perculation rates observed in'the field for the.following holes
are:
Test Hole Number 1 - 30.minutes per inch
TTe.~stHole ~2_.__l~tt~.~,~jl~b
est Hole Number 3 - 30 minutes per inch
Test Hole Number 5 - 25 minutes per inch
Test Hole Number 6 - 45 minutes per ~nch
Test Hole Number 7 - 60 minutes per inch
Test Hole Number 8 - 5 minutes per inch
Test Hole Number 9 - 5 minutes per inch
On-site waste disposal systems appear feasible on all lots. An aerated package
plant or other treatment process is advisable for the lots with high percula-
tion rates.
We hope this is sufficient for your present needs.
clarification, please do not hesitate.to contact us.
Attachments
EDK/clr
If we can offer further
Very truly yours~
Earl D.~ Korynta, P.E.
· 5.17
/
i
/
.%
RG
LEGEND
I
/
/
/
/
/
/
/
/
/
/
'SURVEYOR'S .CER 3' I FI CATE._~_~
~ ~ · profes~al
'" 752
DRILLING, INC.
79-108A
Well Owner.
Location
DRILLING LOG
GUNNARSON CONSTRUCTION
Use of Well
DOM.
(address of: To~vnship, Range, Section, if kno~vn; or distance main road_
Lot 2 Block 1 Bubbling Brook; Subdivision, Anchorage
Size of casing
Static water level
Screen (
1t
);
Depth of Itole 2__0__2_ ....... feet Cased to__29__1 .__2___deer
ft. (RtR~IK) (below) land surface. Finish of well (cheek one)
Perforated ( ).
Describe screen or perforation N/A
Well pumping test at_2L0___gallons per of drawdown from static level.
Date of completion 1 / 4 / 79
(minute) for ..... _1_ ....hours with
WELL LOG
Depth in feet frmn
ground surface Give details of formations l)enetrated, size of material, color and hardness
open end ( );
..... O__TO Z
.... 2 TO 23
4_3~_TO 35
_ ~5__TO 50
.... ~Q__TO 68
.... TO 95
2~5__TO 105
105 _TO 135
_..~J5 .... TO. 14i
_i56 _TO_ 165
196 _TO__~)_2_
..... Ga s in g ~Jz.Lc kup .........
Silty gravel: cobbly
Sandy g_~_a ze 1-
..... L_Lgo s_e__g_r_aye ~_
_S i_ 1 tf__c__l_a_y_ _
S__i__l_t.'l hard pan__.
Boulders
..... ~and_y hard pan
....... _D_am~p_gr ave 1
Silty. clay
.2tar d_ pan
Boulders
_C!~y
.... _Water gr2v al
1 - CUSTOMER
MUNICIPALITY OF ANCHORAGE
DEPARTMENT OF HEALTH & ENVl RONMENTAL PROTECTIO~'VIRONMENT'~'L
825 L Street-Anchorage, Alaska 99501 J A N
ENVIRONMENTAL ENGINEERING DIVISION
Telephone 264-4720RECEIVED
REQUEST FOR APPROVAL OF INDIVIDUAL WATER AND SEWER FACILITIES
DIRECTIONS: Complete all parts on page 1. Incomplete reques~ will not be proces~d. Please allow ten (10) davs for processing.
1. PROPERTY OWNER I PHONE
MAILING ADDRESS ~
PROPERT~ RESIDENT (If different from above) PHONE
2. BUYER PHONE
3. LENDING INSTITUTION I PHONE
MAILING ADDRESS
5. LEGAL DESCRIPTION
S*R[ET LOC^'nO~
J~ SINGLE FAMILY
[] MULTIPLE FAMILY
NUMBER OF BEDROOMS
[] One [] Four
[] Two [] Five
~ Three [] Six
[] Other
7. WATER SUPPLY
INDIVIDUAL~
[] COMMUNITY
[] PUBLIC UTI LITY
8. SEWAGE DISPOSAL SYSTEM
INDIVIDUAL/ON-SITE**
[] PUBLIC UTILITY
* ATTACH WELL LOG. ,A wel! Io~] is required for all wells drilled
since June 1975. For wells drilled prior ~o that date, gJ, ve well
depth (attach log if available.) ~
**If individual/on-site, give installation date,-~- ~ )'~?~.
If system is over two (2) years old an adequacy test is required
by this Department.
NOTE: THE INSPECTION FEE MUST ACCOMPANY EACH REQUEST BEFORE PROCESSING CAN BE INITIATED.
