HomeMy WebLinkAboutTIMBERLANE PARK #1 BLK 3 LT 9Onsite File Timberlane Park #1 Block 3 Lot 9 #019-152-30 Municipality of Anchorage On-Site Water and Wastewater Section • (907) 343-7904 Page 1 of 3 ON-SITE WASTEWATER INSPECTION REPORT Permit Number: OSP181173 PID Number: 019-152-30 Dwelling: F0 Single Family (SF) ❑ with ADU ❑ Duplex (D) ❑ Two Single Family Project: ❑ New ❑E Upgrade Name Wesley Allen & Jushin Yan Rogers ABSORPTION FIELD ❑ Deep Trench t❑ Wide Trench ❑ Bed ❑ Mound Site Address 12141 Hilltop Dr. Anchorage, AK 99515 ❑ Other Phone Number of Bedrooms Soil Rating Total depth from original grade (907) 844-7005 4 1.2 GPD/SF 9.3 Ft. LEGAL DESCRIPTION Depth to pipe invert from original grade 8.3 Ft. Gravel depth beneath pipe 1.0 Ft. Subdivision Block Lot Timberlane Park #1 3 9 Fill added above original grade 0.0 Ft. Gravel length 27'* Ft. Township Range Section Gravel width 5.0 Ft. Beds: Number of Lines Distance between lines Ft. SEPARATION DISTANCES To Septic Absorption Lift Station Holding Sewer Total absorption area Number of trenches Dist. between trenches From Tank Field Tank Line 153* Ft2 1 Ft. Well >100' >1 00' N/A N/A >25' TANK N Septic ❑ S.T.E.P. ❑ Holding ❑ Other Manufacturer Anchorage Tank Capacity 1250 Gal. Surface Water >1 >100' N/A N/A Material Steel Number of compartments 2 Lot Line >5' >10' N/A N/A NA Foundation >10' >10' N/A N/A LIFT STATION Manufacturer Capacity Gal. Remarks Line between house and tank is insulated. *Existing 67' long, 381 SF trench was extended 27' to accommodate a 4 bedroom home. Alarm location Electrical installed by PIPE MATERIAL House to tank D3034 Tank to drainfield D3034 Installer A+ Home Services. Drainfield D3034 Co/MT D3034 Inspector J. Mlllette BENCH MARK (Assumed elevation) 100 ft Inspection151 8/15/18 8/17/18 n Location and description dates:2 t Bottom of siding. 3rd 4 ON-SITE WATER AND WASTEWATER SECTION APPROVAL Engineer's Stamp Conditional Approval:Date P.��•°""' � � °• ''7 o, �® �49th .....:. ...... .... ....... .... ..'s...,. 0 ....................... v.................... MICHAEL E. ANDERSON �LrCC� 00%- �: 4_,J Ar } n NO. CE-4381 Septic System I Approved Date /,5 .2D2D6QF^.,12/31/19 .............. ,,.•' fir® \ '� • Q �e®p�FESS\� Note: this approval does not include well permit requirements. (Rev 05/02/18) TIMBERLANE PARK #1, BLOCK 3, LOT 9 PERMIT # OSP181173 SERVICE LINE CURB ST\\WATER & KEY B EXISTING CITY \\ SEPTIC TANK WATER MAIN GE ENGINEERING 49th° '.MICHAEL E. ANDERSON .• 4 No CE -4381 ' ..4/20 ......vi IL ,••�F �i TIMBERLANE PARK SV2 2CO O B LOT 9 ° O C01 MT1 MT2 02• TP2o t ALTERNATE SITE TP1 PLAN AS -BUILT PID # 019-152-30 20' UTILITY EASMENTS LOT 10 MUNICIPAL WATER SYSTEM NEW 27' LONG x 5' WIDE x 1' EFFECTIVE DEPTH EXTENSION TO EXISTING ABSORPTION TRENCH EXISTING 67' LONG ABSORPTION TRENCH A B C FCO 7.8 47.5 - SV1 34.5 21.1 - SV2 42.3 16.0 - 2CO 44.7 15.3 - COI 90.6 - 26.1 MTI 90.5 - 25.8 CO2 117.2 - 52.7 MT2 115.9 - 51.6 0 50 100 FEET 111=50' LEGEND CO - CLEANOUT 2CO - DOUBLE CLEANOUT FCO - FOUNDATION CLEANOUT MT - MONITORING TUBE SV - SEPTIC VENT TH - TEST HOLE LEGAL DESCRIPTION: PERFORMED FOR: DATE: PARCEL ID#: SOILS LOG AND PERCOLATION TEST TECHNICIAN: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 DEPTH (feet) PROJECT No.: TEST HOLE 1 SLOPE SLOPE SITE PLAN See Site Plan DATE READING GROSS TIME(minutes)NET TIME(minutes) DEPTH toWATER NET DROP TEST HOLE PRESOAKED PRIOR TO TESTING: PERC. HOLE DIA. (INCHES)PERCOLATION RATE: (MIN/INCH) TEST RUN BETWEEN: FT. and FT. COMMENTS: (inches)(inches) TIMBERLANE PARK #1, BLOCK 3, LOT 9 7/11/18 J. Millette Development Services Department 4700 Elmore Road Anchorage, AK 99519-6650 Municipality of Anchorage DATE OF MONITORING: WAS GROUND WATER ENCOUNTERED? DEPTH OF WATER AFTER MONITORING: IF YES @ WHAT DEPTH? NO - NONE 1.8 6 4.5 5.5 019-152-30 WESLEY ROGERS Professional Engineers Stamp: 14:18/14:26 7/13/18 1 2 3 4 5 6 10 10 10 4" / 10" N/A 5 12 16" 5 9 16" 14:28/14:37 14:39/14:49 14:51/15:01 15:03/15:13 15:15/15:25 1' OB SANDY SILTY GRAVEL 7/19/18 GM 10 10 10 4" / 10" 4" / 9 13 16" 4" / 9 12 16" 4" / 9 10 16" 4" / 9 9 16" 6 6 5 13 16" 5 10 16" 1/14/20 as PO