HomeMy WebLinkAboutSPERSTAD #2 BLK 4 LT 5perstad #2 Block 4 Lot 5 #018-072-19 Municipality of Anchorage Community Development Department Page 1 of 3 On-Site Water and Wastewater Program 4700 Elmore St. • P.O. Box 186650 Anchorage, AK 99519-6650 • http;Ifwww.muni.org/onsite • (907) 343-7904 ONSITE WASTEWATER INSPECTION REPORT Permit Number: ADEC10957 PID Number; 018-072-19 ❑ New �g Upgrade (dame: - H. J. &Beverly Carlson ABSORPTION FIELD ❑r Deep Trench ❑ Shallow Trench ❑ Bed ❑ Mound Address P.O. Box 110048 Anchorage, AK 99511 0 Other Phone Number of Bedrooms Soil Rating Total depth from original grade 5 .6 GPD/SF 13 Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade 5 Ft. Gravel depth beneath_ pipe 8Ft. Subdivision Block Lot. Sperstad #2 4 5 Fill added above original grade 1-2 Ft. Gravel length 80FL ownshp Range .Section Gravel width 3Ft, Beds: Number of Lines Distance between lines I FL SEPARATION DISTANCES To Septic Absorption Holding Sewer Total absorption area Number of trenches Dist. between trenches From Tank Field Lift Station Tank Lire 1,280 Fe Two I >1017t. Well 91'"' >100' N/A NIA >25' TANK El Septic 0 S.T.E.P. 0 Holding, El Other Manufacturer Anchorage Tank Capacity I 500Ga1. Surface water >100' >100' NIA NIA Materia( Steel Number of compartments One Lot Lyle >5' >70' N/A NIA NA Foundation >5' >10' NIR N/A LIFT STATION Manufacturer Capacity Gal. Curtain Drain None Noted Pump on level at Pump ox level at High water alarm at RemarksExisting 1,250 Gallon Generate Septic Tank in: in. in: was inspected, Tested and Verified Sound. Existing 500 Gallon Tank Decommissioned in Accordance with Pump make and model Electrical Inspections performed by Municipal Cade. * See ADEC Waiver. PIPE MATERIAL House to tank ()3034 d4 Installer G & R Excavating Dra'mfield F810 4 Inspector j, Berkram BENCHMARK (Assumed elevation) 100 Inspection .r 1 7117/14 2-- 7/18/14 Locationand description dates: V 7/22/14 a" ]d3 Garage Slab. COMMUNITY DEVELOPMENT DEPARTMENT APPROVAL ;E.$ O°FConditional Approval: Dateo493'HA eaaweti.s.. ..... � I* : SAI AEL E. ANDERSON CE-4381 a� 1111 Approved Date-// %%FESStc'04- Inspection ReporLI-1-12.doc 1110' r a p °' ssN o 0 a. eat 0 N O 4:00 L) a'o C c , O c= C U f amg� g 12 UN / cc 11 00 n o —5 > s l / II el 0 10. % Plumb , cs o v� m K-1 v Cannes son .,` A, m M v yam. Cj - m U o WO C, t o m o Cl) `I. �v N NyOy�Cp3 O $S' h Z{p } �0 'SG OOOaO0 WFN]0F_Ua LYS ©.y 00<q LU 0 pM m rc¢ a n m vi c Wi m __- g Q ffJ _ 0% U? }uawas03 3 V i ,OL wm Q O 0 l6'Si�t r < Co w n w rrr�� p C:�Lli V n � Z c sn c z 1{y 'ry in to .- b 0 O o fl i2��g Zcmi 1n C +b� b Z i w $ §9z a �r� Municipality of Anchorage DEVEOPMENT SERVICES DEPARTMENT 4700 South Bragaw Street Anchorage, AK. 99519.6655 - 343-7904 On -Site Wastewater Disposal System or Well Inspection Report ADEC Permit Number 10957 23,358 S.F. 99.4 N NM M UI UU N Page 3 PID No. 018-072-19 UU � N 00 U M H g U 92.0 84.0—/ II 84.0 Length) No Groundwater No Bedrock 7-24-14 78.0 PROFILE AS -BUILT No Scale --- 92.0 8' Drainfield Rock 84.0—/ II 84.0 Length) No Groundwater No Bedrock 7-24-14 78.0 PROFILE AS -BUILT No Scale --- 92.0 MUNICIPALITY OF ANCHORAGE DEVELOPMENT SERVICES DEPARTMENT 4700 BRAGAW STREET ANCHORAGE, AK 99519-6650 SOILS LOG - PERCOLATION TEST LEGAL DESCRIPTION: SPERSTAD No.2 BLOCK 4 LOT 5 PERFORMEDFOR: H. J. CARLSON DATE: 6 / 3 / 2 014 PROJECT No.: PARCEL ID#: TECHNICIAN: JB DEPTH TEST HOLE 1 (Feet) 1 2 3 4 5 6 7 8 9 OB/OG GM/SM WE •' 49th.* MICHAEL E. ANDERSON No. CE -4381 . SITE PLAN n.s x 34' SEE SITE PLAN i 1 O WAS GROUND WATER ENCOUNTERED? No IF YES Q WHAT DEPTH? NONE DEPTH OF WATER AFTER MONITORING: NONE 2-5D%0 1 1 DATE OF MONITORING: 6112/14 13 14 15 16 17 1 20 COMMENTS: TEST HOLE PRE SOAKED PRIOR DATE READING GROSS TIME (MINUTES) NET TIME (MINUTES) DEPTH To WATER (INCHES) NET DROP (INCHES) TEST HOLE PRESOAKED PRIOR TO TESTING: 6/3 1 9:18 3.7511 2 9:48 30 9.0011 5.2511 3 9:55 3.2511 4 10:25 30 8.2511 5.0011 5 10:26 3.2511 6 10:56 30 8.25f1 5.0011 PERCOLATION RATE: 6 (MIN/INCH) PERC. HOLE DIA. 6 (INCHES) TEST RUN BETWEEN: 5 FT. and 6 FT. TEST PERFORMED BY ANDERSON ENGINEERING. I, MICHAEL E. ANDERSON CERTIFY THAT THIS WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS DATE: 6/11/2014 MUNICIPALITY OF ANCHORAGE DEVELOPMENT SERVICES DEPARTMENT 4700 BRAGAW STREET ANCHORAGE, AK 99519-6650 DEPTH (feet) 1- 2 3 4 5 6 7 8 9 SOILS LOG - PERCOLATION TEST LEGAL DESCRIPTION: SPERSTAD NO.2 BLOCK 4 LOT 5 PERFORMED FOR: HANK CARLSON DATE: 6/2/1/, PROJECT No.: PARCEL ID#: TECHNICIAN: JB OB/OG GM TEST HOLE 2 SLOPE 49th MICHAEL E. ANDERSON SITE PLAN 59' 20.5' 1 O READING WAS GROUNDWATER ENCOUNTERED? NO NET TIME (MINUTES) DEPTH TO WATER (INCHES) IF YES @ WHATDEPTH? NONE S TEST HOLE PRESOAKED PRIOR TO TESTING: DEPTH OF WATER AFTER MONITORING: NONE O 11 9:26 DATE OF MONITORING: 7/24/IL 0 1 BOH @ 19' DATE READING GROSS TIME (MINUTES) NET TIME (MINUTES) DEPTH TO WATER (INCHES) NET DROP (INCHES) TEST HOLE PRESOAKED PRIOR TO TESTING: 6/3 1 9:26 3.00" 2 9:56 30 4.625" 1.625' 3 9:57 3.00" 4 10:27 30 4.50" 1.50" 5 10:28 3.00" 6 10:58 30 4.50" 1.50" PERCOLATION RATE: 20 (MIN/INCH) PERC. HOLE DIA. 6 (INCHES) TEST RUN BETWEEN: 5 FT. and 6 FT. COMMENTS: TEST HOLE PRE SOAKED PRIOR TO TEST. TEST HOLE DEEPENED 7/17 TO 19' PRIOR TO CONSTRUCTION TO VERIFY LACK OF GROUNDWATER AND BEDROCK. TEST PERFORMED BY ANDERSON ENGINEERING. I, MICHAEL E. ANDERSON CERTIFY THAT THIS WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS DATE: 11/22/2014 MUNICIPALITY OF ANCHORAGE DEVELOPMENT SERVICES DEPARTMENT 4700 BRAGAW STREET ANCHORAGE, AK 99519-6650 SOILS LOG - PERCOLATION TEST LEGAL DESCRIPTION: SPERSTAD No.2 BLOCK 4 LOT 5 PERFORMED FOR: HANK CARLSON DATE: 6 /17 /14 PROJECT No.: PARCEL ID#: TECHNICIAN: JB DEPTH TEST HOLE 3 (feet) I OB/OG 2 3 4 5 6 7 8 GM w SLOPE 10 WAS GROUND WATER ENCOUNTERED? No IF YES @ WHAT DEPTH? *S DEPTH OF WATER AFTER MOMTORAIG: NONE li_J 11 DATE OF MONITORING: 6/17/14 p 12 Fc 13 14 BOH @ 14' 15- 16- 17- 18- 19— DATE 516171819 SITE PLAN 59' zo.s' a DATE READING GROSS TIME (MINUTES) NET TIME (MINUTES) WATERD (INCHES) NET DROP (INCHES) TEST HOLE PRESOAKED PRIOR TO TESTING: 6/17 1 10:14 1.25" 2 10:44 30 3.00" 1.75" 3 10:45 1.50" 4 11:15 30 3.25" 1.75" 5 11:16 1.25" 6 11:46 30 3.00" 1.75" PERCOLATION RATE: 1 �• 1(MIN/INCH) PERC. HOLE DIA. 6 (INCHES) TEST RUN BETWEEN: 6 FT. and 7 FT. COMMENTS: TEST HOLE PRE SOAKED PRIOR TO TEST. TEST PERFORMED BY ANDERSON ENGINEERING. I, MICHAEL E. ANDERSON CERTIFY THAT THIS WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPLE GUIDELINES IN EFFECT ON THIS DATE: 6/12/2014 June 30, 2014 State of Alaska Dept. of Environmental Conservation 555 Cordova Street Anchorage, AK 99515 Attention: Mr. William Reith, P.E. Subject: Sperstad Subdivision No. 2, Block 4, Lot 5 Two Home Septic System Certificate to Certificate to Construct Septic System Dear Mr. Reith; The existing absorption trench on the subject lot has failed and must be replaced. The septic system currently serves two residential structures on the lot. The first is a four bedroom home and the second is a one bedroom rental property. Both are operated and maintained by the same owner. We are therefore requesting a Certificate to Construct a new septic system absorption trench. The existing septic tanks which were constructed in the past will be exposed, inspected and verified suitable for continued use. They will be replaced by a single 1,500 gallon steel septic tank if they are found to be defective. The septic system is designed for five bedrooms and an average daily flow of 750 gallons per day. A test hole recently placed in the area of the proposed absorption trench revealed gravel and sand with some silt (GM/SM) to depths of 18'. The material absorbed water at a rate of 6 minutes per inch. We are proposing to place a new absorption trench 80' in length by 3' wide with an effective depth of 8'. The total depth of the trench will be 12' from existingde. A design factor o f Xlonn perr aldgay t per square foowas used in the design of the trench. �4,i,,, l The existing absorption trench will remain in place and a flow diverter valve will be installed to allow for future use if the trench should regenerate to a usable condition. The surface of the lot is virtually flat in the area of the new absorption trench. There are no slopes greater than 25% within 50' of the absorption trenches. All vertical and horizontal separation distances are met by the system design and construction. The system has been designed and will be constructed in accordance with the latest update to State Statute 18AAC 72. We have included the Owner's Statement, Data Sheet/Generals Checklist and the General Checklist for Approval to Construct. The existing Class C Well on the lot currently has waivers in place to the existing septic tanks and absorption trench. We have completed a waiver request Lot 5, Block 4, Sperstau No. 2 June 30, 2014 Page 2 of 2 to allow the new trench to be located 109' from the well and the new septic tante to be 105' from the well. We hereby request -a Certificate to Construct the septic system be issued. Sincerely, Michael E. Anderson, P.E. Attachments MICHAEL E. ANDERSON 2D AWWU Water System I `•/y y% 1 D r I 14 D 2 T O D 13 �. r= ; 5� oD 1g 12 ' r r I o 5 0 1CV I , r , I � I I I r 3 O I , I � I ------------------____-_-_ ; r I , I � 9A p 2 m 8 7 Y f r , r 5 1B 1A m 9B " �?,�•.F� '�—44#, Road CROSSM• ! 49th ...6 ... ,.�. r... �,5 MICHAEL ..................E. ANDERSON: No. -tsar AREA IyI A P f'• cE r•••�i q11 4% ESSt�Pi4 SCALE 1" - roo' - nrt++rte O CIP ei b S t° o .SO au N O z z -It O Y (.) LL j 00 1 W m m M D N Q O m ALJ V) rn c y N j wx° d Z 6\ N a bO N o V)_oN D cN U 0 3 4 N h mw 4U) ZIZ�}i2 \ N \ }uaw9s03 3 V 1 ,Ot F-�.'1 wrvamlwa xwrrmvv O / o a U / N a o > F-00S0.