72-010(3/78)
THIS SIDE FOR OFFICIAL USE ONLY
DATE RECEIVED
INSPECTION APPOINTMENTS
TIME TIME TIME
DATE DATE DATE
INSPECTOR INSPECTOR INSPECTOR
DIRECTIONS:
NUMBER OF BEDROOMS
1. TYPE OF RESIDENCE
~ SINGLE FAMILY
[] MULTIPLE FAMILY
2. WATER SUPPLY
[~'"~N DIVI DUAL
F-I COMMUNITY
[] PUBLIC UTILITY
Connection Verified
3. SEWAGE DISPOSAL SYSTEM
[~]~IVI DUAL/ON -SITE
[~]PUBLIC UTILITY
Connection Verified
[--]Septic Tank or []Holding Tank
Size:~ If Tank is homemade
give dimensions:
TYPE OF TANK
TOTAL ABSORPTION AREA
4. DISTANCES
WELL TO:
Absorption Area to nearest Lot Line
[] ONE [] THREE [] FIVE
[] TWO [] FOUR [] SlX
PERMIT NUMBER
DEPTH OF WELL
DATE DRILLED
LOG RECEIVED
PERMIT NUMBER
DATE INSTALLED
INSTALLER
SOl LS RATING
MANUFACTURER
MATERIAL
Septic/Holding Tank
Absorption Area 1Sewer Line
[] OTHER
Nearest Lot Line
5. COMMENTS
~]~PPROV ED FOR ~ BEDROOMS
[] CONDITIONAL APPROVAL (letter must accompany certificate)
[] DISAPPROVED ~L~~ ~/~//~
I BY (Title~,~
DATE
LEGAL DESCRIPTION
72-010 (Rev. 3/78)
Municipality of Anchorage °
On -Site Water and Wastewater Program
(907) 343-7904 5
Certificate of On -Site Systems Approval
Parcel I. D.015-492-14
1. GENERAL INFORMATION:
Complete legal description Bubbling Brook; Lot 2
Location (site address) 6251 Bunnyshoe Circle *Anchorage, AK
Expiration Date: /f - I3 •ZD7
Current Property owner(s) Day phone
Mailing address
Real Estate Agent Michelle Webb Day phone
2. TYPE OF DWELLING:
® Single Family (w/wo ADU)
❑ Duplex
❑ Multiple Dwellings (Single Family and/or Duplex)
3. NUMBER OF BEDROOMS:
4
4. TYPE OF WATER SUPPLY:
TYPE OF WASTEWATER DISPOSAL:
Individual Well
®
Individual
Individual Water Storage
❑
Holding Tank
❑
Community Class Well
❑
Community
❑
Public Water System
❑
Public Sewer
❑
WaiverNariance request for: Distance:
Received by: Date:
COSA to be released to the engineer, unless otherwise requested by the engineer.
COSA Fee $ 50 Waiver Fee $
Date of Payment g 13 a a 2 t Date of Payment
Receipt Number 0 L4 601 G Receipt Number
COSA # OSC 2 I I L1 79 Waiver #
5. STATEMENT OF INSPECTION BY ENGINEER
As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation,
based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application,
shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate
for the number of bedrooms and type of structure indicated herein. I further verify that based on the information
obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water
supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes,
ordinances, and regulations in effect at the time of installation.
Name of Firm: Garness Engineerinq Group, Ltd (GEG) Phone: 907-337-6179
Address: 3701 East Tudor Road, Suite 101- Anchorage, Alaska 99507
Engineer's Printed Name: Jeffrey A. Garness Date
�b)tt I•Zr
In conducting this evaluation, GEG provided an engineering evaluation of the well and/or septic system
in accordance with the guidelines and regulations established by the Municipality of Anchorage and
industry practices. The reported results describe the condition of the system/s on the date/s of the G DE A
evaluation. Separation distances were measured to readily identifiable features. Hidden defects ori�� • . • • • . .
encroachments may exist that were not identified during the evaluation. The operational life of all wells ,� P .- S% i
and septic systems depend upon a variety of variables, including but not limited to, soil conditions,;Il
�' ✓� : is , , � ; , •, -y- !)