BOX 240773 ANCHORAGE, AK 99524 522-7773 677-7766 (FAX) August 18, 2018 Municipality of Anchorage Development Services Dept- On -Site Water & Wastewater Program 4700 Elmore Rd Anchorage, AK 99507 Subject: Timberlane Subdivision 91, Block 3, Lot 9 Septic System Design and Permit Application Dear On -Site Services Engineer: The septic system on the subject lot was installed on Friday, August 17, 2018. A requirement of Change Order No. 2 to the initial permit was to provide verification that no impervious soil layers were found at least 15' below the surface. The test hole provided for the absorption trench extension extended to 14' below the surface. Our study of the surrounding lots indicated that all subsurface soils in the area are consistent with silty gravel found to all depths on the lots studied. Test holes were found to depths in excess of 14' on several lots including Lot 11, Block 3, Lot 12A, Block 3, Lot 12B, Block 3 and to 18' on Lot 7A, Block 4 which is found immediately east of the subject lot across Hilltop Lane. No impermeable soil layers were found on any of the lots studied. We are therefore confident no impermeable layer exists between 14' and 15' on the subject lot. Sincerely, WI'/"z ez� Michael E. Anderson, P.E. O F' 4gcS'l�� ' 49 zH .. Michael E. Anderson %4 81-E •.4!,Z7i 1�r1:�p�'OFE5S10N��'�,.•► Lot 7 5.0'x10.0' DECK EAST 155.00'(R) OD ai _ N — 2.0'x15.8 29.7' CANT 244' �N \ GRAVEL A ro o 2.0'x20.8'- m N o N 2.0'x42. CANT - CANT / u z O u Lot 10 _ n j _nRP EWP 24.4' 29.3 ;. _ WATER SERVICE \\CPANT \ p-0 A' N 53'45'W Lot 6 20' UTILITY EASEMENTS =GRAVEL 5.0'x10.0' DECK 12.5'x16.2' SHED M \ �N o Lot 10 Lot 9 27,102 s.f. (C) PIPES NOTES \ 1) LOT IS SERVED BY A COMMUNITY WATER SERVICE. 2) ERRORS WERE FOUND ON THE PLAT (No. P -209A) AND COMPUTED DISTANCES ARE SHOWN HEREON. 3) DUE TO SNOW & ICE COVER; THE LOCATION OF THE DRIVEWAY IS \ APPROXIMATE. 28.62'(C) \ \ 28.47'(R) \ PLOT PLAN AS BUILT _X_ SCALE --I—" —" _= 50__ GRID SW 2729 __ Project No. 11500 Daryl Avenue, Anchorage, Alaska 99515-3049 Lang & Associates in C. , (907) 522-6476 Phone ooaOppp (907) 522-4625 Fax o� Professional Land Surveyors kenolongsurvey.com jonothanOlongsurvey.com ooP ._S QO I hereby certify that I have surveyed the following described property: LOT 9, BLOCK 3, TIMBERLANE PARK — No. 1 (PLAT No. P -209A) Anchorage Recording District, Alaska, and that the Improvements situated thereon are within the property lines and do not encroach onto the property adjacent thereto, that no improvements on the property lying adjacent thereto encroach on the surveyed premises and that there are no roadways, transmission lines or other visible easements on said property except as indicated hereon. Dated this the __�A4 _ Day of __ — __--, — _, at Anchorage, Alaska It is the responsibility of the owner to determine the existence of any easements, covenants, or restrictions which do not appear on the recorded subdivision plat. KENN H' {f-C� o� .,. I�l4IZo2a � .LS -5202.•' SSG 1Q100FfSSIONA1- Ml • g r7-18 MUNICIPALITY OF ANCHORAGE On -Site Water & Wastewater Program t PO Box 196650 4700 Elmore Road �- i Anchorage, Alaska 99519-6650 Phone: (907) 343-7904 Fax: (907) 343-7997 + http://www.muni.org/onsite i r 1)clrirtmcnt On -Site Wastewater Disposal System Permit Permit Number: OSP181173 Effective Date: 7/31/2018 Work Type: Septic Upgrade Expiration Date: 7/31/2019 Tax Code Number: 01915230000 Site Legal Address: TIMBERLANE PARK #1 BLK 3 LT 9 G:2729 Site Mailing Address: 12141 HILLTOP DR, Anchorage Owner: ROGERS WESLEY ALLEN & Lot Size in Sq Ft: 29185 Design Engineer: FORGE ENGINEERING Total Bedrooms: 4 This permit is for the construction of: Q Disposal Field Q Septic Tank ❑ Holding Tank ❑ Privy ❑ Private Well ❑ Water Storage All construction shall be in accordance with: 1. The attached approved design. 2. All requirements specified in Anchorage Municipal code Chapters 15.55 and 15.65 and the State of Alaska Wastewater Disposal Regulations (18AAC72) and Drinking Water Regulations (18AAC80) 3. The wastewater code requires inspections during the installation. The engineer shall notify the Development Services Department per AMC 15.65. Provide notification by calling (907) 343-7904 (24/7). 