� O CIP ei b S t° o .SO au N O z z -It O Y (.) LL j 00 1 W m m M D N Q O m ALJ V) rn c y N j wx° d Z 6\ N a bO N o V)_oN D cN U 0 3 4 N h mw 4U) ZIZ�}i2 \ N \ }uaw9s03 3 V 1 ,Ot F-�.'1 wrvamlwa xwrrmvv 2 O C W 0 C ® W /!�\e X 0 a / /f•J w x° O O :7 L v O � j O a; J mm N Ln c 0 C o N O N p / z U D o �c,Z02 N NN -�0 rno r uuyy a.G a 3V) / i V / / �C L y J H �- \\--- ---- -- }u,9wasD3 3 V 1 ,OL Q O F-- J Cf) m rK w =- 00 w0N N M ? F- X U O C w d mow$ o CO pN W x N N 1� N V / / �C L y J H �- \\--- ---- -- }u,9wasD3 3 V 1 ,OL Q O F-- J Cf) m rK w =- 00 w0N N M ? F- X U O C w d mow$ o CO pN W x LOT 5, BLOCK 4, SPERSTAD SUBDIVISION NO. 2 DESIGN FACTORS: SYSTEM REQUIREMENTS: Five Bedroom System Deep Trench System Perc. Rate: 16-30 Min./Inch Verify Existing Tanks for Continued Use Application Rate: .6 GPD/SF Replace with 1,500 Gallon Septic Tank B' Dralnfield Rock 5 Bedrooms " 150 GPD/Bedroom = 750 SF Absorption Area 750 SF/.6 GPD/SF/16 SF/LF = 78.13 LF Trench Length THEREFORE: Construct an 80' Long x T Wide x 8' Effective Depth Absorption Trench atthe Location Shown. Flow Line Elevation to be 4' Below Ground. Total Depth to be 12' Below Ground. Verify the Integrity of the Existing Septic Tanks. Replace with 1,500 Gallon Septic Tank if Required. Place Flow Diverter Valve and Connect Existing Absorption Trench for Future Use. Place 4' of Cover Over Tank and 3' Cover Over Trench. 3' TYPICAL DEEP TRENCH SECTION (NO SCALE) zr�•p�• ?l•" NOTE: Grade Area Over Trench to Drain Away. Minimum 6' Separation From Bedrock. :....i ....,9t Minimum 4' Separation From Groundwater.i Minimum 100' Separation From Private Wells in the Area. x4' *IZ , Minimum 100' Separation From Surface Water or Streams..W, No THE STATE °fALASKA GOVERNOR SEAN PARNELI, Michael E. Anderson, P.E. Anderson Engineering P.O. Box 240773 Anchorage, Alaska 99524 Department of Environmental Conservation Division of Water July 17, 2014 Wastewater Discharge Authorization Program 555 Cordova Street Anchorage, Alaska 99501 Main:(907)269-7519 Faz:(907)334-2415 Re: Anchorage —Sperstad No. 2 Subdivision, Block 4, Lot 5 --Conditional Approval to Construct and Establishment of Separation Distance Waivers for the Treatment and Disposal of Domestic Wastewater for this Development having Two Homes on One Property-ADEC Plan Tracking Number 10957 Dear Mr. Anderson, On July 8, 2014 the Department received an engineering plan submittal for waivers and the replacement of the existing wastewater treatment system and the establishment of a new disposal field because of failure of the existing domestic wastewater system. Several waivers were requested as part of the design and a discussion on July 17, 2014 also added one for the existing concrete septic tank to remain and allow flow into the now 1,500 gallon two compartment septic tank. Normally all waivers for a wastewater system are voided, when failure of the wastewater system is identified. Based on an online search of septic system and the files at the local ADEC Office, it does appear that waivers were previously conditionally approved. They were pending an engineering report on the status or condition of the septic tanks for the existing wastewater system on this property. It does not appear that the public water system has the classification statements or forms on file in their Department files. Water samples analyzed for this public water system show that the level for Arsenic is 20.8 ug/1. Treatment is needed as the allowable level is less than 10 ug/1. Provide with the submittal for Classification, your design for treatment to meet Arsenic limits to our Drinking Water personnel for their use. Also provide a copy to this office as well of the method used for the Arsenic treatment with the Records Drawings for the wastewater records. The following waivers were requested as part of this project: From the existing source well to a new septic tank of 1,500 gallon size to be placed no closer than 105 feet in distance this distance is reduced from the required 150 feet. The existing disposal field shall be allowed to remain to recover and for potential future use. The existing separation distance is established per your request at 115 feet from the source well This is reduced from the required 150 feet. The proposed new onsite soil absorption field a deep trench type is designed to be installed but will need a waiver of 109 feet at its closest point to the existing source well. This is a reduction from the required 150 feet. The existing concrete septic tank is adjudged as functional a waiver to 91 feet is established. This is a reduction from the required 150 feet. Based upon the Engineers recommendation and the submitted information waivers for this application have been determined to be protective of public health. Please note that the waivers are conditional and should the wastewater treatment system or any part of the disposal be found to be