groundwater levels (that may fluctuate during the year), quality of construction (materials and
workmanship), and the water usage of the family utilizing the system/s. These conditions can vary, and""""'" """" ""' """"" ""'
are outside the control of GEG. Satisfactory test results do not guarantee future performance of the
system/s; therefore, GEG makes no warranty (express or implied) regarding the future performance of �• (/
the well or septic system. GEG makes no representation whether an alternative well or septic system (b. y A. :.:emess,
can be installed on the property in the event either of the current systems fail to perform adequately in �0, �. 1, CE- 719-
the
9 the future. The content of this report is for the sole benefit of the person/party that retained GEG to
perform the evaluation. Reliance upon the information provided in this report by any other person or �;��� qC1
party (including subsequent property purchasers) is not authorized, nor will it confer any legal right �rores�!`
whatsoever. `
#AECC884
6. DSD SIGNATURE
System #1 Approved for '1 bedrooms
System #2 Approved for bedrooms TYf OF(a((,��•��
Disapproved `\SJ��G\e
Conditional approval for bedrooms, with the followinc�t�iul Ic?y-srrE
O�
a�
o IAIA ER AND m
J
l
J�
ATER z
Original Certificate Date:— r 3 ^ zo?_
The Municipality of Anchorage Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only
upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality
of Anchorage is not responsible for errors or omissions in the professional engineer's work.
7. ATTACHMENTS:
COSA Checklist 7K -
Nitrate Advisory
Septic System Advisory Arsenic Advisory
Well Flow Advisory Other
„AA
Legal Description: BUBBLING BROOK; LOT 2
If more than 1 septic system on lot: COSA Checklist # of
A. WELL DATA
❑ Well log is filed with Onsite (or attached)
Date drilled 1/4/79
Total depth 202 ft
Cased to 201.2 ft
❑ Sanitary seal is functioning correctly
Ef Wires are properly protected
Casing height (above ground) 12+ in.
Date of flow test for COSA 7/27/21
Static water level at beginning of test 158.3 ft
Comments
Parcel ID: 015-492-14
Structure served by this system
"Well production at time of test 5.5+ gpm
Water storage tank volume gallons
' WO'disinfected for coliform test? ❑ Yes ❑ No
V Coliform bacteria is Negative
F,.
Nitrate mg/L NrNitrateless than MRL (ND)
Arsenic ug/L fq/Arsenic less than MRL (ND)
Collected by GEG
Date of Sample
7/27/21
DOUBLE CLEANOUTS AFTER TANK ARE HOLDING WATER.
POSSIBLY A SLIGHT REVERSE GRADE AFTER TANK
B. TANK DATA C. LIFT STATION
Age of tank(s) 18 years ❑ Required maintenance co
Tank type/material SEPTIGSTEE Age of lift station ¢-a
Measured operating fluid level in septic tank *52 Lift station materiail"'
OR Standpipes/foundation cleanout per record drawing
Date of pumping SI VT -I
—
D. ABSORPTION FIELD DATA
Which system tested (date installed) 9/2003
❑ ALL standpipes present per record drawing
Total measured depth from grade 12 ft (max)
r Measured depth to pipe invert from grade 4.2 ft (min)
❑ NIA – pressurized field
❑ Monitor tubes go to bottom of effective. If not, state
depth into effective 7.6
Comme
Adequacy test date
7/28/21
Results ❑✓ Pass
For 4 bedrooms
Fluid depth prior to test
68 in
Water added 800
gal
New depth 87 in
Elapsed time 185
min
❑ Code -required soil cover over field
Final fluid depth 82 in
❑ System presoaked Absorption rate 600+ gpd
(Required if vacant for greater than 30 days prior to Any rejuvenation treatment (past 12 months)
date of test) N/A
Gallons introduced "2418 gallons If yes, enter date
Comments/Deficiencies: PIPE AT END OF 1978 TRENCH NOT LOCATED "DRAINFIELD DRY PRIOR TO THE PRE-SOAK ON 7/27/2021
COSA Checklist yellow sheet
NO
E. SEPARATION DISTANCES
From Private Well on Lot to: (Please enter distances if less than required or if community well)
Septic Tank/Lift Station on Lot > 100'
® Yes
Neighboring Tank > 100' ❑✓ Yes
Absorption Field on Lot > 100' F/� Yes
Neighboring Absorption Fields > 100'
0 Yes
Community Sewer Main > 75' F/ Yes
From Septic/Holding Tank on Lot to: (Please enter distances if less than required)
Building Foundations > 10' ❑ Yes if No **5 + ft Surface Water > 100'
ft
ft
ft
ft
ft
0 Yes if No ft
Property Line > 5'
❑✓
Community Sewer Manhole/Cleanout > 100'
if No
ft
Q✓ Yes
if No
if No
ft
Private Sewer/Septic Line > 25' ❑✓ Yes
if No
if No
ft
Holding Tank > 100' Z Yes
if No
*
ft
Animal Containment > 50' F✓ Yes
if No
if No
ft
if No
ft
If septic tank is under driveway comment below
Manure/Animal Excreta Storage > 100'
if No
ft
❑✓ Yes
if No
From Septic/Holding Tank on Lot to: (Please enter distances if less than required)
Building Foundations > 10' ❑ Yes if No **5 + ft Surface Water > 100'
ft
ft
ft
ft
ft
0 Yes if No ft
Property Line > 5'
❑✓
Yes
if No
ft
Wells on Adjacent Lots:
Absorption Field > 5'✓�
0
Yes
if No
ft
Private Wells > 100'✓Q Yes if No.