4. From October 15 to April 15, a subsurface soil absorption system under construction during freezing weather shall be either: a. Opened and Closed on the same day, or b. Covered, sealed, and heated to prevent freezing Special Provisions: The Engineer needs to do an additional test hole, minimum of 15' deep, prior to the construction of the septic field. Construction may proceed at your own risk before the 7 day water monitoring is complete. Please submit stamped and signed results with the As -built Inspection Report. If the results require a design change, construction of the system will stop pending On -Site review and approval. Received By: Issued 10,�S NO Date: U Date: v ‘'7.c,3 6 7 8 9 707 MUNICIPALITY OF ANCHORAG ; w 5. 0022018 ,: � j:: Community Development Department 4gb...., Phon �e -343- Development Services Division `-� Fa ' • r On-Site Water & Wastewater Program ON-SITE SEWER/WELL PERMIT APPLICATION Parcel I.D. 019-152-30 Property owner(s) Wesley Allen & Jushin Yan Rogers Day phone (907) 844-7005 Mailing address 12141 Hilltop Dr. Anchorage, AK 99515 Site address Same Legal description (Sub'd., Block & Lot) Timberlane Park #1 Block 3 Lot 9 Legal description (Township, Range & Section) Lot Size 29,185 Sq. Ft. Number of Bedrooms `t APPLICATION IS FOR: APPLICATION IS AN: TYPE OF DWELLING: (® all that apply) Absorption Field X Initial Single Family (SF) U (w/wo ADU) Septic Tank (XI Upgrade ❑X Duplex (D) 7 Holding Tank I I Renewal I IMultiple Dwellings I Privy ❑ (SF and/or D) Private Well Water Storage n THIS APPLICATION INCLUDES A VARIANCE /WAIVER REQUEST FOR: Distance: I certify that the above information is correct. I further certify that this is in accordance with applicable Municipal Codes. 714.,-.LJ Lati_— / - (Signature of property owner or authorized agent) Permit/Rush Fees: ✓(1)1q'OlD Waiver Fees: Date of Payment: —113/W1 Y Date of Payment: Receipt Number:CC000(h50 Receipt Number: Permit No. OJi'(0 11 !3 Waiver No. Permit App_'- :• ::..,c NS *,) GE ENGINEERING PO BOX 240773 ANCHORAGE,AK 99524 522-7773 677-7766(FAX) August 7, 2018 Municipality of Anchorage Development Services Dept- On-Site Water& Wastewater Program 4700 Elmore Rd Anchorage,AK 99507 Subject: Timberlane Subdivision #1, Block 3, Lot 9 Septic System Design and Permit Application Dear On-Site Services Engineer: The septic system on the subject lot has failed and must be replaced. We are submitting this design permit application for the construction of a new 4-bedroom septic system. The attached site plan identifies the location of the home as well as the proposed and existing septic location. No conflicts exist between this proposed system and any other well or septic system, whether on this lot or adjacent lots. The ground surface on the lot is relatively flat. There are no slopes greater than 25% within 50 feet downslope of the proposed site. Storm water drainage will not impact this septic system. The new trench will be constructed parallel to the slope as much as possible. All adjacent properties are on the municipal water system. The new system will be a minimum of 100' from all wells and surface water,and more than 5' away from the septic tank. We request a provision to the permit requiring a new test hole and percolation test be completed prior to construction. Results to be submitted with the inspection report. Please refer to the attached test hole log and plan and profile sheets for the septic design. If this design is followed,there will be no adverse impacts to adjacent properties. Sincerely, OAF AC\q�\1, *. 49 Michael E. Anderson, P.E. Y441-44t 1 .I` '. Michael E.Anderson Attachments (r��F�sr,. 43381 v\`t, ,`,i_PROFEssI0,,,, \ ALTERNATE SITE: 77LON6xA WIDE vZEpFECTNEDEPTH PLACE CLEAN MONITOR TUBE 20'UTILITY EASMENTS EXPOSE TQCONFIRM INSULATION |NPARKING AREA. AMINIMUM Op4^ orINSULATION ABOVE PIPE |G REQUIRED. EXISTING TANK. DECOMMISSION IN ACCORDANCE WITH MOA CODE. UNDOCUMENTED TRENCH. NEW m7LOwGx5'VNDEx1' EFFECTIVE DEPTH EXTENSION TOEXISTING ABSORPTION TRENCH EXISTING 67LOmGABSORPTION \ NOTE NUSLOPES >25%WITHIN 50'ORSURFACE WATER WITHIN 1O0'OFTHE PROPOSED SEPTIC SYSTEM too TH ALL WELLS ONSURROUNDING LOTS WITH IMPACTS TOTHIS 49 ........