failing or endangering public health, the waivers are rescinded and corrective engineering will be required. An older septic tank that will not be in service must be properly decommissioned per the Uniform Plumbing Code, Part 722.2. A record drawing plan showing the routing for the piping needs to be provided. The new drainfield designed to be 109 feet from the source well must be a deep trench with an effective depth of 8 feet as it's effective depth and must have four feet of cover material not three feet of cover material. Please be aware of this frost protection requirement and provide the proper depths (show on the record drawings for confirmation). The Department has reviewed the engineering plans submitted for the new treatment system consisting of the old concrete tank and a new 1,500 gallon septic tank and a deep trench type soil absorption system of 80 feet in length with an eight foot effective depth, and per the Wastewater Regulations 18 AAC 72.235 Conditional Approval to Construct the proposed system is hereby issued. A "Certificate of Construction" for the community wastewater system is enclosed. Please use the referenced plan number in correspondence regarding this project. This approval is contingent upon compliance with the following conditions: 1) The engineer must provide a site inspection at the time the soil absorption system is -installed to assure the soil conditions are the same as those used in the design. 2) If the applicant fails to construct, alter, install, or modify the system within two (2) years after the date that the department issues an approval to construct, the approval is void, and plans must be resubmitted, [along with associated fees], for department review and approval. 3) Deviations from approved plans which affect capacity, flow, operation, major design of units, point of discharge, materials of major system components (such as pipe, lagoon liners, etc.), or separation distances, must be approved by DEC in writing prior to their implementation. 4) This approval is contingent upon compliance with the conditions of Wastewater Disposal Regulations, 18 AAC 72.235, Construction Certification. The noted section of the regulations requires that a "Certification of Construction" be completed and submitted to the Department within ninety (90) days of completion of construction. As -built plans or record drawings should indicate any changes or deviations from the approved plans to facilitate final review. A "Certification of Construction" form is enclosed for your use. 5) This approval is contingent upon your receipt of any other state, federal or local authorizations which are required for your project. You are required to obtain all other necessary authorizations before proceeding with your project. 6) You are advised that if this development will require placing fill in wetlands or working in a stream, river, or lake, permits from the U.S. Army Corps of Engineers and the Alaska Department of Natural Resource may be required. The previous required Coastal Projects Questionnaire could be helpful to you to identify other permits and approvals that may be required for your project. This approval does not imply the granting of additional authorizations nor obligate any state, federal or local regulatory body to grant required authorizations. Any person who disagrees with this decision may request an adjudicatory hearing in accordance with 18 AAC 15.195- 18 AAC 15.340 or an informal review by the Division Director in accordance with 18 AAC 15.185. Informal review requests must be delivered to the Division Director, 410 Willoughby Avenue, Suite 303, P.O. Box 111800, Juneau, Alaska 99801, within 15 days of receiving the decision. Guidance information on the informal review process may be found at http://www.dec.state.ak.us/commish/Review- Guidance.htm. Adjudicatory hearings requests must be delivered to the Commissioner of the Department of Environmental Conservation, 410 Willoughby Avenue, Suite 303, P.O. Box 111800, Juneau, Alaska 99801, within 30 days of the decision. If a hearing is not requested within 30 days, the right to appeal is waived. Thank you for your cooperation. If you have any questions please do not hesitate to contact me at 269-7519. Respectfully, William R. Rieth, P.E. Environmental Engineer Enclosure: As stated a STATE OF ALASKA DEPAATMENTOF ENVfRONMENTAL CONSERVATION CONSTRUCTION AND OPERATION CERTIFICATE for DOMESTIC WASTEWATER DISPOSAL S' �(71_D 666vGFi'D1ZLiGE-SP�c25`jTAp J N IBJ I�) 50o GALLON 5EPIPIC APPROVAL TO CONSTRUCT P[ -PT N 0 iT'14 COV DEC PIAN 'PI Plans for the construction or modification of t,JAN E :TW 6 Ce PA /I 7' 4IJ-k �- poria] 8 T5vaDtViSldhl f3j,OGK`F Lair 5 ANK 8Q' D EP TRF_N `EFF.EC?