Water Main > 10'
F71
Yes
if No
ft
Community Wells > 200' 0 Yes if No
Water Service Line > 10'
✓l
Yes
if No
ft
If septic tank is under driveway comment below
From Absorption Field on Lot to: (Please enter distances if less than required)
Building Foundation > 10' Fv Yes if No ft If absorption field is under driveway comment below
Property Line > 10'
F/�
Yes
if No
ft
Wells on Adjacent Lots:
Water Main > 10'
0
Yes
if No
ft
Private Wells > 100' ® Yes if No
Water Service Line > 10'
1771
Yes
if No
ft
Community Wells > 200' Yes if No
Surface Water > 100'
0
Yes
if No
ft
F. ENGINEER'S COMMENTS
'PER CONVERSATIONS WITH THE OWNER OF BUBBLING BROOK, LOT 1 DURING GEG SITE VISIT ON 7/28/21, THE SEPTIC PIPES FOR THE
DRAINFIELD ARE NOT PRESENT AND COULD THEREFORE NOT BE LOCATED. THE EXACT SEPERATION DISTANCE
IS UNKNOWN BUT ASSUMED TO BE 100'+ **MET CODE AT TIME OF INSTALLATION
G. ENGINEER'S CERTIFICATION
1 certify that l have determined through field inspections and review
of Municipal records that the above systems are in conformance with y QO
O
MDA COSH guidelines in effect on this date. \ � . .. . . .. . . . . . .. . .. • • . _ _ .. •
J�f r y rness., ..0
Q 9. CE i7j9r 3 �p
e
COSA Checklist yellow sheet �o\ o0
ofessW 0
I1
ft
ft
ft
#AECC884
Municipality of Anchorage
Development Services Department
Building Safety Division
On-Site Water and Wastewater Program
4700 Bragaw Street
P.O. Box 196650
Anchorage, AK 99519-6650
www. muni.org/onsite
(907) 343-7904
CERTIFICATE OF ON-SITE SYSTEMS APPROVAL
FOR A SINGLE FAMILY DWELLING
Parcel I.D. 015-492-14
GENERAL INFORMATION
Complete legal description
Location (site address)
Lot 2, Bubbling Brook Subdivision
6251 Bunnyshoe Circle Anchorage, AK 99516
Expiration Date:
Current Property owner(s) Edwin and Jennifer Simeonoff
Mailing address 6251 Bunnyshoe Circle Anchorage, AK 99516
Day phone
Lending agency
Mailing address
Day phone
Real Estate Agent
Mailing Address
Unless otherwise requested, COSA will be held by DSD for pickup.
NUMBER OF BEDROOMS: Four (4)
Day phone
TYPE OF WATER SUPPLY:
Individual Well
Individual Water Storage
Community Class ~ Well
Public Water System
TYPE OF WASTEWATER DISPOSAL:
Individual On-site []
Individual Holding Tank []
Community On-site []
Public Sewer []
The Municipality of Anchorage Development Services Department (DSD) issues Certificates of On-Site Systems
Approval (COSA) based only upon the representations given in paragraph 4 by an independent professional civil
engineer registered in the State of Alaska. Certificates of On-Site Systems Approval are required for the transfer of
title (except between spouses) for properties served by a single-family on-site wastewater disposal and/or water
supply system. DSD also issues COSAs upon request to homeowners. Certificates of On-Site Systems Approval
are valid for 90 days from the date of issue for properties served by a private or Class C well and may be reissued
with new water sample results. (Certificates may be reissued for a period of up to one year with valid water
samples.) Certificates are valid for one year for properties served by Class A or B wells or a public water system.