—~~~~� " PROPERTY ARE SHOWN. NOCONFLICTS WITH WELLS ORSEPTIC SYSTEMS. .4 Michael =Anderson U 50 100 n FEB LOT 10 WiViVill WIN 1 1.06 LEGEND CO'CLEANOUT 2CO'DOUBLE CLEANOUT FCO ' FOUNDATION CLB0 MT'MONITORING TUBE SV-SEPT|CVENT TH - TEST HOLE 99. We W.• SYSTEM REQUIREMENTS: 5' WIDE TRENCH SYSTEM 1,250 -GAL SEPTIC TANK 600 GPD / 1.2 GPD/SF / V DEEP * 0.87 REDUCTION = 87 LF TRENCH REQUIRED (87 LF SPECIFIED) EXISTING TRENCH 67' LONG - 20' EXTENSION REQUIRED -11 i 5' (NO SCALE) NOTES: 1. GRADE AREA OVER TRENCH TO DRAIN AWAY 2. PROVIDE 3' OF COVER OVER TRENCHES AND 4' OVER SEPTIC TANK, OR 2' WITH 2" OF INSULATION 3. CHECK GROUNDWATER AT TIME OF CONSTRUCTION. IF LEVEL IS HIGHER THAN PREVIOUSLY OBSERVED, CALL ENGINEER IMMEDIATELY • i •i C N G I N E E R I N 4 • o \ 1 Lot 7 _ � Lot 6 \,,,. .\—\ I I N 90'00'00"E 155.00' (R&H) _ — _ -03 N \ . . .. .' / 2.0'x15.8' •. N • CANT- 29.7 24.4' 20' UTILITY \ •• GR•AVEL:;• m N 2•C' CANT EASEMENTS 4i '4\ 2.0'x20.8'..: :•.MMN o N �— CANT ' '.v wzou ASPN4-1,, i m ' -RP\-' 24.4• 29.3' 6p 2 2.0'x4.3' '.. GRAVEL::. 5.0'x10.0' DECK WATER SERVICE \ CANT Z .. '')`' .r-_ 12.5'x16.2' SHED O oo SEPTIC ai ' •• PIPES Q ✓ Lot 10 74 LALO G W o \ '...1 cr‘ VILot 9 0 J 27,102 s.f. (C) o \ cn N NOTE: LOT IS SERVED BY A N COMMUNITY WATER SERVICE N 53'45'00"W (R) N N 28.62' (C) N N PLOT PLAN AS BUILT X SCALE 1" = 50' GRID _ SW 2729Project No. 18-164/A1 _ 11500 Daryl Avenue, Anchorage, Alaska 99515-3049 Lang & Associates , inc . (907) 522-6476 Phone 0000OpO� (907) 522-4625 Fax . Professional Land Surveyors kenOlangsurvey.com vl OF ,4 ( N JonathanOlangsurvey.com p'�C�.• ,'Qs�4 I herebycertifythat I have surveyed the followingdescribed property: 6:,;;_.. o�P. ��\ '.3 LOT 9, BLOCK 3, TIMBERLANE PARK — No. 1 (PLAT No. P-209A) if*:' 49TH i� . *0(0 Anchorage Recording District, Alaska, and that the improvements situated thereon are within the property lines and do not encroach onto the property adjacent thereto, that r i D no Improvements on the property lying adjacent thereto encroach on the surveyed • •`KENNETH G LAG �0 premises and that there are no roadways, transmission lines or other visible 0>c' . oQ easements on said property except as indicated hereon. 0I\ ... 513t (% ��- •1'F •. 5-5202.••• gJpO Dated this the ok Day of I'`11d , ' y; , at Anchorage, Alaska N �,o ••••••" . 00 40o\\ SSIONA�-o It is the responsibility of the owner to determine the existence of any easements, '4p000�� covenants, or restrictions which do not appear on the recorded subdivision plat. AECC963 Municipality of Anchorage Page _ DEPARTMENT OF HEALTH AND HUMAN SERVICES ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 · Anchorage, Alaska 99519-6650 · Telephone: 343-4744 On-Site Wastewater DisposalCSystem and/or Well InspectiOn Report Permit Number: ~'~ct~2'~ PIDNumber: D 191 Name: ~US~t~ %~ /~LGY ~E~ Wastewater System: ~New ~ Upgrade Address:~ ~ ~E~ ~C~, A~ ~O~ ABSORPTION FIELD Phone: ~--~0~ lNo. of Be~oms: ~ Deep Trench ~Trenoh BBed DMound BOther LEGAL DESCRIPTION so..~...: Total ~pt~ f rom origi,al grade: ~ · ~ GPD/Sq. Ft. Township: IRa,ge: ~ Seclion: Fill added above original grade: Gravel lenglh: ~~ U New~TE~)~ Upgra iravelwidth: ~.O Fb [ ~ Ft, ~ ~ Pipe material: Total Depth' Cesed To: Total absorption area: Classification (Prwa Driller: ~ ~ Stalic W~ter Level: Installer: ~ Dale installed: ~EPARATION DISTANCES ~Septic U Holding ~ S,T.E.P, TO Seplic Absorplion Lifl Holding ~ublic/Privale Manufaclurer: Capacity in gallons: From Tank Field Station Tank Sewer Lines ~~ ~ [~ I ~ Material: Number of Compartments: Surface Lot clurer: Curtain Drain ¢¢* ¢/~ ¢/~ ~/* ~/* ~~lrical Inspeclions perlormed~ Remarks: BENCH MARK Location and Description: ENGINEER'S SEAL Inspections performed by:.~ ~& Dates: 1st 4-Z5- ~ .~.