`IVJ 2 �QuA L +T�o 4 ;70077o;70077DS - EP'rq �GICt PJG UKOEf2 105.8-7 _2Efl�Ae_Er✓i>=n7T .v3etaf 50oGALLot7 nrz>=NGN DEPpq rastewater disposal system or r^_oVL.P, located In AM {oleAG Alaska, submitted in accordance with 18 AAC 72,225, A L3oVE .PRA(oJ • las PING. by Mir—PA&• Aprsrl sofj have beets reviewed and are ❑ approved. conditionally approved (see attached.conditions). BY TITLE DATE If construction'has not started within two years of the approval date, this' certificate, is vold and new plans and specifications must be submitted for review and approval before constructton. 3. APPROVED CHANGE ORDERS Change (contract ardarno. ordasodptiva rate renaa) Approved by . • Date At erlWVAL IU UP IZHATE The "APPROVAL TO OPERATt section must be completed and signed by the Department befors'thls system Is made available for. use. Tne construction of the . domestic ,.vastawater disposal systam was completed on (date). Ttia systam is hereby granted interim approval to'operate for 90.days following ths'compl6tion date. 3Y TITLE DATE As -built plans submitted during the interim approval pariod,.or an inspection by the Dacarment, has confirmed the system was constructed according to the approved plans. The system Is hereby granted final approval to operate. ey Mr -_184D NOK N �vrr�NlrUT ARCHORAGE/WESTER€i DISTRICT OFFICE 437 "E' SnEET, SHITE 303 ANCHORAGE, ALASKA 99501 February 19, 19$7 Alaska Environmental Central Servics, Inc. 1200 West 33rd Avenue, Suite B Anchorage, Alaska 99503 274•-2533 SUBWECT. Waiver Horizontal Separation between Well and Septic system, Lot 5, Block 4, Sperstad. Subdivision* Anch6rage € 72144-051) pear Sirs. The Department has reviewed the subject ..,dyer request and hereby conditionally waives the horizontal' separation between the well and septic system to the following: on -lot well to septic tank; 91 ft - Well to drainfield; 11.5 ft. Lot 4, Block 4 Well to drainfield, lotl €t. Lot:.13, Bloc'c. 5 Well to septic tank: 140 its Well to €frainfield; 119 ft.. Lot 14, BlG&- 5 Well to drainfielda 100 ft= (Waiver previously - approved 2/3/87) Conditional Approval Is given ep meeting the f*.110wisg re€Weme tst ' 1. An engineered inspection and report for the on -lot septic tank will be required to determine its structural integrity. 2. 1 An adequacy test will be required is be performed on the septic system. The waiver will not val4d until operational --certification has been given for bobs om-lot eater and sewerage systems from our office.. The waiver also shalt only be valid for the present existing rs bedroom multi -family residence oA the subject lot. ' If YOU have aRY questions, please contact me at our Anchorage/Western District Office. Sincerely r r 41ichael P. Lewis Environmental Engineer t.PLzcaa M m 04 M m 1 • '� Municipality of Anchorage On -Site Water and Wastewater Program OCT (907)343-7904 Certificate of On -Site Systems Approiil Parcel I.D. 018-072-19 Expiration Date: y 5 iS 1. GENERAL INFORMATION Complete legal description Sperstad #2, Block 4, Lot 5 Location (site address) 13000 Back Road Anchorage, AK 99511 Current Property owner(s) H. J. & Beverly Carlson Day phone 240-9605 Mailing address 20130 David Avenue Eagle River, AK 99577 Real Estate Agent Day phone 2. TYPE OF DWELLING: El Single Family (w/wo ADU) ❑ Duplex ❑ Multiple Dwellings (Single Family and/or Duplex) 3. NUMBER OF BEDROOMS: Five 4. TYPE OF WATER SUPPLY: TYPE OF WASTEWATER DISPOSAL: Individual,Well El Individual F-1 Individual W ater Storage ElHolding Tank ❑ Community Class Well ❑ Community ❑ Public Water System ❑ Public Sewer ❑ WaiverNariance request yReceived by: UdO� Date: � G COSA to be releaW a engineer, unless otheruvise requested by the engineer. COSA Fee $ MOM Date of Payment !0`19'1!4 Receipt Number COSA #� 5;7..6- H1i5/i y 070q 16 Waiver Fee $ 2- 11 DateofPayment IIAZS/_//y Receipt Number _ 0 -70(11& - Waiver # -7001GWaiver# 05P14/-1513 5. STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, I verify that my investigation, based on procedures outlined in the Certificate of On -Site Systems Approval Guidelines for this application, shows that the on-site water supply and/or wastewater disposal system is (are) safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is(are) in compliance with all applicable Municipal and State codes, ordinances, and regulations in effect at the time of installation. Name of Firm Anderson Engineering Address P.O. Box 240773 Anchorage, AK 99524 Engineer's Printed Name Michael E. Anderson, P.E. 6. DSD SIGNATURE x Phone 522-7773 10 System #1 Approved for bedrooms ♦ A System #2 Approved for Disapproved Conditional approval for bedrooms _ bedrooms, with the following stipulations: By: r t / Original Certificate Date: 1117,0 The Municipality of Anch ge Development Services Division (DSD) issues Certificates of On -Site Systems Approval (COSA) based only upon the representations given in paragraph 5 by an independent professional civil engineer registered in the State of Alaska. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 7. ATTACHMENTS: COSA Checklist X Nitrate Advisory Septic System Advisory Arsenic Advisory Well Flow Advisory Other COSAblueshm r I- ], c If more than 1 septic system is on the lot COSA Checklist # Of Structure served by this system Certificate of On -Site Systems Approval Checklist Legal Description: Sperstad ##2, Block 4, Lot 5 parcel ID: 018-072-19 A. WELL DATA Well type Private If A, B, or C provide PWSID # Well Log (YIN) Y Date completed 11/15/66 Sanitary seal (YIN) Y Wires properly protected (Y/N) Y Total depth 67 ft, Cased to 62.5 & Casing height (above ground) >12 in. FROM WELL LOO Date of test 11/15/66 Static water level 36.3 ft. Well production 30 g.p.m. WATER SAMPLE RESULTS: AT INSPECTION 7/9/14 38.1 ft. 4.5 g. p_m. Coliform 0 colonies/100 mL Nitrate 1°l/D mg/L Arsenic 20.8 ug/L Date of sample: 6/30/14 Collected by: Anderson Engrg. B. SEPTICIHOLDING TANK DATA Tank Type/Material Septic/Steel Date installed 10/21/82 & 7/17/14 Tank size 9'250!510 gal. Number of Compartrnents 2/1 Cleanouts (Y/N) Y Foundation cleanout (Y/N) Y Depression over tank (YIN) N High water alarm (Y/N) N Date of pumping 7/17114 Pumper Around the Clock Pumping C. ABSORPTION FIELD DATA 7/17/14 .6 GPD/SF Deep Trench Date installed Boil rating (g.p.d./f4� or ftZibdrm) _System type Length 80 ft. Width 3 ft. Gravel below pipe 8 ft. 14-15 1 280 Y N Tota( depth it. Eff. absorption. area � ff Monitoring tube � Depression over field.,,_ Date of adequacy test New Const. Resuhs{PassiFail) For — bedrooms Fluid depth in absorption field before test in. Water added gal. New depth in. Elapsed Time: min, final fluid depth in. Absorption rate >= g.p.d. Any rejuvenation treatment (past 12 me.) (YIN & type) Itil If yes, give date D. LIFT STATION No Add On Manhole -Gravity Flow to Adsorption Trench. Date installed Size in gallons ManholefAocess (Y/N) "Pump on" level at in. "Pump off' level at in. Nigh water alarm level Datum Cycles tested Meets alarm & circuit requirements? E. SEPARATION DISTANCES WELL ON LOT TO: .Septic tank/lift station on lot 91'** Adsorption field on lot >100' Public sewer main N/A Sewer /septic service fine >25' On adjacent lots >100' On adjacent lots >100' Public sewer manhole/cleanout N/A Holding tank NIA Animal containment areas >50' Manurelanimal excrete storage areas >100' SEPTICiHOLDINC TANK ON LOT TO: Building foundation >5' Property fine >5' Absorption field >5' 1 Water main >10 Water service line �' 0 Surface water >100' Wells on adjacent lots >100' ABSORPTION FIELD ON LOT TO: Property line X10' Water Service line >10' Curtain drain None Noted F. COMMENTS Building foundation X10' Surtacewater X100' Wells on adjacent lots >100, Water main N/A Driveway, pantingivehidestorage >10' Absorption Trench Connected with Flow Diverter Valve. **See ADEC Well to Septic Tank Separation Distance Waiver. G. ENGINEER !S CERTIFICATION 1 certify that i have determined through held inspections and review of Municipal records that the above systems are in conformance with MOA COSA,guideiines in effect on this date. Engineer's Printed Name Michael E. Anderson, P.E. Date 10116/14 [AAL E. ANDERSON GE -4381 DRQFFSSO� COSA brown sheet-10-10-12.doc In 3 0 5 PLOT PLAN AS BUILT X SCALE 1" $ 40' GRID SW 2832 Project No. 14-077 Lang & Associates, i n c. 11500 Daryi Avenue, Anchorage, Alaska 99515-3049 Registered Land Surveyors (907) 522-6476 Phone(907) 522-4625 Fax oa�O A kenOlan su cora "! g rvey. J jonathanOlangaurvey.com �',`�!,.•••••• ..,•9s I hereby certify that i have surveyed the following described property: LOT 5, BLOCK 4, SPERSTAD SUBDIVISION #2 (PLAT P-453-B)t} g Anchorage Recording District, Alaska, and that the improvemensituated thereon an ............ within the property lines and do not encroach onto the property adjacent thereto, that no improvements on the properly lying adjacent thereto encroach on the surveyed premises and that there are no roadways, transmission lines or other visible KENNE�1 .LAN i rc .easements on said property except as indicated hereon. '•, ttjsa Pa., Dated this the Z144- Day of Mdlgs e , 2gt$- , of Anchorage, Alaski it is the responsibility of the owner to determine the existence of any easements, covenants, or restriatlons which do not appear on the recorded subdivision plat. Municipality of Anchorage �. Community Development Department _ Development Services Division S . Y 5> ETY On -Site Water and Wastewater Program 4700 Elmore Street P.O. Box 196650 Anchorage, AK 99519-6650 www.muni.org/onsite (907)343-7904 Arsenic Advisory Certificate of On -Site Systems Approval # 141545 A Certificate of On -Site Systems Approval inspection and test of potable water was recently conducted on the well water supply on Block 4, Lot 5 of Sperstad #2 Subdivision. This inspection revealed an arsenic concentration of 20.8 micrograms per liter (ug/L) for the property's well water sample. The Environmental Protection Agency (EPA) has established a maximum contaminant level (MCL) of 10.0 ug/L for public drinking water systems. While private wells are not subject to this regulation, EPA standards are based on existing health information and can therefore be used to gauge the relative quality of water from private wells. Information on arsenic is available from the On -Site Water and Wastewater Program website (=.muni.org/onsite) or at 343-7904. This advisory must be attached to all copies of the subject Certificate of On - Site Systerns Approval. 