The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work.
4. STATEMENT OF INSPECTION BY ENGINEER
As certified by my seal affixed hereto and as of the validation date shown below, I vedfy that my investigation,
based on procedures outlined in the Certificate of On-Site Systems Approval Guidelines for this application,
shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate
for the number of bedrooms and type of structure indicated herein. I further verify that based on the information
obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water
supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes,
ordinances, and regulations in effect at the time of installation.
Name of Firm Anderson Engineering
Address P.O. Box 240773 Anchorage, AK 99524
Engineer's Printed Name Michael E. Anderson, P.E.
DSD SIG,.NATURE
Disapproved.
Conditional approval for
bedrooms.
Phone 522-7773
Date 7/22/2010
bedrooms, with the following stipulations:
Attachments: COSA Checklist
Septic System Advisory
Well Flow Advisory
Nitrate Advisory
(Rev. 11/05)
X
Arsenic Advisory
Maintenance Agreements
Supplemental Engineer's Report
Other
Original Certificate Date: 7~ ~ '~''' / ''~'
Municipality of Anchorage
Development Services Department
Building Safety Division
On-Site Water & Wastewater Program
4700 Elmore Road
P.O. Box 196650
Anchorage, AK 99507
www.muni.org/onsite
(907) 343-7904
CERTIFICATE OF ON-SITE SYSTEMS APPROVAL CHECKLIST
Legal Description: Lot 2, Bubbling Brook Subdivision Parcel iD: 015-492-14
A. WELL DATA
Well type Pdvate IfA, B, or C provide PWSID # Well Log (Y/N) Y
Date completed 1/4/79 Sanitary seal (Y/N)... Y Wires properly protected (Y/N) Y
Total depth 202 ft: Cased to 201.2 fl:. Casing height (above ground) >18 in.
FROM WELL LOG AT INSPECTION
Date of test 1/4/79 7/15/10
Static water level Unknown ft. 145.2 ft.
Well production 30 g.p.m. 7.0 g.p.m. ~
WATER SAMPLE RESULTS:
Coliform 0 colonies/100mL Nitrate N/D mg/L
ArSenic: N/D ug/I 'Date of sample: .71110
B. SEPTIC/HOLDING TANK DATA
Other bacteria
Collected by: M. Anderson
Tank Type/Material Septic/Steel
Date installed 9/8/03
Tank size 1,250 gal.
Foundation cleanout (Y/N) Y
Date of pumping 7/20/10
Number of Compartments Two
Depression over tank (Y/N) N
Pumper A Plus Home Services
Cleanouts (Y/N)
High water alarm (Y/N)
C. ABSORPTION FIELD DATA
Date installed 9/8-11/03 Soil rating (g.p.d./ft2 or ft2/bdrm).6 GPD/SF
Length 65 ft. Width 2 ft.
Total depth 12 ft. Eft. absorption area ..1..,040 ft2 Monitoring tube
Date of adequacy test 7/15/10 Results (Pass/Fail) Pass
Fluid depth in absorption field before test 83.5 in.
Elapsed Time: 1,285 min. Final fluid depth 84
Any rejuvenation treatment (past 12 mo.) (YIN & type) '
0 colonies/100 mL
System type Deep Trench
Gravel below pipe ... 8 ft.
Y Depression over field N
For 4 bedrooms
Water added 620 gal. New depth 93.2 in.
in. Absorption rate >= $0o g.p.d.
N If yes, give date
D. LIFT STATION
Date installed
"Pump on" level at~
in.
Size in gallons
"Pump off" level at~
in.
Manhole/Access (Y/N)
High water alarm level at
in.
Datum Cycles tested
E. SEPARATION DISTANCES
Meets alarm & circuit requirements?
SEPARATION DISTANCES FROM WELL ON LOT TO:
Septic tank/lift station on lot >1oo'
Absorption field on lot ·1oo'
Public sewer main N/A
On adjacent lots >100'
On adjacent lots >loo'
Public sewer manhole/cleanout
N/A
Sewer/septic service line >25' Holding tank N/A
Animal containment areas >50' Manure/animal excrete storage areas
SEPARATION DISTANCES FROM SEPTIC/HOLDING TANK ON LOT TO:
· 100'
Building foundation >5' Property line >5' Absorption field >5'
Water main N/A Water service line >10' Surface water >100'
Wells on adjacent lots >100'
SEPARATION DISTANCE FROM ABSORPTION FIELD ON LOT TO:
Property line >1o' Building foundation >1o' Water main >1o'
Water Service line >1o'
Curtain drain None Noted
Surface water >100'
Wells on adjacent lots >100'
Driveway, parking/vehicle storage ·25'
F. COMMENTS: Diverter Valve Turned Directing Flow to Old System. Valve Should be Turned Back to New System Once it
Ddes Out.