~ ~'4~'~ ~z /~, Permit No. Municipality of Anchorage Department of Health and Human Services ENVIRONMENTAL SERVICES DMSION Page. 1 of 2 W.O. 95060 Date 4-27-94 P.O. Box?196650' Anchorage, Al( 99519-6650' Tel: 343-4744 On-Site Wastewater Disposal System/Well Inspection Report Legal Description: LOT 9 BLOCK 3 TIMBE12LANE PARK SUB. ADD'N #1 PID No. APPROX HOUSE ~/ LOCATION / / 2' Ii CLEANOUT FROM ' ~ \ /I I ! TANK INL \ I\ \ 1000 GALLON SEPTIC TANK W/ 2" RIGID INSULATION INVERT TANK OUTLET \ INVERT - \k \ TBM ELEV = 93.4 /11 \ I ~1// CLEANOUT @ TRENCH INLET INVERT = ~ ¢ PERF HDPE @ 0.0% SLOPE (TYP) ¢ MONITOR TUBE CLEANOUT @ END OF TRENCH INVERT =..88r6~ fferr~it No. Municipality of Anchorage Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650 * Anchorage, AK 99519-6650' Tel: 343-4744 On-Site Legal Descripfion: LOT 9 BLOCK 3 TIMBERLINE SUB. ADD'N #1 Wastewater Disposal Page 2 of 2 W.O. 93060 Dale 4-27-94 System/Well Inspection Report PID No. 4" ¢ MONITORING TUBE W/ WATERTIGHT CAP EXISTING GRADE GEOTEXTILE FABRIC 4" PERF. NDPE INVERT = BOTTOM OF TRENCH ELEV = ~ TYPICAL TRENCH SECTION SCALE: 1" = 2' SEWER ROCK PER MUNICIPAL SPECS. MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH AND HUMAN SERVICES P.O. BOX 196650, 825 "L" STREET, ROOM 502 ANCHORAGE, ALASKA 99519-6650 PAGE 1 OF ON-SITE WASTEWATER DISPOSAL SYSTEM PERMIT PERMIT NUMBER:SW930238 DESIGN ENGINEER:DEE HIGH ENGINEERING OWNER NAME:YAN JUSHIN S OWNER ADDRESS:P.O. BOX 90719 ANCHORAGE, AK 99509 DATE ISSUED: 7/20/93 EXPIRATION DATE: 7/20/94 PARCEL ID:01915230 LEGAL DESCRIPTION: TIMBERLANE PARK #1 BLK 9 3 LT LOT SIZE: 29185 (SQ. FT.) NUMBER OF BEDROOMS: 3 THIS PERMIT: 3 THIS PERMIT IS FOR THE CONTRUCTION OF: DISPOSAL FIELD /SEPTIC TANK SYSTEM ALI. CONSTRUCTION MUST BE IN ACCORDANCE WITH: 1. THE ATTACHED APPROVED DESIGN. 2. ALL REQUIREMENTS SPECIFIED IN ANCHORAGE MUNICIPAL CODE CHAPTERS 15.55 AND 15.65 AND THE STATE OF ALASKA WASTEWATER DISPOSAL REGULATIONS (18AAC72) AND DRINKING WATER REGULATIONS (18AAC80). 3. THE ENGINEER MUST NOTIFY DHHS AT LEAST 2 HOURS PRIOR TO EACH INSPECTION. PROVIDE NOTIFICATION BY CALLING 343-4329 OR 343-4681 AFTER BUSINESS HOURS 4. FROM OCTOBER 15 TO APRIL 15 A SUBSURFACE SOIL ABSORPTION SYSTEM UNDER CONSTRUCTION DURING FREEZING WEATHER MUST BE EITHER: A. OPENED AND CLOSED ON THE SAME DAY B. COVERED, SEALED AND HEATED TO PREVENT FREEZING 5. THE FOLLOWING SPECIAL PROVISIONS. 1 SPECIAL PROVISIONS: DATE: DATE: Permit :No. ; Municipality of Anchorage Depar[ment of Health and Human Services ENVIRONMENTAL SERVICES DIVISION Page J of ,~ W.O. 95060 Date 7-6-95 P.O. Box 196650 · Anchorage, AK 99519-6650 ® Tel: 343-4?44 On-Site Wastewater Disposal System/Well Inspection Legal Description: LOT 9 BLOCK 3 TIMBERLINE SUB. ADD'N #1 PlO No. Report SITE NARRATIVE Lot 9, Block 3, Timbeflane Subdivision Addition gl is bordered by two lots. The lot is undeveloped, and the septic system design is based on the proposed location of a 3 bedroom house. The lots in the area are on city water with on-site septic systems. WELLS: The adjacent lots are serviced by city water. Since no wells are present, separation between the proposed septic system and wells will not be an issue. WASTEWATER SYSTEMS: Both of the bordering lots have septic systems which are well beyond the required separation distance. The proposed system will have no impact on these systems. DRAINAGE: All fills will be sloped to drain in the direction of natural drainage. The system will receive topsoil and seeding to prevent erosion. Permif No. On-Site Legal Municipality of Anchorage DeparLment of Health and Human Services ENVIRONMENTAL SERVICES DIVISION P.O. Box 196660 · Anchorage, AK 99519-6660 ° Tel: 343-4744 Wastewater Disposal System/Well Inspection Description: LOT 9 BLOCK 3 TIMBEI2LANE PAI~K SUB. ADD'N #1 PI0 No. Page ~ of W.O. 9,5060 Dafe 7-19-95 Report 20' UTILITY EASEMENT\ \ \ \ NOTE: CITY WATER SYSTEM 10' PROPERTY LINE SETBACK (TYP) PROPOSED TRENCH RESERVE \ 30' TEST PIT RADIUS~ \~ XX~\ "~"'\\XX~ .CHOUSE ORNER EXISTING SEPTIC SYSTEM SCALE: I" = 50' Permlf..No. Municipality of Anchorage Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION Page'~of ~ W.O. 95060 Dale 7-6-95 P.O. Box 196650 * Anchorage, AK 99519-6650' Tel: 343-4744 On-Site Wastcwater Disposal System/Well Inspection Legal Description: LOT 9 ]3LOCK 3 TIMBERLANE SUB. ADD'N #1 PID No. Report SYSTEM