4'1 Municipality of Anchorage P.O. Box 196650 • 4700 Elmore Road Anchorage, Alaska 99519-6650 • (907) 343-7904 • Fax (907) 343-7997 http:/hyww.m un i.or-/Onsite Development Services Division On -Site Water and Wastewater Program t?1 e ]] t Department **** VARIANCE/WAIVER REVIEW **** Waiver#: OSP141613 COSA#:OSC141645 Permit#: PID#: 018-072-19 Legal Description: Sperstad #2 Block 4 Lot 5 Engineer: Anderson Engineering Applicant: H.J. And Beverly Carlson Your request for a waiver of the required 22 feet horizontal separation from the absorption field to the absorption field has been approved. The approved separation distance is 12.5 feet. This waiver approval applies to the existing absorption field only. Any future upgrade to the on- site wastewater disposal system will require all separation distances be met or another approval from this department. ❑ The affected adjacent property owner(s) have been given a 7 day notice regarding this waiver. ❑ Notarized letter(s) of nonobjection have been received from the owner(s) of the affected adjacent property. ® Adjacent properties are not affected by this waiver. ............................................................................... Waiver is Granted: X Waiver is not Granted: Date: i Approved by: Name of ReViewer ...........................................................7 ............... **** VARIANCEIWAIVER REVIEW **** ANDERSON ENGINEERING P.O. BOX 240773 ANCHORAGE, AK 99524 522-7773 677-7766 FAX November 22, 2014 Municipality of Anchorage Development Services Department On -Site Water and Wastewater Program 4700 South Bragaw Street Anchorage, AK 99519-6650 Subject: Lot 5, Block 4, Sperstad Subdivision #2 Absorption Trench to Absorption Trench Waiver Dear Onsite Services Engineer: The location of the new absorption trench on the subject lot was limited by the location several mature trees. The northern 32' of the new absorption trench was placed between 22' and 12.5' from the existing trench. The existing trench is documented as having an effective depth of 11'. No migration of effluent from the existing trench was noted during excavation on the lot for the septic tank replacement or new test holes. In addition, the soil encountered in the trenches is clean silty sand with gravel (GM) which is very good for the absorption of septic effluent. Most of the effluent absorption will be down with little or no migration of effluent to occur toward the adjacent trenches. A waiver allowing the new trench to remain at its current location seems justified. Sincerely, Michael E. Anderson, P.E. MICHAEL E. ANDERSON No. CE -4381 MUNICIPALITY OF ANCHORAGE ® DEPARTMENT OF HEALTH & ENVIRONMENTAL PROTEC710N 11ENVIRONMENTAL ENGINEERING DIVISION 825 L Street • Anchorage, Alaska 99501 Telephone 264-4720 ON-SITE SEWAGE DISPOSAL SYSTEM AND/OR WELL INSPECTION REPORT y� NAME PHONE ❑NEW - I`-� r' ,' •- (,)- UPGRADE — -� MAILING ADDRESS P. 0. Box 10w 0.106 Arr�v�r �_ Ai< cmni i LEGAL DESCRI?TION -a-a BOCK '4 L_©+ 5. LOCATIOO NO. OF BEDROOMS OE 0IcL r r05s C DISTANCE TO: Well / Absorption area ` Dwelling _ PERMIT NO. �G� P2 Manufacturer Material No. of compartments y Liu. capacity,jn ga ons < ' IF HOMEMADE-- Inside length Width � Liquid depth •.---s" DISTANCE TO: Well Dwelling PERMIT NO. -I O Z Z 0< TManufacturer Z I- Material Liquid capacity in gallons O DISTANCE TO: Well Foundation%i Nearest lot line PERIT NO w y u� ��i J a U No. of lines Length of each lin. i g Total length of line g Trench widtI Distance between Iii s Z W �-a r inches aQ. I.. Top of tile to finish grade i Material beneath tile ! Total effective absorption area p _ 1 / inches Length Width Depth PERMIT NO. Lu Q h_ Type of crib Crib diameter Crib depth Total effective absorption area wa y Well Building foundation Nearest lot line DISTANCE TO: Class Depth Driller Distance to lot line PERMIT NO. r W DISTANCE TO: Building foundation Sewer line Septic tank Absorption area(s) OTHER PIPE MATERIALS C, SOIL TEST RATING dors INSTALLER REMARKS LEGAL Ln APPROVED DATE 72-013 (Rev. 3/78) MUNICIPALITY OF ANCHORAGE Department E Health and Environmenta" )rotection 825 Street, Anchorage, AK. ��501 264-4720 HANDWRITTEN PERMIT Permit �':� I���Z 4ELL_ANZ R—ON-SITE SEWER PERMIT Applicant: ; ;! Mailing Address: Location: Phone Number: Legal Description: L- 'I ;a Lot Size: Type of Soil Absorption System s: Trench: L--' Drainfield: Seepage Bed Holding rank: Maximum Number of Bedrooms: li Soil Rating(sq.ft/br) ! The Required Size of the Soil Absorption System Is: DEPTH ! LENGTH s GRAVEL DEPTH ;L WIDTH The length dimension is the length(in feet) of the trench or drainfield. The depth of a trench or pit is the distance between the surface of the ground and the bottom of the excavation(in feet). There is no set width for trenches. The gravel depth is the minimum depth of gravel between the outfall pipe and the bottom of the excavation(in feet). * * REQUIRED SEPTIC(HOLDING) TANK SIZE GALLONS Permit applicant has the responsibility to inform this department during the installation inspections of any wells adjacent to this property and the number of residences that the well will serve. # # TWO(2) INSPECTIONS ARE REQUIRED # Backfilling of any system without final inspection and approval by'this department will be subject to prosecution. Minimum distance between a well and any on-site sewage disposal system is 100 feet for a private well or 150 to 200 feet from a public well depending upon the type of public well. Minimum distance from a private well to a private sewer line is 25 feet and to a community sewer line is 75 feet. Well logs are required and must be returned to this department within 30 days of the well completion. Other requirements may apply. Specifications and construction diagrams are available to insure proper installation. * * * PERMIT EXPIRES DECEMBER 31, 1 9 u 2 # �" I certify that: (1) I am familiar with the requirements for on-site sewers and wells as set forth by the Municipality of Anchorage. (2) I will install the system in accordance with codes. (3) I understand that the on-site sewer system may require enlargement if the residence is remodeled to include more that_53"bedrooms. Signed. `' Issued by. �f'c pplicantt( Date: SWP/024(1/81) - C'," / . rV SOILS LOG 171, MUNICIPALITY OF ANCHORAGE 4/ DEPARTMENT OF HEALTH AND ENVIRONMENTAL PROTECTION PERCOLATION TEST 825 L. Street, Anchorage, Alaska 99501 264-4720 —/ SOILS LOG -PERCOLATION TEST PERFORMED FOR: \ r� ` C7 t A DATE PERFORMED: / LEGAL DESCRIPTION: h ?'2 � y /3/ DEPTH SLOPE r SITE PLAN FEET) lfi� _�I� I —i �� K"1 1 2 3. 4 5 6 d (Al 7 VC 8 9 11 12 13 41516 14- 15- 16 7- 18- 19- 20- 191 '181920191 COMMENTS PERFORMED BY: 72-008 (6/79) WAS GROUND WATER ENCOUNTERED? IF YES, AT WHAT DEPTH? .1' Reading Date Gross Time Net Time Depth to Water Net Drop is�3 i� dsi cls -3 // �- 7 PERCOLATION RATE _(_'� (minutes/inch) /- �( TEST RUN BETWEEN FT AND 5. S FT S -e le). - l 7 ,lf/ C%_[.a J� i CERTIFIED BY: DATE: r GARB HDI GRe ATER ANCHORAGE AREA a®ROLIt',H HEALTH DEPARTMENT 327 EAGLE ST. ANCHORAGE, ALASKA 99501 279-2511 INSPECTION REPORT ON-SITE SEWAGE DISPOSAL SYSTEM MAILING r. / s "'; I / NAME— + ` s'7 �1. L ) C�/�J ADDRESS/ e. %� PHONE LOCATION _LEGAL DESCRIPTION Zig% �S , h�"h- �I ��1 i�= a' �I/•�7 �! SEPTIC TANK: DISTANCE FROM WE LIQUID CAPACITY—L SEEPAGE SYSTEM NUMBER OF PITS LINING MATERIAL NEAREST LOT LINE d ALLONS. ' NUMBER OF \TERIAL -��fl 4.. �.l COMPARTMENTS 114, INSIDE LENGTH INSIDE WIDTH LIQUID DEPTH_ SEEPAGE PIT: OUTSIDE DIAMETER – OR WIDTH LENGTH, DEPTH? i r DISTANCE FROM WELL BUILDING FOUNDATION TOTAL EFFECTIVE ABSORPTION AREA (WALL AREA) ^� 36 SQ. FT. TILE DRAIN FIELD: DISTA CE FROM WELL FOUNDATION NUMB OF LINES DISTANC BETWEEN LINES ABSORPT N AREA SQ. FT. LEt� OF EACH LINE TOTAL LENGTH L, NEAREST T LINE_ , OF LIN S —, TRENCH IDTH IN. OTAL EJECT VE DEPTH: TOP OF TILE TO FINISH GRADE DEPTH OF FILTER MATERIAL BENEATH TILE: IN. ABOVE TILE— WELL; � DISTANCE FROM � WATER {� TYPE DEPTH A It'r "� l DEPTH 6 BUILDING FOUNDATION. J SAMPLE Y NEAREST ry NEAREST / SEPTIC SEEPAGE </ OTHER LOT LINE SEWER LINE TANK 6 /� , SYSTEM � CESSPOOL SOURCES - DIAGRAM OF SYSTEM DISTANCES: A r 7 o D -f L' APPROVED ATE =�i f . L G ( tG UGg C HEALTH AUi40RITY i E y., D -f L' APPROVED ATE =�i f . L G ( tG UGg C HEALTH AUi40RITY GAAB-HD-2 GREATF ANCHORAGE AREA HEALTH DEPARTMENT 327 Eagle St. Anchorage, Alaska 99501 4)ROUGH Case No. - 279.2511 1 SEWAGE DISPOSAL SYSTEM - APPLICATION & PERMIT i�KI�ra NAME OF APPLICANT I• `J. WLS().1/ `MAILING ADDRESSf+�}�A PHONE 1\103114'36Y RESIDENCE ADDRESS -56'WaW 11"1 LOCATION OF INSTALLATION LEGAL DESCRIPTION–�/(- APPLICATION TO INSTALL: SEPTIC TANK___- _, SEEPAGE PIT DRAIN FIELD , OTHER TO SERVE THE FOLLOWING FACILITY 2- 8-r4061`11 1 FINANCED THROUGH "'e _ TO BE INSTALLED BY PERCOLATION TEST RESULTS_ ANTICIPATED DATE OF COMPLETION /BELOW TO BE FILLED OUT BY HEALTH DEPARTMENT THIS IS I'D SERVE AS PERMIT TO INSTALL A ✓� / �--- AS DESCRIBED BELOW, SIZE OF UNIT TO BE SERVED SEPTIC TANK SIZE Id") TYPE f�W"A SEEPAGE AREA 411AI. DISTANCES: �0-� TYPE Health Authority I4rtify that I am familiar with the requirements of Greater Anchorage Area Borough Ordnance No. 28-68 and that the above described system is in accordance with said code. DATE�jJ L�� 0_ APPLICANTS SIGNATURE �,