G.
ENGINEER'S CERTIFICATION
I certify that ! have determined through field inspections and
review of Municipal records that the above systems are in
conformance with MOA COSA guidelines in effect on this date.
Engineer's Printed Name Michael E. Anderson, P.E.
Date 7/22/2010
COSA Fee $.,,
Date of Payment
Receipt Number
(Rev. 11/05)
Waiver Fee $
Date of Payment
Receipt Number
~ASEMENTS OF RE C~ORD. OTHER THAN
THOSE SHOWN ON TJ',~E RtSCORDED
PLAT ARE NOT SHOWN HE~EON,
AS-BUILT NO CORNERS SET THiS DATE
I hereby certify that I. have performed ~ Mo'[lagee's kn~
speed, on ~ ~e foHow~ng d.escr~bed propertyt ...............................................................
men~ situated thereon are within the property ~nes and do
not overlap or en~oa~h on the proD~ty lying adjacen~ there~
t~ that no }mprovemen~ on property ly'in~ adjacent there~
encroach on the pre~ses in question ~nd ~a~. thee are no
roadway. /r~s~ission lines or o~he~ 'tds~b]e easements on
sai. d prOpe~ty except as indica~d hereon.
FRED WALATKA & ASSOCIATES
Engineers :md Surveyors
ANDERSON ENGINEERING
P.O. BOX 240773
ANCHORAGE, AK 99524
522-7773 522-6779 (FAX)
July 21, 2010
Ed Simeonoff
6251 Bunnyshoe Circle
Anchorage, AK 99516
Subject:
Lot 2, Bubbling Brook Subdivision
Well and Septic System Inspection, Testing and Certification
Dear Ed:
A flow test was performed on the well and water system on Lot 2, Bubbling Brook
Subdivision on July 15, 2010. The static water level in the well was found to be 145.2'
below the top of the casing prior to beginning of the test. The water was then allowed to
flow freely for a period of 4 hours and the well production measured on a regular basis
during that period. The average flow monitored during the test period was slightly more
than 7.0 gallons per minute and the static water level dropped slightly and recovered
rapidly once the test ended. The well and water system is in compliance with Municipal
and State of Alaska Department of Environmental Conservation (ADEC) regulations and
meets all requirements for a three bedroom home. We did note, however, a gap
between the electrical conduit leading to the well head cover. The current code requires
all wiring be encased in conduit from the well head to a minimum of 6" below ground.
A water sample was taken from the system and tested for coliform, bacteria, arsenic
and nitrate content. The results from the testing are attached and indicate the nitrate
content is below the maximum allowable limit. No coliform, bacteria or arsenic was
found in the water sample.
The septic system was inspected to verify it was functioning in accordance with the
original design. MuniciPal records indicate the system was constructed in 2003 and
replaced a system constructed in 1978. The newer system is composed of a 1,250
gallon septic tank and a 65' long x 2' wide x 8' effective depth absorption trench. The
original absorption trench is composed of a 51' long x 3' wide x 6' absorption trench and
is connected to the new system with a flow diverter valve. No monitor tube was found in
the old trench, but our probing indicating it is probably dry.
The absorption trench constructed in 2003 and currently in service was found to have a
total of 83.5" of water indicating only 12.5" of freeboard remaining. We then injected
620 gallons of water into the absorption trench. The water level rose to 93.2". The
water level then receded back to its original depth over the next 24 hours. The system
is therefore capable of absorbing a minimum of 150 gallons of water per bedroom over
a 24 hour period and meets Municipal criteria for certification.
Lot 2, Bubbling Brook
July 21, 2010
Page 2 of 2
The septic tank was recently pumped and the diverter valve turned to allow flow into the
old trench. We recommend using the old trench for at least the next year to allow the
new trench to rest and dry out. The valve should then be turned back to allow flow into
the newer trench. No monitor tube is in place in the old trench so it will not be possible
to monitor the water level in this trench.
Sincerely,
Michael E. Anderson, P.E.
Attachments