DESIGN CALCULATIONS 1. NO. BEDROOMS 2. USE 5' WIDE TRENCH SYSTEM 5. ABSORBTION AREA = (# BEDROOMS)(150 GPD/BR) TRENCH APPLICATION RATE = (5)(150) = ,575 SF 1.2 * 4. TRENCH BOTTOM AREA = (5' WlDTH)(LENGTH) = 575 SF IF GRAVEL DEPTH = 6" BELOW PERF PIPE THEN LENGTH OF TRENCH = 75.0' IF GRAVEL DEPTH = 1' BELOW PERF PiPE THEN LENGTH = 87% OF STANDARD TRENCH LENGTH (SEE MANUAL OF SEPTIC-TANK PRACTICE) LENGTH = (.87)(75.0') = 65.5' PERCOLATION RATE PIT & TRENCH APPLICATION RATE MIN/INCH CPD/SF 0-1 NOT SUITABLE 1-5 1.2 I 6-15 0.8 16-50 0.6 CREATER THAN 60 NOT SUITABLE FILTER LAYER 1.0 MOUND & BED APPLICATION RATE BPD/SF NOT SUITABLE 0.8 0.5 0.4 0..3 NOT SUITABLE .7 · RermH'No. Municipality of Anchorage Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION P.O. Box?196650, Anchorage, AK 99519-6650' Tel: 343-4744 On-Site Wastewater Disposal System/Well Inspection Legol Description: LOT 9 BLOCK 3 TIMBERLANE PARK SUB. ADD'N #1 PID No. Page z~r of ~ W.O. 93060 Dale 7-6-93 Report 2 LF @ 2.0% MIN PROPOSED HOUSE FF-- 92.0' TANK INLET \ INVERT = 89.15 TANK OUTLET INVERT = 8g.05 2 TBM ELEV = 95.4 CLEANOUT 2' FROM FACE OF PROPOSED BUILDING INVERT = 90.04 0 O) GALLON SEPTIC TANK W/ 2" RIGID INSULATION SEE NOTES 2, 12, 18 & 19 CLEANOUT @ TRENCH INLET INVERT = 88.0 ¢ PERF PVC @ 0.0% SLOPE (TYP) /I 4" ¢ MONITOR TUBE CLEANOUT @ END OF TRENCH INVERT - 88.0 / / / SCALE: 1" = 50' Permit. No. On-Site Municipality of Anchorage Department of Health and Human Services ENVIRONMENTAL SERVICES DIVISION P.O. Box 196650' Anchorage, AK 99519-6650' Teh 343-4744 Wastewater Disposal System/Well Inspection Legal Description: Page ~' Of '~ W.O. 95060 Dale 7-6-95 LOT 9 BLOCK 3 TIMBERLANE SUB. ADD'N #1 Report PID No. 4" ¢ MONITORING TUBE W/ WATERTIGHT CAP 4,5' .5' 1.0' BOTTOM OF TRENCH ELEV = 87.0 5.0' .~ ~: ~- EXISTING GRADE MATCH ~H ~XISTING WALLS AS / REQUIRED TO MEET ALL / LOCAL, STATE AND ~~/ F~D~ ~GULATIONS. GEOTEXTILE FABRIC SEE NOTE 15 4" P£RF. PVC INVERT = SEE NOTE 11 TYPICAL TRENCH SECTION SCALE: 1" = 2' SEWER ROCK PER MUNICIPAL SPECS. SEE NOTE 10 Permit No. Legal Description: LOT 9 BLOCK 3 TIMBERLANE SUB. ADD'N /fl Poge (~ of ~ W.O. 93060 Date 7-6-93 NOTES: ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH CHAPTER 15.65. WASTEWATER DISPOSAL REGULATIONS OF THE MUNICIPAL CODE AS CURRENTLY AMENDED. 2 INSTALL NEW 1000 GAL SEPTIC TANK AS SHOWN ON THE DRAWINGS. RECORD INLET AND OUTLET ELEVATIONS OF THE TANK. TANK SHALL BE PLACED ON UNDISTURBED NATIVE SOIL. SITE TOPOGRAPHIC SURVEY CONDUCTED BY DHI ON 6-24-93. EXISTING STRUCTURES, WELLS, SEPTIC SYSTEMS OBSERVED WITHIN 200 FT. OF PROPOSED SYSTEM SITE ARE SHOWN ON DESIGN DRAWINGS. ANY DEVIATION FROM THE DESIGN MUST BE AUTHORIZED BY THE ENGINEER PRIOR TO ITS INCORPORATION INTO THE SYSTEM. CONTRACTOR TO LOCATE ALL UNDERGROUND UTILITIES, PROPERTY LINES, EXISTING WELLS, WATER WAYS, SURFACE AND SUBSURFACE DRAINAGE FACILITIES, LAKES, PONDS, AND OTHER FACILITIES REQUIRING SEPARATION DISTANCES FROM THE PROPOSED SEPTIC SYSTEM. CONTRACTOR TO STAKE PROPOSED SYSTEM PRIOR TO CONSTRUCTION. NOTIFY THE ENGINEER OF ANY OBSERVED CONFLICTS PRIOR TO CONSTRUCTION. CONTRACTOR TO NOTIFY THE ENGINEER AND DHHS 24 HOURS PRIOR TO COMMENCING WITH CONSTRUCTION. A MINIMUM OF THREE INSPECTIONS ARE REQUIRED. THE FIRST INSPECTION SHALL BE OF THE SUBGRADE PRIOR TO PLACING THE SEWER ROCK, THE SECOND INSPECTION SHALL BE AFTER THE PLACEMENT OF GRAVEL, DISTRIBUTION PIPING, STANDPIPES, TANK, AND OTHER COMPONENTS AS SPECIFIED. THE THIRD INSPECTION SHALL BE AFTER THE WORK IS COMPLETED, CONTRACTOR SHALL DELIVER TO THE ENGINEER A SET OF RED LINED, AS--BUILT DRAWINGS SHOWING ALL DATA AS SPECIFIED IN SEC. 15.65.F.2, 5, 4, 5, 6 OF MUNICIPAL WASTEWATER DISPOSAL CODE WITHIN FIVE DAYS OF THE FINAL INSPECTION. INVERTS AND SWING fiE LOCATES SHALL BE TO THE NEAREST TENTH OF A FOOT. THESE AS-BUILTS SHALL BE USED BY THE ENGINEER TO PREPARE AND SUBMIT RECORD DRAWING TO DHHS. ALL EXCAVATION DEPTHS ARE ADVISORY. THEY ARE TO BE VERIFIED AND MAY BE MODIFIED BY THE ENGINEER IF ACTUAL FIELD CONDITIONS VARY FROM THOSE USED TO PREPARE THE DESIGN. EXCAVATE THE ABSORPTION FIELD. BOTTOM OF EXCAVATION SHALL BE LEVEL AND SCARIFIED. RECORD ELEVATIONS AT BEGINNING, MIDDLE, AND END OF TRENCH BOTTOM. CONSTRUCTION EQUIPMENT SHALL NOT OPERATE ON THE FLOOR OF THE EXCAVATION. ANY MATERIAL COMPACTED BY THE OPERATION OF THE CONSTRUCTION EQUIPMENT SHALL BE REMOVED AND REPLACED WITH UNCOMPACTED MATERIAL. 10 PLACE THE SEWER ROCK TO THE SPECIFIED DEPTHS. DO NOT CONTAMINATE SEWER ROCK WITH NATIVE MATERIAL OR SPOILS FROM EXCAVATION. LEVEL ROCK SURFACE TO -+ ~" PRIOR TO INSTALLING THE PERFORATED PIPE. ALL PIPE SHALL BE PVC CONFORMING TO ASTM D3034 OR ENGINEER-APPROVED EQUAL. MINIMUM SOIL COVER SHALL BE 3 FT (OR 2' SOIL AND 1" RIGID INSULATION BOARD - SEE NOTE 12) 12 ALL INSULATION BOARD SHALL BE 2" THICK DOW H1-55 INSULBOARD OR ENGINEER-APPROVED EQUAL. CENTER INSULBOARD WIDTH OVER PIPES, TRENCH, AND SEPTIC TANK. 13 GEOTEXTILE SHALL BE MIRAFI 140S OR ENGINEER-APPROVED EQUAL. LAP ALL JOINTS 2' MIN. 14 COVER THE DISTRIBUTION PIPE WITH MIN 2" SEWER ROCK, AND COVER WITH GEOTEXTILE BEFORE PLACING INSULATION AND BACKFILL. 15 MATERIAL USED AS FILL SHALL BE CLEAN AND FREE OF ORGANICS, TRASH AND CONSTRUCTION DEBRIS. 16 SLOPE ALL FILL MATERIAL TO DRAIN AT 2% MIN. SLOPE, AND .5:1 MAX SLOPE, AND IN SUCH A MANNER THAT PONDING AT OR NEAR THE DRAIN FIELD DOES NOT OCCUR. THE FILL SHALL BE LEFT AT 6" HIGHER THAN SHOWN TO ALLOW FOR SETTLEMENT. SEED SURFACE AFTER COMPLETING INSTALLATION AS PER MUNICIPAL SPECS. 17 RECORD THE FINISH GROUND ELEVATION OVER TOP OF TRENCH. 18 INSTALL SEPTIC TANK 46.5' FROM FACE OF PROPOSED BUILDING TO ALLOW FOR POSSIBLE FUTURE 40' ADDITION. 19 COORDINATE LOCATION OF TANK AND LINE FROM PROPOSED HOUSE TO TRENCH WITH ACTUAL HOUSE LOCATION. PERFORMED FOR: L-c~ LEGAL DESCRIPTION: Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street. Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST DATE PERFORE Township, Range, Section; 1 2 3 4 5 6 7 8 9 .... - 10 11 t2 13 14 15 16 17 18 19 20 COMMENTS SLOPE WASGROUND WATER ENCOUNTERED? S IF YES, AT WHAT DEPTH? P E Depth lo Waler After Me~ilering? Nck~- SITE PLAN I- N $ t T'~ Gross Net Depth to Net Reading Date Time Time Water Drop PERCOLATION RATE __ TEST RUN BETWEEN ~ (minutes/inch) PERC HOLE DIAMETER '~'~ FT AND ~' ~ FT PERFORMED BY: ~---------",~' //~J?*~"~,Y*/~ ~ I CERTIFY THAT THIS TEST WAS PERFORMED IN ACCOROANCE WITH ALL STATE AND MUNICIPAL GUIDELIN£S IN ETFEOT ON ¢~f'~ DATE. DATE'. 72-008 (Rev. 4/85) PERFORMED FOR: Municipality of Anchorage DEPARTMENT OF HEALTH & HUMAN SERVICES 825 "L" Street, Anchorage, Alaska 99502-0650 SOILS LOG -- PERCOLATION TEST "['F-%T- fhT ~o, '7_ DATE PERFORF LEGAL DESCRIPTION: Township, Range, Section: 1 2 3 4 5 6 7 8~ SLOPE SITE PLAN 10 11 12 13- 14- 15- 16- 17- 18- 19- 20- WAS GROUND WATER ENCOUNTERED? T~O IF YES. AT WHAT DEPTH? ~ E Oeplh lo Waler After Mor~ilorieg? ~OJ~ Oate: Gross Net Depth to Net Reading Date Time Time Water Drop PERCOLATION RATE TEST RUN BETWEEN -- '~ · ~ (minutes/inch) PERC HOLE DIAMETER ~ FT AND q FT COMMENTS PERFORMED BY: ~' /~ ' ~ · C ~.~ ~,YL~ I ~ CERTIFY THAT THIS TEST WAS PERFORMED IN ACCORDANCE WITH ALL STATE AND MUNICIPAL GUIDELINES l, EFFECT O~ T~fDATE. DATE: f~_C~ _~.~_~ 72-o08 (Rev. 4/85) MUNICIPALITY OF ANCHORAGE DEPARTMENT OF HEALTH & HUMAN SERVICES Division of Environmental Services On-Site Services Section P.O. Box 196650 Anchorage, Alaska 99519-6650 343-4744 CERTIFICATE OF HEALTH AUTHORITY APPROVAL FOR A SINGLE FAMILY DWELLING Parcel I.D. # C_~ ( ~ /'$~30 HAA# 1. GENERAL INFORMATION Complete legal description Location (site address or directions) ~/ ,'~'/~ 7~/~ /'-~/~z~d -- C ;-/- ~- Property owner Mailing address Lending agency Mailing address Agent Address ~'~c~1¢¢~'s' Day phone Day phone Day phone Unless otherwise requested, HAA will be held for pickup. NUMBER OF BEDROOMS: TYPE OF WATER SUPPLY: Individual well Community well Public water NOTE: X If community well system, provide written confirmation from State ADEC attest- ing to the legality and status of system. TYPE OF WASTEWATER DISPOSAL: Individual on-site Holding tank Community on-site Public sewer NOTE: If community wastewater system, provide written confirmation from State ADEC attesting to the legality and status of system, 72-025 (Rev. 1/91) Front MOA#21 STATEMENT OF INSPECTION BY ENGINEER As certified by my seal affixed hereto and as of the validation date shown below, 1 verify that my investigation of this Health Authority Approval application shows that the on-site water supply and/or wastewater disposal system is safe, functional and adequate for the number of bedrooms and type of structure indicated herein. I further verify that based on the information obtained from the Municipality of Anchorage files and from my investigation and inspection, the on-site water supply and/or wastewater disposal system is in compliance with all Municipal and State codes, ordinances, and regulations in effect on the date of this inspection. Name of Firm ~0~% Address, ,~ ,-¢© "'~%~¢r,'~c~/3 Engineer s signature ~,,V~/~ .~- Phone Date DHHS SIGNATURE Approved for Disapproved. Conditional approval for bedrooms. bedrooms, with the following stipulations: Additional Comments Date ~/Z_,,~(.~ / The Municipality of Anchorage Department of Health and Human Services (DHHS) issues Health Authority Approval Certificates based only upon the representations given in paragraph 5 above by an independent professional engineer registered in the State of Alaska. The DHHS does this as a courtesy to purchasers of homes and their lending institutions in order to satisfy certain federal and state requirements. Employees of DHHS do not conduct inspections or analyze data before a certificate is issued. The Municipality of Anchorage is not responsible for errors or omissions in the professional engineer's work. 72*025 (Rev. 1/91) Back MOA ~t'Zl Municipality of Anchorage Department of Health and Human Services HEALTH AUTHORITY APPROVAL CHECKLIST Legal Description: A. Well Data Well type GtT~/ Log present (Y/N) Total depth Sanitary seal (Y/N) Parcel I,D. If A, B, or C, attach ADEC letter. ADEC water system number ~ Date completed -- Driller Casedto -- Casing height Wires properly protected (Y/N) -- .J FROM WELL LOG AT INSPECTION Static water level Well flow '~ g.p.m. Pump level1 SEPARATION DISTANCES FROM WELL TO: Septic/holding tank on lot ~ / A Absorption field on lot N//~ l~, Public sewer main Sewer service line ; On adjacent lots ; On adjacent lots Public sewer manhole/cleanout Petroleum tank g.p.m. (-3 l-il WATER SAMPLE RESULTS: Coliform ......... Nitrate Other bacteria Date of sample: Collected by: '--'"-- B. SEPTIC/HOLDING,. TANK D~TA Date installed .~.~/~// ~c~~ Cleanouts (Y/N) ~ High water alarm (Y/N) /V Date of pumping /i~¢= ' Tank size Foundation cleanout (Y/N) c~ c.- Compartments y' Depression (Y/N) Alarm tested (Y/N) Pumper ,u/~/'~, SEPARATION DISTANCES FROM SEPTiC/HOLDING TANK TO: Well(s) on lot /V/'A To property line Sudace water/drainage /'J//'~ On adjacent lots Absorption field Foundation /'-/'/ Water main/service line 80/7~ 72.026 (3~3)O Front CONTINUED ON BACK PAGE C. LIFT STATION Date installed ~ Size in gallons Vent (Y/N) _';~ump on" level at High water alarm level ~ Meets MOA electrical codes (Y/N) '~ SEPARATION DISTANCE FROM LIF'r~TATION TO: Well on lot On'~djacent lots Manufacturer Manhole/Access (Y/N) "Pump off" Level at Cycles tested D. ABSORPTION FIELD DATA Surface water Date installed /4- ¢5 - Length ~' '7 Width Total absorption area Date of adequacy test Water level in absorption field before test Peroxide treatment (past 12 months) (Y/N) Soil rating (GPD/Ft2) /-~ System type O Gravel thickness Total depth Cleanout present (Y/N) ¥/ Depression over field (Y/N) boeco s¥$-/-. Results(pass/fail) fl" /o~.oc, 5,./3'/. for ,,~ If yes, give date Bedrooms SEPARATION DISTANCE FROM ABSORPTION FIELD TO: Well o. lot To building foundation On adjacent lots Sudace water ~o ~--~ On adjacent lots /V'//,4 Property line To existing or abandoned system on lot rJ//¥ Cutbank /~/o,~ -E' Water main/service line /oo ' '(- / Driveway, parking/vehicle storage area Curtain drain E. ENGINEER'S CERTIFICATION I certify that I have checked, verified, or conformed to all MOA and HAA S~gnatu re~'~-c.- E'ngineer's Name Date of this inspection. HAA Fee $ Date of Payment O--,/'~7/~/Z Waiver Fee $ Date of Payment Receipt Number